Drives Solutions www.danfoss.com/drives Instruction Manual DeviceNet VLT ® 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA

Transcript of Device Net Vlt 5000

Page 1: Device Net Vlt 5000

Drives Solutions

www.danfoss.com/drives

Instruction ManualDeviceNet

VLT® 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUAVLT® 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA

Instruction Manual

175R5287 MG50H422

XREF__BCNOT LOADED ON RIP

*MG50H422*REV. 2003-04-28

Page 2: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

■ Contents

Introduction to Danfoss VLT series and DeviceNet ...................... 2Product Overview ................................................................................................... 2Product and Environment ....................................................................................... 2Overall Function ..................................................................................................... 2Network ................................................................................................................. 2User Profile ............................................................................................................. 2Data Communication Interface ............................................................................... 2Initialization of VLT frequency converter Interface .................................................... 2Network Variable Handling ..................................................................................... 3Error Handling ........................................................................................................ 3Overall Function ..................................................................................................... 3

Technical Data .................................................................................................. 5Identity Object ........................................................................................................ 5Message Router ..................................................................................................... 5General Information ................................................................................................ 5Network Power Supply ........................................................................................... 5Cable Lengths ........................................................................................................ 6Cable Specifications ............................................................................................... 6Cable Cross Section ............................................................................................... 7Connection of the Cable Screen ............................................................................. 7Earth Connection ................................................................................................... 7DeviceNet Connection ............................................................................................ 7User Interface ......................................................................................................... 8Understanding Module Configuration Switches ...................................................... 9EMC Precautions ................................................................................................... 10Setting the DeviceNet Node Address ..................................................................... 11Switch Settings for DeviceNet Node Addressing .................................................... 11Setting the Baud Rate ............................................................................................ 11VLT Response Time ............................................................................................... 12General Purpose Discrete I/O ................................................................................. 12I/O Assembly Instances .......................................................................................... 12

Fieldbus Profile ................................................................................................ 13Fieldbus Profile ....................................................................................................... 13Control Word .......................................................................................................... 13Status Word ........................................................................................................... 15Control Word under VLT standard .......................................................................... 17Status Word under VLT standard ............................................................................ 18Control Word and Status Word under Instance 20/70 ............................................ 19

Programming .................................................................................................... 20Quick Setup ........................................................................................................... 20Special Attention .................................................................................................... 20Warning and Alarm Messages ................................................................................ 26Factory Settings ..................................................................................................... 27

MG.50.H4.22 - VLT is a registered Danfoss trademark 1

Page 3: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

■ Product Overview

■ Product and EnvironmentThe DeviceNet Option Card is an interface betweenthe DeviceNet serial communication bus and the VLTfrequency converter from Danfoss. The option cardwill function as an integrated part of the drive.

DeviceNet is a distributed control network. TheDeviceNet protocol is embedded in the controller optioncard and is a communication protocol conforming to theOpen DeviceNet Vendor Association (ODVA) standard.

The option card allows DeviceNet compatiblecontrollers, sensors, and network management toolsto control, monitor, and supervise the VLT frequencyconverter. The option is designed to the DeviceNetSystem Protocol for Vendors as a slave device.

■ Overall FunctionA DeviceNet compatible device has the ability toperform the following operations with the VLT frequencyconverter over the DeviceNet network:

1. Control speed references and send drivecontrol commands.

2. Monitor the status of the drive, access alarmand warning messages, and monitor driveand motor information.

3. Upload and download drive settings, configuredrives, and also perform the operationsdefined in 1 and 2.

Therefore, the level of control and flexibility of the VLTfrequency converter over the network depends onthe capabilities built into the controlling device.

The application program has the following functions:1. Support interger parameters through the

dual ported RAM.2. Manipulate the dual ported RAM parameters

to interface with the CAN.3. Monitor network activity "watchdog" function to

determine Master – Slave communication continuity.

■ NetworkThe VLT frequency converter will function as a slaveon the DeviceNet network. All addressing and linkingto nodes is done at installation time by a networkmanager tool. The network installer and the networkmanagement master have a significant influence onhow the node functions on the network. A DeviceNetnetwork can support up to 64 nodes.

■ User ProfileThe end-user is a network manager programmer ora controller who see the DeviceNet control card asa transparent bridge to the VLT frequency converter.Control and supervision of the VLT frequency converterwill still be possible through the standard parameter set.

■ Data Communication InterfaceNo direct data communication interface (e.g. via aserial port) other than the DeviceNet interface and theVLT frequency converter interface is considered.

■ Initialization of VLT frequency converter InterfaceThe VLT frequency converter interface is initialized inthree phases. The first two phases are initiated andcontrolled by the VLT which will write commands tothe option card through the dual port RAM.

MG.50.H4.22 - VLT is a registered Danfoss trademark2

Page 4: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Intr

oduc

tion

to D

anfo

ss V

LT s

erie

san

d D

evic

eNet

Phase 1:Is the initialization of the communication system.During this phase the option card must respondcorrectly to the VLT frequency converter initializationcommand or else the VLT will not function anddisplay a "No Option Init" message.

Phase 2:Is the interface watchdog function performed bythe option card as the first operational action. Aftercompletion of this phase, data can be passed betweenthe VLT frequency converter and the option cardthrough the command channel in the dual port RAM.

Phase 3:The VLT frequency converter will write to the InitializationChannel of the dual port RAM which will set thedisplacement values of the various channels (ControlChannel, Status Channel, Command Channel 1,Command Channel 2, Command Channel 3, WarningChannel, and Spontan Channel), and the DeviceNetoption card software will read these displacementsand return a response to the VLT frequency converternotifying that the initialization was successful or anerror was obtained in the process.

During operation (after initialization) the dual port RAMinterface is supervised by a watch-dog in the VLTfrequency converter. The VLT frequency converter willbe kept "alive" by cyclic writing to a channel in the dualport RAM by the watch-dog handler of the option card.

■ Network Variable HandlingThe parameter access network variable is a structurecontaining parameter number, data, value, and afunction code containing a read or write command.The application program shall receive the data,validate the data, convert the data to the format ofthe VLT frequency converter, process the read orwrite of the parameter, then send the informationback in an output network variable of the samestructure. This output variable would contain theparameter number, error code information in the eventof an exception, and parameter value.

■ Error HandlingThe option card will stop sending a watchdog signalto the VLT frequency converter when:

1. The node has been disconnected from the network2. A network management tool has the

Option Card go Off-line3. A hardware fault on the DeviceNet Option Card

PCB prevents reliable operation

By withholding the watchdog message, the VLTfrequency converter can detect a "Bus Time-out"and enter secure, pre-defined state.

For recoverable errors such as [1] and [2] the optioncard shall re-send the watchdog message whenthe fault or condition has disappeared such as afterre-connection of the node to the network.

For unrecoverable errors such as [3] the applicationprogram shall permit logging of network errorswithout resetting or restarting the microprocessor.This will send information to a network managementtool that will allow appropriate actions to be taken.The only way to recover from a serious error is tore-initialize the VLT frequency converter DeviceNetoption card by cycling power.

In case of serious VLT frequency converter fault, theDeviceNet processor shall hold the CAN chip reset,thereby disabling any communication to the node untilthe VLT frequency converter has been re-initialized.

■ Overall FunctionDeviceNet is a low-level network that standardizescommunications between industrial devices (sensors,limit switches) and high level devices (controllers).The communication network can be peer to peer ormaster/slave. DeviceNet uses CAN technology forMedia Access Control and Physical Signaling and itsupports up to 64 nodes. DeviceNet also definesdevice profiles for devices belonging to specific classes.For other devices, a custom class must be defined inorder to make it DeviceNet compatible. This furtherenhances the interchangeability and interoperability ofthe network. Each node on the network has its ownunique media access control identifier (MAC ID) todistinguish it on the network. The MAC ID is storedin the header of the message which is split into fourdifferent message groups. However, DeviceNet onlymakes use of three message groups keeping the fourthone for future use. If two nodes attempt to get controlof the network bus simultaneously, the CAN protocol

MG.50.H4.22 - VLT is a registered Danfoss trademark 3

Page 5: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

resolves the issue by arbitration. A dominant bit (0)will win arbitration over a recessive bit (1).

For the VLT frequency converter, the option cardwill be slave node on the DeviceNet network. Theoption card will be a message server that will requestand set parameters in the VLT via a dual portedRAM interface. The option card has an embeddedCAN controller that will screen all network messageswith a Mask and Match register. This featureallows the option card to filter out any unwantedmessages from the network. The option card willreceive group 2 and group 3 messages. Group 2messages allows the option card to use the predefinedMaster/Slave connection set which identifies a usefor all group 2 message identifiers. The ability toreceive Group 3 messages allows the option card toalso be an Unconnected Explicit Message Manager(UCMM) with the UCMM request and responsemessage identifier. Explicit message connectionsare unconditionally point-to-point. Point-to-pointconnections exist between two devices only.

MG.50.H4.22 - VLT is a registered Danfoss trademark4

Page 6: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Tec

hnic

alD

ata

■ Technical Data

■ Identity ObjectThis object is used to provide identification andgeneral information about the device. This objectis required by all DeviceNet products.

This object requires no class attributes. Its instanceattributes are the following:

Vendor 97

Device Type 2

Product Code Depends of the Drive

Revision - Major, Minor Depends of option

Status

Serial Number

Product Name VLT 5000

■ Message RouterThe Message Router object provides a messagingconnection point through which a Client mayaddress a service to any object class or instanceresiding in the physical device.

This object requires no class attributes. Its instanceattributes are the following:1. Object List - Number of Classes

■ General InformationParameter 502 = "BUS".Otherwise terminals 12 and 27 of the control cardmust be connected, before motor start. In parameters502-508 it is possible to define how to gate the controlcommands from the DeviceNet with the equivalentcontrol commands of the digital inputs.

■ Network Power SupplyThe DeviceNet option is an optically isolated node,where transceiver power is provided by the network.External network power supply requirements are:- 11 - 25 VDC- 70 mA draw per VLT 5000 DeviceNet node

MG.50.H4.22 - VLT is a registered Danfoss trademark 5

Page 7: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

■ Cable Lengths

Drop LengthBaud Rate Max. total cable length [m]

Maximum Cumulative125k baud 500 meters (1640 ft.) 156 meters (512 ft.)250k baud 250 meters (820 ft.) 78 meters (256 ft.)500k baud 100 meters (328 ft.)

6 meters (20 ft.)for one drop 39 meters (128 ft.)

■ Cable Specifications

Physical Characteristics SpecificationTwo shielded pairs Common axis with drain wire in centerOverall braid shield 65% coverage 36 AWG Cu braid. (individually tinned)Drain wire # 18 (19 x 30 AWG) Copper (individually tinned)Outside diameter 0.475 ± 0.015 inches (round),

roundness - radius delta to be within 15% of 0.5 O.D.*Jacket insulation * 0.040 inches minimumJacket marking * Vendor Name & Part # 1 Pr 18 and 1 Pr 15 AWG

shielded, additional markings are acceptableElectrical Characteristics SpecificationDRC (braid + tape + drain) 1.75 Ohms/1000 ft. (nom. @ 20°C)Applicable Environmental Characteristics SpecificationAgency Certifications (U.S. and Canada) NEC (UL) type, CL2/CL3 (min.)Bend radius - installation / fixed 20 x diameter / 7 x diameterOperating ambient temperature -20° to + 60°C @ 8 amps; de-rate current linearly to

zero @ 80°CStorage temperature -40° to + 85°CPull tension 190 Ibs max

* Other types of jacket insulation are allowableprovided that internal construction and electricalcharactersitics adhere to this specification.

MG.50.H4.22 - VLT is a registered Danfoss trademark6

Page 8: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Tec

hnic

alD

ata

■ Cable Cross Section

■ Connection of the Cable ScreenThe screen of the DeviceNet cable must alwaysbe connected to ground at both ends, that meansthe screen must be connected to ground in allstations connected to the DeviceNet network. It isvery important to have a low impedance groundconnection of the screen, also at high frequencies.This can be obtained by connecting the surfaceof the screen to ground, for example by means ofa cable clamp or a conductive cable gland. VLTfrequency converter Series are provided with differentclamps and brackets to enable a proper groundconnection of the DeviceNet cable screen. Thescreen connection is shown in the drawing.

■ Earth ConnectionIt is important that all stations connected to theDeviceNet network are connected to the same earthpotential. The earth connection must have a low HF(high frequency) impedance. This can be achievedby connecting a large surface area of the cabinet toground, for example by mounting the VLT frequencyconverter on a conductive rear plate. Especiallywhen having long distances between the stations

in a DeviceNet network it can be necessary to useadditional potential equalizing cables, connecting theindividual stations to the same earth potential.

■ DeviceNet ConnectionIt is essential that the bus line be terminated properly.A mismatch of impedance may result in reflections onthe line that will corrupt data transmission.

The DeviceNet Option Card is provided with apluggable screw connector.

By using a pluggable screw connector as a splicebetween two trunk lines, removal of devices willnot sever the network. Strain relief, if required,must be provided by the developer. In currentinstallations of this type of connector, the strainrelief is attached to the product.

NOTEWires should not be installed while thenetwork is active. This will prevent problemssuch as shorting the network supply or

disrupting communications.

MG.50.H4.22 - VLT is a registered Danfoss trademark 7

Page 9: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

■ User InterfaceThe DeviceNet option card contains two bi-color(green/red) LED’s for each connector hookupport, to indicate the state of the device andnetwork, respectively.For the device status LED:1. when the LED is off, the device is off2. when the LED is green, the device is operational3. When the LED is flashing green, the device

is in standby4. when the LED is flashing red, the device

detects a minor fault5. when the LED is red, the device detects

an unrecoverable fault6. when the LED is flashing red/green, the

device is self testing

For the network status LED:1. when the LED is off, the network is

non-powered/not online2. when the LED is flashing green, the network

is online but not connected3. when the LED is green, the network is

online and connected4. when the LED is flashing red, the network

has a connection time-out5. when the LED is red, the network has a critical link

failure. No further direct user interface is considered

No further direct user interface is considered.

MG.50.H4.22 - VLT is a registered Danfoss trademark8

Page 10: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Tec

hnic

alD

ata

■ Understanding Module Configuration SwitchesThe DeviceNet Communication module’s DIPswitch settings determine:

• DeviceNet node address• DeviceNet baud rate

When you make changes to the switchsettings, use a pointed instrument suchas a ball point pen. DO NOT use a

pencil because damage may occur

Unpredictable operation may occur ifyou fail to check connections and DIPswitch settings for compatibility with your

application. Unpredictable operation may result indeath, personal injury, and equipment damage.

Hazard of injury or equipment damagemay occur due to unintended or incorrectmachine motion. When a system

is configured for the first time, the motor mustbe disconnected from the machine or processduring initial system testing.

NOTEWhen setting the Communication Module’saddressing Dip Switches, you must ensurethat each serial device on the network has a

unique address. Also, all devices connected to thenetwork must be set at the same baud rate.

MG.50.H4.22 - VLT is a registered Danfoss trademark 9

Page 11: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

■ EMC PrecautionsEMC precautions The following EMC precautions arerecommended to obtain interference free operation ofthe DeviceNet network. Additional information on EMCcan be found in the VLT 5000 Series Instruction Manual.

NOTERelevant national and local regulations,for example regarding protective earthconnection, must be observed

The DeviceNet communication cable must be keptaway from motor and brake resistor cables to avoid

coupling of high frequency noise from one cableto the other. Normally a distance of 8 inches (200mm) is sufficient, but it is generally recommendedto keep the greatest possible distance betweenthe cables, especially where cables are runningin parallel over long distances.

If the DeviceNet cable has to cross a motorand brake resistor cable they must cross eachother at an angle of 90°.

MG.50.H4.22 - VLT is a registered Danfoss trademark10

Page 12: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Tec

hnic

alD

ata

■ Setting the DeviceNet Node AddressDip switches 6 through 1 set the module’s nodeaddress using binary addressing.

■ Switch Settings for DeviceNet Node AddressingFollow these steps to set the DeviceNet node address:

1. Refer to the table below for the switch settingsof a specific address.

2. Using your finger or a pointed object, slide switches1 through 6 to the appropriate ON/OFF positions.

DeviceNetAddress

SwitchSettings1⇒ 6

DeviceNetAddress

SwitchSettings1⇒ 6

DeviceNetAddress

SwitchSettings1⇒ 6

DeviceNetAddress

SwitchSettings1⇒ 6

0 000000 16 000010 32 000001 48 0000111 100000 17 100010 33 100001 49 1000112 010000 18 010010 34 010001 50 0100113 110000 19 110010 35 110001 51 1100114 001000 20 001010 36 001001 52 0010115 101000 21 101010 37 101001 53 1010116 011000 22 011010 38 011001 54 0110117 111000 23 111010 39 111001 55 1110118 000100 24 000110 40 000101 56 0001119 100100 25 100110 41 100101 57 10011110 010100 26 010110 42 010101 58 01011111 110100 27 110110 43 110101 59 11011112 001100 28 001110 44 001101 60 00111113 101100 29 101110 45 101101 61 10111114 011100 30 011110 46 011101 62 01111115 111100 31 111110 47 111101 63 111111

■ Setting the Baud RateDip switches 7 and 8 set the baud rate at whichthe Communication Module communicates on thenetwork. The factory default setting is 125K BPS.

Switch Settings for DeviceNet Module Baud Rate:

Baud Rate Switch Setting7

Switch Setting8

125 kBPS 0 0250 kBPS 1 0500 kBPS 0 1125 kBPS 1 1

MG.50.H4.22 - VLT is a registered Danfoss trademark 11

Page 13: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

■ VLT Response TimeThe update time via the DeviceNet connectioncan be divided into two parts:

1. The communication time, which is the time ittakes to transmit data from the master to theslave (VLT with DeviceNet option).

2. The internal update time, which is the time it takesto transmit data between the VLT 5000 controlcard and the DeviceNet option card.

Communication time (tcom) depends on the actualtransmission speed (baudrate) and the type of master

in use. More data or lower transmission speedwill increase the communication time.

The internal update time (tint) depends on the type ofdata in question as there are different channels forthe data transfer where time critical data e.g. controlword has highest priority. The internal update time forthe different types of data are stated below.

Data Updatetime, tint

Control word/Main reference (part ofPPO)

2 msec

Status word/Actual output frequency(part of PPO)

2 msec

Parameter read via PCD-part of PPO 2 msecParameter write via PCD-part of PPO 83 msecParameter read/write via explicitemessage

22 msec

■ General Purpose Discrete I/OThe General Purpose Discrete I/O device I/Oassemblies consist of:

• five predefined input assemblies with singlestatus bits

• one product–specific input assembly witha single status bit

• five predefine input assemblies with multiplestatus bits

• one product–specific input assembly withmultiple status bits

• five predefined output assemblies• one product–specific output assembly

■ I/O Assembly InstancesThe I/O Assembly Instance definitions in this sectiondefine the format of the "data" attribute (attribute 3)for I/O Assembly Instances. I/O Assemblies supporta hierarchy of motor control devices. The devicehierarchy includes motor starters, soft starters, ACand DC drives, and servo drives. Assembly Instancesare numbered within the hierarchy so that eachdevice type is assigned a range of Assembly Instance

numbers, with higher functionality devices supportinghigher instance numbers. Devices in the hierarchycan choose to support instance numbers that arelower than theirs in the hierarchy. For example an ACdrive may choose to support some I/O Assembliesin the starter profile to make it easier to interchangestarters and drives within the system.

Parameter904

Decimal WRITE Decimal READ

PP03 20 CTW SPEEDRPM

70 STW ACREF

PP01 100 CTW REF 150 STW MAVPP02 101 CTW REF 915.1 915.2 151 STW MAV 916.1 916.2PP04 102 915.1 915.2 915.3 915.4 152 916.1 916.2 916.3 916.4

MG.50.H4.22 - VLT is a registered Danfoss trademark12

Page 14: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Fie

ldbu

sP

rofil

e

■ Fieldbus Profile

■ Control WordControl Word as per Profidrive standard(parameter 512 = Fieldbus Profile). The control word isused for transmitting commands from a master (e.g.a PC) to a slave (VLT frequency converter).

Bit Bit = 0 Bit =100 OFF 1 ON 101 OFF 2 ON 202 OFF 3 ON 303 Motor coasting Enable04 Quick stop Ramp05 Freeze output

frequencyRamp enable

06 Ramp stop Start07 No function Reset08 Jog 1 OFF ON09 Jog 2 OFF ON10 Data not valid Valid11 No function Slow down12 No function Catch13 Choice of Setup (lsb)14 Choice of Setup (msb)15 No function Reversing

Bit 00, OFF1/ON1:An ordinary ramp stop which uses the ramp timein parameters 207/208 or 209/210. Bit 00 = "0"leads to a stop and leads to output relay 01 or04 being activated, the output frequency is 0 Hz,provided Relay 123 has been selected in parameter323 or 326. Bit 00 = "1" means that the adjustablefrequency drive will be able to start if the otherconditions for starting have been fulfilled.

Bit 01, OFF2/ON2:Coasting stop. Bit 01 = "0" leads to a coasting stop andleads to output relay 01 or 04 being activated, when theoutput frequency is 0 Hz, provided Relay 123 has beenselected in parameter 323 or 326. Bit 01 = "1" meansthat the adjustable frequency drive is able to startprovided the other conditions for starting are fulfilled.

Bit 02. OFF3/ON3:Quick-stop, which uses the ramp time set in parameter212. Bit 02 = "0" leads to a quick stop and leadsto output relay 01 or 04 being activated, when theoutput frequency is 0 Hz, provided Relay 123 has beenselected in parameter 323 or 326. Bit 02 = "1" meansthat the adjustable frequency drive is able to start,provided the other conditions for starting are fulfilled.

Bit 03, Coasting/enable:Coasting stop. Bit 03 = "0" leads to a stop. Bit 03 ="1" means that the adjustable frequency drive is ableto stop, provided the other conditions for starting arefulfilled. Note: in parameter 502 the choice is madeas to how bit 03 is to be combined (gated) with thecorresponding function in the digital inputs.

Bit 04, Quick-stop/ramp:Quick-stop which uses the ramp time in parameter212. Bit 04 = "0" leads to a quick- stop. Bit 04 ="1" means that the adjustable frequency drive is ableto start, provided the other conditions for starting arefulfilled. Note: In parameter 503 the choice is madeas to how dit o4 is to be combined (gated) with thecorresponding function on the digital inputs.

Bit 05, Freeze output frequency/ramp enable:Bit 05 = "0" means that the given output frequency ismaintained even if the reference is changed. Bit 05 ="1" means that the adjustable frequency drive is againable to regulate, and the given reference is followed.

Bit 06, Ramp stop/start:An ordinary ramp stop that uses the ramp time inparameters 207/208 or 209/210; in addition, outputrelay 01 or 04 will be activated when the outputfrequency is ) Hz, provided Relay 123 has beenselected in parameter 323 or 326. Bit 06 = "0" leadsto a stop. Bit 06 = ’1" means the adjustable frequencydrive is able to start, provided the other conditions forstarting are fulfilled. In parameter 505 the choice ismade as to how bit 06 is to be combined (gated) withthe corresponding function on the digital inputs.

Bit 07, No function/reset:Reset of trip. Bit 07 = "0" means that there is noreset. Bit 07 = "1" means that a trip is reset.

MG.50.H4.22 - VLT is a registered Danfoss trademark 13

Page 15: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Bit 08, Jog 1 OFF/ON:Activation of pre-programmed speed in parameter509 (Bus Jog 1). JOG 1 is only possible whenBit 04 = "0" and bit 00-03 = "1".

Bit 09, Jog 2 OFF/ON:Activation of pre-programmed speed in parameter510 (Bus Jog 2). JOG 2 is only possible when Bit04 = "0" and bits 00-03 = "1". If both JOG 1 andJOG 2 are activated (bits 08 and 09 = "1"), JOG 1has the higher priority, which means that the speedprogrammed in parameter 509 will be used.

Bit 10, Data not valid/valid:Used for telling VLT 5000 whether the control word isto be used or ignored. Bit 10 = "0" means that thecontrol word is ignored. Bit 10 = "1" means that thecontrol word is used. This function is relevant becausethe control word is always contained in the telegram,regardless of the type of telegram used, i.e. it is possibleto disconnect the control word if it is not to be used inconnection with updating or reading of parameters.

Bit 11, No function/slow down:Used for reducing the speed reference by thevalue in parameter 219. Bit 11 = "0" means thatthere is no change of the reference. Bit 11 = "1"means that the reference is reduced.

Bit 12, No function/catch-up:Used for increasing the speed reference by the value ofparameter 219. Bit 12 = "0" means that the referenceis increased. If both slow down and catch-up areactivated (bits 11 and 12 = "1"), slow down has thehigher priority, i.e. the speed reference is reduced.

Bits 13/14, Choice of Setup:Bits 13 and 14 are used for choosing among thefour menu Setups in accordance with:

Setup Bit 14 Bit 13

1 0 0

2 0 1

3 1 0

4 1 1

This function is only possible if Multi-Setups havebeen selected in parameter 004.

NOTEParameter 507 is used for choosing how bits13/14 are to be combined (gated) with thecorresponding function on the digital inputs.

Bit 15, No function/reversing:Reversing of the direction of rotation of themotor. Bit 15 = "0" leads to no reversing, bit15 = "1" leads to reversing.

Note that as a point of departure reversing hasbeen selected as Digital in parameter 506. Bit 15only leads to reversing if bus, logical or or logicaland has been selected (logical and, however,only together with terminal 19).

NOTEUnless otherwise mentioned, the controlword bit is combined (gated) with thecorresponding function on the digital

inputs as a logical "or" function.

MG.50.H4.22 - VLT is a registered Danfoss trademark14

Page 16: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Fie

ldbu

sP

rofil

e

■ Status WordStatus Word (according to Profidrive standard(parameter 512 = Fieldbus Profile). The status wordis used for informing the master (e.g. a PC) of thecondition of a slave (VLT frequency converter).

Bit Bit = 0 Bit =100 Control not ready Ready01 VLT not ready Ready02 Motor coasting Enable03 NO fault Trip04 ON 2 OFF 205 ON 3 OFF 306 Start enable Start disable07 No warning Warning08 Speed - reference Speed = ref.09 Local control Bus control10 Out of operating

rangeFreq. limit OK

11 Not running Running12 VLT OK Stalls, auto-start13 Voltage OK Above limit14 Torque OK Above limit15 Timer OK Above limit

Bit 00, Control not ready/ready:Bit 00 = "0" means that bit 00, 01 or 02 of the controlword is "0" (OFF1, OFF2 or OFF3), or that the adjustablefrequency drive has tripped. Bit 00 = "1" means thatthe adjustable frequency drive is ready, but that thereis not necessarily any supply to the power component(in case of external 24 V supply to the controls).

Bit 01, VLT not ready/ready:Same meaning as bit 00; however, there is also asupply to the mains component, and the adjustablefrequency drive is ready to run when it receivesthe necessary start signals.

Bit 02, Coasting/enable:Bit 02 = "0" means that the control word bit 00, 02or 03 is "0" (OFF1, OFF2, OFF3 or Coasting), or theVLT 5000 Series unit has tripped. Bit 02 = "1" meansthat the control word bits 00, 01, 02 or 03 are "1"and that VLT 5000 Series has not tripped.

Bit 03, No fault/trip:Bit 03 = "0" means that VLT 5000 Series is not in a faultcondition. Bit 03 = "1" means that VLT 5000 Series hastripped and needs a reset signal in order to run.

Bit 04, ON2/OFF2:Bit 04 ="0" means that control word bit 01 ="1". Bit04 ="1" means that control word bit 01 ="0".

Bit 05, ON3/OFF3:Bit 05 ="0" means that control word bit 02 ="1". Bit05 -"1" means that control word bit 02 ="0".

Bit 06, Start enable/start disable:Bit 06 is always "0" if Danfoss has been selected inparameter 512. If Profidrive has been selected inparameter 512, bit 06 will be "1" after reset of a trip,after activation of OFF2 or OFF3 and after connectionof mains voltage. Start disable is reset, setting controlword bit 00 to "0" and bits 01, 02 and 10 to "1".

Bit 07, No warning/warning:Bit 07 = "0" means that there is no unusual situation.Bit 07 = "1" means that an abnormal condition hasarisen for the VLT 5000 Series. All warnings describedin the VLT 5000 instruction manual will set bit 07 to "1".

Bit 08, Speed ref/speed. = ref.:Bit 08 = "0" means that the actual motor speed isdifferent from the speed reference set. This can bethe case while the speed is ramped up/down duringstart/stop. Bit 08 = "1" means that the present motorspeed equals the speed reference set.

Bit 09, Local control/Bus control:Bit 09 = "0" means that VLT 5000 Series has beenstopped by means of the stop key on the control panel,or that Local operation has been selected in parameter002. Bit 09 = "1" means that it is possible to controlthe adjustable frequency drive via the serial port.

Bit 10, Out of operating range/Freq. limit OK:Bit 10 = "0" means that the output frequency isout of the range set in parameter 225 (Warning:Low frequency) and parameter 226 (Warning: Highfrequency). Bit 10 = "1" means that the outputfrequency lies within the mentioned range.

Bit 11, Does not run/runs:Bit 11 = "0" means that the motor is not running. Bit11 = "1" means that VLT 5000 Series has a start signalof that the output frequency is greater than 0 Hz.

MG.50.H4.22 - VLT is a registered Danfoss trademark 15

Page 17: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Bit 12, VLT OK/stalling, autostart:Bit 12 = "0" means that there is no temporaryovertemperature on the inverter. Bit 12 = ’1" means thatthe inverter has stopped because of overtemperature,but that the unit has not tripped and will continue,once the overtemperature stops.

Bit 13, Voltage OK/above limit:Bit 13 = "0" means that the voltage limits of VLT5000 Series have not been exceeded. Bit 13 = "1"means that the DC voltage of the VLT 5000 Seriesintermediate circuit is too low or too high.

Bit 14, Torque OK/above limit:Bit 14 = "0" means that the motor current islower than the torque limit selected in parameter221. Bit 14 = "1" means that the torque limit inparameter 221 has been exceeded.

Bit 15, Timers OK/above limit:Bit 15 = "0" means that the timers for the motor thermalprotection and VLT thermal protection, respectively,have not exceeded 100%. Bit 15 = "1" means thatone of the timers has exceeded 100%.

MG.50.H4.22 - VLT is a registered Danfoss trademark16

Page 18: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Fie

ldbu

sP

rofil

e

Control Word under VLT standard(parameter 512 = FC Profile). The control word isused for sending commands from a master (e.g. aPC) to a slave (VLT frequency converter).

Bit Bit = 0 Bit =100 Preset reference

choice IsbON 1

01 Preset referencechoice msb

ON 2

02 DC brake Ramp03 Coasting Enable04 Quick stop Ramp05 Hold Ramp enable06 Ramp stop Start07 No function Reset08 No function Jog09 Ramp 1 Ramp 210 Data not valid Valid11 No function Relay 01 activated12 No function Relay 04 activated13 Choice of Setup (lsb)14 Choice of Setup (msb)15 No function Reversing

Bit 00/01: Bits 00 and 01 are used for choosing amongthe four pre-programmed references (parameters215-218) in accordance with the following table:

Preset ref. Parameter Bit 01 Bit 00

1 215 0 0

2 216 0 1

3 217 1 0

4 218 1 1

NOTEParameter 508 is where to choose the waybits 1/12 are to be combined (gated) with thecorresponding function on the digital inputs.

Bit 02, DC Brake:Bit 02 = "0" leads to DC braking and stop. Brakingcurrent and duration are set in parameters 125 and126. Bit 02 = "1" leads to ramping.

Bit 08, Activation of Jog speed in parameter 213:Bit 08 = "0": Jog speed not activated. Bit 08 = "1"means that the motor is running at Jog speed.

Bit 09, Choice of ramp 1/2:Bit 09 = "0" means that ramp 1 is active (parameters207/208). Bit 09 = "1" means that ramp 2(parameters 209/210) is active.

Bit 11, Relay 01:Bit 11 = "0": Relay 01 not activated. Bit 11 =1: Relay 01 activated, provided Control word bithas been chosen in parameter 323.

Bit 12, Relay 04:Bit 12 = "0": Relay 04 has not been activated. Bit 12= "1": Relay 04 has been activated, provided Controlword bit has been chosen in parameter 326.See the description of other bits under controlword for Profidrive standard.

NOTEUnless otherwise mentioned, the controlword bit is combined (gated) with thecorresponding function on the digital

inputs as a logical "or" function.

MG.50.H4.22 - VLT is a registered Danfoss trademark 17

Page 19: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Status Word under VLT standard(parameter 512 = FC Profile). The status word isused for informing the master (e.g. a PC) about thecondition of the slave (VLT frequency converter).

Bit Bit = 0 Bit =100 Control not ready Ready01 VLT not ready Ready02 Coasting Enable03 NO fault Trip04 Reserved05 Reserved06 Reserved07 No warning Warning08 Speed - reference Speed = ref.09 Local control Bus control10 Out of range Frequency OK11 Not running Running12 VLT OK Stalling, auto-start13 Voltage OK Above limit14 Torque OK Above limit15 Timer OK Above limit

Bit 00, Control not ready/ready:Bit 00 = "0" means that the adjustable frequency drivehas tripped. Bit 00 = "1" means that the adjustablefrequency drive controls are ready, but the powercomponent is not necessarily receiving any powersupply (in case of external 24 V supply to controls).

Bit 02, Coasting/enable:Bit 02 = "0" means that the control word bit 03 is "0"(Coasting) or that VLT 5000 Series has tripped.Bit 02 = "1" means that control word bit 03 is "1"and that VLT 5000 Series has not tripped.See the description of other bits under statusword for the Profidrive standard.

Bus reference value:

The frequency reference value is transmitted to theadjustable frequency drive in the form of a 16-bit word.The value is transmitted as a whole number (0-32767).16384 (4000 Hex) corresponds to 100%. (Negativefigures are formatted by means of 2’s complement.)The bus reference has the following format:Parameter 203 = "0"

"refMIN - ref MAX"0-16384 (4000 Hex) ~ 0-100% ~ ref MIN - refMAX

Parameter 203 = "1"

- refMIN - + ref MAX

- 16384 (...Hex) - + 16384 (4000 Hex) ~- 1000 - + 100% ~ - refMAX - + refMAX

Actual output frequency

The value of the actual output frequency of theadjustable frequency drive is transmitted in theform of a 16-bit word. The value is transmittedas a whole number (0-32767). 16384 (4000 Hex)corresponds to 100%. (Negative figures are formedby means of 2’s complement).

MG.50.H4.22 - VLT is a registered Danfoss trademark18

Page 20: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Fie

ldbu

sP

rofil

e

■ Control Word and Status Word under Instance 20/70Set parameter 904 PPO type 1(900) to choose

Instance 20/70.The control word in Instance 20 is defined asfollowing:

Instance Byte 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

20 0 Fault

Reset

Run

Fwd

1

2 Speed reference (low byte)

3 Speed reference (high byte)

Bit 0, Run Fwd:Bit 0 = "0" means that the VLT frequencyconverter has a stop command.Bit 0 = "1" leads to a start command and the VLTfrequency converter will start to run the motor.

Bit 2, Fault ResetBit 0 = "0" means that there is no reset of a trip.Bit 0 = "1" means that a trip is reset.

The Speed reference in Instance 20 is defined as aword. See description by Bus reference Value.

The status word in Instance 70 is defined as following:

Instance Byte 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

70 0 Run-

ning

Fault

1

2 Speed actual value (low byte)

3 Speed actual value (high byte)

Bit 0,Fault:Bit 0 = "0" means that there is no fault on theVLT frequency converter.Bit 0 = "1" means that there is a fault on theVLT frequency converter.

Bit 2, RunningBit 0 = "0" means that there is no active start command.Bit 0 = "1" means that there is an active start command.

The Speed Actual value in Instance 70 is defined as aword. See description by Actual Output frequency

MG.50.H4.22 - VLT is a registered Danfoss trademark 19

Page 21: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

■ Quick SetupFor how to program the ordinary VLT parametersrefer to the VLT 5000 Series Instruction Manual.Communication is established by setting thefollowing parameters:

Parameter 904:Select the PPO type to be applied.

Parameter 918:Readout of the actual address of the DeviceNetoption via dip switch.

Parameter 801:Readout the transmission speed in bit/sec. Thedefault setting is 125 kbaud, which means the VLTautomatically detects the transmission speed of theconnected bus. If you set a fixed value it must bethe same as that selected in the master.

■ Special AttentionSpecial attention must be given to the followingparameters described in the VLT 5000 SeriesInstruction Manual:

• 002:If operation site = Local, then control viaDeviceNet is not possible.

• 502-508:Selection of how to gate DeviceNet controlcommands with control commands on the digitalinputs of the control card.

• 512:Selects DeviceNet profile.

• 515-538:Data read out parameters that can be used to readvarious actual data from the VLT, as for example actualstatus on the analog and digital inputs of the controlcard thus using these as inputs to the master.

801 Baud rate selection(BAUD RATE SELECT)

Value:125 kBaud (125 KBAUD) [20]250 kBaud (250 KBAUD) [21]500 kBaud (500 KBAUD) [22]

Function:This parameter displays the actual Baud rateof the devicenet option.

803 Time after bus error(BUS TIME OUT)

Value:1 - 99 sec ✭ 1 sec

804 Response after bus error

(TIME OUT FUNCT.)

Value:✭ Off (OFF) [0]

Freeze output frequency (FREEZE OUTPUT) [1]Stop with auto restart (STOP) [ 2]Output frequency = JOG frequency (JOGGING) [3]Output frequency = Max. freq. (MAX SPEED) [4]Stop with trip (STOP AND TRIP) [ 5]Control without DeviceNet( NO DEVICENET CONTROL) [6]Select set up 4 (SELECT SETUP 4) [ 7]

Function:The time out counter is triggered at the first receptionof a valid control word i.e. bit 10 = ok.1. CTW is not updated within the specified time2. Parameter 805 = "bit 10 = 0 ⇒ time out"

and bit 10 = "0"

The VLT remains in the timeout state until one ofthe following four conditions occurs:

1. Valid control word (Bit 10 = ok) is received and reset(Bus, terminals or local control panel) is activated(reset is only necessary when the time out functionStop w/trip is selected) ⇒ control via DeviceNetis resumed with the actual control word

2. Parameter 002 = Local ⇒ Local control vialocal control panel is enabled.

3. Parameter 928 = Disabled ⇒ Normal control viaterminals and RS485 is enabled.

4. Parameter 804 = Off ⇒ control via DeviceNetis resumed, with the control word usedlast being taken.

NOTEThe time out counter is reset and needs tobe triggered by a valid control word beforea new timeout can be activated

✭ = factory setting. () = display text [] = value for use in communication via serial communication port

MG.50.H4.22 - VLT is a registered Danfoss trademark20

Page 22: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Pro

gram

min

g

Description of choice:

- Save output frequency: Save (‘freeze’) the outputfrequency until communication resumes.

- Stop with auto restart: Stop with automatic restarton resumption of communication.

- Output frequency = Fixed speed frequency:Motor runs with fixed speed frequency untilresumption of communication.

- Output frequency = max. frequency: Motorruns with the maximum frequency untilresumption of communication.

- Stop with trip: Motor has stopped, a reset isnecessary for a restart, see explanation above.

- Control without DeviceNet: Control via DeviceNetis inactive; control is possible via the terminalsand/or the RS 485 standard interface untilcommunication resumes.

- Selection parameter setup 4: Parameter setup 4 isselected in parameter 004; the settings of parametersetup 4 are used. Parameter 004 is not reset to theoriginal value upon resumption of communication.

805 Function control word bit 10(BIT 10 FUNCTION)

Value:Without function (NO FUNCTION) [ 0]

✭ Bit 10 = 1 ⇒ CTW active(BIT 10 = 1 ⇒ CTW ACTIVE) [1]Bit 10 = 0 ⇒ CTW active(BIT 10 = 0 ⇒ CTW ACTIVE) [2]Bit 10 = 0⇒Timeout (BIT 10 = 0 ⇒ TIMEOUT ) [3]

Function:This is sometimes necessary since some mastersset all bits to 0 in different error situations. In thesecases it makes sense to change the function ofbit 10 so that the command to stop (coasting)goes to the VLT if all bits are 0.

Description of choice:

- Bit 10 = 1⇒ CTW active: If bit 10 = 0, the controlword and speed reference value are ignored.

- Bit 10 = 0⇒ CTW active: If bit 10 = 1, the controlword and speed reference value are ignored. Ifall bits of the control word are 0, the VLT willswitch to coasting in response hereto.

- Bit 10 = 0 ⇒ Timeout: If bit 10 = 0, the timeoutfunction selected in parameter 804 is activated.

- Without function: Bit 10 is ignored, i.e. the controlword and speed reference value are always valid.

✭ = factory setting. () = display text [] = value for use in communication via serial communication port

MG.50.H4.22 - VLT is a registered Danfoss trademark 21

Page 23: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

904 PPO selection(PPO TYPE SELECT)

Value:✭ PPO type 1 (PPO TYPE 1) [900 ]

PPO type 2 (PPO TYPE 2) [901 ]PPO type 3 (PPO TYPE 3) [902 ]PPO type 4 (PPO TYPE 4) [903 ]

Function:The choice of PPO type has to match the inputand output data of the master.

Description of choice:

900 = PPO type 1 (100/150):This PPO type has a 16 bit control word and a 16bit reference to controlling the VLT. The status wordand the actual speed value will also be returnedas 16 bit value. See Fieldbus profile.

901 = PPO type 2 (101/151):The same structure as in PPO type 1, but with 2additional free selectable process data.

902 = PPO type 3 (20/70):This profile fulfill the Instance 20/70 profile. SeeControl word under Instance 20/70.

903 = PPO type 4 (102/152):4 free selectable process data that can be chosenin parameter 915/916 PCD configuration.

915 PCD write configuration

(PCD CONFIG WRITE)

Value:Sub index 1 (PCD 1) [Parameter number]Sub index 2 (PCD 2) [Parameter number]

Function:Different parameters can be assigned to PCD 1-2 ifinstance 101/151 is selected in parameter 904 PPOSelection. The values in PCD 1-2 will be written to theselected parameters in the form of data values.

Description of choice:

The sequence of the subindixes corresponds to thesequence of the PCD in the PPO, i.e. subindex 1 =PCD 1, subindex 2 = PCD 2 etc. Each subindex maycontain the number of any VLT parameter.

Note that subindex 3 - 8 are having no function.

916 PCD read configuration

(PCD CONFIG READ)

Value:Sub index 1 (PCD 1) [Parameter number]Sub index 2 (PCD 2) [Parameter number]

Function:Different parameters can be assigned to PCD 1-2 ifinstance 101/151 is selected in parameter 904 PPOSelection. The values in PCD 1-2 will be read from theselected parameters in the form of data values.

Description of choice:

The sequence of subindices corresponds to thesequence of the PCD in the PPO, i.e.subindex 1 =PCD 1, subindex 2 = PCD 2 etc. Each subindex maycontain the number of any VLT parameter.

Note that subindex 3 - 8 are having no function.

918 User address(STATION ADDRESS)

Value:0 - 63 ✭ 63

Function:Readout of actual address of the devicenet option.

927 PCV operating authority

(PARAMETER EDIT)

Value:Without DeviceNet (DISABLE) [ 0]

✭ With DeviceNet (ENABLE) [1 ]

Function:The parameter channel PCV may be blocked sothat the modification of parameters through thischannel is not possible. Access through the standardRS 485 interface is still possible.

NOTEWhen parameters 927 and 928 are deactivated,the "Warning 34" in the display of the VLTwill also be suppressed.

✭ = factory setting. () = display text [] = value for use in communication via serial communication port

MG.50.H4.22 - VLT is a registered Danfoss trademark22

Page 24: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Pro

gram

min

g

Description of choice:

- Without DeviceNet: Parameter processingthrough the DeviceNet is not active.

- With DeviceNet: Parameter processing throughthe DeviceNet is active

928 Control authority

(PROCESS CONTROL)

Value:Without DeviceNet (DISABLE) [ 0]

✭ With DeviceNet (ENABLE) [1 ]

Function:The process control (adjustment of control word andspeed reference value and of the following variablePCD) can be blocked. Control through the control cardterminals is still possible via the terminals, depending onhow the parameters 502-508 have been set. Accessthrough the standard RS 485 is also still possible.

NOTEWhen parameters 927 and 928 are deactivated,the "Warning 34" in the display of the VLTwill also be suppressed.

Description of choice:

- Without DeviceNet: Process control throughthe DeviceNet is not active.

- With DeviceNet: Process control throughthe DeviceNet is active

NOTEThe motor may start without advance warningwhen parameter 928 is being changed andstart commands are present.

953 Warning messages

(WARNING PARAM.)

Value:Read only (16 bit binary code)No control panel access

Function:A bit is assigned to every warning (see the following list)

Bit In the following cases, bit is = "1"0 LSB Connection to the master is not OK12 FDL (field bus data security layer)

is not OK3 Command to erase data received4 Current value not updated5 FIFO overflow of the spontaneous

messages6 DeviceNet ASIC does not transmit7 Initialization of the DeviceNet option

is not OK8 Not used9 Not used10 Not used11 Not used12 Not used13 Not used14 Not used15 MSB Not used

967 Control Word(CONTROL WORD)

Value:16 bit binary code

Function:Parameter 967 is dedicated to sending a control wordto the VLT frequency converter when using explicitmessage. This parameter is not available via LCP.

✭ = factory setting. () = display text [] = value for use in communication via serial communication port

MG.50.H4.22 - VLT is a registered Danfoss trademark 23

Page 25: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

968 Status Word(STATUS WORD)

Value:Read only (16 bit binary code)

Function:Parameter 968 is dedicated to read the status wordfrom the VLT frequency converter when using explicitmessage. This parameter is not available via LCP.

970 Parameter setup selection

(EDIT SETUP SELECT)

Value:Factory setting () [0]Parameter setup 1 (SETUP 1) [ 1]Parameter setup 2 (SETUP 2) [ 2]Parameter setup 3 (SETUP 3) [ 3]Parameter setup 4 (SETUP 4) [ 4]

✭ Active set up (ACTIVE SETUP) [ 5]

Function:Like parameter 005 (described in the productmanual for the VLT 2800 series).

971 Save date values(STORE DATA VALUE)

Value:✭ Not active (OFF) [0]

Save active setup (STORE ACTIVE SETUP) [1]Save edit setup (STORE EDIT SETUP) [ 2]Save all setups (STORE ALL SETUPS) [ 3]Store Always (STORE ALWAYS) [ 4]

Function:Parameter values modified through DeviceNet areonly saved in RAM, i.e. the modifications are lostin the event of a power failure. This parameter isused to activate a function by means of which allparameter values are saved in EEPROM, preservingthem even in the case of a power failure.

Description of choice:

- Not active: The function is not active.- Save active setup: All parameter setups of

the active setup are saved in EEPROM. The

value returns to Not active after all parametervalues have been saved.

- Save edit setup: All parameter setups of thesetup being processed are saved in EEPROM.The value returns to Not active after all parametervalues have been saved.

- Save all setups: All parameter setups in all setupsare saved in EEPROM. The value returns to Notactive after all parameter values have been saved.

- Store Always: Each parameter write request willautomatically be stored in EEPROM.

NOTEPlease note that continous writing via explicitmessage may damage the EEPROM.

980–982 Defined parameters

(DEFINED PARAM.)

Value:Read only

Function:The three parameters contain a list of all parametersdefined in the VLT. Each of the three parameters canbe read as an array by means of a explicit message.

Each parameter contains up to 116 elements(parameter numbers). The number of parametersthat are in use (980, 981 and 982) depends onthe respective VLT configuration.

When a 0 is issued as a parameter number, the list ends.

990–992 Modified parameters

(MODIFI. PARAM.)

Value:Read only

Function:The three parameters contain a list of all parametersthat have been changed from the factory setting.Every one of the three parameters can be read as anarray with the help of the explicit read service. Thesubindices begin with 1 and follow the sequence ofthe parameter numbers. Each parameter contains upto 116 elements (parameter numbers). The numberof parameters that are in use (990, 991 and 992)

✭ = factory setting. () = display text [] = value for use in communication via serial communication port

MG.50.H4.22 - VLT is a registered Danfoss trademark24

Page 26: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Pro

gram

min

g

depends on how many parameters have been modifiedin comparison with the factory setting.

Pure read parameters (Read only), such as dataoutput parameters, are not logged as modifiedeven if they are changing.

When a 0 is issued as a parameter number, the list ends.

✭ = factory setting. () = display text [] = value for use in communication via serial communication port

MG.50.H4.22 - VLT is a registered Danfoss trademark 25

Page 27: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

■ Warning and Alarm MessagesThere is a clear distinction between alarms andwarnings. In the case of an alarm, The VLT will entera fault condition. After the cause for the alarm hasbeen cleared, the master will have to acknowledge thealarm message for the VLT to start operating again. Awarning on the other hand may come when a warningcondition appears, and disappear when conditionsreturn to normal without interfering with the process.

■ WarningsAny warning within the VLT is represented by asingle bit within a warning word. A warning wordis always an action parameter. Bit status FALSE [0]means no warning, while bit status TRUE [1] meanswarning. To each bit and each bit status there is acorresponding text string. In addition to the warningword message the master will also be notified througha change of bit 7 in the Status Word.

■ AlarmsFollowing an Alarm message the VLT will enter Faultcondition. Only after the fault has been alleviated andthe master has acknowledged the alarm messageby setting bit 3 in the Control Word, can the VLTresume operation. Any warning within the VLT isrepresented by a single bit within a warning word.A warning word is always an action parameter. Bitstatus FALSE [0] means no fault, while bit statusTRUE [1] means fault. To each bit and each bitstatus there is a corresponding text string.

✭ = factory setting. () = display text [] = value for use in communication via serial communication port

MG.50.H4.22 - VLT is a registered Danfoss trademark26

Page 28: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Pro

gram

min

g

■ Factory Settings

PNU Parameter Factory setting Changes 4-Setup Conversion Data# description during operation index type001 LLLLaaaannnngggguuuuaaaaggggeeee English Yes No 0 5002 LLLLooooccccaaaallll////rrrreeeemmmmooootttteeee ccccoooonnnnttttrrrroooollll Remote control Yes Yes 0 5003 LLLLooooccccaaaallll rrrreeeeffffeeeerrrreeeennnncccceeee 000.000 Yes Yes -3 4004 AAAAccccttttiiiivvvveeee sssseeeettttuuuupppp Setup 1 Yes No 0 5005 PPPPrrrrooooggggrrrraaaammmmmmmmiiiinnnngggg sssseeeettttuuuupppp Active setup Yes No 0 5006 CCCCooooppppyyyyiiiinnnngggg ooooffff sssseeeettttuuuuppppssss No copying No No 0 5007 LLLLCCCCPPPP ccccooooppppyyyy No copying No No 0 5008 DDDDiiiissssppppllllaaaayyyy ssssccccaaaallll iiiinnnngggg ooooffff mmmmoooottttoooorrrr ffffrrrreeeeqqqquuuueeeennnnccccyyyy 1 Yes Yes -2 6009 DDDDiiiissssppppllllaaaayyyy llll iiiinnnniiiieeee 2222 Frequency [Hz] Yes Yes 0 5010 DDDDiiiissssppppllllaaaayyyy llll iiiinnnneeee 1111....1111 Reference [%] Yes Yes 0 5011 DDDDiiiissssppppllllaaaayyyy llll iiiinnnneeee 1111....2222 Motor current [A] Yes Yes 0 5012 DDDDiiiissssppppllllaaaayyyy llll iiiinnnneeee 1111....3333 Power [kW] Yes Yes 0 5013 LLLLooooccccaaaallll ccccoooonnnnttttrrrroooollll////ccccoooonnnnffffiiiigggguuuurrrraaaa LCP digital control/as par.100 Yes Yes 0 5014 LLLLooooccccaaaallll ssssttttoooopppp Possible Yes Yes 0 5015 LLLLooooccccaaaallll jjjjoooogggg Not possible Yes Yes 0 5016 LLLLooooccccaaaallll rrrreeeevvvveeeerrrrssssiiiinnnngggg Not possible Yes Yes 0 5017 LLLLooooccccaaaallll rrrreeeesssseeeetttt ooooffff ttttrrrriiiipppp Possible Yes Yes 0 5018 LLLLoooocccckkkk ffffoooorrrr ddddaaaattttaaaa cccchhhhaaaannnnggggeeee Not locked Yes Yes 0 5019 OOOOppppeeeerrrraaaattttiiiinnnngggg ssssttttaaaatttteeee aaaatttt ppppoooowwwweeeerrrr----uuuupppp,,,, llllooooccccaaaallll

ccccoooonnnnttttrrrroooollll

Forced stop, use saved ref. Yes Yes 0 5

Changes during operation:"Yes" means that the parameter can be changed,while the VLT frequency converter is in operation."No" means that the VLT frequency converter mustbe stopped before a change can be made.

4-Setup:"Yes" means that the parameter can be programmedindividually in each of the four setups, i.e. thesame parameter can have four different datavalues. "No" means that the data value will bethe same in all four setups.

Conversion index:This number refers to a conversion figure tobe used when writing or reading by means ofa VLT frequency converter.

Conversion index Conversion factor

74 0.1

2 100

1 10

0 1

-1 0.1

-2 0.01

-3 0.001

-4 0.0001

Data type:

Data type shows the type and length of the telegram.

Data type Description

3 Integer 16

4 Integer 32

5 Unsigned 8

6 Unsigned 16

7 Unsigned 32

9 Text string

MG.50.H4.22 - VLT is a registered Danfoss trademark 27

Page 29: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

PNU Parameter Factory setting Changes 4-Setup Conversion Data

# description during operation index type

100 CCCCoooonnnnffffiiiigggguuuurrrraaaattttiiiioooonnnn Speed control, open loop No Yes 0 5

101 TTTToooorrrrqqqquuuueeee cccchhhhaaaarrrraaaacccctttteeeerrrriiiissssttttiiiiccccssss High - constant torque Yes Yes 0 5

102 MMMMoooottttoooorrrr ppppoooowwwweeeerrrr Depends on the unit No Yes 1 6

103 MMMMoooottttoooorrrr vvvvoooollllttttaaaaggggeeee Depends on the unit No Yes 0 6

104 MMMMoooottttoooorrrr ffffrrrreeeeqqqquuuueeeennnnccccyyyy 50 Hz / 60 Hz No Yes 0 6

105 MMMMoooottttoooorrrr ccccuuuurrrrrrrreeeennnntttt Depends on the unit No Yes -2 7

106 RRRRaaaatttteeeedddd mmmmoooottttoooorrrr ssssppppeeeeeeeedddd Depends on the unit No Yes 0 6

107 AAAAuuuuttttoooommmmaaaattttiiiicccc mmmmoooottttoooorrrr aaaaddddaaaappppttttaaaattttiiiioooonnnn,,,, AAAAMMMMAAAA Adaptation off No No 0 5

108 SSSSttttaaaattttoooorrrr rrrreeeessssiiiissssttttoooorrrr Depends on the unit No Yes -4 7

109 SSSSttttaaaattttoooorrrr rrrreeeeaaaaccccttttaaaannnncccceeee Depends on the unit No Yes -2 7

110 MMMMoooottttoooorrrr mmmmaaaaggggnnnneeeettttiiiizzzziiiinnnngggg,,,, 0000 rrrrppppmmmm 100 % Yes Yes 0 6

111 MMMMiiiinnnn.... ffffrrrreeeeqqqquuuueeeennnnccccyyyy nnnnoooorrrrmmmmaaaallll mmmmaaaaggggnnnneeeettttiiiizzzziiiinnnngggg 1.0 Hz Yes Yes -1 6

112

113 LLLLooooaaaadddd ccccoooommmmppppeeeennnnssssaaaattttiiiioooonnnn aaaatttt lllloooowwww ssssppppeeeeeeeedddd 100 % Yes Yes 0 6

114 LLLLooooaaaadddd ccccoooommmmppppeeeennnnssssaaaattttiiiioooonnnn aaaatttt hhhhiiiigggghhhh ssssppppeeeeeeeedddd 100 % Yes Yes 0 6

115 SSSSllll iiiipppp ccccoooommmmppppeeeennnnssssaaaattttiiiioooonnnn 100 % Yes Yes 0 3

116 SSSSllll iiiipppp ccccoooommmmppppeeeennnnssssaaaattttiiiioooonnnn ttttiiiimmmmeeee ccccoooonnnnssssttttaaaannnntttt 0.50 s Yes Yes -2 6

117 RRRReeeessssoooonnnnaaaannnncccceeee ddddaaaammmmppppeeeennnniiiinnnngggg 100 % Yes Yes 0 6

118 RRRReeeessssoooonnnnaaaannnncccceeee ddddaaaammmmppppeeeennnniiiinnnngggg ttttiiiimmmmeeee ccccoooonnnnssssttttaaaannnntttt 5 ms Yes Yes -3 6

119 HHHHiiiigggghhhh ssssttttaaaarrrrtttt iiiinnnngggg ttttoooorrrrqqqquuuueeee 0.0 sec. Yes Yes -1 5

120 SSSSttttaaaarrrrtttt ddddeeeellllaaaayyyy 0.0 sec. Yes Yes -1 5

121 SSSSttttaaaarrrrtttt ffffuuuunnnnccccttttiiiioooonnnn Coasting in start delay time Yes Yes 0 5

122 FFFFuuuunnnnccccttttiiiioooonnnn aaaatttt ssssttttoooopppp Coasting Yes Yes 0 5

123 MMMMiiiinnnn.... ffffrrrreeeeqqqquuuueeeennnnccccyyyy ffffoooorrrr aaaaccccttttiiiivvvvaaaattttiiiinnnngggg ffffuuuunnnnccccttttiiiioooonnnn

aaaatttt ssssttttoooopppp

0.0 Hz Yes Yes -1 5

124 DDDDCCCC hhhhoooollllddddiiiinnnngggg ccccuuuurrrrrrrreeeennnntttt 50 % Yes Yes 0 6

125 DDDDCCCC bbbbrrrraaaakkkkiiiinnnngggg ccccuuuurrrrrrrreeeennnntttt 50 % Yes Yes 0 6

126 DDDDCCCC bbbbrrrraaaakkkkiiiinnnngggg ttttiiiimmmmeeee 10.0 sec. Yes Yes -1 6

127 DDDDCCCC bbbbrrrraaaakkkkeeee ccccuuuutttt----iiiinnnn ffffrrrreeeeqqqquuuueeeennnnccccyyyy Off Yes Yes -1 6

128 MMMMoooottttoooorrrr tttthhhheeeerrrrmmmmaaaallll pppprrrrooootttteeeeccccttttiiiioooonnnn No protection Yes Yes 0 5

129 EEEExxxxtttteeeerrrrnnnnaaaallll mmmmoooottttoooorrrr ffffaaaannnn No Yes Yes 0 5

130 SSSSttttaaaarrrrtttt ffffrrrreeeeqqqquuuueeeennnnccccyyyy 0.0 Hz Yes Yes -1 5

131 IIIInnnniiiitttt iiiiaaaallll vvvvoooollllttttaaaaggggeeee 0.0 V Yes Yes -1 6

MG.50.H4.22 - VLT is a registered Danfoss trademark28

Page 30: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Pro

gram

min

g

PNU Parameter Factory setting Changes 4-Setup Conversion Data

# description during operation index type

200 OOOOuuuuttttppppuuuutttt ffffrrrreeeeqqqquuuueeeennnnccccyyyy rrrraaaannnnggggeeee////ddddiiiirrrreeeeccccttttiiiioooonnnn Only clockwise, 0-132 Hz No Yes 0 5

201 OOOOuuuuttttppppuuuutttt ffffrrrreeeeqqqquuuueeeennnnccccyyyy lllloooowwww llll iiiimmmmiiiitttt 0.0 Hz Yes Yes -1 6

202 OOOOuuuuttttppppuuuutttt ffffrrrreeeeqqqquuuueeeennnnccccyyyy hhhhiiiigggghhhh llll iiiimmmmiiiitttt 66 / 132 Hz Yes Yes -1 6

203 RRRReeeeffffeeeerrrreeeennnncccceeee////ffffeeeeeeeeddddbbbbaaaacccckkkk aaaarrrreeeeaaaa Min - max Yes Yes 0 5

204 MMMMiiiinnnniiiimmmmuuuummmm rrrreeeeffffeeeerrrreeeennnncccceeee 0.000 Yes Yes -3 4

205 MMMMaaaaxxxxiiiimmmmuuuummmm rrrreeeeffffeeeerrrreeeennnncccceeee 50.000 Yes Yes -3 4

206 RRRRaaaammmmpppp ttttyyyyppppeeee Linear Yes Yes 0 5

207 RRRRaaaammmmpppp----uuuupppp ttttiiiimmmmeeee 1111 Depends on unit Yes Yes -2 7

208 RRRRaaaammmmpppp----ddddoooowwwwnnnn ttttiiiimmmmeeee 1111 Depends on unit Yes Yes -2 7

209 RRRRaaaammmmpppp----uuuupppp ttttiiiimmmmeeee 2222 Depends on unit Yes Yes -2 7

210 RRRRaaaammmmpppp----ddddoooowwwwnnnn ttttiiiimmmmeeee 2222 Depends on unit Yes Yes -2 7

211 JJJJoooogggg rrrraaaammmmpppp ttttiiiimmmmeeee Depends on unit Yes Yes -2 7

212 QQQQuuuuiiiicccckkkk ssssttttoooopppp rrrraaaammmmpppp----ddddoooowwwwnnnn ttttiiiimmmmeeee Depends on unit Yes Yes -2 7

213 JJJJoooogggg ffffrrrreeeeqqqquuuueeeennnnccccyyyy 10.0 Hz Yes Yes -1 6

214 RRRReeeeffffeeeerrrreeeennnncccceeee ffffuuuunnnnccccttttiiiioooonnnn Sum Yes Yes 0 5

215 PPPPrrrreeeesssseeeetttt rrrreeeeffffeeeerrrreeeennnncccceeee 1111 0.00 % Yes Yes -2 3

216 PPPPrrrreeeesssseeeetttt rrrreeeeffffeeeerrrreeeennnncccceeee 2222 0.00 % Yes Yes -2 3

217 PPPPrrrreeeesssseeeetttt rrrreeeeffffeeeerrrreeeennnncccceeee 3333 0.00 % Yes Yes -2 3

218 PPPPrrrreeeesssseeeetttt rrrreeeeffffeeeerrrreeeennnncccceeee 4444 0.00 % Yes Yes -2 3

219 CCCCaaaattttcccchhhh uuuupppp////sssslllloooowwww ddddoooowwwwnnnn vvvvaaaalllluuuueeee 0.00 % Yes Yes -2 6

220

221 TTTToooorrrrqqqquuuueeee llll iiiimmmmiiiitttt ffffoooorrrr mmmmoooottttoooorrrr mmmmooooddddeeee 160 % Yes Yes -1 6

222 TTTToooorrrrqqqquuuueeee llll iiiimmmmiiiitttt ffffoooorrrr rrrreeeeggggeeeennnneeeerrrraaaattttiiiivvvveeee

ooooppppeeeerrrraaaattttiiiioooonnnn

160 % Yes Yes -1 6

223 WWWWaaaarrrrnnnniiiinnnngggg:::: LLLLoooowwww ccccuuuurrrrrrrreeeennnntttt 0.0 A Yes Yes -1 6

224 WWWWaaaarrrrnnnniiiinnnngggg:::: HHHHiiiigggghhhh ccccuuuurrrrrrrreeeennnntttt IVLT,MAX Yes Yes -1 6

225 WWWWaaaarrrrnnnniiiinnnngggg:::: LLLLoooowwww ffffrrrreeeeqqqquuuueeeennnnccccyyyy 0.0 Hz Yes Yes -1 6

226 WWWWaaaarrrrnnnniiiinnnngggg:::: HHHHiiiigggghhhh ffffrrrreeeeqqqquuuueeeennnnccccyyyy 132.0 Hz Yes Yes -1 6

227 WWWWaaaarrrrnnnniiiinnnngggg:::: LLLLoooowwww ffffeeeeeeeeddddbbbbaaaacccckkkk -4000.000 Yes -3 4

228 WWWWaaaarrrrnnnniiiinnnngggg:::: HHHHiiiigggghhhh ffffeeeeeeeeddddbbbbaaaacccckkkk 4000.000 Yes -3 4

229 FFFFrrrreeeeqqqquuuueeeennnnccccyyyy bbbbyyyyppppaaaassssssss,,,, bbbbaaaannnnddddwwwwiiiiddddtttthhhh OFF Yes Yes 0 6

230 FFFFrrrreeeeqqqquuuueeeennnnccccyyyy bbbbyyyyppppaaaassssssss 1111 0.0 Hz Yes Yes -1 6

231 FFFFrrrreeeeqqqquuuueeeennnnccccyyyy bbbbyyyyppppaaaassssssss 2222 0.0 Hz Yes Yes -1 6

232 FFFFrrrreeeeqqqquuuueeeennnnccccyyyy bbbbyyyyppppaaaassssssss 3333 0.0 Hz Yes Yes -1 6

233 FFFFrrrreeeeqqqquuuueeeennnnccccyyyy bbbbyyyyppppaaaassssssss 4444 0.0 Hz Yes Yes -1 6

234 MMMMoooottttoooorrrr pppphhhhaaaasssseeee mmmmoooonnnniiiittttoooorrrr Enable Yes Yes 0 5

MG.50.H4.22 - VLT is a registered Danfoss trademark 29

Page 31: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

PNU Parameter Factory setting Changes 4-Setup Conversion Data

# description during operation index type

300 TTTTeeeerrrrmmmmiiiinnnnaaaallll 11116666,,,, iiiinnnnppppuuuutttt Reset Yes Yes 0 5

301 TTTTeeeerrrrmmmmiiiinnnnaaaallll 11117777,,,, iiiinnnnppppuuuutttt Freeze reference Yes Yes 0 5

302 TTTTeeeerrrrmmmmiiiinnnnaaaallll 11118888 SSSSttttaaaarrrrtttt,,,, iiiinnnnppppuuuutttt Start Yes Yes 0 5

303 TTTTeeeerrrrmmmmiiiinnnnaaaallll 11119999,,,, iiiinnnnppppuuuutttt Reversing Yes Yes 0 5

304 TTTTeeeerrrrmmmmiiiinnnnaaaallll 22227777,,,, iiiinnnnppppuuuutttt Coasting stop, inverse Yes Yes 0 5

305 TTTTeeeerrrrmmmmiiiinnnnaaaallll 22229999,,,, iiiinnnnppppuuuutttt Jog Yes Yes 0 5

306 TTTTeeeerrrrmmmmiiiinnnnaaaallll 33332222,,,, iiiinnnnppppuuuutttt Choice of setup, msb/speed up Yes Yes 0 5

307 TTTTeeeerrrrmmmmiiiinnnnaaaallll 33333333,,,, iiiinnnnppppuuuutttt Choice of setup, lsb/speed down Yes Yes 0 5

308 TTTTeeeerrrrmmmmiiiinnnnaaaallll 55553333,,,, aaaannnnaaaalllloooogggguuuueeee iiiinnnnppppuuuutttt vvvvoooollllttttaaaaggggeeee Reference Yes Yes 0 5

309 TTTTeeeerrrrmmmmiiiinnnnaaaallll 55553333,,,, mmmmiiiinnnn.... ssssccccaaaallll iiiinnnngggg 0.0 V Yes Yes -1 5

310 TTTTeeeerrrrmmmmiiiinnnnaaaallll 55553333,,,, mmmmaaaaxxxx.... ssssccccaaaallll iiiinnnngggg 10.0 V Yes Yes -1 5

311 TTTTeeeerrrrmmmmiiiinnnnaaaallll 55554444,,,, aaaannnnaaaalllloooogggguuuueeee iiiinnnnppppuuuutttt vvvvoooollllttttaaaaggggeeee No operation Yes Yes 0 5

312 TTTTeeeerrrrmmmmiiiinnnnaaaallll 55554444,,,, mmmmiiiinnnn.... ssssccccaaaallll iiiinnnngggg 0.0 V Yes Yes -1 5

313 TTTTeeeerrrrmmmmiiiinnnnaaaallll 55554444,,,, mmmmaaaaxxxx.... ssssccccaaaallll iiiinnnngggg 10.0 V Yes Yes -1 5

314 TTTTeeeerrrrmmmmiiiinnnnaaaallll 66660000,,,, aaaannnnaaaalllloooogggguuuueeee iiiinnnnppppuuuutttt ccccuuuurrrrrrrreeeennnntttt Reference Yes Yes 0 5

315 TTTTeeeerrrrmmmmiiiinnnnaaaallll 66660000,,,, mmmmiiiinnnn.... ssssccccaaaallll iiiinnnngggg 0.0 mA Yes Yes -4 5

316 TTTTeeeerrrrmmmmiiiinnnnaaaallll 66660000,,,, mmmmaaaaxxxx.... ssssccccaaaallll iiiinnnngggg 20.0 mA Yes Yes -4 5

317 TTTTiiiimmmmeeee oooouuuutttt 10 sec. Yes Yes 0 5

318 FFFFuuuunnnnccccttttiiiioooonnnn aaaafffftttteeeerrrr ttttiiiimmmmeeee oooouuuutttt Off Yes Yes 0 5

319 TTTTeeeerrrrmmmmiiiinnnnaaaallll 44442222,,,, oooouuuuttttppppuuuutttt 0 - IMAX ⇒ 0-20 mA Yes Yes 0 5

320 TTTTeeeerrrrmmmmiiiinnnnaaaallll 44442222,,,, oooouuuuttttppppuuuutttt,,,, ppppuuuullllsssseeee ssssccccaaaallll iiiinnnngggg 5000 Hz Yes Yes 0 6

321 TTTTeeeerrrrmmmmiiiinnnnaaaallll 44445555,,,, oooouuuuttttppppuuuutttt 0 - fMAX ⇒ 0-20 mA Yes Yes 0 5

322 TTTTeeeerrrrmmmmiiiinnnnaaaallll 44445555,,,, oooouuuuttttppppuuuutttt,,,, ppppuuuullllsssseeee ssssccccaaaallll iiiinnnngggg 5000 Hz Yes Yes 0 6

323 RRRReeeellllaaaayyyy 00001111,,,, oooouuuuttttppppuuuutttt Ready - no thermal warning Yes Yes 0 5

324 RRRReeeellllaaaayyyy 00001111,,,, OOOONNNN ddddeeeellllaaaayyyy 0.00 sec. Yes Yes -2 6

325 RRRReeeellllaaaayyyy 00001111,,,, OOOOFFFFFFFF ddddeeeellllaaaayyyy 0.00 sec. Yes Yes -2 6

326 RRRReeeellllaaaayyyy 00004444,,,, oooouuuuttttppppuuuutttt Ready - remote control Yes Yes 0 5

327 PPPPuuuullllsssseeee rrrreeeeffffeeeerrrreeeennnncccceeee,,,, mmmmaaaaxxxx.... ffffrrrreeeeqqqquuuueeeennnnccccyyyy 5000 Hz Yes Yes 0 6

328 PPPPuuuullllsssseeee ffffeeeeeeeeddddbbbbaaaacccckkkk,,,, mmmmaaaaxxxx.... ffffrrrreeeeqqqquuuueeeennnnccccyyyy 25000 Hz Yes Yes 0 6

329 EEEEnnnnccccooooddddeeeerrrr ffffeeeeeeeeddddbbbbaaaacccckkkk ppppuuuullllsssseeee////rrrreeeevvvv.... 1024 Yes Yes 0 6

330 FFFFrrrreeeeeeeezzzzeeee rrrreeeeffffeeeerrrreeeennnncccceeee////oooouuuuttttppppuuuutttt ffffuuuunnnnccccttttiiiioooonnnn No operation Yes No 0 5

MG.50.H4.22 - VLT is a registered Danfoss trademark30

Page 32: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Pro

gram

min

g

PNU Parameter Factory setting Changes 4-Setup Conversion Data# description during operation index type400 BBBBrrrraaaakkkkeeee ffffuuuunnnnccccttttiiiioooonnnn////oooovvvveeeerrrrvvvvoooollllttttaaaaggggeeee ccccoooonnnnttttrrrroooollll Off Yes No 0 5401 BBBBrrrraaaakkkkeeee rrrreeeessssiiiissssttttoooorrrr,,,, oooohhhhmmmm Depends on the unit Yes No -1 6402 BBBBrrrraaaakkkkeeee ppppoooowwwweeeerrrr llll iiiimmmmiiiitttt,,,, kkkkWWWW Depends on the unit Yes No 2 6403 PPPPoooowwwweeeerrrr mmmmoooonnnniiiittttoooorrrriiiinnnngggg On Yes No 0 5404 BBBBrrrraaaakkkkeeee cccchhhheeeecccckkkk Off Yes No 0 5405 RRRReeeesssseeeetttt ffffuuuunnnnccccttttiiiioooonnnn Manual reset Yes Yes 0 5406 AAAAuuuuttttoooommmmaaaattttiiiicccc rrrreeeessssttttaaaarrrrtttt tttt iiiimmmmeeee 5 sec. Yes Yes 0 5407 MMMMaaaaiiiinnnnssss FFFFaaaaiiii lllluuuurrrreeee No function Yes Yes 0 5408 QQQQuuuuiiiicccckkkk ddddiiiisssscccchhhhaaaarrrrggggeeee Not possible Yes Yes 0 5409 TTTTrrrriiiipppp ddddeeeellllaaaayyyy ttttoooorrrrqqqquuuueeee Off Yes Yes 0 5410 TTTTrrrriiiipppp ddddeeeellllaaaayyyy----iiiinnnnvvvveeeerrrrtttteeeerrrr Depends on type of unit Yes Yes 0 5411 SSSSwwwwiiiittttcccchhhhiiiinnnngggg ffffrrrreeeeqqqquuuueeeennnnccccyyyy Depends on type of unit Yes Yes 2 6412 OOOOuuuuttttppppuuuutttt ffffrrrreeeeqqqquuuueeeennnnccccyyyy ddddeeeeppppeeeennnnddddeeeennnntttt sssswwwwiiiittttcccchhhhiiiinnnngggg

ffffrrrreeeeqqqquuuueeeennnnccccyyyy

Not possible Yes Yes 0 5

413 OOOOvvvveeeerrrrmmmmoooodddduuuullllaaaattttiiiioooonnnn ffffuuuunnnnccccttttiiiioooonnnn On Yes Yes -1 5414 MMMMiiiinnnniiiimmmmuuuummmm ffffeeeeeeeeddddbbbbaaaacccckkkk 0.000 Yes Yes -3 4415 MMMMaaaaxxxxiiiimmmmuuuummmm ffffeeeeeeeeddddbbbbaaaacccckkkk 1500.000 Yes Yes -3 4416 PPPPrrrroooocccceeeessssssss uuuunnnniiiitttt % Yes Yes 0 5417 SSSSppppeeeeeeeedddd PPPPIIIIDDDD pppprrrrooooppppoooorrrrtttt iiiioooonnnnaaaallll ggggaaaaiiiinnnn 0.015 Yes Yes -3 6418 SSSSppppeeeeeeeedddd PPPPIIIIDDDD iiiinnnntttteeeeggggrrrraaaattttiiiioooonnnn ttttiiiimmmmeeee 8 ms Yes Yes -4 7419 SSSSppppeeeeeeeedddd PPPPIIIIDDDD ddddiiiiffffffffeeeerrrreeeennnnttttiiiiaaaattttiiiioooonnnn ttttiiiimmmmeeee 30 ms Yes Yes -4 6420 SSSSppppeeeeeeeedddd PPPPIIIIDDDD ddddiiii ffffffff.... ggggaaaaiiiinnnn rrrraaaattttiiiioooo 5.0 Yes Yes -1 6421 SSSSppppeeeeeeeedddd PPPPIIIIDDDD lllloooowwww----ppppaaaassssssss ffffiiii llll tttteeeerrrr 10 ms Yes Yes -4 6422 UUUU 0000 vvvvoooollllttttaaaaggggeeee aaaatttt 0000 HHHHzzzz 20.0 V Yes Yes -1 6423 UUUU 1111 vvvvoooollllttttaaaaggggeeee parameter 103 Yes Yes -1 6424 FFFF 1111 ffffrrrreeeeqqqquuuueeeennnnccccyyyy parameter 104 Yes Yes -1 6425 UUUU 2222 vvvvoooollllttttaaaaggggeeee parameter 103 Yes Yes -1 6426 FFFF 2222 ffffrrrreeeeqqqquuuueeeennnnccccyyyy parameter 104 Yes Yes -1 6427 UUUU 3333 vvvvoooollllttttaaaaggggeeee parameter 103 Yes Yes -1 6428 FFFF 3333 ffffrrrreeeeqqqquuuueeeennnnccccyyyy parameter 104 Yes Yes -1 6429 UUUU 4444 vvvvoooollllttttaaaaggggeeee parameter 103 Yes Yes -1 6430 FFFF 4444 ffffrrrreeeeqqqquuuueeeennnnccccyyyy parameter 104 Yes Yes -1 6431 UUUU 5555 vvvvoooollllttttaaaaggggeeee parameter 103 Yes Yes -1 6432 FFFF 5555 ffffrrrreeeeqqqquuuueeeennnnccccyyyy parameter 104 Yes Yes -1 6433 TTTToooorrrrqqqquuuueeee pppprrrrooooppppoooorrrrtttt iiiioooonnnnaaaallll ggggaaaaiiiinnnn 100% Yes Yes 0 6434 TTTToooorrrrqqqquuuueeee iiiinnnntttteeeeggggrrrraaaallll tttt iiiimmmmeeee 0.02 sec. Yes Yes -3 7437 PPPPrrrroooocccceeeessssssss PPPPIIIIDDDD NNNNoooorrrrmmmmaaaallll////iiiinnnnvvvveeeerrrrsssseeee ccccoooonnnnttttrrrroooollll Normal Yes Yes 0 5438 PPPPrrrroooocccceeeessssssss PPPPIIIIDDDD aaaannnnttttiiii wwwwiiiinnnndddduuuupppp On Yes Yes 0 5439 PPPPrrrroooocccceeeessssssss PPPPIIIIDDDD ssssttttaaaarrrrtttt ffffrrrreeeeqqqquuuueeeennnnccccyyyy parameter 201 Yes Yes -1 6440 PPPPrrrroooocccceeeessssssss PPPPIIIIDDDD pppprrrrooooppppoooorrrrttttiiiioooonnnnaaaallll ggggaaaaiiiinnnn 0.01 Yes Yes -2 6441 PPPPrrrroooocccceeeessssssss PPPPIIIIDDDD iiiinnnntttteeeeggggrrrraaaallll tttt iiiimmmmeeee 9999.99 sec. (OFF) Yes Yes -2 7442 PPPPrrrroooocccceeeessssssss PPPPIIIIDDDD ddddiiiiffffffffeeeerrrreeeennnnttttiiiiaaaattttiiiioooonnnn ttttiiiimmmmeeee 0.00 sec. (OFF) Yes Yes -2 6443 PPPPrrrroooocccceeeessssssss PPPPIIIIDDDD ddddiiiiffffffff.... ggggaaaaiiiinnnn llll iiiimmmmiiiitttt 5.0 Yes Yes -1 6444 PPPPrrrroooocccceeeessssssss PPPPIIIIDDDD lllloooowwwwppppaaaassssssss ffffiiii lllltttteeeerrrr tttt iiiimmmmeeee 0.01 Yes Yes -2 6445 FFFFllllyyyyiiiinnnngggg ssssttttaaaarrrrtttt Disable Yes Yes 0 5446 SSSSwwwwiiiittttcccchhhhiiiinnnngggg ppppaaaatttttttteeeerrrrnnnn SFAVM Yes Yes 0 5447 TTTToooorrrrqqqquuuueeee ccccoooommmmppppeeeennnnssssaaaattttiiiioooonnnn 100% Yes Yes 0 3448 GGGGeeeeaaaarrrr rrrraaaattttiiiioooo 1 No Yes -2 4449 FFFFrrrriiiiccccttttiiiioooonnnn lllloooossssssss 0% No Yes -2 6450 MMMMaaaaiiiinnnnssss vvvvoooollll ttttaaaaggggeeee aaaatttt mmmmaaaaiiiinnnnssss ffffaaaauuuulllltttt Depends on unit Yes Yes 0 6

MG.50.H4.22 - VLT is a registered Danfoss trademark 31

Page 33: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

PNU Parameter Factory setting Changes 4-Setup Conversion Data

# description during operation index type

500 AAAAddddddddrrrreeeessssssss 1 Yes No 0 6

501 BBBBaaaauuuuddddrrrraaaatttteeee 9600 Baud Yes No 0 5

502 CCCCooooaaaassssttttiiiinnnngggg Logic or Yes Yes 0 5

503 QQQQuuuuiiiicccckkkk----ssssttttoooopppp Logic or Yes Yes 0 5

504 DDDDCCCC----bbbbrrrraaaakkkkeeee Logic or Yes Yes 0 5

505 SSSSttttaaaarrrrtttt Logic or Yes Yes 0 5

506 RRRReeeevvvveeeerrrrssssiiiinnnngggg Logic or Yes Yes 0 5

507 SSSSeeeelllleeeeccccttttiiiioooonnnn ooooffff sssseeeettttuuuupppp Logic or Yes Yes 0 5

508 SSSSeeeelllleeeeccccttttiiiioooonnnn ooooffff ssssppppeeeeeeeedddd Logic or Yes Yes 0 5

509 BBBBuuuussss jjjjoooogggg 1111 10.0 Hz Yes Yes -1 6

510 BBBBuuuussss jjjjoooogggg 2222 10.0 Hz Yes Yes -1 6

511

512 TTTTeeeelllleeeeggggrrrraaaammmm pppprrrrooooffffiiii lllleeee FC Drive No Yes 0 5

513 BBBBuuuussss ttttiiiimmmmeeee iiiinnnntttteeeerrrrvvvvaaaallll 1 sec. Yes Yes 0 5

514 BBBBuuuussss ttttiiiimmmmeeee iiiinnnntttteeeerrrrvvvvaaaallll ffffuuuunnnnccccttttiiiioooonnnn Off Yes Yes 0 5

515 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: RRRReeeeffffeeeerrrreeeennnncccceeee %%%% No No -1 3

516 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: RRRReeeeffffeeeerrrreeeennnncccceeee uuuunnnniiiitttt No No -3 4

517 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: FFFFeeeeeeeeddddbbbbaaaacccckkkk No No -3 4

518 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: FFFFrrrreeeeqqqquuuueeeennnnccccyyyy No No -1 6

519 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: FFFFrrrreeeeqqqquuuueeeennnnccccyyyy xxxx SSSSccccaaaallll iiiinnnngggg No No -2 7

520 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: CCCCuuuurrrrrrrreeeennnntttt No No -2 7

521 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: TTTToooorrrrqqqquuuueeee No No -1 3

522 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: PPPPoooowwwweeeerrrr,,,, kkkkWWWW No No -1 7

523 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: PPPPoooowwwweeeerrrr,,,, HHHHPPPP No No -2 7

524 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: MMMMoooottttoooorrrr vvvvoooollllttttaaaaggggeeee No No -1 6

525 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: DDDDCCCC llll iiiinnnnkkkk vvvvoooollllttttaaaaggggeeee No No 0 6

526 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: MMMMoooottttoooorrrr tttteeeemmmmpppp.... No No 0 5

527 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: VVVVLLLLTTTT tttteeeemmmmpppp.... No No 0 5

528 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: DDDDiiiiggggiiiittttaaaallll iiiinnnnppppuuuutttt No No 0 5

529 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: TTTTeeeerrrrmmmmiiiinnnnaaaallll 55553333,,,, aaaannnnaaaalllloooogggguuuueeee iiiinnnnppppuuuutttt No No -2 3

530 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: TTTTeeeerrrrmmmmiiiinnnnaaaallll 55554444,,,, aaaannnnaaaalllloooogggguuuueeee iiiinnnnppppuuuutttt No No -2 3

531 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: TTTTeeeerrrrmmmmiiiinnnnaaaallll 66660000,,,, aaaannnnaaaalllloooogggguuuueeee iiiinnnnppppuuuutttt No No -5 3

532 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: PPPPuuuullllsssseeee rrrreeeeffffeeeerrrreeeennnncccceeee No No -1 7

533 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: EEEExxxxtttteeeerrrrnnnnaaaallll rrrreeeeffffeeeerrrreeeennnncccceeee %%%% No No -1 3

534 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: SSSSttttaaaattttuuuussss wwwwoooorrrrdddd,,,, bbbbiiiinnnnaaaarrrryyyy No No 0 6

535 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: BBBBrrrraaaakkkkeeee ppppoooowwwweeeerrrr////2222 mmmmiiiinnnn.... No No 2 6

536 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: BBBBrrrraaaakkkkeeee ppppoooowwwweeeerrrr////sssseeeecccc.... No No 2 6

537 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: HHHHeeeeaaaatttt ssssiiiinnnnkkkk tttteeeemmmmppppeeeerrrraaaattttuuuurrrreeee No No 0 5

538 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: AAAAllllaaaarrrrmmmm wwwwoooorrrrdddd,,,, bbbbiiiinnnnaaaarrrryyyy No No 0 7

539 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: VVVVLLLLTTTT ccccoooonnnnttttrrrroooollll wwwwoooorrrrdddd,,,, bbbbiiiinnnnaaaarrrryyyy No No 0 6

540 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: WWWWaaaarrrrnnnniiiinnnngggg wwwwoooorrrrdddd,,,, 1111 No No 0 7

541 DDDDaaaattttaaaa rrrreeeeaaaadddd----oooouuuutttt:::: WWWWaaaarrrrnnnniiiinnnngggg wwwwoooorrrrdddd,,,, 2222 No No 0 7

MG.50.H4.22 - VLT is a registered Danfoss trademark32

Page 34: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Pro

gram

min

g

PNU Parameter Factory setting Changes 4-Setup Conversion Data

# description during operation index ype

600 OOOOppppeeeerrrraaaattttiiiinnnngggg ddddaaaattttaaaa:::: OOOOppppeeeerrrraaaattttiiiinnnngggg hhhhoooouuuurrrrssss No No 74 7

601 OOOOppppeeeerrrraaaattttiiiinnnngggg ddddaaaattttaaaa:::: HHHHoooouuuurrrrssss rrrruuuunnnn No No 74 7

602 OOOOppppeeeerrrraaaattttiiiinnnngggg ddddaaaattttaaaa:::: kkkkWWWWhhhh ccccoooouuuunnnntttteeeerrrr No No 2 7

603 OOOOppppeeeerrrraaaattttiiiinnnngggg ddddaaaattttaaaa:::: NNNNuuuummmmbbbbeeeerrrr ooooffff ppppoooowwwweeeerrrr----uuuupppp’ssss No No 0 6

604 OOOOppppeeeerrrraaaattttiiiinnnngggg ddddaaaattttaaaa:::: NNNNuuuummmmbbbbeeeerrrr ooooffff oooovvvveeeerrrrtttteeeemmmmppppeeeerrrraaaattttuuuurrrreeeessss No No 0 6

605 OOOOppppeeeerrrraaaattttiiiinnnngggg ddddaaaattttaaaa:::: NNNNuuuummmmbbbbeeeerrrr ooooffff oooovvvveeeerrrrvvvvoooollllttttaaaaggggeeeessss No No 0 6

606 DDDDaaaattttaaaa lllloooogggg:::: DDDDiiiiggggiiiittttaaaallll iiiinnnnppppuuuutttt No No 0 5

607 DDDDaaaattttaaaa lllloooogggg:::: BBBBuuuussss ccccoooommmmmmmmaaaannnnddddssss No No 0 6

608 DDDDaaaattttaaaa lllloooogggg:::: BBBBuuuussss ssssttttaaaattttuuuussss wwwwoooorrrrdddd No No 0 6

609 DDDDaaaattttaaaa lllloooogggg:::: RRRReeeeffffeeeerrrreeeennnncccceeee No No -1 3

610 DDDDaaaattttaaaa lllloooogggg:::: FFFFeeeeeeeeddddbbbbaaaacccckkkk No No -3 4

611 DDDDaaaattttaaaa lllloooogggg:::: MMMMoooottttoooorrrr ffffrrrreeeeqqqquuuueeeennnnccccyyyy No No -1 3

612 DDDDaaaattttaaaa lllloooogggg:::: MMMMoooottttoooorrrr vvvvoooollllttttaaaaggggeeee No No -1 6

613 DDDDaaaattttaaaa lllloooogggg:::: MMMMoooottttoooorrrr ccccuuuurrrrrrrreeeennnntttt No No -2 3

614 DDDDaaaattttaaaa lllloooogggg:::: DDDDCCCC llll iiiinnnnkkkk vvvvoooollllttttaaaaggggeeee No No 0 6

615 FFFFaaaauuuullll tttt lllloooogggg:::: EEEErrrrrrrroooorrrr ccccooooddddeeee No No 0 5

616 FFFFaaaauuuullll tttt lllloooogggg:::: TTTTiiiimmmmeeee No No -1 7

617 FFFFaaaauuuullll tttt lllloooogggg:::: VVVVaaaalllluuuueeee No No 0 3

618 RRRReeeesssseeeetttt ooooffff kkkkWWWWhhhh ccccoooouuuunnnntttteeeerrrr No reset Yes No 0 5

619 RRRReeeesssseeeetttt ooooffff hhhhoooouuuurrrrssss----rrrruuuunnnn ccccoooouuuunnnntttteeeerrrr No reset Yes No 0 5

620 OOOOppppeeeerrrraaaattttiiiinnnngggg mmmmooooddddeeee NNNNoooorrrrmmmmaaaallll ffffuuuunnnnccccttttiiiioooonnnn Normal function No No 0 5

621 NNNNaaaammmmeeeeppppllllaaaatttteeee:::: VVVVLLLLTTTT ttttyyyyppppeeee No No 0 9

622 NNNNaaaammmmeeeeppppllllaaaatttteeee:::: PPPPoooowwwweeeerrrr sssseeeeccccttttiiiioooonnnn No No 0 9

623 NNNNaaaammmmeeeeppppllllaaaatttteeee:::: VVVVLLLLTTTT oooorrrrddddeeeerrrriiiinnnngggg nnnnuuuummmmbbbbeeeerrrr No No 0 9

624 NNNNaaaammmmeeeeppppllllaaaatttteeee:::: SSSSooooffffttttwwwwaaaarrrreeee vvvveeeerrrrssssiiiioooonnnn nnnnoooo.... No No 0 9

625 NNNNaaaammmmeeeeppppllllaaaatttteeee:::: LLLLCCCCPPPP iiiiddddeeeennnnttttiiiiffffiiiiccccaaaattttiiiioooonnnn nnnnoooo.... No No 0 9

626 NNNNaaaammmmeeeeppppllllaaaatttteeee:::: DDDDaaaattttaaaabbbbaaaasssseeee iiiiddddeeeennnnttttiiiiffff iiiiccccaaaattttiiiioooonnnn nnnnoooo.... No No -2 9

627 NNNNaaaammmmeeeeppppllllaaaatttteeee:::: PPPPoooowwwweeeerrrr sssseeeeccccttttiiiioooonnnn iiiiddddeeeennnnttttiiiiffffiiiiccccaaaattttiiiioooonnnn nnnnoooo.... No No 0 9

628 NNNNaaaammmmeeeeppppllllaaaatttteeee:::: AAAAppppppppllll iiiiccccaaaattttiiiioooonnnn ooooppppttttiiiioooonnnn ttttyyyyppppeeee No No 0 9

629 NNNNaaaammmmeeeeppppllllaaaatttteeee:::: AAAAppppppppllll iiiiccccaaaattttiiiioooonnnn ooooppppttttiiiioooonnnn oooorrrrddddeeeerrrriiiinnnngggg nnnnoooo.... No No 0 9

630 NNNNaaaammmmeeeeppppllllaaaatttteeee:::: CCCCoooommmmmmmmuuuunnnniiiiccccaaaattttiiiioooonnnn ooooppppttttiiiioooonnnn ttttyyyyppppeeee No No 0 9

631 NNNNaaaammmmeeeeppppllllaaaatttteeee:::: CCCCoooommmmmmmmuuuunnnniiiiccccaaaattttiiiioooonnnn ooooppppttttiiiioooonnnn oooorrrrddddeeeerrrriiiinnnngggg nnnnoooo.... No No 0 9

MG.50.H4.22 - VLT is a registered Danfoss trademark 33

Page 35: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

PNU Parameter Factory Changes 4-setup Conversion Data-

# description setting during operation index type

700 RRRReeeellllaaaayyyy 6666,,,, ffffuuuunnnnccccttttiiiioooonnnn Ready signal Yes Yes 0 5

701 RRRReeeellllaaaayyyy 6666,,,, OOOONNNN ddddeeeellllaaaayyyy 0 sec. Yes Yes -2 6

702 RRRReeeellllaaaayyyy 6666,,,, OOOOFFFFFFFF ddddeeeellllaaaayyyy 0 sec. Yes Yes -2 6

703 RRRReeeellllaaaayyyy 7777,,,, ffffuuuunnnnccccttttiiiioooonnnn Motor running Yes Yes 0 5

704 RRRReeeellllaaaayyyy 7777,,,, OOOONNNN ddddeeeellllaaaayyyy 0 sec. Yes Yes -2 6

705 RRRReeeellllaaaayyyy 7777,,,, OOOOFFFFFFFF ddddeeeellllaaaayyyy 0 sec. Yes Yes -2 6

706 RRRReeeellllaaaayyyy 8888,,,, ffffuuuunnnnccccttttiiiioooonnnn Mains ON Yes Yes 0 5

707 RRRReeeellllaaaayyyy 8888,,,, OOOONNNN ddddeeeellllaaaayyyy 0 sec. Yes Yes -2 6

708 RRRReeeellllaaaayyyy 8888,,,, OOOOFFFFFFFF ddddeeeellllaaaayyyy 0 sec. Yes Yes -2 6

709 RRRReeeellllaaaayyyy 9999,,,, ffffuuuunnnnccccttttiiiioooonnnn Fault Yes Yes 0 5

710 RRRReeeellllaaaayyyy 9999,,,, OOOONNNN ddddeeeellllaaaayyyy 0 sec. Yes Yes -2 6

711 RRRReeeellllaaaayyyy 9999,,,, OOOOFFFFFFFF ddddeeeellllaaaayyyy 0 sec. Yes Yes -2 6

NOTEThis VLT Parameter List is only valid whenRelay Option is installed.

MG.50.H4.22 - VLT is a registered Danfoss trademark34

Page 36: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

Pro

gram

min

g

PNU Parameter Factory setting Changes 4-Setup

Conver-

sionData

# description during operation index type

700 SSSSyyyysssstttteeeemmmm ccccoooonnnnttttrrrroooollll 0 – 1 Yes No 0 6

701 PPPPrrrrooooggggrrrraaaammmm nnnnuuuummmmbbbbeeeerrrr - 1 -1 - 127 Yes No 0 4

702 PPPPIIIIDDDD,,,, PPPPrrrrooooppppoooorrrrttttiiiioooonnnnaaaallll ffffaaaaccccttttoooorrrr 30 0 - 65000 Yes No 0 4

703 PPPPIIIIDDDD,,,, DDDDeeeerrrriiiivvvvaaaattttiiiivvvveeee ffffaaaaccccttttoooorrrr 0 0 - 65000 Yes No 0 4

704 PPPPIIIIDDDD,,,, IIIInnnntttteeeeggggrrrraaaallll ffffaaaaccccttttoooorrrr 0 0 - 65000 Yes No 0 4

705 PPPPIIIIDDDD,,,, IIIInnnntttteeeeggggrrrraaaallll bbbbaaaannnnddddwwwwiiiiddddtttthhhh 1000 0 - 1000 Yes No 0 4

706 PPPPIIIIDDDD,,,, BBBBAAAANNNNDDDDWWWWIIIIDDDDTTTTHHHH 1000 0 - 65000 Yes No 0 4

707 PPPPIIIIDDDD,,,, VVVVeeeelllloooocccciiiittttyyyy FFFFeeeeeeeedddd----ffffoooorrrrwwwwaaaarrrrdddd 0 0 - 65000 Yes No 0 4

708 PPPPIIIIDDDD,,,, AAAAcccccccceeeelllleeeerrrraaaattttiiiioooonnnn

FFFFeeeeeeeedddd----ffffoooorrrrwwwwaaaarrrrdddd

0 0 - 65000 Yes No 0 4

709 PPPPIIIIDDDD,,,, VVVVeeeelllloooocccciiiittttyyyy ffffiiii lllltttteeeerrrr 0 0 - 65000 Yes No 0 4

710 UUUUsssseeeerrrr ppppaaaarrrraaaammmmeeeetttteeeerrrr 11110000 0 Defined by

user 1

Yes No 0 4

711 UUUUsssseeeerrrr ppppaaaarrrraaaammmmeeeetttteeeerrrr 11111111 0 Defined by

user 1

Yes No 0 4

...

778 UUUUsssseeeerrrr ppppaaaattttaaaammmmeeeetttteeeerrrr 77778888 0 Defined by

user 1

Yes No 0 4

779 UUUUsssseeeerrrr ppppaaaarrrraaaammmmeeeetttteeeerrrr 77779999 0 Defined by

user 1

Yes No 0 4

780 AAAAccccttttiiiivvvvaaaatttteeeedddd ddddeeeeaaaadddd ttttiiiimmmmeeee

ccccoooommmmppppeeeennnnssssaaaattttiiiioooonnnn

OFF 0 - 1 No No 0 4

795 UUUUsssseeeerrrr ppppaaaarrrraaaammmmeeeetttteeeerrrr 99995555 ((((rrrreeeeaaaadddd oooonnnnllllyyyy)))) 0 Defined by

user 1

Read only No 0 4

796 UUUUsssseeeerrrr ppppaaaarrrraaaammmmeeeetttteeeerrrr 99996666((((rrrreeeeaaaadddd oooonnnnllllyyyy)))) 0 Defined by

user 1

Read only No 0 4

797 UUUUsssseeeerrrr ppppaaaarrrraaaammmmeeeetttteeeerrrr 99997777((((rrrreeeeaaaadddd oooonnnnllllyyyy)))) 0 Defined by

user 1

Read only No 0 4

798 UUUUsssseeeerrrr ppppaaaarrrraaaammmmeeeetttteeeerrrr 99998888((((rrrreeeeaaaadddd oooonnnnllllyyyy)))) 0 Defined by

user 1

Read only No 0 4

799 UUUUsssseeeerrrr ppppaaaarrrraaaammmmeeeetttteeeerrrr 99999999((((rrrreeeeaaaadddd oooonnnnllllyyyy)))) 0 Defined by

user 1

Read only No 0 4

NOTEThis VLT Parameter List is only valid whenSync/Pos option is installed.

1) The maximum range is-232 to 2 32 - 1 (-2147483648 to 2147483647)but the actual range is specified when defininga user parameter in the application programusing LINKGPAR or LINKAXPAR.

MG.50.H4.22 - VLT is a registered Danfoss trademark 35

Page 37: Device Net Vlt 5000

VLT® 5000/ 5000 FLUX/ 6000 HVAC/8000 AQUA DeviceNet

■ Factory settings

PNU Parameter Factory setting Changes 4-Setup Conversion Data

# description during operation index type

801 BBBBaaaauuuudddd rrrraaaatttteeee sssseeeelllleeeeccccttttiiiioooonnnn -1 3

803 TTTTiiiimmmmeeee aaaafffftttteeeerrrr bbbbuuuussss eeeerrrrrrrroooorrrr 1 sec. -1 3

804 RRRReeeessssppppoooonnnnsssseeee aaaafffftttteeeerrrr bbbbuuuussss eeeerrrrrrrroooorrrr Off -1 3

805 FFFFuuuunnnnccccttttiiiioooonnnn ccccoooonnnnttttrrrroooollll wwwwoooorrrrdddd bbbbiiiitttt BBBBiiiitttt 11110000 Bit 10 = CTW active -1 6

904 PPPPPPPPOOOO sssseeeelllleeeeccccttttiiiioooonnnn ffffoooorrrr DDDDPPPP 900 0 6

915 PPPPCCCCDDDD wwwwrrrriiiitttteeee ccccoooonnnnffffiiiigggguuuurrrraaaattttiiiioooonnnn 0 6

916 PPPPCCCCDDDD rrrreeeeaaaadddd ccccoooonnnnffffiiiigggguuuurrrraaaattttiiiioooonnnn 0 6

927 PPPPCCCCVVVV ooooppppeeeerrrraaaattttiiiinnnngggg aaaauuuutttthhhhoooorrrriiii ttttyyyy With PROFIBUS 0 6

928 CCCCoooonnnnttttrrrroooollll aaaauuuutttthhhhoooorrrriiiittttyyyy With PROFIBUS 0 6

953 WWWWaaaarrrrnnnniiiinnnngggg MMMMeeeessssssssaaaaggggeeeessss 0 35

967 CCCCoooonnnnttttrrrroooollll WWWWoooorrrrdddd 0 35

968 SSSSttttaaaattttuuuussss WWWWoooorrrrdddd 0 35

970 PPPPaaaarrrraaaammmmeeeetttteeeerrrr sssseeeettttuuuupppp sssseeeelllleeeeccccttttiiiioooonnnn Active setup 0 5

971s SSSSaaaavvvveeee ddddaaaattttaaaa vvvvaaaalllluuuueeeessss Not active (OFF) 0 5**

980 DDDDeeeeffffiiiinnnneeeedddd ppppaaaarrrraaaammmmeeeetttteeeerrrrssss 0 6

981

982

990 MMMMooooddddiiiiffffiiiieeeedddd ppppaaaarrrraaaammmmeeeetttteeeerrrrssss 0

991

992

** Automatic reset to (0)S Only in stop mode (VLT must be stoppedin order to change data value)

MG.50.H4.22 - VLT is a registered Danfoss trademark36

Page 38: Device Net Vlt 5000

Drives Solutions

www.danfoss.com/drives

Instruction ManualDeviceNet