Technical Data
Distribution BoxesBulletin Numbers 898D, 898H, 898P
Topic Page
DC Micro Style Distribution Boxes 2
Four-Pin, One Signal per Port Cable Connector Distribution Box 2
Four-Pin, Two Signals per Port Cable Connector Distribution Box 3
Four-Pin, One Signal per Port Cable with Terminal Block Connector Distribution Box 5
Four-Pin, One or Two Signals per Port Cable with M23 Main Connector Distribution Box 6
Pico Style Distribution Boxes 8
Three-Pin, Cable Connector Distribution Box 8
Three-Pin, DC Micro Main Connector Distribution Box 10
IDC Style Distribution Boxes 11
One Signal per Port Cable Connector Distribution Box 11
Distribution Boxes
DC Micro Style Distribution Boxes
Four-Pin, One Signal per Port Cable Connector Distribution Box
Figure 1 - Approximate Dimensions
Figure 2 - Typical Wiring Diagram(s)
Table 1 - Specifications
Certifications UL recognized and CSA certified
MechanicalMaterial Gray Pocan
Connector insert material PBT
Receptacle shell material Zinc diecast with nickel plating
Contact material Gold-plated palladium/nickel
Cable type Oil-resistant black PUR/PVC jacket, (3) 18 AWG stranded copper, (4, 6, or 8) 22 AWG flex rated for 1 million cycles
Cable diameter• 4-port: 7.5 mm (0.30 in.)• 6-port: 7.8 mm (0.31 in.)• 8-port: 8.2 mm (0.32 in.)
EnvironmentalEnclosure type rating IP67, NEMA 6P, 1200 psi (8270 kPa) washdown
Operating temperature -20…+90 °C (-4…+194 °F)
Eight-port DC Micro Distribution Box
107 (4.21)73 (2.87)
60(2.36)
39(1.54)
4.5(0.18)
25(0.98)
7, 9, or 11conductor cable
33(1.3)
102 (4.02) 4-port127 (5.0) 6-port
152 (5.98) 8-port
13.5 (0.53)
16.5 (0.65)
18 (0.71)
898D
-54P
T-B5
Allen
-Bra
dley
-
5.0(0.20)
Allen
-Bra
dley
Dimensions are shown in mm (in.). Illustrations are not drawn to scale.Dimensions shown are not intended to be used for installation purposes.
NPN NPN
PNP PNP
NPN NPN NPN
51
51
51
5
43 4 3 3 4 3 4
15
15
15
15
13 4 3 4 3 4 3 4
4-Port
Gree
n/Ye
llow
(+)B
rown
(-)Bl
ue Whit
e
Gree
n
(PE)
PNP
NPN
PNP
NPN
PNP PNP PNP PNP
NPN
Yello
w
Grey
Pink
Red
Blac
k
Viole
t
6-Port 8-Port
1 2 3 4 5 6 7 8
Wiring diagram shows both PNP and NPN wiring. Actual units use PNP LED, NPN LED or neither.
Table 2 - Mating Components and Accessories
Description Cat. No.
Device patchcords 889D-F4ACDM-x(3)
(3) Replace x with 1 [1 m (3.28 ft)], 2 [2 m (6.56 ft)], 3 [3 m (9.84 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)] for standard cable lengths.
Field attachable connectors 871A-TS4-DM
IDC field attachable connectors 889D-M4DC-H
Sealing caps(1)
(1) Two provided with box.
1485A-M12
Labels(2)
(2) One set provided with box.
1492-MS9X20
Table 3 - Pinout
Device Connection Main Connection
Ports (4-Pin Female) Cable Connector
4-Port 6-Port 8-Port —
Ground Ground Ground Green/Yellow
(+) All Ports Pin 1 (+) All Ports Pin 1 (+) All Ports Pin 1 Brown
(-) All Ports Pin 3 (-) All Ports Pin 3 (-) All Ports Pin 3 Blue
Port 1 Pin 4 Port 1 Pin 4 Port 1 Pin 4 White
Port 2 Pin 4 Port 2 Pin 4 Port 2 Pin 4 Green
Port 3 Pin 4 Port 3 Pin 4 Port 3 Pin 4 Yellow
Port 4 Pin 4 Port 4 Pin 4 Port 4 Pin 4 Gray
— Port 5 Pin 4 Port 5 Pin 4 Rose
— Port 6 Pin 4 Port 6 Pin 4 Red
— — Port 7 Pin 4 Black
— — Port 8 Pin 4 Violet
Table 4 - Product Selection
Ports Illumination Assembly Rating Cat. No.(1)
(1) Replace x with 5 [5 m (16.40 ft)] or 10 [10 m (32.81 ft)] for standard cable lengths.
4 Port
No LED
10…30V DC,2 A per channel/ 10 A total
898D-54PT-Bx
PNP LED 898D-P54PT-Bx
NPN LED 898D-N54PT-Bx
6 Port
No LED 898D-56PT-Bx
PNP LED 898D-P56PT-Bx
NPN LED 898D-N56PT-Bx
8 Port
No LED 898D-58PT-Bx
PNP LED 898D-P58PT-Bx
NPN LED 898D-N58PT-Bx
Device patchcords (straight to straight) 889D-F4ACDM-y(2)
(2) Replace y with 1 [1 m (3.28 ft)], 2 [2 m (6.56 ft)], 3 [3 m (9.84 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)] for standard cable lengths.
5
4 3
1
2
2 Rockwell Automation Publication 898-TD001B-EN-P - June 2019
Distribution Boxes
Four-Pin, Two Signals per Port Cable Connector Distribution Box
Figure 3 - Approximate Dimensions
Figure 4 - Typical Wiring Diagram
Table 5 - Specifications
Certifications UL recognized and CSA certified
MechanicalMaterial Gray Pocan
Connector insert material PBT
Receptacle shell material Zinc diecast with nickel plating
Contact material Gold-plated palladium/nickel
Cable type Oil-resistant black PUR/PVC jacket, (3) 18 AWG stranded copper, (8 or 16) 22 AWG flex rated for 1 million cycles
Cable diameter • 4-port: 8.2 mm (0.32 in.)• 8-port: 9.7 mm (0.38 in.)
EnvironmentalEnclosure type rating IP67, NEMA 6P, 1200 psi (8270 kPa) washdown
Operating temperature -20…+90 °C (-4…+194 °F)
Eight-port DC Micro Distribution Box
60(2.36)
107 (4.21)73 (2.87)
39(1.54)
4.5(0.18)
25(0.98)
33(1.30)
102 (4.02) 4-port127 (5.0) 6-port
152 (5.98) 8-port
13.5(0.53)
16.5 (0.65)
18(0.71)
-
5.0(0.20)
ALLE
N-BR
ADLE
Y
ALLE
N-BR
ADLE
Y
11 or 19conductor
table
Dimensions are shown in mm (in.). Illustrations are not drawn to scale.
51
3
1
4
51
3 4
2
51
51
3 4
3
3 4
4
51
5
3 4
5
3
6
15
15
134 4
7
3 4
8
2 2 2 2 2 2 2 2
4-Port
Gree
n-Ye
llow
(+)B
rown
(-)Bl
ueW
hite
Gree
n
(PE)
PNP
Yello
w
Gray
Pink
Red
Blac
k
Viol
et
6-Port 8-Port
PNP
PNP
PNP
PNP
PNP
PNP
PNP
PNP
PNP
PNP
PNP
PNP
PNP
PNP
PNP
Gray
-Pin
k
Red-
Blue
Whi
te-G
reen
Brow
n-Gr
een
Whi
te-Y
ellow
Yello
w0-B
rown
Whi
te-G
ray
Gray
-Bro
wn
Wiring diagram shows PNP wiring. Actual units use PNP LED or no LED.
Table 6 - Mating Components and Accessories
Description Cat. No.
Device patchcords 889D-F4ACDM-x(3)
(3) Replace x with 1 [1 m (3.28 ft)], 2 [2 m (6.56 ft)], 3 [3 m (9.84 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)] for standard cable lengths.
Field attachable connectors 871A-TS4-DM
IDC field attachable connectors 889D-M4DC-H
V-cables 879D-F4ACDM-x(3)
Splitter 879D-F4DM
Sealing caps(1)
(1) Two provided with box.
1485A-M12
Labels(2)
(2) One set provided with box.
1492-MS9X20
Table 7 - Pinout
Device Connection Main Connection
Ports (4-Pin Female) Cable Connector
4-Port 8-Port —
Ground Ground Green-Yellow
(+) All Ports Pin 1 (+) All Ports Pin 1 Brown
(-) All Ports Pin 3 (-) All Ports Pin 3 Blue
Port 1 Pin 4 Port 1 Pin 4 White
Port 2 Pin 4 Port 2 Pin 4 Green
Port 3 Pin 4 Port 3 Pin 4 Yellow
Port 4 Bin 4 Port 4 Pin 4 Gray
— Port 5 Pin 4 Rose
— Port 6 Pin 4 Red
— Port 7 Pin 4 Black
— Port 8 Pin 4 Violet
Port 1 Pin 2 Port 1 Pin 2 Gray-Pink
Port 2 Pin 2 Port 2 Pin 2 Red-Blue
Port 3 Pin 2 Port 3 Pin 2 White-Green
Port 4 Pin 2 Port 4 Pin 2 Brown-Green
— Port 5 Pin 2 White-Yellow
— Port 6 Pin 2 Yellow-Brown
— Port 7 Pin 2 White-Gray
— Port 8 Pin 2 Gray-Brown
5
4 3
1
2
Rockwell Automation Publication 898-TD001B-EN-P - June 2019 3
Distribution Boxes
Table 8 - Product Selection
Ports Illumination Assembly Rating Cat. No.(1)(2)
(1) Replace x with 5 [5 m (16.40 ft)] or 10 [10 m (32.81 ft)] for standard cable lengths.(2) Replace y with 1 [1 m (3.28 ft)], 2 [2 m (6.56 ft)], 3 [3 m (9.84 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)]
for standard cable lengths.
4 PortNo LED
10…30V DC, 2 A per channel/ 10 A total
898D-54DT-Bx
PNP LED 898D-P54DT-Bx
8 PortNo LED 898D-58DT-Bx
PNP LED 898D-P58DT-Bx
Device patchcords (straight to straight) 889D-F4ACDM-y
Device V-cables (straight) 879D-F4ACDM-y
4 Rockwell Automation Publication 898-TD001B-EN-P - June 2019
Distribution Boxes
Four-Pin, One Signal per Port Cable with Terminal Block Connector Distribution Box
Figure 5 - Approximate Dimensions
Figure 6 - Typical Wiring Diagram(s)
Table 9 - Specifications
Certifications UL recognized and CSA certified
MechanicalMaterial Gray Pocan
Connector insert material PBT
Receptacle shell material Zinc diecast with nickel plating
Contact material Gold-plated palladium/nickel
Cable gland M20 mounting thread
Cable diameter 6…10 mm (0.24…0.39 in.)
EnvironmentalEnclosure type rating IP67, 1200 psi (8270 kPa) washdown
Operating temperature -20…+90 °C (-4…+194 °F)
Eight-port DC Micro Distribution Box
107 (4.21)73 (2.87) 4.5
(0.18)
41.5(1.63)
33(1.30)5.0
(0.20)
ALLE
N-BR
ADLE
Y
13.5(0.53)
16.5 (0.65)
18(0.71)
ALLE
N-BR
ADLE
Y
13.5(0.53)
39(1.54)
898D
-54P
T-T B
60(2.36)
102 (4.02) 4-port
127 (5.0) 6-port
152 (5.98) 8-port
Dimensions are shown in mm (in.). Illustrations are not drawn to scale.Dimensions shown are not intended to be used for installation purposes.
Blue
-- --
3
5
4
1
1
5
31
4
5
3 4
2 3
15
3 4
15
3
4 5
1
4
5
3 4
1
6
4
5
31
5
31
4
7 8
4-Port
1 2(PE)
NPN
3 4 5 6 7 8
6-Port 8-Port
PNP
NPN
PNP
NPN
PNP
NPN
PNP
NPN
PNP
NPN
PNP
NPN
PNP
NPN
PNP
++
1917U2U1
++
1820U1U2
Red
Wiring diagram shows both PNP and NPN wiring. Actual units use PNP LED, NPN LED or neither.
Table 10 - Mating Components and Accessories
Description Cat. No.
Device patchcords 889D-F4ACDM-x(3)
(3) Replace x with 1 [1 m (3.28 ft)], 2 [2 m (6.56 ft)], 3 [3 m (9.84 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)] for standard cable lengths.
Field attachable connectors 871A-TS4-DM
IDC field attachable connectors 889D-M4DC-H
Sealing caps(1)
(1) Two provided with box.
1485A-M12
Labels(2)
(2) One set provided with box.
1492-MS9X20
Table 11 - Pinout
Device Connection Main Connection
Ports (4-Pin Female) Terminal Block Connector
4-Port 8-Port —
Ground Ground PE
(+) Odd Ports Pin 1 (+) Odd Ports Pin 1 17
(+) Even Ports Pin 1 (+) Even Ports Pin 1 19
(-) Odd Ports Pin 3 (-) Odd Ports Pin 3 18
(-) Even Ports Pin 3 (-) Even Ports Pin 3 20
Port 1 Pin 4 Port 1 Pin 4 1
Port 2 Pin 4 Port 2 Pin 4 2
Port 3 Pin 4 Port 3 Pin 4 3
Port 4 Pin 4 Port 4 Pin 4 4
— Port 5 Pin 4 5
— Port 6 Pin 4 6
— Port 7 Pin 4 7
— Port 8 Pin 4 8
Table 12 - Product Selection
Ports Illumination Assembly Rating Cat. No.
4 Port No LED
10…30V DC, 2 A per channel/ 10 A total or8 A per input when 2 inputs are used
898D-54PT-T
PNP LED 898D-P54PT-T
NPN LED 898D-N54PT-T
8 Port No LED 898D-58PT-T
PNP LED 898D-P58PT-T
NPN LED 898D-N58PT-T
Device patchcords (straight to straight) 889D-F4ACDM-x(1)
(1) Replace x with 1 [1 m (3.28 ft)], 2 [2 m (6.56 ft)], 3 [3 m (9.84 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)] for standard cable lengths.
5
4 3
1
2 15 7 13 5 11 3 4 12 6 14 8 16
9 1 19 17 21 18 20 2 10
Rockwell Automation Publication 898-TD001B-EN-P - June 2019 5
Distribution Boxes
Four-Pin, One or Two Signals per Port Cable with M23 Main Connector Distribution Box
Figure 7 - Approximate Dimensions
Figure 8 - Typical Wiring Diagram(s)
Table 13 - Specifications
Certifications UL recognized and CSA certified
MechanicalMaterial Gray Pocan
Connector insert material PBT
Receptacle shell material Zinc diecast with nickel plating
Contact material Gold-plated palladium/nickel
Main connector style 12- and 19- pin M23
EnvironmentalEnclosure type rating IP67, 1200 psi (8270 kPa) washdown
Operating temperature -20…+90 °C (-4…+194 °F)
Eight-port DC Micro Distribution Box
73 (2.87)107 (4.21)
4.5(0.18)
5.0 (0.20)
ALLEN
-BRAD
LEY
16.5 (0.65)
898D
-54P
T-M
12 B
19.7(0.78)
M23
3 (0.12)
29.2(0.15)
33(1.30)
39(1.54)
60(2.36)60
(2.36)
102 (4.02) 4-port
127 (5.0) 6-port
152 (5.98) 8-port
ALLE
N-BR
ADLE
Y
Dimensions are shown in mm (in.). Illustrations are not drawn to scale.Dimensions shown are not intended to be used for installation purposes.
Table 14 - Mating Components and Accessories
Description Cat. No.(3)
(3) Replace x with 1 [1 m (3.28 ft)], 2 [2 m (6.56 ft)], 3 [3 m (9.84 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)] for standard cable lengths.
Device patchcords 889D-F4ACDM-x
Homerun patchcord (12-pin) 889M-R11RMMU-x
Homerun patchcord (19-pin) 889M-R19RMMU-x
V-cable (dual) 879D-F4ADM-2
Sealing caps(1)
(1) Two provided with box.
1485A-M12
Labels(2)
(2) One set provided with box.
1492-MS9X20
3
5
41
5
3
PNP1 2
14
5
3 41
PNP PNP3
4
5
31
5
31
4
PNP4 5
PNP
3
5
41
5
3
PNP6 7
14
5
31
4
8PNP PNP
(-)1012
(PE)11(+)
19(-)
2 3 4 5 6 7 84 Port 6 Port 8 Port
5
52
1
PNP
3 4
1
PNP
6 7 8
(PE)12
(+)11
(-)(-)10 9 1 2 3 4
2
3
51
4 PNP
PNP1
3
52
1
PNP4
PNP1
PNP1
2
3
51
PNP4
4 Port
1
51
3
1
11217316515619
4
51
3 4
2
12(PE)
51
51
3 4
3
3 4
4
51
5
3 4
5
3
6
15
15
134 4
7
3 4
8
2 2 2 2 2 2 2 2
PNPPNP PNP PNP PNP PNP PNP PNP
PNP PNP PNP PNP PNP PNP PNP PNP
181013914847
4 Port 6 Port 8 Port
6 Rockwell Automation Publication 898-TD001B-EN-P - June 2019
Distribution Boxes
Table 15 - Pinout
Device Connection Main Connection
Ports (4-Pin Female)M23 Connector(12-Pin Male)
4-Port (Single Channel)
4-Port (Dual Channel)
8-Port (Single Channel)
—
Ground Ground Ground 12
(+) All Ports Pin 1 (+) All Ports Pin 2 (+) All Ports Pin 1 11
(-) All Ports Pin 3 (-) All Ports Pin 4 (-) All Ports Pin 3 10 and 9
Port 1 Pin 4 Port 1 Pin 4 Port 1 Pin 4 1
Port 2 Pin 4 Port 2 Pin 4 Port 2 Pin 4 2
Port 3Pin 4 Port 3 Pin 4 Port 3 Pin 4 3
Port 4 Pin 4 Port 4 Pin 4 Port 4 Pin 4 4
— Port 1 Pin 2 Port 5 Pin 4 5
— Port 2 Pin 2 Port 6 Pin 4 6
— Port 3 Pin 2 Port 7 Pin 4 7
— Port 4 Pin 2 Port 8 Pin 4 8
Table 16 - Product Selection
PortsNo. of
Signals per Port
Illumination Assembly Rating Cat. No.(1)
(1) Replace x with 1 [1 m (3.28 ft)], 2 [2 m (6.56 ft)], 3 [3 m (9.84 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)] for standard cable lengths.
4 Port
Single (1)
No LED
10…30V DC,2 A per channel/
10 A total
898D-54PT-M12
PNP LED 898D-P54PT-M12
8 PortNo LED 898D-58PT-M12
PNP LED 898D-P58PT-M12
4 Port
Dual (2)
No LED 898D-54DT-M12
PNP LED 898D-P54DT-M12
8 PortNo LED 898D-58DT-M19
PNP LED 898D-P58DT-M19
Device patchcords (straight to straight) 889D-F4ACDM-x
Homerun patchcord for 12-pin (right angle to straight) 889M-R11RMMU-x
Homerun patchcord for 19-pin (right angle to straight) 889M-R19RMMU-x
5
4 3
1
2
2
3
45
6
1
11
10
98
712
Table 17 - Pinout
Device Connection Main Connection
Ports (4-Pin Female) M23 Connector (19-Pin Male)
8-Port (Dual Channel) —
Ground 12
(+) All Ports Pin 1 19
(-) All Ports Pin 3 6
Port 1 Pin 4 15
Port 2 Pin 4 5
Port 3 Pin 4 16
Port 4 Pin 4 3
Port 5 Pin 4 17
Port 6 Pin 4 2
Port 7 Pin 4 11
Port 8 Pin 4 1
Port 1 Pin 2 7
Port 2 Pin 2 4
Port 3 Pin 2 8
Port 4 Pin 2 14
Port 5 Pin 2 9
Port 6 Pin 2 13
Port 7 Pin 2 10
Port 8 Pin 2 18
5
4 3
1
2 2
3
456
11110
9
87
12
1813
1416
1719
15
Rockwell Automation Publication 898-TD001B-EN-P - June 2019 7
Distribution Boxes
Pico Style Distribution Boxes
Three-Pin, Cable Connector Distribution Box
Figure 9 - Approximate Dimensions
Figure 10 - Typical Wiring Diagrams
Table 18 - Specifications
Certifications UL recognized and CSA certified
MechanicalMaterial Gray Pocan
Connector insert material PBT
Receptacle shell material Nickel-plated brass
Contact material Gold-plated palladium/nickel
Cable typeOil-resistant black PUR/PVC jacket, (3) 18 AWG stranded copper, (4, 6, 8, 10 or 12) 22 AWG flex rated for 1 million cycles
Cable diameter
4-port: 6.4 mm (0.25 in.)6-port: 7.2 mm (0.28 in.)8-port: 7.4 mm (0.29 in.)10-port: 7.6 mm (0.30 in.)12-port: 9.8 mm (0.39 in.)
EnvironmentalEnclosure type rating IP67
Operating temperature -20…+80 °C (-4…+176 °F)
Table 19 -
No. of Ports L R B A
4 57 (2.2) 39 (1.5) 85 (3.3) 92. (3.6)
6 83 (3.3) 65 (2.6) 111 (4.4) 118 (4.6)
8 109 (4.3) 91 (3.6) 137 (5.4) 144 (5.7)
10 135 (5.3) 117 (4.6) 163 (6.4) 170 (6.7)
12 161 (6.3) 143 (5.6) 189 (7.4) 196 (7.7)
Eight-port Pico Distribution Box
412
34.8 (1.37)
12 1 10 4
24(0.95)
AL
4.2 (0.17) Ø
17 (0.67)
8(0.31) 4.5
(0.18)
3.5 (0.14)
20 (0.79)
3.2(0.13)
R
4.2(0.17) Ø
4.2(0.17)
17 (0.67)18.2 (0.72) B
13
A B ALLEN-BRADLEY 898P-34PT-B5
Table 20 - Mating Components and Accessories
Description Cat. No.
Device patchcords 889P-F3ABPM-x(3)
(3) Replace x with 1 [1 m (3.28 ft)], 2 [2 m (6.56 ft)], 3 [3 m (9.84 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)] for standard cable lengths.
Field attachable connectors 871A-TS3-PM
IDC field attachable connectors 889P-M3DC-H
Sealing caps(1)
(1) Two provided with box.
889A-PMCAP
Labels(2)
(2) One set provided with box.
1492-M5X10
4-Port 6-Port 8-Port 10-Port
12-Port
LED-
GN
3
4
Bu1
Bu2
31
Bu3
31 1
4 4
Bu4
3 1
Bu5
3 31
4 4 4
Bu8
Bu6
1 3
Bu7
1 3
4 4
Bu9
31
Bu10
31 1
4 4
BROW
N(+
)
BLUE
(-)
AW
HITE
AGR
EEN
AYE
LLOW
AGR
AY
A A
PINK
GRAY
/PIN
KA
RED
ARE
D/BL
UE
BROW
N/GR
EEN
WHI
TE/G
REEN
A A
Bu12
Bu11
3
4
1 3
4
1
YELL
OW/B
ROW
N
WHI
TE/Y
ELLO
WA A
BLUE
(-)
BROW
N(+
)
3 1
4
WHI
TE
4
3 1
4
3 1 3
4
1 13
4
3
4
1 3
4 4
31 1
A A A A A A A A
GREE
N
YELL
OW
PINK
RED
BLAC
K
VIOL
ET
LED-
GN
Bu1
Bu2
Bu3
Bu4
Bu5
Bu6
Bu7
Bu8
4
313
Bu9
4
1
Bu10
A
GRAY
/PIN
KA
RED/
BLUE
GRAY
8 Rockwell Automation Publication 898-TD001B-EN-P - June 2019
Distribution Boxes
Table 21 - Pinout
Device Connection Main Connection
Ports (3-Pin Female) Cable
4-Port 6-Port 8-Port 10-Port 12-Port —
Ground Ground Ground Ground Ground Green/Yellow
(+) All Ports Pin 1 (+) All Ports Pin 1 (+) All Ports Pin 1 (+) All Ports Pin 1 (+) All Ports Pin 1 Brown
(-) All Ports Pin 3 (-) All Ports Pin 3 (-) All Ports Pin 3 (-) All Ports Pin 3 (-) All Ports Pin 3 Blue
Port 1 Pin 4 Port 1 Pin 4 Port 1 Pin 4 Port 1 Pin 4 Port 1 Pin 4 White
Port 2 Pin 4 Port 2 Pin 4 Port 2 Pin 4 Port 2 Pin 4 Port 2 Pin 4 Green
Port 3 Pin 4 Port 3 Pin 4 Port 3 Pin 4 Port 3 Pin 4 Port 3 Pin 4 Yellow
Port 4 Pin 4 Port 4 Pin 4 Port 4 Pin 4 Port 4 Pin 4 Port 4 Pin 4 Gray
— Port 5 Pin 4 Port 5 Pin 4 Port 5 Pin 4 Port 5 Pin 4 Rose
— Port 6 Pin 4 Port 6 Pin 4 Port 6 Pin 4 Port 6 Pin 4 Red
— — Port 7 Pin 4 Port 7 Pin 4 — Black
— — Port 8 Pin 4 Port 8 Pin 4 — Violet
— — — Port 9 Pin 4 Port 7 Pin 4 Gray/Pink
— — — Port 10 Pin 4 Port 8 Pin 4 Red/Blue
— — — — Port 9 Pin 4 White/Green
— — — — Port 10 Pin 4 Brown/Green
— — — — Port 11 Pin 4 White/Yellow
— — — — Port 12 Pin 4 Yellow/Brown
3 1
4
Table 22 - Product Selection
Ports Illumination Assembly Rating Cat. No.(1)
(1) Replace x with 5 [5 m (16.40 ft)] or 10 [10 m (32.81 ft)] for standard cable lengths.
4 Port
PNP LED 10…30V DC,2 A per channel/ 6 A total
898P-P34PT-Bx
6 Port 898P-P36PT-Bx
8 Port 898P-P38PT-Bx
10 Port 898P-P310PT-Bx
12 Port 898P-P312PT-Bx
Device patchcords (3-pin straight to straight) 889P-F3ABPM-y(2)
(2) Replace y with 1 [1 m (3.28 ft)], 2 [2 m (6.56 ft)], 3 [3 m (9.84 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)] for standard cable lengths.
Rockwell Automation Publication 898-TD001B-EN-P - June 2019 9
Distribution Boxes
Three-Pin, DC Micro Main Connector Distribution Box
Figure 11 - Approximate Dimensions
Figure 12 - Typical Wiring Diagram(s)
Table 23 - Specifications
Certifications UL recognized and CSA certified
MechanicalMaterial Gray Pocan
Connector insert material PBT
Receptacle shell material Nickel-plated brass
Contact material Gold-plated palladium/nickel
Main connector style 8-pin DC micro
EnvironmentalEnclosure type rating IP67
Operating temperature -20…+80 °C (-4…+176 °F)
No. of Ports L R B A
4 57 (2.2) 39 (1.5) 80 (3.1) 87 (3.4)
6 83 (3.3) 65 (2.6) 106 (4.2) 113 (4.4)
Table 24 - Product Selection
Ports Illumination Assembly Rating Cat. No.
4 PortPNP LED 10…30V DC,
2 A per channel/ 3 A total898P-P34PT-D8
6 Port 898P-P36PT-D8
Device patchcords (3-pin straight to straight) 889P-F3ABPM-x(1)
(1) Replace x with 1 [1 m (3.28 ft)], 2 [2 m (6.56 ft)], 3 [3 m (9.84 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)] for standard cable lengths.
Homerun patchcord for D8 models (right angle to straight) 889D-R8ABDM-x(1)
Six-port Pico Distribution Box
17(0.67)
3.2(0.13)
4.2(0.17)
4.2 (0.17) Ø11 (0.43)
9 (0.35)
3.5 (0.14)
R
18.2(0.72)
B
3.5 (0.14)
23(0.91)
AL
3.5 (0.14)
17(0.67)
24(0.95)
39.8 (1.17)
A B A B A B A B A B A B
41 3A B
ALLEN-BRADLEY 898P-P34PT-D8
Table 25 - Mating Components and Accessories
Description Cat. No.
Device patchcords (3-pin) 889P-F3ABPM-x(3)
(3) Replace x with 1 [1 m (3.28 ft)], 2 [2 m (6.56 ft)], 3 [3 m (9.84 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)] for standard cable lengths.
DC micro homerun patchcord 889D-R8ABDM-x(3)
Field attachable connectors 871A-TS3-PM
IDC field attachable connectors 889P-M3DC-H
Sealing caps(1)
(1) Two provided with box.
889A-PMCAP
Labels(2)
(2) One set provided with box.
1492-M5X10
Table 26 - Pinout
Device Connection Main Connection
Ports (3-Pin Female) 8-Pin DC Micro
4-Port 6-Port —
(+) All Ports Pin 1 (+) All Ports Pin 1 7
(-) All Ports Pin 3 (-) All Ports Pin 3 5
Port 1 Pin 4 Port 1 Pin 4 1
Port 2 Pin 4 Port 2 Pin 4 2
Port 3 Pin 4 Port 3 Pin 4 3
Port 4 Pin 4 Port 4 Pin 4 4
— Port 5 Pin 4 6
— Port 6 Pin 4 8
5(-)
7(+
)
3 1
4
4
4 Channel
6 Channel
4
3 1
4
3 1 3
4
1 13
4
3
4
1
321 6 8
LED-
GN
Bu1
Bu2
Bu3
Bu4
Bu5
Bu6
LED-
A
LED-
A
LED-
A
LED-
A
LED-
A
LED-
A
3 1
4
5-Aux A 6-Aux A7
8
4
3-GND1-Safety A
2-Safety A
10 Rockwell Automation Publication 898-TD001B-EN-P - June 2019
Distribution Boxes
IDC Style Distribution Boxes
One Signal per Port Cable Connector Distribution Box
Figure 13 - Approximate Dimensions
Figure 14 - Typical Wiring Diagram
Table 27 - Specifications
Certifications UL recognized and CSA certified
MechanicalMaterial Gray Pocan
Connector insert material PBT
Receptacle shell material Nickel-plated brass
Contact material Gold-plated palladium/nickel
IDC installations, max 10
Cable type Oil-resistant black PUR/PVC jacket, (3) 18 AWG stranded copper, (8 or 16) 22 AWG flex rated for 1 million cycles
Cable diameter 7.4 mm (0.29 in.)
Conductor OD 24…22 AWG, 1.6…2.0 mm (0.063…0.079 in.)
EnvironmentalEnclosure type rating IP67, 1200 psi (8270 kPa) washdown
Operating temperature -20…+90 °C (-4…+194 °F)
Table 28 - Product Selection
Ports Illumination Assembly Rating Cat. No.
8 PortNo LED 10…30V DC,
2 A per channel/ 10 A total
898H-58PT-Bx(1)
(1) Replace x with 5 [5 m (16.40 ft)] or 10 [10 m (32.81 ft)] for standard cable lengths.
PNP LED 898H-P58PT-Bx(1)
Device patchcords (3-pin straight to straight) 889A-HCC3
Device patchcords (3-pin straight to straight) 889D-F4AC-y(2)
(2) Replace y with 2 [2 m (6.56 ft)], 5 [5 m (16.40 ft)] or 10 [10 m (32.81 ft)] for standard cable lengths.
Eight-port IDC Style Distribution Box
IDC Insert
60(2.36)
39(1.54)
25(0.98)
898H
-58PT-
B5 B
Allen
Brad
ley 1 231
2 3 12 3
31 2
12 3
31 2
12 3
31 2
152(5.98) 8 port
107 (4.21)73 (2.87)
4.5(0.18)
13.5(0.53)
33(1.3)
13.5 (0.53)
16.5 (0.65)
18 (0.71)
5.0(0.2)
Dimensions are shown in mm (in.). Illustrations are not drawn to scale.Dimensions shown are not intended to be used for installation purposes.
Table 29 - Mating Components and Accessories
Description Cat. No.
Device patchcords 889D-F4AC-x(3)
(3) Replace x with 2 [2 m (6.56 ft)], 5 [5 m (16.40 ft)], or 10 [10 m (32.81 ft)] for standard cable lengths.
Three-pole IDC insert (required for connection with IDC box)
889A-HCC3
Sealing caps(1)
(1) Two provided with box.
1485A-M12
Labels(2)
(2) One set provided with box.
1492-MS9X20
Table 30 - Pinout
Device Connection Main Connection
Ports (IDC) Cable Connector
8-Port —
(+) All Ports Pin 1 Brown
(-) All Ports Pin 3 Blue
Port 1 Pin 2 White
Port 2 Pin 2 Green
Port 3 Pin 2 Yellow
Port 4 Pin 2 Gray
Port 5 Pin 2 Rose
Port 6 Pin 2 Red
Port 7 Pin 2 Black
Port 8 Pin 2 Violet
4-Port
(+)B
rown
(-)Bl
ue
Whi
te
Gree
n
Yello
w
Grey
Pink
Red
6-Port 8-Port
3
12
1111
3
2
33
22
3
221
21
3 3
21
3
1 2 3 4 5 6 7 8
Blac
k
Viole
t
Wiring diagram shows PNP wiring. Actual units use PNP LED or no LED.
1
3
2
Rockwell Automation Publication 898-TD001B-EN-P - June 2019 11
Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 898-TD001B-EN-P - June 2019
Rockwell Automation SupportUse the following resources to access support information.
Documentation FeedbackYour comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates. www.rockwellautomation.com/knowledgebase
Local Technical Support Phone Numbers Locate the phone number for your country. www.rockwellautomation.com/global/support/get-support-now.page
Direct Dial CodesFind the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer.
www.rockwellautomation.com/global/support/direct-dial.page
Literature Library Installation Instructions, Manuals, Brochures, and Technical Data. www.rockwellautomation.com/literature
Product Compatibility and Download Center (PCDC)
Get help determining how products interact, check features and capabilities, and find associated firmware.
www.rockwellautomation.com/global/support/pcdc.page
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.
Waste Electrical and Electronic Equipment (WEEE)
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Supersedes Publication 898-TD001A-EN-P - April 2016 Copyright © 2019 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.