MTU 16V4000 DS2750Diesel Generator Set
Product highlights
380V–11kV/50Hz/standbypower/fuelconsumptionoptimized16V4000G94F/water charge air cooling
Bene� ts— Lowfuelconsumption— Optimizedsystemintegrationability— High reliability— High availability of power— Longmaintenanceintervals
Support— Globalproductsupportoffered
Standards— Engine-generatorsetisdesignedandmanufacturedinfacilitiescertifiedtostandardsISO2008:9001andISO2004:14001
— GeneratorsetcompliestoISO8528— GeneratormeetsNEMAMG1,BS5000,ISO,DINENandIECstandards
— NFPA 110
Power rating— Systemratings:2800kVA-2860kVA— Accepts rated load in one step per NFPA 110— GeneratorsetcompliestoG3accordingtoISO8528-5— GeneratorsetexceedsloadstepsaccordingtoISO8528-5
Performance assurance certi� cation (PAC)— Engine-generatorsettestedtoISO8528-5fortransientresponse— 85% load factor— Verifiedproductdesign,qualityandperformanceintegrity— Allenginesystemsareprototypeandfactorytested
Complete range of accessories available— Controlpanel— Power panel— Circuitbreaker/powerdistribution— Fuel system— Fuelconnectionswithshut-offvalvemountedtobaseframe— Starting/chargingsystem— Exhaust system— Mechanicalandelectricaldrivenradiators— Mediumandoversizedvoltagealternators
Emissions— Fuelconsumptionoptimized
Certi� cations— CEcertificationoption
Optionalequipmentandfinishingshown.Standardmayvary.
-
Application data 1)
EngineManufacturer MTU Model 16V4000G94F Type 4-cycle Arrangement 16V Displacement: l 76.3 Bore: mm 170 Stroke: mm 210 Compression ratio 16.4 Rated speed: rpm 1500 Engine governor ADEC (ECU 9) Max power: kWm 2387 Air cleaner Dry
Fuel systemMaximum fuel lift: m 5 Total fuel flow: l/min 27
Fuel consumption 2) l/hr g/kwh At 100% of power rating: 567 197 At 75% of power rating: 406 188 At 50% of power rating: 277 192
Liquid capacity (lubrication)Total oil system capacity: l 300 Engine jacket water capacity: l 175 Intercooler coolant capacity: l 50
Combustion air requirementsCombustion air volume: m3/s 2.9 Max. air intake restriction: mbar 30
Cooling/radiator systemCoolant flow rate (HT circuit): m3/hr 53Coolant flow rate (LT circuit): m3/hr 25 Heat rejection to coolant: kW 1025Heat radiated to charge air cooling: kW 585Heat radiated to ambient: kW 90
Exhaust systemExhaust gas temp. (after engine, max.): °C 450 Exhaust gas temp., max (after engine): °C 550 Exhaust gas temp. (before turbocharger): °C 680 Exhaust gas volume: m3/s 7.4 Maximum allowable back pressure: mbar 50
1 All data refers only to the engine and is based on ISO standard conditions (25°C and 100m above sea level).
2 Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml. All fuel consumption values refer to rated engine power.
Standard and optional features
System ratings (kW/kVA)
Generator model Voltage fuel consumption optimized
without radiator with mechanical radiator
kWel kVA* AMPS kWel kVA* AMPS
Leroy Somer LSA53.2 M7(Low voltage Leroy Somer standard)
380 V 2240 2800 4254 2216 2770 4209
400 V 2240 2800 4041 2216 2770 3998
415 V 2240 2800 3895 2216 2770 3854
Leroy Somer LSA53.2 M9 (Low voltage Leroy Somer oversized)
380 V 2240 2800 4254 2216 2770 4209
400 V 2240 2800 4041 2216 2770 3998
415 V 2240 2800 3895 2216 2770 3854
Leroy Somer LSA53.2 M9(Low voltage engine output oversized)
380 V 2296 2870 4361 2216 2770 4209
400 V 2296 2870 4142 2216 2770 3998
480 V 2296 2870 3993 2216 2770 3854
Marathon 1020FDL7108 (Low voltage Marathon)
380 V 2240 2800 4254 2216 2720 4133
400 V 2240 2800 4041 2216 2720 3926
415 V 2176 2720 3784 2216 2720 3784
Leroy Somer LSA 53.2 XL11 (Med. volt. Leroy Somer)
11 kV 2280 2850 150 2208 2760 145
Leroy Somer LSA53.2 XL9 (Medium volt. Marathon)
11 kV 2280 2850 150 2208 2760 145
* cos phi = 0.8
-
Engine
4-Cycle Standardsinglestageairfilter Oildrainextension&shut-offvalve
Closedcrankcaseventilation Governor-electronicisochronous Commonrailfuelinjection
Fuelconsumptionoptimizedengine Tier2optimizedengine NEA(ORDE)optimizedengine
Generator
4polethree-phasesynchronous generator Brushless,self-excited,self-regulating,self-ventilated
Digital voltage regulator Anticondensationheater Stator winding Y-connected, accessible neutral(broughtout) ProtectionIP23
InsulationclassH,utilizationacc.toH RadiosuppressionEN55011,group1,cl.B Shortcircuitcapability3xInfor10sec WindingandbearingRTDs (withoutmonitoring) ExcitationbyAREP+PMI MountingofCT´s:3x2coreCT´s Windingpitch:5/6winding Voltagesetpointadjustment±5%
Meets NEMA MG-1, BS 5000, IEC60034-1,VDE0530, DINEN12601andISO8528 requirements
Leroy Somer low voltage generator Oversized generator Engineoutputoptimizedgenerator Medium voltage generator
Cooling system
Jacket water pump Thermostat(s) Water charge air cooling
Mechanical radiator Electricaldrivenfront-endcooler Jacket water heater
Pulleyforfandrive
Standard and optional features
Control panel
Pre-wiredcontrolcabinetforeasyapplicationofcustomizedcontroller(V1+) Islandoperation(V2) Automaticmainsfailureoperationwith ATS (V3a) Automaticmainsfailureoperation incl.controlofgeneratorandmainsbreaker (V3b) Islandparalleloperationof multiplegensets(V4) Automaticmainsfailureoperationwithshort(<10s)mainsparalleloverlapsynchronization(V5) Mainsparalleloperationofa single genset (V6)
Mainsparalleloperationof multiplegensets(V7) Baslercontroller Deifcontroller Completesystemmetering Digitalmetering Engine parameters GeneratorProtectionFunctions Engineprotection SAEJ1939engineECUcommunications Parametrizationsoftware Multilingualcapability Multipleprogrammablecontactinputs Multiplecontactoutputs Event recording
IP54frontpanelratingwith integrated gasket Differentexpansionmodules Remote annunciator Daytankcontrol Generatorwindingtemperature monitoring Generatorbearingtemperature monitoring ModbusTCP-IP
Power panel
Available in 600x600 and 600x1000 Phasemonitoringrelay230V/400V Supplyforbatterycharger
Supplyforjacketwaterheater Supplyforanticondensationheating Plugsocketcabinetfor230V compatibleEuro/USA
Supplyforelectricaldrivenradiator from75kW(PP600x1000)Euro/USA
Representsstandardfeatures
Representsoptionalfeatures
-
Standard and optional features
Representsstandardfeatures
Representsoptionalfeatures
Fuel system
Flexible fuel connectors mounted to base frame Fuelfilterwithwaterseparator Fuelfilterwithwaterseparatorheavy-duty
Switchablefuelfilterwithwaterseparator Switchablefuelfilterwithwaterseparatorheavy-duty
Seperate fuel cooler
Fuel cooler integrated into cooling equipment
Starting/charging system
24Vstarter Starterbatteries,cables,rack, disconnect switch
Batterycharger Redundantstarter2x15kW
Mounting system
Welded base frame Resilientengineandgeneratormounting Modular base frame design
Exhaust system
Exhaustbellowswithconnectionflange Exhaustsilencerwith10dB(A)soundattenuation
Exhaustsilencerwith 30dB(A)soundattenuation
Exhaustsilencerwith 40dB(A)soundattenuation Y-connection-pipe
Circuit Breaker
3-pole circuit breaker 4-pole circuit breaker
Manual-actuatedcircuitbreaker Electrical-actuatedcircuitbreaker
Stand-alonesolutioninseperate cabinet
-
Rolls-Royce Group
www.mtu-solutions.com/powergen
Weights and dimensions
Sound data
— Consult your local MTU distributor for sound data.
Emissions data
— Consult your local MTU distributor for emissions data.
Rating definitions and conditions
— Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. No overload capability for this rating. Ratings are in accordance with ISO 8528-1, ISO-3046-1, BS 5514 and AS 2789. Average Load Factor: ≤ 85%. Operating hours/year: max. 500.
— Consult your local MTU distributor for derating information.
Drawing above for illustration purposes only, based on a standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design. See website for unit specific template drawings.
Sub
ject
to
chan
ge.
| 32
3116
21 |
Editi
on 0
1/19
| ES
M 2
019
-08.
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.
System Dimensions (L x W x H) Weight (dry/less tank)
Open power unit (OPU) 5290 x 1810 x 2350 mm approx. 14.520 kg