DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of...

106
DIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120 CCSU PROJECT #23-113 OCTOBER 6TH, 2014;Page 1 of 4 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The Drawings and the general provisions of the Contract Documents, including the General Conditions and Division 1 Specification Sections, apply to the work of this section. B. Related work specified elsewhere includes, but shall not be limited to, the following: 1. Section 07270 – Firestopping 1.02 DESCRIPTION OF WORK A. The extent of Unit Masonry Work is shown on the Drawings consisting of, but not limited to, the following: 1. Concrete masonry units (CMU) 2. Mortar and Grout 3. Masonry Accessories 1.03 QUALITY ASSURANCE A. Unit Masonry Standard: Perform work in accordance with ACI 530.1/ASCE 6, “Specifications for Masonry Structures”, except as otherwise noted. B. Obtain mortar ingredients of uniform quality, including color for exposed masonry, from one manufacturer for each cementitious component and from one source and producer for each aggregate. 1.04 REFERENCES A. All work of this section shall be constructed in accordance with the latest edition of the following standards, which are a part of this specification as if bound herein: 1. ASTM A153 Class B2, Zinc coating (Hot-Dip) on Iron and Steel Hardware. 2. ASTM C90, Hollow Load Bearing Concrete Masonry Units. 3. ANSI A41.1, Building Code Requirements for Masonry. 4. American Concrete Institute Publications ACI 530.1-88/asce 6-88 and ACI 530-88/ASCE 5-88. 1.05 SUBMITTALS A. General: Submit the following in accordance with the provisions of Section 01300 of the General Requirements. 1. Product Data: for each masonry unit, accessory, and other manufactured product specified. 2. Certification: for CMUs certifying that the fire rating, or equivalent fire rating, of any concrete masonry unit incorporated in a fire rated assembly, exceeds one hour. Submit

Transcript of DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of...

Page 1: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 4 UNIT MASONRY SECTION 04200

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014;Page 1 of 4

PART 1 - GENERAL 1.01 RELATED DOCUMENTS

A. The Drawings and the general provisions of the Contract Documents, including the General Conditions and Division 1 Specification Sections, apply to the work of this section.

B. Related work specified elsewhere includes, but shall not be limited to, the following:

1. Section 07270 – Firestopping

1.02 DESCRIPTION OF WORK

A. The extent of Unit Masonry Work is shown on the Drawings consisting of, but not limited to, the following:

1. Concrete masonry units (CMU) 2. Mortar and Grout 3. Masonry Accessories

1.03 QUALITY ASSURANCE

A. Unit Masonry Standard: Perform work in accordance with ACI 530.1/ASCE 6, “Specifications for Masonry Structures”, except as otherwise noted.

B. Obtain mortar ingredients of uniform quality, including color for exposed masonry, from one

manufacturer for each cementitious component and from one source and producer for each aggregate.

1.04 REFERENCES

A. All work of this section shall be constructed in accordance with the latest edition of the following standards, which are a part of this specification as if bound herein:

1. ASTM A153 Class B2, Zinc coating (Hot-Dip) on Iron and Steel Hardware. 2. ASTM C90, Hollow Load Bearing Concrete Masonry Units. 3. ANSI A41.1, Building Code Requirements for Masonry. 4. American Concrete Institute Publications ACI 530.1-88/asce 6-88 and ACI 530-88/ASCE

5-88. 1.05 SUBMITTALS

A. General: Submit the following in accordance with the provisions of Section 01300 of the General Requirements.

1. Product Data: for each masonry unit, accessory, and other manufactured product

specified. 2. Certification: for CMUs certifying that the fire rating, or equivalent fire rating, of any

concrete masonry unit incorporated in a fire rated assembly, exceeds one hour. Submit

Page 2: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 4 UNIT MASONRY SECTION 04200

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014;Page 2 of 4

calculations in accordance with Article 2.01,A,1,a,1,a. when providing units of equivalent thickness to laboratory tested, fire rated units.

1.06 DELIVERY, STORAGE AND HANDLING

A. Deliver masonry materials to the Project Site in an undamaged condition.

B. Store cementitious materials off the ground, under cover, and in dry location. C. Store aggregates where grading and other required characteristics can be maintained and

contamination avoided. D. Store masonry accessories, including metal items, to prevent corrosion and accumulation of dirt and

oil. E. Inspect all materials. Remove from the Project Site any damaged, or frozen, materials and replace

with new materials. 1.07 PROJECT CONDITIONS

A. Prevent grout, mortar, and soil from staining the face of masonry. Immediately remove any grout, mortar, and soil that comes in contact with masonry.

PART 2 - PRODUCTS 2.01 MATERIALS

A. CONCRETE MASONRY UNITS (CMU):

1. General: Obtain masonry units from one manufacturer, of uniform texture and color for each type of unit required.

a. Hollow Units: shall conform to ASTM C90, Grade N, Type 1 - Moisture

controlled, normal weight. Hollow load bearing units shall have a min. average net area compressive strength of 1800 psi.

1. Provide concrete masonry units (CMU) of required thickness with a fire resistance rating, or an equivalent fire resistance rating, of not less than 1 hour a. Fire rated concrete masonry units shall be tested and certified by the

Underwriters Laboratory Inc., or another testing laboratory acceptable to the Agency. The equivalent fire rating of concrete masonry units may be determined in accordance with the “BOCA Guidelines for Determining Fire Resistance Rating of Building Elements”, as specified in the “National Concrete Masonry Association, Technical Manual, (NCMA-TEK), 7-3”: performed in accordance with “Standard Methods of Sampling and Testing Concrete Masonry Units”, ASTM-C140.

2. Concrete Masonry Units: Shall be smooth faced, nominal 8" high x 16" long x thickness

to match existing CMU wall. Stock bond coursing to match existing.

Page 3: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 4 UNIT MASONRY SECTION 04200

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014;Page 3 of 4

B. MORTAR AND GROUT:

1. Portland Cement: shall comply with ASTM C150.

2. Hydrated Lime: shall comply with ASTM C207, Type S. 3. Aggregate for mortar: shall comply with ASTM C144. Natural, light tan, sharp, clean

sand.

4. Water: Clean , potable, and free of deleterious amounts of acids, alkalies, and organic materials.

5. Mortar materials and mix proportions shall meet the applicable requirements of ASTM C

476; Type S made with lime. Minimum 28-day strength of grout for reinforcing walls shall be 2500 psi.

C. MASONRY ACCESSORIES:

1. Horizontal joint reinforcing: shall be fabricated from cold-drawn steel wire conforming

to ASTM A82, with smooth, 9 gauge cross rods butt welded not more than 16” o.c. vertically to deformed 9 gauge side rods. Provide units pre-fabricated in straight lengths of not less than ten (10) feet. Finish shall conform to ASTM A153, Class B2, (1.5 oz. zinc coating per sq. ft.). Joint reinforcing shall be the following:

a. Walls: reinforcing shall be #120 Truss-Mesh by Hohmann & Barnard, Inc. or

approved equal (width per existing condition).

PART 3 - EXECUTION 3.01 INSPECTION

A. The Installer shall inspect the existing conditions. He shall immediately notify the Contractor, in writing, with a copy to the Architect, and the Construction Coordinator of any condition detrimental to the timely execution of his work as specified herein. Failure to due so shall constitute acceptance of the substrata, the prevailing conditions and the risks inherent therein.

3.02 PREPARATION

A. Ensure items built in by other trades for this Work are properly located and sized. B. Establish lines, levels and coursing. Protect from disturbances.

3.03 INSTALLATION - GENERAL

A. Comply with referenced unit masonry standard and other requirements indicated applicable to each type of installation included in the Project.

B. Do not shift or tap masonry after mortar has taken initial set. Where adjustment must be made,

remove mortar and replace. C. Ensure masonry courses are of uniform height. Make vertical and horizontal joints equal and of

uniform thickness. Lay in full bed of mortar, properly jointed with other Work.

Page 4: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 4 UNIT MASONRY SECTION 04200

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014;Page 4 of 4

3.04 TOLERANCES

A. Maximum Variation From Unit to Adjacent Unit: 1/16 inch. B. Maximum Variation From Plane of Wall: 1/4 inch in 10 feet and 1/2 inch in 20 feet or more. C. Maximum Variation From Plumb: 1/4 inch.

3.05 LAYING MASONRY WALLS

A. Lay up walls to comply with specified construction tolerances, coordinated with other construction.

B. Built-In Work: As construction progresses, build-in items specified under this and other sections of the specifications. Fill in solidly with masonry around built-in items.

1. Fill cores in hollow concrete masonry units with grout three courses (24 inches) under bearing

plates, beams, lintels, posts, and similar items, unless otherwise indicated.

3.06 MORTAR BEDDING AND JOINTING

A. Lay hollow concrete masonry units with full mortar coverage on horizontal and vertical face shells.

B. Cut joints flush for masonry walls to be concealed or to be covered by other materials. 3.07 HORIZONTAL JOINT REINFORCING

A. General: Provide continuous horizontal joint reinforcing where specified. Install longitudinal side rods in mortar for their entire length with a minimum cover of 5/8 inch on sides of walls,

3.08 LINTELS

A. N/A. 3.09 REPAIRING, RE-POINTING, AND CLEANING

A. N/A

3.10 PROTECTION A. Provide final protection and maintain conditions, in a manner acceptable to the installer that will

ensure unit masonry is without damage and deterioration at the Date of Substantial Completion.

+ + END OF SECTION + +

Page 5: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 7 FIRESTOPPING SECTION 07270

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 3

PART 1 - GENERAL 1.01 RELATED DOCUMENTS

A. The Drawings and the general provisions of the Contract Documents, including the General Conditions and Division 1 Specification Sections, apply to the work of this section.

1.02 DESCRIPTION OF WORK

A. The extent of Firestopping Work is specified herein consisting of, but not limited to, the following:

1. Penetrations through fire-rated floor construction. 2. Penetrations through fire-rated walls and partitions. 3. Sealant joints in fire-and smoke rated constructions.

1.03 QUALITY ASSURANCE

A. Work shall be performed by a firm with expertise in the installation of firestopping systems. This firm shall be licensed, or otherwise approved, by the firestopping material manufacturer. Work shall be in accordance with the manufactures written installation specifications.'

B. Obtain firestop system materials for each type of penetration specified from a single manufacturer. C. Coordinate the construction of openings and the installation of penetrating items to ensure that

firestop systems are installed in accordance with the specified system requirements. 1.04 SUBMITTALS

A. General: Submit the following in accordance with the applicable provisions of the General Requirements.

1. Product data: for each type of product specified.

2. Shop drawings: detailing materials, systems and installation methods, for each firestop

system. Include firestop design designation of the testing laboratory.

3. Product certificates: signed by manufacturers of firestopping products, certifying that their products comply with the specified requirements.

1.05 SYSTEM PERFORMANCE REQUIREMENTS

A. General: Provide firestopping systems that are designed and installed to resist the spread of fire,

and the passage of smoke and other gases. B. Fire-Rated Through-Penetration Firestop Systems: Provide systems with one hour ratings,

determined in accordance with ASTM E 814, Fire Tests of Through- Penetration Fire Stops.

C. Fire-Resistive Joint Sealants: Provide joint sealants with one-hour fire-resistance ratings, in accordance with ASTM E 119.

Page 6: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 7 FIRESTOPPING SECTION 07270

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 3

1.06 PROJECT CONDITIONS

A. Do not install firestopping materials when ambient temperatures are outside limits permitted by firestopping manufacturers recommendations, or when substrates are wet due to rain, frost, condensation, or other causes.

PART 2 - PRODUCTS 2.01 MATERIALS

A. General: Use only components specified by the firestopping system manufacturer for the

designated systems. Materials shall include, but are not limited to the following.

1. Intumescent putty shall be USG. Firecode Compound. 2. Fire safing insulation shall be USG Thermafiber Firespan,.

B. The materials specified above are manufactured by United States Gypsum, (USG) 125 South

Franklin Street P.O. Box 806278, Chicago, IL 60680-4124. C. Intumescent, Latex Sealant: Single-component, intumescent, latex formulation. Provide product

equal to:

1. Metacaulk 950, The Rector Seal Corporation 2. Fire Barrier CP 25WB, 3M Fire Protection Products

PART 3 - EXECUTION 3.01 INSPECTION

A. The installer shall inspect the substrata and the conditions prevailing at the time of installation. He shall immediately notify the Contractor in writing, with a copy to the Architect, of any condition detrimental to the timely execution of his work as specified herein. Failure to due so shall constitute acceptance of the substrata, the prevailing conditions and the risks inherent therein.

3.02 PREPARATION

A. Remove all foreign materials from surfaces of opening, joint substrates and from penetrating items that may be detrimental to the adhesion of the intumescent putty and sealant.

B. Install masking tape to prevent from soiling adjoining surfaces that will remain exposed upon the

completion of the Work. Remove tape as soon as the intumegcent putty has been placed. 3.03 INSTALLATION

A. General: The firestop systems specified below are proprietary. Construct the systems in accordance with the testing agencies written instructions.

Page 7: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 7 FIRESTOPPING SECTION 07270

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 3

B. Fire Stop Systems: Penetrating Type of Firestopping Min Max Item Wall or Material Forming Annular Annular Fire UL System (Diameter) Floor (Min. Depth) Material Space Space Rating Number

Steel Pipe, Up to 14” CW 1” 3”, 3.5pcf 0” 1 15/16” 2 CAJ-1081 CF 1” 3”, 3.5pcf 0” 1 15/16” 2 CAJ-1081 Steel Pipe Up to 10” CW 1” 3”, 3.5pcf ¼” 2 ¼” 3 CAJ-1081 CF 1” 3”, 3.5pcf ¼” 2 ¼” 3 CAJ-1081 Steel Pipe, Tubing, or Conduit CW 1” 3”, 3.5pcf ¼” 3 ¼” 3 CAJ-1081 Up to 4” CF 1” 3”, 3.5pcf ¼” 3 ¼” 3 CAJ-1081 Steel or Iron Pipe, Up to 4” GW ½” 2 ½”,3.5pcf ¼” 1 ¼” 1 WL-1039 Insulated Steel Pipe, Up to 4” GW ¼” 2”, 3.5pcf(1) ½” ½” 2 WL-5043 Steel Pipe Up to 3 ½ “ GW 1” 1”, 3.5pcf(1) ½” 5/8” 2 WL-5044 Steel Pipe, Tubing, or Conduit GW 1” 3”, 305pcf ¼” 2 ¼” 1 WL-1039 Up to 4” Tubing or Steel Conduit, Up to 4” GW ½” 2 ½”,3.5pcf ¼” 1 ¼” 1 WL-1039 Steel Pipe, Conduit or Tubing GW 1” 0 ½” 2 WL-1063 Up to 3 ½” Multiple Steel Pipe, Conduit, GW 1 3”, 3.5PCF 3/8” 1 ¼” 2 WL-1065 Or Tubing Up to 1” Copper Pipe, Up to 6” CW 1” 3”, 3.5pcf 0 1 13/16” 2 CAJ-1081 CF 1” 3”, 3.5pcf 0 1 13/16/” 2 CAJ-1081 Copper Pipe Up to 6” GW 1” 3’, 3.5pcf 1” 1 5/8” 2 WL-1027 Copper Pipe Up to 4” GW ½” 2 ½”,3.5pcf 3/8” 1 ¼” 2 WL-1039 Copper Pipe or Tubing Up to 4” GW 1” 1”, 3.5pcf(1) ½” 5/8” 2 WL-5044 Copper Tubing Up to 4” GW 1” 0 ½” 2 WL-1063 Insulated Copper Tubing Up to 4” GW ¼” 2”,3.5pcf(1) ½” ½” 2 WL-5043 Copper Tubing Up to ¾” ½” 2 ½”,3.5pcf ¼” 1 13/16” 1 WL-1039 PVC Pipe Up to 4” GW ½” 2 ½”,3.5pcf 5/16” 1 1/16 1 WL-2036 Air Duct 28-ga. Galv. Sheet Metal GW 1” 3”,3.5pcf ½” 1” 2 WL-7002 4” x 6” Air Duct 24-ga. Sheet Metal 3” x 10” GW ½” 2 ½”,3.5pcf 7/16 1” 1 WL-7001 Cables CW 1” 3”,3.5pcf ¼” 3 ½” 3 CAJ-3045 CF 1” 3”,3.5pcf ¼” 3 ½” 3 CAJ-3045 Cables GW ½” 2 ½”,3.5pcf ½” 3 7/8 1 WL_3034

(CF-Concrete Floor, CW-Concrete Wall, GW- Gypsum Wall) (1) Pipe covering material 3.04 CLEANING

A. Clean off excess fill materials and sealants adjacent to openings and joints as work progresses by methods and with cleaning materials approved by the Manufacturers of firestopping products and of products in which opening and joints occur. Clean areas of all debris and left over materials.

B. Protect firestopping during and after curing period from contact with contaminating substances or

from damage resulting from construction operations or other causes so that they are without deterioration or damage at time of Substantial Completion. If, despite such protection, damage or deterioration occurs, cut out and remove damaged or deteriorated firestopping immediately and install new materials to produce firestopping complying with specified requirements.

+ + END OF SECTION + +

Page 8: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 7 SEALANTS

SECTION 07900

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 3

PART 1 - GENERAL 1.01 RELATED DOCUMENTS

A. The Drawings and the general provisions of the Contract Documents, including the General Conditions and Division 1 Specification Sections, apply to the work of this section.

B. Related work specified elsewhere includes, but shall not be limited to the following.

1. Section 07270, Firestopping systems sealant

1.02 DESCRIPTION OF WORK

A. The extent of Sealant Work is shown on the Drawings consisting of, but not limited to, the following:

1. Sealant for control joints (if any). 2. Sealant for plumbing fixtures. 3. Acoustical sealant.

1.03 QUALITY ASSURANCE

A. Installer Qualifications: Engage an installer with not less than three years experience, who has completed sealant applications similar in material, design, and extent to that specified for the Project.

B. Single Source Responsibility: Obtain sealant materials from a single manufacturer for each

different product required. C. Approved Manufacturers:

1. Pecora Corp. 5. General Electric 2. Tremco 6. Illbruck 3. Dow Corning Corp. 7. Emseal Corp. 4. DAP

1.04 SUBMITTALS

A. General: Submit the following in accordance with the applicable provisions of Section 01300 of the General Requirements:

1. Product data from manufacturers for each joint sealant product required.

1.05 DELIVERY, STORAGE, AND HANDLING

A. Deliver materials to Project Site in original unopened containers, or bundles, with labels specifying

the manufacturer, product name and designation, color, expiration date, pot life, curing time, and mixing instructions for multi-component materials.

B. Store and handle materials in compliance with manufacturer's recommendations to prevent their

deterioration due to moisture, high or low temperatures, contaminants, or other causes.

Page 9: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 7 SEALANTS

SECTION 07900

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 3

1.06 PROJECT CONDITIONS A. Do not proceed with the installation of sealant when the ambient air temperature is outside the limits

permitted by the sealant manufacturer, or when the joint substrates are wet. B. Do not proceed with the installation of sealants until contaminants capable of interfering with their

adhesion are removed from the joint substrate. 1.08 WARRANTY/GUARANTEE

A. Provide manufacturer’s standard five-year warranty/guarantee, signed by the Contractor and the Installer. It shall cover the Work specified herein against defects in workmanship and materials.

PART 2 - PRODUCTS 2.01 GENERAL

A. Provide sealants, joint fillers, and miscellaneous materials that are compatible with one another and

with the joint substrates. Provide sealants that have been produced and installed as required to maintain watertight seals; without causing staining, or deterioration, of joint substrates.

B. The Agency shall select colors from the manufacturer's full range of standard colors for the products

specified.

2.02 SEALANTS

A. Interior Sealant: Equal to #864 Silicone one-part, Type II (non-sag) silicone sealant by Pecora Corp.

B. Plumbing Fixture Sealant: Mildew resistant, silicone rubber sealant conforming to F.S. TT-S-

001543, Class A. 2.03 MISCELLANEOUS MATERIALS

A. Joint Fillers: Pre-formed, compressible, closed-cell, polyethylene foam extrusions of size, shape,

and density required to form the proper sealant profile.

B. Bond-Breaker Tape: Self adhering, polyethylene tape recommended by the sealant manufacturer to prevent sealant from adhering to joint filler materials, or to joint surfaces where such adhesion detrimental to the sealant bond.

C. Primer: Material recommended by the joint sealant manufacturer for adhesion of sealant to the

joint substrates. D. Cleaners: Chemical cleaners recommended by the joint sealant manufacturer. They shall be free

of oily residues, and formulated to provide optimum adhesion of the sealant with the joint substrate.

Page 10: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 7 SEALANTS

SECTION 07900

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 3

PART 3 - EXECUTION 3.01 INSPECTION

A. The Installer shall inspect the substrata and the conditions prevailing at the time of installation. He

shall immediately notify the Contractor, in writing, with a copy to the Architect, and the Construction Administrator of any condition detrimental to the timely execution of his work as specified herein. Failure to due so shall constitute acceptance of the substrata, the prevailing conditions and the risks inherent therein.

3.02 PREPARATION

A. Remove all foreign material from joint substrates that is detrimental to the adhesion of sealants. Clean concrete, masonry, and similar porous joint substrate surfaces by wire brushing, Remove loose particles remaining by vacuuming, or blowing out, joints with oil-free compressed air. Clean metal, glass, and other nonporous surfaces with chemical cleaners.

B. Prime joint substrates as recommended by the sealant manufacturer. Apply primer in accordance

with the sealant manufacturer's recommendations. Confine primers to areas of sealant bond; do not allow migration onto adjoining surfaces.

3.03 INSTALLATION

A. Comply with sealant manufacturer's printed installation instructions, and ASTM V 1193. B. Install bond breaker tape, where backer rods are not used, between the sealant and the back of the

joint. C. Install sealant directly in contact with and fully wetting the joint substrate. Completely fill the joint

recess. Install sealant immediately after the backer rods, or bond breakers, have been installed. D. Immediately after sealant application, tool the sealant surface as required to form a smooth uniform

surface, to eliminate air pockets, and to ensure contact and adhesion of the sealant with the sides of the joint. Remove excess sealants from surfaces adjacent to the joint.

3.04 CLEANING

A. Clean excess sealant material from surfaces adjacent to joints by methods and with cleaning

materials approved by the manufacturers of sealant materials. 3.05 PROTECTION

A. Protect sealant installations from construction operations, so that they are without deterioration, or

damage at the time of Substantial Completion. If, damage or deterioration occurs, remove the sealant immediately and reconstruct the joint.

+ + END OF SECTION + +

Page 11: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 9 ACOUSTICAL CEILINGS

SECTION 09510

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 4

PART 1 - GENERAL 1.01 RELATED DOCUMENTS

A. The Drawings and the general provisions of the Contract Documents, including the General Conditions and Division 1 Specification Sections, apply to the work of this section.

1.02 DESCRIPTION OF WORK

A. The extent of Acoustical Ceiling Work is shown on the Drawings consisting of, but not limited to, the following:

1. Acoustical Ceiling Panels. 2. Metal Ceiling Suspension System.

1.03 QUALITY ASSURANCE

A. Qualifications of Installer: Engage an experienced installer who has successfully completed acoustical ceilings similar in material, design and extent to those of the Project.

B. Single Source Responsibility: Obtain each type of ceiling panel and each type of suspension

system from a single source who has resources to provide products of consistent quality in appearance and physical properties, without delaying the progress of the work.

C. Tolerances:

1. Deflection: Suspension system components, hangers, and fastening devices supporting light fixtures, ceiling grilles, and acoustical panels shall have a maximum deflection 1/360 of the span. When tested in accordance with ASTM C635-76

2. Surface tolerance in plane: shall be 1/8 inch in 12 feet, non-accumulative.

D. Fire Hazard Classification: Class A, with flame spread of 25, or less, and smoke developed rating

of 50, or less when tested in accordance with ASTM E 84.

E. Coordination of Work: Coordinate layout and installation of acoustical ceiling work with other construction that penetrates ceilings, or is supported by them, including light fixtures, HVAC equipment, fire-suppression system components, and partition system.

1.04 SUBMITTALS

A. Samples:

1. Submit one 12" x 12" sample of acoustical panel to illustrate color and range of appearance and edge conditions.

Page 12: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 9 ACOUSTICAL CEILINGS

SECTION 09510

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 4

2. Submit one full size sample of each suspension system member, moldings and hangers. B. Manufacturer's Literature: Submit the manufacturer's recommendation for the installation of

suspension system. C. Certificates: Submit certification of the fire hazard classification specified.

1.05 PRODUCT DELIVERY, STORAGE AND HANDLING

A. Deliver materials in original, unopened, packaging, with manufacturer's labels indicating brand

name, pattern, size, thickness and fire rating, legible and intact. B. Store materials in the original packaging to prevent soiling, physical damage or wetting. Cartons

should be removed from pallets or stringers to prevent distortion of material. Store cartons open at each end to stabilize moisture content and temperature.

C. Handle acoustical panels carefully to avoid chipping edges or damaging in any way.

1.06 ENVIRONMENTAL REQUIREMENTS

A. Do not install interior acoustical ceilings until space has been enclosed and is weather-tight; and until wet-work in the space has been completed and is nominally dry; and until work above ceilings has been completed.

B. Maintain a uniform temperature of 60 to 85 degrees F. in the area where acoustical panels are to

be installed for 24 hours before, during and after the installation. PART 2 - PRODUCTS 2.01 MATERIALS

A. Acoustical Panels: Armstrong Dune Tegular fine texture, Item 1775, square lay-in, 24”x24”x5/8” panel white or equal.

B. Ceiling Suspension System (at toilet rooms): shall be a 9/16” face, non-rated, exposed tee grid,

intermediate duty system for 24” x 24” panels, Armstrong Suprafine System or equal, complying with ASTM C 635 or C 636, as applicable. Color: shall be white, in standard factory baked enamel finish on exposed surfaces. Provide the manufacturer’s standard exposed runners, cross-runners, retention clips and accessories, of the types and profiles indicated, with exposed cross-runners coped to lay flush with main runners.

1. Seismic restraint: Comply with the provisions of ASTM E580. Provide splayed wire

hangers, and or bracing, designed to resist the lateral forces applied to the ceiling suspension system, determined in accordance with Article 1113.10 of the State Building Code.

Page 13: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 9 ACOUSTICAL CEILINGS

SECTION 09510

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 4

2. Wire for hangers and ties: shall be not less than 12ga., galvanized carbon steel, in accordance with ASTM A-641, Class 1, zinc coating, soft temper, pre-stretched. Provide wire sized five times the design load indicated in ASTM C 635, Table 1, direct hung.

3. Edge moldings: shall be the manufacturer’s standard angle molding with a baked enamel finish,

matching the color of the exposed suspension system. PART 3 - EXECUTION 3.01 CONDITION OF SURFACES

A. Examine areas scheduled to receive suspended acoustical units for unevenness, irregularities, and dampness that would affect quality and execution of work.

B. Install suspension systems in accordance the lighting layouts detailed on the plans. If plan is not

available, measure each ceiling area and establish layout of acoustical units to balance border widths at opposite edges of each ceiling. Avoid use of less-than-4” width units at borders.

3.02 INSTALLATION

A. General: Install materials in accordance with the manufacturer’s printed instructions, in accordance with governing regulations, and fire resistance rating requirements as specified.

B. Install suspension systems in accordance with ASTM C 636, with hangers supported from the

underside of the existing concrete structure with the main runners supported at each end and 4’-0” oc., unless otherwise indicated,

C. Secure wire hangers by looping and wire-tying to powder activated fasteners, or other fasteners,

which are, secure and appropriate for substrate. D. Install hangers plumb and free from contact with objects within ceiling plenum. Splay hangers only

where required to miss obstructions. Offset resulting horizontal force by bracing, countersplaying or other equally effective means.

E. Install edge moldings at the perimeter of the acoustical ceiling area and at locations where

necessary to conceal edges of acoustical units. F. Apply continuous ribbon of acoustical sealant, concealed on back of vertical leg before installing

moldings. Screw-attach molding to substrate at intervals not over 16” o.c. and not more than 3” from ends, level with ceiling suspension system to tolerance of 1/8” in 12’-0”. Miter corners accurately and connect securely.

G. Install acoustical panels with edges concealed by suspension members. Scribe and cut panels to fit

accurately at borders and at penetration

3.03 CLEANING

Page 14: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 9 ACOUSTICAL CEILINGS

SECTION 09510

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 4

A. Clean exposed surfaces of acoustical ceilings, including trim, edge moldings, and suspension

members; comply with manufacturer's instructions for cleaning and touch-up of minor finish damage. Remove and replace work that cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.

B. Protect acoustical ceilings, and provide proper temperature and humidity limitations and dust

control, so that the work will be without damage and deterioration at the Date of Substantial Completion.

+ + END OF SECTION + +

Page 15: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 9 PAINTING

SECTION 09900

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 5

PART 1 - GENERAL 1.01 RELATED DOCUMENTS

A. The Drawings and the general provisions of the Contract Documents, including the General Conditions and Division 1 Specification Sections, apply to the Work of this Section.

1.02 DESCRIPTION OF WORK

A. The extent of Painting Work is shown on the Drawings and specified herein. "Paint" shall mean all finish coating systems and materials, including primers, emulsions, enamels, special coatings, sealers, fillers, and other applied materials, whether used as prime, intermediate, or finish coats. Paint all exposed surfaces, except where the natural finish of the material is obviously intended, or specifically noted, as a surface not to be painted. Painting Work shall include, but shall not be limited to, the following:

1. Hollow Metal Frames 2. Exposed Conduits, Piping. 3. Concrete Masonry Unit Walls.

1.03 WORK NOT INCLUDED

A. General: The following categories of substrata, or items, shall not receive a paint finish. They are considered to be surfaces that are not intended to be painted:

1. Metal Surfaces: Do not paint any anodized aluminum, stainless steel, chromium plate,

copper, or bronze. 2. Operating Parts and Labels: Do not paint any moving parts of operating units. Do not

paint over any code required labels, such as Underwriters' Laboratories and Factory Mutual labels, or any equipment identification, performance rating, name or nomenclature plates.

3. Shop Priming: Do not apply the specified prime coat to any pre-primed substrate.

4. Do not paint pre-finished items, concealed surfaces, finished metal surfaces, operating

parts and labels. 1.04 QUALITY ASSURANCE

A. Product Manufacturer: Company specializing in manufacturing quality paint and finish products

with a minimum three years experience. B. Applicator: Company specializing in commercial painting and finishing with a minimum of three

years of experience. C. Paint Coordination: Provide finish coats which are compatible with prime paints used and

produced by the same manufacturer as the prime coat. Review other sections of these Specifications in which prime paints are to be provided to ensure the compatibility of each coating system with its substrate. Provide barrier coats over all incompatible primers or remove and re-prime as required. Notify the Agency, in writing, of any anticipated problems in applying the specified coating systems.

Page 16: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 9 PAINTING

SECTION 09900

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 5

1.05 REFERENCES

A. All Work of this Section shall be provided in accordance with the latest edition of the following

standards which are considered to be a part of this specification the same as if bound herein:

1. ANSI/ASTM D16: Definitions of Terms Relating to Paint, Varnish, Lacquer, and Related Products.

1.06 SUBMITTALS

A. General: Submit the following in accordance with the applicable provisions of Section 01300 of the

General Requirements:

1. Product data for each material specified. 2. Manufacturer's application instructions for each material specified.

1.07 REGULATORY REQUIREMENTS

A. Conform to the applicable codes for flame, fuel, and smoke rating requirements for finishes. B. All paint and finishes shall conform to ANSI A66.1 - 1964, "Specifications to Minimize Hazards to

Children from Residual Coating Materials". 1.08 DELIVERY, STORAGE, AND HANDLING

A. Deliver products to the Site in sealed and labeled containers. B. Container labeling shall include manufacturer's name, type of paint, brand name, brand code,

coverage, surface preparation, drying time, clean up, color designation, and instructions for mixing and reducing.

C. Store paint materials at a temperature between 45 degrees F. and 90 degrees F., in a well

ventilated area.

D. Take all precautionary measures required to prevent fire hazards and spontaneous combustion.

1.09 ENVIRONMENTAL REQUIREMENTS

A. Provide continuous ventilation in, and heat, area to be painted as required to maintain ambient temperature above 45 degrees F. for 24 hours before, during, and 48 hours after the application of finishes.

B. Provide minimum lighting level of 80-ft. candles measured mid-height at the substrate surface. C. Cover, or otherwise protect, finish work of other trades and surfaces not being painted concurrently,

or not specified to be painted.

Page 17: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 9 PAINTING

SECTION 09900

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 5

1.10 JOB CONDITIONS

A. Safety: Take all precautions required to ensure that the workmen, and work areas, are adequately protected from fire and health hazards resulting from the handling, mixing, and application of volatile finish coating systems.

PART 2 - PRODUCTS 2.01 MATERIALS

A. Coatings: shall be ready mixed, except field catalyzed coatings. Process pigments to a soft paste consistency, capable of being readily and uniformly dispersed to a homogeneous coating. Coatings shall have good flow and brushing properties, capable of drying or curing free of streaks and sags.

B. Accessory Materials: shall include linseed oil, shellac, turpentine, paint thinners and other

materials not specifically indicated, but required to achieve the finishes specified, of commercial quality.

PART 3 - EXECUTION 3.01 INSPECTION

A. The installer shall inspect the substrata and the conditions prevailing at the time of installation. He shall immediately notify the Contractor in writing, with a copy to the Agency, of any condition detrimental to the timely execution of his work as specified herein. Failure to due so shall constitute acceptance of the substrata, the prevailing conditions and the risks inherent therein.

B. Verify that surfaces are ready to receive work as instructed by the Product Manufacturer. C. Examine surfaces scheduled to be finished prior to commencement of the Work. Report any

condition that may potentially affect proper application.

D. Measure moisture content of surfaces using an electronic moisture meter. Do not apply finishes unless moisture content of surfaces is below the maximums stated by the Manufacturer.

3.02 PREPARATION

A. Remove electrical plates, hardware, light fixture trim, and fittings prior to preparing surfaces or applying any finish. Re-install the above after the Painting Work has been completed.

B. Correct minor defects and clean the surfaces that affect the Work of this Section in accordance with

the Paint Manufacturers written instructions. Schedule the cleaning and painting so that contaminants from the cleaning process will not fall onto wet, newly painted surfaces. Do not paint over dirt, scale, rust, grease, or conditions otherwise detrimental to the formation of a durable paint film.

C. Touch-up any shop-primed or galvanized steel surfaces which have been damaged. Sand and

scrape to remove loose primer and rust. Feather edges to make touch-up patches inconspicuous. Clean surfaces as directed by Manufacturer.

Page 18: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 9 PAINTING

SECTION 09900

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 5

3.03 PROTECTION

A. Protect: the work of other trades, whether it is scheduled to be painted or not, against any damage by the Work specified herein. Repair all damage as directed by Architect, at no cost to the Agency.

B. Furnish drop cloths, shields, and protective methods to prevent spray or droppings from disfiguring

other Work. C. Remove empty paint containers from the Site, and dispose of legally.

3.04 APPLICATION

A. General: Apply products in accordance with the Manufacturer’s written instructions. Do not apply

finishes to surfaces that are not dry. Apply each coat to a uniform finish. Sand lightly and vacumn and/or wipe with tack cloths between coats. Allow applied coat to dry for the time period recommended by the Manufacturer before applying the next coat.

C. Minimum Coating Thickness: Apply each paint system at not less than the Manufacturer's

recommended wet/dry film thickness, or spreading rate. D. Additional Prime Coats: Re-coat primed and sealed surfaces where there is evidence of suction

spots or unsealed areas, as required to assure a finish coat with no burn through, or other defects.

E. Additional Finish Coats: When undercoats, stains or other conditions show through the final coat of paint, apply additional finish coats of paint until the paint film is of uniform finish, color and appearance, and is acceptable to the Architect.

F. Application: Apply each coat of paint free of cloudiness, spotting, holidays, laps and brush marks,

runs, sags, ropiness, or other surface imperfections. Apply by brush, spray, or roller as deemed needed for best finish.

3.05 MAINTENANCE

A. As the Work proceeds, promptly remove paint where spilled, splashed, or spattered. B. During the progress of the Work, maintain the premises free of unnecessary accumulation of tools,

surplus materials and debris.

C. Collect cotton waste, cloths, and other materials that constitute a fire hazard, place in closed metal containers, and remove daily from the Site.

3.06 CLEANUP AND PROTECTION

A. Clean Up: Remove from the Site on a daily basis all discarded paint materials, rubbish, cans and rags. Upon the completion of the Painting Work, clean all window glass and other paint spattered surfaces. Remove spattered paint as directed by the Manufacturer of the product, using care not to scratch or otherwise damage any finished surfaces.

B. Provide "Wet Paint" signs: as required to adequately inform the public of newly painted surfaces.

Page 19: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 9 PAINTING

SECTION 09900

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 5 of 5

C. Protect: newly painted surfaces from any kind of damage until the Date of Substantial Completion. If any painted surface should be damaged in any way, repair damaged areas by cleaning, sanding, priming and finish painting the surface as required by the Architect.

PART 4 - PAINT SYSTEMS 4.01 GENERAL

A. Except as otherwise required to provide a specific type of coating, materials specified shall be equal to the products of Benjamin Moore Paints, which is the standard paint for the University Paint Shop. Paint Systems for wall and ferrous metal surfaces are specified below. Refer also to the Room Finish Schedule. The Architect shall choose all Paint System Colors from the Manufacturer’s complete range of colors.

1. Paint System # 1 All Walls:

a. Apply one coat primer/sealer equal to #1030-1200 “Ultra-Hide PVA Interior All Purpose Primer/Sealer”.

b. Apply two coats latex epoxy coating with a semi-gloss finish equal to

Benjamin Moore Filtered Sunlight 2154-60.

2. Paint System # 2 – Interior Shop-Primed Ferrous Metal (galvanized and non-

galvanized):

a. Touch-up galvanized finish on exterior ferrous metal in the field with Z.R.C. cold galvanizing material, or approved equal.

b. Touch-up shop-primed finish in the field with a primer compatible with oil-

based finish paint equal to #4160 “Devguard Multi-Purpose Tank and Structural Primer”. Apply one coat of primer to ducts, piping and conduit that has not been factory primed.

c. Apply two coats finish paint equal to #2518 “Ultra-Hide Durus Exterior Alkyd

Gloss Finish”.

+ + END OF SECTION + +

Page 20: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 BASIC MECHANICAL REQUIREMENTS

SECTION 15010

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014;Page 1 of 1

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Basic Mechanical Requirements specifically applicable to Division 15 Sections, in addition to

Division 1 - General Requirements. 1.2 SUBMITTALS A. Submit under provisions of Division 1. B. Include Products specified in the individual Sections. C. Submit shop drawings and product data grouped to include complete submittals of related

systems, products, and accessories in a single submittal. D. Mark dimensions and values in units to match those specified. 1.3 SEQUENCING AND SCHEDULING A. Construct Work in sequence under provisions of Division 1. B. Connections to existing systems shall be coordinated with Owner. Contractor shall notify Owner 48

hours in advance of making connections. PART 2 - PRODUCTS Not Used PART 3 - EXECUTION Not Used END OF SECTION

Page 21: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 SUPPORTS AND ANCHORS

SECTION 15140

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 5

PART 1 – GENERAL 1.1 SECTION INCLUDES A. Pipe hangers and supports. B. Sleeves. 1.2 RELATED SECTIONS A. Division 3 - Cast-In-Place Concrete: Equipment bases. B. Division 7 - Thermal and Moisture Protection: Joint seals for piping and duct penetration of fire

rated assemblies. C. Section 07270 - Fire Stopping. D. Division 9 - Finishes for Painting. E. Section 15246 - Vibration Isolation and Seismic Restraints. F. Section 15260 - Piping Insulation. G. Section 15310 - Fire Protection Piping. H. Section 15410 - Plumbing Piping. 1.3 REFERENCES A. ASME B31.1 - Power Piping. B. ASME B31.2 - Fuel Gas Piping. C. ASME B31.9 - Building Services Piping. D. ASTM F708 - Design and Installation of Rigid Pipe Hangers. E. MSS SP58 - Pipe Hangers and Supports - Materials, Design and Manufacturer. F. MSS SP69 - Pipe Hangers and Supports - Selection and Application. G. MSS SP89 - Pipe Hangers and Supports - Fabrication and Installation Practices. H. NFPA 13 - Installation of Sprinkler Systems. I. NFPA 14 - Installation of Standpipe and Hose Systems. J. UL 203 - Pipe Hanger Equipment for Fire Protection Service. 1.4 SUBMITTALS

Page 22: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 SUPPORTS AND ANCHORS

SECTION 15140

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 5

A. Submit under provisions of Division 1. B. Shop Drawings: Indicate system layout with location and detail of trapeze hangers. C. Product Data: Provide manufacturers catalog data including load capacity. D. Design Data: Indicate load carrying capacity of trapeze, multiple pipe, and riser support hangers. E. Manufacturer's Installation Instructions: Indicate special procedures and assembly of components. 1.5 REGULATORY REQUIREMENTS A. All piping supports shall conform to ASTM F708, MSS SP58, MSS SP69, MSS SP89, Connecticut

State Building Code and local building codes. B. Plumbing piping (DWV) shall conform to ASME B31.9. C. Plumbing piping (Water) shall conform to ASME B31.9. D. Supports for Sprinkler Piping: In conformance with NFPA 13. E. Supports for Standpipes: In conformance with NFPA 14. PART 2 - PRODUCTS 2.1 PIPE HANGERS AND SUPPORTS A. Manufacturers: 1. Grinnell Corp. models listed below. 2. Other acceptable manufacturers offering equivalent products: a) Mason Industries Inc. b) B Line Systems Inc. B. Hangers: Carbon steel, adjustable, clevis; Grinnell Figure 260. Other acceptable manufacturers

offering equivalent products: 1. Mason Industries Inc. 2. B Line Systems Inc. C. Multiple or Trapeze Hangers: Steel channels with welded spacers, hanger rods and U-bolt pipe

clamp. D. Wall Support for Pipe Sizes to 3 Inches (76 mm): Cast iron clamp; Grinnell Figure 126 or steel

bracket and hanger. Other acceptable manufacturers offering equivalent products: 1. Mason Industries Inc. 2. B Line Systems Inc. E. Wall Support for Pipe Sizes 3 Inches (76 mm) and Over: Welded steel bracket and hanger.

Page 23: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 SUPPORTS AND ANCHORS

SECTION 15140

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 5

F. Vertical Support: Steel riser clamp; Grinnell Figure 261. Other acceptable manufacturers offering equivalent products:

1. Mason Industries Inc. 2. B Line Systems Inc. G. Floor Support: Carbon steel adjustable pipe saddle, U-bolt, lock nut, nipple and floor flange;

Grinnell Figure 191. Other acceptable manufacturers offering equivalent products: 1. Mason Industries Inc. 2. B Line Systems Inc. H. Hanger Rods: Mild steel threaded both ends, or continuous threaded. I. Beam Clamps: Carbon steel, center I-beam clamp for providing even distribution on "T" flanges;

Grinnell Figure 133 or 134. Other acceptable manufacturers offering equivalent products: 1. Mason Industries Inc. 2. B Line Systems Inc. J. Beam Clamps For Piping 2" Diameter and Less: Malleable iron C-clamp with locknut; Grinnell Fig

86. Provide retaining clip for piping to be seismically braced. Other acceptable manufacturers offering equivalent products:

1. Mason Industries Inc. 2. B Line Systems Inc. K. Insulation Shields: Galvanized carbon steel; Grinnell Figure 167. Other acceptable manufacturers

offering equivalent products: 1. Mason Industries Inc. 2. B Line Systems Inc. 2.2 SLEEVES A. Sleeves for Pipes Through Non-fire Rated Floors, Beams, Walls and Footings: Schedule 10

carbon steel pipe or 18 gage (1.2 mm thick) galvanized steel or schedule 40 PVC. B. Sleeves for Pipes Through Fire Rated and Fire Resistive Floors, Walls, Building Components and

Fire Proofing: Schedule 40 carbon steel sleeve with firestop sealant. C. Sleeves for Round and Rectangular Ductwork: Galvanized steel. D. Firestopping Insulation: Glass fiber type, non-combustible; refer to Division 7. E. Sealant: RTV Silicone; refer to Division 7. PART 3 - EXECUTION 3.1 INSTALLATION A. Install in accordance with manufacturer's instructions. 3.2 PIPE HANGERS AND SUPPORTS

Page 24: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 SUPPORTS AND ANCHORS

SECTION 15140

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 5

A. Install hangers to provide minimum 1/2 inch (13 mm) space between finished covering and adjacent work.

B. Place hangers within 12 inches (300 mm) of each horizontal elbow. C. Use hangers with 1-1/2 inch (38 mm) minimum vertical adjustment. D. Support horizontal cast iron pipe adjacent to each hub, with 5 feet (1.5 m) maximum spacing

between hangers. E. Support vertical piping at every floor; maximum distance of 15 feet between vertical supports.

Support vertical cast iron pipe at each floor at hub. F. Where several pipes can be installed in parallel and at same elevation, provide multiple or trapeze

hangers. G. Support riser piping independently of connected horizontal piping. H. Design hangers for pipe movement without disengagement of supported pipe. I. Provide insulation shields at all insulated piping. J. Provide supplemental steel channels, unistrut, etc. supported from building structure as required. 3.3 SLEEVES A. Set sleeves in position in formwork. Provide reinforcing around sleeves. B. Size sleeves large enough to allow for movement due to expansion and contraction. Provide for

continuous insulation wrapping. C. Extend sleeves through floors one inch (25 mm) above finished floor level. Caulk sleeves. D. Where piping or ductwork penetrates floor, ceiling, or wall, close off space between pipe or duct

and adjacent work with fire stopping insulation and caulk. Provide close fitting metal collar or escutcheon covers at both sides of penetration.

E. Install chrome plated steel escutcheons at finished surfaces. 3.4 SCHEDULE HANGER SPACING

Pipe Material & Size Max. Horizontal Spacing Min. Hanger Rod Diameter

Max. Vertical Spacing

Steel 1/4" thru 1-1/4" 7' 3/8" 12'

Steel 1-1/2" 9' 3/8" 12'

Page 25: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 SUPPORTS AND ANCHORS

SECTION 15140

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 5 of 5

Steel 2" 10' 3/8" 12'

Steel 3" 12' 1/2" 12'

Steel 4" 14' 5/8" 12'

Steel 5" 16' 5/8" 12'

Steel 6" 17' 3/4" 12'

Steel 8" 19' 7/8" 12'

Copper 1/4" thru 3/4" 5' 3/8" 10'

Copper 1" 6' 3/8" 10'

Copper 1-1/4" 7' 3/8" 10'

Copper 1-1/2" thru 2" 8 3/8" 10'

Copper 3" 10' 1/2" 10'

Copper 4" 12' 5/8" 10'

C.I. 3" thru 5" 10' * 5/8" 15'

C.I. 6" 10' * 3/4" 15'

C.I 8" thru 10" 10' * 7/8" 15'

PVC 2" and smaller 4' 3/8" 4'

PVC 3" thru 6" 4' 1/2" 4' * Spacing for C.I. Pipe assumes a 10' length of pipe. Adjust spacing accordingly for shorter sections.

END OF SECTION

Page 26: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 MECHANICAL IDENTIFICATION

SECTION 15190

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 4

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Nameplates. B. Tags. C. Stencils. D. Pipe Markers. 1.2 RELATED SECTIONS A. Division 9 - Finishes for Painting. 1.3 REFERENCES A. ASME A13.1 - Scheme for the Identification of Piping Systems. 1.4 SUBMITTALS A. Submit under provisions of Division 1. B. Submit list of wording, symbols, letter size, and color coding for mechanical identification. C. Submit valve chart and schedule, including valve tag number, location, function, and valve

manufacturer's name and model number. D. Product Data: Provide manufacturers catalog literature for each product required. E. Manufacturer's Installation Instructions: Indicate special procedures, and installation. 1.5 PROJECT RECORD DOCUMENTS A. Submit under provisions of Division 1. B. Record actual locations of tagged valves. PART 2 - PRODUCTS 2.1 NAMEPLATES A. Manufacturers: Best, EMED Co. or approved equal. B. Equipment nameplates shall match current CCSU Campus Mechanical Identification/Color Coding

Standards.

Page 27: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 MECHANICAL IDENTIFICATION

SECTION 15190

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 4

C. Description: Laminated three-layer plastic with engraved white letters on black background. For equipment, text indicating equipment name shall be 1" in height and all remaining text shall be 1/4" in height.

2.2 TAGS A. Manufacturers: Seton Name Plate Co., EMED Co. or approved equal. B. Plastic Tags: Laminated three-layer plastic with engraved black letters on light contrasting

background color. Tag size minimum 1-1/2 inch (40 mm) square. C. Metal Tags: Brass with stamped letters; tag size minimum 1-1/2 inch (40 mm) square with smooth

edges. D. Chart: Typewritten letter size list in anodized aluminum frame. 2.3 STENCILS A. Manufacturers: Seton Name Plate Co., EMED Co. or approved equal. B. Stencils: With clean cut symbols and letters of following size: 1. 3/4 to 1-1/4 inch (20-30 mm) Outside Diameter of Insulation or Pipe: 8 inch (200 mm) long

color field, 1/2 inch (15 mm) high letters. 2. 1-1/2 to 2 inch (40-50 mm) Outside Diameter of Insulation or Pipe: 8 inch (200 mm) long

color field, 3/4 inch (20 mm) high letters. 3. 2-1/2 to 6 inch (65-150 mm) Outside Diameter of Insulation or Pipe: 12 inch (300 mm) long

color field, 1-1/4 inch (30 mm) high letters. 4. 8 to 10 inch (200-250 mm) Outside Diameter of Insulation or Pipe: 24 inch (600 mm) long

color field, 2-1/2 inch (65 mm) high letters. 5. Over 10 inch (250 mm) Outside Diameter of Insulation or Pipe: 32 inch (800 mm) long color

field, 3-1/2 inch (90 mm) high letters. 6. Ductwork and Equipment: 2-1/2 inch (65 mm) high letters. C. Stencil Paint: As specified in Division 9, semi-gloss enamel, colors conforming to ASME A13.1. 2.4 PIPE MARKERS A. Manufacturers: Setmark Type SNA or STR as manufactured by Seton Name Plate Co., EMED

Co. or approved equal. B. Color: Shall match current CCSU Campus Mechanical Identification/Color Coding Standards. C. Plastic Pipe Markers: Factory fabricated, flexible, semi- rigid plastic, preformed to fit around pipe or

pipe covering; minimum information indicating flow direction arrow and identification of fluid being conveyed.

D. Plastic Tape Pipe Markers: Flexible, vinyl film tape with pressure sensitive adhesive backing and

printed markings; minimum information indicating flow direction arrow and identification of fluid being conveyed.

Page 28: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 MECHANICAL IDENTIFICATION

SECTION 15190

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 4

E. Underground Plastic Pipe Markers: Bright colored continuously printed plastic ribbon tape,

minimum 6 inches (150 mm) wide by 4 mil (0.10 mm) thick, manufactured for direct burial service. PART 3 - EXECUTION 3.1 PREPARATION A. Degrease and clean surfaces to receive adhesive for identification materials. B. Prepare surfaces in accordance with Division 9 for stencil painting. 3.2 INSTALLATION A. Install plastic nameplates with corrosive-resistant mechanical fasteners, or adhesive. Apply with

sufficient adhesive to ensure permanent adhesion and seal with clear lacquer. B. Install tags with corrosion resistant brass or nylon chain. C. Apply stencil painting in accordance with Division 9. D. Install plastic pipe markers in accordance with manufacturer's instructions. E. Install plastic tape pipe markers complete around pipe in accordance with manufacturer's

instructions. F. Install underground plastic pipe markers 6 to 8 inches (150 to 200 mm) below finished grade,

directly above buried pipe. G. Identify all equipment with nameplates in accordance with current CCSU Campus Mechanical

Identification/Color Coding Standards. Small devices may be identified with tags. H. Identify control panels and major control components outside panels with nameplates. I. Identify thermostats with nameplates. J. Identify valves in main and branch piping with tags. K. Tag all control components, instruments and relays. Key to control schematic. L. Identify all piping, concealed or exposed, with pipe markers or stencilled painting. Use tags on

piping 3/4 inch (20 mm) diameter and smaller. Identify service and flow direction. Install in clear view and align with axis of piping. Locate identification not to exceed 20 feet (6 m) on straight runs including risers and drops, adjacent to each valve and Tee, at each side of penetration of structure or enclosure, and at each obstruction.

M. Identify ductwork with stencilled painting. Identify system type (supply, exhaust, etc.) and direction

of flow. Locate identification at air handling unit, at each side of penetration of structure or enclosure, and at each obstruction.

Page 29: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 MECHANICAL IDENTIFICATION

SECTION 15190

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 4

END OF SECTION

Page 30: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PIPING INSULATION

SECTION 15260

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 6

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Piping insulation. B. Tank insulation. C. Jackets and accessories. 1.2 RELATED SECTIONS A. Division 9 - Finishes for painting. B. Section 15140 - Supports and Anchors. C. Section 15190 - Mechanical Identification. D. Section 15410 - Plumbing Piping. E. Division 16 - Electrical. 1.3 REFERENCES A. ASTM C177 - Steady-State Heat Flux Measurements and Thermal Transmission Properties by

Means of the Guarded-Hot-Plate Apparatus. B. ASTM C195 - Mineral Fiber Thermal Insulation Cement. C. ASTM C335 - Steady-State Heat Transfer Properties of Horizontal Pipe Insulation. D. ASTM C449 - Mineral Fiber Hydraulic-setting Thermal Insulating and Finishing Cement. E. ASTM C518 - Steady-State Heat Flux Measurements and Thermal Transmission Properties by

Means of the Heat Flow Meter Apparatus. F. ASTM C534 - Preformed Flexible Elastomeric Cellular Thermal Insulation in Sheet and Tubular

Form. G. ASTM C547 - Mineral Fiber Preformed Pipe Insulation. H. ASTM C585 - Inner and Outer Diameters of Rigid Thermal Insulation for Nominal Sizes of Pipe

and Tubing (NPS System). I. ASTM C921 - Properties of Jacketing Materials for Thermal Insulation. J. ASTM D1056 - Flexible Cellular Materials - Sponge or Expanded Rubber.

Page 31: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PIPING INSULATION

SECTION 15260

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 6

K. ASTM D1667 - Flexible Cellular Materials - Vinyl Chloride Polymers and Copolymers (Closed Cell Foam).

L. ASTM D1784 - Rigid Poly (Vinyl Chloride) (PVC) Compounds and Chlorinated Poly (Vinyl Chloride)

(CPVC) Compounds. M. ASTM D2842 - Water Absorption of Rigid Cellular Plastics. N. ASTM E84 - Surface Burning Characteristics of Building Materials. O. ASTM E96 - Water Vapor Transmission of Materials. P. NFPA 255 - Surface Burning Characteristics of Building Materials. Q. UL 723 - Surface Burning Characteristics of Building Materials. 1.4 SUBMITTALS A. Submit under provisions of Division 1. B. Product Data: Provide product description, list of materials and thickness for each service, and

locations. C. Samples: Submit two samples of any representative size illustrating each insulation type. D. Manufacturer's Installation Instructions: Indicate procedures which ensure acceptable

workmanship and installation standards will be achieved. 1.5 QUALITY ASSURANCE A. Materials: Flame spread/smoke developed rating of 25/50 or less in accordance with ASTM E84,

NFPA 255, and UL 723. 1.6 QUALIFICATIONS A. Applicator: Company specializing in performing the work of this section with minimum three years

experience. 1.7 DELIVERY, STORAGE, AND HANDLING A. Deliver, store, protect, and handle products to site under provisions of Division 1. B. Deliver materials to site in original factory packaging, labelled with manufacturer's identification,

including product density and thickness. C. Store insulation in original wrapping and protect from weather and construction traffic. D. Protect insulation against dirt, water, chemical, and mechanical damage.

Page 32: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PIPING INSULATION

SECTION 15260

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 6

1.8 ENVIRONMENTAL REQUIREMENTS A. Maintain ambient temperatures and conditions required by manufacturers of adhesives, mastic,

and insulation cements. B. Maintain temperature during and after installation for minimum period of 24 hours. PART 2 - PRODUCTS 2.1 GLASS FIBER A. Manufacturers: 1. Manville Micro-Lok. 2. Other acceptable manufacturers offering equivalent products: a) Owens Corning. b) Certainteed Manson. c) Knauf. B. Insulation: ASTM C547; rigid molded, noncombustible. 1. 'K' value (SI 'k' value): ASTM C335, 0.25 at 75 degrees F (0.036 at 24 degrees C). 2. Minimum Service Temperature: -20 degrees F (-28.9 degrees C). 3. Maximum Service Temperature: 850 degrees F (454 degrees C). 4. Maximum Moisture Adsorption: 0.2 percent by volume. C. Vapor Barrier Jacket: 1. White kraft paper reinforced with glass fiber yarn and bonded to aluminized film. 2. Moisture Vapor Permeability: ASTM E96; 0.02 perm inch. D. Installation and Jacketing: 1. Secure seams with pressure sensitive tape closure and butt joints with minimum 3 inch (76

mm) wide tape of same material as vapor barrier jacket. 2. PVC jacket shall be installed on following: a) Insulated piping located within mechanical rooms that is installed less than 10 feet (3

m) above finished floor. b) All piping systems located within eight feet of finished floor in occupied spaces, locker

and shower rooms, and rest rooms. c) All insulated fittings and valves. 3. For finish see Division 9. 2.2 GLASS FIBER, RIGID A. Manufacturers: 1. Manville 800 Series. 2. Other acceptable manufacturers offering equivalent products: a) Owens Corning. b) Certainteed.

Page 33: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PIPING INSULATION

SECTION 15260

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 6

B. Insulation: ASTM C612; rigid, noncombustible. 1. 'K' value (SI 'K' value): ASTM C518, 0.22 at 75 degrees F (0.032 at 24 degrees C). 2. Maximum service temperature: 450 degrees F (232 degrees C). 3. Maximum moisture adsorption: 1.0 percent by volume. 4. Density: 6.0 lb/cu ft (96 kg/cu m). 5. Thickness: 4 inch (25 mm). C. Vapor Barrier Jacket 1. Kraft paper reinforced with glass fiber yarn and bonded to aluminized film for equipment

interior to building. 2. Moisture vapor permeability: ASTM E96; .02 perm inch. 3. Secure with pressure sensitive tape. 4. For finish see Division 9. D. Vapor Barrier Tape: Kraft paper reinforced with glass fiber yarn and bonded to aluminized film,

with pressure sensitive rubber based adhesive. 2.3 FLEXIBLE ELASTOMERIC CELLULAR A. Manufacturers: Armstrong Armaflex AP or approved equal. B. Insulation: ASTM C534; flexible, cellular elastomeric, tubular. 1. 'K' value (SI 'k' value): ASTM C177 or C518; 0.27 at 75 degrees F (0.04 at 24 degrees C). 2. Minimum Service Temperature: -40 degrees F (-40 degrees C). 3. Maximum Service Temperature: 220 degrees F (104 degrees C). 4. Maximum Moisture Absorption: ASTM D1056; 5 percent by volume. 5. Moisture Vapor Permeability: ASTM E96; 0.20 perm inches. C. Installation 1. Slip insulation over piping or slit and snap over piping. 2. Apply Armstrong 520 adhesive to all seams and butt joints. 3. Fittings and Valves: Field fabricate per manufacturer's instructions. 4. Finish with WB Armaflex finish. 2.4 JACKETS A. Polyvinyl Chloride (PVC) Plastic 1. Manufacturer: Manville Zeston 2000 or approved equal. 2. Jacket: ASTM D1784, one piece molded type fitting covers and sheet material, off white

color. a) Minimum Service Temperature: 0 degrees F (-18 degrees C). b) Maximum Service Temperature: 150 degrees F (66 degrees C). c) Thickness: 10 mil (.26 mm). 3. Installation: a) Fittings and Valves: Factory precut inserts. b) Apply vapor retardant mastic to all seams and joints. c) Secure all seams and joints with Zeston PVC Z-Tape.

Page 34: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PIPING INSULATION

SECTION 15260

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 5 of 6

PART 3 - EXECUTION 3.1 EXAMINATION A. Verify that piping has been tested before applying insulation materials. B. Verify that surfaces are clean, foreign material removed, and dry. 3.2 INSTALLATION A. Install materials in accordance with manufacturer's instructions. B. On exposed piping, locate insulation and cover seams in least visible locations. C. Continue insulation through walls, sleeves, pipe hangers, and other pipe penetrations. D. Insulate entire system including fittings, valves, unions, flanges, strainers, flexible connections and

expansion joints. E. Inserts and Shields: 1. Application: Piping 2 inches (50 mm) diameter or larger. 2. Shields: Refer to Section 15140. 3. Insert Location: Between support shield and piping and under the finish jacket. 4. Insert Configuration: Minimum 6 inches (150 mm) long, of same thickness and contour as

adjoining insulation; may be factory fabricated. 5. Insert Material: ASTM C640 cork, hydrous calcium silicate insulation or other heavy density

insulating material suitable for the planned temperature range. F. Finish insulation at supports, protrusions, and interruptions. 3.3 TOLERANCE A. Substituted insulation materials shall provide thermal resistance within 10 percent at normal

conditions, as materials indicated. 3.4 GLASS FIBER INSULATION SCHEDULE PIPING SYSTEMS PIPE SIZE THICKNESS Inch (mm) Inch (mm)

Domestic Hot and Cold Water All 1"

Domestic Hot Water Recirculating All 1"

Horizontal Storm Piping Above Grade Up to 6" 1"

Horizontal Storm Piping Above Grade Over 6" 1-1/2"

Page 35: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PIPING INSULATION

SECTION 15260

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 6 of 6

HOT WATER STORAGE TANK

4"

3.5 FLEXIBLE ELASTOMERIC CELLULAR INSULATION SCHEDULE PIPING SYSTEMS PIPE SIZE THICKNESS Inch (mm) Inch (mm)

Refrigerant Piping All 3/4"

END OF SECTION

Page 36: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK INSULATION

SECTION 15290

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 5

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Ductwork insulation. B. Duct liner. C. Insulation jackets. 1.2 RELATED SECTIONS A. Division 9 - Painting. B. Section 15190 - Mechanical Identification. C. Section 15890 - Ductwork. D. Section 15910 - Ductwork Accessories. 1.3 REFERENCES A. ASTM B209 - Aluminum and Aluminum-Alloy Sheet and Plate. B. ASTM C518 - Steady-State Heat Flux Measurements and Thermal Transmission Properties by

Means of the Heat Flow Meter Apparatus. C. ASTM C553 - Mineral Fiber Blanket and Felt Insulation. D. ASTM C612 - Mineral Fiber Block and Board Thermal Insulation. E. ASTM E84 - Surface Burning Characteristics of Building Materials. F. ASTM E96 - Water Vapor Transmission of Materials. G. NFPA 255 - Surface Burning Characteristics of Building Materials. H. SMACNA - HVAC Duct Construction Standards - Metal and Flexible. I. UL 723 - Surface Burning Characteristics of Building Materials. 1.4 SUBMITTALS A. Submit under provisions of Division 1. B. Product Data: Provide product description, list of materials and thickness for each service, and

locations.

Page 37: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK INSULATION

SECTION 15290

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 5

C. Manufacturer's Installation Instructions: Indicate procedures which ensure acceptable workmanship and installation standards will be achieved.

1.5 QUALITY ASSURANCE A. Materials: Flame spread/smoke developed rating of 25/50 in accordance with ASTM E84, NFPA

255 and UL 723. 1.6 QUALIFICATIONS A. Applicator: Company specializing in performing the work of this section with minimum three years

experience. 1.7 DELIVERY, STORAGE, AND HANDLING A. Deliver, store, protect and handle products to site under provisions of Division 1. B. Deliver materials to site in original factory packaging, labeled with manufacturer's density and

thickness. C. Store insulation in original wrapping and protect from weather and construction traffic. D. Protect insulation against dirt, water, chemical, and mechanical damage. 1.8 ENVIRONMENTAL REQUIREMENTS A. Maintain ambient temperatures and conditions required by manufacturers of adhesives, mastics,

and insulation cements. B. Maintain temperature during and after installation for minimum period of 24 hours. PART 2 - PRODUCTS 2.1 GLASS FIBER, FLEXIBLE A. Manufacturers: 1. Manville Microlite. 2. Other acceptable manufacturers offering equivalent products: a) Owens Corning. b) Certainteed. B. Insulation: ASTM C553; flexible, noncombustible blanket. 1. 'K' value (SI 'K' value): ASTM C518, 0.26 at 75 degrees F (0.038 at 24 degrees C). 2. Maximum service temperature: 250 degrees F (121 degrees C). 3. Maximum moisture adsorption: 0.20 percent by volume. 4. Density: Type 100; 1.0 lb/cu ft (16 kg/cu m). 5. Thickness: 1.5 inches (38 mm). C. Vapor Barrier Jacket

Page 38: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK INSULATION

SECTION 15290

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 5

1. Kraft paper reinforced with glass fiber yarn and bonded to aluminized film. 2. Moisture vapor permeability: ASTM E96; 0.02 perm inch. 3. Secure with pressure sensitive tape. D. Vapor Barrier Tape: Kraft paper reinforced with glass fiber yarn and bonded to aluminized film,

with pressure sensitive rubber based adhesive. 2.2 GLASS FIBER, RIGID A. Manufacturers: 1. Manville 800 Series. 2. Other acceptable manufacturers offering equivalent products: a) Owens Corning. b) Certainteed. B. Insulation: ASTM C612; rigid, noncombustible blanket. 1. 'K' value (SI 'K' value): ASTM C518, 0.22 at 75 degrees F (0.032 at 24 degrees C). 2. Maximum service temperature: 450 degrees F (232 degrees C). 3. Maximum moisture adsorption: 1.0 percent by volume. 4. Density: 6.0 lb/cu ft (96 kg/cu m). 5. Thickness: 1 inch (25 mm). C. Vapor Barrier Jacket 1. Kraft paper reinforced with glass fiber yarn and bonded to aluminized film for ductwork

interior to building. 2. Moisture vapor permeability: ASTM E96; .02 perm inch. 3. Secure with pressure sensitive tape. D. Vapor Barrier Tape: Kraft paper reinforced with glass fiber yarn and bonded to aluminized film,

with pressure sensitive rubber based adhesive. E. Outdoor Vapor Barrier Mastic: Vinyl emulsion type acrylic or mastic, compatible with insulation,

black color. 2.3 GLASS FIBER DUCT LINER A. Manufacturers: 1. Owens Corning Aeroflex Type 200. 2. Other acceptable manufacturers offering equivalent products. a) Manville. b) Certainteed. B. Insulation: ASTM C1071; flexible, noncombustible blanket. 1. 'K' value (SI 'K' value): ASTM C518, 0.26 at 75 degrees F (0.038 at 24 degrees C). 2. Maximum service temperature: 250 degrees F (121 degrees C). 3. Density: 2.0 lb/cu ft (32 kg/cu m). 4. Maximum Velocity on Coated Air Side: 5,000 ft/min (20.3 m/sec). 5. Thickness: 2 inch (25 mm).

Page 39: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK INSULATION

SECTION 15290

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 5

C. Noise Reducing Coefficient: NRC shall not exceed 0.6. D. Adhesive: Waterproof, fire retardant type. E. Liner Fasteners: Galvanized steel mechanical fasteners. PART 3 - EXECUTION 3.1 EXAMINATION A. Verify that ductwork has been tested before applying insulation materials. B. Verify that surfaces are clean, foreign material removed, and dry. 3.2 INSTALLATION A. Install materials in accordance with manufacturer's instructions and as outlined within this

specification. B. Continue insulation through walls, sleeves, hangers, and other duct penetrations. C. Insulate entire system including fittings, joints, flanges, fire dampers, flexible connections, and

expansion joints. D. Flexible Glass Fiber Insulation Application: 1. Secure insulation seams with staples, spaced at 6 inches (150 mm) on center. 2. Seal seams with pressure sensitive tape. 3. Install without sags on underside of ductwork. Use mechanical fasteners where necessary

to prevent sagging. Lift ductwork off trapeze hangers and insert spacers. 4. Seal vapor barrier penetrations by mechanical fasteners with vapor barrier adhesive. 5. Stop and point insulation around access doors and damper operators to allow operation

without disturbing wrapping. 6. Seal all tears, punctures and other penetrations with pressure sensitive tape. E. Rigid Glass Fiber Insulation Application: 1. Secure insulation with weld pins or stick clips at 12 inches (350 mm) on center. Locate at

maximum 3 inches (76 mm) from each edge and corner of board. 2. Cover pins and clips with vapor sealing pressure sensitive patches or tape. 3. Apply 5 inch (130 mm) wide vapor sealing pressure sensitive tape to all joints and seams. F. Duct Liner Application: 1. Adhere insulation with adhesive for 90 percent coverage and adhere adhesive at all

exposed edges and transverse joints. 2. Secure insulation with mechanical liner fasteners. Refer to SMACNA Standards for spacing. 3. Seal and smooth joints. 4. Seal liner surface penetrations with adhesive. 5. Duct dimensions indicated are net inside dimensions required for air flow. Increase duct

size to allow for insulation thickness.

Page 40: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK INSULATION

SECTION 15290

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 5 of 5

3.3 TOLERANCE A. Substituted insulation materials shall provide thermal resistance within 10 percent at normal

conditions, as materials indicated. 3.4 DUCTWORK INSULATION SCHEDULE A. Schedule of Ductwork In Concealed Spaces: DUCTWORK TYPE Supply Air Flexible Glass Fiber Return Air Flexible Glass Fiber Outside Air Flexible Glass Fiber Plenums Flexible Glass Fiber B. Schedule of Ductwork In Exposed Unconditioned Spaces: DUCTWORK TYPE Supply Air Rigid Glass Fiber Return Air Rigid Glass Fiber Outside Air Rigid Glass Fiber Plenums Rigid Glass Fiber C. Schedule of Miscellaneous Ductwork: DUCTWORK TYPE Ductwork shown lined on Drawings Glass Fiber Liner Ductwork exposed to outdoors Glass Fiber Liner Exposed ductwork in Insulation not required conditioned spaces END OF SECTION

Page 41: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 SPRINKLER SYSTEMS

SECTION 15325

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 6

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wet-pipe sprinkler system. B. System design, installation, and certification. C. Fire department connections. 1.2 PRODUCTS INSTALLED BUT NOT FURNISHED UNDER THIS SECTION A. Section 15310 - Fire Protection Piping: Piping and valves. 1.3 RELATED SECTIONS A. Section 02225 - Trenching. B. Section 07270 - Fire Stopping. C. Section 15140 - Supports and Anchors. D. Section 15190 - Mechanical Identification. E. Section 15246 - Vibration Isolation and Seismic Restraints. 1.4 REFERENCES A. NFPA 13 - Installation of Sprinkler Systems. 1.5 SYSTEM DESCRIPTION A. System to provide coverage for entire building. B. Fire protection sprinkler system is designed for total coverage light hazard occupancy

requirements. C. Volume and pressure of incoming water supply (for information only of contractor to prepare bid)

from water flow test taken on June 25, 1991 by H.F.P. Sprinkler of Hazardville, Inc at flow hydrant at North side of Sheridan Hall near entrance and residual hydrant East side of Sheridan Hall near pump house.

Static - 108 psi Residual - 93 psi GPM - 1480 gpm Contractor shall be responsible to obtain current, within three months, flow tests for use as basis of

design.

Page 42: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 SPRINKLER SYSTEMS

SECTION 15325

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 6

D. Determine volume and pressure of incoming water supply for hydraulic calculations from water flow

test data. E. When performing hydraulic calculations, a minimum of 8 psi safety cushion shall be provided,

unless this will result in having to install a fire pump. F. Interface system with building fire and smoke alarm system. G. Provide fire department connection as indicated. 1.6 SUBMITTALS A. Submit under provisions of Division 1. B. Where the terms "authority having jurisdiction" is used within this specification, it is intended to

include the Insurance Underwriter and all regulatory agencies having vested interest in this project. C. Preliminary Shop Drawings: Prior to detailed submission, submit preliminary layout of finished

ceiling areas indicating only sprinkler locations coordinated with ceiling installation. D. Shop Drawings: Indicate hydraulic calculations, detailed pipe layout, hangers and supports,

components and accessories. Indicate system controls. E. Product Data: Provide data on sprinkler heads, valves, and specialties, including manufacturers

catalogue information. Submit performance ratings rough-in details, weights, support requirements, and piping connections.

F. Contractor shall submit shop drawings and hydraulic calculations to authority having jurisdiction for

approval. Submit proof of approval to Architect/Engineer. G. Manufacturer's Certificate: Certify that system has been tested and meets or exceeds specified

requirements and all code requirements. H. Drawings and calculations shall be sealed by a Professional Engineer currently registered in the

State of Connecticut. I. Contractor shall forward additional copies of approved shop drawings to the State Fire Marshal and

State Insurance Carrier. It is noted that before transmitting the copies to the State Insurance Carrier and the State Fire Marshal, the Architect must first have these copies reviewed for concurrence by him or his fire protection consultant.

Travelers Property and Casualty Company City Place, 5th Floor 185 Asylum Street Hartford, CT 06183 Att: Greg Murin

Page 43: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 SPRINKLER SYSTEMS

SECTION 15325

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 6

Loss Prevention and Engineering Services Tel: (860) 277-8021 1.7 PROJECT RECORD DOCUMENTS A. Submit under provisions of Division 1. B. Record actual locations of sprinkler heads and deviations of piping from drawings. Indicate drain

and test locations. 1.8 OPERATION AND MAINTENANCE DATA A. Submit under provisions of Division 1. B. Maintenance Data: Include components of system, servicing requirements, Record Drawings,

inspection data, replacement part numbers and availability, and location and numbers of service depot.

1.9 QUALITY ASSURANCE A. Workmanship and Qualifications: All materials and equipment shall be installed in accordance with

NFPA Standard 13 and all applicable local codes and ordinances. The Sprinkler Contractor shall be state licensed to install sprinkler systems. The Sprinkler Contractor shall make sure that all work and materials conform to the requirements set forth by this Specification. Fire protection equipment shall be installed to conform to NFPA Standard 13 as applicable, and devices used shall be listed and approved by Underwriters laboratories (UL) and/or Factory Mutual (FM). Welding shall be in accordance with NFPA Standard 13 by certified welders.

B. Codes and Standards: All work shall be equal or superior to that required by codes, regulations,

ordinances, and laws imposed by the jurisdictional authorities. Nothing in the Specifications permit violation of such directives, and where conflict occurs, the directive shall govern, except where superior work is specified or indicated.

C. In addition to complying with the above codes and regulations, comply with the requirements of the

following: 1. NFPA Standard 13. 2. State Building and Fire Codes. 3. Local Jurisdictional Authorities. D. Maintain one copy of document on site. 1.10 QUALIFICATIONS A. Installer: Company specializing in performing work of this Section with minimum five years

experience. B. Design sprinkler system under direct supervision of a Professional Engineer experienced in design

of this work and licensed in the State of Connecticut.

Page 44: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 SPRINKLER SYSTEMS

SECTION 15325

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 6

1.11 REGULATORY REQUIREMENTS A. Hydraulic Calculations and Shop Drawings: Bear stamp of approval of Owner's fire insurance

underwriter. 1.12 DELIVERY, STORAGE, AND HANDLING A. Deliver, store, protect, and protect products to site under provisions of Division 1. B. Store products in shipping containers and maintain in place until installation. Provide temporary

inlet and outlet caps. Maintain caps in place until installation. C. All equipment, valves, alarms, gages and etc., shall be covered and protected during the execution

of the work. All equipment and piping shall be protected from freezing. Labeling to remain in place.

D. All unloading, hauling, and handling of materials shall be the responsibility of the Sprinkler

Contractor. E. The Sprinkler Contractor can obtain information on available storage space on site from the Owner

when making examination of the site. 1.13 EXTRA MATERIALS A. Furnish under provisions of Division 1. B. Provide extra sprinklers under provisions of NFPA 13. C. Provide suitable wrenches for each sprinkler type. D. Provide metal storage cabinet in location designated. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Grinnell Fire Protection Equipment. B. Viking Corp. C. Reliable Automatic Sprinkler Co. D. Substitutions: Shall be approved by the Architect/Engineer. 2.2 SPRINKLERS A. Manufacturers:

Page 45: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 SPRINKLER SYSTEMS

SECTION 15325

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 5 of 6

1. Grinnell Fire Protection Equip., Model F980. 2. Other acceptable manufacturers offering equivalent products include: a) Viking Corp. b) Reliable Automatic Sprinkler Co. B. Suspended Ceiling: 1. Type: Standard pendant type with matching escutcheon plate. 2. Head Finish: Chrome plated. 3. Escutcheon Plate Finish: Chrome plated. 4. Fusible Link: Bulb type with a rated temperature of 155 deg. 5. Sprinkler shall be Grinnell, Model F-980. C. Exposed Area Type: 1. Type: Standard pendant type. 2. Head Finish: Brass. 3. Fusible Link: Bulb type with a rated temperature of 155 deg. 4. Sprinkler shall be Grinnell, Model F-980. D. Spare Sprinklers: The Sprinkler Contractor shall furnish spare automatic sprinklers in accordance

with the requirements of NFPA Standard 13 for stock of extra sprinklers. The sprinklers shall be packed in a suitable container and shall be representative of, and in proportion to, the number of each type and temperature rating of the sprinklers installed. The Sprinkler Contractor shall furnish no less than two special sprinkler head wrenches, or at least one head wrench for each container or sprinkler box, whichever is greater.

2.3 PIPING SPECIALTIES A. Wet Pipe Sprinkler Alarm Valve: Check type valve with divided seat ring, rubber faced clapper to

automatically actuate electrically and hydraulically operated alarms, with pressure retard chamber and variable pressure trim.

B. Water Flow Switch: Vane type switch for mounting horizontal or vertical, with two form C contacts

rated 10 amp at 115 volt AC. C. Fire Department Connection: 1. Type: Flush mounted wall type with brass finish. 2. Outlet: one 2 1/2" with thread size to suit fire department hardware; threaded dust cap and

chain of matching material and finish. 3. Drain: 3/4 inch (19 mm) automatic drip, connected to drain. 4. Label: "Sprinkler - Fire Department Connection". PART 3 - EXECUTION 3.1 PREPARATION A. Coordinate work of this Section with other affected work. 3.2 INSTALLATION

Page 46: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 SPRINKLER SYSTEMS

SECTION 15325

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 6 of 6

A. Install equipment in accordance with manufacturers instructions. B. Products shall be installed in accordance with the requirements of this Specification and all

applicable NFPA Standards. C. All work shall be complete before making the final connections to the existing water supplies. D. The Contractor shall maintain a clean and orderly site during the installation of the sprinkler

system. Materials shall not be stored in the halls or other public areas. E. Provide reduced pressure backflow preventer assembly at sprinkler system water source

connection. F. Locate fire department connection with sufficient clearance from walls, obstructions, to allow full

swing of fire department wrench handle. G. Place pipe runs to minimize obstruction to other work. H. Place piping in concealed spaces above finished ceilings. I. Center sprinklers in one direction only in ceiling tile with location in other direction variable,

dependent upon spacing and coordination with ceiling elements. J. Flush entire piping system of foreign matter. K. Hydrostatically test entire system. L. Require test be witnessed by authority having jurisdiction. 3.3 IDENTIFICATION A. Provide and apply signs to control, drain, test and alarm valves to identify their purpose and

function. Provide and permanently attach hydraulic calculations data nameplate at the controlling valve for the sprinkler system. Provide lettering size and style from NFPA's suggested styles.

3.4 TESTING A. For Testing of sprinkler system, refer to Section 15310 - Fire Protection Piping. END OF SECTION

Page 47: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING PIPING

SECTION 15410

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 11

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings. B. Valves. C. Sanitary sewer piping system. D. Domestic water piping system. E. Storm water piping system. 1.2 RELATED SECTIONS A. Division 2 - Excavating. B. Division 2 - Backfilling. C. Section 07270 - Fire Stopping. D. Section 15010 - Basic Mechanical Requirements. E. Section 15140 - Supports and Anchors. F. Section 15190 - Mechanical Identification. G. Section 15246 - Vibration Isolation and Seismic Restraint. H. Section 15260 - Piping Insulation. I. Section 15430 - Plumbing Specialties. J. Section 15440 - Plumbing Fixtures. K. Section 15450 - Plumbing Equipment. L. Section 16010 - Basic Electrical Requirements. 1.3 REFERENCES A. ANSI B31.1 - Power Piping. B. ANSI B31.9 - Building Service Piping. C. ASME Sec. 9 - Welding and Brazing Qualifications.

Page 48: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING PIPING

SECTION 15410

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 11

D. ASME B16.1 - Cast Iron Pipe Flanges and Flanged Fittings Class 25, 125, 250 and 800. E. ASME B16.3 - Malleable Iron Threaded Fittings. F. ASME B16.4 - Cast Iron Threaded Fittings Class 125 and 250. G. ASME B16.18 - Cast Bronze Solder-Joint Pressure Fittings. H. ASME B16.22 - Wrought Copper and Bronze Solder-Joint Pressure Fittings I. ASTM A53 - Pipe, Steel, Black and Hot-Dipped Zinc Coated, Welded and Seamless. J. ASTM A74 - Cast Iron Soil Pipe and Fittings. K. ASTM A120 - Pipe, Steel, Black and Hot-Dipped Zinc Coated (Galvanized), Welded and

Seamless, for Ordinary Uses. L. ASTM A234 - Pipe Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and Elevated

Temperatures. M. ASTM B32 - Solder Metal. N. ASTM B88 - Seamless Copper Water Tube. O. ASTM B251 - Wrought Seamless Copper and Copper-Alloy Tube. P. ASTM C564 - Rubber Gaskets for Cast Iron Soil Pipe and Fittings. Q. AWWA C110 - Ductile - Iron and Gray - Iron Fittings 3 in. through 48 in., for Water and Other

Liquids. R. AWWA C111- Rubber-Gasket Joints for Ductile Iron and Gray-Iron Pressure Pipe and Fittings. S. AWWA C151 - Ductile-Iron Pipe, Centrifugally Cast in Metal Molds or Sand-Lined Molds, for Water

or Other Liquids. T. AWWA C651 - Disinfecting Water Mains. U. CISPI 301 - Cast Iron Soil Pipe and Fittings for Hubless Cast Iron Sanitary Systems. V. CISPI 310 - Joints for Hubless Cast Iron Sanitary Systems. W. NCPWB - Procedure Specifications for Pipe Welding. 1.4 SUBMITTALS A. Submit under provisions of Division 1.

Page 49: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING PIPING

SECTION 15410

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 11

B. Product Data: Provide data on pipe materials, pipe fittings, valves, and accessories. Provide manufacturers catalog information. Indicate valve data and ratings.

1.5 PROJECT RECORD DOCUMENTS A. Submit under provisions of Division 1. B. Record actual locations of valves. 1.6 OPERATION AND MAINTENANCE DATA A. Submit under provisions of Division 1. B. Maintenance Data: Include installation instructions, spare parts lists, exploded assembly views. 1.7 QUALITY ASSURANCE A. Valves: Manufacturer's name and pressure rating marked on valve body. B. Welding Materials and Procedures: Conform to ASME Code and applicable state labor

regulations. C. Welders Certification: In accordance with ASME Sec 9. D. Maintain one copy of each document on site. 1.8 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing the Products specified in this section with

minimum five years documented experience. B. Installer: Company specializing in performing the work of this section with minimum five years

documented experience. 1.9 REGULATORY REQUIREMENTS A. Perform Work in accordance with State of Connecticut Building Code and BOCA plumbing code. B. Conform to applicable codes for installation of backflow prevention devices. C. Provide certificate of compliance from authority having jurisdiction indicating approval of installation

of backflow prevention devices. 1.10 DELIVERY, STORAGE, AND HANDLING A. Deliver, store, protect and handle products to site under provisions of Division 1. B. Accept valves on site in shipping containers with labelling in place. Inspect for damage. C. Provide temporary protective coating on cast iron and steel valves.

Page 50: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING PIPING

SECTION 15410

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 11

D. Provide temporary end caps and closures on piping and fittings. Maintain in place until installation. E. Protect piping systems from entry of foreign materials by temporary covers, completing sections of

the work, and isolating parts of completed system. 1.11 ENVIRONMENTAL REQUIREMENTS A. Do not install underground piping when bedding are wet or frozen. 1.12 EXTRA MATERIALS A. Furnish under provisions of Division 1. B. Provide one repacking kit for each size valve. PART 2 - PRODUCTS 2.1 SANITARY SEWER PIPING, BURIED A. Cast Iron Pipe: ASTM A74 service weight. 1. Fittings: Cast iron. 2. Joints: Hub-and-spigot, compression type with ASTM C564 neoprene gaskets. 2.2 SANITARY SEWER PIPING, ABOVE GRADE A. Cast Iron Pipe: CISPI 301, hubless, service weight. 1. Fittings: Cast iron. 2. Joints: Neoprene gaskets and stainless steel clamp-and-shield assemblies. B. PVC pipe under 3" size may be ASTM D2665. 1. Fittings: PVC. 2. Joints: ASTM D2855, solvent weld with ASTM D2564 solvent cement. 2.3 SANITARY SEWER PIPING, FORCE MAIN A. Cast Iron (Ductile Iron) Cement Lined Pipe: 3" size and over, AWWA C151. 1. Fittings: (Ductile) iron, standard thickness. 2. Joints: AWWA C111, rubber basket with 3/4 inch (19 mm) diameter rods. 2.4 WATER PIPING, BURIED A. Copper tubing: under 3" size, ASTM B88, type K. 1. Fittings: (ASME B16.18, cast bronze or ASTM B16.22 wrought copper and bronze. 2. Joints: ASTM B32, solder, Grade 95TA. B. Cast Iron (Ductile Iron) Cement Lined Pipe: 3" size and over, AWWA C151. 1. Fittings: (Ductile) iron, standard thickness. 2. Joints: AWWA C111, rubber basket with 3/4 inch (19 mm) diameter rods.

Page 51: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING PIPING

SECTION 15410

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 5 of 11

2.5 WATER PIPING, ABOVE GRADE A. Copper Tubing: ASTM B88, Type L, hard drawn. 1. Fittings: ASME B16.18, cast bronze, or ASME B16.22, wrought copper and bronze. 2. Joints: ASTM B32, solder, Grade 95TA. 2.6 STORM WATER PIPING, BURIED A. Cast Iron Pipe: ASTM A74 service weight. 1. Fittings: Cast iron. 2. Joints: Hub-and-spigot, compression type ASTM C564, neoprene gasket system. 2.7 STORM WATER PIPING, ABOVE GRADE A. Cast Iron Pipe: CISPI 301, hubless, service weight. 1. Fittings: Cast iron. 2. Joints: Neoprene gaskets and stainless steel clamp-and-shield assemblies. 2.8 NATURAL GAS PIPING, BURIED A. Steel Pipe: ASTM A53 or A120, schedule 40 black. 1. Fittings: ASTM A234, forged steel welding type, with AWWA C105 polyethylene jacket or

double layer, half-lapped 10 mil polyethylene tape. 2. Joints: ANSI B31.1, welded. 2.9 NATURAL GAS PIPING, ABOVE GRADE A. Steel Pipe: ASTM A53 or A120, schedule 40 black. 1. Fittings: ASME B16.3, malleable iron screwed up to 3" size and ASTM A234, forged steel

welding type for sizes over 3". 2. Joints: NFPA 54, threaded or welded to ANSI B31.1. 2.10 UNIONS AND DIELECTRIC CONNECTIONS A. Unions for Pipe 3 Inches (50 mm) and Under: 1. Ferrous Piping: 150 psig (1034 kPa) malleable iron, threaded. 2. Copper Pipe: Bronze, soldered joints. B. Dielectric Connections: Union or flange with water impervious isolation barrier; Watts 3000 Series

or approved equal. 2.11 GATE VALVES A. Up To and Including 2 Inches (50 mm): 1. Manufacturers: a) NIBCO, Figure T-113 or S-113. b) Other acceptable manufacturers offering equivalent products include: (1) Watts. (2) Stockham.

Page 52: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING PIPING

SECTION 15410

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 6 of 11

2. Bronze body, bronze trim, screwed bonnet, non-rising stem, non-asbestos packing, handwheel, inside screw, solid wedge disc, Class 125, threaded or solder ends.

B. Over 2 Inches (50 mm): 1. Manufacturers: a) NIBCO, Figure F-619. b) Other acceptable manufacturers offering equivalent products include: (1) Watts. (2) Stockham. 2. Iron body, bronze trim, bolted bonnet, non-asbestos packing, non-rising stem, handwheel,

solid wedge disc with bronze seat rings, Class 125, flanged ends. 2.12 GLOBE VALVES A. Up To and Including 2 Inches (50 mm): 1. Manufacturers: a) NIBCO, Figure T-211 or S-211. b) Other acceptable manufacturers offering equivalent products include: (1) Watts. (2) Stockham. 2. Bronze body, bronze trim, screwed bonnet, non-asbestos packing, rising stem, handwheel,

inside screw, renewable composition disc and bronze seat, Class 125, threaded or solder ends.

2.13 BALL VALVES A. Up To and Including 2 Inches (50 mm): 1. Manufacturers: a) NIBCO, Model 580-70-66. b) Other acceptable manufacturers offering equivalent products include: (1) Watts. (2) Jamesbury. 2. Bronze two piece body, blowout-proof stem, stainless steel ball, teflon seats and packing,

lever handle, solder or threaded ends. Provide with full port thru 1" and conventional port in sizes over 1".

2.14 PRESSURE REDUCING VALVES A. PRV shall be rated to 175 PSI water working pressure and temperature range from 32 degrees F

to 180 degrees F. Minimum adjust range 120 psi - 60 psi. B. PRV shall be watts Series 2300 - Size 4" Direct Operated Water Pressure Regulator or equal as

approved by the New Britain Water Department. 2.15 SWING CHECK VALVES A. Up To and Including 2 Inches (50 mm): 1. Manufacturers: a) NIBCO, Figure T-413 or S-413. b) Other acceptable manufacturers offering equivalent products include: (1) Watts.

Page 53: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING PIPING

SECTION 15410

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 7 of 11

(2) Stockham. 2. Bronze body, bronze trim, bronze rotating swing disc, Buna-N seat disc, Class 125, threaded

or solder ends. B. Over 2 Inches (50 mm): 1. Manufacturers: a) NIBCO, Figure F-918. b) Other acceptable manufacturers offering equivalent products include: (1) Watts. (2) Stockham. 2. Iron body, bronze trim, cast bronze rotating swing disc, bolted bonnet, non-asbestos

gaskets, renewable disc and seat, Class 125, flanged ends. 2.16 TEMPERATURE AND PRESSURE RELIEF VALVES A. Manufacturers: 1. Watts 2. Other acceptable manufacturers offering equivalent products. a) ITT b) T&S Brass c) Zurn B. Bronze body, teflon seat, steel stem and springs,automatic, direct pressure actuated, capacities

ASME certified and labelled. PART 3 - EXECUTION 3.1 EXAMINATION A. Verify excavations under provisions of Division 1. B. Verify that excavations are to required grade, dry, and not over-excavated. 3.2 PREPARATION A. Ream pipe and tube ends. Remove burrs. B. Remove scale and dirt, on inside and outside, before assembly. C. Prepare piping connections to equipment with flanges or unions. 3.3 INSTALLATION A. Install in accordance with manufacturer's instructions. B. Use fittings for all changes in direction and branch connections. C. Install exposed piping at right angles or parallel to building walls. Diagonal runs are not permitted

unless expressly indicated.

Page 54: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING PIPING

SECTION 15410

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 8 of 11

D. Conceal all pipe installations in walls, pipe chases, utility spaces, above ceilings, below grade or floors, unless indicated to be exposed to view.

E. Exterior Wall Penetrations: Seal pipe penetrations through exterior walls with sleeves and

mechanical sleeve seals. Pipe sleeves smaller than 6 inches shall be galvanized steel pipe; pipe sleeves 6 inches and larger shall be galvanized steel sheet metal.

F. Fire Barrier Penetrations: Where pipes pass through fire rated walls, partitions, ceilings, and floors,

maintain the fire rated integrity. G. Install water piping with 1/32 inch per foot (1/4 percent) downward slope towards drain point. H. Provide non-conducting dielectric connections wherever jointing dissimilar metals. I. Route piping in orderly manner and maintain gradient. J. Install piping to conserve building space and not interfere with use of space. K. Group piping whenever practical at common elevations. L. Install piping to allow for expansion and contraction without stressing pipe, joints, or connected

equipment. M. Provide clearance for installation of insulation and access to valves and fittings. N. Provide access where valves and fittings are not exposed. O. Establish elevations of buried piping outside the building to ensure not less than three feet of cover

for drainage, four feet for domestic water and 18 inches for natural gas piping. P. Where pipe support members are welded to structural building framing, scrape, brush clean, and

apply one coat of zinc rich primer to welding. Q. Provide support for utility meters in accordance with requirements of utility companies. R. Prepare pipe, fittings, supports, and accessories not prefinished, ready for finish painting. S. Excavate in accordance with Division 2 and for work of this Section. T. Backfill in accordance with Division 2 for work of this Section. U. Install bell and spigot pipe with bell end upstream. V. Install valves with stems upright or horizontal, not inverted. 3.4 APPLICATION A. Use grooved mechanical couplings and fasteners only in accessible locations. B. Install unions downstream of valves and at equipment or apparatus connections.

Page 55: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING PIPING

SECTION 15410

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 9 of 11

C. Install brass male adapters each side of valves in copper piped system. Sweat solder adapters to

pipe. D. Install ball valves for shut-off and to isolate equipment, part of systems, or vertical risers. E. Install ball valves for throttling, bypass, or manual flow control services. F. Provide spring loaded check valves on discharge of water pumps. G. Provide flow controls in water recirculating systems where indicated. 3.5 ERECTION TOLERANCES A. Establish invert elevations, slopes for drainage to 1/8 inch per foot (one percent) minimum.

Maintain gradients. B. Slope water piping minimum 0.25 percent and arrange to drain at low points. 3.6 TABLES HANGER SPACING MAX. HORIZONTAL MAX. VERTICAL SPACING (ft) SPACING (FT)

Cast Iron pipe* 5 15

PVC pipe 4 4

Copper tubing (1-1/4 inch and smaller) 6 10

Copper tubing (1-1/2 inch and larger) 10 10

Steel pipe (gas 1 inch and larger) 12 12 * The maximum spacing of cast-iron pipe hangers shall be increased to 10 feet when 10-foot lengths of pipe are installed. 3.7 CLEANING AND FLUSHING A. Upon completion of all work, all piping systems shall be flushed with water/liquid alkaline solution

with emulsifying agents and detergents, to remove dirt, grease, grit, chips and foreign matter. B. Solutions for flushing shall be used in sufficient quantity to produce a velocity of at least 2.5 feet per

second. Flushing shall continue until discharge solution shows no discoloration or evidence of foreign materials.

C. During flushing operation, all valves shall be operated several times, bypasses opened, pumps

operated and equipment flushed.

Page 56: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING PIPING

SECTION 15410

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 10 of 11

D. Upon completion of flushing operations, all strainers, filters and blowdowns shall be removed and cleaned of accumulated waste.

3.8 TESTING A. All new piping systems installed under this contract shall be tested as prescribed hereinafter. B. All piping systems shall be left uncovered and unconcealed until tested and approved. Where such

work has been covered or concealed before tested and approved, it shall be exposed for testing. C. Contractor shall be responsible for furnishing all plugs, piping, valves, hoses, pumps and

equipment necessary for required tests and for proper disposal of the water upon completion of the tests. All systems shall be thoroughly cleaned before testing.

D. The drainage and vent systems shall be tested in accordance with BOCA National Plumbing Code.

Rough piping shall be tested by water or air and proved water-tight. Either of the following methods shall be used.

1. Water test: Subject to not less than 10 foot head of water. Keep water in system for a minimum of 15 minutes before inspection starts. The system shall than be tight at all points.

2. Air test: Subject to not less than gauge pressure of 5 pounds per square inch. The air pressure shall be held without introduction of additional air for a minimum period of 15 minutes.

E. Water piping shall be tested in accordance with BOCA National Plumbing Code. The system shall

be proved tight under a water pressure of 150 PSIG. The system shall be filled with water through a low connection point, care being taken to completely vent air so that no air pockets remain. The pressure shall be applied gradually and than held for a minimum of two hours. Care shall be taken to insure that at no point a dangerous overpressure is experienced. The hydrostatic test shall be considered satisfactory if no visible leakage, cracks or other signs of distress are discovered. Pressure drop other than that due to temperature change or similar reasons shall not be allowed. The water used for the test shall be obtained from a potable source of supply.

F. At completion of tests Contractor shall submit a typewritten log of test data for State's permanent

file including: 1. Data of test. 2. Section tested-attach sketch. 3. Equipment used. 4. Personnel involved. 5. State or State's witness in attendance. 6. Results. After repair any failed test shall be repeated until all requirements of this Section are met. 3.9 DISINFECTION OF DOMESTIC WATER PIPING SYSTEM A. Prior to starting work, verify system is complete, flushed and clean. B. Ensure PH of water to be treated is between 7.4 and 7.6 by adding alkali (caustic soda or soda

ash) or acid (hydrochloric).

Page 57: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING PIPING

SECTION 15410

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 11 of 11

C. Inject disinfectant, free chlorine in liquid, powder, tablet or gas form, throughout system to obtain 50 to 80 mg/L residual.

D. Bleed water from outlets to ensure distribution and test for disinfectant residual at minimum 15

percent of outlets. E. Maintain disinfectant in system for 24 hours. F. If final disinfectant residual tests less than 25 mg/L, repeat treatment. G. Flush disinfectant from system until residual equal to that of incoming water or 1.0 mg/L. H. Take samples no sooner than 24 hours after flushing, from 2 percent of outlets and from water

entry, and analyze in accordance with AWWA C651. 3.10 SERVICE CONNECTIONS A. Provide new sanitary and storm sewer services. Before commencing work check invert elevations

required for sewer connections, confirm inverts and ensure that these can be properly connected with slope for drainage and cover to avoid freezing.

B. Provide new water service complete with shut-off valve. 1. Provide 18 gage (1.20 mm) galvanized sheet metal sleeve around service main to 6 inch

(150 mm) above floor and 6 feet (1800 mm) minimum below grade. Size for minimum of 2 inches (50 mm) of loose batt insulation stuffing.

END OF SECTION

Page 58: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING SPECIALTIES

SECTION 15430

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 6

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Area drains. B. Floor drains. C. Cleanouts. D. Hose bibs. E. Backflow preventers. F. Water hammer arrestors. G. Trap Primers. H. Heating cable. 1.2 RELATED SECTIONS A. Section 15010 - Basic Mechanical Requirements. B. Section 15410 - Plumbing Piping. C. Section 15440 - Plumbing Fixtures. D. Section 15450 - Plumbing Equipment. E. Section 16010 - Basic Electrical Requirements. 1.3 REFERENCES A. ANSI/ASSE 1011 - Hose Connection Vacuum Breakers. B. ANSI/ASSE 1012 - Backflow Preventers with Immediate Atmospheric Vent. C. ANSI/ASSE 1013 - Backflow Preventers, Reduced Pressure Principle. D. ANSI/ASSE 1019 - Wall Hydrants, Frost Proof Automatic Draining Anti-Backflow Types. E. ANSI A112.21.1 - Floor Drains. F. ANSI A112.26.1 - Water Hammer Arrestors. G. AWWA C506 - Backflow Prevention Devices - Reduced Pressure Principle and Double Check

Valve Types.

Page 59: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING SPECIALTIES

SECTION 15430

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 6

H. PDI WH-201 Water Hammer Arresters. 1.4 SUBMITTALS A. Submit under provisions of Division 1. B. Shop Drawings: Indicate dimensions, weights, and placement of openings and holes. C. Product Data: Provide component sizes, rough-in requirements, service sizes, and finishes. D. Manufacturer's Installation Instructions: Indicate assembly and support requirements. 1.5 PROJECT RECORD DOCUMENTS A. Submit under provisions of Division 1. B. Record actual locations of equipment, cleanouts, backflow preventers and valves. 1.6 OPERATION AND MAINTENANCE DATA A. Submit under provisions of Division 1. B. Maintenance Data: Include installation instructions, spare parts lists, exploded assembly views. 1.7 DELIVERY, STORAGE, AND HANDLING A. Deliver, store, protect and handle products to site under provisions of Division 1. B. Accept specialties on site in original factory packaging. Inspect for damage. 1.8 EXTRA MATERIALS A. Furnish under provisions of Division 1. PART 2 - PRODUCTS 2.1 AREA DRAINS A. Manufacturers: 1. J R Smith 2. Other acceptable manufacturers offering equivalent products. a) Zurn b) Jonespec c) Wade B. Deck Drains (AD-1): ANSI A112.21.2. 1. Body: Lacquered cast iron. 2. Collar and Grate: Lacquered cast iron. 3. Accessories: 2" extension sleeve, adjustable under deck clamp and sump receiver.

Page 60: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING SPECIALTIES

SECTION 15430

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 6

4. Model: SQ-1-48 manufactured by J R Smith. C. Deck Drains (AD-2): ANSI A112.21.2. 1. Body: Lacquered cast iron. 2. Collar and Dome: Polyethylene dome and stainless steel mesh screen. 3. Collar and Grate: Lacquered cast iron. 4. Model: 2675Y manufactured by J R Smith. 2.2 FLOOR DRAINS A. Manufacturers: 1. J R Smith 2. Other acceptable manufacturers offering equivalent products. a) Zurn b) Jonespec c) Wade B. FD-1: ANSI A112.21.1; lacquered cast iron body with flashing collar with nickel bronze adjustable

strainer head and top grate; Model 2005-A manufactured by J. R. Smith. C. FD-2: ANSI A112.21.1; lacquered cast iron body with flashing collar with cast iron tractor grate and

solid freestanding sediment bucket; Model 2142 manufactured by J R Smith. D. FS: ANSI A112.21.1; cast iron body with dome strainer, acid resistant coated interior and 1/2

grate; Model 3410 manufactured by J R Smith. 2.3 CLEANOUTS A. Manufacturers: 1. J R Smith 2. Other acceptable manufacturers offering equivalent products. a) Zurn b) Jonespec c) Wade B. Interior Finished Floor Areas: Lacquered cast iron body with square adjustable scoriated secured

nickel bronze top, and vandal proof screws; Model 4040 manufactured by J R Smith. C. Interior Finished Wall Areas: Line type with lacquered cast iron body and round epoxy coated

gasketed cover, and round stainless steel access cover secured with machine screw; Model 4422 manufactured by J R Smith.

D. Interior Unfinished Floor Areas: Lacquered cast iron body with round adjustable scoriated secured

cast iron top; Model 4231 manufactured by J R Smith. 2.4 HOSE BIBS A. Manufacturers: 1. Watts

Page 61: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING SPECIALTIES

SECTION 15430

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 6

2. Other acceptable manufacturers offering equivalent products. a) Zurn b) NIBCO c) Woodford B. Interior: Brass with hose thread spout, handwheel, integral vacuum breaker in conformance with

ANSI/ASSE 1011. C. Freezeless-Exterior: Brass with chrome finish, hose thread spout, Tee-key operator, integral

vacuum breaker-backflow preventer, automatic draining in conformance with ASSE 1019. Woodford Model B65.

2.5 BACKFLOW PREVENTERS A. Manufacturers: 1. Watts 2. Other acceptable manufacturers offering equivalent products. a) Beeco b) Hersey c) Cla-Val d) Grinnell e) Zurn f) Febco B. Reduced Pressure Backflow Preventers: ANSI/ASSE 1013, AWWA C506; bronze body; two

independently operating, spring loaded check valves; diaphragm type differential pressure relief valve located between check valves; assembled with two non-rising stem gate valves, strainer, and test cocks; Model 909 manufactured by Watts.

C. Air Vent Type Backflow Preventer: ASSE 1012, bronze body, stainless steel internal parts, built in

strainer, primary and secondary check valves, and drain and vent connection; Model 9D manufactured by Watts.

2.6 WATER HAMMER ARRESTORS A. Manufacturers: 1. PPP, Model WH-201 2. Other acceptable manufacturers offering equivalent products. a) J R Smith b) Amtrol c) Josam d) Tyler B. ANSI A112.26.1; sized in accordance with PDI WH-201, precharged suitable for operation in

temperature range -100 to 300 degrees F (-73 to 149 degrees C) and maximum 250 psig (1700 kPa) working pressure.

2.7 TRAP PRIMERS

Page 62: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING SPECIALTIES

SECTION 15430

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 5 of 6

A. Manufacturers: 1. PPP 2. Other acceptable manufacturers offering equivalent products. a) Zurn b) Watts B. Brass construction, integral backflow preventer, automatically activated, to prime traps through a

trap primer distribution unit, when a valve or faucet is opened. Provide with distribution units. 2.8 HEATING CABLE A. Manufacturers: 1. BriskHeat Model SL-CAB-5 2. Other acceptable manufacturers offering equivalent products. a) EasyHeat b) Smith-Gates B. Heating Cable: Self-limiting, parallel resistance heating cable. Provide with Ambient Sensing

adjustable bulb and capillary temperature controller with a range of 20F-110F, Model TB261N. C. Rating: 120V, 5 W/lineal ft. PART 3 - EXECUTION 3.1 PREPARATION A. Coordinate cutting and forming of deck and floor construction to receive drains to required invert

elevations. 3.2 INSTALLATION A. Install in accordance with manufacturer's instructions. B. Extend cleanouts to finished floor or wall surface. Lubricate threaded cleanout plugs with mixture of

graphite and linseed oil. Ensure clearance at cleanout for rodding of drainage system. Cleanouts on 6-inch and smaller pipes shall have a clearance of not less than 18 inches for rodding. Cleanouts on 8-inch and larger pipes shall have a clearance of not less than 36 inches for rodding.

C. Cleanouts shall be of the same size as the pipes served, up to 4 inches; 5 and 6 inch pipes shall

have 4 inch cleanouts; 8 inch pipes shall have 6 inch cleanouts; 10 inch and larger pipes shall have 8 inch cleanouts.

D. Encase exterior cleanouts in concrete flush with grade. E. Pipe relief from back flow preventer through wall. F. Install water hammer arrestors complete with accessible isolation valve on hot and cold water

supply piping to lavatories and sinks.

Page 63: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 PLUMBING SPECIALTIES

SECTION 15430

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 6 of 6

G. Install wall hose bibs within single brick course. H. Install trap primers with distribution units and pipe to floor drain traps. 3.2 HEATING CABLE INSTALLATION A. Verify that piping is ready to receive work. B. Verify that required utilities are available, in proper location, and ready for use. A. Beginning of installation means installer accepts conditions. B. Install in accordance with manufacturer's instructions. C. Bending Radius: Six times cable diameter, minimum. D. Avoid pinching and making sharp bends in cable. E. Prevent damage by sharp metal or other objects during installation. F. Do not install heating cable across expansion or construction joints. G. Test continuity of heating cable. H. Measure insulation resistance to manufacturer's recommended values. Use test instruments in

accordance with manufacturer's instructions. I. Perform continuity and insulation resistance test on completed cable installation. For cables

embedded in concrete, perform tests immediately before and after concrete placement. J. Measure voltage and current at each unit. K. Submit written test report showing values measured on each test for each cable. END OF SECTION

Page 64: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK

SECTION 15890

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 6

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Metal ductwork. B. Non-metal ductwork. C. Duct cleaning. 1.2 RELATED SECTIONS A. Section 07270 - Fire Stopping. B. Division 9 - Finishes for Painting. C. Section 15140 - Supports and Anchors: Sleeves. D. Section 15290 - Duct Insulation. E. Section 15910 - Ductwork Accessories. F. Section 15940 - Air Inlets and Outlets. G. Section 15990 - Testing, Adjusting and Balancing. 1.3 REFERENCES A. ASTM A36 - Structural Steel. B. ASTM A90 - Weight of Coating on Zinc-Coated (Galvanized) Iron or Steel Articles. C. ASTM A167 - Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip. D. ASTM A366 - Steel, Sheet, Carbon, Cold Rolled, Commercial Quality. E. ASTM A480 - General Requirements for Flat-Rolled Stainless and Heat-Resisting Steel Plate,

Sheet, and Strip. F. ASTM A525 - General Requirements for Steel Sheet, Zinc- Coated (Galvanized) by the Hot-Dip

Process. G. ASTM A527 - Steel Sheet, Zinc-Coated (Galvanized) by Hot-Dip Process, Lock Forming Quality. H. ASTM A568 - Steel, Sheet, Carbon, and High-Strength, Low-Alloy, Hot-Rolled and Cold-Rolled. I. ASTM A569 - Steel, Carbon (0.15 Maximum, Percent), Hot-Rolled Sheet and Strip, Commercial

Quality.

Page 65: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK

SECTION 15890

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 6

J. ASTM B209 - Aluminum and Aluminum-Alloy Sheet and Plate. K. AWS D9.1 - Welding of Sheet Metal. L. NFPA 90A - Installation of Air Conditioning and Ventilating Systems. M. NFPA 90B - Installation of Warm Air Heating and Air Conditioning Systems. N. NFPA 91 - Installation of Blower and Exhaust Systems for Dust, Stock and Vapor Removal or

Conveying. O. SMACNA - HVAC Air Duct Leakage Test Manual. P. SMACNA - HVAC Duct Construction Standards - Metal and Flexible. Q. UL 181 - Factory-Made Air Ducts and Connectors. 1.4 PERFORMANCE REQUIREMENTS A. No variation of duct configuration or sizes permitted except by written permission. Size round

ducts installed in place of rectangular ducts in accordance with ASHRAE table of equivalent rectangular and round ducts.

1.5 SUBMITTALS A. Submit under provisions of Division 1. B. Sheet Metal Shop Drawings: Provide drawings at minimum 1/4" = 1'-0" scale indicating duct

fittings, gages, sizes, welds, and configuration prior to start of work. C. Product Data: Provide data for manufactured ductwork and flexible ducts. D. Test Reports: Indicate pressure tests performed. Include date, section tested, test pressure, and

leakage rate, following SMACNA HVAC Air Duct Leakage Test Manual. E. Manufacturers installation instructions. 1.6 PROJECT RECORD DOCUMENTS A. Submit under provisions of Division 1. B. Record actual locations of ducts and duct fittings. Record changes in fitting location and type.

Show additional fittings used. 1.7 QUALITY ASSURANCE

Page 66: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK

SECTION 15890

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 6

A. Perform Work in accordance with SMACNA - HVAC Duct Construction Standards - Metal and Flexible.

1.8 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing the Products specified in this section with

minimum three years documented experience. B. Installer: Company specializing in performing the work of this section with minimum three years

documented experience. 1.9 ENVIRONMENTAL REQUIREMENTS A. Do not install duct sealants when temperatures are less than those recommended by sealant

manufacturers. B. Maintain temperatures during and after installation of duct sealants. PART 2 - PRODUCTS 2.1 MATERIALS A. Rectangular Galvanized Steel Ducts: ASTM A525 and ASTM A527 galvanized steel sheet,

lock-forming quality, having G60 zinc coating in conformance with ASTM A90. B. Round Galvanized Steel Ducts and Fittings: 1. Manufacturers: a) SEMCO Type SS (85). b) Other acceptable manufacturers offering equivalent products include: 1. United McGill. 2. Quickdraft. 2. ASTM A527 galvanized steel sheet, spiral lock seam construction, with G60 zinc coating in

conformance with ASTM A90. C. Aluminum Ducts: ASTM B209; aluminum sheet, alloy 3003-H14. Aluminum Connectors and Bar

Stock: Alloy 6061-T6 or of equivalent strength. D. Insulated Flexible Ducts: 1. Manufacturers: a) Thermaflex Model M-KF. b) Other acceptable manufacturers offering equivalent products include: 1. Technaflex. 2. Tuttle and Bailey. 2. UL 181, Class 1, CPE inner liner bonded to helically wound spring steel wire; fiberglass

insulation; metalized polyester vapor barrier film; complying with NFPA 90A and NFPA 90B. 3. Pressure Rating: 10 inches WG (2.50 kPa) positive and 1.0 inches WG (250 Pa) negative. 4. Maximum Velocity: 4000 fpm (20.3 m/sec). 5. Thermal Conductance: 0.23 BTU/hr/s.f./deg F maximum.

Page 67: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK

SECTION 15890

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 6

6. Insulation: 1 1/2" thick; 3/4 lb.density. 7. Temperature Range: -20 degrees F to 250 degrees F (-28 degrees C to 121 degrees C). E. Fasteners: Rivets, bolts, or sheet metal screws. F. Sealant: Non-hardening, water resistant, fire resistive, compatible with mating materials; liquid

used alone or with tape, or heavy mastic. G. Hanger Rod: ASTM A36; steel; threaded both ends, threaded one end, or continuously threaded. 2.2 METAL DUCTWORK FABRICATION A. Fabricate and support in accordance with standards scheduled at Part 3 - EXECUTION. Provide

duct material, gages, reinforcing, and sealing for static pressures classifications listed in Part 3 -EXECUTION. Exposed duct in occupied spaces shall be minimum 16 ga. galvanized steel or equivalent aluminum construction.

B. Construct T's, bends, and elbows with radius of not less than 1-1/2 times width of duct on

centerline. Where not possible and where rectangular elbows are used, provide double bladed air foil turning vanes. Where acoustical lining is indicated, provide turning vanes of perforated metal with glass fiber insulation.

C. Increase duct sizes gradually, not exceeding 15 degrees divergence wherever possible; maximum

30 degrees divergence upstream of equipment and 45 degrees convergence downstream. D. Fabricate continuously welded round and oval duct fittings two gages heavier than duct gages

indicated in SMACNA Standard. Joints shall be minimum 4 inch (100 mm) cemented slip joint, brazed or electric welded. Prime coat welded joints.

E. Provide standard 45 degree lateral wye takeoffs unless otherwise indicated where 90 degree

conical tee connections may be used. 2.3 MANUFACTURED DUCTWORK AND FITTINGS A. Manufacture in accordance with SMACNA HVAC Duct Construction Standards - Metal and

Flexible, and as indicated. Provide duct material, gages, reinforcing, and sealing for static pressures classifications listed in Part 3 - EXECUTION.

PART 3 - EXECUTION 3.1 INSTALLATION A. Install in accordance with manufacturer's instructions. B. Install and seal ducts in accordance with SMACNA HVAC Duct Construction Standards - Metal

and Flexible. C. Duct Sizes are inside clear dimensions. For lined ducts, maintain sizes inside lining.

Page 68: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK

SECTION 15890

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 5 of 6

D. Provide openings in ductwork where required to accommodate control devices. Provide pilot tube

openings where required for testing of systems, complete with metal can with spring device or screw to ensure against air leakage. Where openings are provided in insulated ductwork, install insulation material inside a metal ring.

E. Locate ducts with sufficient space around equipment to allow normal operating and maintenance

activities. F. Use double nuts and lock washers on threaded rod supports. G. Locate ducts, except as otherwise indicated, vertically and horizontally, parallel and perpendicular

to building lines; avoid diagonal runs. Install duct systems in shortest route that does not obstruct usable space or block access for servicing building and its equipment.

H. Conceal ducts from view in finished and occupied spaces by locating in mechanical shafts, hollow

wall construction, or above suspended ceilings. Do not encase horizontal runs in solid partitions, except as specifically shown.

I. Coordinate layout with suspended ceiling and lighting layouts and similar finish work. J. Connect diffusers to low pressure ducts with 8 feet (1.5 m) maximum length of flexible duct held in

place with strap or clamp. K. Connect return and exhaust grilles directly to ductwork. Flexible duct shall not be allowed. L. Connect flexible ducts to metal ducts with draw bands plus adhesive. M. During construction provide temporary closures of metal or taped polyethylene on open ductwork to

prevent construction dust from entering ductwork system. 3.2 CLEANING A. Clean work under provisions of Division 1. B. Clean duct system and force air at high velocity through duct to remove accumulated dust. To

obtain sufficient air, clean half the system at a time. Protect equipment which may be harmed by excessive dirt with temporary filters, or bypass during cleaning.

C. Clean duct systems with high power vacuum machines. Protect equipment which may be harmed

by excessive dirt with filters, or bypass during cleaning. Provide adequate access into ductwork for cleaning purposes.

3.3 SCHEDULES A. Ductwork Material Schedule: Air System Material

Page 69: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK

SECTION 15890

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 6 of 6

Supply air, Return air, Galvanized Steel General and Toilet exhaust Outside Air Intake Galvanized Steel Locker Room Supply/Return/Exhaust Aluminum B. Ductwork Pressure Class Schedule: Air System Pressure Class Supply, AHU-1 & 3 2 inch (250 Pa) Supply, AHU-2 & 4 1 inch (250 Pa) Return/Outside Air Intake 1 inch (125 Pa) Exhaust, EF-4 1 inch (125 Pa) Exhaust, EF-1, 2, 3, 5, 6, 7 & 8 1/2 inch (125 Pa) C. Construction Standards Schedule: Air System Construction Standard Supply air, Return air, SMACNA - HVAC Duct Outside air, Exhaust air. Construction Standards Metal and Flexible. END OF SECTION

Page 70: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK ACCESSORIES

SECTION 15910

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 6

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Backdraft dampers. B. Duct access doors. C. Combination fire and smoke dampers. D. Counterbalanced dampers. E. Duct test holes. F. Fire dampers. G. Volume control dampers. H. Flexible duct connections. 1.2 RELATED SECTIONS A. Section 15290 - Ductwork Insulation. B. Section 15890 - Ductwork. 1.3 REFERENCES A. NFPA 90A - Installation of Air Conditioning and Ventilating Systems. B. NFPA 92A - Smoke Control Systems. C. NFPA 70 - National Electrical Code. D. SMACNA - HVAC Duct Construction Standards - Metal and Flexible. E. SMACNA - Fire, Smoke and Radiation Damper Installation Guide for HVAC Systems. F. UL 33 - Heat Responsive Links for Fire-Protection Service. G. UL 555 - Fire Dampers and Ceiling Dampers. H. UL 555S - Leakage Rated Dampers for Use in Smoke Control Systems. 1.4 SUBMITTALS A. Submit under provisions of Division 1. B. Shop Drawings: Indicate dimensions, required clearances and construction details for dampers.

Page 71: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK ACCESSORIES

SECTION 15910

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 6

C. Product Data: 1. For counterbalanced and backdraft dampers indicate pressure drop and minimum static

pressure required to open. 2. For combination fire and smoke dampers indicate fusible link rating, UL listing and electrical

characteristics. 3. For fire dampers indicate fusible link rating and UL listing. D. Manufacturer's Installation Instructions. 1.5 PROJECT RECORD DOCUMENTS A. Submit under provisions of Division 1. B. Record actual locations of dampers, access doors and test holes. 1.6 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing the Products specified in this section with

minimum three years documented experience. 1.7 REGULATORY REQUIREMENTS A. Products Requiring Electrical Connection: Listed and classified by Underwriters' Laboratories Inc.,

as suitable for the purpose specified and indicated. 1.8 DELIVERY, STORAGE, AND HANDLING A. Deliver, store, protect and handle products to site under provisions of Division 1. B. Protect dampers from damage to operating linkages and blades. PART 2 - PRODUCTS 2.1 COUNTERBALANCED DAMPERS. A. Manufacturers: 1. Ruskin Model CBD4. 2. Other acceptable manufacturers offering equivalent products include: a) Air Balance b) Greenheck B. Counterbalance Weights: Adjustable from .01" to .05" WG. C. Multi-Blade, Parallel Action Gravity Balanced Backdraft Dampers: Extruded aluminum frame

minimum .07" thick with extruded aluminum blades of maximum 6 inch (150 mm) width, with extruded vinyl edge seals, linked together in rattle-free manner with 90 degree stop.

2.2 BACKDRAFT DAMPERS

Page 72: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK ACCESSORIES

SECTION 15910

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 6

A. Manufacturers: 1. Ruskin Model BD6. 2. Other acceptable manufacturers offering equivalent products include: a) Air Balance b) Greenheck B. Multi-Blade, Parallel Action Gravity Balanced Backdraft Dampers: Extruded aluminum frame

minimum .125" thick with extruded aluminum blades minimum .07" thick with extruded vinyl edge seals. Blades shall be maximum 6 inch (150 mm) wide, linked together in rattle-free manner with 90 degree stop.

2.3 DUCT ACCESS DOORS A. Manufacturers: 1. Ruskin. 2. Air Balance. 3. Greenheck. B. Fabricate in accordance with SMACNA HVAC Duct Construction Standards - Metal and Flexible,

and as indicated. C. Fabrication: Rigid and close-fitting of galvanized steel with sealing gaskets and quick fastening

locking devices. For insulated ductwork, install minimum one inch (25 mm) thick insulation with sheet metal cover.

1. Less Than 12 Inches (300 mm) Square: Secure with sash locks. 2. Up to 18 Inches (450 mm) Square: Provide two hinges or continuous hinge and two sash

locks. 3. Up to 24 x 48 Inches (600 x 1200 mm): Three hinges or continuous hinge and two

compression latches with outside and inside handles. 4. Larger Sizes: Provide an additional hinge. D. Access doors with sheet metal screw fasteners are not acceptable. 2.4 DUCT TEST HOLES A. Temporary Test Holes: Cut or drill in ducts as required. Cap with neat patches, neoprene plugs,

threaded plugs, or threaded or twist-on metal caps. B. Permanent Test Holes: Factory fabricated, air tight flanged fittings with screw cap. Provide

extended neck fittings to clear insulation. 2.5 COMBINATION FIRE AND SMOKE DAMPERS A. Manufacturers: 1. Ruskin Model FSD60. 2. Other acceptable manufacturers offering equivalent products include: a) Air Balance. b) Greenheck.

Page 73: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK ACCESSORIES

SECTION 15910

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 6

c) Prefco. B. Fabricate in accordance with NFPA 90A, UL 555, UL 555S, and as indicated. C. Provide factory sleeve, minimum 20 gage, and collar for each damper. D. Multiple Blade Dampers: Fabricate with minimum 16 gage (1.5 mm) galvanized steel frame and

airfoil-shaped blades, stainless steel sleeve bearings and plated steel axles, stainless steel jamb seals, concealed linkage, stainless steel closure spring, blade stops, and lock, and 1/2 inch (12.7 mm) actuator shaft.

E. Operators: UL listed and labelled spring return electric type suitable for 120 volts, single phase, 60

Hz. Locate damper operator on exterior of duct and link to damper operating shaft. F. Damper shall have 1 1/2 hour fire rating. G. Fusible link: Set to melt at 165 degrees F (74 degrees C). 2.6 FIRE DAMPERS A. Manufacturers: 1. Ruskin models noted below. 2. Other acceptable manufacturers offering equivalent products include: a) Air Balance. b) Greenheck. B. Fabricate in accordance with NFPA 90A and UL 555, and as indicated. C. Ceiling Dampers: Galvanized steel, minimum 22 gage (0.76 mm) frame and 22 gage (0.76 mm)

insulated blades. Provide with adjustable air flow balancing device and thermal insulation blanket for diffusers. Dampers shall be Ruskin Model CFD.

D. Curtain Type Dampers: Galvanized steel minimum 22 gage (0.76 mm) frame and interlocking

blades. Provide stainless steel closure springs and latches for horizontal installations. Damper shall be Ruskin Model IBD.

E. Multiple Blade Dampers: 16 gage (1.5 mm) galvanized steel frame and blades, oil-impregnated

bronze or stainless steel sleeve bearings and plated steel axles, 1/8 x 1/2 inch (3.2 x 12.7 mm) plated steel concealed linkage, stainless steel closure spring, blade stops, and lock. Damper shall be Ruskin Model FD31.

F. Fusible Links: UL 33, separate at 165 degrees F (74 degrees C). G. Fire rating of dampers shall be 1 1/2 hour unless noted otherwise on the drawings. 2.7 VOLUME CONTROL DAMPERS A. Manufacturers: 1. Ruskin models listed below.

Page 74: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK ACCESSORIES

SECTION 15910

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 5 of 6

2. Other acceptable manufacturers offering equivalent products include: a) Air Balance. b) Greenheck. B. Fabricate in accordance with SMACNA HVAC Duct Construction Standards - Metal and Flexible,

and as indicated. C. Single Blade Dampers: For duct sizes up to 6 x 30 inch (150 x 760 mm) with minimum 20 gage

frame and blade and nylon bearings. Dampers shall be Ruskin Model MD25 and MDR525. D. Multi-Blade Damper: Fabricate of opposed blade pattern with maximum blade sizes 8 x 48 inch

(200 x 1200 mm). Provide with minimum 16 gage frame and blades and molded synthetic bearings. Dampers shall be Ruskin Model MD35.

E. Quadrants: 1. Provide locking, indicating quadrant regulators on single and multi-blade dampers. 2. On insulated ducts mount quadrant regulators on stand-off mounting brackets, bases, or

adapters. 2.8 FLEXIBLE DUCT CONNECTIONS A. Fabricate in accordance with SMACNA HVAC Duct Construction Standards - Metal and Flexible,

and as indicated. B. Connector: Fabric crimped into metal edging strip. 1. Fabric: UL listed fire-retardant neoprene coated woven glass fiber fabric to NFPA 90A,

minimum density 30 oz per sq yd (1.0 kg/sq m). 2. Net Fabric Width: Approximately 3 inches (75 mm) wide. 3. Metal: 3 inch (75 mm) wide, 24 gage (0.6 mm thick) galvanized steel. PART 3 - EXECUTION 3.1 INSTALLATION A. Install equipment in accordance with manufacturer's instructions, NFPA 90A, and SMACNA

publications and guidelines. Refer to Section 15890 for duct construction and pressure class. B. Provide backdraft dampers on all exhaust fans where damper is not provided as an accessory to

the fan and where shown on the drawings. C. Provide duct access doors for inspection and cleaning before and after manual dampers, control

dampers, fire dampers and where shown on the drawings. Minimum door size shall be 12 x 12 inches (250 x 300 mm) except where limited by duct size.

D. Provide duct test holes where indicated and required for testing and balancing purposes. E. Provide fire dampers and combination fire and smoke dampers at locations indicated, and where

ducts and outlets pass through fire rated components. Install with required perimeter mounting

Page 75: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 DUCTWORK ACCESSORIES

SECTION 15910

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 6 of 6

angles, sleeves, breakaway duct connections, corrosion resistant springs, bearings, bushings and hinges.

F. Install combination fire and smoke dampers in accordance with NFPA 92A. G. Demonstrate re-setting of fire dampers to Owner's representative. H. Provide balancing dampers at points on supply, return, outside air and exhaust systems where

branches are taken from larger ducts as required for air balancing and where shown on the drawings. Install minimum 2 duct widths from duct take-off.

I. Provide balancing dampers on duct take-off to diffusers, grilles, and registers, regardless of

whether dampers are specified as part of the diffuser, grille, or register assembly. J. Provide flexible connections immediately adjacent to equipment in ducts associated with fans and

motorized equipment and supported by vibration isolators. Refer to Section 15246. END OF SECTION

Page 76: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 AIR OUTLETS AND INLETS

SECTION 15940

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 4

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Diffusers. B. Registers. C. Grilles. 1.2 RELATED SECTIONS A. Division 9 - Finishes for Painting. B. Section 15890 - Ductwork. C. Section 15910 - Ductwork Accessories. 1.3 REFERENCES A. ADC 1062 - Certification, Rating and Test Manual. B. AMCA 500 - Test Method for Louvers, Dampers and Shutters. C. ARI 650 - Air Outlets and Inlets. D. ASHRAE 70 - Method of Testing for Rating the Air Flow Performance of Outlets and Inlets. E. SMACNA - HVAC Duct Construction Standard - Metal and Flexible. F. NFPA 70 - National Electrical Code. G. NFPA 90A - Installation of Air Conditioning and Ventilating Systems. 1.4 SUBMITTALS A. Submit under provisions of Division 1. B. Product Data: Provide data for equipment required for this project. Review outlets and inlets as to

size, finish, and type of mounting prior to submission. Submit schedule of outlets and inlets showing type, size, location, application, and noise level.

C. Samples: Submit two of each required air outlet and inlet type. 1.5 PROJECT RECORD DOCUMENTS A. Submit under provisions of Division 1. B. Record actual locations of air outlets and inlets.

Page 77: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 AIR OUTLETS AND INLETS

SECTION 15940

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 4

1.6 QUALITY ASSURANCE A. Test and rate air outlet and inlet performance in accordance with ADC Equipment Test Code 1062

and ASHRAE 70. 1.7 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing the Products specified in this section with

minimum three years documented experience. PART 2 - PRODUCTS 2.1 GENERAL A. For all diffusers, grilles and registers, Noise Criteria (NC) shall not exceed 30 unless noted

otherwise on drawings. NC rating shall be for diffuser/neck assembly. B. For schedule of sizes, airflows, etc. refer to schedule on the drawings. 2.2 SQUARE CEILING DIFFUSERS; SCHEDULED TYPES A THRU D A. Manufacturers: 1. Titus Model TMSA. 2. Other acceptable manufacturers offering equivalent products: a) Metal Aire. b) Carnes Co. B. Type: Square, adjustable pattern, stamped, multi-core, multi-louvered diffuser to discharge air in

360 degree pattern with removable inner core and round neck. C. Frame: Compatible with ceiling to be mounted in. D. Fabrication: Steel with baked enamel off-white finish. E. Accessories: Model AG-75 opposed blade damper for round neck with damper adjustable from

diffuser face without removing inner core. 2.3 RECTANGULAR CEILING DIFFUSERS; SCHEDULED TYPES E THRU H & R A. Manufacturers: 1. Titus Model TDCA. 2. Other acceptable manufacturers offering equivalent products: a) Metal Aire. b) Carnes Co. B. Type: Rectangular, adjustable pattern, stamped, multi-core, multi-louvered diffuser to discharge

air in 360 degree pattern with removable inner core.

Page 78: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 AIR OUTLETS AND INLETS

SECTION 15940

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 4

C. Frame: Compatible with ceiling to be mounted in. D. Fabrication: Steel with baked enamel off-white finish. E. Accessories: Model AG-95 opposed blade damper with damper adjustable from diffuser face. 2.4 SUPPLY REGISTERS; SCHEDULED TYPES I THRU L A. Manufacturers: 1. Titus Model 272RS. 2. Other acceptable manufacturers offering equivalent products: a) Metal Aire. b) Carnes Co. B. Type: Streamlined and individually adjustable blades, 3/4 inch (19 mm) deep, 3/4 inch (19 mm)

maximum spacing with friction pivots at both ends to set blades, vertical face, double deflection. C. Frame: Compatible with ceiling to be mounted in. D. Fabrication: 20 gage (0.90 mm) minimum steel frames and aluminum extruded airfoil type blades

with factory off-white enamel finish. E. Damper: Model AG-35-AA aluminum, integral, gang-operated opposed blade type with removable

key operator, operable from face. 2.5 EXHAUST AND RETURN REGISTERS; SCHEDULED TYPE M A. Manufacturers: 1. Titus Model 23RL. 2. Other acceptable manufacturers offering equivalent products: a) Metal Aire. b) Carnes Co. B. Type: Streamlined fixes blades parallel to the long dimension, 3/4 inch spacing (19 mm), 3/4 inch

deep. C. Frame: Compatible with ceiling to be mounted in. Fasteners shall be Type C concealed screw

type. D. Fabrication: 20 gauge (0.90 mm) steel frame with aluminum extruded airfoil type blades. Finish

shall be factory off-white enamel. E. Damper: Model AG-35 steel, integral, gang-operated, opposed blade type with removable key

operator, operable from face. 2.6 EXHAUST, TRANSFER AND RETURN GRILLES; SCHEDULED TYPES N THRU Q A. Manufacturers: 1. Titus Model 50F.

Page 79: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 15 AIR OUTLETS AND INLETS

SECTION 15940

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 4

2. Other acceptable manufacturers offering equivalent products: a) Metal Aire. b) Carnes Co. B. Type: Fixed 1/2 x 1/2 x 1/2 inch (13 x 13 x 13 mm) aluminum core. C. Frame: Compatible with ceiling to be mounted in. D. Fabrication: Aluminum with factory off-white enamel finish. E. Damper: Model AG-35-AA aluminum, integral, gang-operated, opposed blade type with removable

key operator, operable from face. PART 3 - EXECUTION 3.1 INSTALLATION A. Install in accordance with manufacturer's instructions. B. Check location of outlets and inlets and make necessary adjustments in position to conform with

architectural features, symmetry, and lighting arrangement. C. Install diffusers to ductwork with air tight connection. D. Provide balancing dampers on duct take-off to each air inlet or outlet, despite whether dampers are

specified as part of the air inlet or outlet assembly. E. Paint ductwork visible behind air outlets and inlets matte black. Refer to Division 9 - Finishes for

Painting. END OF SECTION

Page 80: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 CONDUIT

SECTION 16111

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 5

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Metal conduit. B. Flexible metal conduit. C. Liquid-tight flexible metal conduit. D. Electrical metallic tubing. E. Non-metallic conduit. F. Fittings and conduit bodies. 1.2 RELATED SECTIONS A. Section 07270 - Fire Stopping. B. Section 15246 - Vibration Isolation and Seismic Restraints. C. Section 16118 - Underground Duct Bank. D. Section 16130 - Boxes. E. Section 16170 - Grounding and Bonding. F. Section 16190 - Supporting Devices. G. Section 16195 - Electrical Identification. 1.3 REFERENCES A. ANSI C80.1 - Rigid Steel Conduit, Zinc Coated. B. ANSI C80.3 - Electrical Metallic Tubing, Zinc Coated. C. ANSI C80.6 - Intermediate Metal Conduit, Zinc Coated. D. ANSI/NEMA FB 1 - Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit and Cable

Assemblies. E. ANSI/NFPA 70 - National Electrical Code. F. UL 360 - Liquid-tight Flexible Metal Conduit and Fittings. G. NECA "Standard of Installation." H. NEMA TC-2 and UL 651 - Electrical Plastic Tubing (EPT) and Conduit (Schedule 40 and 80 PVC).

Page 81: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 CONDUIT

SECTION 16111

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 5

I. NEMA TC-3 - PVC Fittings for Use with Rigid PVC Conduit and Tubing. 1.4 DESIGN REQUIREMENTS A. Conduit Size: ANSI/NFPA 70. 1.5 SUBMITTALS A. Submit under provisions of Division 1. B. Product Data: Provide for metallic conduit, flexible metal conduit, liquid-tight flexible metal conduit,

electrical metallic tubing, non-metallic conduit, fittings, and conduit bodies. 1.6 PROJECT RECORD DOCUMENTS A. Submit under provisions of Division 1. B. Accurately record actual routing of conduits larger than 2 inches (51 mm). C. Accurately record actual routing of all conduit below or in floor slabs, and in concrete or masonry

walls. 1.7 REGULATORY REQUIREMENTS A. Conform to requirements of ANSI/NFPA 70. B. Provide Products listed and classified by a Nationally Recognized Testing Laboratory (NRTL) as

suitable for the purpose specified and indicated. NRTL's are defined under the regulations of the Occupational Health and Safety Administration (OSHA).

1.8 DELIVERY, STORAGE AND HANDLING A. Deliver, store, protect, and handle Products on site under provisions of Division 1. B. Accept conduit on site. Inspect for damage. C. Protect conduit from corrosion and entrance of debris by storing above grade. Provide appropriate

covering. D. Protect PVC conduit from sunlight. 1.9 PROJECT CONDITIONS A. Verify routing and termination locations of conduit prior to rough-in. B. Conduit routing is shown on Drawings in approximate locations unless dimensioned. Route as

required to complete wiring system. PART 2 - PRODUCTS

Page 82: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 CONDUIT

SECTION 16111

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 5

2.1 METAL CONDUIT A. Rigid Steel Conduit: ANSI C80.1, Zinc coated galvanized steel. B. Intermediate Metal Conduit (IMC): ANSI C80.6. Zinc coated galvanized steel. C. Fittings and Conduit Bodies: ANSI/NEMA FB 1; material to match conduit. All fittings shall be

threaded. 2.2 FLEXIBLE METAL CONDUIT A. Description: Interlocked steel construction. B. Fittings: ANSI/NEMA FB 1. 2.3 LIQUID-TIGHT FLEXIBLE METAL CONDUIT A. Description: Interlocked steel construction with PVC jacket. B. Fittings: ANSI/NEMA FB 1. 2.4 ELECTRICAL METALLIC TUBING (EMT) A. Description: ANSI C80.3; galvanized tubing. B. Fittings and Conduit Bodies: ANSI/NEMA FB 1; steel or malleable iron, compression type. 2.5 NONMETALLIC CONDUIT A. Description: NEMA TC-2; Schedule 40 PVC. B. Fittings and Conduit Bodies: NEMA TC 3. PART 3 - EXECUTION 3.1 CONDUIT REQUIREMENTS A. Minimum Size: 3/4 inch (19 mm) unless otherwise specified. B. Underground Installation: 1. Buried, 30" or more below grade, outside of a building: Use rigid non-metallic conduit (Sch.

40 PVC). 2. Underground conduits penetrating foundation walls: Use rigid galvanized steel conduit. 3. In or under-slab on grade construction: Use rigid non-metallic conduit (Sch. 40 PVC). C. Outdoor Locations: 1. Exposed, above grade: Use rigid steel or intermediate metal conduit. D. Wet and Damp Locations Exposed: Use rigid steel or intermediate metal conduit.

Page 83: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 CONDUIT

SECTION 16111

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 5

E. Dry Locations: 1. Exposed less than 15' AFF: Use rigid steel or intermediate metal conduit. 2. Exposed more than 15' AFF: Use electrical metallic tubing (EMT). 3. Concealed, above suspended ceilings: Use electrical metallic tubing (EMT). 4. Concealed in metal stud walls: Use Type AC or Type MC cable; or electrical metallic tubing

(EMT). 5. Concealed in concrete or masonry walls: Use rigid steel or intermediate metal conduit. F. Connection to vibrating or movable equipment: 1. Dry Locations: Flexible metal conduit, 1'0" minimum length, 3'0" maximum length, 3/4"

minimum. 2. Wet Locations: Watertight flexible metal conduit, 1'0" minimum length, 3'0" maximum

length, 3/4" minimum. 3.2 INSTALLATION A. Install in accordance with NECA "Standard of Installation." B. Install nonmetallic conduit in accordance with manufacturer's instructions. C. Arrange supports to prevent misalignment during wire installation. D. Support individual conduit using coated steel or malleable iron straps, lay-in adjustable hangers,

clevis hangers, or split hangers. E. Group related conduits; support using conduit rack. Construct rack using steel channel; provide

space on each for 25 percent additional conduits. F. Fasten conduit supports to building structure and surfaces under provisions of Section 16190. G. Do not support conduit with wire or perforated pipe straps. Remove wire used for temporary

supports. Do not attach conduit to ceiling support wires. H. Arrange conduit to maintain headroom and present neat appearance. I. Route exposed conduit parallel and perpendicular to exterior walls. J. Route conduit installed above accessible ceilings parallel and perpendicular to walls. K. Route conduit in and under slab from point-to-point. Do not cross conduits in slab. L. Maintain adequate clearance between conduit and piping. M. Maintain 12 inch (300 mm) clearance between conduit and surfaces with temperatures exceeding

104 degrees F (40 degrees C). N. Cut conduit square using saw or pipe cutter; de-burr cut ends. Thread rigid and intermediate steel

conduit.

Page 84: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 CONDUIT

SECTION 16111

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 5 of 5

O. Bring conduit to shoulder of fittings. Use threaded couplings for rigid and intermediate steel conduit. Use compression type couplings for EMT.

P. Join nonmetallic conduit using cement as recommended by manufacturer. Wipe nonmetallic

conduit dry and clean before joining. Apply full even coat of cement to entire area inserted in fitting. Allow joint to cure for 20 minutes, minimum.

Q. Use conduit hubs or sealing locknuts to fasten conduit to welded sheet metal boxes (without

pre-punched knockouts) in damp and wet locations. R. Use double locknuts to fasten conduit to sheet metal boxes with a NEMA-1 rating. S. Install no more than equivalent of three 90-degree bends between boxes. Use conduit bodies to

make sharp changes in direction, as around beams. Use hydraulic one-shot bender to fabricate or factory elbows for bends in metal conduit larger than 2 inch (50 mm) size.

T. Avoid moisture traps; provide junction box with drain fitting at low points in conduit system. U. Provide suitable fittings to accommodate expansion and deflection where conduit crosses control

and expansion joints V. Provide suitable pull string in each empty conduit except sleeves and nipples. W. Use suitable caps to protect installed conduit against entrance of dirt and moisture. X. Provide sheet metal sleeves where conduit passes through concrete slabs. Sleeves shall be

minimum of 3" above finished floor. Y. Connections to vibrating equipment such as transformers, motors etc shall be with liquid tight

flexible conduit (min. length of 12"). Z. A rigid steel transition shall be used when PVC conduit enters or exits a concrete slab. AA. Ground and bond conduit under provisions of Section 16170. BB. Identify conduit under provisions of Section 16195. 3.3 INTERFACE WITH OTHER PRODUCTS A. Install conduit to preserve fire resistance rating of partitions and other elements, using materials

and methods under the provisions of Section 07270. END OF SECTION

Page 85: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 BUILDING WIRE AND CABLE

SECTION 16123

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 6

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Building wire and cable. B. Armored cable. C. Metal-clad cable. D. Wiring connectors and connections. E. Wire pulling lubricants. 1.2 RELATED SECTIONS A. Section 07270 - Fire Stopping. B. Section 16111 - Conduit. C. Section 16130 - Boxes. D. Section 16195 - Electrical Identification. E. Section 16990 - Testing. 1.3 REFERENCES A. NFPA 70 - National Electric Code. B. NEMA ICS 1 - General Standard for Industrial Control and Systems. 1.4 SUBMITTALS A. Submit under provisions of Division 1. B. Product Data: Provide for each cable assembly type and wire pulling lubricants. C. Manufacturer's Installation Instructions: Indicate application conditions and limitations of use

stipulated by product testing agency specified under Regulatory Requirements. D. Calibration reports and documentation for torque wrenches. 1.5 QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing products specified in this Section with

minimum ten years experience.

Page 86: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 BUILDING WIRE AND CABLE

SECTION 16123

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 6

1.6 REGULATORY REQUIREMENTS A. Conform to requirements of Connecticut State Building Code. B. Conform to requirements of ANSI/NFPA 70. C. Furnish products listed and classified by a Nationally Recognized Testing Laboratory (NRTL) as

suitable for purpose specified and shown. NRTL's are defined under the regulations of the Occupational Health and Safety Administration (OSHA).

1.7 PROJECT CONDITIONS A. Conductor sizes are based on copper. B. Wire and cable routing shown on Drawings is approximate. Route wire and cable as required to

meet Project Conditions. C. Where wire and cable routing is not shown, and destination only is indicated, determine exact

routing and lengths required. 1.8 COORDINATION A. Coordinate Work under provisions of Division 1. B. Determine required separation between cable and other work. C. Determine cable routing to avoid interference with other work. PART 2 - PRODUCTS 2.1 BUILDING WIRE AND CABLE A. Description: Single conductor insulated wire. B. Conductor: Copper, stranded (Class B). C. Insulation Voltage Rating: 600 volts. D. Insulation: ANSI/NFPA 70; Type THWN or XHHW insulation for feeders and branch circuits larger

than 6 AWG; Type THHN/THWN insulation for feeders and branch circuits 6 AWG and smaller. Insulation temperature rating shall be 75 degrees C.

2.2 ARMORED CABLE A. Description: ANSI/NFPA 70, Type AC with insulated ground conductor. B. Conductor: Copper, solid.

Page 87: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 BUILDING WIRE AND CABLE

SECTION 16123

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 6

C. Insulation Voltage Rating: 600 volts. D. Insulation Temperature Rating: 75 degrees C. E. Insulation Material: THHN/THWN. F. Armor Material: Steel or aluminum. G. Armor Design: Interlocked metal tape. 2.3 METAL-CLAD CABLE A. Description: ANSI/NFPA 70, Type MC. B. Conductor: Copper, solid for sizes No. 10 AWG and smaller; stranded (Class B) for sizes No. 8

AWG and larger. C. Insulation Voltage Rating: 600 volts. D. Insulation Temperature Rating: 75 degrees C. E. Insulation Material: THHN/THWN. F. Armor Material: Steel or aluminum. G. Armor Design: Interlocked metal tape or corrugated tube. H. Jacket: PVC in locations specified in Article 3.03 WIRING METHODS. 2.4 WIRING CONNECTORS A. Solderless pressure connectors. B. Spring wire connectors. C. Hydraulic compression connectors. 2.5 TIMER SYSTEM CABLE A. Timer system cable shall be a 2 conductor, #18 AWG, tinned copper conductors with a rubber

insulation, a tinned copper braid shield and a PVC jacket. Equal to Belden No. 8208. 2.6 WIRE PULLING LUBRICANTS A. Water soluble, non-toxic and non-sensitizing. B. Percent volatile solids shall be less than 6%.

Page 88: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 BUILDING WIRE AND CABLE

SECTION 16123

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 6

C. Appearance: Thick gel material. D. No flash point in gel state. E. Non-flammable residue when dry F. Useful temperature range: 20 - 100 degrees F. G. Lubricant shall be equal to Polywater J lubricant or Ideal AquaGel II. PART 3 - EXECUTION 3.1 EXAMINATION A. Verify that interior of building has been protected from weather. B. Verify that mechanical work likely to damage wire and cable has been completed. 3.2 PREPARATION A. Completely and thoroughly swab raceway before installing wire 3.3 WIRING METHODS A. Concealed in Concrete or Masonry Walls: Use only building wire, Type THHN/THWN or XHHW

insulation in conduit. B. Concealed Dry Interior Locations: Use only building wire, Type THHN/THWN or XHHW insulation

in conduit. C. Concealed in metal stud walls: Use only building wire, Type THHN/THWN or XHHW insulation in

conduit, Type AC or Type MC cable. D. Exposed Dry Interior Locations: Use only building wire, Type THHN/THWN or XHHW insulation, in

conduit or surface metal raceway. E. Wet or Damp Interior Locations: Use only building wire, Type THHN/THWN or XHHW insulation in

conduit. F. Above Accessible Ceilings: Use only building wire, Type THHN/THWN or XHHW insulation, in

conduit. G. Exterior Locations: Use only building wire, Type THHN/THWN or XHHW insulation, in conduit. H. Underground Installations: Use only building wire, Type THHN/THWN or XHHW insulation, in

conduit.

Page 89: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 BUILDING WIRE AND CABLE

SECTION 16123

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 5 of 6

I. Use wiring methods indicated on Drawings. 3.4 INSTALLATION A. Install products in accordance with manufacturers instructions. B. Use conductor not smaller than 12 AWG for power and lighting circuits. C. Use conductor not smaller than 14 AWG for control circuits, unless otherwise noted. D. Use 10 AWG conductors for 20 ampere, 120 volt branch circuits longer than 75 feet (23 m) E. Use 10 AWG conductors for 20 ampere, 277 volt branch circuits longer than 100 feet (30.5 m) F. Pull all conductors into raceway at same time. G. Use suitable wire pulling lubricant for building wire. H. Protect exposed cable from damage. I. Support cables above accessible ceiling, using two hole conduit straps and plastic cable ties to

support cables from structure. Do not rest cable on ceiling panels. J. Use suitable cable fittings and connectors. K. Neatly train and secure wiring with plastic cable ties inside boxes, equipment, and panelboards. L. Clean conductor surfaces before installing lugs and connectors. M. Make splices, taps, and terminations to carry full ampacity of conductors with no perceptible

temperature rise. N. Use solderless pressure, hydraulic compression connectors or power distribution blocks with

insulating covers for copper conductor splices and taps, 8 AWG and larger. Split bolts shall not be used.

O. Use insulated spring wire connectors with plastic caps for copper conductor splices and taps, 10

AWG and smaller. 3.5 INTERFACE WITH OTHER PRODUCTS A. Identify wire and cable under provisions of Section 16195. B. Identify each conductor with its circuit number or other designation indicated on Drawings. 3.6 FIELD QUALITY CONTROL A. Inspect wire and cable for physical damage and proper connection.

Page 90: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 BUILDING WIRE AND CABLE

SECTION 16123

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 6 of 6

B. Color code secondary service, feeder and branch circuit conductors as follows:

Phase 208Y/120 Volts 480Y/277 Volts 120/240 Volts

A Black Brown Black

B Red Orange Red

C Blue Yellow

Neutral White White or Light Gray White

Ground Green Green Green

Isolated Ground Green with Yellow Stripe

C. Color coding for branch circuits, No. 8 AWG and smaller shall be by colored insulation; No. 6

AWG and larger by banding with colored tape not less than 3 inches in width. D. Where color coding is not followed, contractor shall remove the conductors and install the

appropriately colored conductors. E. Measure tightness of bolted connections with a calibrated torque wrench and compare torque

measurements with manufacturer's recommended values. F. Verify continuity of each branch circuit conductor. END OF SECTION

Page 91: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 BOXES

SECTION 16130

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 3

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wall and ceiling outlet boxes. B. Pull and junction boxes. 1.2 RELATED SECTIONS A. Section 07270 - Firestopping. B. Section 16140 - Wiring Devices: Mounting heights of wiring devices. C. Section 16721 - Fire Alarm System. D. Section 16741 - Telephone Service, Pathways and Wiring. E. Section 16770 - Public Address System 1.3 REFERENCES A. ANSI/NEMA FB 1 - Fittings and Supports for Conduit and Cable Assemblies. B. ANSI/NEMA OS 1 - Sheet-steel Outlet Boxes, Device Boxes, Covers, and Box Supports. C. ANSI/NFPA 70 - National Electrical Code. D. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum). 1.4 PROJECT RECORD DOCUMENTS A. Submit under provisions of Division 1. B. Accurately record actual locations and mounting heights of outlet, pull, and junction boxes. 1.5 REGULATORY REQUIREMENTS A. Conform to requirements of ANSI/NFPA 70. B. Furnish products listed and classified by a Nationally Recognized Testing Laboratory (NRTL) as

suitable for purpose specified and shown. NRTL's are defined under the regulations of the Occupational Health and Safety Administration (OSHA).

1.6 PROJECT CONDITIONS A. Electrical boxes are shown on Drawings in approximate locations unless dimensioned. Install at

location required for box to serve intended purpose. Include installation within 10 feet (3 m) of location shown.

Page 92: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 BOXES

SECTION 16130

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 3

PART 2 - PRODUCTS 2.1 OUTLET BOXES A. Sheet Metal Outlet Boxes: ANSI/NEMA OS 1, galvanized steel. 1. Luminaire and Equipment Supporting Boxes: Rated for weight of equipment supported;

include 1/2 inch (13 mm) male fixture studs where required. 2. Minimum size for outlet boxes shall be 4" x 4" x 1 1/2" unless otherwise noted. 3. In Stud walls: Provide plaster frames on outlet boxes. 4. Minimum size for Masonry Boxes shall 3 1/2" deep, two gang. Provide oversize cover-plate

with central opening for single devices. B. Cast Boxes: NEMA FB 1, Type FD, cast feralloy with threaded hubs. Provide gasketed cover

where required. 2.2 PULL AND JUNCTION BOXES A. Sheet Metal Boxes: NEMA OS 1, galvanized steel with gray baked enamel finish. PART 3 - EXECUTION 3.1 INSTALLATION A. Install electrical boxes as shown on Drawings, and as required for splices, taps, wire pulling,

equipment connections and compliance with regulatory requirements. B. Install electrical boxes to maintain headroom and to present neat mechanical appearance. C. Install pull boxes and junction boxes above accessible ceilings and in unfinished areas only. D. Install boxes to preserve fire resistance rating of partitions and other elements, using materials and

methods under the provisions of Section 07270. E. Align adjacent wall-mounted outlet boxes for switches, thermostats, and similar devices with each

other. F. Use flush mounting outlet boxes in finished areas. G. Do not install flush mounting boxes back-to-back in walls; provide minimum 6 inch (150 mm)

separation. Provide minimum 24 inches (600 mm) separation in acoustic rated walls. H. Secure flush mounting box to interior wall and partition studs. Accurately position to allow for

surface finish thickness. I. Use stamped steel bridges to fasten flush mounting outlet box between studs. J. Install flush mounting box without damaging wall insulation or reducing its effectiveness.

Page 93: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 BOXES

SECTION 16130

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 3

K. Use adjustable steel channel fasteners for hung ceiling outlet box. L. Do not fasten boxes to ceiling support wires. M. Support boxes independently of conduit, except cast box that is connected to two rigid metal

conduits both supported within 12 inches (300 mm) of box. N. Use gang box where more than one device is mounted together. Do not use sectional box. O. Use two gang box with plaster ring for single device outlets. P. Use cast outlet box in exterior locations exposed to the weather and wet locations. Q. Surface mounted switch and receptacles shall be installed in Type FD cast feralloy outlet boxes

with threaded hubs. 3.2 INTERFACE WITH OTHER PRODUCTS A. Coordinate installation of outlet box for products furnished under other Sections. B. Locate flush mounting box in masonry wall to require cutting of masonry unit corner only.

Coordinate masonry cutting to achieve neat opening. C. Coordinate mounting heights and locations of outlets mounted above counters, benches and back-

splashes. D. Position outlet boxes to locate luminaires as shown on reflected ceiling plan. 3.3 ADJUSTING A. Adjust flush-mounting outlets to make front flush with finished wall material. B. Install knockout closure in unused box opening. END OF SECTION

Page 94: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 WIRING DEVICES

SECTION 16140

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 5

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Wall switches. B. Wall dimmers. C. Receptacles. D. Device plates. 1.2 RELATED SECTIONS A. Section 16112 - Surface Raceways. B. Section 16130 - Boxes. 1.3 REFERENCES A. NECA - Standard of Installation. B. NEMA WD 1 - General Requirements for Wiring Devices. C. NEMA WD 6 - Wiring Device -- Dimensional Requirements. D. NFPA 70 - National Electrical Code. 1.4 SUBMITTALS A. Submit under provisions of Division 1. B. Product Data: Provide manufacturer's catalog information showing dimensions, colors, and

configurations. C. Where a substitute manufacturer's product is submitted for review, two sample devices shall be

provided with the submittal. D. Submit manufacturer's installation instructions. 1.5 REGULATORY REQUIREMENTS A. Conform to requirements of NFPA 70. B. Provide Products listed and classified by a Nationally Recognized Testing Laboratory (NRTL) as

suitable for the purpose specified and indicated. NRTL's are defined under the regulations of the Occupational Health and Safety Administration (OSHA).

PART 2 - PRODUCTS

Page 95: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 WIRING DEVICES

SECTION 16140

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 5

2.1 WALL SWITCHES A. Single Pole Switch: 1. Arrow-Hart. Model 1991. 2. General Electric. Model GE5951. 3. Bryant Electric. Model 4901. 4. Hubbell. Model 1221. 5. Leviton. Model 1221-2. B. Double Pole Switch: 1. Arrow-Hart. Model 1992. 2. General Electric. Model GE5952. 3. Bryant Electric. Model 4902. 4. Hubbell. Model 1222. 5. Leviton. Model 1222-2. C. Three-way Switch: 1. Arrow-Hart. Model 1993. 2. General Electric. Model GE5953. 3. Bryant Electric. Model 4903. 4. Hubbell. Model 1223. 5. Leviton. Model 1223-2. D. Four-way Switch: 1. Arrow- Hart. Model 1994. 2. General Electric. Model GE5953. 3. Bryant Electric. Model 4904. 4. Hubbell. Model 1224. 5. Leviton. Model 1224. E. Substitutions: Under provisions of Section 16140, item 1.4 C. F. Description: NEMA WD 1, Heavy-Duty, AC only general-use snap switch. G. Body and Handle: Ivory plastic with toggle handle. H. Ratings: 1. Voltage: 120-277 volts, AC. 2. Current: 20 amperes. 2.2 WALL DIMMERS - FLUORESCENT A. Manufacturers: 1. Leviton. 2. Lightolier. 3. Lutron. 4. Substitutions: Under provisions of Section 16140, item 1.4 C.

Page 96: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 WIRING DEVICES

SECTION 16140

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 5

B. Description: Dimming for control of fluorescent dimming ballasts, with an air gap switch and control lead. Dimmer shall meet the applicable requirements of UL 20 and UL 1472, and shall withstand a voltage surge of 6000V and current surge of 200A in accordance with ANSI/IEEE C62.41-1980.

C. Dimmers shall utilize filtering network to minimize RF interference. D. Dimmers shall have power failure memory, such that upon restoration of power after a power

failure, the lighting level shall return to the pre-outage level. E. Body and Handle: White plastic with linear slide. F. Voltage: 120 volts. 2.3 RECEPTACLES A. Duplex Convenience Receptacle: (NEMA 5-20R) 1. Arrow-Hart. Model 5362. 2. General Electric. Model GE5362. 3. Bryant Electric. Model 5362. 4. Hubbell. Model 5362. 5. Leviton. Model 5362. B. GFCI Receptacle: (NEMA 5-20R) 1. Arrow-Hart. Model GF5342. 2. General Electric. Model GF5342. 3. Bryant Electric. Model GFR53FT. 4. Hubbell. Model GF5352. 5. Leviton. Model 6898. C. Substitutions: Under provisions of Section 16140, item 1.4 C. D. Description: NEMA WD 1, Heavy-duty general use receptacle. E. Device Body: Ivory plastic. Porvide yellow receptacles for the P.O.S. terminals in the concession

stand. F. GFCI Receptacle: Convenience receptacle with integral ground fault circuit interrupter, conforming

to UL Standard 943 Class A requirements. 2.4 DEVICE PLATES A. Cover Plate: Stainless steel 302 or 304. B. Provide oversize or jumbo device plates for devices installed in recessed masonry boxes. C. Weatherproof Cover Plate: Gasketed thermoplastic with hinged gasketed device cover. Cover

shall be capable of being closed with a plug inserted in the receptacle.

Page 97: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 WIRING DEVICES

SECTION 16140

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 4 of 5

PART 3 - EXECUTION 3.1 EXAMINATION A. Verify that outlet boxes are installed at proper height. B. Verify that wall openings are neatly cut and will be completely covered by wall plates. C. Verify that branch circuit wiring installation is completed, tested, and ready for connection to wiring

devices. D. Install surface mounted switch and receptacles in Type FD cast feralloy outlet boxes only. 3.2 PREPARATION A. Provide extension rings to bring outlet boxes flush with finished surface. B. Clean debris from outlet boxes. 3.3 INSTALLATION A. Install in accordance with NECA "Standard of Installation." B. Install devices plumb and level. C. Install switches with OFF position down. D. Install wall dimmers to achieve full rating specified and indicated. Wall dimmers shall be mounted

in individual outlet boxes, and shall not be ganged. E. Do not share neutral conductor on load side of dimmers. F. Install receptacles with grounding pole on bottom. G. Connect wiring device grounding terminal to branch circuit equipment grounding conductor. Bond

outlet box to circuit equipment grounding conductor. H. Install decorative plates on switch, receptacle, and blank outlets in finished areas. I. Use jumbo size plates for outlets installed in masonry walls. J. Install galvanized steel plates on outlet boxes and junction boxes in unfinished areas, above

accessible ceilings, and on surface mounted outlets in unfinished areas. 3.4 INTERFACE WITH OTHER PRODUCTS A. Coordinate locations of outlet boxes provided under Section 16130 to obtain mounting heights

specified.

Page 98: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 WIRING DEVICES

SECTION 16140

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 5 of 5

B. Install wall switch 48 inches above finished floor, measured to the top of the cover plate. C. Install convenience receptacle 18 inches (450 mm) above finished floor. D. Install convenience receptacle 6 inches (150 mm) above back-splash of counter. E. Install dimmer 48 inches (top of the cover plate) above finished floor, measured to top of the cover

plate. 3.5 FIELD QUALITY CONTROL A. Inspect each wiring device for defects. B. Operate each wall switch with circuit energized and verify proper operation. C. Verify that each receptacle device is energized. D. Test each receptacle device for proper polarity. E. Test each GFCI receptacle device for proper operation. F. Adjust devices and wall plates to be flush and level. 3.6 CLEANING A. Clean exposed surfaces to remove splatters and restore finish. END OF SECTION

Page 99: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 GROUNDING AND BONDING

SECTION 16170

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 3

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Grounding electrodes and conductors. B. Equipment grounding conductors. C. Bonding. 1.2 RELATED SECTIONS A. Section 16990 - Electrical Testing. 1.3 REFERENCES A. ANSI/NFPA 70 - National Electrical Code. 1.4 GROUNDING ELECTRODE SYSTEM A. Metal underground water pipe. B. Ground ring. C. Rod electrode. 1.5 PERFORMANCE REQUIREMENTS A. Grounding System Resistance: 5 ohms. 1.6 SUBMITTALS A. Submit under provisions of Division 1. B. Product Data: Provide data for grounding electrodes, conductors, and connections. C. Manufacturer's Instructions: Include instructions for storage, handling, protection, examination,

preparation and installation of exothermic connectors and hydraulic compression connectors. D. Test Reports: Indicate overall resistance to ground. 1.7 PROJECT RECORD DOCUMENTS A. Submit under provisions of Division 1. B. Accurately record actual locations of grounding electrodes and conductors. 1.8 QUALIFICATIONS

Page 100: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 GROUNDING AND BONDING

SECTION 16170

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 3

A. Manufacturer: Company specializing in manufacturing Products specified in this Section with minimum five years experience.

1.9 REGULATORY REQUIREMENTS A. Conform to requirements of ANSI/NFPA 70. B. Furnish products listed and classified by a Nationally Recognized Testing Laboratory (NRTL) as

suitable for purpose specified and shown. NRTL's are defined under the regulations of the Occupational Health and Safety Administration (OSHA).

PART 2 - PRODUCTS 2.1 ROD ELECTRODE A. Material: Copper-clad steel. B. Diameter: 3/4 inch (19 mm). C. Length: 10 feet (3 m). 2.2 MECHANICAL CONNECTORS A. Material: Bronze. B. Hydraulic compression type for conductor to conductor connections as indicated on the drawings. C. Mechanical set screw/clamp type for connection to water piping. 2.3 EXOTHERMIC CONNECTIONS A. Exothermic connections shall be equal to Cadweld as manufactured by Erico Products Company. 2.4 WIRE A. Material: Stranded copper. B. Grounding Electrode Conductor: As indicated on the drawings. PART 3 - EXECUTION 3.1 EXAMINATION A. Verify that final backfill and compaction has been completed before driving rod electrodes. 3.2 INSTALLATION A. Install Products in accordance with manufacturer's instructions.

Page 101: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 GROUNDING AND BONDING

SECTION 16170

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 3

B. Install rod electrodes at locations indicated. Install additional rod electrodes as required to achieve specified resistance to ground.

C. Provide bonding to meet Regulatory Requirements. D. Bond together metal siding and roofing not attached to grounded structure; bond to ground. E. Equipment Grounding Conductor: Provide separate, insulated conductor within each feeder and

branch circuit raceway. Terminate each end on suitable lug, bus, or bushing. 3.3 FIELD QUALITY CONTROL A. Inspect grounding and bonding system conductors and connections for tightness and proper

installation. B. Grounding system shall be tested under Section 16990 Electrical Testing. END OF SECTION

Page 102: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 SUPPORTING DEVICES

SECTION 16190

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 2

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Conduit and equipment supports. B. Anchors and fasteners. 1.2 REFERENCES A. NECA - National Electrical Contractors Association. B. ANSI/NFPA 70 - National Electrical Code. 1.3 SUBMITTALS A. Submit under provisions of Section 01300. B. Product Data: Provide manufacturer's catalog data for fastening systems. C. Manufacturer's Instructions: Indicate application conditions and limitations of use stipulated by

Product testing agency specified under Regulatory Requirements. Include instructions for storage, handling, protection, examination, preparation, and installation of Product.

1.4 REGULATORY REQUIREMENTS A. Conform to requirements of ANSI/NFPA 70. B. Furnish products listed and classified by a Nationally Recognized Testing Laboratory (NRTL) as

suitable for purpose specified and shown. NRTL's are defined under the regulations of the Occupational Health and Safety Administration (OSHA).

PART 2 - PRODUCTS 2.1 PRODUCT REQUIREMENTS A. Materials and Finishes: Provide adequate corrosion resistance. B. Provide materials, sizes, and types of anchors, fasteners and supports to carry the loads of

equipment and conduit. Consider weight of wire in conduit when selecting products. C. Anchors and Fasteners: 1. Concrete Structural Elements: Use precast insert system, expansion anchors, powder

actuated anchors or preset inserts. 2. Steel Structural Elements: Use beam clamps, or powder actuated fasteners. 3. Concrete Surfaces: Use expansion anchors. 4. Hollow Masonry, Plaster, and Gypsum Board Partitions: Use toggle bolts. 5. Solid Masonry Walls: Use expansion anchors or preset inserts. 6. Sheet Metal: Use sheet metal screws.

Page 103: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 SUPPORTING DEVICES

SECTION 16190

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 2

7. Wood Elements: Use wood screws. 2.2 STEEL CHANNEL A. Manufacturer: 1. Unistrut. 2. B-Line. 3. Grinnell. 4. Kindorf Superstrut. B. Description: Rolled steel channel, finished after fabrication. For damp areas, use hot dip

galvanized finished channel. For dry areas, use electro-deposition acrylic enamel or epoxy finish. PART 3 - EXECUTION 3.1 INSTALLATION A. Install products in accordance with manufacturer's instructions. B. Provide anchors, fasteners, and supports in accordance with NECA "Standard of Installation". C. Do not fasten supports to pipes, ducts, mechanical equipment, and conduit. D. Obtain permission from Architect/Engineer before using powder-actuated anchors. E. Obtain permission from Architect/Engineer before drilling or cutting structural members. F. Fabricate supports from structural steel or steel channel. Rigidly weld members or use hexagon

head bolts to present neat appearance with adequate strength and rigidity. Use spring lock washers under all nuts.

G. Install surface-mounted cabinets and panelboards with minimum of four anchors. H. In wet and damp locations use steel channel supports to stand cabinets and panelboards one inch

(25 mm) off wall. I. Use sheet metal channel to bridge studs above and below cabinets and panelboards recessed in

hollow partitions. END OF SECTION

Page 104: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 ELECTRICAL IDENTIFICATION

SECTION 16195

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 1 of 3

PART 1 - GENERAL 1.1 SECTION INCLUDES A. Nameplates and labels. B. Wire and cable markers. C. Conduit markers. 1.2 REFERENCES A. ANSI/NFPA 70 - National Electrical Code. B. Occupational Safety and Health Administration. C. ANSI Z535il-1991. 1.3 SUBMITTALS A. Submit under provisions of Division 1. B. Product Data: Provide catalog data for nameplates, labels, and markers. C. Manufacturer's Instructions: Indicate application conditions and limitations of use stipulated by

Product testing agency specified under regulatory requirements. Include instructions for storage, handling, protection, examination, preparation and installation of Product.

1.4 REGULATORY REQUIREMENTS A. Conform to requirements of ANSI/NFPA 70. B. Furnish products listed and classified by a Nationally Recognized Testing Laboratory (NRTL) as

suitable for purpose specified and shown. NRTL's are defined under the regulations of the Occupation Safety and Health Administration (OSHA).

PART 2 - PRODUCTS 2.1 NAMEPLATES AND LABELS A. Nameplates: Engraved three-layer laminated plastic. Black letters on white background for

electrical equipment. White letters on Red background for Fire Alarm and life safety equipment. B. Letter Size: 1. Use 1/4 inch (6 mm) letters for identifying individual equipment and loads. 2. Use 1/2 inch (12 mm) letters for identifying grouped equipment and loads. 2.2 WIRE MARKERS

Page 105: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 ELECTRICAL IDENTIFICATION

SECTION 16195

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 2 of 3

A. Description: 3 inch (72 mm) wide split sleeve or tubing type wire markers. 2.3 CONDUIT MARKERS A. Description: Plastic 'snap-on' or adhesive type. Length and size of marker determined by 1 inch

(24 mm) minimum characters. B. Color: 1. 480 Volt System: Safety orange. 2. 208 Volt System: Safety orange. 3. Fire Alarm System: Red. 4. Telephone System: Green. 5. Data System: Blue. C. Legend: 1. 480 Volt System: 480/277V. 2. 208 Volt System: 208/120V. 3. Fire Alarm System: FA. 4. Telephone System: TEL. 5. Data System: DATA. 2.4 UNDERGROUND WARNING TAPE A. Description: 6 inch (150 mm) wide plastic tape, detectable type with suitable warning legend

describing the buried utility. B. Warning tape shall be colored as follows: 1. Electrical: Red with black lettering. 2. Telephone: Orange with black lettering. PART 3 - EXECUTION 3.1 PREPARATION A. Degrease and clean surfaces to receive nameplates and labels. 3.2 APPLICATION A. Install nameplate parallel to equipment lines. B. Secure nameplate to equipment front using screws. C. Nameplate shall be on distribution and control equipment. On switchboards and motor control

centers, each circuit or controller shall be identified as shown on drawings. D. Identify conductor with wire markers. Marker shall identify the conductor's phase and voltage by

color of insulation or by banding and labeling circuit number at junction boxes, pull boxes and at terminations. Control wire numbers shall be installed at terminals for all controls. Numbers shall agree with schematic and interconnection diagram.

Page 106: DIVISION 4 UNIT MASONRY SECTION 04200 PART 1 - … Geotech Lab Tech Specs Divsions of Work.pdfDIVISION 4 UNIT MASONRY SECTION 04200 COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

DIVISION 16 ELECTRICAL IDENTIFICATION

SECTION 16195

COPERNICUS HALL PROPOSED GEOTECH LAB AT ROOM #120

CCSU PROJECT #23-113 OCTOBER 6TH, 2014; Page 3 of 3

E. Color coding of conductors shall be strictly followed. Conductors No. 8 AWG and smaller shall be

color coded by colored insulation. Conductors No. 6 AWG and larger shall be color coded using tape or heat shrink tubing. Tape bands or heat shrink tubing shall be a minimum of 3" in length. Color coding shall be as follows:

Phase 120/240V 208/120V 480/277V A Red Black Brown B Black Red Orange C --- Blue Yellow N White White Light Gray Ground Green Green Green F. Identify conduits over 10 feet long with markers at 20 feet on center. Place markers on the bottom

of conduit so that they can be identified from the floor. G. Identify underground conduits using underground warning tape. Install one tape per trench at 12

inches below finished grade. END OF SECTION