DIVISION 15 - MECHANICAL Page 1 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 MECHANICAL 15050 - COMMON WORK RESULTS FOR HVAC & PLUMBING PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Piping materials and installation instructions common to most piping systems. 2. Dielectric fittings. 3. Mechanical sleeve seals. 4. Sleeves. 5. Escutcheons. 6. Grout. 7. Equipment installation requirements common to equipment sections. 8. Concrete bases. 9. Supports and anchorages. 1.2 DEFINITIONS A. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spaces, pipe and duct chases, unheated spaces immediately below roof, spaces above ceilings, unexcavated spaces, crawlspaces, and tunnels. B. Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied spaces and mechanical equipment rooms. C. Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor ambient temperatures and weather conditions. Examples include rooftop locations. D. Concealed, Interior Installations: Concealed from view and protected from physical contact by building occupants. Examples include above ceilings and chases. E. Concealed, Exterior Installations: Concealed from view and protected from weather conditions and physical contact by building occupants but subject to outdoor ambient temperatures. Examples include installations within unheated shelters. 1.3 SUBMITTALS A. As noted on contract documents; Minimum requirements as follows: 1. Submit shop drawings on each piece of HVAC and Plumbing equipment, fixtures and trim ductwork accessories, grilled, registers, and diffusers, control devices, temperature control wiring and systems, air intakes, exhaust fittings, and other special equipment. 2. Mechanical units and equipment: show size and weight of equipment, special structural support requirements, size and location of roof openings, which units operate on specified electrical voltage and phase, and within the FLA shown on Drawings. 3. Catalogue cuts shall be marked to indicate equipment model numbers, capacities, per equipment schedules on the working drawings, controls, options and accessories and similar data. Submitted data shall be reviewed, stamped and approved by contractor prior to submittal review. 4. Ductwork, sheet metal, piping and insulation shop drawings shall be prepared and submitted for approval before installation is begun on the job site. 5. Shop drawings that are not marked to show model numbers, capacities, accessories, ets., and do not bear the submitting contractor’s approval stamp will be rejected.

Transcript of DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 -...

Page 1: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15050 - COMMON WORK RESULTS FOR HVAC & PLUMBING

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes the following:

1. Piping materials and installation instructions common to most piping systems. 2. Dielectric fittings. 3. Mechanical sleeve seals. 4. Sleeves. 5. Escutcheons. 6. Grout. 7. Equipment installation requirements common to equipment sections. 8. Concrete bases. 9. Supports and anchorages.

1.2 DEFINITIONS

A. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spaces, pipe and duct chases, unheated spaces immediately below roof, spaces above ceilings, unexcavated spaces, crawlspaces, and tunnels.

B. Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied spaces and mechanical equipment rooms.

C. Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor ambient temperatures and weather conditions. Examples include rooftop locations.

D. Concealed, Interior Installations: Concealed from view and protected from physical contact by building occupants. Examples include above ceilings and chases.

E. Concealed, Exterior Installations: Concealed from view and protected from weather conditions and physical contact by building occupants but subject to outdoor ambient temperatures. Examples include installations within unheated shelters.

1.3 SUBMITTALS

A. As noted on contract documents; Minimum requirements as follows: 1. Submit shop drawings on each piece of HVAC and Plumbing equipment, fixtures and trim ductwork

accessories, grilled, registers, and diffusers, control devices, temperature control wiring and systems, air intakes, exhaust fittings, and other special equipment.

2. Mechanical units and equipment: show size and weight of equipment, special structural support requirements, size and location of roof openings, which units operate on specified electrical voltage and phase, and within the FLA shown on Drawings.

3. Catalogue cuts shall be marked to indicate equipment model numbers, capacities, per equipment schedules on the working drawings, controls, options and accessories and similar data. Submitted data shall be reviewed, stamped and approved by contractor prior to submittal review.

4. Ductwork, sheet metal, piping and insulation shop drawings shall be prepared and submitted for approval before installation is begun on the job site.

5. Shop drawings that are not marked to show model numbers, capacities, accessories, ets., and do not bear the submitting contractor’s approval stamp will be rejected.

Page 2: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1.4 QUALITY ASSURANCE

A. Steel Support Welding: Qualify processes and operators according to AWS D1.1, "Structural Welding Code--Steel."

B. Steel Pipe Welding: Qualify processes and operators according to ASME Boiler and Pressure Vessel Code: Section IX, "Welding and Brazing Qualifications."

1. Comply with provisions in ASME B31 Series, "Code for Pressure Piping." 2. Certify that each welder has passed AWS qualification tests for welding processes involved and

that certification is current.

C. Electrical Characteristics for HVAC Equipment: Equipment of higher electrical characteristics may be furnished provided such proposed equipment is approved in writing and connecting electrical services, circuit breakers, and conduit sizes are appropriately modified. If minimum energy ratings or efficiencies are specified, equipment shall comply with requirements.

1.5 SUBSITIUTIONS

A. The electrical service, and electrical distributions system, HVAC control system, roof structure, exterior penetrations, HVAC equipment space clearances are all designed around the HVAC and plumbing equipment scheduled on the contract documents. Any additional costs to the project for electrical devices, wiring, conduit, structural members, and design changes required because different HVAC and plumbing equipment than scheduled on the contract documents is supplied to the project shall be made the responsibility of the HVAC and Plumbing Contractor. These additional costs will not be borne by the Owner, Architect, Engineer, or other trades

1.6 RECORD DRAWINGS

A. HVAC and Plumbing Contractor is required to provide and submit project record drawings on all HVAC and on all plumbing systems.

1.7 WARRANTY

A. Refer to architectural specifications.

1.8 INTERFEREVCES AND COORDINATION

A. HVAC and Plumbing Contractor shall provide coordination and cooperation with all trades. Conflicts that arise shall be brought to the attention, of the General Contractor and Architect. Before Installation, verify that HVAC and Plumbing will not interfere with structural systems. Architectural systems, electrical systems, sprinkler systems, or other trades.

PART 2 - PRODUCTS

2.1 PIPE, TUBE, AND FITTINGS

A. Refer to individual Division 15 Sections for pipe, tube, and fitting materials and joining methods.

B. Pipe Threads: ASME B1.20.1 for factory-threaded pipe and pipe fittings.

2.2 JOINING MATERIALS

A. Refer to individual Division 15 Sections for special joining materials not listed below.

B. Pipe-Flange Gasket Materials: ASME B16.21, nonmetallic, flat, asbestos-free, 1/8-inch maximum thickness unless thickness or specific material is indicated.

Page 3: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

C. Plastic, Pipe-Flange Gasket, Bolts, and Nuts: Type and material recommended by piping system manufacturer, unless otherwise indicated.

D. Solder Filler Metals: ASTM B 32, lead-free alloys. Include water-flushable flux according to ASTM B 813.

E. Brazing Filler Metals: AWS A5.8, BCuP Series or BAg1, unless otherwise indicated.

F. Welding Filler Metals: Comply with AWS D10.12.

2.3 DIELECTRIC FITTINGS

A. Description: Combination fitting of copper alloy and ferrous materials with threaded, solder-joint, plain, or weld-neck end connections that match piping system materials.

B. Insulating Material: Suitable for system fluid, pressure, and temperature.

C. Dielectric Unions: Factory-fabricated, union assembly, for 250-psig minimum working pressure at 180 deg F.

D. Dielectric Flanges: Factory-fabricated, companion-flange assembly, for 150- or 300-psig minimum working pressure as required to suit system pressures.

E. Dielectric Couplings: Galvanized-steel coupling with inert and noncorrosive, thermoplastic lining; threaded ends; and 300-psig minimum working pressure at 225 deg F.

F. Dielectric Nipples: Electroplated steel nipple with inert and noncorrosive, thermoplastic lining; plain, threaded, or grooved ends; and 300-psig minimum working pressure at 225 deg F.

2.4 MECHANICAL SLEEVE SEALS

A. Description: Modular sealing element unit, designed for field assembly, to fill annular space between pipe and sleeve.

B. Sealing Elements: EPDM interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe.

C. Pressure Plates: Plastic. Include two for each sealing element.

D. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of length required to secure pressure plates to sealing elements. Include one for each sealing element.

2.5 SLEEVES

A. Galvanized-Steel Sheet: 0.0239-inch minimum thickness; round tube closed with welded longitudinal joint.

B. Steel Pipe: ASTM A 53, Type E, Grade B, Schedule 40, galvanized, plain ends.

C. Cast Iron: Cast or fabricated "wall pipe" equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop, unless otherwise indicated.

D. Stack Sleeve Fittings: Manufactured, cast-iron sleeve with integral clamping flange. Include clamping ring and bolts and nuts for membrane flashing.

1. Underdeck Clamp: Clamping ring with set screws.

Page 4: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

E. Molded PE: Reusable, PE, tapered-cup shaped, and smooth-outer surface with nailing flange for attaching to wooden forms.

2.6 ESCUTCHEONS

A. Description: Manufactured wall and ceiling escutcheons and floor plates, with an ID to closely fit around pipe, tube, and insulation of insulated piping and an OD that completely covers opening.

B. One-Piece, Deep-Pattern Type: Deep-drawn, box-shaped brass with polished chrome-plated finish.

C. One-Piece, Cast-Brass Type: With set screw.

1. Finish: Polished chrome-plated.

D. Split-Casting, Cast-Brass Type: With concealed hinge and set screw.

1. Finish: Polished chrome-plated.

2.7 GROUT

A. Description: ASTM C 1107, Grade B, nonshrink and nonmetallic, dry hydraulic-cement grout.

1. Characteristics: Post-hardening, volume-adjusting, nonstaining, noncorrosive, nongaseous, and recommended for interior and exterior applications.

2. Design Mix: 5000-psi, 28-day compressive strength. 3. Packaging: Premixed and factory packaged.

PART 3 - EXECUTION

3.1 PIPING SYSTEMS - COMMON REQUIREMENTS

A. Install piping according to the following requirements and Division 15 Sections specifying piping systems.

B. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems. Indicated locations and arrangements were used to size pipe and calculate friction loss, expansion, pump sizing, and other design considerations. Install piping as indicated unless deviations to layout are approved on Coordination Drawings.

C. Install piping in concealed locations, unless otherwise indicated and except in equipment rooms and service areas.

D. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise.

E. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal.

F. Install piping to permit valve servicing.

G. Install piping at indicated slopes.

H. Install piping free of sags and bends.

I. Install fittings for changes in direction and branch connections.

Page 5: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

J. Install piping to allow application of insulation.

K. Select system components with pressure rating equal to or greater than system operating pressure.

L. Install escutcheons for penetrations of walls, ceilings, and floors.

M. Install sleeves for pipes passing through concrete and masonry walls, gypsum-board partitions, and concrete floor and roof slabs.

N. Aboveground, Exterior-Wall Pipe Penetrations: Seal penetrations using sleeves and mechanical sleeve seals. Select sleeve size to allow for 1-inch annular clear space between pipe and sleeve for installing mechanical sleeve seals.

1. Install steel pipe for sleeves smaller than 6 inches in diameter. 2. Install cast-iron "wall pipes" for sleeves 6 inches and larger in diameter. 3. Mechanical Sleeve Seal Installation: Select type and number of sealing elements required for pipe

material and size. Position pipe in center of sleeve. Assemble mechanical sleeve seals and install in annular space between pipe and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.

O. Underground, Exterior-Wall Pipe Penetrations: Install cast-iron "wall pipes" for sleeves. Seal pipe penetrations using mechanical sleeve seals. Select sleeve size to allow for 1-inch annular clear space between pipe and sleeve for installing mechanical sleeve seals.

1. Mechanical Sleeve Seal Installation: Select type and number of sealing elements required for pipe material and size. Position pipe in center of sleeve. Assemble mechanical sleeve seals and install in annular space between pipe and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.

P. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials. Refer to Division 7 Section "Through-Penetration Firestop Systems" for materials.

Q. Verify final equipment locations for roughing-in.

R. Refer to equipment specifications in other Sections of these Specifications for roughing-in requirements.

3.2 PIPING JOINT CONSTRUCTION

A. Join pipe and fittings according to the following requirements and Division 15 Sections specifying piping systems.

B. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.

C. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before assembly.

D. Soldered Joints: Apply ASTM B 813, water-flushable flux, unless otherwise indicated, to tube end. Construct joints according to ASTM B 828 or CDA's "Copper Tube Handbook," using lead-free solder alloy complying with ASTM B 32.

E. Brazed Joints: Construct joints according to AWS's "Brazing Handbook," "Pipe and Tube" Chapter, using copper-phosphorus brazing filler metal complying with AWS A5.8.

F. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows:

Page 6: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 6 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1. Apply appropriate tape or thread compound to external pipe threads unless dry seal threading is specified.

2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. Do not use pipe sections that have cracked or open welds.

G. Welded Joints: Construct joints according to AWS D10.12, using qualified processes and welding operators according to Part 1 "Quality Assurance" Article.

H. Flanged Joints: Select appropriate gasket material, size, type, and thickness for service application. Install gasket concentrically positioned. Use suitable lubricants on bolt threads.

3.3 PIPING CONNECTIONS

A. Make connections according to the following, unless otherwise indicated:

1. Install unions, in piping NPS 2 and smaller, adjacent to each valve and at final connection to each piece of equipment.

2. Install flanges, in piping NPS 2-1/2 and larger, adjacent to flanged valves and at final connection to each piece of equipment.

3. Wet Piping Systems: Install dielectric coupling and nipple fittings to connect piping materials of dissimilar metals.

3.4 EQUIPMENT INSTALLATION - COMMON REQUIREMENTS

A. Install equipment to allow maximum possible headroom unless specific mounting heights are not indicated.

B. Install equipment level and plumb, parallel and perpendicular to other building systems and components in exposed interior spaces, unless otherwise indicated.

C. Install equipment to facilitate service, maintenance, and repair or replacement of components. Connect equipment for ease of disconnecting, with minimum interference to other installations. Extend grease fittings to accessible locations.

D. Install equipment to allow right of way for piping installed at required slope.

3.5 CONCRETE BASES

A. Concrete Bases: Anchor equipment to concrete base according to equipment manufacturer's written instructions and according to seismic codes at Project.

1. Construct concrete bases of dimensions indicated, but not less than 4 inches larger in both directions than supported unit.

2. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch centers around the full perimeter of the base.

3. Install epoxy-coated anchor bolts for supported equipment that extend through concrete base, and anchor into structural concrete floor.

4. Place and secure anchorage devices. Use supported equipment manufacturer's setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded.

5. Install anchor bolts to elevations required for proper attachment to supported equipment. 6. Install anchor bolts according to anchor-bolt manufacturer's written instructions. 7. Use 3000-psi, 28-day compressive-strength concrete and reinforcement as specified in

Architecture 3 Section.

Page 7: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 7 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

3.6 ERECTION OF METAL SUPPORTS AND ANCHORAGES

A. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation to support and anchor HVAC materials and equipment.

B. Field Welding: Comply with AWS D1.1.

3.7 ERECTION OF WOOD SUPPORTS AND ANCHORAGES

A. Cut, fit, and place wood grounds, nailers, blocking, and anchorages to support, and anchor HVAC materials and equipment.

B. Select fastener sizes that will not penetrate members if opposite side will be exposed to view or will receive finish materials. Tighten connections between members. Install fasteners without splitting wood members.

C. Attach to substrates as required to support applied loads.

3.8 GROUTING

A. Mix and install grout for HVAC equipment base bearing surfaces, pump and other equipment base plates, and anchors.

B. Clean surfaces that will come into contact with grout.

C. Provide forms as required for placement of grout.

D. Avoid air entrapment during placement of grout.

E. Place grout, completely filling equipment bases.

F. Place grout on concrete bases and provide smooth bearing surface for equipment.

G. Place grout around anchors.

H. Cure placed grout.

END OF SECTION 15050

Page 8: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15060 – HVAC & PLUMBING - HANGERS AND SUPPORTS FOR PIPING AND EQUIPMENT

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes the following:

1. Steel pipe hangers and supports. 2. Trapeze pipe hangers. 3. Metal framing systems. 4. Thermal-hanger shield inserts. 5. Equipment supports.

1.2 DEFINITIONS

A. Terminology: As defined in MSS SP-90, "Guidelines on Terminology for Pipe Hangers and Supports."

1.3 PERFORMANCE REQUIREMENTS

A. Design supports for multiple pipes capable of supporting combined weight of supported systems, system contents, and test water.

B. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.

1.4 SUBMITTALS

A. Product Data: For the following:

1. Steel pipe hangers and supports. 2. Thermal-hanger shield inserts.

B. Shop Drawings: Show fabrication and installation details and include calculations for the following:

1. Trapeze pipe hangers. Include Product Data for components. 2. Metal framing systems. Include Product Data for components. 3. Equipment supports.

C. Welding certificates.

1.5 QUALITY ASSURANCE

A. Welding: Qualify procedures and personnel according to ASME Boiler and Pressure Vessel Code: Section IX.

Page 9: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. In other Part 2 articles where titles below introduce lists, the following requirements apply to product selection:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, manufacturers specified.

2.2 STEEL PIPE HANGERS AND SUPPORTS

A. Description: MSS SP-58, Types 1 through 58, factory-fabricated components. Refer to Part 3 "Hanger and Support Applications" Article for where to use specific hanger and support types.

B. Available Manufacturers:

1. B-Line Systems, Inc.; a division of Cooper Industries. 2. ERICO/Michigan Hanger Co. 3. Grinnell Corp. 4. PHD Manufacturing, Inc. 5. PHS Industries, Inc. 6. Piping Technology & Products, Inc. 7. Tolco Inc.

C. Galvanized, Metallic Coatings: Pregalvanized or hot dipped.

D. Nonmetallic Coatings: Plastic coating, jacket, or liner.

E. Padded Hangers: Hanger with fiberglass or other pipe insulation pad or cushion for support of bearing surface of piping.

2.3 TRAPEZE PIPE HANGERS

A. Description: MSS SP-69, Type 59, shop- or field-fabricated pipe-support assembly made from structural-steel shapes with MSS SP-58 hanger rods, nuts, saddles, and U-bolts.

2.4 METAL FRAMING SYSTEMS

A. Description: MFMA-3, shop- or field-fabricated pipe-support assembly made of steel channels and other components.

B. Available Manufacturers:

1. B-Line Systems, Inc.; a division of Cooper Industries. 2. ERICO/Michigan Hanger Co.; ERISTRUT Div. 3. GS Metals Corp. 4. Power-Strut Div.; Tyco International, Ltd. 5. Thomas & Betts Corporation. 6. Tolco Inc. 7. Unistrut Corp.; Tyco International, Ltd.

C. Coatings: Manufacturer's standard finish, unless bare metal surfaces are indicated.

Page 10: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

D. Nonmetallic Coatings: Plastic coating, jacket, or liner.

2.5 THERMAL-HANGER SHIELD INSERTS

A. Description: 100-psig- minimum, compressive-strength insulation insert encased in sheet metal shield.

B. Available Manufacturers:

1. Carpenter & Paterson, Inc. 2. ERICO/Michigan Hanger Co. 3. PHS Industries, Inc. 4. Pipe Shields, Inc. 5. Rilco Manufacturing Company, Inc. 6. Value Engineered Products, Inc.

C. Insulation-Insert Material for Cold Piping: Water-repellent treated, ASTM C 533, Type I calcium silicate with vapor barrier.

D. Insulation-Insert Material for Hot Piping: Water-repellent treated, ASTM C 533, Type I calcium silicate.

E. For Trapeze or Clamped Systems: Insert and shield shall cover entire circumference of pipe.

F. For Clevis or Band Hangers: Insert and shield shall cover lower 180 degrees of pipe.

G. Insert Length: Extend 2 inches beyond sheet metal shield for piping operating below ambient air temperature.

2.6 EQUIPMENT SUPPORTS

A. Description: Welded, shop- or field-fabricated equipment support made from structural-steel shapes.

2.7 MISCELLANEOUS MATERIALS

A. Structural Steel: ASTM A 36/A 36M, steel plates, shapes, and bars; black and galvanized.

B. Grout: ASTM C 1107, factory-mixed and -packaged, dry, hydraulic-cement, nonshrink and nonmetallic grout; suitable for interior and exterior applications.

1. Properties: Nonstaining, noncorrosive, and nongaseous. 2. Design Mix: 5000-psi, 28-day compressive strength.

PART 3 - EXECUTION

3.1 HANGER AND SUPPORT APPLICATIONS

A. Specific hanger and support requirements are specified in Sections specifying piping systems and equipment.

B. Comply with MSS SP-69 for pipe hanger selections and applications that are not specified in piping system Sections.

C. Use hangers and supports with galvanized, metallic coatings for piping and equipment that will not have field-applied finish.

Page 11: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

D. Use nonmetallic coatings on attachments for electrolytic protection where attachments are in direct contact with copper tubing.

E. Use padded hangers for piping that is subject to scratching.

F. Horizontal-Piping Hangers and Supports: Unless otherwise indicated and except as specified in piping system Sections, install the following types:

1. Adjustable, Steel Clevis Hangers (MSS Type 1): For suspension of noninsulated or insulated stationary pipes, NPS 1/2 to NPS 30.

2. Yoke-Type Pipe Clamps (MSS Type 2): For suspension of 120 to 450 deg F pipes, NPS 4 to NPS 16, requiring up to 4 inches of insulation.

3. Carbon- or Alloy-Steel, Double-Bolt Pipe Clamps (MSS Type 3): For suspension of pipes, NPS 3/4 to NPS 24, requiring clamp flexibility and up to 4 inches of insulation.

4. Adjustable, Steel Band Hangers (MSS Type 7): For suspension of noninsulated stationary pipes, NPS 1/2 to NPS 8.

5. U-Bolts (MSS Type 24): For support of heavy pipes, NPS 1/2 to NPS 30. 6. Pipe Saddle Supports (MSS Type 36): For support of pipes, NPS 4 to NPS 36, with steel pipe

base stanchion support and cast-iron floor flange. 7. Single Pipe Rolls (MSS Type 41): For suspension of pipes, NPS 1 to NPS 30, from 2 rods if

longitudinal movement caused by expansion and contraction might occur. 8. Complete Pipe Rolls (MSS Type 44): For support of pipes, NPS 2 to NPS 42, if longitudinal

movement caused by expansion and contraction might occur but vertical adjustment is not necessary.

G. Vertical-Piping Clamps: Unless otherwise indicated and except as specified in piping system Sections, install the following types:

1. Extension Pipe or Riser Clamps (MSS Type 8): For support of pipe risers, NPS 3/4 to NPS 20. 2. Carbon- or Alloy-Steel Riser Clamps (MSS Type 42): For support of pipe risers, NPS 3/4 to

NPS 20, if longer ends are required for riser clamps.

H. Hanger-Rod Attachments: Unless otherwise indicated and except as specified in piping system Sections, install the following types:

1. Steel Turnbuckles (MSS Type 13): For adjustment up to 6 inches for heavy loads. 2. Steel Clevises (MSS Type 14): For 120 to 450 deg F piping installations.

I. Building Attachments: Unless otherwise indicated and except as specified in piping system Sections, install the following types:

1. Steel or Malleable Concrete Inserts (MSS Type 18): For upper attachment to suspend pipe hangers from concrete ceiling.

2. Top-Beam C-Clamps (MSS Type 19): For use under roof installations with bar-joist construction to attach to top flange of structural shape.

3. Side-Beam or Channel Clamps (MSS Type 20): For attaching to bottom flange of beams, channels, or angles.

4. Center-Beam Clamps (MSS Type 21): For attaching to center of bottom flange of beams. 5. Welded Beam Attachments (MSS Type 22): For attaching to bottom of beams if loads are

considerable and rod sizes are large. 6. C-Clamps (MSS Type 23): For structural shapes. 7. Welded-Steel Brackets: For support of pipes from below, or for suspending from above by using

clip and rod. Use one of the following for indicated loads:

a. Light (MSS Type 31): 750 lb. b. Medium (MSS Type 32): 1500 lb. c. Heavy (MSS Type 33): 3000 lb.

8. Side-Beam Brackets (MSS Type 34): For sides of steel or wooden beams. 9. Plate Lugs (MSS Type 57): For attaching to steel beams if flexibility at beam is required.

Page 12: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

J. Saddles and Shields: Unless otherwise indicated and except as specified in piping system Sections, install the following types:

1. Steel Pipe-Covering Protection Saddles (MSS Type 39): To fill interior voids with insulation that matches adjoining insulation.

2. Protection Shields (MSS Type 40): Of length recommended in writing by manufacturer to prevent crushing insulation.

3. Thermal-Hanger Shield Inserts: For supporting insulated pipe.

K. Spring Hangers and Supports: Unless otherwise indicated and except as specified in piping system Sections, install the following types:

1. Spring Cushions (MSS Type 48): For light loads if vertical movement does not exceed 1-1/4 inches.

2. Spring-Cushion Roll Hangers (MSS Type 49): For equipping Type 41 roll hanger with springs. 3. Variable-Spring Base Supports (MSS Type 52): Preset to indicated load and limit variability factor

to 25 percent to absorb expansion and contraction of piping system from base support.

L. Comply with MSS SP-69 for trapeze pipe hanger selections and applications that are not specified in piping system Sections.

M. Comply with MFMA-102 for metal framing system selections and applications that are not specified in piping system Sections.

3.2 HANGER AND SUPPORT INSTALLATION

A. Steel Pipe Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Install hangers, supports, clamps, and attachments as required to properly support piping from building structure.

B. Trapeze Pipe Hanger Installation: Comply with MSS SP-69 and MSS SP-89. Arrange for grouping of parallel runs of horizontal piping and support together on field-fabricated trapeze pipe hangers.

1. Pipes of Various Sizes: Support together and space trapezes for smallest pipe size or install intermediate supports for smaller diameter pipes as specified above for individual pipe hangers.

2. Field fabricate from ASTM A 36/A 36M, steel shapes selected for loads being supported. Weld steel according to AWS D1.1.

C. Metal Framing System Installation: Arrange for grouping of parallel runs of piping and support together on field-assembled metal framing systems.

D. Thermal-Hanger Shield Installation: Install in pipe hanger or shield for insulated piping.

E. Install hangers and supports complete with necessary inserts, bolts, rods, nuts, washers, and other accessories.

F. Equipment Support Installation: Fabricate from welded-structural-steel shapes.

G. Install hangers and supports to allow controlled thermal and seismic movement of piping systems, to permit freedom of movement between pipe anchors, and to facilitate action of expansion joints, expansion loops, expansion bends, and similar units.

H. Install lateral bracing with pipe hangers and supports to prevent swaying.

I. Install building attachments within concrete slabs or attach to structural steel. Install additional attachments at concentrated loads, including valves, flanges, and strainers, NPS 2-1/2 and larger and at changes in direction of piping. Install concrete inserts before concrete is placed; fasten inserts to forms and install reinforcing bars through openings at top of inserts.

Page 13: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 6 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

J. Load Distribution: Install hangers and supports so piping live and dead loads and stresses from movement will not be transmitted to connected equipment.

K. Pipe Slopes: Install hangers and supports to provide indicated pipe slopes and so maximum pipe deflections allowed by ASME B31.1 (for power piping) and ASME B31.9 (for building services piping) are not exceeded.

L. Insulated Piping: Comply with the following:

1. Attach clamps and spacers to piping.

a. Piping Operating above Ambient Air Temperature: Clamp may project through insulation. b. Piping Operating below Ambient Air Temperature: Use thermal-hanger shield insert with

clamp sized to match OD of insert. c. Do not exceed pipe stress limits according to ASME B31.1 for power piping and

ASME B31.9 for building services piping.

2. Install MSS SP-58, Type 39, protection saddles if insulation without vapor barrier is indicated. Fill interior voids with insulation that matches adjoining insulation.

3. Install MSS SP-58, Type 40, protective shields on cold piping with vapor barrier. Shields shall span an arc of 180 degrees.

4. Shield Dimensions for Pipe: Not less than the following:

a. NPS 1/4 to NPS 3-1/2: 12 inches long and 0.048 inch thick. b. NPS 4: 12 inches long and 0.06 inch thick. c. NPS 5 and NPS 6: 18 inches long and 0.06 inch thick. d. NPS 8 to NPS 14: 24 inches long and 0.075 inch thick. e. NPS 16 to NPS 24: 24 inches long and 0.105 inch thick.

5. Pipes NPS 8 and Larger: Include wood inserts. 6. Insert Material: Length at least as long as protective shield. 7. Thermal-Hanger Shields: Install with insulation same thickness as piping insulation.

3.3 EQUIPMENT SUPPORTS

A. Fabricate structural-steel stands to suspend equipment from structure overhead or to support equipment above floor.

B. Grouting: Place grout under supports for equipment and make smooth bearing surface.

C. Provide lateral bracing, to prevent swaying, for equipment supports.

3.4 METAL FABRICATIONS

A. Cut, drill, and fit miscellaneous metal fabrications for trapeze pipe hangers and equipment supports.

B. Fit exposed connections together to form hairline joints. Field weld connections that cannot be shop welded because of shipping size limitations.

C. Field Welding: Comply with AWS D1.1 procedures for shielded metal arc welding, appearance and quality of welds, and methods used in correcting welding work, and with the following:

1. Use materials and methods that minimize distortion and develop strength and corrosion resistance of base metals.

2. Obtain fusion without undercut or overlap. 3. Remove welding flux immediately.

Page 14: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 7 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

4. Finish welds at exposed connections so no roughness shows after finishing and contours of welded surfaces match adjacent contours.

3.5 ADJUSTING

A. Hanger Adjustments: Adjust hangers to distribute loads equally on attachments and to achieve indicated slope of pipe.

3.6 PAINTING

A. Touch Up: Clean field welds and abraded areas of shop paint. Paint exposed areas immediately after erecting hangers and supports. Use same materials as used for shop painting. Comply with SSPC-PA 1 requirements for touching up field-painted surfaces.

1. Apply paint by brush or spray to provide minimum dry film thickness of 2.0 mils.

B. Galvanized Surfaces: Clean welds, bolted connections, and abraded areas and apply galvanizing-repair paint to comply with ASTM A 780.

END OF SECTION 15060

Page 15: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 2

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15075 - IDENTIFICATION FOR HVAC & PLUMBING PIPING AND EQUIPMENT

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Equipment labels. 2. Warning signs and labels. 3. Pipe labels. 4. Duct labels.

1.2 SUBMITTAL

A. Product Data: For each type of product indicated.

PART 2 - PRODUCTS

2.1 EQUIPMENT LABELS

A. Plastic Labels for Equipment:

1. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/16 inch thick, and having predrilled holes for attachment hardware.

2. Letter Color: Site Standard. 3. Background Color: Site Standard. 4. Maximum Temperature: Able to withstand temperatures up to 160 deg F. 5. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by

3/4 inch. 6. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2 inch

for viewing distances up to 72 inches, and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering.

7. Fasteners: Stainless-steel rivets or self-tapping screws. 8. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.

B. Label Content: Include equipment's Drawing designation or unique equipment number, Drawing numbers where equipment is indicated (plans, details, and schedules), plus the Specification Section number and title where equipment is specified.

2.2 PIPE LABELS

A. General Requirements for Manufactured Pipe Labels: Preprinted, color-coded, with lettering indicating service, and showing flow direction.

B. Pretensioned Pipe Labels: Precoiled, semirigid plastic formed to cover full circumference of pipe and to attach to pipe without fasteners or adhesive.

C. Pipe Label Contents: Include identification of piping service using same designations or abbreviations as used on Drawings, pipe size, and an arrow indicating flow direction.

Page 16: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 2

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1. Flow-Direction Arrows: Integral with piping system service lettering to accommodate both directions, or as separate unit on each pipe label to indicate flow direction.

2. Lettering Size: At least 1-1/2 inches high.

2.3 DUCT LABELS

A. Adhesive: Contact-type permanent adhesive, compatible with label and with substrate.

B. Duct Label Contents: Include identification of duct service using same designations or abbreviations as used on Drawings, duct size, and an arrow indicating flow direction.

1. Flow-Direction Arrows: Integral with duct system service lettering to accommodate both directions, or as separate unit on each duct label to indicate flow direction.

2. Lettering Size: At least 1-1/2 inches high.

PART 3 - EXECUTION

3.1 PREPARATION

A. Clean piping and equipment surfaces of substances that could impair bond of identification devices, including dirt, oil, grease, release agents, and incompatible primers, paints, and encapsulants.

3.2 EQUIPMENT LABEL INSTALLATION

A. Install or permanently fasten labels on each major item of mechanical equipment.

B. Locate equipment labels where accessible and visible.

3.3 PIPE LABEL INSTALLATION

A. Locate pipe labels where piping is exposed or above accessible ceilings in finished spaces; machine rooms; accessible maintenance spaces such as shafts, tunnels, and plenums; and exterior exposed locations as follows:

1. Near each valve and control device. 2. Near each branch connection, excluding short takeoffs for fixtures and terminal units. Where flow

pattern is not obvious, mark each pipe at branch. 3. Near penetrations through walls, floors, ceilings, and inaccessible enclosures. 4. At access doors, manholes, and similar access points that permit view of concealed piping. 5. Near major equipment items and other points of origination and termination. 6. Spaced at maximum intervals of 50 feet along each run. Reduce intervals to 25 feet in areas of

congested piping and equipment. 7. On piping above removable acoustical ceilings. Omit intermediately spaced labels.

3.4 DUCT LABEL INSTALLATION

A. Locate labels near points where ducts enter into concealed spaces and at maximum intervals of 50 feet in each space where ducts are exposed or concealed by removable ceiling system.

END OF SECTION 15075

Page 17: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 9

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15082 - PLUMBING INSULATION

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Insulation Materials:

a. Cellular glass. b. Flexible elastomeric.

2. Insulating accessories.

1.2 SUBMITTALS

A. Product Data: For each type of product indicated.

1.3 QUALITY ASSURANCE

A. Insulation must be listed and approved for use in return air plenums.

B. Fire-Test-Response Characteristics: Insulation and related materials shall have fire-test-response characteristics indicated, as determined by testing identical products per ASTM E 84, by a testing and inspecting agency acceptable to authorities having jurisdiction. Factory label insulation and jacket materials and adhesive, mastic, tapes, and cement material containers, with appropriate markings of applicable testing and inspecting agency.

1. Insulation Installed Indoors: Flame-spread index of 25 or less, and smoke-developed index of 50 or less.

2. Insulation Installed Outdoors: Flame-spread index of 75 or less, and smoke-developed index of 150 or less.

PART 2 - PRODUCTS

2.1 INSULATION MATERIALS

A. Products shall not contain asbestos, lead, mercury, or mercury compounds.

B. Products that come in contact with stainless steel shall have a leachable chloride content of less than 50 ppm when tested according to ASTM C 871.

C. Foam insulation materials shall not use CFC or HCFC blowing agents in the manufacturing process.

D. Flexible Elastomeric: Closed-cell, sponge- or expanded-rubber materials. Comply with ASTM C 534, Type I for tubular materials and Type II for sheet materials.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

Page 18: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 9

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

a. Aeroflex USA Inc.; Aerocel. b. Armacell LLC; AP Armaflex.

E. Mineral-Fiber, Preformed Pipe Insulation:

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following: a. Johns Manville; Micro-Lok. b. Knauf Insulation; 1000 Pipe Insulation. c. Manson Insulation Inc.; Alley-K. d. Owens Corning; Fiberglas Pipe Insulation.

2.2 INSULATING CEMENTS

A. Mineral-Fiber, Hydraulic-Setting Insulating and Finishing Cement: Comply with ASTM C 449/C 449M.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. Insulco, Division of MFS, Inc.; SmoothKote. b. P. K. Insulation Mfg. Co., Inc.; PK No. 127, and Quik-Cote. c. Rock Wool Manufacturing Company; Delta One Shot.

2.3 ADHESIVES

A. Materials shall be compatible with insulation materials, jackets, and substrates and for bonding insulation to itself and to surfaces to be insulated, unless otherwise indicated.

B. Flexible Elastomeric and Polyolefin Adhesive: Comply with MIL-A-24179A, Type II, Class I.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. Aeroflex USA Inc.; Aeroseal. b. Armacell LCC; 520 Adhesive.

2. For indoor applications, use adhesive that has a VOC content of 50 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24).

C. Mineral-Fiber Adhesive: Comply with MIL-A-3316C, Class 2, Grade A.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. Childers Products, Division of ITW; CP-82. b. Foster Products Corporation, H. B. Fuller Company; 85-20. c. ITW TACC, Division of Illinois Tool Works; S-90/80. d. Marathon Industries, Inc.; 225. e. Mon-Eco Industries, Inc.; 22-25.

2. For indoor applications, use adhesive that has a VOC content of 80 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24).

2.4 FIELD-APPLIED JACKETS

A. Field-applied jackets shall comply with ASTM C 921, Type I, unless otherwise indicated.

Page 19: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 9

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

B. PVC Jacket: High-impact-resistant, UV-resistant PVC complying with ASTM D 1784, Class 16354-C; thickness as scheduled; roll stock ready for shop or field cutting and forming. Thickness is indicated in field-applied jacket schedules.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. Johns Manville; Zeston. b. P.I.C. Plastics, Inc.; FG Series. c. Proto PVC Corporation; LoSmoke. d. Speedline Corporation; SmokeSafe.

2. Adhesive: As recommended by jacket material manufacturer. 3. Color: White. 4. Factory-fabricated fitting covers to match jacket if available; otherwise, field fabricate.

a. Shapes: 45- and 90-degree, short- and long-radius elbows, tees, valves, flanges, unions, reducers, end caps, soil-pipe hubs, traps, mechanical joints, and P-trap and supply covers for lavatories.

5. Factory-fabricated tank heads and tank side panels.

2.5 TAPES

A. ASJ Tape: White vapor-retarder tape matching factory-applied jacket with acrylic adhesive, complying with ASTM C 1136.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. Avery Dennison Corporation, Specialty Tapes Division; Fasson 0835. b. Compac Corp.; 104 and 105. c. Ideal Tape Co., Inc., an American Biltrite Company; 428 AWF ASJ. d. Venture Tape; 1540 CW Plus, 1542 CW Plus, and 1542 CW Plus/SQ.

2. ASJ Tape Disks and Squares: Precut disks or squares of ASJ tape.

B. PVC Tape: White vapor-retarder tape matching field-applied PVC jacket with acrylic adhesive. Suitable for indoor and outdoor applications.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. Avery Dennison Corporation, Specialty Tapes Division; Fasson 0555. b. Compac Corp.; 130. c. Ideal Tape Co., Inc., an American Biltrite Company; 370 White PVC tape. d. Venture Tape; 1506 CW NS.

2.6 SECUREMENTS

A. Insulation Pins and Hangers:

1. Metal, Adhesively Attached, Perforated-Base Insulation Hangers: Baseplate welded to projecting spindle that is capable of holding insulation, of thickness indicated, securely in position indicated when self-locking washer is in place. Comply with the following requirements:

a. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

Page 20: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 9

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1) AGM Industries, Inc.; Tactoo Insul-Hangers, Series T. 2) GEMCO; Perforated Base. 3) Midwest Fasteners, Inc.; Spindle.

b. Baseplate: Perforated, galvanized carbon-steel sheet, 0.030 inch thick by 2 inches square. c. Spindle: Copper- or zinc-coated, fully annealed, 0.106-inch diameter shank, length to suit

depth of insulation indicated. d. Adhesive: Recommended by hanger manufacturer. Product with demonstrated capability

to bond insulation hanger securely to substrates indicated without damaging insulation, hangers, and substrates.

B. Staples: Outward-clinching insulation staples, nominal 3/4-inch wide, stainless steel or Monel.

PART 3 - EXECUTION

3.1 PREPARATION

A. Surface Preparation: Clean and dry surfaces to receive insulation. Remove materials that will adversely affect insulation application.

B. Coordinate insulation installation with the trade installing heat tracing. Comply with requirements for heat tracing that apply to insulation.

C. Mix insulating cements with clean potable water; if insulating cements are to be in contact with stainless-steel surfaces, use demineralized water.

3.2 GENERAL INSTALLATION REQUIREMENTS

A. Install insulation materials, accessories, and finishes with smooth, straight, and even surfaces; free of voids throughout the length of equipment and piping including fittings, valves, and specialties.

B. Install insulation materials, forms, vapor barriers or retarders, jackets, and thicknesses required for each item of equipment and pipe system as specified in insulation system schedules.

C. Install accessories compatible with insulation materials and suitable for the service. Install accessories that do not corrode, soften, or otherwise attack insulation or jacket in either wet or dry state.

D. Install insulation with longitudinal seams at top and bottom of horizontal runs.

E. Install multiple layers of insulation with longitudinal and end seams staggered.

F. Do not weld brackets, clips, or other attachment devices to piping, fittings, and specialties.

G. Keep insulation materials dry during application and finishing.

H. Install insulation with tight longitudinal seams and end joints. Bond seams and joints with adhesive recommended by insulation material manufacturer.

I. Install insulation with least number of joints practical.

J. Where vapor barrier is indicated, seal joints, seams, and penetrations in insulation at hangers, supports, anchors, and other projections with vapor-barrier mastic.

1. Install insulation continuously through hangers and around anchor attachments.

Page 21: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 9

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2. For insulation application where vapor barriers are indicated, extend insulation on anchor legs from point of attachment to supported item to point of attachment to structure. Taper and seal ends at attachment to structure with vapor-barrier mastic.

3. Install insert materials and install insulation to tightly join the insert. Seal insulation to insulation inserts with adhesive or sealing compound recommended by insulation material manufacturer.

4. Cover inserts with jacket material matching adjacent pipe insulation. Install shields over jacket, arranged to protect jacket from tear or puncture by hanger, support, and shield.

K. Apply adhesives, mastics, and sealants at manufacturer's recommended coverage rate and wet and dry film thicknesses.

L. Install insulation with factory-applied jackets as follows:

1. Draw jacket tight and smooth. 2. Cover circumferential joints with 3-inchwide strips, of same material as insulation jacket. Secure

strips with adhesive and outward clinching staples along both edges of strip, spaced 4 inches o.c. 3. Overlap jacket longitudinal seams at least 1-1/2 inches. Install insulation with longitudinal seams at

bottom of pipe. Clean and dry surface to receive self-sealing lap. Staple laps with outward clinching staples along edge at 4 inches o.c.

a. For below ambient services, apply vapor-barrier mastic over staples.

4. Cover joints and seams with tape as recommended by insulation material manufacturer to maintain vapor seal.

5. Where vapor barriers are indicated, apply vapor-barrier mastic on seams and joints and at ends adjacent to pipe flanges and fittings.

M. Cut insulation in a manner to avoid compressing insulation more than 75 percent of its nominal thickness.

N. Finish installation with systems at operating conditions. Repair joint separations and cracking due to thermal movement.

O. Repair damaged insulation facings by applying same facing material over damaged areas. Extend patches at least 4 inches beyond damaged areas. Adhere, staple, and seal patches similar to butt joints.

P. For above ambient services, do not install insulation to the following:

1. Vibration-control devices. 2. Testing agency labels and stamps. 3. Nameplates and data plates. 4. Manholes. 5. Handholes. 6. Cleanouts.

3.3 PENETRATIONS

A. Insulation Installation at Roof Penetrations: Install insulation continuously through roof penetrations.

1. Seal penetrations with flashing sealant. 2. For applications requiring only indoor insulation, terminate insulation above roof surface and seal

with joint sealant. For applications requiring indoor and outdoor insulation, install insulation for outdoor applications tightly joined to indoor insulation ends. Seal joint with joint sealant.

3. Extend jacket of outdoor insulation outside roof flashing at least 2 inches below top of roof flashing. 4. Seal jacket to roof flashing with flashing sealant.

B. Insulation Installation at Underground Exterior Wall Penetrations: Terminate insulation flush with sleeve seal. Seal terminations with flashing sealant.

Page 22: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 6 of 9

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

C. Insulation Installation at Aboveground Exterior Wall Penetrations: Install insulation continuously through wall penetrations.

1. Seal penetrations with flashing sealant. 2. For applications requiring only indoor insulation, terminate insulation inside wall surface and seal

with joint sealant. For applications requiring indoor and outdoor insulation, install insulation for outdoor applications tightly joined to indoor insulation ends. Seal joint with joint sealant.

3. Extend jacket of outdoor insulation outside wall flashing and overlap wall flashing at least 2 inches. 4. Seal jacket to wall flashing with flashing sealant.

D. Insulation Installation at Interior Wall and Partition Penetrations (That Are Not Fire Rated): Install insulation continuously through walls and partitions.

E. Insulation Installation at Fire-Rated Wall and Partition Penetrations: Install insulation continuously through penetrations of fire-rated walls and partitions.

1. Comply with requirements in Division 7 Section "Through-Penetration Firestop Systems" for firestopping and fire-resistive joint sealers.

F. Insulation Installation at Floor Penetrations:

1. Pipe: Install insulation continuously through floor penetrations. 2. Seal penetrations through fire-rated assemblies. Comply with requirements in Division 7 Section

"Through-Penetration Firestop Systems."

3.4 GENERAL PIPE INSULATION INSTALLATION

A. Requirements in this article generally apply to all insulation materials except where more specific requirements are specified in various pipe insulation material installation articles.

B. Insulation Installation on Fittings, Valves, Strainers, Flanges, and Unions:

1. Install insulation over fittings, valves, strainers, flanges, unions, and other specialties with continuous thermal and vapor-retarder integrity, unless otherwise indicated.

2. Insulate pipe elbows using preformed fitting insulation or mitered fittings made from same material and density as adjacent pipe insulation. Each piece shall be butted tightly against adjoining piece and bonded with adhesive. Fill joints, seams, voids, and irregular surfaces with insulating cement finished to a smooth, hard, and uniform contour that is uniform with adjoining pipe insulation.

3. Insulate tee fittings with preformed fitting insulation or sectional pipe insulation of same material and thickness as used for adjacent pipe. Cut sectional pipe insulation to fit. Butt each section closely to the next and hold in place with tie wire. Bond pieces with adhesive.

4. Insulate valves using preformed fitting insulation or sectional pipe insulation of same material, density, and thickness as used for adjacent pipe. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. For valves, insulate up to and including the bonnets, valve stuffing-box studs, bolts, and nuts. Fill joints, seams, and irregular surfaces with insulating cement.

5. Insulate strainers using preformed fitting insulation or sectional pipe insulation of same material, density, and thickness as used for adjacent pipe. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker. Fill joints, seams, and irregular surfaces with insulating cement. Insulate strainers so strainer basket flange or plug can be easily removed and replaced without damaging the insulation and jacket. Provide a removable reusable insulation cover. For below ambient services, provide a design that maintains vapor barrier.

6. Insulate flanges and unions using a section of oversized preformed pipe insulation. Overlap adjoining pipe insulation by not less than two times the thickness of pipe insulation, or one pipe diameter, whichever is thicker.

7. Cover segmented insulated surfaces with a layer of finishing cement and coat with a mastic. Install vapor-barrier mastic for below ambient services and a breather mastic for above ambient services.

Page 23: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 7 of 9

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

Reinforce the mastic with fabric-reinforcing mesh. Trowel the mastic to a smooth and well-shaped contour.

8. For services not specified to receive a field-applied jacket except for flexible elastomeric and polyolefin, install fitted PVC cover over elbows, tees, strainers, valves, flanges, and unions. Terminate ends with PVC end caps. Tape PVC covers to adjoining insulation facing using PVC tape.

9. Stencil or label the outside insulation jacket of each union with the word "UNION." Match size and color of pipe labels.

C. Insulate instrument connections for thermometers, pressure gages, pressure temperature taps, test connections, flow meters, sensors, switches, and transmitters on insulated pipes, vessels, and equipment. Shape insulation at these connections by tapering it to and around the connection with insulating cement and finish with finishing cement, mastic, and flashing sealant.

3.5 FLEXIBLE ELASTOMERIC INSULATION INSTALLATION

A. Seal longitudinal seams and end joints with manufacturer's recommended adhesive to eliminate openings in insulation that allow passage of air to surface being insulated.

B. Insulation Installation on Pipe Flanges:

1. Install pipe insulation to outer diameter of pipe flange. 2. Make width of insulation section same as overall width of flange and bolts, plus twice the thickness

of pipe insulation. 3. Fill voids between inner circumference of flange insulation and outer circumference of adjacent

straight pipe segments with cut sections of sheet insulation of same thickness as pipe insulation. 4. Secure insulation to flanges and seal seams with manufacturer's recommended adhesive to

eliminate openings in insulation that allow passage of air to surface being insulated.

C. Insulation Installation on Pipe Fittings and Elbows:

1. Install mitered sections of pipe insulation. 2. Secure insulation materials and seal seams with manufacturer's recommended adhesive to

eliminate openings in insulation that allow passage of air to surface being insulated.

D. Insulation Installation on Valves and Pipe Specialties:

1. Install preformed valve covers manufactured of same material as pipe insulation when available. 2. When preformed valve covers are not available, install cut sections of pipe and sheet insulation to

valve body. Arrange insulation to permit access to packing and to allow valve operation without disturbing insulation.

3. Install insulation to flanges as specified for flange insulation application. 4. Secure insulation to valves and specialties and seal seams with manufacturer's recommended

adhesive to eliminate openings in insulation that allow passage of air to surface being insulated.

3.6 MINERAL-FIBER INSULATION INSTALLATION

A. Insulation Installation on Straight Pipes and Tubes:

1. Secure each layer of preformed pipe insulation to pipe with wire or bands and tighten bands without deforming insulation materials.

2. Where vapor barriers are indicated, seal longitudinal seams, end joints, and protrusions with vapor-barrier mastic and joint sealant.

3. For insulation with factory-applied jackets on above ambient surfaces, secure laps with outward clinched staples at 6 inches o.c.

4. For insulation with factory-applied jackets on below ambient surfaces, do not staple longitudinal tabs but secure tabs with additional adhesive as recommended by insulation material manufacturer and seal with vapor-barrier mastic and flashing sealant.

Page 24: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 8 of 9

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

B. Insulation Installation on Pipe Flanges:

1. Install preformed pipe insulation to outer diameter of pipe flange. 2. Make width of insulation section same as overall width of flange and bolts, plus twice the thickness

of pipe insulation. 3. Fill voids between inner circumference of flange insulation and outer circumference of adjacent

straight pipe segments with mineral-fiber blanket insulation. 4. Install jacket material with manufacturer's recommended adhesive, overlap seams at least 1 inch ,

and seal joints with flashing sealant.

C. Insulation Installation on Pipe Fittings and Elbows:

1. Install preformed sections of same material as straight segments of pipe insulation when available. 2. When preformed insulation elbows and fittings are not available, install mitered sections of pipe

insulation, to a thickness equal to adjoining pipe insulation. Secure insulation materials with wire or bands.

D. Insulation Installation on Valves and Pipe Specialties:

1. Install preformed sections of same material as straight segments of pipe insulation when available. 2. When preformed sections are not available, install mitered sections of pipe insulation to valve body. 3. Arrange insulation to permit access to packing and to allow valve operation without disturbing

insulation. 4. Install insulation to flanges as specified for flange insulation application.

3.7 FINISHES

A. Equipment and Pipe Insulation with ASJ or Other Paintable Jacket Material: Paint jacket with paint system identified below and as specified in Division 9 painting Sections.

1. Flat Acrylic Finish: Two finish coats over a primer that is compatible with jacket material and finish coat paint. Add fungicidal agent to render fabric mildew proof.

a. Finish Coat Material: Interior, flat, latex-emulsion size.

B. Flexible Elastomeric Thermal Insulation: After adhesive has fully cured, apply two coats of insulation manufacturer's recommended protective coating.

C. Color: Final color as selected by Architect. Vary first and second coats to allow visual inspection of the completed Work.

D. Do not field paint aluminum or stainless-steel jackets.

3.8 FIELD QUALITY CONTROL

A. Perform tests and inspections.

B. Tests and Inspections:

1. Inspect field-insulated materials randomly selected by Architect, by removing field-applied jacket and insulation in layers in reverse order of their installation. Extent of inspection shall be limited to one location(s) for each type of equipment defined in the "Equipment Insulation Schedule" Article. For large equipment, remove only a portion adequate to determine compliance.

C. All insulation applications will be considered defective Work if sample inspection reveals noncompliance with requirements.

Page 25: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 9 of 9

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

3.9 PIPING INSULATION SCHEDULE, GENERAL

A. Acceptable preformed pipe and tubular insulation materials and thicknesses are identified for each piping system and pipe size range. If more than one material is listed for a piping system, selection from materials listed is Contractor's option.

B. Items Not Insulated: Unless otherwise indicated, do not install insulation on the following:

1. Drainage piping located in crawl spaces. 2. Underground piping. 3. Chrome-plated pipes and fittings unless there is a potential for personnel injury.

3.10 INDOOR PIPING INSULATION SCHEDULE

A. Domestic Cold Water: Insulation shall be 3/4” thick.

B. Domestic Hot Water and Recirculated Hot Water (Potable): Insulation shall be 1” thick.

C. Stormwater, Roof Drain and Drain Bodies: Insulation shall be 1” thick.

D. Sanitary Risers: Insulation shall be 1” thick.

3.11 INDOOR, FIELD-APPLIED JACKET SCHEDULE

A. Install jacket over insulation material. For insulation with factory-applied jacket, install the field-applied jacket over the factory-applied jacket.

B. If more than one material is listed, selection from materials listed is Contractor's option.

END OF SECTION 15082

Page 26: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 6

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15083 - HVAC INSULATION

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Insulation Materials: a. Mineral fiber.

2. Insulation accessories.

1.2 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Field quality-control reports.

1.3 QUALITY ASSURANCE

A. Fire-Test-Response Characteristics: Insulation and related materials shall have fire-test-response characteristics indicated, as determined by testing identical products per ASTM E 84, by a testing and inspecting agency acceptable to authorities having jurisdiction. Factory label insulation and jacket materials and adhesive, mastic, tapes, and cement material containers, with appropriate markings of applicable testing and inspecting agency.

1. Insulation Installed Indoors: Flame-spread index of 25 or less, and smoke-developed index of 50 or less.

2. Insulation Installed Outdoors: Flame-spread index of 75 or less, and smoke-developed index of 150 or less.

PART 2 - PRODUCTS

2.1 INSULATION MATERIALS

A. Comply with requirements in Part 3 schedule articles for where insulating materials shall be applied.

B. Products shall not contain asbestos, lead, mercury, or mercury compounds.

C. Products that come in contact with stainless steel shall have a leachable chloride content of less than 50 ppm when tested according to ASTM C 871.

D. Mineral-Fiber Blanket Insulation: Mineral or glass fibers bonded with a thermosetting resin. Comply with ASTM C 553, Type II and ASTM C 1290. Factory-applied jacket requirements are specified in "Factory-Applied Jackets" Article.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. CertainTeed Corp.; Duct Wrap.

Page 27: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 6

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

b. Johns Manville; Microlite. c. Knauf Insulation; Duct Wrap. d. Manson Insulation Inc.; Alley Wrap. e. Owens Corning; All-Service Duct Wrap.

E. Mineral-Fiber Board Insulation: Mineral or glass fibers bonded with a thermosetting resin. Comply with ASTM C 612, Type IA or Type IB. Factory-applied jacket requirements are specified in "Factory-Applied Jackets" Article.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. CertainTeed Corp.; Commercial Board. b. Fibrex Insulations Inc.; FBX. c. Johns Manville; 800 Series Spin-Glas. d. Knauf Insulation; Insulation Board. e. Manson Insulation Inc.; AK Board. f. Owens Corning; Fiberglas 700 Series.

2.2 INSULATING CEMENTS

A. Mineral-Fiber, Hydraulic-Setting Insulating and Finishing Cement: Comply with ASTM C 449/C 449M.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. Insulco, Division of MFS, Inc.; SmoothKote. b. P. K. Insulation Mfg. Co., Inc.; PK No. 127, and Quik-Cote. c. Rock Wool Manufacturing Company; Delta One Shot.

2.3 ADHESIVES

A. Materials shall be compatible with insulation materials, jackets, and substrates and for bonding insulation to itself and to surfaces to be insulated, unless otherwise indicated.

B. Mineral-Fiber Adhesive: Comply with MIL-A-3316C, Class 2, Grade A.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. Childers Products, Division of ITW; CP-82. b. Foster Products Corporation, H. B. Fuller Company; 85-20. c. ITW TACC, Division of Illinois Tool Works; S-90/80. d. Marathon Industries, Inc.; 225. e. Mon-Eco Industries, Inc.; 22-25.

2.4 TAPES

A. ASJ Tape: White vapor-retarder tape matching factory-applied jacket with acrylic adhesive, complying with ASTM C 1136.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. Avery Dennison Corporation, Specialty Tapes Division; Fasson 0835. b. Compac Corp.; 104 and 105.

Page 28: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 6

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

c. Ideal Tape Co., Inc., an American Biltrite Company; 428 AWF ASJ. d. Venture Tape; 1540 CW Plus, 1542 CW Plus, and 1542 CW Plus/SQ.

B. FSK Tape: Foil-face, vapor-retarder tape matching factory-applied jacket with acrylic adhesive; complying with ASTM C 1136.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. Avery Dennison Corporation, Specialty Tapes Division; Fasson 0827. b. Compac Corp.; 110 and 111. c. Ideal Tape Co., Inc., an American Biltrite Company; 491 AWF FSK. d. Venture Tape; 1525 CW, 1528 CW, and 1528 CW/SQ.

C. Aluminum-Foil Tape: Vapor-retarder tape with acrylic adhesive.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

a. Avery Dennison Corporation, Specialty Tapes Division; Fasson 0800. b. Compac Corp.; 120. c. Ideal Tape Co., Inc., an American Biltrite Company; 488 AWF. d. Venture Tape; 3520 CW.

D. Insulation Pins and Hangers:

1. Metal, Adhesively Attached, Perforated-Base Insulation Hangers: Baseplate welded to projecting spindle that is capable of holding insulation, of thickness indicated, securely in position indicated when self-locking washer is in place. Comply with the following requirements:

a. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:

1) AGM Industries, Inc.; Tactoo Insul-Hangers, Series T. 2) GEMCO; Perforated Base. 3) Midwest Fasteners, Inc.; Spindle.

PART 3 - EXECUTION

3.1 PREPARATION

A. Surface Preparation: Clean and dry surfaces to receive insulation. Remove materials that will adversely affect insulation application.

B. Coordinate insulation installation with the trade installing heat tracing. Comply with requirements for heat tracing that apply to insulation.

C. Mix insulating cements with clean potable water; if insulating cements are to be in contact with stainless-steel surfaces, use demineralized water.

3.2 GENERAL INSTALLATION REQUIREMENTS

A. Install insulation materials, accessories, and finishes with smooth, straight, and even surfaces; free of voids throughout the length of equipment, ducts and fittings, and piping including fittings, valves, and specialties.

Page 29: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 6

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

B. Install insulation materials, forms, vapor barriers or retarders, jackets, and thicknesses required for each item of equipment, duct system, and pipe system as specified in insulation system schedules.

C. Install accessories compatible with insulation materials and suitable for the service. Install accessories that do not corrode, soften, or otherwise attack insulation or jacket in either wet or dry state.

D. Install insulation with longitudinal seams at top and bottom of horizontal runs.

E. Install multiple layers of insulation with longitudinal and end seams staggered.

F. Do not weld brackets, clips, or other attachment devices to piping, fittings, and specialties.

G. Keep insulation materials dry during application and finishing.

H. Install insulation with tight longitudinal seams and end joints. Bond seams and joints with adhesive recommended by insulation material manufacturer.

I. Install insulation with least number of joints practical.

J. Where vapor barrier is indicated, seal joints, seams, and penetrations in insulation at hangers, supports, anchors, and other projections with vapor-barrier mastic.

1. Install insulation continuously through hangers and around anchor attachments. 2. For insulation application where vapor barriers are indicated, extend insulation on anchor legs from

point of attachment to supported item to point of attachment to structure. Taper and seal ends at attachment to structure with vapor-barrier mastic.

3. Install insert materials and install insulation to tightly join the insert. Seal insulation to insulation inserts with adhesive or sealing compound recommended by insulation material manufacturer.

4. Cover inserts with jacket material matching adjacent pipe insulation. Install shields over jacket, arranged to protect jacket from tear or puncture by hanger, support, and shield.

K. Apply adhesives, mastics, and sealants at manufacturer's recommended coverage rate and wet and dry film thicknesses.

L. Cut insulation in a manner to avoid compressing insulation more than 75 percent of its nominal thickness.

M. Finish installation with systems at operating conditions. Repair joint separations and cracking due to thermal movement.

N. Repair damaged insulation facings by applying same facing material over damaged areas. Extend patches at least 4 inches beyond damaged areas. Adhere, staple, and seal patches similar to butt joints.

3.3 PENETRATIONS

A. Insulation Installation at Roof Penetrations: Install insulation continuously through roof penetrations.

1. Seal penetrations with flashing sealant. 2. For applications requiring only indoor insulation, terminate insulation above roof surface and seal

with joint sealant. For applications requiring indoor and outdoor insulation, install insulation for outdoor applications tightly joined to indoor insulation ends. Seal joint with joint sealant.

3. Extend jacket of outdoor insulation outside roof flashing at least 2 inches below top of roof flashing. 4. Seal jacket to roof flashing with flashing sealant.

B. Insulation Installation at Aboveground Exterior Wall Penetrations: Install insulation continuously through wall penetrations.

1. Seal penetrations with flashing sealant.

Page 30: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 6

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2. For applications requiring only indoor insulation, terminate insulation inside wall surface and seal with joint sealant. For applications requiring indoor and outdoor insulation, install insulation for outdoor applications tightly joined to indoor insulation ends. Seal joint with joint sealant.

3. Extend jacket of outdoor insulation outside wall flashing and overlap wall flashing at least 2 inches. 4. Seal jacket to wall flashing with flashing sealant.

C. Insulation Installation at Interior Wall and Partition Penetrations (That Are Not Fire Rated): Install insulation continuously through walls and partitions.

D. Insulation Installation at Fire-Rated Wall and Partition Penetrations: Install insulation continuously through penetrations of fire-rated walls and partitions. Terminate insulation at fire damper sleeves for fire-rated wall and partition penetrations. Externally insulate damper sleeves to match adjacent insulation and overlap duct insulation at least 2 inches.

1. Comply with requirements in Division 7 Section "Through-Penetration Firestop Systems" for firestopping and fire-resistive joint sealers.

E. Insulation Installation at Floor Penetrations:

1. Duct: Install insulation continuously through floor penetrations that are not fire rated. For penetrations through fire-rated assemblies, terminate insulation at fire damper sleeves and externally insulate damper sleeve beyond floor to match adjacent duct insulation. Overlap damper sleeve and duct insulation at least 2 inches.

2. Pipe: Install insulation continuously through floor penetrations. 3. Seal penetrations through fire-rated assemblies. Comply with requirements in Division 7 Section

"Through-Penetration Firestop Systems."

3.4 MINERAL-FIBER INSULATION INSTALLATION

A. Blanket Insulation Installation on Ducts and Plenums: Secure with adhesive and insulation pins.

1. Apply adhesives according to manufacturer's recommended coverage rates per unit area. 2. Apply adhesive to entire circumference of ducts and to all surfaces of fittings and transitions. 3. Install either capacitor-discharge-weld pins and speed washers or cupped-head, capacitor-

discharge-weld pins on sides and bottom of horizontal ducts and sides of vertical ducts as follows:

a. On duct sides with dimensions 18 inches and smaller, place pins along longitudinal centerline of duct. Space 3 inches maximum from insulation end joints, and 16 inches o.c.

b. On duct sides with dimensions larger than 18 inches, place pins 16 inches o.c. each way, and 3 inches maximum from insulation joints. Install additional pins to hold insulation tightly against surface at cross bracing.

c. Pins may be omitted from top surface of horizontal, rectangular ducts and plenums. d. Do not overcompress insulation during installation. e. Impale insulation over pins and attach speed washers. f. Cut excess portion of pins extending beyond speed washers or bend parallel with insulation

surface. Cover exposed pins and washers with tape matching insulation facing.

4. For ducts and plenums with surface temperatures below ambient, install a continuous unbroken vapor barrier. Create a facing lap for longitudinal seams and end joints with insulation by removing 2 inches from 1 edge and 1 end of insulation segment. Secure laps to adjacent insulation section with 1/2-inch outward-clinching staples, 1 inch o.c. Install vapor barrier consisting of factory- or field-applied jacket, adhesive, vapor-barrier mastic, and sealant at joints, seams, and protrusions.

a. Repair punctures, tears, and penetrations with tape or mastic to maintain vapor-barrier seal. b. Install vapor stops for ductwork and plenums operating below 50 deg F at 18-foot intervals.

Vapor stops shall consist of vapor-barrier mastic applied in a Z-shaped pattern over insulation face, along butt end of insulation, and over the surface. Cover insulation face and surface to be insulated a width equal to 2 times the insulation thickness but not less than 3 inches.

Page 31: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 6 of 6

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

5. Install insulation on rectangular duct elbows and transitions with a full insulation section for each surface. Install insulation on round and flat-oval duct elbows with individually mitered gores cut to fit the elbow.

3.5 FIELD QUALITY CONTROL

A. Perform tests and inspections.

B. Tests and Inspections:

1. Inspect ductwork, randomly selected by Architect, by removing field-applied jacket and insulation in layers in reverse order of their installation. Extent of inspection shall be limited to one location(s) for each duct system defined in the "Duct Insulation Schedule, General" Article.

C. All insulation applications will be considered defective Work if sample inspection reveals noncompliance with requirements.

3.6 DUCT INSULATION SCHEDULE, GENERAL

A. Plenums and Ducts Requiring Insulation:

1. Indoor, concealed supply and outdoor air. 2. Indoor, exposed supply and outdoor air. 3. Indoor, concealed return located in nonconditioned space. 4. Indoor, exposed return located in nonconditioned space. 5. Indoor, concealed exhaust between isolation damper and penetration of building exterior. 6. Indoor, exposed exhaust between isolation damper and penetration of building exterior. 7. Outdoor, concealed supply and return. 8. Outdoor, exposed supply and return.

B. Items Not Insulated: 1. Factory-insulated flexible ducts. 2. Factory-insulated plenums and casings. 3. Flexible connectors. 4. Vibration-control devices. 5. Factory-insulated access panels and doors.

END OF SECTION 15083

Page 32: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 3

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15111 - GENERAL-DUTY VALVES FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes: 1. Bronze ball valves.

B. Related Sections: 1. Division 15 plumbing piping Sections for specialty valves applicable to those Sections only. 2. Division 15 Section "Identification for Plumbing Piping and Equipment" for valve tags and

schedules.

1.2 SUBMITTALS

A. Product Data: For each type of valve indicated.

1.3 QUALITY ASSURANCE

A. ASME Compliance: ASME B16.10 and ASME B16.34 for ferrous valve dimensions and design criteria.

B. NSF Compliance: NSF 61 for valve materials for potable-water service.

PART 2 - PRODUCTS

2.1 GENERAL REQUIREMENTS FOR VALVES

A. Valve Pressure and Temperature Ratings: Not less than indicated and as required for system pressures and temperatures.

B. Valve Sizes: Same as upstream piping unless otherwise indicated.

C. Valve Actuator Types: 1. Handlever: For quarter-turn valves NPS 6 and smaller.

D. Valves in Insulated Piping: With 2-inch stem extensions and the following features: 1. Ball Valves: With extended operating handle of non-thermal-conductive material, and protective

sleeve that allows operation of valve without breaking the vapor seal or disturbing insulation.

E. Valve-End Connections:

1. Flanged: With flanges according to ASME B16.1 for iron valves. 2. Solder Joint: With sockets according to ASME B16.18. 3. Threaded: With threads according to ASME B1.20.1.

2.2 BRONZE BALL VALVES

A. Two-Piece, Full-Port, Bronze Ball Valves with Bronze Trim:

Page 33: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 3

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. American Valve, Inc. b. Conbraco Industries, Inc.; Apollo Valves. c. Crane Co.; Crane Valve Group; Crane Valves. d. Hammond Valve. e. Lance Valves; a division of Advanced Thermal Systems, Inc. f. Legend Valve. g. Milwaukee Valve Company. h. NIBCO INC. i. Red-White Valve Corporation. j. Watts Regulator Co.; a division of Watts Water Technologies, Inc.

2. Description:

a. Standard: MSS SP-110. b. SWP Rating: 150 psig. c. CWP Rating: 600 psig. d. Body Design: Two piece. e. Body Material: Bronze. f. Ends: Threaded. g. Seats: PTFE or TFE. h. Stem: Bronze. i. Ball: Chrome-plated brass. j. Port: Full.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine valve interior for cleanliness, freedom from foreign matter, and corrosion. Remove special packing materials, such as blocks, used to prevent disc movement during shipping and handling.

B. Operate valves in positions from fully open to fully closed. Examine guides and seats made accessible by such operations.

C. Examine threads on valve and mating pipe for form and cleanliness.

D. Examine mating flange faces for conditions that might cause leakage. Check bolting for proper size, length, and material. Verify that gasket is of proper size, that its material composition is suitable for service, and that it is free from defects and damage.

E. Do not attempt to repair defective valves; replace with new valves.

3.2 VALVE INSTALLATION

A. Install valves with unions or flanges at each piece of equipment arranged to allow service, maintenance, and equipment removal without system shutdown.

B. Locate valves for easy access and provide separate support where necessary.

C. Install valves in horizontal piping with stem at or above center of pipe.

D. Install valves in position to allow full stem movement.

Page 34: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 3

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

3.3 ADJUSTING

A. Adjust or replace valve packing after piping systems have been tested and put into service but before final adjusting and balancing. Replace valves if persistent leaking occurs.

3.4 GENERAL REQUIREMENTS FOR VALVE APPLICATIONS

A. If valves with specified SWP classes or CWP ratings are not available, the same types of valves with higher SWP class or CWP ratings may be substituted.

B. Select valves, except wafer types, with the following end connections:

1. For Copper Tubing, NPS 2 and Smaller: Threaded ends except where solder-joint valve-end option is indicated in valve schedules below.

2. For Copper Tubing, NPS 2-1/2 to NPS 4: Flanged ends except where threaded valve-end option is indicated in valve schedules below.

3. For Copper Tubing, NPS 5 and Larger: Flanged ends. 4. For Steel Piping, NPS 2 and Smaller: Threaded ends. 5. For Steel Piping, NPS 2-1/2 to NPS 4: Flanged ends except where threaded valve-end option is

indicated in valve schedules below. 6. For Steel Piping, NPS 5 and Larger: Flanged ends.

3.5 DOMESTIC, HOT- AND COLD-WATER VALVE SCHEDULE

A. Pipe NPS 2 and Smaller:

1. Bronze Valves: May be provided with solder-joint ends instead of threaded ends. 2. Bronze Angle Valves: Class 125, bronze disc. 3. Ball Valves: Two piece, full port, bronze with bronze trim.

B. Pipe NPS 2-1/2 and Larger:

1. Iron Valves, NPS 2-1/2 to NPS 4: May be provided with threaded ends instead of flanged ends.

END OF SECTION 15111

Page 35: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 11

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15140 - DOMESTIC WATER PIPING

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Under-building slab and aboveground domestic water pipes, tubes, fittings, and specialties inside the building.

2. Specialty valves. 3. Flexible connectors. 4. Escutcheons. 5. Sleeves and sleeve seals.

B. Related Section:

1.2 PERFORMANCE REQUIREMENTS

1.3 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Field quality-control reports.

1.4 QUALITY ASSURANCE

A. Piping materials shall bear label, stamp, or other markings of specified testing agency.

B. Comply with NSF 14 for plastic, potable domestic water piping and components.

C. Comply with NSF 61 for potable domestic water piping and components.

PART 2 - PRODUCTS

2.1 PIPING MATERIALS

A. Comply with requirements in "Piping Schedule" Article for applications of pipe, tube, fitting materials, and joining methods for specific services, service locations, and pipe sizes.

2.2 COPPER TUBE AND FITTINGS

A. Hard Copper Tube: ASTM B 88, Type Lwater tube, drawn temper.

1. Cast-Copper Solder-Joint Fittings: ASME B16.18, pressure fittings. 2. Wrought-Copper Solder-Joint Fittings: ASME B16.22, wrought-copper pressure fittings. 3. Bronze Flanges: ASME B16.24, Class 150, with solder-joint ends. 4. Copper Unions: MSS SP-123, cast-copper-alloy, hexagonal-stock body, with ball-and-socket,

metal-to-metal seating surfaces, and solder-joint or threaded ends.

Page 36: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 11

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

5. Copper Pressure-Seal-Joint Fittings:

a. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1) Elkhart Products Corporation; Industrial Division. 2) NIBCO INC. 3) Viega; Plumbing and Heating Systems.

b. NPS 2 and Smaller: Wrought-copper fitting with EPDM-rubber O-ring seal in each end. c. NPS 2-1/2 to NPS 4: Cast-bronze or wrought-copper fitting with EPDM-rubber O-ring seal

in each end.

6. Copper Push-on-Joint Fittings:

a. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1) NVent LLC.

b. Description: Cast-copper fitting complying with ASME B16.18 or wrought-copper fitting complying with ASME B 16.22; with stainless-steel teeth and EPDM-rubber O-ring seal in each end instead of solder-joint ends.

B. Soft Copper Tube: ASTM B 88, Type K water tube, annealed temper.

1. Copper Solder-Joint Fittings: ASME B16.22, wrought-copper pressure fittings. 2. Copper Pressure-Seal-Joint Fittings:

a. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1) Elkhart Products Corporation; Industrial Division. 2) NIBCO INC. 3) Viega; Plumbing and Heating Systems.

b. NPS 2 and Smaller: Wrought-copper fitting with EPDM-rubber O-ring seal in each end. c. NPS 3 and NPS 4: Cast-bronze or wrought-copper fitting with EPDM-rubber O-ring seal in

each end.

2.3 PIPING JOINING MATERIALS

A. Pipe-Flange Gasket Materials: AWWA C110, rubber, flat face, 1/8 inch thick or ASME B16.21, nonmetallic and asbestos free, unless otherwise indicated; full-face or ring type unless otherwise indicated.

B. Solder Filler Metals: ASTM B 32, lead-free alloys. Include water-flushable flux according to ASTM B 813.

C. Brazing Filler Metals: AWS A5.8/A5.8M, BCuP Series, copper-phosphorus alloys for general-duty brazing unless otherwise indicated.

2.4 SPECIALTY VALVES

A. Comply with requirements in Division 15 Section "General-Duty Valves for Plumbing Piping" for general-duty metal valves.

Page 37: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 11

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2.5 TRANSITION FITTINGS

A. Fitting-Type Transition Couplings: Manufactured piping coupling or specified piping system fitting.

B. Sleeve-Type Transition Coupling: AWWA C219.

2.6 DIELECTRIC FITTINGS

A. General Requirements: Assembly of copper alloy and ferrous materials or ferrous material body with separating nonconductive insulating material suitable for system fluid, pressure, and temperature.

B. Dielectric Unions:

1. Description:

a. Pressure Rating: 150 psig at 180 deg F. b. End Connections: Solder-joint copper alloy and threaded ferrous.

C. Dielectric Flanges:

1. Description:

a. Factory-fabricated, bolted, companion-flange assembly. b. Pressure Rating: 150 psig. c. End Connections: Solder-joint copper alloy and threaded ferrous; threaded solder-joint

copper alloy and threaded ferrous.

D. Dielectric-Flange Kits:

1. Description:

a. Nonconducting materials for field assembly of companion flanges. b. Pressure Rating: 150 psig. c. Gasket: Neoprene or phenolic. d. Bolt Sleeves: Phenolic or polyethylene. e. Washers: Phenolic with steel backing washers.

E. Dielectric Couplings:

1. Description:

a. Galvanized-steel coupling. b. Pressure Rating: 300 psig at 225 deg F. c. End Connections: Female threaded. d. Lining: Inert and noncorrosive, thermoplastic.

F. Dielectric Nipples:

1. Description:

a. Electroplated steel nipple complying with ASTM F 1545. b. Pressure Rating: 300 psig at 225 deg F. c. End Connections: Male threaded or grooved. d. Lining: Inert and noncorrosive, propylene.

Page 38: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 11

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2.7 FLEXIBLE CONNECTORS

A. Bronze-Hose Flexible Connectors: Corrugated-bronze tubing with bronze wire-braid covering and ends brazed to inner tubing.

1. Working-Pressure Rating: Minimum 200 psig. 2. End Connections NPS 2 and Smaller: Threaded copper pipe or plain-end copper tube. 3. End Connections NPS 2-1/2 and Larger: Flanged copper alloy.

B. Stainless-Steel-Hose Flexible Connectors: Corrugated-stainless-steel tubing with stainless-steel wire-braid covering and ends welded to inner tubing.

1. Working-Pressure Rating: Minimum 200 psig. 2. End Connections NPS 2 and Smaller: Threaded steel-pipe nipple. 3. End Connections NPS 2-1/2 and Larger: Flanged steel nipple.

2.8 ESCUTCHEONS

A. General: Manufactured ceiling, floor, and wall escutcheons and floor plates.

B. One Piece, Cast Brass: Polished, chrome-plated finish with setscrews.

C. One Piece, Deep Pattern: Deep-drawn, box-shaped brass with chrome-plated finish.

D. One Piece, Stamped Steel: Chrome-plated finish with setscrew.

E. Split Casting, Cast Brass: Polished, chrome-plated finish with concealed hinge and setscrew.

F. Split Plate, Stamped Steel: Chrome-plated finish with concealed hinge and setscrew.

G. One-Piece Floor Plates: Cast-iron flange.

H. Split-Casting Floor Plates: Cast brass with concealed hinge.

2.9 SLEEVES

A. Cast-Iron Wall Pipes: Fabricated of cast iron, and equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop unless otherwise indicated.

B. Galvanized-Steel-Sheet Sleeves: 0.0239-inch minimum thickness; round tube closed with welded longitudinal joint.

C. PVC-Pipe Sleeves: ASTM D 1785, Schedule 40.

D. Galvanized-Steel-Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, zinc-coated, with plain ends.

E. Stack Sleeve Fittings: Manufactured, cast-iron sleeve with integral clamping flange. Include clamping ring and bolts and nuts for membrane flashing.

1. Underdeck Clamp: Clamping ring with setscrews.

Page 39: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 11

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2.10 SLEEVE SEALS

A. Description: Modular sealing element unit, designed for field assembly, used to fill annular space between pipe and sleeve.

1. Sealing Elements: EPDM-rubber interlocking links shaped to fit surface of pipe. Include type and number required for pipe material and size of pipe.

2. Pressure Plates: Carbon steel. 3. Connecting Bolts and Nuts: Carbon steel, with corrosion-resistant coating, of length required to

secure pressure plates to sealing elements.

2.11 GROUT

A. Standard: ASTM C 1107, Grade B, post-hardening and volume-adjusting, dry, hydraulic-cement grout.

B. Characteristics: Nonshrink; recommended for interior and exterior applications.

C. Design Mix: 5000-psi, 28-day compressive strength.

D. Packaging: Premixed and factory packaged.

PART 3 - EXECUTION

3.1 PIPING INSTALLATION

A. Drawing plans, schematics, and diagrams indicate general location and arrangement of domestic water piping. Install piping as indicated unless deviations to layout are approved on Coordination Drawings.

B. Install copper tubing under building slab according to CDA's "Copper Tube Handbook."

C. Install shutoff valve immediately upstream of each dielectric fitting.

D. Install domestic water piping level with 0.25 percent slope downward toward drain and plumb.

E. Install piping concealed from view and protected from physical contact by building occupants unless otherwise indicated and except in equipment rooms and service areas.

F. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise.

G. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal, and coordinate with other services occupying that space.

H. Install piping adjacent to equipment and specialties to allow service and maintenance.

I. Install piping to permit valve servicing.

J. Install nipples, unions, special fittings, and valves with pressure ratings the same as or higher than system pressure rating used in applications below unless otherwise indicated.

K. Install piping free of sags and bends.

L. Install fittings for changes in direction and branch connections.

M. Install unions in copper tubing at final connection to each piece of equipment, machine, and specialty.

Page 40: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 6 of 11

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

3.2 JOINT CONSTRUCTION

A. Ream ends of pipes and tubes and remove burrs. Bevel plain ends of steel pipe.

B. Remove scale, slag, dirt, and debris from inside and outside of pipes, tubes, and fittings before assembly.

C. Threaded Joints: Thread pipe with tapered pipe threads according to ASME B1.20.1. Cut threads full and clean using sharp dies. Ream threaded pipe ends to remove burrs and restore full ID. Join pipe fittings and valves as follows:

1. Apply appropriate tape or thread compound to external pipe threads. 2. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged.

D. Brazed Joints: Join copper tube and fittings according to CDA's "Copper Tube Handbook," "Brazed Joints" Chapter.

E. Soldered Joints: Apply ASTM B 813, water-flushable flux to end of tube. Join copper tube and fittings according to ASTM B 828 or CDA's "Copper Tube Handbook."

F. Pressure-Sealed Joints: Join copper tube and pressure-seal fittings with tools recommended by fitting manufacturer.

G. Copper-Tubing, Push-on Joints: Clean end of tube. Measure insertion depth with manufacturer's depth gage. Join copper tube and push-on-joint fittings by inserting tube to measured depth.

H. Flanged Joints: Select appropriate asbestos-free, nonmetallic gasket material in size, type, and thickness suitable for domestic water service. Join flanges with gasket and bolts according to ASME B31.9.

I. Dissimilar-Material Piping Joints: Make joints using adapters compatible with materials of both piping systems.

3.3 VALVE INSTALLATION

A. Install shutoff valve close to water main on each branch and riser serving plumbing fixtures or equipment, on each water supply to equipment, and on each water supply to plumbing fixtures that do not have supply stops. Use ball valves for piping NPS 2 and smaller. Use butterfly or gate valves for piping NPS 2-1/2 and larger.

B. Install drain valves for equipment at base of each water riser, at low points in horizontal piping, and where required to drain water piping.

1. Hose-End Drain Valves: At low points in water mains, risers, and branches. 2. Stop-and-Waste Drain Valves: Instead of hose-end drain valves where indicated.

3.4 TRANSITION FITTING INSTALLATION

A. Install transition couplings at joints of dissimilar piping.

B. Transition Fittings in Underground Domestic Water Piping:

1. NPS 1-1/2 and Smaller: Fitting-type coupling. 2. NPS 2 and Larger: Sleeve-type coupling.

C. Transition Fittings in Aboveground Domestic Water Piping NPS 2 and Smaller: Plastic-to-metal transition fittings or unions.

Page 41: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 7 of 11

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

3.5 DIELECTRIC FITTING INSTALLATION

A. Install dielectric fittings in piping at connections of dissimilar metal piping and tubing.

B. Dielectric Fittings for NPS 2 and Smaller: Use dielectric couplings or nipples.

3.6 FLEXIBLE CONNECTOR INSTALLATION

A. Install bronze-hose flexible connectors in copper domestic water tubing.

B. Install stainless-steel-hose flexible connectors in steel domestic water piping.

3.7 HANGER AND SUPPORT INSTALLATION

A. Comply with requirements in Division 15 Section "Hangers and Supports for Plumbing Piping and Equipment" for pipe hanger and support products and installation.

1. Vertical Piping: MSS Type 8 or 42, clamps. 2. Individual, Straight, Horizontal Piping Runs:

a. 100 Feet and Less: MSS Type 1, adjustable, steel clevis hangers.

B. Support vertical piping and tubing at base and at each floor.

C. Rod diameter may be reduced one size for double-rod hangers, to a minimum of 3/8 inch.

D. Install hangers for copper tubing with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 3/4 and Smaller: 60 inches with 3/8-inch rod. 2. NPS 1 and NPS 1-1/4: 72 inches with 3/8-inch rod. 3. NPS 1-1/2 and NPS 2: 96 inches with 3/8-inch rod. 4. NPS 2-1/2: 108 inches with 1/2-inch rod. 5. NPS 3 to NPS 5: 10 feet with 1/2-inch rod. 6. NPS 6: 10 feet with 5/8-inch rod.

E. Install supports for vertical copper tubing every 10 feet.

3.8 CONNECTIONS

A. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Install piping adjacent to equipment and machines to allow service and maintenance.

C. Connect domestic water piping to water-service piping with shutoff valve; extend and connect to the following: 1. Plumbing Fixtures: Cold- and hot-water supply piping in sizes indicated, but not smaller than

required by plumbing code. 2. Equipment: Cold- and hot-water supply piping as indicated, but not smaller than equipment

connections. Provide shutoff valve and union for each connection. Use flanges instead of unions for NPS 2-1/2 and larger.

Page 42: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 8 of 11

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

3.9 ESCUTCHEON INSTALLATION

A. Install escutcheons for penetrations of walls, ceilings, and floors.

B. Escutcheons for New Piping:

1. Piping with Fitting or Sleeve Protruding from Wall: One piece, deep pattern. 2. Bare Piping at Wall and Floor Penetrations in Finished Spaces: One piece, cast brass with

polished chrome-plated finish. 3. Bare Piping at Ceiling Penetrations in Finished Spaces: One piece, cast brass with polished

chrome-plated finish. 4. Bare Piping in Unfinished Service Spaces: One piece, cast brass with polished chrome-plated

finish. 5. Bare Piping in Equipment Rooms: One piece, cast brass. 6. Bare Piping at Floor Penetrations in Equipment Rooms: One-piece floor plate.

3.10 SLEEVE INSTALLATION

A. General Requirements: Install sleeves for pipes and tubes passing through penetrations in floors, partitions, roofs, and walls.

B. Sleeves are not required for core-drilled holes.

C. Permanent sleeves are not required for holes formed by removable PE sleeves.

D. Cut sleeves to length for mounting flush with both surfaces unless otherwise indicated.

E. Install sleeves in new partitions, slabs, and walls as they are built.

F. For interior wall penetrations, seal annular space between sleeve and pipe or pipe insulation using joint sealants appropriate for size, depth, and location of joint. Comply with requirements in Division 07 Section "Joint Sealants" for joint sealants.

G. For exterior wall penetrations above grade, seal annular space between sleeve and pipe using joint sealants appropriate for size, depth, and location of joint. Comply with requirements in Division 07 Section "Joint Sealants" for joint sealants.

H. For exterior wall penetrations below grade, seal annular space between sleeve and pipe using sleeve seals specified in this Section.

I. Seal space outside of sleeves in concrete slabs and walls with grout.

J. Install sleeves that are large enough to provide 1/4-inch annular clear space between sleeve and pipe or pipe insulation unless otherwise indicated.

K. Install sleeve materials according to the following applications:

1. Sleeves for Piping Passing through Concrete Floor Slabs: Steel pipe. 2. Sleeves for Piping Passing through Concrete Floor Slabs of Mechanical Equipment Areas or Other

Wet Areas: Steel pipe.

a. Extend sleeves 2 inches above finished floor level. b. For pipes penetrating floors with membrane waterproofing, extend cast-iron sleeve fittings

below floor slab as required to secure clamping ring if ring is specified. Secure flashing between clamping flanges. Install section of cast-iron soil pipe to extend sleeve to 2 inches above finished floor level. Comply with requirements in Division 07 Section "Sheet Metal Flashing and Trim" for flashing.

Page 43: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 9 of 11

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

3. Sleeves for Piping Passing through Gypsum-Board Partitions:

a. Steel pipe sleeves for pipes smaller than NPS 6. b. Galvanized-steel sheet sleeves for pipes NPS 6 and larger. c. Exception: Sleeves are not required for water supply tubes and waste pipes for individual

plumbing fixtures if escutcheons will cover openings.

4. Sleeves for Piping Passing through Concrete Roof Slabs: Steel pipe. 5. Sleeves for Piping Passing through Exterior Concrete Walls:

a. Steel pipe sleeves for pipes smaller than NPS 6. b. Cast-iron wall pipe sleeves for pipes NPS 6 and larger. c. Install sleeves that are large enough to provide 1-inch annular clear space between sleeve

and pipe or pipe insulation when sleeve seals are used.

L. Fire-Barrier Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at pipe penetrations. Seal pipe penetrations with firestop materials. Comply with requirements in Division 07 Section for firestop materials and installations.

3.11 SLEEVE SEAL INSTALLATION

A. Install sleeve seals in sleeves in exterior concrete walls at water-service piping entries into building.

B. Select type and number of sealing elements required for pipe material and size. Position pipe in center of sleeve. Assemble sleeve seal components and install in annular space between pipe and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.

3.12 IDENTIFICATION

A. Identify system components. Comply with requirements in Division 15 Section "Identification for Plumbing Piping and Equipment" for identification materials and installation.

B. Label pressure piping with system operating pressure.

3.13 FIELD QUALITY CONTROL

A. Perform tests and inspections.

B. Piping Inspections:

1. Do not enclose, cover, or put piping into operation until it has been inspected and approved by authorities having jurisdiction.

2. During installation, notify authorities having jurisdiction at least one day before inspection must be made. Perform tests specified below in presence of authorities having jurisdiction:

a. Roughing-in Inspection: Arrange for inspection of piping before concealing or closing-in after roughing-in and before setting fixtures.

b. Final Inspection: Arrange final inspection for authorities having jurisdiction to observe tests specified below and to ensure compliance with requirements.

3. Reinspection: If authorities having jurisdiction find that piping will not pass tests or inspections, make required corrections and arrange for reinspection.

4. Reports: Prepare inspection reports and have them signed by authorities having jurisdiction.

C. Piping Tests:

Page 44: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 10 of 11

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1. Fill domestic water piping. Check components to determine that they are not air bound and that piping is full of water.

2. Test for leaks and defects in new piping and parts of existing piping that have been altered, extended, or repaired. If testing is performed in segments, submit a separate report for each test, complete with diagram of portion of piping tested.

3. Leave new, altered, extended, or replaced domestic water piping uncovered and unconcealed until it has been tested and approved. Expose work that was covered or concealed before it was tested.

4. Cap and subject piping to static water pressure of 50 psig above operating pressure, without exceeding pressure rating of piping system materials. Isolate test source and allow to stand for four hours. Leaks and loss in test pressure constitute defects that must be repaired.

5. Repair leaks and defects with new materials and retest piping or portion thereof until satisfactory results are obtained.

6. Prepare reports for tests and for corrective action required.

D. Domestic water piping will be considered defective if it does not pass tests and inspections.

E. Prepare test and inspection reports.

3.14 CLEANING

A. Clean and disinfect potable domestic water piping as follows:

1. Purge new piping and parts of existing piping that have been altered, extended, or repaired before using.

2. Use purging and disinfecting procedures prescribed by authorities having jurisdiction; if methods are not prescribed, use procedures described in either AWWA C651 or AWWA C652 or follow procedures described below:

a. Flush piping system with clean, potable water until dirty water does not appear at outlets. b. Fill and isolate system according to either of the following:

1) Fill system or part thereof with water/chlorine solution with at least 50 ppm of chlorine. Isolate with valves and allow to stand for 24 hours.

2) Fill system or part thereof with water/chlorine solution with at least 200 ppm of chlorine. Isolate and allow to stand for three hours.

c. Flush system with clean, potable water until no chlorine is in water coming from system after the standing time.

d. Submit water samples in sterile bottles to authorities having jurisdiction. Repeat procedures if biological examination shows contamination.

B. Prepare and submit reports of purging and disinfecting activities.

C. Clean interior of domestic water piping system. Remove dirt and debris as work progresses.

3.15 PIPING SCHEDULE

A. Transition and special fittings with pressure ratings at least equal to piping rating may be used in applications below unless otherwise indicated.

B. Flanges and unions may be used for aboveground piping joints unless otherwise indicated.

C. Aboveground domestic water piping, shall be the following: 1. Hard copper tube, ASTM B 88, Type L; wrought-copper solder-joint fittings; and soldered joints

Page 45: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 11 of 11

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

3.16 VALVE SCHEDULE

A. Drawings indicate valve types to be used. Where specific valve types are not indicated, the following requirements apply:

1. Shutoff Duty: Use ball valves for piping NPS 2 and smaller. Use butterfly, ball, or gate valves with flanged ends for piping NPS 2-1/2 and larger.

END OF SECTION 15140

Page 46: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15145 - DOMESTIC WATER PIPING SPECIALTIES

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes the following domestic water piping specialties:

1. Vacuum breakers. 2. Water pressure-reducing valves. 3. Balancing valves. 4. Temperature-actuated water mixing valves. 5. Strainers. 6. Hose bibbs. 7. Drain valves. 8. Water hammer arresters. 9. Trap-seal primer valves.

1.2 PERFORMANCE REQUIREMENTS

A. Minimum Working Pressure for Domestic Water Piping Specialties: 125 psig, unless otherwise indicated.

1.3 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Field quality-control test reports.

C. Operation and maintenance data.

1.4 QUALITY ASSURANCE

A. NSF Compliance:

1. Comply with NSF 14, "Plastics Piping Components and Related Materials," for plastic domestic water piping components.

2. Comply with NSF 61, "Drinking Water System Components - Health Effects; Sections 1 through 9."

PART 2 - PRODUCTS

2.1 VACUUM BREAKERS

A. Pipe-Applied, Atmospheric-Type Vacuum Breakers:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. FEBCO; SPX Valves & Controls. b. Watts Industries, Inc.; Water Products Div. c. Zurn Plumbing Products Group; Wilkins Div.

Page 47: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2. Standard: ASSE 1001. 3. Size: NPS 1/4 to NPS 3, as required to match connected piping. 4. Body: Bronze. 5. Inlet and Outlet Connections: Threaded. 6. Finish: Chrome plated.

B. Hose-Connection Vacuum Breakers:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. . b. MIFAB, Inc. c. Watts Industries, Inc.; Water Products Div. d. Woodford Manufacturing Company. e. Zurn Plumbing Products Group; Light Commercial Operation. f. Zurn Plumbing Products Group; Wilkins Div.

2. Standard: ASSE 1001. 3. Body: Bronze, nonremovable, with manual drain. 4. Outlet Connection: Garden-hose threaded complying with ASME B1.20.7. 5. Finish: Chrome or nickel plated.

2.2 BALANCING VALVES

A. Memory-Stop Balancing Valves:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: a. Hammond Valve. b. Milwaukee Valve Company. c. NIBCO INC.

2. Standard: MSS SP-110 for two-piece, copper-alloy ball valves. 3. Pressure Rating: 400-psig minimum CWP. 4. Size: NPS 2 or smaller. 5. Body: Copper alloy. 6. Port: Standard or full port. 7. Ball: Chrome-plated brass. 8. Seats and Seals: Replaceable. 9. End Connections: Solder joint or threaded. 10. Handle: Vinyl-covered steel with memory-setting device.

2.3 STRAINERS FOR DOMESTIC WATER PIPING

A. Y-Pattern Strainers:

1. Pressure Rating: 125 psig minimum, unless otherwise indicated. 2. Body: Bronze for NPS 2 and smaller; cast iron with interior lining complying with AWWA C550 or

FDA-approved, epoxy coating and for NPS 2-1/2 and larger. 3. End Connections: Threaded for NPS 2 and smaller; flanged for NPS 2-1/2 and larger. 4. Screen: Stainless steel with round perforations, unless otherwise indicated. 5. Perforation Size:

a. Strainers NPS 2 and Smaller: 0.020 inch. b. Strainers NPS 2-1/2 to NPS 4: 0.045 inch.

6. Drain: Pipe plug.

Page 48: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2.4 HOSE BIBBS

A. Hose Bibbs:

1. Standard: ASME A112.18.1 for sediment faucets. 2. Body Material: Bronze. 3. Seat: Bronze, replaceable. 4. Supply Connections: NPS 1/2 or NPS 3/4 threaded or solder-joint inlet. 5. Outlet Connection: Garden-hose thread complying with ASME B1.20.7. 6. Pressure Rating: 125 psig. 7. Vacuum Breaker: Integral nonremovable, drainable, hose-connection vacuum breaker complying

with ASSE 1011. 8. Finish for Equipment Rooms: Rough bronze, or chrome or nickel plated. 9. Finish for Service Areas: Rough bronze. 10. Finish for Finished Rooms: Chrome or nickel plated. 11. Operation for Equipment Rooms: Wheel handle or operating key. 12. Operation for Service Areas: Wheel handle. 13. Operation for Finished Rooms: Wheel handle. 14. Include operating key with each operating-key hose bibb. 15. Include integral wall flange with each chrome- or nickel-plated hose bibb.

2.5 WATER HAMMER ARRESTERS

A. Water Hammer Arresters:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. AMTROL, Inc. b. Josam Company. c. MIFAB, Inc. d. Sioux Chief Manufacturing Company, Inc. e. Smith, Jay R. Mfg. Co.; Division of Smith Industries, Inc. f. Watts Drainage Products Inc. g. Zurn Plumbing Products Group; Specification Drainage Operation.

3. Standard: ASSE 1010 or PDI-WH 201. 4. Type: Metal bellows. 5. Size: ASSE 1010, Sizes AA and A through F or PDI-WH 201, Sizes A through F.

2.6 TRAP-SEAL PRIMER VALVES

A. Supply-Type, Trap-Seal Primer Valves:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. MIFAB, Inc. b. Sioux Chief Manufacturing Company, Inc. c. Smith, Jay R. Mfg. Co.; Division of Smith Industries, Inc. d. Watts Industries, Inc.; Water Products Div.

2. Standard: ASSE 1018. 3. Pressure Rating: 125 psig minimum. 4. Body: Bronze. 5. Inlet and Outlet Connections: NPS 1/2 threaded, union, or solder joint. 6. Gravity Drain Outlet Connection: NPS 1/2 threaded or solder joint.

Page 49: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

7. Finish: Chrome plated, or rough bronze for units used with pipe or tube that is not chrome finished.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Refer to Division 15 Section "Basic Mechanical Materials and Methods" for piping joining materials, joint construction, and basic installation requirements.

B. Install water regulators with inlet and outlet shutoff valves and bypass with memory-stop balancing valve. Install pressure gages on inlet and outlet.

C. Install balancing valves in locations where they can easily be adjusted.

D. Install temperature-actuated water mixing valves with check stops or shutoff valves on inlets and with shutoff valve on outlet.

1. Install thermometers and water regulators if specified. 2. Install cabinet-type units recessed in or surface mounted on wall as specified.

E. Install Y-pattern strainers for water on supply side of each control valve, water pressure-reducing valve, solenoid valve, and pump.

F. Install water hammer arresters in water piping according to PDI-WH 201.

G. Install supply-type, trap-seal primer valves with outlet piping pitched down toward drain trap a minimum of 1 percent, and connect to floor-drain body, trap, or inlet fitting. Adjust valve for proper flow.

H. Piping installation requirements are specified in other Division 15 Sections. Drawings indicate general arrangement of piping and specialties.

I. Equipment Nameplates and Signs: Install engraved plastic-laminate equipment nameplate or sign on or near each of the following:

1. Intermediate atmospheric-vent backflow preventers. 2. Reduced-pressure-principle backflow preventers. 3. Double-check backflow-prevention assemblies. 4. Water pressure-reducing valves. 5. Primary, thermostatic, water mixing valves. 6. Supply-type, trap-seal primer valves.

J. Distinguish among multiple units, inform operator of operational requirements, indicate safety and emergency precautions, and warn of hazards and improper operations, in addition to identifying unit. Nameplates and signs are specified in Division 15 Section "Mechanical Identification."

3.2 FIELD QUALITY CONTROL

A. Perform the following tests and prepare test reports:

1. Test each reduced-pressure-principle backflow preventer and double-check backflow-prevention assembly according to authorities having jurisdiction and the device's reference standard.

B. Remove and replace malfunctioning domestic water piping specialties and retest as specified above.

Page 50: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

3.3 ADJUSTING

A. Set field-adjustable pressure set points of water pressure-reducing valves.

B. Set field-adjustable flow of balancing valves.

C. Set field-adjustable temperature set points of temperature-actuated water mixing valves.

END OF SECTION 15145

Page 51: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15150 - SANITARY WASTE AND VENT PIPING

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes the following soil and waste, sanitary drainage and vent piping inside the building:

1. Pipe, tube, and fittings. 2. Special pipe fittings.

B. See Drawings for additional chemical-waste and vent piping systems. In locations shown contractor shall match existing PV and PW piping currently utilized within the facility.

1.2 PERFORMANCE REQUIREMENTS

A. Components and installation shall be capable of withstanding the following minimum working pressure, unless otherwise indicated:

1. Soil, Waste, and Vent Piping: 10-foot head of water.

1.3 SUBMITTALS

A. Field quality-control inspection and test reports.

1.4 QUALITY ASSURANCE

A. Piping materials shall bear label, stamp, or other markings of specified testing agency.

PART 2 - PRODUCTS

2.1 PIPING MATERIALS

A. Hub-and-Spigot, Cast-Iron Pipe and Fittings: ASTM A 74, Service class.

1. Gaskets: ASTM C 564, rubber.

B. Hubless Cast-Iron Pipe and Fittings: ASTM A 888 or CISPI 301.

1. Sovent Stack Fittings: ASME B16.45 or ASSE 1043, hubless, cast-iron aerator and deaerator drainage fittings.

2. Shielded Couplings: ASTM C 1277 assembly of metal shield or housing, corrosion-resistant fasteners, and rubber sleeve with integral, center pipe stop.

a. Standard, Shielded, Stainless-Steel Couplings: CISPI 310, with stainless-steel corrugated shield; stainless-steel bands and tightening devices; and ASTM C 564, rubber sleeve.

b. Heavy-Duty, Shielded, Stainless-Steel Couplings: With stainless-steel shield, stainless-steel bands and tightening devices, and ASTM C 564, rubber sleeve.

C. ABS Pipe: ASTM D 2661, Schedule 40, solid wall.

Page 52: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1. ABS Socket Fittings: ASTM D 2661, made to ASTM D 3311, drain, waste, and vent patterns. 2. Solvent Cement and Adhesive Primer:

a. Use ABS solvent cement that has a VOC content of 325 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24).

b. Use adhesive primer that has a VOC content of 550 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24).

D. PVC Pipe: ASTM D 2665, solid-wall drain, waste, and vent.

1. PVC Socket Fittings: ASTM D 2665, socket type, made to ASTM D 3311, drain, waste, and vent patterns.

2. Solvent Cement and Adhesive Primer:

a. Use PVC solvent cement that has a VOC content of 510 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24).

b. Use adhesive primer that has a VOC content of 550 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24).

PART 3 - EXECUTION

3.1 PIPING APPLICATIONS

A. Special pipe fittings with pressure ratings at least equal to piping pressure ratings may be used in applications below, unless otherwise indicated.

B. Flanges and unions may be used on aboveground pressure piping, unless otherwise indicated.

C. Aboveground, soil, waste, and vent piping shall be the following:

1. Service class, hub-and-spigot, cast-iron soil pipe and fittings; gaskets; and compression joints. 2. Hubless cast-iron soil pipe and fittings and sovent stack fittings; standard, shielded, stainless-steel

couplings; and hubless-coupling joints. 3. ABS pipe, ABS socket fittings, and solvent-cemented joints. 4. PVC pipe, PVC socket fittings, and solvent-cemented joints

D. Underground, soil, waste, and vent piping NPS 4 and smaller shall be the following:

1. Service class, hub-and-spigot, cast-iron soil pipe and fittings; gaskets; and compression joints. 2. Hubless cast-iron soil pipe and fittings; standard, shielded, stainless-steel couplings; and hubless-

coupling joints. 3. ABS pipe, ABS socket fittings, and solvent-cemented joints. 4. PVC pipe, PVC socket fittings, and solvent-cemented joints.

3.2 PIPING INSTALATION

A. Basic piping installation requirements are specified in Division 15 Section "Common Work Results for Plumbing."

B. Install cleanouts at grade and extend to where building sanitary drains connect to building sanitary sewers.

C. Install wall penetration system at each service pipe penetration through foundation wall. Make installation watertight. Wall penetration systems are specified in Division 15 Section "Common Work Results for Plumbing."

Page 53: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

D. Install cast-iron soil piping according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook," Chapter IV, "Installation of Cast Iron Soil Pipe and Fittings."

E. Make changes in direction for soil and waste drainage and vent piping using appropriate branches, bends, and long-sweep bends. Sanitary tees and short-sweep 1/4 bends may be used on vertical stacks if change in direction of flow is from horizontal to vertical. Use long-turn, double Y-branch and 1/8-bend fittings if 2 fixtures are installed back to back or side by side with common drain pipe. Straight tees, elbows, and crosses may be used on vent lines. Do not change direction of flow more than 90 degrees. Use proper size of standard increasers and reducers if pipes of different sizes are connected. Reducing size of drainage piping in direction of flow is prohibited.

F. Lay buried building drainage piping beginning at low point of each system. Install true to grades and alignment indicated, with unbroken continuity of invert. Place hub ends of piping upstream. Install required gaskets according to manufacturer's written instructions for use of lubricants, cements, and other installation requirements. Maintain swab in piping and pull past each joint as completed.

G. Install soil and waste drainage and vent piping at the following minimum slopes, unless otherwise indicated:

1. Building Sanitary Drain: 2 percent downward in direction of flow for piping NPS 3 and smaller; 1 percent downward in direction of flow for piping NPS 4 and larger.

2. Horizontal Sanitary Drainage Piping: 2 percent downward in direction of flow. 3. Vent Piping: 1 percent down toward vertical fixture vent or toward vent stack.

H. Sleeves are not required for cast-iron soil piping passing through concrete slabs-on-grade if slab is without membrane waterproofing.

I. Do not enclose, cover, or put piping into operation until it is inspected and approved by authorities having jurisdiction.

3.3 JOINT CONSTRUCTION

A. Basic piping joint construction requirements are specified in Division 15 Section "Common Work Results for Plumbing."

B. Cast-Iron, Soil-Piping Joints: Make joints according to CISPI's "Cast Iron Soil Pipe and Fittings Handbook," Chapter IV, "Installation of Cast Iron Soil Pipe and Fittings."

1. Gasketed Joints: Make with rubber gasket matching class of pipe and fittings. 2. Hubless Joints: Make with rubber gasket and sleeve or clamp.

C. Soldered Joints: Use ASTM B 813, water-flushable, lead-free flux; ASTM B 32, lead-free-alloy solder; and ASTM B 828 procedure, unless otherwise indicated.

3.4 HANGER AND SUPPORT INSTALLATION

A. Pipe hangers and supports are specified in Division 15 Section "Hangers and Supports for Plumbing Piping and Equipment." Install the following:

1. Vertical Piping: MSS Type 8 or Type 42, clamps. 2. Individual, Straight, Horizontal Piping Runs: According to the following:

a. 100 Feet and Less: MSS Type 1, adjustable, steel clevis hangers.

B. Install supports according to Division 15 Section "Hangers and Supports for Plumbing Piping and Equipment."

Page 54: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

C. Support vertical piping and tubing at base and at each floor.

D. Rod diameter may be reduced 1 size for double-rod hangers, with 3/8-inch minimum rods.

E. Install hangers for cast-iron soil piping with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 1-1/2 and NPS 2: 60 inches with 3/8-inch rod. 2. NPS 3: 60 inches with 1/2-inch rod. 3. NPS 4 and NPS 5: 60 inches with 5/8-inch rod. 4. NPS 6: 60 inches with 3/4-inch rod. 5. Spacing for 10-foot lengths may be increased to 10 feet. Spacing for fittings is limited to 60 inches.

F. Install supports for vertical cast-iron soil piping every 15 feet.

G. Install hangers for steel piping with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 1-1/4: 84 inches with 3/8-inch rod. 2. NPS 1-1/2: 108 inches with 3/8-inch rod. 3. NPS 2: 10 feet with 3/8-inch rod. 4. NPS 2-1/2: 11 feet with 1/2-inch rod. 5. NPS 3: 12 feet with 1/2-inch rod. 6. NPS 4 and NPS 5: 12 feet with 5/8-inch rod. 7. NPS 6: 12 feet with 3/4-inch rod.

H. Install supports for vertical steel piping every 15 feet.

I. Install hangers for copper tubing with the following maximum horizontal spacing and minimum rod diameters:

1. NPS 1-1/4: 72 inches with 3/8-inch rod. 2. NPS 1-1/2 and NPS 2: 96 inches with 3/8-inch rod. 3. NPS 2-1/2: 108 inches with 1/2-inch rod. 4. NPS 3 to NPS 5: 10 feet with 1/2-inch rod. 5. NPS 6: 10 feet with 5/8-inch rod.

J. Install supports for vertical copper tubing every 10 feet.

K. Support piping and tubing not listed above according to MSS SP-69 and manufacturer's written instructions.

3.5 CONNECTIONS

A. Connect soil and waste piping to exterior sanitary sewerage piping. Use transition fitting to join dissimilar piping materials.

B. Connect drainage and vent piping to the following:

1. Plumbing Fixtures: Connect drainage piping in sizes indicated, but not smaller than required by plumbing code.

3.6 FIELD QUALITY CONTROL

A. During installation, notify authorities having jurisdiction at least 24 hours before inspection must be made. Perform tests specified below in presence of authorities having jurisdiction.

Page 55: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1. Roughing-in Inspection: Arrange for inspection of piping before concealing or closing-in after roughing-in and before setting fixtures.

2. Final Inspection: Arrange for final inspection by authorities having jurisdiction to observe tests specified below and to ensure compliance with requirements.

B. Reinspection: If authorities having jurisdiction find that piping will not pass test or inspection, make required corrections and arrange for reinspection.

C. Reports: Prepare inspection reports and have them signed by authorities having jurisdiction.

D. Test sanitary drainage and vent piping according to procedures of authorities having jurisdiction.

1. Repair leaks and defects with new materials and retest piping, or portion thereof, until satisfactory results are obtained.

2. Prepare reports for tests and required corrective action.

3.7 CLEANING

A. Clean interior of piping. Remove dirt and debris as work progresses.

B. Protect drains during remainder of construction period to avoid clogging with dirt and debris and to prevent damage from traffic and construction work.

C. Place plugs in ends of uncompleted piping at end of day and when work stops.

END OF SECTION 15150

Page 56: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 4

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15155 - SANITARY WASTE PIPING SPECIALTIES

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes the following sanitary drainage piping specialties: 1. Cleanouts. 2. Floor drains. 3. Miscellaneous sanitary drainage piping specialties.

1.2 QUALITY ASSURANCE

A. Drainage piping specialties shall bear label, stamp, or other markings of specified testing agency.

PART 2 - PRODUCTS

2.1 CLEANOUTS

A. Exposed Cast-Iron Cleanouts:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

2. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 3. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated

on Drawings or a comparable product by one of the following:

a. Josam Company; Josam Div. b. MIFAB, Inc. c. Smith, Jay R. Mfg. Co.; Division of Smith Industries, Inc. d. Tyler Pipe; Wade Div. e. Watts Drainage Products Inc. f. Zurn Plumbing Products Group; Specification Drainage Operation.

4. Standard: ASME A112.36.2M for cast iron for cleanout test tee. 5. Size: Same as connected drainage piping 6. Body Material: As required to match connected piping. 7. Closure: Countersunk, brass plug. 8. Closure Plug Size: Same as or not more than one size smaller than cleanout size.

B. Cast-Iron Floor Cleanouts:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

2. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 3. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated

on Drawings or a comparable product by one of the following:

a. Josam Company; Josam Div. b. Oatey. c. Sioux Chief Manufacturing Company, Inc. d. Smith, Jay R. Mfg. Co.; Division of Smith Industries, Inc. e. Tyler Pipe; Wade Div.

Page 57: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 4

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

f. Watts Drainage Products Inc. g. Zurn Plumbing Products Group; Light Commercial Operation. h. Zurn Plumbing Products Group; Specification Drainage Operation.

4. Standard: ASME A112.36.2M for adjustable housing cleanout. 5. Size: Same as connected branch. 6. Type: Adjustable housing. 7. Body or Ferrule: Cast iron. 8. Clamping Device: Not required. 9. Outlet Connection: Inside calk. 10. Closure: Brass plug with straight threads and gasket. 11. Adjustable Housing Material: Cast iron with threads. 12. Frame and Cover Material and Finish: Nickel-bronze, copper alloy. 13. Frame and Cover Shape: Round. 14. Top Loading Classification: Medium Duty. 15. Riser: ASTM A 74, Service class, cast-iron drainage pipe fitting and riser to cleanout.

C. Cast-Iron Wall Cleanouts:

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

2. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 3. Basis-of-Design Product: Subject to compliance with requirements, provide the product indicated

on Drawings or a comparable product by one of the following:

a. Josam Company; Josam Div. b. MIFAB, Inc. c. Smith, Jay R. Mfg. Co.; Division of Smith Industries, Inc. d. Tyler Pipe; Wade Div. e. Watts Drainage Products Inc. f. Zurn Plumbing Products Group; Specification Drainage Operation.

4. Standard: ASME A112.36.2M. Include wall access. 5. Size: Same as connected drainage piping. 6. Body: As required to match connected piping. 7. Closure: Countersunk, drilled-and-threaded plug. 8. Closure Plug Size: Same as or not more than one size smaller than cleanout size. 9. Wall Access: Round, deep, chrome-plated bronze cover plate with screw.

2.2 MISCELLANEOUS SANITARY DRAINAGE PIPING SPECIALTIES

A. Open Drains:

1. Description: Shop or field fabricate from ASTM A 74, Service class, hub-and-spigot, cast-iron, soil-pipe fittings. Include P-trap, hub-and-spigot riser section; and where required, increaser fitting joined with ASTM C 564, rubber gaskets.

2. Size: Same as connected waste piping.

B. Deep-Seal Traps:

1. Description: Cast-iron or bronze casting, with inlet and outlet matching connected piping and cleanout trap-seal primer valve connection.

2. Size: Same as connected waste piping.

a. NPS 2: 4-inch- minimum water seal. b. NPS 2-1/2 and Larger: 5-inch- minimum water seal.

C. Floor-Drain, Trap-Seal Primer Fittings:

Page 58: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 4

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1. Description: Cast iron, with threaded inlet and threaded or spigot outlet, and trap-seal primer valve connection.

2. Size: Same as floor drain outlet with NPS 1/2 side inlet.

D. Air-Gap Fittings:

1. Standard: ASME A112.1.2, for fitting designed to ensure fixed, positive air gap between installed inlet and outlet piping.

2. Body: Bronze or cast iron. 3. Inlet: Opening in top of body. 4. Outlet: Larger than inlet. 5. Size: Same as connected waste piping and with inlet large enough for associated indirect waste

piping.

E. Trap Guards:

1. As approved by authority having jurisdiction.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Refer to Division 15 Section "Common Work Results for Plumbing" for piping joining materials, joint construction, and basic installation requirements.

B. Install cleanouts in aboveground piping and building drain piping according to the following, unless otherwise indicated:

1. Size same as drainage piping up to NPS 4. Use NPS 4 for larger drainage piping unless larger cleanout is indicated.

2. Locate at each change in direction of piping greater than 45 degrees. 3. Locate at minimum intervals of 50 feet for piping NPS 4 and smaller and 100 feet for larger piping. 4. Locate at base of each vertical soil and waste stack.

C. For floor cleanouts for piping below floors, install cleanout deck plates with top flush with finished floor.

D. For cleanouts located in concealed piping, install cleanout wall access covers, of types indicated, with frame and cover flush with finished wall.

E. Install floor drains at low points of surface areas to be drained. Set grates of drains flush with finished floor, unless otherwise indicated.

1. Position floor drains for easy access and maintenance. 2. Set floor drains below elevation of surrounding finished floor to allow floor drainage. Set with

grates depressed according to the following drainage area radii:

a. Radius, 30 Inches or Less: Equivalent to 1 percent slope, but not less than 1/4-inch total depression.

b. Radius, 30 to 60 Inches: Equivalent to 1 percent slope. c. Radius, 60 Inches or Larger: Equivalent to 1 percent slope, but not greater than 1-inch total

depression.

3. Install floor-drain flashing collar or flange so no leakage occurs between drain and adjoining flooring. Maintain integrity of waterproof membranes where penetrated.

4. Install individual traps for floor drains connected to sanitary building drain, unless otherwise indicated.

Page 59: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 4

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

F. Assemble open drain fittings and install with top of hub 2 inches above floor.

G. Install deep-seal traps on floor drains and other waste outlets, if indicated.

H. Install floor-drain, trap-seal primer fittings on inlet to floor drains that require trap-seal primer connection.

1. Exception: Fitting may be omitted if trap has trap-seal primer connection. 2. Size: Same as floor drain inlet.

I. Install air-gap fittings on draining-type backflow preventers and on indirect-waste piping discharge into sanitary drainage system.

J. Install traps on plumbing specialty drain outlets. Omit traps on indirect wastes unless trap is indicated.

K. Install escutcheons at wall, floor, and ceiling penetrations in exposed finished locations and within cabinets and millwork. Use deep-pattern escutcheons if required to conceal protruding pipe fittings.

3.2 CONNECTIONS

A. Piping installation requirements are specified in other Division 15 Sections. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Install piping adjacent to equipment to allow service and maintenance.

3.3 LABELING AND IDENTIFYING

A. Distinguish among multiple units, inform operator of operational requirements, indicate safety and emergency precautions, and warn of hazards and improper operations, in addition to identifying unit. Nameplates and signs are specified in Division 15 Section "Identification for Plumbing Piping and Equipment."

3.4 PROTECTION

A. Protect drains during remainder of construction period to avoid clogging with dirt or debris and to prevent damage from traffic or construction work.

B. Place plugs in ends of uncompleted piping at end of each day or when work stops.

END OF SECTION 15155

Page 60: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15195 - NATURAL-GAS PIPING

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Pipes, tubes, and fittings. 2. Piping specialties. 3. Piping and tubing joining materials. 4. Valves.

1.2 PERFORMANCE REQUIREMENTS

A. Minimum Operating-Pressure Ratings:

1. Piping and Valves: 100 psig minimum unless otherwise indicated.

B. Natural-Gas System Pressure within Buildings: 0.5 psig or less.

C. Natural-Gas System Pressures within Buildings: Two pressure ranges. Primary pressure is more than 0.5 psig.

1.3 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Welding certificates.

C. Field quality-control reports.

D. Operation and maintenance data.

1.4 QUALITY ASSURANCE

A. Steel Support Welding Qualifications: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel."

B. Pipe Welding Qualifications: Qualify procedures and operators according to ASME Boiler and Pressure Vessel Code.

C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

Page 61: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

PART 2 - PRODUCTS

2.1 PIPES, TUBES, AND FITTINGS

A. Steel Pipe: ASTM A 53/A 53M, black steel, Schedule 40, Type E or S, Grade B.

1. Malleable-Iron Threaded Fittings: ASME B16.3, Class 150, standard pattern. 2. Wrought-Steel Welding Fittings: ASTM A 234/A 234M for butt welding and socket welding. 3. Unions: ASME B16.39, Class 150, malleable iron with brass-to-iron seat, ground joint, and

threaded ends. 4. Protective Coating for Underground Piping: Factory-applied, three-layer coating of epoxy,

adhesive, and PE.

a. Joint Cover Kits: Epoxy paint, adhesive, and heat-shrink PE sleeves.

B. PE Pipe: ASTM D 2513, SDR 11.

1. PE Fittings: ASTM D 2683, socket-fusion type or ASTM D 3261, butt-fusion type with dimensions matching PE pipe.

2. PE Transition Fittings: Factory-fabricated fittings with PE pipe complying with ASTM D 2513, SDR 11; and steel pipe complying with ASTM A 53/A 53M, black steel, Schedule 40, Type E or S, Grade B.

3. Anodeless Service-Line Risers: Factory fabricated and leak tested.

a. Underground Portion: PE pipe complying with ASTM D 2513, SDR 11 inlet. b. Casing: Steel pipe complying with ASTM A 53/A 53M, Schedule 40, black steel, Type E or

S, Grade B, with corrosion-protective coating covering. c. Aboveground Portion: PE transition fitting. d. Outlet shall be threaded or suitable for welded connection. e. Tracer wire connection. f. Ultraviolet shield. g. Stake supports with factory finish to match steel pipe casing or carrier pipe.

4. Transition Service-Line Risers: Factory fabricated and leak tested.

a. Underground Portion: PE pipe complying with ASTM D 2513, SDR 11 inlet connected to steel pipe complying with ASTM A 53/A 53M, Schedule 40, Type E or S, Grade B, with corrosion-protective coating for aboveground outlet.

b. Outlet shall be threaded or suitable for welded connection. c. Bridging sleeve over mechanical coupling. d. Factory-connected anode. e. Tracer wire connection. f. Ultraviolet shield. g. Stake supports with factory finish to match steel pipe casing or carrier pipe.

2.2 PIPING SPECIALTIES

A. Appliance Flexible Connectors:

1. Indoor, Fixed-Appliance Flexible Connectors: Comply with ANSI Z21.24. 2. Indoor, Movable-Appliance Flexible Connectors: Comply with ANSI Z21.69. 3. Outdoor, Appliance Flexible Connectors: Comply with ANSI Z21.75. 4. Corrugated stainless-steel tubing with polymer coating. 5. Operating-Pressure Rating: 0.5 psig. 6. End Fittings: Zinc-coated steel. 7. Threaded Ends: Comply with ASME B1.20.1. 8. Maximum Length: 24 inches.

Page 62: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

B. Quick-Disconnect Devices: Comply with ANSI Z21.41.

1. Copper-alloy convenience outlet and matching plug connector. 2. Nitrile seals. 3. Hand operated with automatic shutoff when disconnected. 4. For indoor or outdoor applications. 5. Adjustable, retractable restraining cable.

2.3 JOINING MATERIALS

A. Joint Compound and Tape: Suitable for natural gas.

B. Welding Filler Metals: Comply with AWS D10.12/D10.12M for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded.

C. Brazing Filler Metals: Alloy with melting point greater than 1000 deg F complying with AWS A5.8/A5.8M. Brazing alloys containing more than 0.05 percent phosphorus are prohibited.

2.4 MANUAL GAS SHUTOFF VALVES

A. General Requirements for Metallic Valves, NPS 2 and Smaller: Comply with ASME B16.33.

1. CWP Rating: 125 psig. 2. Threaded Ends: Comply with ASME B1.20.1. 3. Dryseal Threads on Flare Ends: Comply with ASME B1.20.3. 4. Service Mark: Valves 1-1/4 inches to NPS 2 shall have initials "WOG" permanently marked on

valve body.

2.5 DIELECTRIC UNIONS

A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. Hart Industries International, Inc. 2. McDonald, A. Y. Mfg. Co. 3. Watts Regulator Co.; Division of Watts Water Technologies, Inc. 4. Wilkins; Zurn Plumbing Products Group.

B. Minimum Operating-Pressure Rating: 150 psig.

C. Combination fitting of copper alloy and ferrous materials.

D. Insulating materials suitable for natural gas.

E. Combination fitting of copper alloy and ferrous materials with threaded, brazed-joint, plain, or welded end connections that match piping system materials.

2.6 LABELING AND IDENTIFYING

A. Detectable Warning Tape: Acid- and alkali-resistant, PE film warning tape manufactured for marking and identifying underground utilities, a minimum of 6 inches wide and 4 mils thick, continuously inscribed with a description of utility, with metallic core encased in a protective jacket for corrosion protection, detectable by metal detector when tape is buried up to 30 inches deep; colored yellow.

Page 63: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

PART 3 - EXECUTION

3.1 OUTDOOR PIPING INSTALLATION

A. Comply with NFPA 54 and the International Fuel Gas Code for installation and purging of natural-gas piping.

B. Install underground, natural-gas piping buried at least 36 inches below finished grade. Comply with requirements in Division 2 Section "Earthwork" for excavating, trenching, and backfilling.

1. If natural-gas piping is installed less than 36 inches below finished grade, install it in containment conduit.

C. Install underground, PE, natural-gas piping according to ASTM D 2774.

D. Steel Piping with Protective Coating:

1. Apply joint cover kits to pipe after joining to cover, seal, and protect joints. 2. Repair damage to PE coating on pipe as recommended in writing by protective coating

manufacturer. 3. Replace pipe having damaged PE coating with new pipe.

E. Install fittings for changes in direction and branch connections.

3.2 INDOOR PIPING INSTALLATION

A. Comply with NFPA 54 and the International Fuel Gas Code for installation and purging of natural-gas piping.

B. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems. Indicated locations and arrangements are used to size pipe and calculate friction loss, expansion, and other design considerations. Install piping as indicated unless deviations to layout are approved on Coordination Drawings.

C. Arrange for pipe spaces, chases, slots, sleeves, and openings in building structure during progress of construction, to allow for mechanical installations.

D. Install piping in concealed locations unless otherwise indicated and except in equipment rooms and service areas.

E. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise.

F. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal.

G. Locate valves for easy access.

H. Install natural-gas piping at uniform grade of 2 percent down toward drip and sediment traps.

I. Install piping free of sags and bends.

J. Install fittings for changes in direction and branch connections.

K. Verify final equipment locations for roughing-in.

Page 64: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

L. Comply with requirements in Sections specifying gas-fired appliances and equipment for roughing-in requirements.

M. Drips and Sediment Traps: Install drips at points where condensate may collect, including service-meter outlets. Locate where accessible to permit cleaning and emptying. Do not install where condensate is subject to freezing.

1. Construct drips and sediment traps using tee fitting with bottom outlet plugged or capped. Use nipple a minimum length of 3 pipe diameters, but not less than 3 inches long and same size as connected pipe. Install with space below bottom of drip to remove plug or cap.

N. Extend relief vent connections for service regulators, line regulators, and overpressure protection devices to outdoors and terminate with weatherproof vent cap.

O. Conceal pipe installations in walls, pipe spaces, utility spaces, above ceilings, below grade or floors, and in floor channels unless indicated to be exposed to view.

P. Use eccentric reducer fittings to make reductions in pipe sizes. Install fittings with level side down.

Q. Connect branch piping from top or side of horizontal piping.

R. Install unions in pipes NPS 2 and smaller, adjacent to each valve, at final connection to each piece of equipment.

S. Do not use natural-gas piping as grounding electrode.

T. Install strainer on inlet of each line-pressure regulator and automatic or electrically operated valve.

U. Install sleeves for piping penetrations of walls, ceilings, and floors. Comply with requirements for sleeves specified in Division 15 Section "Sleeves and Sleeve Seals for HVAC Piping."

V. Install sleeve seals for piping penetrations of concrete walls and slabs. Comply with requirements for sleeve seals specified in Division 15 Section "Sleeves and Sleeve Seals for HVAC Piping."

W. Install escutcheons for piping penetrations of walls, ceilings, and floors. Comply with requirements for escutcheons specified in Division 15 Section "Escutcheons for HVAC Piping."

3.3 VALVE INSTALLATION

A. Install manual gas shutoff valve for each gas appliance ahead of corrugated stainless-steel tubing or copper connector.

B. Install regulators and overpressure protection devices with maintenance access space adequate for servicing and testing.

3.4 PIPING JOINT CONSTRUCTION

A. Ream ends of pipes and tubes and remove burrs.

B. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before assembly.

C. Threaded Joints:

1. Thread pipe with tapered pipe threads complying with ASME B1.20.1. 2. Cut threads full and clean using sharp dies. 3. Ream threaded pipe ends to remove burrs and restore full inside diameter of pipe.

Page 65: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 6 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

4. Apply appropriate tape or thread compound to external pipe threads unless dryseal threading is specified.

5. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. Do not use pipe sections that have cracked or open welds.

D. Welded Joints:

1. Construct joints according to AWS D10.12/D10.12M, using qualified processes and welding operators.

2. Bevel plain ends of steel pipe. 3. Patch factory-applied protective coating as recommended by manufacturer at field welds and

where damage to coating occurs during construction.

E. PE Piping Heat-Fusion Joints: Clean and dry joining surfaces by wiping with clean cloth or paper towels. Join according to ASTM D 2657.

1. Plain-End Pipe and Fittings: Use butt fusion. 2. Plain-End Pipe and Socket Fittings: Use socket fusion.

3.5 HANGER AND SUPPORT INSTALLATION

A. Comply with requirements for pipe hangers and supports specified in Division 15 Section "Hangers and Supports."

B. Install hangers for horizontal steel piping with the following maximum spacing and minimum rod sizes:

1. NPS 1 and Smaller: Maximum span, 96 inches; minimum rod size, 3/8 inch. 2. NPS 1-1/4: Maximum span, 108 inches; minimum rod size, 3/8 inch. 3. NPS 1-1/2 and NPS 2: Maximum span, 108 inches; minimum rod size, 3/8 inch.

3.6 CONNECTIONS

A. Connect to utility's gas main according to utility's procedures and requirements.

B. Install natural-gas piping electrically continuous, and bonded to gas appliance equipment grounding conductor of the circuit powering the appliance according to NFPA 70.

C. Install piping adjacent to appliances to allow service and maintenance of appliances.

D. Connect piping to appliances using manual gas shutoff valves and unions. Install valve within 72 inches of each gas-fired appliance and equipment. Install union between valve and appliances or equipment.

E. Sediment Traps: Install tee fitting with capped nipple in bottom to form drip, as close as practical to inlet of each appliance.

3.7 LABELING AND IDENTIFYING

A. Comply with requirements in Division 15 Section "Mechanical Identification" for piping and valve identification.

B. Install detectable warning tape directly above gas piping, 12 inches below finished grade, except 6 inches below subgrade under pavements and slabs.

Page 66: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 7 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

3.8 FIELD QUALITY CONTROL

A. Test, inspect, and purge natural gas according to NFPA 54 and the International Fuel Gas Code and authorities having jurisdiction.

B. Natural-gas piping will be considered defective if it does not pass tests and inspections.

C. Prepare test and inspection reports.

3.9 PIPING SCHEDULE

A. Underground natural-gas piping shall be the following:

1. PE pipe and fittings joined by heat fusion; service-line risers with tracer wire terminated in an accessible location.

B. Aboveground natural-gas piping shall be the following:

1. Steel pipe with malleable-iron fittings and threaded joints – NPS 2 and smaller. 2. Steel pipe with wrought-steel fittings and welded joints – NPS 2 1/2 and larger.

END OF SECTION 15195

Page 67: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 3

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15410 - PLUMBING FIXTURES

PART 1 - GENERAL

1.1 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Shop Drawings: Diagram power, signal, and control wiring.

C. Operation and maintenance data.

1.2 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

B. Regulatory Requirements: Comply with requirements in ICC A117.1, "Accessible and Usable Buildings and Facilities"; Public Law 90-480, "Architectural Barriers Act"; and Public Law 101-336, "Americans with Disabilities Act"; for plumbing fixtures for people with disabilities.

C. Regulatory Requirements: Comply with requirements in Public Law 102-486, "Energy Policy Act," about water flow and consumption rates for plumbing fixtures.

D. NSF Standard: Comply with NSF 61, "Drinking Water System Components--Health Effects," for fixture materials that will be in contact with potable water.

E. Select combinations of fixtures and trim, faucets, fittings, and other components that are compatible.

F. Comply with the following applicable standards and other requirements specified for plumbing fixtures:

1. Enameled, Cast-Iron Fixtures: ASME A112.19.1M. 2. Porcelain-Enameled, Formed-Steel Fixtures: ASME A112.19.4M. 3. Solid-Surface-Material Lavatories and Sinks: ANSI/ICPA SS-1. 4. Stainless-Steel Residential Sinks: ASME A112.19.3. 5. Vitreous-China Fixtures: ASME A112.19.2M. 6. Water-Closet, Flush Valve, Tank Trim: ASME A112.19.5.

G. Comply with the following applicable standards and other requirements specified for lavatory and sink faucets: 1. Backflow Protection Devices for Faucets with Hose-Thread Outlet: ASME A112.18.3M. 2. Faucets: ASME A112.18.1. 3. Hose-Connection Vacuum Breakers: ASSE 1011. 4. Hose-Coupling Threads: ASME B1.20.7. 5. Integral, Atmospheric Vacuum Breakers: ASSE 1001. 6. NSF Potable-Water Materials: NSF 61. 7. Pipe Threads: ASME B1.20.1. 8. Sensor-Actuated Faucets and Electrical Devices: UL 1951. 9. Supply Fittings: ASME A112.18.1. 10. Brass Waste Fittings: ASME A112.18.2.

H. Comply with the following applicable standards and other requirements specified for shower faucets: 1. Combination, Pressure-Equalizing and Thermostatic-Control Antiscald Faucets: ASSE 1016. 2. Faucets: ASME A112.18.1. 3. High-Temperature-Limit Controls for Thermal-Shock-Preventing Devices: ASTM F 445.

Page 68: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 3

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

4. Hose-Coupling Threads: ASME B1.20.7. 5. Manual-Control Antiscald Faucets: ASTM F 444. 6. Pipe Threads: ASME B1.20.1. 7. Pressure-Equalizing-Control Antiscald Faucets: ASTM F 444 and ASSE 1016. 8. Thermostatic-Control Antiscald Faucets: ASTM F 444 and ASSE 1016.

I. Comply with the following applicable standards and other requirements specified for miscellaneous fittings:

1. Atmospheric Vacuum Breakers: ASSE 1001. 2. Brass and Copper Supplies: ASME A112.18.1. 3. Brass Waste Fittings: ASME A112.18.2.

J. Comply with the following applicable standards and other requirements specified for miscellaneous components: 1. Flexible Water Connectors: ASME A112.18.6. 2. Hose-Coupling Threads: ASME B1.20.7. 3. Off-Floor Fixture Supports: ASME A112.6.1M. 4. Pipe Threads: ASME B1.20.1. 5. Plastic Toilet Seats: ANSI Z124.5. 6. Supply and Drain Protective Shielding Guards: ICC A117.1.

PART 2 - PRODUCTS

A. See plumbing drawing schedule.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Assemble plumbing fixtures, trim, fittings, and other components according to manufacturers' written instructions.

B. Install off-floor supports, affixed to building substrate, for wall-mounting fixtures.

1. Use carrier supports with waste fitting and seal for back-outlet fixtures. 2. Use carrier supports without waste fitting for fixtures with tubular waste piping. 3. Use chair-type carrier supports with rectangular steel uprights for accessible fixtures.

C. Install back-outlet, wall-mounting fixtures onto waste fitting seals and attach to supports.

D. Install floor-mounting fixtures on closet flanges or other attachments to piping or building substrate.

E. Install wall-mounting fixtures with tubular waste piping attached to supports.

F. Install fixtures level and plumb according to roughing-in drawings.

G. Install water-supply piping with stop on each supply to each fixture to be connected to water distribution piping. Attach supplies to supports or substrate within pipe spaces behind fixtures. Install stops in locations where they can be easily reached for operation.

H. Install trap and tubular waste piping on drain outlet of each fixture to be directly connected to sanitary drainage system.

I. Install tubular waste piping on drain outlet of each fixture to be indirectly connected to drainage system.

J. Install toilet seats on water closets.

Page 69: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 3

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

K. Install faucet-spout fittings with specified flow rates and patterns in faucet spouts if faucets are not available with required rates and patterns. Include adapters if required.

L. Install water-supply flow-control fittings with specified flow rates in fixture supplies at stop valves.

M. Install faucet flow-control fittings with specified flow rates and patterns in faucet spouts if faucets are not available with required rates and patterns. Include adapters if required.

N. Install shower flow-control fittings with specified maximum flow rates in shower arms.

O. Install traps on fixture outlets.

1. Exception: Omit trap on fixtures with integral traps. 2. Exception: Omit trap on indirect wastes, unless otherwise indicated.

P. Install escutcheons at piping wall and ceiling penetrations in exposed, finished locations and within cabinets and millwork. Use deep-pattern escutcheons if required to conceal protruding fittings. Escutcheons are specified in Division 15 Section "Basic Mechanical Materials and Methods."

Q. Seal joints between fixtures and walls, floors, and countertops using sanitary-type, one-part, mildew-resistant silicone sealant. Match sealant color to fixture color. Sealants are specified in Division 7 Section.

3.2 CONNECTIONS

A. Piping installation requirements are specified in other Division 15 Sections. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Connect fixtures with water supplies, stops, and risers, and with traps, soil, waste, and vent piping. Use size fittings required to match fixtures.

C. Ground equipment according to Division 16 Section "Grounding and Bonding."

D. Connect wiring according to Division 16 Section "Conductors and Cables."

3.3 FIELD QUALITY CONTROL

A. Verify that installed plumbing fixtures are categories and types specified for locations where installed.

B. Check that plumbing fixtures are complete with trim, faucets, fittings, and other specified components.

C. Inspect installed plumbing fixtures for damage. Replace damaged fixtures and components.

D. Test installed fixtures after water systems are pressurized for proper operation. Replace malfunctioning fixtures and components, then retest. Repeat procedure until units operate properly.

3.4 PROTECTION

A. Provide protective covering for installed fixtures and fittings.

B. Do not allow use of plumbing fixtures for temporary facilities unless approved in writing by Owner.

END OF SECTION 15410

Page 70: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15486 - FUEL-FIRED WATER HEATERS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes: 1. Gas-fired, tankless, domestic-water heaters.

1.3 SUBMITTALS

A. Product Data: For each type and size of domestic-water heater indicated. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.

B. Shop Drawings:

1. Wiring Diagrams: For power, signal, and control wiring.

C. Product Certificates: For each type of gas-fired, tankless domestic-water heater, from manufacturer.

D. Domestic-Water Heater Labeling: Certified and labeled by testing agency acceptable to authorities having jurisdiction.

E. Source quality-control reports.

F. Field quality-control reports.

G. Operation and Maintenance Data: For fuel-fired, domestic-water heaters to include in emergency, operation, and maintenance manuals.

H. Warranty: Sample of special warranty.

1.4 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

B. ASHRAE/IESNA 90.1 Compliance: Fabricate and label fuel-fired, domestic-water heaters to comply with ASHRAE/IESNA 90.1.

C. ASME Compliance:

1. Where ASME-code construction is indicated, fabricate and label commercial, domestic-water heater storage tanks to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

2. Where ASME-code construction is indicated, fabricate and label commercial, finned-tube, domestic-water heaters to comply with ASME Boiler and Pressure Vessel Code: Section IV.

Page 71: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

D. NSF Compliance: Fabricate and label equipment components that will be in contact with potable water to comply with NSF 61, "Drinking Water System Components - Health Effects."

1.5 COORDINATION

A. Coordinate sizes and locations of concrete bases with actual equipment provided.

1.6 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of fuel-fired, domestic-water heaters that fail in materials or workmanship within specified warranty period.

PART 2 - PRODUCTS

2.1 GAS-FIRED, TANKLESS, DOMESTIC-WATER HEATERS

A. Manufacturers: Subject to compliance with requirements available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following: 1. Bosch Water Heating. 2. Bradford White Corporation. 3. NORITZ America Corp. 4. Paloma Industries, Inc. 5. Rheem Manufacturing Company; Rheem Water Heating. 6. Rinnai Corporation. 7. Smith, A. O. Water Products Co.; a division of A. O. Smith Corporation. 8. State Industries.

B. Standard: ANSI Z21.10.3/CSA 4.3 for gas-fired, instantaneous, domestic-water heaters for indoor application.

C. Construction: Copper piping or tubing complying with NSF 61 barrier materials for potable water, without storage capacity.

1. Tappings: ASME B1.20.1 pipe thread. 2. Pressure Rating: 150 psig. 3. Heat Exchanger: Copper tubing. 4. Insulation: Comply with ASHRAE/IESNA 90.1. 5. Jacket: Metal, with enameled finish, or plastic. 6. Burner: For use with tankless, domestic-water heaters and natural-gas fuel. 7. Automatic Ignition: Manufacturer's proprietary system for automatic, gas ignition. 8. Temperature Control: Adjustable thermostat.

D. Support: Bracket for wall mounting.

2.2 SOURCE QUALITY CONTROL

A. Factory Tests: Test and inspect assembled domestic-water heaters and storage tank specified to be ASME-code construction, according to ASME Boiler and Pressure Vessel Code.

B. Hydrostatically test commercial domestic-water heaters and storage tank to minimum of one and one-half times pressure rating before shipment.

Page 72: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

C. Domestic-water heaters will be considered defective if they do not pass tests and inspections. Comply with requirements in Division 1 Section "Quality Requirements" for retesting and reinspecting requirements and Division 1 Section "Execution Requirements" for requirements for correcting the Work.

D. Prepare test and inspection reports.

PART 3 - EXECUTION

3.1 DOMESTIC-WATER HEATER INSTALLATION

A. Tankless, Domestic-Water Heater Mounting: Install tankless, domestic-water heaters on wall bracket.

1. Maintain manufacturer's recommended clearances. 2. Arrange units so controls and devices that require servicing are accessible. 3. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and

directions furnished with items to be embedded. 4. Install anchor bolts to elevations required for proper attachment to supported equipment. 5. Anchor domestic-water heaters to substrate.

B. Install domestic-water heaters level and plumb, according to layout drawings, original design, and referenced standards. Maintain manufacturer's recommended clearances. Arrange units so controls and devices needing service are accessible.

1. Install shutoff valves on domestic-water-supply piping to domestic-water heaters and on domestic-hot-water outlet piping. Comply with requirements for shutoff valves specified in Division 15 Section "General-Duty Valves for Plumbing Piping."

C. Install gas-fired, domestic-water heaters according to NFPA 54.

1. Install gas shutoff valves on gas supply piping to gas-fired, domestic-water heaters without shutoff valves.

2. Install gas pressure regulators on gas supplies to gas-fired, domestic-water heaters without gas pressure regulators if gas pressure regulators are required to reduce gas pressure at burner.

3. Install automatic gas valves on gas supplies to gas-fired, domestic-water heaters if required for operation of safety control.

4. Comply with requirements for gas shutoff valves, gas pressure regulators, and automatic gas valves specified in Division 15 Section "Facility Natural-Gas Piping."

D. Install oil-fired, domestic-water heaters according to NFPA 31.

1. Install shutoff valves on fuel-oil supply piping to oil-fired water-heater burners without shutoff valves. Comply with requirements for shutoff valves specified in Division 15 Section "General-Duty Valves for HVAC Piping."

E. Install commercial domestic-water heaters with seismic-restraint devices. Comply with requirements for seismic-restraint devices specified in Division 15 Section "Vibration and Seismic Controls for Plumbing Piping and Equipment."

F. Install combination temperature-and-pressure relief valves in top portion of storage tanks. Use relief valves with sensing elements that extend into tanks. Extend commercial-water-heater relief-valve outlet, with drain piping same as domestic-water piping in continuous downward pitch, and discharge by positive air gap onto closest floor drain.

G. Install combination temperature-and-pressure relief valves in water piping for domestic-water heaters without storage. Extend commercial-water-heater relief-valve outlet, with drain piping same as domestic-water piping in continuous downward pitch, and discharge by positive air gap onto closest floor drain.

Page 73: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

H. Install water-heater drain piping as indirect waste to spill by positive air gap into open drains or over floor drains. Install hose-end drain valves at low points in water piping for domestic-water heaters that do not have tank drains. Comply with requirements for hose-end drain valves specified in Division 15 Section "Domestic Water Piping Specialties."

I. Install thermometer on outlet piping of domestic-water heaters. Comply with requirements for thermometers specified in Division 15 Section "Meters and Gages for Plumbing Piping."

J. Assemble and install inlet and outlet piping manifold kits for multiple domestic-water heaters. Fabricate, modify, or arrange manifolds for balanced water flow through each domestic-water heater. Include shutoff valve and thermometer in each domestic-water heater inlet and outlet, and throttling valve in each domestic-water heater outlet. Comply with requirements for valves specified in Division 15 Section "General-Duty Valves for Plumbing Piping," and comply with requirements for thermometers specified in Division 15 Section "Meters and Gages for Plumbing Piping."

K. Install piping-type heat traps on inlet and outlet piping of domestic-water heater storage tanks without integral or fitting-type heat traps.

L. Fill domestic-water heaters with water.

M. Charge domestic-water compression tanks with air.

3.2 CONNECTIONS

A. Comply with requirements for domestic-water piping specified in Division 15 Section "Domestic Water Piping."

B. Comply with requirements for fuel-oil piping specified in Division 15 Section "Facility Fuel-Oil Piping."

C. Comply with requirements for gas piping specified in Division 15 Section "Facility Natural-Gas Piping."

D. Drawings indicate general arrangement of piping, fittings, and specialties.

E. Where installing piping adjacent to fuel-fired, domestic-water heaters, allow space for service and maintenance of water heaters. Arrange piping for easy removal of domestic-water heaters.

3.3 IDENTIFICATION

A. Identify system components. Comply with requirements for identification specified in Division 15 Section "Identification for Plumbing Piping and Equipment."

3.4 FIELD QUALITY CONTROL

A. Perform tests and inspections.

1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.

2. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist.

3. Operational Test: After electrical circuitry has been energized, start units to confirm proper operation.

4. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

Page 74: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 5

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

B. Domestic-water heaters will be considered defective if they do not pass tests and inspections. Comply with requirements in Division 1 Section "Quality Requirements" for retesting and reinspecting requirements and Division 1 Section "Execution Requirements" for requirements for correcting the Work.

C. Prepare test and inspection reports.

3.5 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain gas-fired, tankless domestic-water heaters.

END OF SECTION 15486

Page 75: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 6

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15732 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the following components and accessories:

1. Direct-expansion cooling. 2. Gas heat exchanger. 3. Economizer section. 4. Roof curbs.

1.2 SUBMITTALS

A. Product Data: Include manufacturer's technical data for each RTU, including rated capacities, dimensions, required clearances, characteristics, furnished specialties, and accessories.

B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

1. Wiring Diagrams: Power, signal, and control wiring.

C. Field quality-control test reports.

D. Operation and maintenance data.

E. Warranty.

1.3 QUALITY ASSURANCE

A. ARI Compliance:

1. Comply with ARI 210/240 and ARI 340/360 for testing and rating energy efficiencies for RTUs. 2. Comply with ARI 270 for testing and rating sound performance for RTUs.

B. ASHRAE Compliance:

1. Comply with ASHRAE 15 for refrigerant system safety. 2. Comply with ASHRAE 33 for methods of testing cooling and heating coils. 3. Comply with applicable requirements in ASHRAE 62.1-2004, Section 5 - "Systems and Equipment"

and Section 7 - "Construction and Startup."

C. ASHRAE/IESNA 90.1-2004 Compliance: Applicable requirements in ASHRAE/IESNA 90.1-2004, Section 6 - "Heating, Ventilating, and Air-Conditioning."

D. NFPA Compliance: Comply with NFPA 90A and NFPA 90B.

E. UL Compliance: Comply with UL 1995.

F. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

Page 76: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 6

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1.4 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to replace components of RTUs that fail in materials or workmanship within specified warranty period per USD 259 standards.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

B. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. AAON, Inc. 2. Addison Products Company. 3. Carrier Corporation. 4. Lennox Industries Inc. 5. McQuay International. 6. Trane; American Standard Companies, Inc. 7. YORK International Corporation.

2.2 CASING

A. General Fabrication Requirements for Casings: Formed and reinforced double-wall insulated panels, fabricated to allow removal for access to internal parts and components, with joints between sections sealed.

B. Exterior Casing Material: Galvanized steel with factory-painted finish, with pitched roof panels and knockouts with grommet seals for electrical and piping connections and lifting lugs.

1. Exterior Casing Thickness: 0.079 inch thick.

C. Inner Casing Fabrication Requirements:

1. Inside Casing: Galvanized steel, 0.034 inch thick, perforated 40 percent free area.

D. Casing Insulation and Adhesive: Comply with NFPA 90A or NFPA 90B.

1. Materials: ASTM C 1071, Type I. 2. Thickness: 1 inch. 3. Liner materials shall have air-stream surface coated with an erosion- and temperature-resistant

coating or faced with a plain or coated fibrous mat or fabric. 4. Liner Adhesive: Comply with ASTM C 916, Type I.

E. Condensate Drain Pans: Formed sections of galvanized-steel sheet, a minimum of 2 inches deep, and complying with ASHRAE 62.1-2004.

1. Double-Wall Construction: Fill space between walls with foam insulation and seal moisture tight. 2. Drain Connections: Threaded nipple both sides of drain pan. 3. Pan-Top Surface Coating: Corrosion-resistant compound.

F. Airstream Surfaces: Surfaces in contact with the airstream shall comply with requirements in ASHRAE 62.1-2004.

Page 77: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 6

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2.3 FANS

A. Direct-Driven Supply-Air Fans: Double width, forward curved, centrifugal; with permanently lubricated, motor resiliently mounted in the fan inlet. Aluminum or painted-steel wheels, and galvanized- or painted-steel fan scrolls.

B. Belt-Driven Supply-Air Fans: Double width, forward curved, centrifugal; with permanently lubricated, single-speed motor installed on an adjustable fan base resiliently mounted in the casing. Aluminum or painted-steel wheels, and galvanized- or painted-steel fan scrolls.

C. Condenser-Coil Fan: Propeller, mounted on shaft of permanently lubricated motor.

D. Seismic Fabrication Requirements: Fabricate fan section, internal mounting frame and attachment to fans, fan housings, motors, casings, accessories, and other fan section components with reinforcement strong enough to withstand seismic forces defined in Division 15 Section "Vibration and Seismic Controls for HVAC Piping and Equipment" when fan-mounted frame and RTU-mounted frame are anchored to building structure.

E. Fan Motor: Comply with requirements in Division 15 Section "Motors."

2.4 COILS

A. Supply-Air Refrigerant Coil:

1. Copper-plate fin and seamless internally grooved copper tube in steel casing with equalizing-type vertical distributor.

2. Polymer strip shall prevent all copper coil from contacting steel coil frame or condensate pan. 3. Coil Split: Interlaced. 4. Condensate Drain Pan: Galvanized steel with corrosion-resistant coating formed with pitch and

drain connections complying with ASHRAE 62.1-2004.

2.5 REFRIGERANT CIRCUIT COMPONENTS

A. Compressor: Scroll, mounted on vibration isolators; with internal overcurrent and high-temperature protection, internal pressure relief, and crankcase heater.

B. Refrigeration Specialties:

1. Refrigerant: R-410A. 2. Expansion valve with replaceable thermostatic element. 3. Refrigerant filter/dryer. 4. Manual-reset high-pressure safety switch. 5. Automatic-reset low-pressure safety switch. 6. Minimum off-time relay. 7. Automatic-reset compressor motor thermal overload. 8. Brass service valves installed in compressor suction and liquid lines.

2.6 AIR FILTRATION

A. Minimum arrestance according to ASHRAE 52.1, and a minimum efficiency reporting value (MERV) according to ASHRAE 52.2.

1. Pleated: Minimum 90 percent arrestance, and MERV 7.

Page 78: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 6

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2.7 GAS HEAT EXCHANGER

A. Description: Factory assembled, piped, and wired; complying with ANSI Z21.47 and NFPA 54.

1. CSA Approval: Designed and certified by and bearing label of CSA.

B. Burners: Stainless steel.

1. Fuel: Natural gas. 2. Ignition: Electronically controlled electric spark or hot-surface igniter with flame sensor.

C. Heat-Exchanger and Drain Pan: Stainless steel.

D. Venting: Gravity vented.

E. Safety Controls: 1. Gas Train: Single-body, regulated, redundant, 24-V ac gas valve assembly containing pilot

solenoid valve, pilot filter, pressure regulator, pilot shutoff, and manual shutoff.

2.8 DAMPERS

A. Outdoor- and Return-Air Mixing (Economizer) Dampers: Opposed-blade galvanized-steel dampers mechanically fastened to cadmium plated for galvanized-steel operating rod in reinforced cabinet. Connect operating rods with common linkage and interconnect linkages so dampers operate simultaneously.

1. Damper Motor: Modulating with adjustable minimum position. 2. Relief-Air Damper: Gravity actuated or motorized, as required by ASHRAE/IESNA 90.1-2004, with

bird screen and hood.

2.9 ELECTRICAL POWER CONNECTION

A. Provide for single connection of power to unit with unit-mounted disconnect switch accessible from outside unit and control-circuit transformer with built-in overcurrent protection.

2.10 CONTROLS

A. Control equipment and sequence of operation are specified in Division 15 Section "HVAC Instrumentation and Controls."

2.11 ACCESSORIES

A. Coil guards of painted, galvanized-steel wire.

B. Hail guards of galvanized steel, painted to match casing.

2.12 ROOF CURBS (FACTORY)

A. Materials: Galvanized steel with corrosion-protection coating, watertight gaskets, and factory-installed wood nailer; complying with NRCA standards.

1. Curb Insulation and Adhesive: Comply with NFPA 90A or NFPA 90B.

Page 79: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 6

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

a. Materials: ASTM C 1071, Type I or II. b. Thickness: 2 inches.

2. Application: Factory applied with adhesive and mechanical fasteners to the internal surface of curb.

a. Liner Adhesive: Comply with ASTM C 916, Type I. b. Mechanical Fasteners: Galvanized steel, suitable for adhesive attachment, mechanical

attachment, or welding attachment to duct without damaging liner when applied as recommended by manufacturer and without causing leakage in cabinet.

c. Liner materials applied in this location shall have air-stream surface coated with a temperature-resistant coating or faced with a plain or coated fibrous mat or fabric depending on service air velocity.

d. Liner Adhesive: Comply with ASTM C 916, Type I.

B. Curb Height: 14 inches.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Roof Curb: Install on roof structure, level and secure, according to NRCA's "Low-Slope Membrane Roofing Construction Details Manual," Illustration "Raised Curb Detail for Rooftop Air Handling Units and Ducts" ARI Guideline B. Install RTUs on curbs and coordinate roof penetrations and flashing with roof construction specified in Division 7 Section "Roof Accessories." Secure RTUs to upper curb rail, and secure curb base to roof framing or concrete base with anchor bolts.

B. Unit Support: Install unit level on structural curbs or pilings. Coordinate penetrations and flashing with wall construction. Secure RTUs to structural support with anchor bolts.

C. Install condensate drain, minimum connection size, with trap and indirect connection to nearest roof drain or area drain.

D. Install piping adjacent to RTUs to allow service and maintenance.

1. Gas Piping: Comply with applicable requirements in Division 15 Section "Fuel Gas Piping." Connect gas piping to burner, full size of gas train inlet, and connect with union and shutoff valve with sufficient clearance for burner removal and service.

E. Duct installation requirements are specified in other Division 15 Sections. Drawings indicate the general arrangement of ducts. The following are specific connection requirements:

1. Install ducts to termination at top of roof curb. 2. Remove roof decking only as required for passage of ducts. Do not cut out decking under entire

roof curb. 3. Connect supply ducts to RTUs with flexible duct connectors specified in Division 15 Section "Duct

Accessories." 4. Install return-air duct continuously through roof structure.

3.2 FIELD QUALITY CONTROL

A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections. Report results in writing.

B. Perform tests and inspections and prepare test reports.

Page 80: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 6 of 6

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing. Report results in writing.

C. Tests and Inspections:

1. After installing RTUs and after electrical circuitry has been energized, test units for compliance with requirements.

2. Inspect for and remove shipping bolts, blocks, and tie-down straps. 3. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor

rotation and unit operation. 4. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and

equipment.

D. Remove and replace malfunctioning units and retest as specified above.

3.3 CLEANING AND ADJUSTING

A. After completing system installation and testing, adjusting, and balancing RTU and air-distribution systems, clean filter housings and install new filters.

END OF SECTION 15732

Page 81: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15815 - METAL DUCTS

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Rectangular ducts and fittings. 2. Round ducts and fittings. 3. Sheet metal materials. 4. Sealants and gaskets. 5. Hangers and supports.

B. Related Sections: 1. Division 15 Section "Duct Accessories" for dampers, sound-control devices, duct-mounting access

doors and panels, turning vanes, and flexible ducts. 2. Division 15 Section "Testing, Adjusting, and Balancing" for testing, adjusting, and balancing

requirements for metal ducts.

1.2 PERFORMANCE REQUIREMENTS

A. Delegated Duct Design: Duct construction, including sheet metal thicknesses, seam and joint construction, reinforcements, and hangers and supports, shall comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" and performance requirements and design criteria indicated.

1. Static-Pressure Classes:

a. Supply Ducts (except in Mechanical Rooms): 1-inch wg. b. Supply Ducts (Upstream from Air Terminal Units): 4-inch wg. c. Supply Ducts (Downstream from Air Terminal Units): 2-inch wg. d. Supply Ducts (in Mechanical Equipment Rooms): 6-inch wg. e. Return Ducts (Negative Pressure): 1-inch wg. f. Exhaust Ducts (Upstream from Air Terminal Units): 2-inch wg. g. Exhaust Ducts (Downstream from Air Terminal Units): 10-inch wg. h. Exhaust Ducts (Negative Pressure): 1-inch wg. i. Or as noted on drawings.

2. Leakage Class:

a. Round Supply-Air Duct: 3 cfm/100 sq. ft. at 1-inch wg. b. Rectangular Supply-Air Duct: 6 cfm/100 sq. ft. at 1-inch wg. c. Flexible Supply-Air Duct: 6 cfm/100 sq. ft. at 1-inch wg.

B. Structural Performance: Duct hangers and supports shall withstand the effects of gravity loads and stresses within limits and under conditions described in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible"

Page 82: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

PART 2 - PRODUCTS

2.1 RECTANGULAR DUCTS AND FITTINGS

A. General Fabrication Requirements: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" based on indicated static-pressure class unless otherwise indicated.

B. Transverse Joints: Select joint types and fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 1-4, "Transverse (Girth) Joints," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."

C. Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 1-5, "Longitudinal Seams - Rectangular Ducts," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."

D. Elbows, Transitions, Offsets, Branch Connections, and Other Duct Construction: Select types and fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Chapter 2, "Fittings and Other Construction," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."

2.2 ROUND DUCTS AND FITTINGS

A. General Fabrication Requirements: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Chapter 3, "Round, Oval, and Flexible Duct," based on indicated static-pressure class unless otherwise indicated.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Lindab Inc. b. McGill AirFlow LLC. c. SEMCO Incorporated. d. Sheet Metal Connectors, Inc. e. Spiral Manufacturing Co., Inc.

B. Transverse Joints: Select joint types and fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 3-2, "Transverse Joints - Round Duct," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."

1. Transverse Joints in Ducts Larger Than 60 Inches in Diameter: Flanged.

C. Longitudinal Seams: Select seam types and fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 3-1, "Seams - Round Duct and Fittings," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."

1. Fabricate round ducts larger Than 90 inches in diameter with butt-welded longitudinal seams.

D. Tees and Laterals: Select types and fabricate according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 3-4, "90 Degree Tees and Laterals," and Figure 3-5, "Conical Tees," for static-pressure class, applicable sealing requirements, materials involved, duct-support intervals, and other provisions in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible."

Page 83: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2.3 SHEET METAL MATERIALS

A. General Material Requirements: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for acceptable materials, material thicknesses, and duct construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections.

B. Galvanized Sheet Steel: Comply with ASTM A 653/A 653M.

1. Galvanized Coating Designation: G90. 2. Finishes for Surfaces Exposed to View: Mill phosphatized.

C. Carbon-Steel Sheets: Comply with ASTM A 1008/A 1008M, with oiled, matte finish for exposed ducts.

D. Stainless-Steel Sheets: Comply with ASTM A 480/A 480M, Type 304 or 316, as indicated in the "Duct Schedule" Article; cold rolled, annealed, sheet. Exposed surface finish shall be No. 2B, No. 2D, No. 3, or No. 4 as indicated in the "Duct Schedule" Article.

E. Aluminum Sheets: Comply with ASTM B 209 Alloy 3003, H14 temper; with mill finish for concealed ducts, and standard, one-side bright finish for duct surfaces exposed to view.

F. Reinforcement Shapes and Plates: ASTM A 36/A 36M, steel plates, shapes, and bars; black and galvanized.

1. Where black- and galvanized-steel shapes and plates are used to reinforce aluminum ducts, isolate the different metals with butyl rubber, neoprene, or EPDM gasket materials.

G. Tie Rods: Galvanized steel, 1/4-inch minimum diameter for lengths 36 inches or less; 3/8-inch minimum diameter for lengths longer than 36 inches.

2.4 SEALANT AND GASKETS

A. General Sealant and Gasket Requirements: Surface-burning characteristics for sealants and gaskets shall be a maximum flame-spread index of 25 and a maximum smoke-developed index of 50 when tested according to UL 723; certified by an NRTL.

B. Two-Part Tape Sealing System:

1. Tape: Woven cotton fiber impregnated with mineral gypsum and modified acrylic/silicone activator to react exothermically with tape to form hard, durable, airtight seal.

2. Tape Width: 3 inches. 3. Sealant: Modified styrene acrylic. 4. Water resistant. 5. Mold and mildew resistant. 6. Maximum Static-Pressure Class: 10-inch wg, positive and negative. 7. Service: Indoor and outdoor. 8. Service Temperature: Minus 40 to plus 200 deg F. 9. Substrate: Compatible with galvanized sheet steel (both PVC coated and bare), stainless steel, or

aluminum.

C. Water-Based Joint and Seam Sealant:

1. Application Method: Brush on. 2. Solids Content: Minimum 65 percent. 3. Shore A Hardness: Minimum 20. 4. Water resistant. 5. Mold and mildew resistant. 6. VOC: Maximum 75 g/L (less water). 7. Maximum Static-Pressure Class: 10-inch wg, positive and negative.

Page 84: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

8. Service: Indoor or outdoor. 9. Substrate: Compatible with galvanized sheet steel (both PVC coated and bare), stainless steel, or

aluminum sheets.

D. Flanged Joint Sealant: Comply with ASTM C 920.

1. General: Single-component, acid-curing, silicone, elastomeric. 2. Type: S. 3. Grade: NS. 4. Class: 25. 5. Use: O.

E. Flange Gaskets: Butyl rubber, neoprene, or EPDM polymer with polyisobutylene plasticizer.

F. Round Duct Joint O-Ring Seals:

1. Seal shall provide maximum leakage class of 3 cfm/100 sq. ft. at 1-inch wg and shall be rated for 10-inch wg static-pressure class, positive or negative.

2. EPDM O-ring to seal in concave bead in coupling or fitting spigot. 3. Double-lipped, EPDM O-ring seal, mechanically fastened to factory-fabricated couplings and fitting

spigots.

2.5 HANGERS AND SUPPORTS

A. Hanger Rods for Noncorrosive Environments: Cadmium-plated steel rods and nuts.

B. Hanger Rods for Corrosive Environments: Electrogalvanized, all-thread rods or galvanized rods with threads painted with zinc-chromate primer after installation.

C. Strap and Rod Sizes: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Table 4-1, "Rectangular Duct Hangers Minimum Size," and Table 4-2, "Minimum Hanger Sizes for Round Duct."

D. Steel Cables for Galvanized-Steel Ducts: Galvanized steel complying with ASTM A 603.

E. Steel Cables for Stainless-Steel Ducts: Stainless steel complying with ASTM A 492.

F. Steel Cable End Connections: Cadmium-plated steel assemblies with brackets, swivel, and bolts designed for duct hanger service; with an automatic-locking and clamping device.

G. Duct Attachments: Sheet metal screws, blind rivets, or self-tapping metal screws; compatible with duct materials.

H. Trapeze and Riser Supports:

1. Supports for Galvanized-Steel Ducts: Galvanized-steel shapes and plates. 2. Supports for Stainless-Steel Ducts: Stainless-steel shapes and plates. 3. Supports for Aluminum Ducts: Aluminum or galvanized steel coated with zinc chromate.

PART 3 - EXECUTION

3.1 DUCT INSTALLATION

A. Drawing plans, schematics, and diagrams indicate general location and arrangement of duct system. Indicated duct locations, configurations, and arrangements were used to size ducts and calculate friction

Page 85: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

loss for air-handling equipment sizing and for other design considerations. Install duct systems as indicated unless deviations to layout are approved on Shop Drawings and Coordination Drawings.

B. Install ducts according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" unless otherwise indicated.

C. Install round ducts in maximum practical lengths.

D. Install ducts with fewest possible joints.

E. Install factory- or shop-fabricated fittings for changes in direction, size, and shape and for branch connections.

F. Unless otherwise indicated, install ducts vertically and horizontally, and parallel and perpendicular to building lines.

G. Install ducts close to walls, overhead construction, columns, and other structural and permanent enclosure elements of building.

H. Install ducts with a clearance of 1 inch, plus allowance for insulation thickness.

I. Route ducts to avoid passing through transformer vaults and electrical equipment rooms and enclosures.

J. Where ducts pass through non-fire-rated interior partitions and exterior walls and are exposed to view, cover the opening between the partition and duct or duct insulation with sheet metal flanges of same metal thickness as the duct. Overlap openings on four sides by at least 1-1/2 inches.

K. Where ducts pass through fire-rated interior partitions and exterior walls, install fire dampers. Comply with requirements in Division 15 Section "Duct Accessories" for fire and smoke dampers.

L. Protect duct interiors from moisture, construction debris and dust, and other foreign materials. Comply with SMACNA's "Duct Cleanliness for New Construction Guidelines."

3.2 SEAM AND JOINT SEALING

A. Seal duct seams and joints for duct static-pressure and leakage classes specified in "Performance Requirements" Article, according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Table 1-2, "Standard Duct Sealing Requirements," unless otherwise indicated.

B. Seal Classes: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Table 1-2, "Standard Duct Sealing Requirements."

3.3 HANGER AND SUPPORT INSTALLATION

A. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Chapter 4, "Hangers and Supports."

B. Hanger Spacing: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Table 4-1, "Rectangular Duct Hangers Minimum Size," and Table 4-2, "Minimum Hanger Sizes for Round Duct," for maximum hanger spacing; install hangers and supports within 24 inches of each elbow and within 48 inches of each branch intersection.

C. Hangers Exposed to View: Threaded rod and angle or channel supports.

D. Support vertical ducts with steel angles or channel secured to the sides of the duct with welds, bolts, sheet metal screws, or blind rivets; support at each floor and at a maximum intervals of 16 feet.

Page 86: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 6 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

E. Install upper attachments to structures. Select and size upper attachments with pull-out, tension, and shear capacities appropriate for supported loads and building materials where used.

3.4 CONNECTIONS

A. Make connections to equipment with flexible connectors complying with Division 15 Section "Duct Accessories."

B. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for branch, outlet and inlet, and terminal unit connections.

3.5 DUCT SCHEDULE

A. Fabricate ducts with galvanized sheet steel unless noted otherwise.

B. Intermediate Reinforcement:

1. Galvanized-Steel Ducts: Galvanized steel. 2. Stainless-Steel Ducts: Galvanized steel. 3. Aluminum Ducts: Aluminum or galvanized sheet steel coated with zinc chromate.

C. Elbow Configuration:

1. Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 2-2, "Rectangular Elbows."

a. Velocity 1000 fpm or Lower:

1) Radius Type RE 1 with minimum 0.5 radius-to-diameter ratio. 2) Mitered Type RE 4 without vanes.

b. Velocity 1000 to 1500 fpm:

1) Radius Type RE 1 with minimum 1.0 radius-to-diameter ratio. 2) Radius Type RE 3 with minimum 0.5 radius-to-diameter ratio and two vanes. 3) Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct Construction

Standards - Metal and Flexible," Figure 2-3, "Vanes and Vane Runners," and Figure 2-4, "Vane Support in Elbows."

c. Velocity 1500 fpm or Higher:

1) Radius Type RE 1 with minimum 1.5 radius-to-diameter ratio. 2) Radius Type RE 3 with minimum 1.0 radius-to-diameter ratio and two vanes. 3) Mitered Type RE 2 with vanes complying with SMACNA's "HVAC Duct Construction

Standards - Metal and Flexible," Figure 2-3, "Vanes and Vane Runners," and Figure 2-4, "Vane Support in Elbows."

2. Round Duct: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 3-3, "Round Duct Elbows."

a. Minimum Radius-to-Diameter Ratio and Elbow Segments: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Table 3-1, "Mitered Elbows." Elbows with less than 90-degree change of direction have proportionately fewer segments.

1) Velocity 1000 fpm or Lower: 0.5 radius-to-diameter ratio and three segments for 90-degree elbow.

Page 87: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 7 of 7

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2) Velocity 1000 to 1500 fpm: 1.0 radius-to-diameter ratio and four segments for 90-degree elbow.

3) Velocity 1500 fpm or Higher: 1.5 radius-to-diameter ratio and five segments for 90-degree elbow.

b. Round Elbows, 12 Inches and Smaller in Diameter: Stamped or pleated. c. Round Elbows, 14 Inches and Larger in Diameter: Welded.

D. Branch Configuration:

1. Rectangular Duct: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 2-6, "Branch Connections."

a. Rectangular Main to Rectangular Branch: 45-degree entry. b. Rectangular Main to Round Branch: Spin in.

2. Round: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible," Figure 3-4, "90 Degree Tees and Laterals," and Figure 3-5, "Conical Tees." Saddle taps are permitted in existing duct.

a. Velocity 1000 fpm or Lower: 90-degree tap. b. Velocity 1000 to 1500 fpm: Conical tap. c. Velocity 1500 fpm or Higher: 45-degree lateral.

END OF SECTION 15815

Page 88: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15820 - DUCT ACCESSORIES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Backdraft and pressure relief dampers. 2. Manual volume dampers. 3. Fire dampers, smoke dampers & combination fire – smoke dampers 4. Turning vanes. 5. Flexible connectors. 6. Flexible ducts. 7. Duct accessory hardware.

1.2 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Operation and maintenance data.

1.3 QUALITY ASSURANCE

A. Comply with NFPA 90A, "Installation of Air Conditioning and Ventilating Systems," and with NFPA 90B, "Installation of Warm Air Heating and Air Conditioning Systems."

B. Comply with AMCA 500-D testing for damper rating.

PART 2 - PRODUCTS

2.1 MATERIALS

A. Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for acceptable materials, material thicknesses, and duct construction methods unless otherwise indicated. Sheet metal materials shall be free of pitting, seam marks, roller marks, stains, discolorations, and other imperfections.

B. Galvanized Sheet Steel: Comply with ASTM A 653/A 653M.

1. Galvanized Coating Designation: G90. 2. Exposed-Surface Finish: Mill phosphatized.

C. Stainless-Steel Sheets: Comply with ASTM A 480/A 480M, Type 304, and having a No. 2 finish for concealed ducts and No. 2 finish for exposed ducts.

D. Aluminum Sheets: Comply with ASTM B 209, Alloy 3003, Temper H14; with mill finish for concealed ducts and standard, 1-side bright finish for exposed ducts.

E. Extruded Aluminum: Comply with ASTM B 221, Alloy 6063, Temper T6.

Page 89: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

F. Reinforcement Shapes and Plates: Galvanized-steel reinforcement where installed on galvanized sheet metal ducts; compatible materials for aluminum and stainless-steel ducts.

G. Tie Rods: Galvanized steel, 1/4-inch minimum diameter for lengths 36 inches or less; 3/8-inch minimum diameter for lengths longer than 36 inches.

2.2 BACKDRAFT AND PRESSURE RELIEF DAMPERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Air Balance Inc.; a division of Mestek, Inc. 2. American Warming and Ventilating; a division of Mestek, Inc. 3. Cesco Products; a division of Mestek, Inc. 4. Duro Dyne Inc. 5. Greenheck Fan Corporation. 6. Lloyd Industries, Inc. 7. Nailor Industries Inc. 8. NCA Manufacturing, Inc. 9. Pottorff; a division of PCI Industries, Inc. 10. Ruskin Company. 11. SEMCO Incorporated. 12. Vent Products Company, Inc.

B. Description: Gravity balanced.

C. Maximum Air Velocity: 3000 fpm.

D. Maximum System Pressure: 3-inch wg.

E. Frame: 0.052-inch- thick, galvanized sheet steel, with welded corners and mounting flange.

F. Blades: Multiple single-piece blades, center-pivoted, maximum 6-inch width, 0.025-inch- thick, roll-formed aluminum with sealed edges.

G. Blade Action: Parallel.

H. Blade Seals: Extruded vinyl, mechanically locked.

I. Blade Axles:

1. Material: Nonferrous metal. 2. Diameter: 0.20 inch.

J. Tie Bars and Brackets: Aluminum.

K. Return Spring: Adjustable tension.

L. Bearings: Steel ball.

M. Accessories:

1. Adjustment device to permit setting for varying differential static pressure. 2. Counterweights and spring-assist kits for vertical airflow installations. 3. 90-degree stops.

N. Sleeve: Minimum 20-gage thickness.

Page 90: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2.3 MANUAL VOLUME DAMPERS

A. Standard, Steel, Manual Volume Dampers:

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Air Balance Inc.; a division of Mestek, Inc. b. American Warming and Ventilating; a division of Mestek, Inc. c. Flexmaster U.S.A., Inc. d. McGill AirFlow LLC. e. METALAIRE, Inc. f. Nailor Industries Inc. g. Pottorff; a division of PCI Industries, Inc. h. Ruskin Company. i. Vent Products Company, Inc.

2. Standard leakage rating, with linkage outside airstream. 3. Suitable for horizontal or vertical applications. 4. Frames:

a. Hat-shaped, galvanized-steel channels, 0.064-inch minimum thickness. b. Mitered and welded corners. c. Flanges for attaching to walls and flangeless frames for installing in ducts.

5. Blades:

a. Multiple or single blade. b. Parallel- or opposed-blade design. c. Stiffen damper blades for stability. d. Galvanized-steel, 0.064 inch thick.

6. Blade Axles: Galvanized steel. 7. Bearings:

a. Oil-impregnated bronze. b. Dampers in ducts with pressure classes of 3-inch wg or less shall have axles full length of

damper blades and bearings at both ends of operating shaft.

8. Tie Bars and Brackets: Galvanized steel.

B. Jackshaft:

1. Size: 1-inch diameter. 2. Material: Galvanized-steel pipe rotating within pipe-bearing assembly mounted on supports at

each mullion and at each end of multiple-damper assemblies. 3. Length and Number of Mountings: As required to connect linkage of each damper in multiple-

damper assembly.

C. Damper Hardware:

1. Zinc-plated, die-cast core with dial and handle made of 3/32-inch- thick zinc-plated steel, and a 3/4-inch hexagon locking nut.

2. Include center hole to suit damper operating-rod size. 3. Include elevated platform for insulated duct mounting.

2.4 FIRE DAMPERS, SMOKE DAMPERS & COMBINATION FIRE – SMOKE DAMPERS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

Page 91: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1. Air Balance Inc.; a division of Mestek, Inc. 2. Cesco Products; a division of Mestek, Inc. 3. Greenheck Fan Corporation. 4. McGill AirFlow LLC. 5. METALAIRE, Inc. 6. Nailor Industries Inc. 7. NCA Manufacturing, Inc. 8. Pottorff; a division of PCI Industries, Inc. 9. Ruskin Company.

B. Type: Static and dynamic; rated and labeled according to UL 555 by an NRTL.

C. Closing rating in ducts up to 4-inch wg static pressure class and minimum 4000-fpm velocity.

D. Fire Rating: 1-1/2 hours (min.)—Refer to Architectural Drawings

E. Frame: Curtain type with blades outside airstream; fabricated with roll-formed, 0.034-inch- thick galvanized steel; with mitered and interlocking corners.

F. Mounting Sleeve: Factory- or field-installed, galvanized sheet steel.

1. Minimum Thickness: 0.052 or 0.138 inch thick, as indicated, and of length to suit application. 2. Exception: Omit sleeve where damper-frame width permits direct attachment of perimeter

mounting angles on each side of wall or floor; thickness of damper frame must comply with sleeve requirements.

G. Mounting Orientation: Vertical or horizontal as indicated.

H. Blades: Roll-formed, interlocking, 0.034-inch- thick, galvanized sheet steel. In place of interlocking blades, use full-length, 0.034-inch- thick, galvanized-steel blade connectors.

I. Horizontal Dampers: Include blade lock and stainless-steel closure spring.

J. Heat-Responsive Device: Replaceable, 212 deg F rated, fusible links.

K. Heat-Responsive Device: Electric resettable link and switch package, factory installed, 212 deg F rated.

2.5 FLANGE CONNECTORS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Ductmate Industries, Inc. 2. Nexus PDQ; Division of Shilco Holdings Inc. 3. Ward Industries, Inc.; a division of Hart & Cooley, Inc.

B. Description: roll-formed, factory-fabricated, slide-on transverse flange connectors, gaskets, and components.

C. Material: Galvanized steel.

D. Gage and Shape: Match connecting ductwork.

2.6 TURNING VANES

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Ductmate Industries, Inc.

Page 92: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2. Duro Dyne Inc. 3. METALAIRE, Inc. 4. SEMCO Incorporated. 5. Ward Industries, Inc.; a division of Hart & Cooley, Inc.

B. Turning Vanes for Metal Ducts: Curved blades of galvanized sheet steel; support with bars perpendicular to blades set; set into vane runners suitable for duct mounting.

1. Acoustic Turning Vanes: Fabricate airfoil-shaped aluminum extrusions with perforated faces and fibrous-glass fill.

C. Manufactured Turning Vanes for Nonmetal Ducts: Fabricate curved blades of resin-bonded fiberglass with acrylic polymer coating; support with bars perpendicular to blades set; set into vane runners suitable for duct mounting.

D. General Requirements: Comply with SMACNA's "HVAC Duct Construction Standards - Metal and Flexible"; Figures 2-3, "Vanes and Vane Runners," and 2-4, "Vane Support in Elbows."

E. Vane Construction: Single wall.

F. Vane Construction: Single wall for ducts up to 48 inches wide and double wall for larger dimensions.

2.7 DUCT-MOUNTED ACCESS DOORS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. American Warming and Ventilating; a division of Mestek, Inc. 2. Cesco Products; a division of Mestek, Inc. 3. Ductmate Industries, Inc. 4. Flexmaster U.S.A., Inc. 5. Greenheck Fan Corporation. 6. McGill AirFlow LLC. 7. Nailor Industries Inc. 8. Pottorff; a division of PCI Industries, Inc.

B. Duct-Mounted Access Doors: Fabricate access panels according to SMACNA's "HVAC Duct Construction Standards - Metal and Flexible"; Figures 2-10, "Duct Access Doors and Panels," and 2-11, "Access Panels - Round Duct."

1. Door:

a. Double wall, rectangular. b. Galvanized sheet metal with insulation fill and thickness as indicated for duct pressure

class. c. Vision panel. d. Hinges and Latches: 1-by-1-inch butt or piano hinge and cam latches. e. Fabricate doors airtight and suitable for duct pressure class.

2. Frame: Galvanized sheet steel, with bend-over tabs and foam gaskets. 3. Number of Hinges and Locks:

a. Access Doors Less Than 12 Inches Square: No hinges and two sash locks. b. Access Doors up to 18 Inches Square: Two hinges and two sash locks. c. Access Doors up to 24 by 48 Inches: Three hinges and two compression latches. d. Access Doors Larger Than 24 by 48 Inches: Four hinges and two compression latches with

outside and inside handles.

Page 93: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 6 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2.8 FLEXIBLE CONNECTORS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Ductmate Industries, Inc. 2. Duro Dyne Inc. 3. Ventfabrics, Inc. 4. Ward Industries, Inc.; a division of Hart & Cooley, Inc.

B. Materials: Flame-retardant or noncombustible fabrics.

C. Coatings and Adhesives: Comply with UL 181, Class 1.

D. Metal-Edged Connectors: Factory fabricated with a fabric strip 5-3/4 inches wide attached to 2 strips of 2-3/4-inch- wide, 0.028-inch- thick, galvanized sheet steel or 0.032-inch- thick aluminum sheets. Provide metal compatible with connected ducts.

E. Indoor System, Flexible Connector Fabric: Glass fabric double coated with neoprene.

1. Minimum Weight: 26 oz./sq. yd.. 2. Tensile Strength: 480 lbf/inch in the warp and 360 lbf/inch in the filling. 3. Service Temperature: Minus 40 to plus 200 deg F.

F. Outdoor System, Flexible Connector Fabric: Glass fabric double coated with weatherproof, synthetic rubber resistant to UV rays and ozone.

1. Minimum Weight: 24 oz./sq. yd.. 2. Tensile Strength: 530 lbf/inch in the warp and 440 lbf/inch in the filling. 3. Service Temperature: Minus 50 to plus 250 deg F.

G. Thrust Limits: Combination coil spring and elastomeric insert with spring and insert in compression, and with a load stop. Include rod and angle-iron brackets for attaching to fan discharge and duct.

1. Frame: Steel, fabricated for connection to threaded rods and to allow for a maximum of 30 degrees of angular rod misalignment without binding or reducing isolation efficiency.

2. Outdoor Spring Diameter: Not less than 80 percent of the compressed height of the spring at rated load.

3. Minimum Additional Travel: 50 percent of the required deflection at rated load. 4. Lateral Stiffness: More than 80 percent of rated vertical stiffness. 5. Overload Capacity: Support 200 percent of rated load, fully compressed, without deformation or

failure. 6. Elastomeric Element: Molded, oil-resistant rubber or neoprene. 7. Coil Spring: Factory set and field adjustable for a maximum of 1/4-inch movement at start and

stop.

2.9 FLEXIBLE DUCTS

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1. Flexmaster U.S.A., Inc. 2. McGill AirFlow LLC. 3. Ward Industries, Inc.; a division of Hart & Cooley, Inc.

B. Insulated, Flexible Duct: UL 181, Class 1, black polymer film supported by helically wound, spring-steel wire; fibrous-glass insulation; polyethylene vapor-barrier film.

1. Pressure Rating: 4-inch wg positive and 0.5-inch wg negative. 2. Maximum Air Velocity: 4000 fpm.

Page 94: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 7 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

3. Temperature Range: Minus 20 to plus 175 deg F.

C. Flexible Duct Connectors:

1. Clamps: Stainless-steel band with cadmium-plated hex screw to tighten band with a worm-gear action in sizes 3 through 18 inches, to suit duct size.

2.10 DUCT ACCESSORY HARDWARE

A. Instrument Test Holes: Cast iron or cast aluminum to suit duct material, including screw cap and gasket. Size to allow insertion of pitot tube and other testing instruments and of length to suit duct-insulation thickness.

B. Adhesives: High strength, quick setting, neoprene based, waterproof, and resistant to gasoline and grease.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install duct accessories according to applicable details in SMACNA's "HVAC Duct Construction Standards - Metal and Flexible" for metal ducts and in NAIMA AH116, "Fibrous Glass Duct Construction Standards," for fibrous-glass ducts.

B. Install duct accessories of materials suited to duct materials; use galvanized-steel accessories in galvanized-steel and fibrous-glass ducts, stainless-steel accessories in stainless-steel ducts, and aluminum accessories in aluminum ducts.

C. Install backdraft dampers at inlet of exhaust fans or exhaust ducts as close as possible to exhaust fan unless otherwise indicated.

D. Install volume dampers at points on supply, return, and exhaust systems where branches extend from larger ducts. Where dampers are installed in ducts having duct liner, install dampers with hat channels of same depth as liner, and terminate liner with nosing at hat channel.

1. Install steel volume dampers in steel ducts. 2. Install aluminum volume dampers in aluminum ducts.

E. Set dampers to fully open position before testing, adjusting, and balancing.

F. Install test holes at fan inlets and outlets and elsewhere as indicated.

G. Install fire and smoke dampers according to UL listing.

H. Install duct access doors on sides of ducts to allow for inspecting, adjusting, and maintaining accessories and equipment at the following locations:

1. On both sides of duct coils. 2. Downstream from manual volume dampers, control dampers, and equipment. 3. Adjacent to and close enough to fire or smoke dampers, to reset or reinstall fusible links. Access

doors for access to fire or smoke dampers having fusible links shall be pressure relief access doors; and shall be outward operation for access doors installed upstream from dampers and inward operation for access doors installed downstream from dampers.

4. At each change in direction and at maximum 50-foot spacing. 5. Upstream of turning vanes. 6. Elsewhere as indicated.

Page 95: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 8 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

I. Install access doors with swing against duct static pressure.

J. Access Door Sizes:

1. One-Hand or Inspection Access: 8 by 5 inches. 2. Two-Hand Access: 12 by 6 inches. 3. Head and Hand Access: 18 by 10 inches. 4. Head and Shoulders Access: 21 by 14 inches. 5. Body Access: 25 by 14 inches. 6. Body plus Ladder Access: 25 by 17 inches.

K. Label access doors according to Division 15 Section "Identification for HVAC Piping and Equipment" to indicate the purpose of access door.

L. Install flexible connectors to connect ducts to equipment.

M. For fans developing static pressures of 5-inch wg and more, cover flexible connectors with loaded vinyl sheet held in place with metal straps.

N. Connect terminal units to supply ducts directly or with maximum 12-inch lengths of flexible duct. Do not use flexible ducts to change directions.

O. Connect diffusers or light troffer boots to low-pressure ducts directly or with maximum 60-inch lengths of flexible duct clamped or strapped in place.

P. Connect flexible ducts to metal ducts with draw bands.

Q. Install duct test holes where required for testing and balancing purposes.

R. Install thrust limits at centerline of thrust, symmetrical on both sides of equipment. Attach thrust limits at centerline of thrust and adjust to a maximum of 1/4-inch movement during start and stop of fans.

3.2 FIELD QUALITY CONTROL

A. Tests and Inspections:

1. Operate dampers to verify full range of movement. 2. Inspect locations of access doors and verify that purpose of access door can be performed. 3. Operate fire and smoke dampers to verify full range of movement and verify that proper heat-

response device is installed. 4. Inspect turning vanes for proper and secure installation.

END OF SECTION 15820

Page 96: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 3

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15838 - POWER VENTILATORS

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes the following:

1. Centrifugal roof ventilators.

2. Ceiling mount ventilators

1.2 SUBMITTALS

A. Product Data: Include rated capacities, furnished specialties, and accessories for each type of product indicated and include the following:

B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection.

C. Field quality-control test reports.

D. Operation and maintenance data.

1.3 QUALITY ASSURANCE

A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.

B. NEMA Compliance: Motors and electrical accessories shall comply with NEMA standards.

C. UL Standard: Power ventilators shall comply with UL 705.

PART 2 - PRODUCTS

2.1 CENTRIFUGAL ROOF VENTILATORS

A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

1. Acme Engineering & Mfg. Corp. 2. Broan Mfg. Co., Inc. 3. Carnes Company HVAC. 4. Greenheck. 5. Loren Cook Company. 6. Penn Ventilation.

B. Description: Direct- or belt-driven centrifugal fans consisting of housing, wheel, fan shaft, bearings, motor and disconnect switch, drive assembly, curb base, and accessories.

Page 97: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 3

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

C. Housing: Removable, spun-aluminum, dome top and outlet baffle: square, one-piece, aluminum base with venturi inlet cone.

1. Hinged Subbase: Galvanized-steel hinged arrangement permitting service and maintenance.

D. Fan Wheels: Aluminum hub and wheel with backward-inclined blades.

E. Belt-Driven Drive Assembly: Resiliently mounted to housing, with the following features:

1. Fan Shaft: Turned, ground, and polished steel; keyed to wheel hub. 2. Shaft Bearings: Permanently lubricated, permanently sealed, self-aligning ball bearings. 3. Pulleys: Cast-iron, adjustable-pitch motor pulley. 4. Fan and motor isolated from exhaust airstream.

F. Accessories:

1. Disconnect Switch: Nonfusible type, with thermal-overload protection mounted inside fan housing, factory wired through an internal aluminum conduit.

2. Bird Screens: Removable, 1/2-inch mesh, aluminum or brass wire. 3. Dampers: Counterbalanced, parallel-blade, backdraft dampers mounted in curb base; factory set

to close when fan stops. 4. Motorized Dampers: Parallel-blade dampers mounted in curb base with electric actuator; wired to

close when fan stops.

G. Roof Curbs: Galvanized steel; mitered and welded corners; 1-1/2-inch- thick, rigid, fiberglass insulation adhered to inside walls; and 1-1/2-inch wood nailer. Size as required to suit roof opening and fan base. 1. Overall Height: 12 inches. 2. Sound Curb: Curb with sound-absorbing insulation matrix. 3. Pitch Mounting: Manufacture curb for roof slope. 4. Metal Liner: Galvanized steel. 5. Mounting Pedestal: Galvanized steel with removable access panel.

H. Housing: Heavy-gage, removable, spun-aluminum, dome top and outlet baffle; venturi inlet cone.

2.2 CEILING-MOUNTING VENTILATORS

A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

B. Description: Centrifugal fans designed for installing in ceiling or wall or for concealed in-line applications.

C. Housing: Steel, lined with acoustical insulation.

D. Fan Wheel: Centrifugal wheels directly mounted on motor shaft. Fan shrouds, motor, and fan wheel shall be removable for service.

E. Grille: Plastic, louvered grille with flange on intake and thumbscrew attachment to fan housing.

F. Electrical Requirements: Junction box for electrical connection on housing and receptacle for motor plug-in.

G. Accessories:

1. Manual Starter Switch: Single-pole rocker switch assembly with cover and pilot light. 2. Time-Delay Switch: Assembly with single-pole rocker switch, timer, and cover plate. 3. Motion Sensor: Motion detector with adjustable shutoff timer. 4. Ceiling Radiation Damper: Fire-rated assembly with ceramic blanket, stainless-steel springs, and

fusible link.

Page 98: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 3

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

5. Filter: Washable aluminum to fit between fan and grille. 6. Isolation: Rubber-in-shear vibration isolators. 7. Manufacturer's standard roof jack or wall cap, and transition fittings.

2.3

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install power ventilators level and plumb.

B. Secure roof-mounting fans to roof curbs with cadmium-plated hardware and per manufacturer’s instructions.

C. Install units with clearances for service and maintenance.

D. Label units according to requirements specified in Division 15 Section "Mechanical Identification."

E. Duct installation and connection requirements are specified in other Division 15 Sections. Drawings indicate general arrangement of ducts and duct accessories. Make final duct connections with flexible connectors. Flexible connectors are specified in Division 15 Section "Duct Accessories."

F. Install ducts adjacent to power ventilators to allow service and maintenance.

G. Ground equipment according to Division 16 Section "Grounding and Bonding."

H. Connect wiring according to Division 16 Section "Conductors and Cables."

3.2 FIELD QUALITY CONTROL

A. Perform the following field tests and inspections and prepare test reports:

1. Verify that shipping, blocking, and bracing are removed. 2. Verify that unit is secure on mountings and supporting devices and that connections to ducts and

electrical components are complete. Verify that proper thermal-overload protection is installed in motors, starters, and disconnect switches.

3. Verify that cleaning and adjusting are complete. 4. Disconnect fan drive from motor, verify proper motor rotation direction, and verify fan wheel free

rotation and smooth bearing operation. Reconnect fan drive system, align and adjust belts, and install belt guards.

5. Adjust belt tension. 6. Adjust damper linkages for proper damper operation. 7. Verify lubrication for bearings and other moving parts. 8. Verify that manual and automatic volume control and fire and smoke dampers in connected

ductwork systems are in fully open position. 9. Disable automatic temperature-control operators, energize motor and adjust fan to indicated rpm,

and measure and record motor voltage and amperage. 10. Shut unit down and reconnect automatic temperature-control operators. 11. Remove and replace malfunctioning units and retest as specified above.

B. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

END OF SECTION 15838

Page 99: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 2

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15855 - DIFFUSERS, REGISTERS, AND GRILLES

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes: 1. Rectangular and square ceiling diffusers. 2. Louver face diffusers. 3. Fixed face registers and grilles.

B. Related Sections: 1. Division 15 Section "Duct Accessories" for fire and smoke dampers and volume-control dampers

not integral to diffusers, registers, and grilles.

1.2 SUBMITTALS

A. Product Data: For each type of product indicated, include the following:

1. Data Sheet: Indicate materials of construction, finish, and mounting details; and performance data including throw and drop, static-pressure drop, and noise ratings.

2. Diffuser, Register, and Grille Schedule: Indicate drawing designation, room location, quantity, model number, size, and accessories furnished.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Reference plans for schedule listing requirements. 1. Products: Subject to compliance with requirements, provide one of the products specified.

2. Available Products: a. Hart & Cooley, Inc., Hart & Cooley Div. b. Nailor Industries of Texas Inc. c. Price Industries. d. Titus. e. Tuttle & Bailey.

2.2 SOURCE QUALITY CONTROL

A. Verification of Performance: Rate diffusers, registers, and grilles according to ASHRAE 70, "Method of Testing for Rating the Performance of Air Outlets and Inlets."

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install diffusers, registers, and grilles level and plumb.

Page 100: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 2

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

B. Ceiling-Mounted Outlets and Inlets: Drawings indicate general arrangement of ducts, fittings, and accessories. Air outlet and inlet locations have been indicated to achieve design requirements for air volume, noise criteria, airflow pattern, throw, and pressure drop. Make final locations where indicated, as much as practical. For units installed in lay-in ceiling panels, locate units in the center of panel. Where architectural features or other items conflict with installation, notify Architect for a determination of final location.

C. Install diffusers, registers, and grilles with airtight connections to ducts and to allow service and maintenance of dampers, air extractors, and fire dampers.

3.2 ADJUSTING

A. After installation, adjust diffusers, registers, and grilles to air patterns indicated, or as directed, before starting air balancing.

END OF SECTION 15855

Page 101: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 2

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15890 - HVAC AIR-DISTRIBUTION SYSTEM CLEANING

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes cleaning HVAC air-distribution equipment, ducts, plenums, and system components.

1.2 QUALITY ASSURANCE

A. UL Compliance: Comply with UL 181 and UL 181A for fibrous-glass ducts.

PART 2 - PRODUCTS (Not Used)

PART 3 - EXECUTION

3.1 PREPARATION

A. Use the existing service openings, as required for proper cleaning, at various points of the HVAC system for physical and mechanical entry and for inspection.

B. Comply with NADCA ACR 2006, "Guidelines for Constructing Service Openings in HVAC Systems" Section.

C. HVAC air-distribution system cleaning shall be performed prior to TAB.

3.2 CLEANING

A. Comply with NADCA ACR 2006.

B. Remove visible surface contaminants and deposits from within the HVAC system.

C. Systems and Components to Be Cleaned:

1. Air devices for supply and return air. 2. Ductwork:

a. Supply-air ducts, including turning vanes and coils, to the air-handling unit.

b. Return-air ducts to the air-handling unit. c. Exhaust-air ducts.

3. Air-Handling Units:

a. Interior surfaces of the unit casing. b. Coil surfaces compartment. c. Condensate drain pans. d. Fans, fan blades, and fan housings.

4. Filters and filter housings.

Page 102: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 2

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

D. Collect debris removed during cleaning. Ensure that debris is not dispersed outside the HVAC system during the cleaning process.

E. Control odors and mist vapors during the cleaning and restoration process.

F. Mark the position of manual volume dampers and air-directional mechanical devices inside the system prior to cleaning. Restore them to their marked position on completion of cleaning.

G. System components shall be cleaned so that all HVAC system components are visibly clean. On completion, all components must be returned to those settings recorded just prior to cleaning operations.

H. Clean all air-distribution devices, registers, grilles, and diffusers.

I. Clean visible surface contamination as follows:

1. Clean air-handling units, airstream surfaces, components, condensate collectors, and drains. 2. Ensure that a suitable operative drainage system is in place prior to beginning wash-down

procedures. 3. Clean evaporator coils, reheat coils, and other airstream components.

END OF SECTION 15890

Page 103: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 1 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

15950 - TESTING, ADJUSTING, AND BALANCING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes TAB to produce design objectives for the following:

1. Air Systems:

a. Constant-volume air systems.

2. Verifying that automatic control devices are functioning properly. 3. Reporting results of activities and procedures specified in this Section.

1.3 SUBMITTALS

A. Certified TAB Reports: Submit seven copies of reports prepared, as specified in this Section, on approved forms certified by TAB firm.

1.4 QUALITY ASSURANCE

A. TAB Firm Qualifications: Engage a TAB firm certified by NEBB.

B. Certification of TAB Reports: Certify TAB field data reports. This certification includes the following:

1. Review field data reports to validate accuracy of data and to prepare certified TAB reports. 2. Certify that TAB team complied with approved TAB plan and the procedures specified and

referenced in this Specification.

C. TAB Report Forms: Use standard forms from NEBB's "Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems."

D. Instrumentation Type, Quantity, and Accuracy: As described in NEBB's "Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems," Section II, "Required Instrumentation for NEBB Certification."

E. Instrumentation Calibration: Calibrate instruments at least every six months or more frequently if required by instrument manufacturer.

1. Keep an updated record of instrument calibration that indicates date of calibration and the name of party performing instrument calibration.

Page 104: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 2 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

1.5 COORDINATION

A. Coordinate the efforts of factory-authorized service representatives for systems and equipment, HVAC controls installers, and other mechanics to operate HVAC systems and equipment to support and assist TAB activities.

B. Notice: Provide seven days' advance notice for each test. Include scheduled test dates and times.

1.6 WARRANTY

A. Special Guarantee: Provide a guarantee on NEBB forms stating that NEBB will assist in completing requirements of the Contract Documents if TAB firm fails to comply with the Contract Documents. Guarantee shall include the following provisions:

1. The certified TAB firm has tested and balanced systems according to the Contract Documents. 2. Systems are balanced to optimum performance capabilities within design and installation limits.

PART 2 - PRODUCTS (Not Applicable)

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine the Contract Documents to become familiar with Project requirements and to discover conditions in systems' designs that may preclude proper TAB of systems and equipment.

1. Contract Documents are defined in the General and Supplementary Conditions of Contract. 2. Verify that balancing devices, such as test ports, gage cocks, thermometer wells, flow-control

devices, balancing valves and fittings, and manual volume dampers, are required by the Contract Documents. Verify that quantities and locations of these balancing devices are accessible and appropriate for effective balancing and for efficient system and equipment operation.

B. Examine system and equipment installations to verify that they are complete and that testing, cleaning, adjusting, and commissioning specified in individual Sections have been performed.

C. Examine HVAC system and equipment installations to verify that indicated balancing devices, such as test ports, gage cocks, thermometer wells, flow-control devices, balancing valves and fittings, and manual volume dampers, are properly installed, and that their locations are accessible and appropriate for effective balancing and for efficient system and equipment operation.

D. Examine systems for functional deficiencies that cannot be corrected by adjusting and balancing.

E. Examine HVAC equipment to ensure that clean filters have been installed, bearings are greased, belts are aligned and tight, and equipment with functioning controls is ready for operation.

F. Examine equipment for installation and for properly operating safety interlocks and controls.

G. Examine automatic temperature system components to verify the following: 1. Thermostats and humidistats are located to avoid adverse effects of sunlight, drafts, and cold walls. 2. Sensors are located to sense only the intended conditions. 3. Controller set points are set at indicated values. 4. Changeover from heating to cooling mode occurs according to indicated values.

H. Report deficiencies discovered before and during performance of TAB procedures. Observe and record system reactions to changes in conditions. Record default set points if different from indicated values.

Page 105: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 3 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

3.2 GENERAL PROCEDURES FOR TESTING AND BALANCING

A. Perform testing and balancing procedures on each system according to the procedures contained in NEBB's "Procedural Standards for Testing, Adjusting, and Balancing of Environmental Systems" and this Section.

B. Cut insulation, ducts, pipes, and equipment cabinets for installation of test probes to the minimum extent necessary to allow adequate performance of procedures. After testing and balancing, close probe holes and patch insulation with new materials identical to those removed. Restore vapor barrier and finish according to insulation Specifications for this Project.

C. Mark equipment and balancing device settings with paint or other suitable, permanent identification material, including damper-control positions, valve position indicators, fan-speed-control levers, and similar controls and devices, to show final settings.

D. Take and report testing and balancing measurements in inch-pound (IP) units.

3.3 GENERAL PROCEDURES FOR BALANCING AIR SYSTEMS

A. Prepare test reports for both fans and outlets. Obtain manufacturer's outlet factors and recommended testing procedures. Crosscheck the summation of required outlet volumes with required fan volumes.

B. Determine the best locations in main and branch ducts for accurate duct airflow measurements.

C. Check airflow patterns from the outside-air louvers and dampers and the return- and exhaust-air dampers, through the supply-fan discharge and mixing dampers.

D. Locate start-stop and disconnect switches, electrical interlocks, and motor starters.

E. Verify that motor starters are equipped with properly sized thermal protection.

F. Check dampers for proper position to achieve desired airflow path.

G. Check for airflow blockages.

H. Check condensate drains for proper connections and functioning.

I. Check for proper sealing of air-handling unit components.

J. Check for proper sealing of air duct system.

3.4 PROCEDURES FOR CONSTANT-VOLUME AIR SYSTEMS

A. Adjust fans to deliver total indicated airflows within the maximum allowable fan speed listed by fan manufacturer.

1. Measure fan static pressures to determine actual static pressure as follows:

a. Measure outlet static pressure as far downstream from the fan as practicable and upstream from restrictions in ducts such as elbows and transitions.

b. Measure static pressure directly at the fan outlet or through the flexible connection. c. Measure inlet static pressure of single-inlet fans in the inlet duct as near the fan as possible,

upstream from flexible connection and downstream from duct restrictions. d. Measure inlet static pressure of double-inlet fans through the wall of the plenum that houses

the fan.

Page 106: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 4 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

2. Measure static pressure across each component that makes up an air-handling unit, rooftop unit, and other air-handling and -treating equipment.

3. Compare design data with installed conditions to determine variations in design static pressures versus actual static pressures. Compare actual system effect factors with calculated system effect factors to identify where variations occur. Recommend corrective action to align design and actual conditions.

4. Do not make fan-speed adjustments that result in motor overload. Consult equipment manufacturers about fan-speed safety factors. Modulate dampers and measure fan-motor amperage to ensure that no overload will occur. Measure amperage in full cooling, full heating, economizer, and any other operating modes to determine the maximum required brake horsepower.

B. Adjust volume dampers for main duct, submain ducts, and major branch ducts to indicated airflows within specified tolerances.

1. Measure static pressure at a point downstream from the balancing damper and adjust volume dampers until the proper static pressure is achieved.

a. Where sufficient space in submain and branch ducts is unavailable for Pitot-tube traverse measurements, measure airflow at terminal outlets and inlets and calculate the total airflow for that zone.

b. Remeasure each submain and branch duct after all have been adjusted. Continue to adjust submain and branch ducts to indicated airflows within specified tolerances.

C. Measure pump flow rate and make final measurements of pump amperage, voltage, rpm, pump heads, and systems' pressures and temperatures including outdoor-air temperature.

D. Measure the differential-pressure control valve settings existing at the conclusions of balancing.

3.5 TOLERANCES

A. Set HVAC system airflow and water flow rates within the following tolerances:

1. Supply, Return, and Exhaust Fans and Equipment with Fans: Plus 5 to plus 10 percent. 2. Air Outlets and Inlets: 0 to minus 10 percent.

3.6 REPORTING

A. Initial Construction-Phase Report: Based on examination of the Contract Documents as specified in "Examination" Article, prepare a report on the adequacy of design for systems' balancing devices. Recommend changes and additions to systems' balancing devices to facilitate proper performance measuring and balancing. Recommend changes and additions to HVAC systems and general construction to allow access for performance measuring and balancing devices.

B. Status Reports: As Work progresses, prepare reports to describe completed procedures, procedures in progress, and scheduled procedures. Include a list of deficiencies and problems found in systems being tested and balanced. Prepare a separate report for each system and each building floor for systems serving multiple floors.

3.7 FINAL REPORT

A. General: Typewritten, or computer printout in letter-quality font, on standard bond paper, in three-ring binder, tabulated and divided into sections by tested and balanced systems.

Page 107: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 5 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

B. Include a certification sheet in front of binder signed and sealed by the certified testing and balancing engineer.

1. Include a list of instruments used for procedures, along with proof of calibration.

C. Final Report Contents: In addition to certified field report data, include the following: 1. Manufacturers' test data. 2. Other information relative to equipment performance, but do not include Shop Drawings and

Product Data.

D. General Report Data: In addition to form titles and entries, include the following data in the final report, as applicable:

1. Title page. 2. Name and address of TAB firm. 3. Project name. 4. Project location. 5. Architect's name and address. 6. Engineer's name and address. 7. Contractor's name and address. 8. Report date. 9. Signature of TAB firm who certifies the report. 10. Table of Contents with the total number of pages defined for each section of the report. Number

each page in the report. 11. Summary of contents including the following:

a. Indicated versus final performance. b. Notable characteristics of systems. c. Description of system operation sequence if it varies from the Contract Documents.

12. Nomenclature sheets for each item of equipment. 13. Test conditions for fans performance forms including the following:

a. Settings for outside-, return-, and exhaust-air dampers. b. Conditions of filters. c. Cooling coil, wet- and dry-bulb conditions. d. Fan drive settings including settings and percentage of maximum pitch diameter. e. Settings for supply-air, static-pressure controller. f. Other system operating conditions that affect performance.

E. Air-Handling Unit Test Reports: For air-handling units with coils, include the following:

1. Unit Data: Include the following:

a. Unit identification. b. Location. c. Make and type. d. Model number and unit size. e. Manufacturer's serial number. f. Unit arrangement and class. g. Discharge arrangement. h. Sheave make, size in inches, and bore. i. Sheave dimensions, center-to-center, and amount of adjustments in inches. j. Number of belts, make, and size. k. Number of filters, type, and size.

2. Motor Data:

a. Make and frame type and size. b. Horsepower and rpm.

Page 108: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 6 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

c. Volts, phase, and hertz. d. Full-load amperage and service factor. e. Sheave make, size in inches, and bore. f. Sheave dimensions, center-to-center, and amount of adjustments in inches.

3. Test Data (Indicated and Actual Values):

a. Total airflow rate in cfm. b. Total system static pressure in inches wg. c. Fan rpm. d. Discharge static pressure in inches wg. e. Filter static-pressure differential in inches wg. f. Cooling coil static-pressure differential in inches wg. g. Heating coil static-pressure differential in inches wg. h. Outside airflow in cfm. i. Return airflow in cfm. j. Outside-air damper position. k. Return-air damper position.

F. Fan Test Reports: For supply, return, and exhaust fans, include the following:

1. Fan Data:

a. System identification. b. Location. c. Make and type. d. Model number and size. e. Manufacturer's serial number. f. Arrangement and class. g. Sheave make, size in inches, and bore. h. Sheave dimensions, center-to-center, and amount of adjustments in inches.

2. Motor Data:

a. Make and frame type and size. b. Horsepower and rpm. c. Volts, phase, and hertz. d. Full-load amperage and service factor. e. Sheave make, size in inches, and bore. f. Sheave dimensions, center-to-center, and amount of adjustments in inches. g. Number of belts, make, and size.

3. Test Data (Indicated and Actual Values):

a. Total airflow rate in cfm. b. Total system static pressure in inches wg. c. Fan rpm. d. Discharge static pressure in inches wg. e. Suction static pressure in inches wg.

G. Round and Rectangular Duct Traverse Reports: Include a diagram with a grid representing the duct cross-section and record the following:

1. Report Data:

a. System and air-handling unit number. b. Location and zone. c. Traverse air temperature in deg F. d. Duct static pressure in inches wg. e. Duct size in inches.

Page 109: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 7 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

f. Duct area in sq. ft.. g. Indicated airflow rate in cfm. h. Indicated velocity in fpm. i. Actual airflow rate in cfm. j. Actual average velocity in fpm. k. Barometric pressure in psig.

H. Instrument Calibration Reports:

1. Report Data:

a. Instrument type and make. b. Serial number. c. Application. d. Dates of use. e. Dates of calibration.

3.8 INSPECTIONS

A. Initial Inspection:

1. After testing and balancing are complete, operate each system and randomly check measurements to verify that the system is operating according to the final test and balance readings documented in the Final Report.

2. Randomly check the following for each system:

a. Measure airflow of at least 10 percent of air outlets. b. Measure room temperature at each thermostat/temperature sensor. Compare the reading

to the set point. c. Verify that balancing devices are marked with final balance position. d. Note deviations to the Contract Documents in the Final Report.

B. Final Inspection:

1. After initial inspection is complete and evidence by random checks verifies that testing and balancing are complete and accurately documented in the final report, request that a final inspection be made by Architect.

2. TAB firm test and balance engineer shall conduct the inspection in the presence of Architect. 3. Architect shall randomly select measurements documented in the final report to be rechecked. The

rechecking shall be limited to either 10 percent of the total measurements recorded, or the extent of measurements that can be accomplished in a normal 8-hour business day.

4. If the rechecks yield measurements that differ from the measurements documented in the final report by more than the tolerances allowed, the measurements shall be noted as "FAILED."

5. If the number of "FAILED" measurements is greater than 10 percent of the total measurements checked during the final inspection, the testing and balancing shall be considered incomplete and shall be rejected.

6. TAB firm shall recheck all measurements and make adjustments. Revise the final report and balancing device settings to include all changes and resubmit the final report.

7. Request a second final inspection. If the second final inspection also fails, Owner shall contract the services of another TAB firm to complete the testing and balancing in accordance with the Contract Documents and deduct the cost of the services from the final payment.

3.9 ADDITIONAL TESTS

A. Upon completing TAB, review the pressure profile map of spaces with Owner. Airflows shall changed per request of Owner allowing for desired room pressure differentials to be achieved.

Page 110: DIVISION 15 - MECHANICAL Page 1 of 7 04-16-15 FINAL APPROVED DRAWINGS/07... · DIVISION 15 - MECHANICAL Page 2 of 7 CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

DIVISION 15 - MECHANICAL Page 8 of 8

CENTRAL PRESBYTERIAN CHURCH OF NEW YORK DIVISION 15 – MECHANICAL

B. Within 90 days of completing TAB, perform additional testing and balancing to verify that balanced conditions are being maintained throughout and to correct unusual conditions.

C. Seasonal Periods: If initial TAB procedures were not performed during near-peak summer and winter conditions, perform additional testing, inspecting, and adjusting during near-peak summer and winter conditions.

END OF SECTION 15950