Distribution System Static VAr Compensators Field Experience
-
Upload
mohsinaman -
Category
Documents
-
view
227 -
download
2
description
Transcript of Distribution System Static VAr Compensators Field Experience
-
Distribution System Static VArCompensators: Field Experience
Ray KemererPower Quality Systems, Inc.
February 4, 1998
-
IntelliVAr Advanced Static VAr Compensator(ASVC)
Block Diagram
-
Some Typical ASVCApplications
Lumber/Paper Mills Arc Welders Arc Furnaces Large Motor Loads Large Power Supplies Pumping Stations
-
Typical ASVC Specifications
Frequency: 50 Hz or 60 Hz Voltage: 7200 to 7967 volts line to neutral (directly
connected) 95 kV BIL -40 to +40C 2500 lbs. (1100 kg) Applied kVAr Capacity: 100 lagging to 1000 leading per
phase Stepless Control Dimensions: 85 (216) x 51 (130) x 47 (119) inches (cm)
-
Requirements for Installation
Install Platform (not required if pole-mounted). Install load break cutout for connection to ASVC line
bushing. Replace pole top insulator with current sensor. Connect neutral to ASVC ground pad. Provide 200 VA, 120 volt service and telephone or cellular
connection (for remote communication only). Installation does not cause customer service interruption.
-
Pole-Mounted InstallationDetroit Edison
-
Pre-Installation Considerations
Source and transformer impedance data Baseline load data such as harmonic
content, power factor, and time duration ofdynamic loads
Modeling and simulation Installation type: pole, platform, or pad-
mount
-
Actual vs. Modeled PowerSystem
220.0
230.0
240.0
250.0
260.0
270.0
280.0
290.0
1 14 27 53 66 79 92 105
118
131
144
157
170
183
196
209
Cycle Number
Vol
tage
Measured Voltage Theoretical Voltage
-
Predicted ASVC Response
114.00
115.00
116.00
117.00
118.00
119.00
120.00
121.00
122.00
Cycle Number
Vol
tage
Uncompensated Voltage Compensated Voltage
-
Oconee EMC(Ogelthorpe Power) Installation -
Dudley, GA 7200 volt line to neutral rating 50 kVAr inductive to 650 kVAr capacitive per
phase (stepless) Installed at highly automated Gilman Building
Products plant (lumber mill) Motor load was generating flicker Gilman plant had motor failures and motor drive
tripping Power factor ranged from .7 lagging to worse than
.866 leading
-
Platform-Mounted ASVC Systemat Gilman Building ProductsInstalled January 27, 1997
-
Improved Voltage Stability
-
Conclusions - Lumber Mill Installation
No customer motor failures in the year sinceinstallation
Power factor improved to near unity duringleading and lagging load conditions
Improved power quality for Gilman andneighboring distribution customers
Directly connected ASVC has been areliable and effective solution.