0.46 cu.in. displacement 2-stroke 0.70 cu.in. displacement ...
Displacement Units - Louvres | Attenuators | Slot · PDF filedistribution unit for...
-
Upload
nguyenkiet -
Category
Documents
-
view
231 -
download
1
Transcript of Displacement Units - Louvres | Attenuators | Slot · PDF filedistribution unit for...
Dis
plac
emen
t Uni
ts
DU.�.ed2
DU.6a
DISPLATEK ADU4
Specification:DISPLATEK ADU04 is a rectangular air distribution unit for displacement ventilla-tion. The armature has a rectangular duct connection with sleeve dimensions.The unit is fitted with diffusion nozzles which make it possible to change the geometry of the near zone.Th eunit is maintenance free and there is no risk of clogging.
Materials & Finish:Internal and external parts are galvanised steel, nozzles are black plastic and face plate 1.5mm galvanised steel. Standard finish is RAL9010 white powder coat, other colours being available on request.
Mounting:Floor mounting against wall.Duct connection from above or below.
DISPLATEK ADU4
DISPLATEK ADU04
DU.6b
Dimensions AccessoriesDuct flashing CEAZ-1 with Telescope
Plinth CEAZ-2
WeightSize A B D H Weight
kg2010 300 300 200 980 12,0
2510 500 350 250 980 24,0
3115 800 500 315 �500 80,0
4015 800 600 400 �500 96,0
WeightSize B Weight kg/m
2010 300 8,0
2510 350 10,0
3115 500 15,0
40�5 600 16,0
DISPLATEK ADU04Technical Specification
Supplied separately
Dis
plac
emen
t Uni
ts
DU.�.ed2
DU.6c
a0,2 is the horizontal distance from the wall to where the maximum velocity has de-creased to 0.2m/s.b0,2 is the horizontal distance from the cen-tre of the unit parallel with the wall to where the maximum velocity has decreased to 0.2m/s.
Sound Pressure Level LA,dB(A)The sound pressure level is specified at room damping of 4dB, corresponding to the damping in a room with a room constant of 10m2 SABINE measured in the reverbera-tion field.
Example of Calculation:Air flow: 150l/s (540 m3/h)Size 2510 lies within the recommended field of application.
Near zone at -3K: a0,2 = 1,2m, b0,2 = 4,0m.Pressure loss: Pt = 16PaSound pressure level: LA = 24 dB(A)
Sound Power LevelSound Power Level LW(dB) = LA + KOK
Sound AttenuationSound attenuation L (dB) including end reflection
DISPLATEK ADU04Technical SpecificationNear zone a0,2, b0,2
KOK
Mean Frequency HZSize 125 250 500 1000 2000 4000 80002010 6 7 � -� -8 -17 -17
2510 9 7 4 -� -9 -21 -23
3115 �� 7 4 -2 -�0 -12 -�5
4015 �� 7 5 -2 -�� -9 -9
Mean Frequency HZSize 125 250 500 1000 2000 4000 80002010 6 � 4 5 3 4 4
2510 6 6 4 2 2 4 3
3115 6 5 3 3 4 4 5
4010 5 3 3 2 3 4 4
DU.6d
DISPLATEK ADU04Technical Specification
Table 1
Near zone measured at an undertemperature of -3K to a maximum terminal velocity of 0.20 m/s.Conversion to other terminal velocitties - see table 1 for -3K and -6K respectively
Large diffusion(factory setting)
Small diffusionTechnical data
Correction of Near Zone (a0,2, b0,2)
Undertemperature -3K -6KMaximum velocity (m/s) 0,20 0,25 0,30 0,35 0,40 0,20 0,25 0,30 0,35 0,40
Mean velocity (m/s) 0,10 0,12 0,15 0,17 0,20 0,10 0,12 0,15 0,17 0,20