Direct Expansion or Chilled WaterWhich is...
Transcript of Direct Expansion or Chilled WaterWhich is...
A S H R A E J O U R N A L a s h r a e . o r g S E P T E M B E R 2 0 166 8
Daniel H. Nall, P.E., FAIA, is vice president at Syska Hennessy Group, New York.
COLUMN ENGINEER’S NOTEBOOK
Daniel H. Nall
Direct-expansion (DX) cooling and heat pump systems have often been the less-respected alternative for building conditioning compared with hydronic systems. In general, they are considered to be a “cheaper” system, with higher maintenance cost, shorter lifespan, limited controllability and lower energy efficiency. On the other hand, they are often more convenient, more amenable to design-build procurement, and less demanding of operator expertise.
Recent improvements, however, to commercially
available products have made these systems more con-
trollable, and more energy efficient, to the point that
they are competitive with chilled-water systems, both
from the standpoint of preciseness of environmental
control and energy efficiency.
This column will describe an office building project in
New Jersey for which custom direct-expansion air con-
ditioning was more energy efficient, and less costly both
to construct and to operate than a built-up chilled-water
system. Since this building was finished, several manu-
facturers have included some of the components incor-
porated in the custom rooftop systems of the project as
options in their standard product lines.
IntroductionDX systems of old were the bottom of the ladder
for environmental control. Originally equipped with
reciprocating compressors, the units were loud, inef-
ficient and had limited controllability. An article from
ASHRAE Journal in 2001 discussed means of evaluating
dehumidification limitations for DX units,1 primarily
addressing the loss of humidity control when the unit
cycles for part-load and humid outdoor air is supplied
continuously. Unloading issues with DX systems often
left various forms of reheat as the only means of accurate
dry-bulb temperature and humidity control within the
space.
Engineers sought various methods of integral reheat
using the refrigeration cycle itself to raise the tempera-
ture of the supply air to reduce sensible capacity while
avoiding energy expenditure for reheat and somewhat
increasing the efficiency of the refrigeration process.2
Even before continuously unloading centrifugal water
chillers were available, chilled-water systems were
able to provide a relatively constant temperature cool-
ing source, without thrashing the stepped unloading
devices, because the thermal mass of the circulating
water dampens the impact of stepped unloading. Even
with slightly varying chilled-water temperature, vari-
able volume air-handling units can, energy efficiently,
vary sensible cooling to meet space loads while main-
taining an acceptable range of the apparatus dew point
to control space humidity. The advent of the centrifugal
chiller, furthermore, not only facilitated part-load cool-
ing control, but also increased the efficiency of cooling
production far beyond the level achievable by DX sys-
tems using positive displacement compressors.
BY DANIEL H. NALL, P.E., BEMP, HBDP, FAIA, FELLOW/LIFE MEMBER ASHRAE
Direct Expansion or Chilled Water–Which is Better?
©ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal at www.syska.com. This article may not be copied nor distributed in either paper or digital form without ASHRAE’s permission. For more information about ASHRAE, visit www.ashrae.org.
S E P T E M B E R 2 0 16 a s h r a e . o r g A S H R A E J O U R N A L 6 9
COLUMN ENGINEER’S NOTEBOOK
is located, while providing energy efficiency superior to
a built-up chilled-water system.
The Chilled-Water AlternativeChilled water systems could be considered the “gold
standard” for high performance building cooling sys-
tems. They have excellent part-load performance,
continuous unloading, flexibility of connection to ter-
minal units to convey cooling to occupied space, and
ease of control. In general, water-cooled chiller plants
are acknowledged as the most energy-efficient cool-
ing source for large buildings. For this study, a chiller
plant complying with ASHRAE Standard 90.1-2013 was
assumed, using the higher EER and lower IPLV option
for Path B, effective Jan. 1, 2015. Following are the code
requirements for the chilled-water plant:
• 0.585 kW/ton (0.166 kW/kW) – chiller power for
units ≥400 tons (1407 kW) and ≤600 tons (2110 kW)3;
• 0.052 kW/ton (0.0148 kW/kW) – cooling tower fans
(40.2 gpm/hp [3.4 L/s·kW], 2.8 gpm/ton [0.05 L/s·kW]
condenser water)4;
• 0.053 kW/ton (0.015 kW/kW) – condenser water
pumps (19 W/gpm [0.084 W/L·s], 10°F range [5.6°C])5;
• 0.044 kW/ton (0.013 kW/kW) – chilled-water pumps
(22 W/gpm [0.097 W/L·s], 12°F range [6.7°C])5;
• 0.73 kW/ton (0.21 kW/kW) – cooling plant energy;
• 20.5 Btu/Wh (6.01 J/J) – compressor-only EER
(6.01 COP); and
• 16.3 Btu/Wh (4.8 J/J) – cooling plant EER. (4.79 COP).
Adding an ASHRAE Standard 90.1-2013-compliant fan
yields the following power requirements:
• 80°F/67°F (26.7°C/19.4°C) entering dry-bulb/wet-
bulb temperature;
• 0.0015 hp/cfm (0.0024 kW/L·s) fan power;
• 0.34 kW/ton (0.10 kW/kW) of cooling fan power;
• 1.07 kW/ton (0.304 kW/kW) total HVAC power; and
• 11.2 Btu/Wh (3.28 J/J) – EER for the system
(3.29 COP).
Comparison of the two cooling source alternatives
required standardization of the air-handling sec-
tion of the system. After rigorous energy modeling
studies, a cold (50°F [10°C]) air delivery strategy was
adopted, because the reduced fan energy more than
offset the additional cooling energy required for the
lower supply air temperature. Because the reduced
mixed airflow has a higher than normal outdoor air
fraction, the mixed air condition onto the coil has a
Current DX systems can be competitive with chilled-
water systems both for control accuracy and energy effi-
ciency due to two technical advances. The first of these is
the ability of small compressors to perform continuous,
rather than stepped, unloading. Prior to the advent of
this technology, small compressors typically had discrete
unloading steps, which for DX units translated directly
into variations in supply air temperature and the appa-
ratus dew-point temperature.
Continuous unloading of small compressors can be
achieved either by variable speed drive, or by timed
rapid cycling of the compressor between a loaded and
unloaded state. The time ratio between loaded and
unloaded states determines the part-load fraction of the
compressor, while the cycling frequency is so fast that
the refrigerant pulses blend into a steady stream, albeit
at a reduced flow rate.
The second innovation is the electronic expansion
valve. This innovation allows more precise handling of
varying refrigerant flow rates, to allow control of evapo-
ration temperature in the face of varying coil loads. With
these two innovations in place and with the increas-
ing efficiency of small compressors, DX systems can
approach the precision and efficiency of chilled-water
systems.
While most packaged DX systems are air-cooled, sev-
eral manufacturers are offering evaporative condensers
as an option for their premium semi-custom packaged
rooftop systems. This measure typically increases the
efficiency of the condenser and compressor section of
the unit by more than 30%. For the larger versions of
such systems, the ASHRAE Standard 90.1-2013 perfor-
mance requirement is for a minimum EER of 11.7 with
an IEER of 11.9.3 This performance requirement com-
pares favorably with the cumulative ASHRAE Standard
90.1-2013 requirements for all-air VAV systems with
water-cooled chillers as the source of cooling.
For a recent build-to-suit office building project in
New Jersey, with aspirations of Platinum Certification
for both LEED NC v.3 and LEED CI v3, a number of HVAC
options were considered and subjected to rigorous
energy modeling and cost estimating study. As a result
of these efforts, a custom packaged direct-expansion
rooftop system with evaporative condenser was recom-
mended and used on the project. The resulting appli-
cation retains many of the advantages of the packaged
rooftop units used in the office park where the building
A S H R A E J O U R N A L a s h r a e . o r g S E P T E M B E R 2 0 167 0
• 0.98 kW/ton (0.28 kW/kW) total HVAC power; and
• 12.3 Btu/Wh (3.60 J/J) – EER for the system
(3.60 COP).
The part-load performance of the chilled-water
plant mandated by ASHRAE Standard 90.1-2013, Path
B, requires an IPLV of 0.380 kW/ton (0.108 kW/kW).
Typically, this path is for centrifugal compressors using
variable speed drive for capacity control.
Prefabricated Evaporative Condenser Dx PenthouseThe system selected for comparison with the chilled-
water plant option was a custom packaged rooftop pent-
house, two of which were used to condition the building.
The two systems had the following characteristics:
• Evaporative condenser with VFD fans;
• Sump temperature-controlled circulating pumps;
• Three variable speed magnetic bearing compres-
sors, one with hot gas bypass, total capacity 405 tons
(1424 kW);
• Nominal compressor power 0.54 kW/ton
(0.15 kW/kW);
significantly higher enthalpy than the AHRI rating
condition.
As a result, fan power per ton (kW) of refrigeration is sig-
nificantly less than the standard condition. However, meet-
ing the supply air temperature goal, given the incoming air
condition, with 44°F (6.7°C) chilled water requires either
a very low coil face velocity, 425 fpm (2.2 m/s), or a coil that
does not meet ASHRAE Standard 62.1-2013 standards for
cleanability (8 rows, 12 fpi). For this study, the impact of the
very close approach of coil leaving air temperature to enter-
ing chilled-water temperature has been ignored. Below are
the specifications for the actual air side of the system and
the resultant EER for the system:
• 84°F/69°F (28.9°C/20.6°C) – entering dry-bulb/wet-
bulb temperature;
• 50°F/50°F (10.0°C/10.0°C) – supply air dry-bulb/
wet-bulb temperature;
• 85,500 cfm (40 714 L/s) – supply and return air
volume;
• 126.9 fan bhp (94.6 kW) – total fan horsepower;
• 0.24 kW/ton (0.07 kW/kW) of cooling fan power;
Advertisement formerly in this space.Advertisement formerly in this space.
Advertisement formerly in this space.Advertisement formerly in this space.
A S H R A E J O U R N A L a s h r a e . o r g S E P T E M B E R 2 0 1672
• 0.068 kW/ton (0.019 kW/kW) – condenser fan;
• 0.012 kW/ton (0.003 kW/kW) – circulating pump;
• 0.62 kW/ton (0.18 kW/kW – cooling plant energy;
• 22.2 Btu/Wh (6.50 J/J) – compressor only EER
(6.50 COP); and
• 19.4 Btu/Wh (5.68 J/J) – cooling plant EER
(5.68 COP).
The airside system is considered to be the same perfor-
mance as for the chilled-water system. The actual DX coil
furnished for the system was 8 row, 10 fpi, with a face veloc-
ity of 440 fpm (2.24 m/s), so it is very near the pressure
drop of the coil required for the chilled-water system:
• 84°F/69°F (28.9°C/20.6°C) – entering dry-bulb/wet-
bulb temperature;
• 50°F/50°F (10.0°C/10.0°C) – supply air dry-bulb/
wet-bulb temperature;
• 85,500 cfm (40 714 L/s) – supply and return airflow
• 126.9 fan bhp (94.6 kW) – total fan horsepower;
• 0.24 kW/ton (0.07 kW/kW) of cooling – fan power;
• 0.86 kW/ton (0.25 kW/kW) – total HVAC power; and
• 14.0 Btu/Wh (4.10 J/J) – EER for the system (4.10 COP).
• Integrated supply fan array with twenty-one
16 in. (406 mm) airfoil centrifugal fans, total airflow
85,500 cfm (40,714 L/s); and
• Integrated return fan array with fourteen 20 in.
(508 mm) airfoil centrifugal fans.
Despite the fact that air is supplied at a low tempera-
ture (50°F [10°C]), and is coming onto the coil at a higher
enthalpy than normal, using a direct-expansion coil
with a low face velocity allows this low-temperature
air to be generated with a refrigerant saturated suction
temperature of 44.2°F (6.8°C). A supply air temperature
reset algorithm is installed to maximize airside econo-
mizer utilization for the system.
The higher saturated suction temperature allowed by
the direct-expansion coil results in an efficiency of the
small centrifugal chillers in the packaged system that
approaches or exceeds that of the larger compressors in
the built-up chilled-water plant. Below are the perfor-
mance parameters for the cooling supply section of the
submitted custom packaged DX system:
• 0.54 kW/ton (0.15 kW/kW) – compressor power;
Advertisement formerly in this space.Advertisement formerly in this space.
Advertisement formerly in this space.Advertisement formerly in this space.
A S H R A E J O U R N A L a s h r a e . o r g S E P T E M B E R 2 0 1674
FIGURE 1 Custom penthouse plan.implications for the
occupant’s exit strategy.
A building located in a
large office park, totally
occupied by buildings
with packaged rooftop
units, that requires
additional operating
staff expertise may
be at a disadvantage
when offered for sale or
lease in the real-estate
marketplace.
Studying the pack-
aged option through
the use of a competi-
tive design-assist pro-
curement enabled the
owner to select a very
cost-effective and high
performance alterna-
tive. Table 1 shows a
comparison of the two
systems at full and part
loads, showing that the packaged DX system maintains
its energy efficiency advantage even at low part loads.
The final advantage of the packaged rooftop system
was the reduction in construction cost. Two of these cus-
tom packaged DX rooftop systems were purchased at a
savings of $1,367,300 compared with the chilled-water
plant option for this 292,000 ft2 (27 138 m2) building.
Figure 1 is a plan of the final packaged rooftop design.
While many of the energy-efficiency alternatives included
in this unit were only available at that time in fully cus-
tom packaged units, several options, including inverter-
driven compressors and evaporative condensers, are
now available as standard options on premium packaged
rooftop lines. These new units are competitive with chiller
water systems both for first cost and operating efficiency.
References1. Doty, S. 2001. “Applying DX equipment in humid climates.”
ASHRAE Journal 43(3):30 – 33.2. Taras, M. F. 2004. “Reheat: Which concept is best.” ASHRAE
Journal 46(12):34 – 39.3. ANSI/ASHRAE/IES Standard 90.1-2013, Energy Standard for Build-
ings Except Low-Rise Residential Buildings, Table 6.8.1-1.4. ANSI/ASHRAE/IES Standard 90.1-2013, Energy Standard for Build-
ings Except Low-Rise Residential Buildings, Table 6.8.1-3.5. ANSI/ASHRAE/IES Standard 90.1-2013, Energy Standard for Build-
ings Except Low-Rise Residential Buildings, Table 6.8.1-7.6. ANSI/ASHRAE/IES Standard 90.1-2013, Energy Standard for Build-
ings Except Low-Rise Residential Buildings, Table 11.5.2-1, Note e.
TABLE 1 Full load, part-load and IPLV performance for chilled-water system vs. custom DX penthouse.
CH ILLED WATER ASHRAE STANDARD 90.1-2013AIRSIDE
APPLICATIONDX–
ACTUAL
PART LOAD
CH ILLER (W/TON)
CT FAN (W/TON)
CW PUMP
(W/TON)
CHW PUMP
(W/TON)
FAN (W/TON)
EER EER
100% 585 52 53 44 243 12.3 14.075% 380 39 53 25 176 17.8 18.650% 374 35 24 16 137 20.5 20.925% 386 26 24 11 109 21.6 15.9
IPLV 380 19.4 19.3
ConclusionThe initial reason for the consideration of the custom
packaged direct-expansion air-conditioning units as
an alternative to a built-up chilled-water plant had to
do with the facility staffing for the occupant. A chilled-
water plant would require personnel with more exten-
sive training than would a packaged system, even a cus-
tom packaged system.
Not only would that personnel requirement have budget-
ary implications for the occupant, but it also would have
COLUMN ENGINEER’S NOTEBOOK