Direct expansion close control units with INVERTER technology, from 4 to 160 kW

Transcript of Direct expansion close control units with INVERTER ...€¦ · Direct expansion close control units...

Direct expansion close control units with INVERTER technology, from 4 to 160 kW

5555555555555%%%%%%% 4545%%

40°C27°C

Key Features

The most efficient and reliable solutionfor high precision high conditioning is

5555555555555%%%%%%% 4545%%

40°C27°C

Engineered to the highest standards, i-ACCURATE high precision air conditioners are the key solution for the most critical IT environments.

Precise temperature and humidity control

Complex IT centers are characterized by extremely variable thermal loads, which require very high cooling capacity at full load in order to avoid compromising the correct operation of the IT machines when they are most needed. The massive use of the new INVERTER technology makes it possible to keep temperature and humidity constant even with very strong load variations, preventing dangerous temperature fluctuations which are almost unavoidable with traditional ON/OFF compressors.

High efficiency at partial loads

In today’s data centers, energy consumed by the HVAC plant is increasing rapidly. In systems characterized by 24/7 operation, even the slightest compromise concerning efficiency may lead to dramatic implications for the operating costs of the whole data center. Working efficiently even at partial loads, which are the most frequent operating condition, is key in order to halve overall operating costs.

Thanks to the adoption of DC inverter brushless compressors and the latest generation of EC fans, i-ACCURATE air conditioners can reduce the partial load energy consumption by 50%.

Versatility

i-ACCURATE SMART: beyond traditional operating limits

The many types of structures used as technical areas and the need to optimize their dimensions, require versatile solutions able to adapt to any room, always granting perfect control and highest efficiency.This means complete flexibility, available both for capacities (from 6 to 150 kW Inverter), and plant configuration thanks to 5 different cooling solutions.

The need for higher efficiency levels and reduced TCO values have led to increasing temperatures (up to 27°C) of intake airflows directed to the air conditioners (ASHRAE, ‘Thermal Guidelines for Data Processing Environments’), thus increasing discharge air temperatures.i-ACCURATE SMART is the winning solution, specifically designed to manage environments with 40°C of inlet air temperature. Available both as DUAL FLUID (i-AD / i-AT ) and FREE COOLING ( i-AF ) versions, the SMART configuration optimize the primary water circuit performance even with high temperature fluids.The chiller’s efficiency and the free cooling operation are therefore maximized also whenoutdoor temperatures are high.

Cooling

IT load

Data center energy consumption

-15%

-15%

-25%

-25%

-10%

-10%

Plug

-in

(AC)

EC (D

C)

EC-N

ewge

nera

tion

(DC)

Constant speed

In case of low Hz operations

AC Inverter DC Inverter

100%

55%

30%

Max

70%

Max

70%

4

Technological choices

Efficiency, versatility and reliability

Inverter Technology

The INVERTER technology on the compressor regulates the powercapacity according to the real requirements of the server. The compressor performance at partial loads is therefore optimized, rapidly increasing its efficiency and reducing unit’s consumption.

i-ACCURATE adopts this technology as standardin all its models, with several benefits in terms of: Regulation of the power capacity according to the load requirements No in-rush starting current Energy savings of up to 50% compared to the traditional on/off technology.

Advanced control

i-ACCURATE features smart algorithms that allow for completecontrol of all the unit’s parameters in any condition.

EVOLUTION + control is completely open and can be set according to the specific needs of the customer, either on site or in advance at the time of manufacturing.

-15%

-15%

-25%

-25%

-10%

-10%

Plug

-in

(AC)

EC (D

C)

EC-N

ewge

nera

tion

(DC)

Constant speed

In case of low Hz operations

AC Inverter DC Inverter

100%

55%

30%

Max

70%

Max

70%

5

These are the key drivers that make i-ACCURATE a point of referencein high precision air conditioning. Advantages that come from distinctive technological choices in every aspect of this unit.

EC PUL Inverter fans

Aimed at optimizing energy costs, this modern technology with electronically commutated EC motor increases the overall energy efficiency of the unit through an accurate management of all parameters such as flow rate, power and pressure. The result is the best system operation in any working conditions. Main features: Noise level reduction by 4-5 dB(A) compared to traditional fans Power absorption reduction by 25% compared to traditional fans 2 versions available, BASIC and high pressure HP (optional)

EC fans also in the remote condensers

The use of EC technology even on the remote condenser fan ensures afurther average reduction of noise levels by 10%, together with a strongreduction of energy consumption by 45% compared to traditionalcondensers with AC technology.

Electronic thermostatic valve

The new generation i-ACCURATE comes with electronic expansion valves. These valves ensure optimal operation of the refrigeration cycle in every environmental condition. Main features: Great control and wider modulation capacity Quickly reaches and maintains operating stability Accurate adjustment to load variations

6

360° flexibility as a service offered for any type of system.

COOLING MODES

AIRFLOW CONFIGURATION

Total versatility

OVER

The versions called OVER with air outflow from the top generally have the air intake either at the front, or bottom* of the units, according to the customer’s requirements. The outflow from the top is along ducts behind suspended ceilings or front delivery plenums.

* For back air intake, the installation of a base with grid is necessary.

Airflow: OVER, air discharged from the top,air intake from the rear/bottom of the unit

Airflow: OVER, air dischargedfrom the top, frontal air intake

O.1

Raised floor: absentRoom Height < 3m

Airflow: OVER, air discharged fromthe top, air intake under the floor

O.2

Raised floor > 400 mmRoom Height < 3m

O.3

Raised floor: absentRoom Height < 3m

Airflow: UNDER, air discharged from the bottomunder the floor with air intake from the top

U.1

Raised floor > 400 mmRoom Height < 3m

i-AXO/i-AXUDIRECT EXPANSION AIR-COOLED UNITS, WITH INVERTER COMPRESSOR

In these direct expansion units refrigerant is used for the heat transfer.The air in the room is treated in the evaporating coil and the heat from condensation is released to an outdoor condenser. The condenser features a fan speed controller aimed at optimizing the condensation pressure even in the most adverse temperature conditions.

i-AWO/i-AWU DIRECT EXPANSION WATER COOLED UNITS, WITH INVERTER COMPRESSOR

In these direct expansion units refrigerant is used for the heat transfer.The air in the room is treated in the evaporating coil and the heat from condensation is released by an internal plate type exchanger connected to a water circuit. The condensation water can be extracted from a well, a local water system or by closed circuits such as cooling towers or dry coolers.

7

i-ACCURATE comes with a capacity from 4 to 160 kW both in the air-cooled direct expansion versions (i-AXO / i-AXU) and the water-cooled one (i-AWO / i-AWU), and capacities from 7 to 144 kW in the dual fluid (i-ADO / i-ADU and i-ATO / i-ATU) and free cooling versions (i-AFO / i-AFU).

UNDER

The versions called UNDER with air outflow under the floor have the airintake on the top of the unit, through intake ducts or plenums.

Airflow: OVER, air discharged from the top,air intake from the rear/bottom of the unit

Airflow: OVER, air dischargedfrom the top, frontal air intake

O.1

Raised floor: absentRoom Height < 3m

Airflow: OVER, air discharged fromthe top, air intake under the floor

O.2

Raised floor > 400 mmRoom Height < 3m

O.3

Raised floor: absentRoom Height < 3m

Airflow: UNDER, air discharged from the bottomunder the floor with air intake from the top

U.1

Raised floor > 400 mmRoom Height < 3m

i-ADO/i-ADU - i-ADO SMART/i-ADU SMARTDUAL FLUID INVERTER

These units are provided with dual cooling systems which never work simultaneously.The PRIMARY circuit, made by a chilled water circuit (CW), is generally connected to an external chiller, whereas the SECONDARY direct expansion circuit (DX) is for BACK-UP. Such units are particularly indicated anywhere RELIABILITY, SAFETY and REDUNDANCY are key.

i-ATO/i-ATU - i-ATO SMART/i-ATU SMARTDUAL FLUID INVERTER

These units are provided with two cooling systems which never work simultaneously.The PRIMARY circuit, made by a chilled water circuit (CW), is generally connected to an external chiller, whereas the SECONDARY direct expansion circuit (DX) is for BACK-UP.Such units are particularly indicated anywhere RELIABILITY, SAFETY and REDUNDANCY are key.

i-AFO/i-AFU - i-AFO SMART/i-AFU SMARTFREE COOLING INVERTER

These units are provided with two cooling systems which are often working simultaneously during the year.The PRIMARY direct expansion circuit (DX) is combined with a SECONDARY chilled water circuit (CW) which is generally connected to an external dry cooler.Such units are particularly indicated anywhere EFFICIENCY & ENERGY SAVINGS are key.

8

Range overview

9

Air cooled direct expansion unit, with R410Arefrigerant and DC inverter driven compressor.From 4 to 151 kW.

NOTES1) Air IN 24°C-50%, cond. water temperature 45°C - ESP 20Pa5) Measured at 1,5m height, 2m in front of the unit in free field

The units highlighted in this publication contain HFC R410A [GWP100 1975] fluorinated greenhouse gases.

Model 12 18 20 29 50 70 90 130 150Frame F2 F3 F4 F5 F6 F7No. Circuits/ No. Compressors 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/3 2/3Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410ANominal air flow mc/h 3500 4900 6500 8000 13500 19000 25000 30000 30000Power supply V/Ph/Hz 230/1/50 400/3N/50PERFORMANCEHigh speedTotal cooling capacity (1) kW 11,1 16,60 19,32 28,07 55,00 70,20 86,50 135,9 151,8Sensible cooling capacity (1) kW 10,6 16,60 19,32 28,07 51,10 68,10 85,50 116,2 124,1SHR (1) 0,95 1,00 1,00 1,00 0,93 0,97 0,99 0,86 0,82Compressors absorbed power kW 2,54 4,09 4,25 7,14 13,20 15,80 20,30 30,80 35,00EC radial fans power abs. kW 0,35 0,84 1,35 1,80 3,20 4,5 6,1 - -HP EC radial fans power abs. kW 0,27 0,47 0,80 1,51 3,13 5,11 6,72 6,90 6,90Low speedTotal cooling capacity (1) kW 4,3 6,3 7,2 10,6 25,4 23,6 24,3 24,7 24,7Sensible cooling capacity (1) kW 4,3 6,3 7,2 10,6 25,4 23,6 24,3 24,7 24,7SHR (1) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00 1,00Compressors absorbed power kW 0,88 1,24 1,33 1,96 4,31 4,40 4,30 4,60 4,60

VENTILATIONNo. EC radial fans 2 2 1 1 2 3 3 - -No. HP EC radial fans 2 2 1 1 2 3 4 3 3Sound pressure level (5) dB(A) 49 53 60 60 64 67 67 69 69HUMIDIFIERCapacity kg/h 3 5 5 5 5 8 8 8 8ELECTRICAL HEATERSSteps 3 3 3 3 3 3 3 3 3Heating Capacity kW 4 8 9 9 15 18 18 18 18DIMENSIONSLength mm 1000 1000 1000 1550 2100 2650 2650Depth mm 500 790 790 790 790 790 890Height mm 1980 1980 1980 1980 1980 1980 2180

Configurations:BASIC - For applications up to 32°C intake air

10

Range overview

Water cooled direct expansion unit, with R410Arefrigerant and DC inverter driven compressor.From 5 to 160 kW.

NOTES 1) Air IN 24°C-50%, cond. water temperature 30- 35°C - ESP 20Pa5) Measured at 1,5m height, 2m in front of the unit in free field

The units highlighted in this publication contain HFC R410A [GWP100 1975] fluorinated greenhouse gases.

Model 12 18 20 29 50 70 90 130 150Frame F2 F3 F4 F5 F6 F7No. Circuits/ No. Compressors 1/1 1/1 1/1 1/1 1/1 2/2 2/2 2/3 2/3Refrigerant R410A R410A R410A R410A R410A R410A R410A R410A R410ANominal air flow mc/h 3500 4900 6500 8000 13500 19000 25000 30000 30000Power supply V/Ph/Hz 230/1/50 400/3N/50PERFORMANCEHigh speedTotal cooling capacity (1) kW 11,7 17,4 20,46 29,3 56,72 73,90 93,30 142,5 159,1Sensible cooling capacity (1) kW 10,9 17 20,41 28,6 51,52 70,20 90,50 118,9 127,6SHR (1) 0,93 0,98 1,00 0,98 0,91 0,95 0,97 0,83 0,80Compressors absorbed power kW 2,12 3,68 3,70 6,38 12,08 13,60 18,60 27,60 31,70EC radial fans power abs. kW 0,35 0,84 1,35 1,80 3,20 4,5 6,1 - -HP EC radial fans power abs. kW 0,27 0,47 0,80 1,51 3,13 5,11 6,72 6,90 6,90Low speedTotal cooling capacity (1) kW 4,8 7,3 7,9 12,3 27,3 25,3 27,9 27,5 27,5Sensible cooling capacity (1) kW 4,8 7,3 7,9 12,3 27,3 25,3 27,9 26,7 26,7SHR (1) 1,00 1,00 1,00 1,00 1,00 1,00 1,00 0,97 0,97Compressors absorbed power kW 0,61 1,24 1,11 1,96 3,20 3,30 3,00 3,30 3,30

VENTILATIONNo. EC radial fans 2 2 1 1 2 3 3 - -No. HP EC radial fans 2 2 1 1 2 3 4 3 3Sound pressure level (5) dB(A) 49 53 60 60 64 67 67 69 69HUMIDIFIERCapacity kg/h 3 5 5 5 5 8 8 8 8ELECTRICAL HEATERSSteps 3 3 3 3 3 3 3 3 3Heating Capacity kW 4 8 9 9 15 18 18 18 18DIMENSIONSLength mm 1000 1000 1000 1550 2100 2650 2650Depth mm 500 790 790 790 790 790 890Height mm 1980 1980 1980 1980 1980 1980 2180

Configurations:BASIC - For applications up to 32°C intake air

COOLING

r HFCR-410A

SCROLL

11

Water cooled unit with free cooling, R410Arefrigerant and DC inverter driven compressor.From 7 to 144 kW.

NOTES 1) Air IN 24°C/50%, cond. water temperature 30-35°C - ESP 20Pa2) Air IN 24°C/50%, water IN 10°C water flow as DX mode - ESP 20Pa3) Air IN 35°C/30%, cond. water temperature 30-35°C - ESP 20Pa

4) Air IN 35°C/30%, water IN 10°C water flow as DX mode - ESP 20Pa5) Measured at 1,5m height, 2m in front of the unit in free field

The units highlighted in this publication contain HFC R410A [GWP100 1975] fluorinated greenhouse gases.

Model 20 29 50 70 90 130Frame F3 F4 F5 F6 F7No. Circuits/ No. Compressors 1/1 1/1 2/2 2/2 2/3Refrigerant R410A R410A R410A R410A R410A R410ANominal air flow mc/h 6500 8000 13500 19000 25000 28000Power supply V/Ph/Hz 400/3N/50BASIC CONFIGURATIONDX PERFORMANCEHigh speedTotal cooling capacity (1) kW 19,4 28,6 55,1 73,0 94,4 130,0Sensible cooling capacity (1) kW 19,4 28,4 51,0 69,2 87,2 111,0SHR (1) 1,00 0,99 0,93 0,95 0,92 0,85Compressors absorbed power kW 4,0 6,2 12,2 13,8 19,1 27,4EC radial fans power abs. kW 1,35 1,80 3,20 4,50 6,10 -HP EC radial fans power abs. kW 0,89 1,51 3,13 5,11 6,72 6,90Low speedTotal cooling capacity (1) kW 7,8 12,4 24,6 22,7 24,4 26,1Sensible cooling capacity (1) kW 7,8 12,4 24,6 22,7 22,5 25,6SHR (1) 1,00 1,00 1,00 1,00 0,92 0,98Compressors absorbed power kW 1,00 1,49 3,30 3,40 3,40 3,30PERFORMANCE IN FREE-COOLINGTotal cooling capacity (2) kW 19,6 24,3 43,6 58,1 78,1 94,1Sensible cooling capacity (2) kW 19,6 24,3 43,6 58,1 78,1 94,1SHR 0,97 1,00 1,00 1,00 1,00 0,99Pressure drop with FC operation kPa 36 66 123 122 137 132SMART CONFIGURATIONDX PERFORMANCEHigh speedTotal cooling capacity (3) kW 24,6 33,1 65,6 98,3 119,3 143,9Sensible cooling capacity (3) kW 24,6 33,1 65,6 98,3 118,8 142,9SHR (3) 1,00 1,00 1,00 1,00 1,00 0,99Compressors absorbed power kW 3,6 6,9 13,7 20,6 23,5 27,0EC radial fans power abs. kW 1,35 1,80 3,20 4,50 6,10 -HP EC radial fans power abs. kW 0,89 1,51 3,13 5,11 6,72 6,90Low speedTotal cooling capacity (1) kW 10,2 14,9 27,3 28,0 29,5 29,1Sensible cooling capacity (1) kW 10,2 14,9 27,3 28,0 29,4 28,9SHR (1) 1,00 1,00 1,00 1,00 0,99 0,99Compressors absorbed power kW 1,0 1,6 3,6 3,4 3,4 3,3PERFORMANCE IN FREE-COOLINGTotal cooling capacity (4) kW 40,2 49,2 88,5 119,5 157,1 161,3Sensible cooling capacity (4) kW 39,8 48,5 84,7 114,2 150,9 158,4SHR 0,99 0,98 0,96 0,96 0,96 0,98Pressure drop with FC operation kPa 46 52 71 81 77 105

VENTILATIONNo. EC radial fans 1 1 2 3 3 -No. HP EC radial fans 1 1 2 3 4 3Sound pressure level (5) dB(A) 56 60 64 67 67 69HUMIDIFIERCapacity kg/h 5 5 5 8 8 8ELECTRICAL HEATERSSteps 3 3 3 3 3 3Heating Capacity kW 9 9 15 18 18 24DIMENSIONSLength mm 1000 1000 1550 2100 2650 2650Depth mm 790 790 790 790 790 890Height mm 1980 1980 1980 1980 1980 2180

Configurations:BASIC - For applications up to 32°C intake air

SMART - For applications up to 40°C intake air

12

Range overview

NOTES1) Air IN 24°C/50%, cond. water temperature 30-35°C - ESP 20Pa2) Air IN 24°C/50%, water temperature 7-12°C - ESP 20Pa3) Air IN 35°C/30%, cond. water temperature 30-35°C - ESP 20Pa

4) Air IN 35°C/30%, water temperature 12-18°C - ESP 20Pa5) Measured at 1,5m height, 2m in front of the unit in free field

The units highlighted in this publication contain HFC R410A [GWP100 1975] fluorinated greenhouse gases.

Air cooled direct expansion dual fluid unit, with R410A refrigerant and DC inverter driven compressor.From 7 to 138 kW.

Configurations:BASIC - For applications up to 32°C intake air

SMART - For applications up to 40°C intake air

Model 20 29 50 70 90 130Frame F3 F4 F5 F6 F7No. Circuits/ No. Compressors 1/1 1/1 2/2 2/2 2/3Refrigerant R410A R410A R410A R410A R410A R410ANominal air flow mc/h 6500 8000 13500 19000 25000 28000Power supply V/Ph/Hz 400/3N/50BASIC CONFIGURATIONDX PERFORMANCEHigh speedTotal cooling capacity (1) kW 18,9 27,5 53,2 69,1 91,4 124,4Sensible cooling capacity (1) kW 18,9 27,5 50,2 67,4 86,0 108,7SHR (1) 1,00 1,00 0,94 0,98 0,94 0,87Compressors absorbed power kW 4,26 6,83 13,40 16,10 20,90 30,80EC radial fans power abs. kW 1,35 1,80 3,20 4,50 6,10 -HP EC radial fans power abs. kW 0,89 1,51 3,13 5,11 6,72 6,90Low speedTotal cooling capacity (1) kW 7,2 11,3 22,7 20,9 22,5 23,9Sensible cooling capacity (1) kW 7,2 11,3 22,7 18,8 21,7 23,9SHR (1) 1,00 1,00 1,00 0,90 0,96 1,00Compressors absorbed power kW 1,28 2,05 4,47 4,52 4,43 4,58CW PERFORMANCETotal cooling capacity (2) kW 24,3 29,5 51,4 67,6 91,0 126,0Sensible cooling capacity (2) kW 20,1 27,6 47,5 64,5 85,0 98,5SHR 0,97 1,00 1,00 1,00 1,00 0,99Pressure drop with FC operation kPa 29 48 55 60 58 68SMART CONFIGURATIONDX PERFORMANCEHigh speedTotal cooling capacity (3) kW 23,7 33,1 63,8 95,2 117,0 138,2Sensible cooling capacity (3) kW 23,7 33,1 63,8 95,2 116,5 137,1SHR (3) 1,00 1,00 1,00 1,00 1,00 0,99Compressors absorbed power kW 4,1 6,8 15,1 23,0 25,1 30,8EC radial fans power abs. kW 1,35 1,80 3,20 4,50 6,10 -HP EC radial fans power abs. kW 0,89 1,51 3,13 5,11 6,72 6,90Low speedTotal cooling capacity (1) kW 9,3 14,1 25,1 25,4 26,7 26,2Sensible cooling capacity (1) kW 9,3 14,1 25,1 25,4 26,5 26,1SHR (1) 1,00 1,00 1,00 1,00 1,00 0,99Compressors absorbed power kW 1,2 2,0 4,5 4,5 4,5 4,5CW PERFORMANCETotal cooling capacity (4) kW 39,7 47,0 82,3 111,4 146,4 150,6Sensible cooling capacity (4) kW 39,7 47,0 82,3 111,4 146,4 150,6SHR 1,00 1,00 1,00 1,00 1,00 1,00Pressure drop with FC operation kPa 56 76 69 57 57 61

VENTILATIONNo. EC radial fans 1 1 2 3 3 -No. HP EC radial fans 1 1 2 3 4 3Sound pressure level (5) dB(A) 56 60 64 67 67 69HUMIDIFIERCapacity kg/h 5 5 5 8 8 8ELECTRICAL HEATERSSteps 3 3 3 3 3 3Heating Capacity kW 9 9 15 18 18 24DIMENSIONSLength mm 1000 1000 1550 2100 2650 2650Depth mm 790 790 790 790 790 890Height mm 1980 1980 1980 1980 1980 2180

13

Water cooled direct expansion dual fluid unit, with R410A refrigerant and DC inverter driven compressor. From 7 to 144 kW.

NOTES1) Air IN 24°C/50%, cond. water temperature 30-35°C - ESP 20Pa2) Air IN 24°C/50%, water temperature 7-12°C - ESP 20Pa3) Air IN 35°C/30%, cond. water temperature 30-35°C - ESP 20Pa

4) Air IN 35°C/30%, water temperature 12-18°C - ESP 20Pa5) Measured at 1,5m height, 2m in front of the unit in free field

The units highlighted in this publication contain HFC R410A [GWP100 1975] fluorinated greenhouse gases.

Model 20 29 50 70 90 130Frame F3 F4 F5 F6 F7No. Circuits/ No. Compressors 1/1 1/1 2/2 2/2 2/3Refrigerant R410A R410A R410A R410A R410A R410ANominal air flow mc/h 6500 8000 13500 19000 25000 28000Power supply V/Ph/Hz 400/3N/50BASIC CONFIGURATIONDX PERFORMANCEHigh speedTotal cooling capacity (1) kW 19,4 28,6 55,1 72,9 94,5 130,0Sensible cooling capacity (1) kW 19,4 28,4 51,0 69,2 87,1 111,0SHR (1) 1,00 0,99 0,93 0,95 0,92 0,85Compressors absorbed power kW 4,0 6,2 12,2 13,8 19,1 27,4EC radial fans power abs. kW 1,35 1,80 3,20 4,50 6,10 -HP EC radial fans power abs. kW 0,89 1,51 3,13 5,11 6,72 6,90Low speedTotal cooling capacity (1) kW 7,8 12,4 24,6 22,7 24,4 26,1Sensible cooling capacity (1) kW 7,8 12,4 24,6 22,7 22,5 25,6SHR (1) 1,00 1,00 1,00 1,00 0,92 0,98Compressors absorbed power kW 1,00 1,49 3,30 3,40 3,40 3,30CW PERFORMANCETotal cooling capacity (2) kW 24,3 29,5 51,4 67,6 91,0 126,0Sensible cooling capacity (2) kW 20,1 27,6 47,5 64,5 85,0 98,5SHR 0,83 0,94 0,92 0,95 0,93 0,78Pressure drop with FC operation kPa 29 48 55 60 58 68SMART CONFIGURATIONDX PERFORMANCEHigh speedTotal cooling capacity (3) kW 24,6 33,1 65,6 98,3 119,3 143,9Sensible cooling capacity (3) kW 24,6 33,1 65,6 98,3 118,8 142,9SHR (3) 1,00 1,00 1,00 1,00 1,00 0,99Compressors absorbed power kW 3,6 6,9 13,7 20,6 23,5 27,0EC radial fans power abs. kW 1,35 1,80 3,20 4,50 6,10 -HP EC radial fans power abs. kW 0,89 1,51 3,13 5,11 6,72 6,90Low speedTotal cooling capacity (1) kW 10,2 14,9 27,3 28,0 29,5 29,1Sensible cooling capacity (1) kW 10,2 14,9 27,3 28,0 29,4 28,9SHR (1) 1,00 1,00 1,00 1,00 1,00 0,99Compressors absorbed power kW 1,0 1,6 3,6 3,4 3,4 3,3CW PERFORMANCETotal cooling capacity (4) kW 39,7 47,0 82,3 111,4 146,4 150,6Sensible cooling capacity (4) kW 39,7 47,0 82,3 111,4 146,4 150,6SHR 1,00 1,00 1,00 1,00 1,00 1,00Pressure drop with FC operation kPa 56 76 69 57 57 61

VENTILATIONNo. EC radial fans 1 1 2 3 3 -No. HP EC radial fans 1 1 2 3 4 3Sound pressure level (5) dB(A) 56 60 64 67 67 69HUMIDIFIERCapacity kg/h 5 5 5 8 8 8ELECTRICAL HEATERSSteps 3 3 3 3 3 3Heating Capacity kW 9 9 15 18 18 24DIMENSIONSLength mm 1000 1000 1550 2100 2650 2650Depth mm 790 790 790 790 790 890Height mm 1980 1980 1980 1980 1980 2180

Configurations:BASIC - For applications up to 32°C intake air

SMART - For applications up to 40°C intake air

CNES - Centre National d'Etudes SpatialesSaint Denis - France

Data centerCooling capacity: 432 kWInstalled machines: 12x CRCC-I 0036 rack cooler units, 1x FOCS-W R 0802, 4x AC close control units Installer: Eiffage Energie Thermie

Range International Information GroupData CenterLangsfang - China

Data centerTotal cooling capacity: 12700 kWInstalled units: 24x AC 221,18x AC 25, 5x air cooled chillers

Nuovo PignoneFlorence - Italy

Data centerCooling capacity: 400 kWInstalled machines:5x i-AX, 4x CRCX-I, 4x i-HCAT

MegacenterMedellin - Colombia

Data centerCooling capacity: 1330 kWInstalled machines:10x i-AX Close Control Units

Bouygues Telecom Several applications in France

Financial institutionsCooling capacity: 433,9 kWInstalled machines: 2x i-AX 18, 15x i-AX 29

Vodafone DatacenterPadua - Italy

Data centerCooling capacity: 968 kWInstalled machines: 2x NX/LN-KS,6x AC close control units

E-tv HeadquartersCape Town - South Africa

Data centerCooling capacity: 1870 kWInstalled machines:2x NECS-D/SL, 6x i-AF,1x MANAGER 3000

Alcatel Data centerBergamo - Italy

Data centerCooling capacity: 3570 kWInstalled machines:2x AC 30, 3x AC 60, 34x AC 90,2x AX 50, 5x AX 55, 2x i-AX 29

CCBChina Construction BankData CenterBeijing - China

Data centerCooling capacity: 70000 kWInstalled machines:48x free-cooling chillers,4x heat pumps

BNP ParibasBailly Romainvilliers - France

Financial institutionsCooling capacity: 12208 kWInstalled machines:2x FX-FC NG 3902 SL-T,10x FOCS2 3602 SL-K-S,8x ACU 25 EC, 4x ACU 30 EC,8x ACU 70 EC, 8x ACU 171 EC

“ By far the best proof is experience” Sir Francis Bacon

British Philosopher (1561-1626)

CNES - Centre National d'Etudes SpatialesSaint Denis - France

Data centerCooling capacity: 432 kWInstalled machines: 12x CRCC-I 0036 rack cooler units, 1x FOCS-W R 0802, 4x AC close control units Installer: Eiffage Energie Thermie

Range International Information GroupData CenterLangsfang - China

Data centerTotal cooling capacity: 12700 kWInstalled units: 24x AC 221,18x AC 25, 5x air cooled chillers

Nuovo PignoneFlorence - Italy

Data centerCooling capacity: 400 kWInstalled machines:5x i-AX, 4x CRCX-I, 4x i-HCAT

MegacenterMedellin - Colombia

Data centerCooling capacity: 1330 kWInstalled machines:10x i-AX Close Control Units

Bouygues Telecom Several applications in France

Financial institutionsCooling capacity: 433,9 kWInstalled machines: 2x i-AX 18, 15x i-AX 29

Vodafone DatacenterPadua - Italy

Data centerCooling capacity: 968 kWInstalled machines: 2x NX/LN-KS,6x AC close control units

E-tv HeadquartersCape Town - South Africa

Data centerCooling capacity: 1870 kWInstalled machines:2x NECS-D/SL, 6x i-AF,1x MANAGER 3000

Alcatel Data centerBergamo - Italy

Data centerCooling capacity: 3570 kWInstalled machines:2x AC 30, 3x AC 60, 34x AC 90,2x AX 50, 5x AX 55, 2x i-AX 29

CCBChina Construction BankData CenterBeijing - China

Data centerCooling capacity: 70000 kWInstalled machines:48x free-cooling chillers,4x heat pumps

BNP ParibasBailly Romainvilliers - France

Financial institutionsCooling capacity: 12208 kWInstalled machines:2x FX-FC NG 3902 SL-T,10x FOCS2 3602 SL-K-S,8x ACU 25 EC, 4x ACU 30 EC,8x ACU 70 EC, 8x ACU 171 EC

All around the world, in the most important datacenters, and in all projects where efficiency,quality and reliability are key drivers, Climaveneta high precision air conditioners are the best guarantee.