Differential Pressure Switch Honeywell
-
Upload
mahmudazakir -
Category
Documents
-
view
275 -
download
0
Transcript of Differential Pressure Switch Honeywell
-
8/9/2019 Differential Pressure Switch Honeywell
1/2
UEC24014 DifferentiaPressure Switch
Copyright 1996 Honeywell Inc. All Rights Reserved
SPECIFICATION DATA
GENERAL
Differential Pressure switches open or close a switch contactin response to a change in the pressure rise across a pumpor filter.
FEATURES
NEMA Enclosures
UL and CSA Listed
Gold Clad Contacts
Brass Pipe Connection
Pipe or Surface Mount
77-2538-
-
8/9/2019 Differential Pressure Switch Honeywell
2/22
UEC24014 DIFFERENTIAL PRESSURE SWITCH
Honeywell Europe S.A.
3 Avenue du Bourget
B-1140 Brussels Belgium
Honeywell Asia Pacific Inc.
Room 3213-3225Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Hong Kong
Home and Building Control
Honeywell Limited-Honeywell Limite155 Gordon Baker Road
North York, Ontario
M2H 2C9
Honeywell Latin American Division
Miami Lakes Headquarters
14505 Commerce Way Suite 500
Miami Lakes FL 33016
Helping You Control Your World
77-25381 Rev. 7-96
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis MN 55408-0524
Printed in U.S.A. on recycled papercontaining at least 10% post-consumer paper fibers
DESCRIPTION
Differential Pressure Switches open or close a switch contactin response to a change in sensed differential pressure.
SPECIFICATIONS
Models:u UEC2401 4M262 NEMA 1 Enclosureu UEC2401 4M262M900 NEMA 4 Enclosure
Burst Pressure:300 psi (2068 kPa)
Set Point Repeatability:Typical 1% of span
Maximum Pressure at Either Port:150 psi (1034 kPa)
Differential Pressure Setpoint (Adjustable):
4 to 43.5 psi (28 to 300 kPa) on decreasing pressure5.5 to 45 psi (38 to 310 kPa) on increasing pressure
Switch Contact Arrangement:Spdt
NOTE: Switch makes common to n.c. at setpoint ondecreasing differential pressure and common to n.o.at setpoint plus switch differential on increasingdifferential pressure.
Electrical Rating:5A at 125/250V ac, 75% power factor1/4 HP5 amps resistive and 3 amps inductive at 30 Vdc
0.5 amps resistive and 0.25 amps inductive at 125 VdcGold clad silver contacts: 1mA at 24 Vdc
Electrical Connections:Terminal Strip, 16 AWG max
Operating Temperature:30 to 160F (-1.1 to 71.1C)
Maximum Media Temperature:200F (93C) at 100 psi (689 kPa)
Enclosure:Reinforced polyester body, stainless steel cover withneoprene gasket.
Wetted Material:Buna-N diaphragm and O-Ring, Brass connnectionsPolysulphone base
Set Point Repeatability:Typical 1% of span
Deadband:Typical 1 psi (7 kPa)
Approvals:UL508, E42272; CSA C22.2 no. 14-1987Certified-LR39690
Fig. 1. Differential pressure switchdimensions in inches (millimeters).
29/32(23.1)
29/32(23.1)
2-3/8(80.5)
2-3/8(80.5)
3-1/2(88.9)
7/8 HOLEFOR 1/2 NPTCONDUITCONNECTION
NEMA 1
CONDUIT FITTING SUPPLIEDWITH NEMA 4 ONLY.
1/4 NPT
C7464
1
2-3/8(57.8)
2(50.5)
3-1/8(79.4)
1-27/32(48.7)
HIGH
LOW CLEARANCE
FOR NO.5
SCREWMOUNTINGHOLES
1