Page 1: DIGITAL POWER FACTOR CONTROLLERS - RTR · PDF fileDIGITAL POWER FACTOR CONTROLLERS PR-5D & PR-6D SERIES-2-VERSIONS • PR5D - 5 steps, 96x96mm housing • PR5D - 7 steps, 96x96mm housing
Page 2: DIGITAL POWER FACTOR CONTROLLERS - RTR · PDF fileDIGITAL POWER FACTOR CONTROLLERS PR-5D & PR-6D SERIES-2-VERSIONS • PR5D - 5 steps, 96x96mm housing • PR5D - 7 steps, 96x96mm housing

DIGITAL POWER FACTOR CONTROLLERSPR-5D & PR-6D SERIES

-2-

VERSIONS• PR5D - 5 steps, 96x96mm housing• PR5D - 7 steps, 96x96mm housing• PR6D - 8 steps, 144x144mm housing• PR-6D - 12steps, 144x144mm housing

DESCRIPTION• Digital microprocessor power factor controller.• 3 digit 7 segment LED display.• 4 key membrane keypad.• TTL-RS232 serial interface for set-up and automatic testing via PC (Personal Computer). • Internal temperature sensor.

INSTALLATION• Install the controller according to wiring diagrams given on the last pages of this instruction manual.• The CT (Current Transformer) must be connected to the free phase to supply the unit as indicated in the

wiring diagrams.• The controller automatically recognizes the TC current flow. In case of co-generation systems contact withour technical department.

• The CT secondary must be earthed/grounded.

CONNECTIONS CONTROL• At the first power up, the DCRK display views which means no parameter has been programmed yet.

(Only for separate sale of the device).• In these conditions, a manual test of the steps can be conducted to check the connections.• By pressing the or key, the step are connected or disconnected. • CAUTION! During this phase, the step control is totally manual and the unit does not control the reconnec-

tion time to consent the capacitor discharge.

PARAMETER SET-UPThere are a two different ways to set up the parameters and commission the controller to operate properly, as

follows:1. Automatic set-up2. Manual keypad set-up

1. AUTOMATIC SET-UPThe automatic set-up of parameters provides for the unit to be set working without programming any parame-

ter.• To activate the automatic set-up, simultaneously press the MODE and MAN/AUT keys for at least 5 seconds.• The wording (Automatic Setup flashes indicating the automatic setup of the parameters, has beenimplemented.

• The procedure will last a few minutes during which the controller measures the power rating of the connec-ted step. This measurement will then be continuously updated during the normal operation.• If the load of the system varies frequently, the same step may have to be measured several times. In this case, the procedure may last longer.• At the end of the automatic set-up, the controller is restored for automatic operation.Important!It is recommended to avoid substantial current variations during the automatic set-up as much as possible.

During this automatic set-up, the controller does not intentionally have particular elements, such as:- The current is viewed as a percentage instead of Ampere value.- The ∆kvar and Σkvar measurements are not available.- The measurement and protection for capacitor overload are not accessible.- All of the relays are considered as normal capacitors banks. So no alarm relay or fan control configurationis possible.

- The capacitors installed must be with a power ratings multiple of 1, 2, 4, 8 or 16 times the smallest capaci-tor step.

- The unused step must be positioned at the higher step numbers.

- - -

ASE

Page 3: DIGITAL POWER FACTOR CONTROLLERS - RTR · PDF fileDIGITAL POWER FACTOR CONTROLLERS PR-5D & PR-6D SERIES-2-VERSIONS • PR5D - 5 steps, 96x96mm housing • PR5D - 7 steps, 96x96mm housing

-3-

Note: After the automatic set-up is terminated, by manually changing the setting of parameters, the controllerwill implement all the parameter programming. Therefore, all of the measurements and functions will be availa-ble once again.

2. MANUAL KEYPAD SET-UP.• Place the unit in manual mode and press the MODE key for 5 consecutive seconds.• The wording is viewed on the display to confirm access to the basic menu parameters.• Press the MAN/AUT key to enter the subsequent parameter.• Press the MODE key to return to the previous parameter.• Press the and keys to view and change the setting of the selected parameter. If no key is pressed for

a few seconds, the selected parameter is displayed once again.• The setup exit is automatic once the last parameter is exceeded.

TABLE OF BASIC MENU PARAMETERS

(1) n = Number of controller steps.noA= Normally open contact in no alarm conditions.ncA= See Measurement and cos ϕ setting section on page 5.

DESCRIPTION OF BASIC MENU PARAMETERSP.01- CT PrimaryCT primary current. For values higher than 1000, a flashing dot indicates "thousands".

P.02- Smallest kvar step Rated power in kvar of the smallest installed capacitor bank.Example: For 10 kvar, set

P.03- Rated capacitor voltage Rated voltage (nameplate) of the capacitors.Example: For 440V, set

P.04- Reconnection time Minimum time needed for the capacitor to discharge and be ready to used again. Example: For 15 seconds, set

SET

IO . 0

015

440

Program Function Range Default

P.01 CT Primary Off ...10.000

Off

P.02 Smallest kvar step 0.10 ...300 1.00

P. 03 Rated capacitorvoltage 80 ... 750 V 400 V

P.04 Reconnection time 5 ... 240sec. 15 sec.

P.05 Sensitivity 5 ... 600sec. 15 sec.

P.06¤ 1 Step 1 coefficient 0 ... 16 0

P.06¤ 2 Step 2 coefficient 0... 16 0

... ... ... ...

P.06¤ n-1

(1)Step n-1 coefficient

0 ... 16noAncAFan

0

P.06¤ n(1)

Step n° coefficient

0 ... 16noAncAFan

0

Setting of required cosϕϕvalue (2)

0.80 Ind ..0.80 Cap

1 Ind

DIGITAL POWER FACTOR CONTROLLERSPR-5D & PR-6D SERIES

Page 4: DIGITAL POWER FACTOR CONTROLLERS - RTR · PDF fileDIGITAL POWER FACTOR CONTROLLERS PR-5D & PR-6D SERIES-2-VERSIONS • PR5D - 5 steps, 96x96mm housing • PR5D - 7 steps, 96x96mm housing

P.05- SensitivityThe sensitivity is a coefficient, which consents to adjust the controller tripping speed. A low sensitivity provi-

des for faster adjustments but with a greater number of switchings. With high sensitivity, the adjustment is slo-wer but with fewer switchings.

The sensitivity value corresponds to the time in which the controller is delayed before taking action to a reac-tive power demand equivalent to the smallest step. For higher power demands, the time will be quicker accor-ding to the criteria of inverse proportion.

Example: For 60 s/step, set In this case with the smallest bank of 10kvar (P.02 = 10.0) and a system demanding 20kvar to achieve the set

cosphi (?kvar = 20), the controller will attend 60/2 = 30 seconds before beginning the capacitor connection pro-cedure (indicated by the flashing AUT LED).

P.06- ¤ 1...n Step coefficientsThe coefficients of the steps represent the power of each step in relation to the smallest capacitor bank, which

value is programmed at P.02. If a step has the same power rating of the smallest step, then its coefficient will be1, while if it is double it will be 2 and so on up to a maximum of 16. By setting 0, the step will be disabled andwill never be considered or used by the controller.

The last two steps can be programmed to operate as normal steps or as alarm relay or again as fan control. If the second last step is linked to a function then the last step cannot be used as a normal step.To select these functions, press until the following codes are viewed:

= Normally open alarm (contact open in absence of alarm).= Normally closed alarm (contact closed in absence of alarm).= Fan control.

N.B. For the alarms, see table on page 10.For fan control, refer to pages 7 and 9.

Example: With a DCRK7 installed in a control panel with 6 capacitor banks, respectively 5, 10, 20, 20, 20, 20kvar at rated 440V and needing to use the last step as alarm, the parameters must be programmed as follows:

P.02 = 5.00 (Smallest step = 5kvar)P.03 = 440 (Rated voltage 440V)P.06¤ 1= 001 (5 kvar = 1 times P.02)P.06¤ 2= 002 (10 kvar = 2 times P.02)P.06¤ 3= 004 (20 kvar = 4 times P.02)P.06¤ 4= 004 (20 kvar = 4 times P.02)P.06¤ 5= 004 (20 kvar = 4 times P.02)P.06¤ 6= 004 (20 kvar = 4 times P.02)P.06¤ 7= nO A (Normally open alarm)

MEASUREMENT VIEWING AND REQUIRED COSPHI SETTINGNormally, the display shows the cosphi of the system together with the IND and CAP LEDs. The flashing deci-

mal point indicates the negative sign (inverse energy flow).

• By pressing the MODE key, the V, A, ∆kvar, etc. LEDs are switched on one after another and the relativemeasurement of each is viewed.

• An optional function is available for each LED and indicated on front viewable by pressing the key; theLED flashes quickly thereafter.

• For some measurements, a second optional function is displayable by pressing the key.

• When the SET COSϕϕ LED switches on, the set-point of the required cosphi can be programmed; the andkeys respectively increase or decrease the value. The set cosphi can be adjusted between 0.80 IND and

0.80 CAP.

The following table summarises all the available measurements.

DIGITAL POWER FACTOR CONTROLLERSPR-5D & PR-6D SERIES

-4-

no A

060

nC AFAN

Page 5: DIGITAL POWER FACTOR CONTROLLERS - RTR · PDF fileDIGITAL POWER FACTOR CONTROLLERS PR-5D & PR-6D SERIES-2-VERSIONS • PR5D - 5 steps, 96x96mm housing • PR5D - 7 steps, 96x96mm housing

TABLE OF INDICATIONS

(1) This PF (Power Factor) value is determined byactive and reactive energy meters of the last 7 daysand referred to positive energy quadrants only.

(2) Overload current caused by harmonic voltageat the capacitor terminals.

(3) Caution! The temperature measurement isconsidered valid after a period of 20-30 minutesafter power up.

ALARMS

• When the controller detects an abnormal situation in the system, a flashing alarm code is displayed. By pres-sing any key, the alarm viewing will be momentarily ignored to permit the user to check all the measurements.If no key is pushed for 30 seconds and the alarm conditions persist, the alarm code will be displayed once again.

• Each alarm can cause diverse results such as the alarm relay tripping, the delayed or immediate step dis-connection, etc., according to the programmed property.

• The property of each alarm can be changed (e.g. disabled, change the delay time or result), by using a PCand the relative software (order code DCRK SW), used for the quick parameter set-up.

Note: None of the above-indicated alarms are non-volatile.

DIGITAL POWER FACTOR CONTROLLERSPR-5D & PR-6D SERIES

-5-

Led FunctionPressing Pressing

V RMS Voltage MAX voltagevalue

A RMS current MAX currentvalue

∆∆kvar kvar required toreach set-point

Σkvar(system kvar)

Steps requiredto achieve theset-point

Week F.P.

Average weeklypower factor (1)

Real powerfactor

CURR%

Capacitor overlo-ad % (2)

MAX overloadvalue

Overloadevent counter

TEMPElectric panel tem-perature (3)

MAX tempera-ture value

Unit of mea-sure °C or °F

SETCOS ϕϕ Required cosϕ Decrease SET

COSφ valueIncrease SETCOSf value

AlarmCode Description Enabling Alarm relay Disconnection Tripping

delay

A01 Under compensation • • 15 min.

A02 Over compensation • 120 s

A03 Low current • • 5 s

A04 High current • 120 s

A05 Low voltage • • 5 s

A06 High voltage • • 15 min.

A07 Capacitor overload • • • 180 s

A08 Overtemperature • • • 30 s

A09 No-voltage release • • 0 s

Page 6: DIGITAL POWER FACTOR CONTROLLERS - RTR · PDF fileDIGITAL POWER FACTOR CONTROLLERS PR-5D & PR-6D SERIES-2-VERSIONS • PR5D - 5 steps, 96x96mm housing • PR5D - 7 steps, 96x96mm housing

DIGITAL POWER FACTOR CONTROLLERSPR-5D & PR-6D SERIES

-6-

ALARM DESCRIPTION

A01 - Under compensationCapacitors are all connected and cosphi is lower than the set-point value.

A02 - Over compensationAll capacitors are disconnected and cosphi is higher than the set-point value.

A03 - Low currentCurrent value is 2.5% lower than end-scale value. in automatic, the capacitors are disconnected after 2 minu-

tes of the alarm activation.

A04 - High currentCurrent value is 120% higher than end scale value.

A05 - Low voltageVoltage value is -15% lower than the inferior rated voltage.

A06 - High voltageVoltage value is +10% higher than superior rated voltage.

A07 - Capacitor overloadCurrent value flowing in the capacitors is higher than the set threshold.

A08 - OvertemperatureInternal temperature value is higher than the set threshold .

A09 - No-voltage releaseVoltage shortage duration is more than 8ms.

TECHNICAL CHARACTERISTICS PR-5D5 PR-5D7 PR-6D8 PR-6D12

Auxiliary supply

• Rated voltage Ue . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 380...415 VAC (other values on request)• Operating limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .-15%...+10% Ue• Rated frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 o 60 Hz +1% (self configurable)• Maximum consumption . . . . . . . . . . . . . . . .6,2 VA . . . . . . . .6,2 VA . . . . . . . . .5 VA . . . . . . . . .5 VA• Maximum dissipation . . . . . . . . . . . . . . . . . .2,7 W . . . . . . . . .2,7 W . . . . . . . . .3 W . . . . . . . . . .3 W• Maximum power dissipated

by output contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0,5 W con 5A• Immunity time for microbreakings . . . . . . . . . . . . . . . . . . . . .< 30 ms• No-voltage release . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .> 8 ms

Current input

• Rated current Ie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 A (1A on request)• Operating limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0,125...6A• Constant overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .+20%• Type of measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .True RMS• Short time withstand current . . . . . . . . . . . . . . . . . . . . . . . . .10 Ie for 1 seg.• Dynamic limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 Ie for 10 ms• Input power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0,65W

Page 7: DIGITAL POWER FACTOR CONTROLLERS - RTR · PDF fileDIGITAL POWER FACTOR CONTROLLERS PR-5D & PR-6D SERIES-2-VERSIONS • PR5D - 5 steps, 96x96mm housing • PR5D - 7 steps, 96x96mm housing

DIGITAL POWER FACTOR CONTROLLERSPR-5D & PR-6D SERIES

-7-

TECHNICAL CHARACTERISTICS PR-5D5 PR-5D7 PR-6D8 PR-6D12

Control range

• Power factor setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.8 IND...0.80 CAP• Reconnection time of the same step . . . . . . . . . . . . . . . . . . .5... 240 seconds.• Sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5... 600 sec./step

Output relay

• Number of outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 . . . . . . . . . . . .7 . . . . . . . . . . . .8 12Note: 1 output contact is galvanically isolated

• Type of output . . . . . . . . . . . . . . . . . . . . . .4 + 1N/O . . . . . .6 + 1N/O . . . .7N/O + 1C/O . .11N/O + 1C/O• Maximum current at contact common . . . . . . . . . . . . . . . . . .12 A• Rated capacity Ith . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 A• Rated operational voltage . . . . . . . . . . . . . . . . . . . . . . . . . . .250 VAC• Maximum switching voltage . . . . . . . . . . . . . . . . . . . . . . . . . .440 VAC• Designation according to

IEC/EN 60947-5-1 AC-DC . . . . . . . . . . . . . . . . . . . . . . . . . . .C/250, B/400• Electrical life at 0.33A, 250VAC

and AC11 load conditions . . . . . . . . . . . . . . . . . . . . . . . . . . .5 x 106• Electrical life at 2A, 250VAC

and AC11 load conditions . . . . . . . . . . . . . . . . . . . . . . . . . . .4 x 105• Electrical life at 2A, 400VAC

and AC11 load conditions . . . . . . . . . . . . . . . . . . . . . . . . . . .2 x 105

• Step combinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1:1:1; 1:2:2; 1:2:4:4; 1:2:4:8

Operating ambient conditions

• Operating temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . .-20ºC...+60ºC• Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .-30ºC...+80ºC• Relative humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .< 90%

Connections

• Type of terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Removable / Plug-in• Cable cross section (min-max) . . . . . . . . . . . . . . . . . . . . . . .0,2 ÷ 2,5 mm2 (24 ÷ 12 AWG)• Tightening torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0,8 Nm (7 LBin)

Enclosure PR-5D5 PR-5D7 PR-6D8 PR-6D12

• Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Flush mount• Dimensions wxhxd . . . . . . . . . . . . . . . . . . . . . .96 x 96 x 65 mm . . . . . . . . . . . .144 x 144 x 62 mm• Panel cutout dimension . . . . . . . . . . . . . . . . . . . .91 x 91 mm . . . . . . . . . . . . . . .138,5 x 138,5 mm• Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . .IP 54 . . . . . . . . . . . . . . . . . . . . . . .IP 41 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .(with protection cover)• Weigh . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .440g . . . . . . . . .460g . . . . . . . . .740g . . . . . . . . .770g

Reference standards

IEC/EN 61010-1; IEC/EN 61000-6-2; ENV 50204; CISPR 11/EN 55011; 61000-3-3; IEC/EN 60068-2-61;IEC/EN60068-2-27; IEC/EN60068-2-6; UL508; CSA C22.2 No14-95

Page 8: DIGITAL POWER FACTOR CONTROLLERS - RTR · PDF fileDIGITAL POWER FACTOR CONTROLLERS PR-5D & PR-6D SERIES-2-VERSIONS • PR5D - 5 steps, 96x96mm housing • PR5D - 7 steps, 96x96mm housing

DIGITAL POWER FACTOR CONTROLLERSPR-5D & PR-6D SERIES

-8-

PR-5D(96 x 96)

CODE TYPE PR-5D

REG05DPR5500000 PR-5D-5

REG07DPR5500000 PR-5D-7

PR-5D7 wiring diagrams

IMPORTANT NOTE:DEVICE PRE-PROGRAMMED IN FACTORY

In this case during the system installation and once the controller is powered up, the display will view a flas-hing (Current Transformer). By pressing and , the CT primary can be directly set.Once programmed, press MAN/AUT to confirm. The unit will store the setting and directly restart in automaticmode.Caution: if the automatic set up is executed, all the data programmed in factory will be deleted.

CT

Page 9: DIGITAL POWER FACTOR CONTROLLERS - RTR · PDF fileDIGITAL POWER FACTOR CONTROLLERS PR-5D & PR-6D SERIES-2-VERSIONS • PR5D - 5 steps, 96x96mm housing • PR5D - 7 steps, 96x96mm housing

DIGITAL POWER FACTOR CONTROLLERSPR-5D & PR-6D SERIES

-9-

PR-6D(144 x 144)

CODE TYPE PR-6D

REG08DPR6500000 PR-6D-8

REG12DPR6500000 PR-6D-12

PR-6D12 wiring diagrams

IMPORTANT NOTE:DEVICE PRE-PROGRAMMED IN FACTORY

In this case during the system installation and once the controller is powered up, the display will view a flas-hing (Current Transformer). By pressing and , the CT primary can be directly set.Once programmed, press MAN/AUT to confirm. The unit will store the setting and directly restart in automaticmode.Caution: if the automatic set up is executed, all the data programmed in factory will be deleted.

CT

Page 10: DIGITAL POWER FACTOR CONTROLLERS - RTR · PDF fileDIGITAL POWER FACTOR CONTROLLERS PR-5D & PR-6D SERIES-2-VERSIONS • PR5D - 5 steps, 96x96mm housing • PR5D - 7 steps, 96x96mm housing

DIGITAL POWER FACTOR CONTROLLERSPR-5D & PR-6D SERIES

-10-

Rear view

Overall dimensions and panel cutout

PR-5D

PR-5D

Page 11: DIGITAL POWER FACTOR CONTROLLERS - RTR · PDF fileDIGITAL POWER FACTOR CONTROLLERS PR-5D & PR-6D SERIES-2-VERSIONS • PR5D - 5 steps, 96x96mm housing • PR5D - 7 steps, 96x96mm housing

DIGITAL POWER FACTOR CONTROLLERSPR-5D & PR-6D SERIES

-11-

PR-6D

PR-6D

Rear view

Overall dimensions and panel cutout

Page 12: DIGITAL POWER FACTOR CONTROLLERS - RTR · PDF fileDIGITAL POWER FACTOR CONTROLLERS PR-5D & PR-6D SERIES-2-VERSIONS • PR5D - 5 steps, 96x96mm housing • PR5D - 7 steps, 96x96mm housing

CONNECTION DIAGRAMS

RTR Energía S.L. keeps the right to modify in any form or by any means all the information published in this catalogue withoutprior notice. Any accepted material to be returned, will be paid in origin.If a devolution is produced by any cause NOT imputable to RTR Energía S.L. the total sale price of the material subjet to devo-lution will be depreciated 10% in concept of expensens.In those cases in which any material is stored for checking or reparation, the customer must inform by writing, within threemonths after RTR Energía S.L. sends the appropriate budget or report regarding these materials, about the actions to under-take on such items. Otherwise, RTR Energía S.L. keeps the right to destroy these materials.

SPAINRTR Energía, S.L.Gavilanes, 11 BisPol. Ind. Pinto-Estación28320 PINTO (Madrid)Tel.: 34 91 691 66 12Fax: 34 91 691 22 57

CHILERTR DNA Chile, S.A.La Estera nº 668Panamericana Norte. Km 17Loteo Valle Grande - Lampa, CHILETel.: 56 2 328 44 00Fax: 56 2 738 69 11e-mail:[email protected]