Distribution System Static VAr Compensators Field Experience

13
Distribution System Static VAr Compensators: Field Experience Ray Kemerer Power Quality Systems, Inc. February 4, 1998

description

Distribution System Static VAr Compensators Field Experience

Transcript of Distribution System Static VAr Compensators Field Experience

  • Distribution System Static VArCompensators: Field Experience

    Ray KemererPower Quality Systems, Inc.

    February 4, 1998

  • IntelliVAr Advanced Static VAr Compensator(ASVC)

    Block Diagram

  • Some Typical ASVCApplications

    Lumber/Paper Mills Arc Welders Arc Furnaces Large Motor Loads Large Power Supplies Pumping Stations

  • Typical ASVC Specifications

    Frequency: 50 Hz or 60 Hz Voltage: 7200 to 7967 volts line to neutral (directly

    connected) 95 kV BIL -40 to +40C 2500 lbs. (1100 kg) Applied kVAr Capacity: 100 lagging to 1000 leading per

    phase Stepless Control Dimensions: 85 (216) x 51 (130) x 47 (119) inches (cm)

  • Requirements for Installation

    Install Platform (not required if pole-mounted). Install load break cutout for connection to ASVC line

    bushing. Replace pole top insulator with current sensor. Connect neutral to ASVC ground pad. Provide 200 VA, 120 volt service and telephone or cellular

    connection (for remote communication only). Installation does not cause customer service interruption.

  • Pole-Mounted InstallationDetroit Edison

  • Pre-Installation Considerations

    Source and transformer impedance data Baseline load data such as harmonic

    content, power factor, and time duration ofdynamic loads

    Modeling and simulation Installation type: pole, platform, or pad-

    mount

  • Actual vs. Modeled PowerSystem

    220.0

    230.0

    240.0

    250.0

    260.0

    270.0

    280.0

    290.0

    1 14 27 53 66 79 92 105

    118

    131

    144

    157

    170

    183

    196

    209

    Cycle Number

    Vol

    tage

    Measured Voltage Theoretical Voltage

  • Predicted ASVC Response

    114.00

    115.00

    116.00

    117.00

    118.00

    119.00

    120.00

    121.00

    122.00

    Cycle Number

    Vol

    tage

    Uncompensated Voltage Compensated Voltage

  • Oconee EMC(Ogelthorpe Power) Installation -

    Dudley, GA 7200 volt line to neutral rating 50 kVAr inductive to 650 kVAr capacitive per

    phase (stepless) Installed at highly automated Gilman Building

    Products plant (lumber mill) Motor load was generating flicker Gilman plant had motor failures and motor drive

    tripping Power factor ranged from .7 lagging to worse than

    .866 leading

  • Platform-Mounted ASVC Systemat Gilman Building ProductsInstalled January 27, 1997

  • Improved Voltage Stability

  • Conclusions - Lumber Mill Installation

    No customer motor failures in the year sinceinstallation

    Power factor improved to near unity duringleading and lagging load conditions

    Improved power quality for Gilman andneighboring distribution customers

    Directly connected ASVC has been areliable and effective solution.