Digital Meters - Power Quality Monitoring and Analysis

34
1 GE Consumer & Industrial Multilin Jun 14, 2022 Digital Meters - Power Quality Monitoring and Analysis John Levine Mar 21, 2006

description

Digital Meters - Power Quality Monitoring and Analysis. John Levine Mar 21, 2006. Contents. Effects of power quality Power Quality definitions revisited What is needed for PQ monitoring ? GE Multilin’s solution PQMII EPM9000 series Summary. - PowerPoint PPT Presentation

Transcript of Digital Meters - Power Quality Monitoring and Analysis

Page 1: Digital Meters - Power Quality Monitoring and Analysis

1GE Consumer & Industrial

MultilinApr 22, 2023

Digital Meters - Power Quality Monitoring and AnalysisJohn LevineMar 21, 2006

Page 2: Digital Meters - Power Quality Monitoring and Analysis

2GE Consumer & Industrial

MultilinApr 22, 2023

Contents

• Effects of power quality • Power Quality definitions revisited• What is needed for PQ monitoring ?• GE Multilin’s solution

o PQMIIo EPM9000 series

• Summary

Monitor and Analyze Power Disturbances, Disruptions & Harmonics

Page 3: Digital Meters - Power Quality Monitoring and Analysis

3GE Consumer & Industrial

MultilinApr 22, 2023

PQ is a Business ProblemPower Quality issues cause business problems such as:• Lost productivity, idle people and equipment• Lost orders, good will, customers and profits• Lost transactions and orders not being

processed• Revenue and accounting problems • Customer and/or management

dissatisfaction• Overtime required to make up for lost work

timeAccording to Electric Light and Power Magazine, 30 to 40 Percent of All Business Downtime Is Related to Power Quality Problems.

Page 4: Digital Meters - Power Quality Monitoring and Analysis

4GE Consumer & Industrial

MultilinApr 22, 2023

Is Power Quality Such a Big Problem?

Page 5: Digital Meters - Power Quality Monitoring and Analysis

5GE Consumer & Industrial

MultilinApr 22, 2023

Why PQ is such a Big Problem?

• The sensitivity of today’s electronic equipment makes it susceptible to power disturbances

• For some devices, a momentary disturbance can cause

o scrambled datao interrupted communicationso a frozen mouse o system crashes and equipment failure

Page 6: Digital Meters - Power Quality Monitoring and Analysis

6GE Consumer & Industrial

MultilinApr 22, 2023

PQ Problems are Expensive• Berkeley Lab Study Estimates $80 Billion

Annual Cost of Power Interruptions … Research News, Berkeley Lab, February 2, 2005

• $50 billon per year in the USA is lost as a results of power quality breakdowns …. Bank of America Report

• A manufacturing company lost more than $3 million one day last summer in Silicon Valley when the “lights went out.” … New York Times January 2000

• “A voltage sag in a paper mill can waste a whole day of production - $250,000 loss” … Business Week, June 17,, 1996

• Half of all computer problems and one-third of all data loss can be traced back to the power line … Contingency Planning Research, LAN Times

Page 7: Digital Meters - Power Quality Monitoring and Analysis

7GE Consumer & Industrial

MultilinApr 22, 2023

Who is Affected?

• Lost production• Scrap• Costs to restart• Labor costs• Equipment damage and repair• Other costs

• High Cost Facilitieso Semiconductor plantso Pharmaceuticalso Data centers

• Medium Cost FacilitiesoAutomotive manufacturingoGlass plantsoPlastics & ChemicalsoTextiles

Page 8: Digital Meters - Power Quality Monitoring and Analysis

8GE Consumer & Industrial

MultilinApr 22, 2023

PQ Definitions RevisitedIEEE CategoriesStd 1159-1995

Short Duration Variations

Typical Duration

Instantaneous Sag 0.5 – 30 cyclesMomentary Sag 30 cycles – 3

secTemporary Sag 3 sec – 1 min

Page 9: Digital Meters - Power Quality Monitoring and Analysis

9GE Consumer & Industrial

MultilinApr 22, 2023

PQ Definitions RevisitedIEEE CategoriesStd 1159-1995

Short Duration Variations

Typical Duration

Instantaneous Sag 0.5 – 30 cyclesMomentary Sag 30 cycles – 3

sec.Temporary Sag 3 sec – 1 min.Instantaneous Swell 0.5 – 30 cyclesMomentary Swell 30 cycles – 3

sec.Temporary Swell 3 sec – 1 min.

Page 10: Digital Meters - Power Quality Monitoring and Analysis

10GE Consumer & Industrial

MultilinApr 22, 2023

PQ Definitions RevisitedIEEE CategoriesStd 1159-1995

Short Duration Variations

Typical Duration

Instantaneous Sag 0.5 – 30 cyclesMomentary Sag 30 cycles – 3

sec.Temporary Sag 3 sec – 1 min.Instantaneous Swell 0.5 – 30 cyclesMomentary Swell 30 cycles – 3

sec.Temporary Swell 3 sec – 1 min.Momentary Interruptions

0.5 – 30 cycles

Temporary Interruptions

30 cycles – 3 sec.

Page 11: Digital Meters - Power Quality Monitoring and Analysis

11GE Consumer & Industrial

MultilinApr 22, 2023

PQ Definitions RevisitedIEEE CategoriesStd 1159-1995

Long Duration Variations

Typical Duration

Sustained interruptions

> 1 min

Under voltages > 1 minOver voltages > 1 min

Page 12: Digital Meters - Power Quality Monitoring and Analysis

12GE Consumer & Industrial

MultilinApr 22, 2023

PQ Definitions RevisitedIEEE CategoriesStd 1159-1995

Long Duration Variations

Typical Duration

Sustained interruptions

> 1 min

Under voltages > 1 minOver voltages > 1 minVoltage imbalance Steady stateWaveform Distortion

Page 13: Digital Meters - Power Quality Monitoring and Analysis

13GE Consumer & Industrial

MultilinApr 22, 2023

PQ Definitions RevisitedIEEE CategoriesStd 1159-1995

Long Duration Variations

Typical Duration

Sustained interruptions

> 1 min

Under voltages > 1 minOver voltages > 1 minVoltage imbalance Steady stateWaveform DistortionDC offset Steady stateHarmonics Steady stateInter harmonics Steady state

For Electric Utilities Control of Voltage and Prevention of Outages is Power Quality

Page 14: Digital Meters - Power Quality Monitoring and Analysis

14GE Consumer & Industrial

MultilinApr 22, 2023

Sources of PQ ProblemsUtility Sources• Lightning• PF Correction Equipment• Faults• Switching

Internal Sources•Individual Loads –Lighting, Elevators,

Coolers, HVAC•Uninterruptible Power Supplies •Variable Frequency Drives •Battery Chargers •Large Motors During Startup •Electronic Dimming Systems •Lighting Ballasts (esp. Electronic) •Arc Welders, and Other Arc Devices •Medical Equipment, e.g. MRIs and X-Ray

Machines •Office Equipment and Computers•Wiring

Page 15: Digital Meters - Power Quality Monitoring and Analysis

15GE Consumer & Industrial

MultilinApr 22, 2023

PQ Problems and Possible CausesTypical problems Disturbance Type Possible Causes

Overheated neutralIntermittent lock-upsFrequency deviations

Steady-state Shared neutralsImproper or inadequate wiringHigh source impedanceSCR/Rectifiers and notchingHarmonics

Page 16: Digital Meters - Power Quality Monitoring and Analysis

16GE Consumer & Industrial

MultilinApr 22, 2023

PQ Problems and Possible CausesTypical problems Disturbance Type Possible Causes

Overheated neutralIntermittent lock-upsFrequency deviations

Steady-state Shared neutralsImproper or inadequate wiringHigh source impedanceSCR/Rectifiers and notchingHarmonics

InterruptionGarbled dataRandom increase in harmonics levels

Utility faultsInrush currentsInadequate wiring

Page 17: Digital Meters - Power Quality Monitoring and Analysis

17GE Consumer & Industrial

MultilinApr 22, 2023

PQ Problems and Possible CausesTypical problems Disturbance Type Possible Causes

Overheated neutralIntermittent lock-upsFrequency deviations

Steady-state Shared neutralsImproper or inadequate wiringHigh source impedanceSCR/Rectifiers and notchingHarmonics

InterruptionGarbled dataRandom increase in harmonics levels

Utility faultsInrush currentsInadequate wiring

Intermittent lock-upsLights flickerGarbled data

Sags/Swell Source voltage variationsInrush/surge currentsInadequate wiring

Page 18: Digital Meters - Power Quality Monitoring and Analysis

18GE Consumer & Industrial

MultilinApr 22, 2023

PQ Problems and Possible CausesTypical problems Disturbance Type Possible Causes

Overheated neutralIntermittent lock-upsFrequency deviations

Steady-state Shared neutralsImproper or inadequate wiringHigh source impedanceSCR/Rectifiers and notchingHarmonics

InterruptionGarbled dataRandom increase in harmonics levels

Utility faultsInrush currentsInadequate wiring

Intermittent lock-upsLights flickerGarbled data

Sags/Swell Source voltage variationsInrush/surge currentsInadequate wiring

Component failureDielectric breakdownLock-upsGarbled dataWavy CRTs

ImpulsesEMI/RFI

LightningLoad switchingCapacitor switchingStatic dischargeHand-held radiosLoose wiring/arcing

Page 19: Digital Meters - Power Quality Monitoring and Analysis

19GE Consumer & Industrial

MultilinApr 22, 2023

PQ Problems and Possible CausesTypical problems Disturbance Type Possible Causes

Overheated neutralIntermittent lock-upsFrequency deviations

Steady-state Shared neutralsImproper or inadequate wiringHigh source impedanceSCR/Rectifiers and notchingHarmonics

InterruptionGarbled dataRandom increase in harmonics levels

Utility faultsInrush currentsInadequate wiring

Intermittent lock-upsLights flickerGarbled data

Sags/Swell Source voltage variationsInrush/surge currentsInadequate wiring

Component failureDielectric breakdownLock-upsGarbled dataWavy CRTs

ImpulsesEMI/RFI

LightningLoad switchingCapacitor switchingStatic dischargeHand-held radiosLoose wiring/arcing

Overheated transformers and motorsVoltage and current distortionsGarbled dataLock-ups

Harmonics Electronic loadsSCR/rectifier

Page 20: Digital Meters - Power Quality Monitoring and Analysis

20GE Consumer & Industrial

MultilinApr 22, 2023

Major PQ Problems

Source: EPRI, 1994

Spikes, 7%

Sags, 56%

Outages, 6%

Swells, 31%

Sags (Dips)Associated with system faults

Switching of heavy loadsStarting of large motors

SwellsSystem fault conditions

Switching on a large capacitor bankSwitching off a large load

Page 21: Digital Meters - Power Quality Monitoring and Analysis

21GE Consumer & Industrial

MultilinApr 22, 2023

Cost of Voltage Sags

Textile Industry

Plastics Industry

Glass Industry

Process Industry

Semiconductors

$1k $10k

$100k $1M $10M

Losses per Voltage Sag Event

Source: EPRI “The Economics of Custom Power”, IEEE T&D Show 2003

Page 22: Digital Meters - Power Quality Monitoring and Analysis

22GE Consumer & Industrial

MultilinApr 22, 2023

Cost of Momentary Outages

Momentary Outages create problems when computers and clocks reset, equipment stalls, and work stops.

Category Minimum MaximumIndustrialSemiconductor Manufacturing $20.0 $60.0Electronics $8.0 $12.0Automobile Manufacturing $5.0 $7.5Pharmaceutical $5.0 $50.0Glass $4.0 $6.0Rubber and Plastics $3.0 $4.5Petrochemical $3.0 $5.0Food Processing $3.0 $5.0Textile $2.0 $4.0Metal Fabrication $2.0 $4.0Mining $2.0 $4.0Paper $1.5 $2.5Printing(Newspapers) $1.0 $2.0CommercialHospitals, banks, civil service $2.0 $3.0Communications, information processing $1.0 $10.0Resturants, bars, hotels $0.5 $1.0Commercial shops $0.1 $0.5Source: EPRI “The Economics of Custom Power”, IEEE T&D 2003

Cost of Momentary Interuption($/kW Demand)

Page 23: Digital Meters - Power Quality Monitoring and Analysis

23GE Consumer & Industrial

MultilinApr 22, 2023

High Speed Waveform Capture

High Speed Waveform Capture Is the Most Important PQ Troubleshooting Tool

Page 24: Digital Meters - Power Quality Monitoring and Analysis

24GE Consumer & Industrial

MultilinApr 22, 2023

Benefits of Continuous PQ Monitoring

Continuous PQ Monitoring Detects, Records, and Leads to the Prevention of PQ Problems

• Power Quality monitoring provides a continuous “Health Check” of a facility’s power system … for example:

o Harmonic interaction between loads and power conditioning equipment spotted

o High Inrush currents from equipment startup detected

o Transients from load switching are seen• It provides data to see, diagnose and

avert looming problems – “like squeaky brakes on a car”

o Trends can be detectedo JIT equipment maintenance

programs can be established• It acts like a “Black Box” on an airplane to

tell you what, when, and where a Power Quality event occurred … to prevent it from reoccurring

Page 25: Digital Meters - Power Quality Monitoring and Analysis

25GE Consumer & Industrial

MultilinApr 22, 2023

What is needed for PQ Monitoring?PQ Monitors must detect and record the 7 types of PQ problems

•Transients•Interruptions•Sag/Under Voltage•Swell/Over Voltage•Waveform Distortion•Voltage Fluctuations•Frequency Variations

These include Flicker and Compliance to ITI(CBEMA), IEEE and ISO Standards

Plus they must …

• Be easy to use• Be Suitable for continuously

monitoring indoors and outdoors

• Interface with standard PQ analysis Software…PQDif format

• Be fast enough to capture high speed events that produce equipment problems

• Have enough storage to save the waveforms you need

• Have PQ analysis tools that produce usable, actionable recommendations

ITI: Information Technology Industry Council (Computer & Business Equipment Manufacturer’s Association)

Page 26: Digital Meters - Power Quality Monitoring and Analysis

26GE Consumer & Industrial

MultilinApr 22, 2023

Real Time Field Recorded Events

Source: AGA BrazilMeter: EPM9650

Period: Jan 2005 – Dec 2005

Continuous Monitoring of the Station for PQ Problems

Page 27: Digital Meters - Power Quality Monitoring and Analysis

27GE Consumer & Industrial

MultilinApr 22, 2023

PQ Meter ITI Capture

Equipment Interrupting Voltage Sags as Recorded

Damage Inducing Voltage Surges as Recorded

ITI Acceptable Power Disturbance Envelope

ITI: Information Technology Industry Council (Computer & Business Equipment Manufacturer’s Association)

Page 28: Digital Meters - Power Quality Monitoring and Analysis

28GE Consumer & Industrial

MultilinApr 22, 2023

Instantaneous Sag Event

Page 29: Digital Meters - Power Quality Monitoring and Analysis

29GE Consumer & Industrial

MultilinApr 22, 2023

Instantaneous Swell Event

Page 30: Digital Meters - Power Quality Monitoring and Analysis

30GE Consumer & Industrial

MultilinApr 22, 2023

Harmonic & Interharmonic Spectrum

Page 31: Digital Meters - Power Quality Monitoring and Analysis

31GE Consumer & Industrial

MultilinApr 22, 2023

Flicker Recording

Page 32: Digital Meters - Power Quality Monitoring and Analysis

32GE Consumer & Industrial

MultilinApr 22, 2023

Flicker Recording

Page 33: Digital Meters - Power Quality Monitoring and Analysis

33GE Consumer & Industrial

MultilinApr 22, 2023

SummaryGE Multilin provides the necessary tools for a successful PQ disturbance analysis and allows users to take remedial actions

Accurate Measurement to determine actual

stateExaminations

Remedial actionsRemedy

Feels the pulse of the power system network

Symptoms

High resolution recordings for longer

durationsGE Communicator

software

Diagnosis

Page 34: Digital Meters - Power Quality Monitoring and Analysis

34GE Consumer & Industrial

MultilinApr 22, 2023

Finally…

If You Can’t Measure it You Can’t Manage it

If You Can Measure it You Can Manage it