District Regulator Service Regulator

35
Farm Tap Service Regulator District Regulator OGA 2015 Regulator Fundamentals Seminar

Transcript of District Regulator Service Regulator

Page 1: District Regulator Service Regulator

Farm Tap

Service Regulator

District Regulator

OGA 2015 Regulator Fundamentals Seminar

Page 2: District Regulator Service Regulator

Diagram of Distribution Piping

Large Industrial Customer

Meter & Regulator

Fuel

Line

Service Line Supply Main (100-200 psig)‏ City Gate Station

District Regulator

Station

District Regulator

Station

High Pressure 60-100 psig

M

R

M

R

R

Farm Tap

Dist Reg

Dist Reg

Dist Reg

Dist Reg

Low Pressure 6-10 in WC

M

Medium Pressure

M R

Feeder Mains

Page 3: District Regulator Service Regulator

Types of Regulators

Self operated

Pilot operated

Page 4: District Regulator Service Regulator

Self-Operated Regulator

Internal Control

Open Throat

Internal

Control

Page 5: District Regulator Service Regulator

Three Essential Elements

Source: Emerson – Fisher Controls Handbook

Adjusting Screw

Vent

Spring - Loading

Element

Measuring

Element

Control Line

Restricting Element

Page 6: District Regulator Service Regulator

Spring-Loading Element

Source: Emerson – Fisher Controls Handbook

60 psig 10 psig

Area = 10 in2

Page 7: District Regulator Service Regulator

Spring Force At Equilibrium

Source: Emerson – Fisher Controls Handbook

FSpring = (K)(X)‏

FDiaphragm = (P2)(AD)‏

FSpring = FDiaphragm

FDiaphragm = (10 psig)(10sq ") = 100 lb

FSpring = (100 lb/in)(X) = 100 lb

FSpring

FDiaphragm

X = 1 inch Compression

To keep Diaphragm

from moving

Spring

force Diaphragm

force =

SPRING COMPRESSION RATIO K

K = 100 lbs / inch

Page 8: District Regulator Service Regulator

Regulator Droop – Plug Travel

Source: Emerson – Fisher Controls Handbook

P2 = 9 psig P1 = 60 psig

FS = 90 lb

FD = 90 lb

0.1 inch

0.9 inch spring

compression

Page 9: District Regulator Service Regulator

Ideal Regulator

Set Pressure

Flow

P2

Page 10: District Regulator Service Regulator

Regulator Droop

Typical Performance Curve

Source: Emerson – Fisher Controls Handbook

Ideal

Flow

Wide-Open

Droop (Offset)‏

Setpoint

Lock-up

P2

Page 11: District Regulator Service Regulator

Spring Effect

Lighter Spring (10 psig downstream)‏

SPRING COMPRESSION RATIO K

K = 50 lbs / inch

FS = 50 lbs / inch x 2 inches = 100 lbs

FD = 10 psig x 10 square inches = 100 lbs

Source: Emerson – Fisher Controls Handbook

X = 2 inch compression

FS

FD

FS = (K)(X)‏

FD = (P2)(AD)‏

Page 12: District Regulator Service Regulator

Spring Effect

Lighter Spring (9 psig downstream)‏

SPRING COMPRESSION RATIO K

K = 50 lbs / inch

FS = 50 lbs / inch x 1.8 inches = 90 lbs

FD = 9 psig x 10 square inches = 90 lbs

Source: Emerson – Fisher Controls Handbook

X = 1.8-inch compression

FS

FD

FS = (K)(X)‏

FD = (P2)(AD)‏

Page 13: District Regulator Service Regulator

Spring Effect

Lighter Spring (Value Travel)‏

Source: Emerson – Fisher Controls Handbook

0.2-inches

Area = 10 in2

Page 14: District Regulator Service Regulator

Spring Effect

Spring Effect on Accuracy

Source: Emerson – Fisher Controls Handbook

Lighter Spring

Ideal

Flow

Wide-Open

Droop (Offset)‏

Setpoint

Lock-up

P2

Page 15: District Regulator Service Regulator

Diaphragm Effect

Diaphragm Effect on Droop

Source: Emerson – Fisher Controls Handbook

FD1

FD2

A = 10 in2

A = 11 in2

When P2 Droops to 9

FD = P2 x A

FD1 = 10 x 10 = 100 lb

FD2 = 9 x 11 = 99 lb

Diaphragm Plate

Diaphragm Plate

Page 16: District Regulator Service Regulator

Diaphragms

Adds to droop effect

Can’t‏‏be‏changed

Larger diaphragms

More sensitive to P2

Low pressure (LP) applications

Service regulators

Page 17: District Regulator Service Regulator

Orifice Size

Increasing orifice size

Increases capacity

Bathtub effect at low flow

Source: Emerson – Fisher Controls Handbook

Page 18: District Regulator Service Regulator

Orifice Size

Effect of Oversized Orifice

Unstable at low flow

Increases wear

Source: Emerson – Fisher Controls Handbook

Time

Setpoint

P2

Flow Increased

Page 19: District Regulator Service Regulator

Balanced Valve

441 & 461 High Capacity Regulators

Pout Pin

Page 20: District Regulator Service Regulator

Lock-up and Critical Flow

Source: Emerson – Fisher Controls Handbook

Ideal

Flow

Wide-Open

Critical Flow

Droop (Offset)‏

Setpoint

Lock-up

P2

Page 21: District Regulator Service Regulator

Control Lines

8-10 pipe diameters downstream of any turbulent flow point ( valve, tee, elbow)‏

Avoid outlet riser

Control Line equal to or greater than tap size

Increase control line size for every 20 feet in length

Protect from damage

Rigid

Buried

Page 22: District Regulator Service Regulator

Vena Contracta

Source: Emerson – Fisher Controls Handbook

Page 23: District Regulator Service Regulator

Pitot Tube

Move sensing point closer to orifice

Source: Emerson – Fisher Controls Handbook

Pitot Tube

Sense Pressure Here

P2 = 10 psig P1 = 100 psig

Page 24: District Regulator Service Regulator

Regulator with Pitot Tube

Source: Emerson – Fisher Controls Handbook

Inlet Pressure

Outlet Pressure

Atmospheric Pressure/

Loading Pressure

Pitot Tube

Page 25: District Regulator Service Regulator

Boost

Source: Emerson – Fisher Controls Handbook

Setpoint

Flow

Pre

ssure

P2

PD

P2 = Downstream Pressure

PD = Pressure Under Diaphragm

Page 26: District Regulator Service Regulator

Service Regulator

Lever Acting – Close Position

Page 27: District Regulator Service Regulator

Service Regulator

Lever Acting – Open Position

Page 28: District Regulator Service Regulator
Page 29: District Regulator Service Regulator
Page 30: District Regulator Service Regulator

Self-Operated Regulators

Narrow-range of control

10-20% droop

Inexpensive

Fast response

Simple

Page 31: District Regulator Service Regulator

Typical Farm Type Regulator

Capacity Tables Table 6. Type 627R Capacities for 1 and 2-Inch body sizes (1)

1. Capacity is based on 20 percent droop unless otherwise noted below.

- Blank areas indicate where maximum operating pressure for a give orifice is exceeded.

Fisher‏”1

Type 627R

Page 32: District Regulator Service Regulator

Typical Commercial Type

Regulator Capacity Tables

and 243-12-2 in SCFH of Natural Gas 243-12-1‏Models‏”2

(0.6 Specific Gravity - 14.65 psia - 60ºF)

Last capacity figure in each group indicates maximum allowable inlet pressure

(except for emergency conditions).

Heavy stepped line indicates the recommended maximum capacity and inlet

pressure for each orifice for operation within the optimum performance range.

Page 33: District Regulator Service Regulator

Typical Large Capacity

Regulator Tables

441-57S Capacity Table‏”6‏&‏”4‏,”3‏,”2

Page 34: District Regulator Service Regulator

Typical Large Capacity

Regulator Limitations

Page 35: District Regulator Service Regulator