Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By...

94
LOGO Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram, Kanyakumari. Dr.D.Devaraj, Professor/EEE, Arulmigu Kalasalingam College of Engineering, Krishnankoil Guided By

Transcript of Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By...

Page 1: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Development and Implementation of Novel Techniques for the Control

of Shunt Active Filter

By

P.Rathika,

Asso.Prof, Cape Institute of Technology

Levengipuram, Kanyakumari.

Dr.D.Devaraj,

Professor/EEE,

Arulmigu Kalasalingam College of Engineering,

Krishnankoil

Guided By

Page 2: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

2

IntroductionI

II Shunt Active Filter

• Power Quality

• Harmonics – an overview

• Sources of harmonics

• Mitigation Techniques for Harmonics

• Principle of operation

• Reference Current Extraction

• Voltage and Current control method

Proposed Control StrategiesIII

Plan of Presentation

• Hysteresis Current Control Techniques

• Fuzzy Logic based Current control strategies

• Voltage Control Techniques

• Time and Frequency domain based current extraction

• Simulation Results

• Hardware Implementation with Results

IV Conclusions

05/07/11

Page 3: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

3

Any deviation from a perfect sinusoidal waveform that can results in failure or mis-operation of customer equipment

Power Quality

Quality of the current and voltage provided to the customers Providing customers with a pure sinusoidal waveforms

at 50 Hz without any deviations. Providing power to allow sensitive electronic

equipment operate reliably.

05/07/11

Page 4: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

4

What are Harmonics

f(x) = sin(x)

f(x) = sin(5x)

5

+

f(x) = sin(x) + sin(5x)5

=

In the resultant wave the

sinusoidal character is lost

HarmonicsA sinusoidal voltage or current having frequencies that are

integral multiples of the power frequency.

05/07/11

Page 5: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

5

Sources of Harmonics

Modern electronic equipments such as personal or notebook computers laser printers fax machines telephone systems, stereos, radios, TVs adjustable speed drives and variable frequency drives battery chargers, UPS, and any other equipment powered

by switched-mode power supply (SMPS) equipment

Non-linear load devices create harmonics when they convert ac to dc, dc to dc, dc to ac, and ac to ac

Non-linear loads: draw current only a part of the voltage cycle

05/07/11

Page 6: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

6

Harmonics

Total Harmonic Distortion (THD)

It is the ratio between the RMS value of the harmonic currents to the fundamental current.

(%)1001

...............

(%)1001

2

2

23

22

I

II

In

nI

THD

05/07/11

Page 7: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

7

Harmonics Sources

Examples

Computer Rectifiers

THD = 80 to 140% THD = 20 to 60%

05/07/11

Page 8: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

8

Effects of Harmonics

Over heating of Transformer Excessive neutral current Damage of sensitive electronic equipments Tripping of Circuit Breakers Low system efficiency Poor power factor Skin Effect Interference in the nearby communication

systems

05/07/11

Page 9: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

9

Recommended limits - IEEE 519

The Institute of Electrical and Electronics Engineers (IEEE)has set recommended limits on both current and voltagedistortion in IEEE 519-1992.

Voltage Harmonic Distortion Limits

Bus Voltage at PCC Individual Voltage Distortion (%)

Total Voltage Distortion THD (%)

69 kV and below 3.0 5.0

69.001 kV through 161kV

1.5 2.5

161.001 kV and above 1.0 1.5

05/07/11

Page 10: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

10

Isc: Maximum short-circuit current at the Point of Common Coupling (PCC).IL: Maximum demand load current (fundamental) at the PCC.

Isc/IL h<11 11≤h<17 17≤h<2323≤h<3

535≤h

THD (%)

<20 4.0 2.0 1.5 0.6 0.3 5.0

20-50 7.0 3.5 2.5 1.0 0.5 8.0

50-100 10.0 4.5 4.0 1.5 0.7 12.0

100-1000 12.0 5.5 5.0 2.0 1.0 15.0

>1000 15.0 7.0 6.0 2.5 1.4 20.0

Harmonic Current Limits

05/07/11

Page 11: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

11

Harmonics Solution Techniques

1

Passive Filter

2 Active Filter

shunt active filter

series active filter

hybrid shunt –

series active filter

3

Hybrid Filter

Filters: The harmonics filters are the solution to eliminate the harmonics.

05/07/11

Page 12: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

12

Basic Operation of Shunt Active Filter

05/07/11

Page 13: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

13

Heart of Shunt Active Filter

Heart of SAF

1

3 2

Reference Current Generator

DC Voltage Control Gating Signal Generator

05/07/11

Page 14: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

14

Block Diagram of SAF

05/07/11

Page 15: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

15

Research Objectives

This research work focuses on developing suitable control techniques and reference current extraction method for the shunt active filter for three phase 3-wire and three phase 4-wire system.

The objectives are To develop an effective and reliable control strategy for three

phase shunt active filter to suppress harmonic currents and compensate reactive power under ideal, non-ideal source voltage condition and also it should maintain a constant switching frequency.

To develop an effective reference current calculation method to extract the harmonics content present in the load current under ideal, non-ideal and noisy voltage source condition.

To develop a suitable voltage controller to maintain constant voltage across the DC bus capacitor.

05/07/11

Page 16: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Shunt Active Filter with Fixed Hysteresis Band

Technique

Page 17: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

17

Hysteresis current controller

When the current through the inductor exceeds the upper hysteresis limit a negative voltage is applied by the inverter to the inductor. This causes the current in the inductor to decrease. Once the current reaches the lower hysteresis limit a positive voltage is applied by the inverter to the inductor and this causes the current to increase and the cycle repeats.

05/07/11

Page 18: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

18

Current Extraction Techniques

Methods Time domain Techniques Frequency Domain Techniques - Large number of calculation is involved hence it is less

practical.

Time Domain Technique Harmonics extraction methods in the time domain are

based on instantaneous derivation of compensating signals in the form of either voltage or current signals from distorted and harmonic polluted voltage or current signals.

05/07/11

Page 19: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

19

Reference Current Extraction

Clarke Transformation

c

b

a

V

V

V

V

V

2

3

2

30

2

1

2

11

3

2

c

b

a

I

I

I

I

I

2

3

2

30

2

1

2

11

3

2

Current

…..Contd

Voltage

05/07/11

Page 20: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

20

Contd…..

I

I

VV

VV

q

p

q

pVV

VV

i

i

c

c~

*

*

Instantaneous Real and Reactive Power

Reference compensation currents in α-β coordinates

Reference compensation currents in a-b-c coordinates

*

*

*

*

*

2

3

2

1

2

3

2

1

01

c

c

cc

cb

ca

i

i

i

i

i

05/07/11

Page 21: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

21

PI – DC Bus Voltage Control

05/07/11

Vc ref – Reference DC Voltage

Vc - Actual DC Voltage

Page 22: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Simulation Results

Page 23: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

23

Test System

05/07/11

Page 24: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

24

Circuit Diagram of Shunt Active Filter

05/07/11

Page 25: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

25

Distorted three phase line current

Without Filter

Harmonic Spectrum of the distorted line current

THD=26.34%

05/07/11

Page 26: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

26

Three phase line current with filter

Harmonic Spectrum of the line current with filter

Results with AF

THD=4.1%

05/07/11

Page 27: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

27

Switching Frequency

• The switching frequency is varying between 19kHz to 20kHz

• The switching loss gets increases

05/07/11

Page 28: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Constant Frequency Hysteresis Band Control

Page 29: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

29

Constant Frequency Hysteresis Current Control

generates switching pulses based on the prediction of current error and its slope and the past switching ON/OFF time of the switches in the inverter. In this technique, the hysteresis bandwidth need not be specified in the entire control algorithm.

05/07/11

Page 30: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

30

Calculation of Switching Time

1

,1*

1,

1

)]()(([

2

ONfafaf

dcOFF ttitiL

Vt

1

,33*,

1

)]()(([

2

OFFfafaf

dcON ttitiL

Vt

2,,

Ttt ONOFF

2,,

Ttt ONOFF

The switching time is calculated from the system parameters

05/07/11

Page 31: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

31

Distorted three phase line current

Without Filter

Harmonic Spectrum of the distorted line current

THD=26.34%

05/07/11

Page 32: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

32

Results with Filter

05/07/11

Page 33: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

33

Harmonic Contents -supply current and voltage

HarmonicOrder

Individual Harmonic Content (% of fundamental)

Without Filter Filter with FHBCC Filter with CFHCC

Current Voltage Current Voltage Current

3 0 0.01 0.5 0 0.03

5 23 0.12 1.5 0.11 1.27

7 12 0.12 1.52 0.13 1.03

9 0 0.01 0.12 0.01 0.07

11 9 0.3 1.61 0.28 1.34

13 7 0.23 1.45 0.23 1.1

15 0 0.02 0.26 0.01 0.15

17 5 0.39 1.33 0.39 1.0

19 4 0.25 0.9 0.25 0.2

THD(%) 26.34 3.3 4.1 2.91 3.89

05/07/11

Page 34: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

34

Source voltage and Current

Real and Reactive power supplied by the source to the Load

05/07/11

Page 35: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

35

Average Switching Frequency of the Inverters

05/07/11

Page 36: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

36

DRAWBACKS

The performance is poor under non-ideal source voltage condition- Not suitable for unbalance system

The switching frequency is high

Switching loss is high

05/07/11

Page 37: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Fuzzy Adaptive Hysteresis Band Current Control

Page 38: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

38

Adaptive Hysteresis Current Control

Band width

CurrentferenceFilteri

VoltageSupplytv

dt

ditvfHB

fa

s

fa

sj

Re

)(

)),((

*

*

05/07/11

Page 39: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

39

Fuzzy Membership function

05/07/11

Page 40: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Fuzzy Rule Base

dt

di fa*

)(tvs

NL NM EZ PM PL

NL PS PM PM PM PS

NM PS PM PL PM PS

EZ PVS PM PVL PM PVL

PM PS PM PL PM PS

PL PS PM PM PM PS

05/07/11 40

Page 41: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Simulation Results

Page 42: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

42

Test System

05/07/11

Page 43: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

43

Four wire System with APF

05/07/11

Page 44: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

44

Distorted Phase and Neutral current

05/07/11

Page 45: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

45

Ideal supply voltage conditions

05/07/11

Page 46: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

46

Ideal supply voltage conditions (Contd..)

05/07/11

Page 47: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

47

Unbalanced and Distorted Condition

05/07/11

Page 48: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

48

Result-After filtering

05/07/11

Page 49: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

49

Results Summary

05/07/11

Voltage

ControlCurrent Control

THD (%)

Phase A Phase B Phase C

Without Filter 18.74 25.74 50.42

PI Fixed Hysteresis 3.4 4.3 4.5

PIFuzzy-Adaptive

Hysteresis2.72 3.6 3.6

Page 50: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

50

Average Switching Frequency

05/07/11

S.No Control TechniqueAverage Switching

Frequency (KHz)

Real Power Supplied from

Source (Kw)

1 Fixed HBCC 19 4500

2 CFHCC 16 4000

3 Fuzzy-Adaptive HBCC 10 3400

Page 51: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

51

Average Switching loss

05/07/11

Page 52: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Fuzzy Logic based PWM Current Control

Page 53: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

53

Block Diagram of SAF

05/07/11

Page 54: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

54

Fuzzy Logic Controller

05/07/11

Page 55: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

55

Membership Function

05/07/11

Page 56: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

56

Rule Base

05/07/11

e

deNL NM EZ PM PL

NL PB PM PM PM PB

NM PB PM PL PM PB

EZ PVB PM PVL PM PVL

PM PB PM PL PM PB

PL PB PM PM PM PB

Page 57: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

57

Fuzzy Based DC bus Voltage Control

The input to the fuzzy logic controller are

I. DC voltage error e (t) II. Rate of Change in error de(t)/dt

Block diagram of the DC voltage control using a Fuzzy controller

05/07/11

Page 58: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

58

Membership Function

05/07/11

Page 59: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

59

Fuzzy Rule Base

e

de

NL NM NS ZE PS PM PL

NL NL NL NL NL NM NS ZE

NM NL NL NL NM NS ZE PS

NS NL NL NM NS ZE PS PM

ZE NL NM NS ZE PS PM PL

PS NM NS ZE PS PM PL PL

PM NS ZE PS PM PL PL PL

PL NL NM NS ZE PS PM PL

05/07/11

Page 60: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Simulation Results

Page 61: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

61

Test System

05/07/11

Load

I

Load

II

Page 62: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

62

Distorted three phase line current

Without Filter

Harmonic Spectrum of the distorted line current

THD=26.34%

05/07/11

Page 63: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

63

Harmonic compensation with Fuzzy-Controller

05/07/11

Page 64: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

64

Result – Unbalanced Condition

05/07/11

Page 65: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

65

Result with Filter

05/07/11

Page 66: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

66

Under Varying load condition

05/07/11

Page 67: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

67

Performance comparison of PI and Fuzzy controller

05/07/11

Page 68: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Wavelet Transform based Current Extraction

Page 69: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

69

Block Diagram of SAF

05/07/11

Page 70: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

70

Wavelet Decomposition

05/07/11

Page 71: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

71

Wavelet Reconstruction

05/07/11

Page 72: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

72

Fundamental Current Extraction

Fundamental current Extraction using Wavelet Transform Technique

Estimated phase A harmonic current using db8

05/07/11

Page 73: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Simulation Results

Page 74: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

74

Test System

05/07/11

Page 75: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

75

Source Current and Spectrum-Before Filtering

05/07/11

Page 76: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

76

Fundamental Current Extraction

05/07/11

Page 77: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

77

Result –After Filtering

05/07/11

Page 78: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

78

Source current –After Filtering with p-q theory

05/07/11

Page 79: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

79

Result-Summary

Phase

THD (%)

Without Filter

With Filter

p-q method Wavelet Method

Phase A 30.66 16.0 10.0

Phase B 29.58 16.3 10.34

Phase C 30.02 16.7 10.34

05/07/11

Page 80: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

80

Performance Summary

Detection Parameter Performance Comparison

Source Voltage Condition Ideal Noisy

THD of Source voltage (%) 0 16

Current Detection Method p-q WT p-q WT

Transient time (cycle) 1 <1/4 1 <1/4

Fundamental Extraction good good bad good

Response Time high low high low

Selective harmonic Elimination Not suitable suitable Not suitable Suitable

05/07/11

Page 81: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Hardware Implementation

Page 82: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

82

Overall Block Diagram

05/07/11

Page 83: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

83

Power circuit

05/07/11

Page 84: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

84

Distorted Source Current

05/07/11

Page 85: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

85

Source Current and Frequency Spectrum

05/07/11

Page 86: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

86

Source Current after Filtering

05/07/11

Source Current

FFT Spectrum

THD = 4.5 %

Page 87: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

87

Hardware setup

05/07/11

Page 88: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

88

ConclusionThis research work has focused on the development and implementation of novel techniques for the control of Shunt Active Filter to suppress harmonics and compensate reactive power. A suitable reference current extraction method is also developed which performs well under noisy condition.

The constant frequency hysteresis current controller proposed to overcome the drawback of the conventional hysteresis control, namely variable switching frequency.

The fuzzy logic based adaptive hysteresis current control technique proposed for the three phase four-wire system can effectively cancel the neutral current produced due to the unbalanced load. Also, the proposed controller maintains constant switching frequency with reduced switching loss.

The fuzzy logic based PWM current control technique proposed to eliminate harmonics under varying load conditions. the proposed fuzzy-logic based DC voltage control keeps constant voltage across the capacitor. The proposed controller maintains the reference voltage without any deviations.

The wavelet transform based approach proposed for current extraction method can effectively calculate the reference compensation current under noisy source voltage condition compared with the conventional p-q theory.

The simulation results obtained using fuzzy logic based hysteresis current control techniques are validated by implementing the proposed technique using DSP processor.

Page 89: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

89

Journal Publications

05/07/11

1. P.Rathika, D. Devaraj, “Fuzzy Logic – Based Approach for Adaptive Hysteresis Band and DC Voltage Control in Shunt Active Filter” International Journal of Computer and Electrical Engineering, vol.2, No.3, June 2010, pp 1793-8163.

2. P.Rathika, D. Devaraj, “Fuzzy Logic Based Three-Phase Four-Wire and Four-Leg Shunt Active Power Filter for Harmonics, Reactive and Neutral Current Compensation”, International journal of Electrical Engineering, 2011.

3. P.Rathika, D. Devaraj, “Fuzzy Logic Based D.C Voltage and Current Control Technique for Shunt Active Filter Design”, Asian journal of Power electronics Applications (Accepted for Publication)

4. P.Rathika, D. Devaraj, “Fuzzy-Adaptive Hysteresis Based Current Control based VSI for Active Power Filter to Reduce Switching Frequency” International journal of Electronics, Taylor and Francis publications (Revised and submitted)

5. P.Rathika, D. Devaraj,” Artificial Intelligent Controller Based Three- Phase Shunt Active Filter for Harmonic Reduction and Reactive Power Compensation” International journal of Lecture notes in Engineering and Computer Science, 2010.

6. P.Rathika, D. Devaraj, “Wavelet Transform Based Reference Current Computation and Fuzzy adaptive Hysteresis Band Current Control for Shunt Active Power Filter”, International journal on Electrical Engineering, Springer Publication. (Under Review)

7. P.Rathika, D. Devaraj, “Fuzzy Logic-Based Adaptive Hysteresis Current Control Technique for Shunt Active Filter”, International Journal on Adaptive and Innovative Systems, Inderscience Publication. (Under Review)

Page 90: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

90

International Conference Publications

05/07/11

1. P.Rathika, D. Devaraj, ” Artificial Intelligent Controller Based Three- Phase Shunt Active Filter For Harmonic Reduction And Reactive Power Compensation” International Multi Conference of Engineers and Computer Scientists 2010 Hotel Royal Garden, Hong Kong , March 2010, pp 1170-1175 .

2. P.Rathika, D. Devaraj, “Discrimination of Power Quality Disturbances using Combined Mathematical Transforms and Artificial Neural Network”, IEEE International Conference on Sustainable Energy Technologies (IEEE-ICSET’08), SMU Conference Centre, Singapore, Nov 2008, pp 1265-1270.

3. P.Rathika, D. Devaraj, “Power Quality Monitoring using wavelet transform and Artificial Neural Networks”, India International Conference on Power Electronics (IICPE ’06), Hotel Le Royal Meridien, Chennai, Dec 2006, pp 425-430.

Page 91: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

91

National Conference Publication

05/07/11

1. P.Rathika, D. Devaraj,” Implementation of Shunt Active Filter using DSP”, INCOS’10 Kalasalingam University, Krishnanakoil, Apr 2010, pp 63-68.

2. P.Rathika, D. Devaraj,” Design of D-STATCOM using DSP Controller for Voltage sag/swell Mitigation”, INCOS’10 Kalasalingam University, Krishnanakoil, Apr 2010, pp 52-56.

3. P.Rathika, D. Devaraj,” Shunt Active Filter with Fuzzy Logic Control of DC Bus Voltage”, Power and Energy Systems (NPES’09) Kalasalingam University, Krishnanakoil, March 2009, pp 183-186.

4. P.Rathika, D. Devaraj,” Power Quality Monitoring by evaluation of Energy curves using wavelet Transform”, Recent Trends and Emerging technologies in Electrical Systems (ELCON’06), National Engineering College, Kovilpatti, Nov 2006, pp 198-207.

5. P.Rathika, D.Devaraj, ”Shunt Active Power Filter for Power Quality Improvement”, Recent Trends and Emerging technologies in Electrical Systems (ELCON’06), National Engineering College, Kovilpatti, Nov 2006, pp 81-88.

Page 92: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

92

REFERENCES

1. Akagi, H., Kanazawa, Y. and Nabae, A. “Generalized theory of the Instantaneous Reactive power in Three-phase circuits”, International Power Electronics Conference Tokyo, Japan, pp. 1375-1386, 1983.

2. Anshuman shukla, Arindam Ghosh and Avinash Joshi. “Hysteresis current control operation of flying capacitor Multilevel inverter and its Application in shunt Compensation of Distribution Systems”, IEEE Transactions on Power Delivery, Vol. 22, No.1, pp.396-405, 2007.

3. Aredes, M. and Watanabe, E.H. “Three-phase four-wire shunt active filter control strategies”, IEEE Transactions on Power Electronics, Vol. 12, No.2, pp.311-318, 1997.

4. Bhim Singh, Kamal Al Haddad and Ambrish Chandra, “A Review of Active Filters for Power Quality Improvement”, IEEE Transactions on Industrial Electronics, Vol. 46, No. 5, pp. 960-970, 1999.

5. Carl Ngai-Man Ho, Victor, S.P., Chung and Henry Shu-Hung Chung, “Constant-Frequency Hysteresis Current Control of Grid Connectec VSI without Bandwidth Control”, IEEE Transactions Power Electronics, Vol. 24, No. 11, 2009.

6. Chelladurai, J., Saravana Ilango, G., Nagamani, C. and Senthil Kumar, S. “Investigation of various PWM techniques for Shunt Active Filter”, proceedings of World Academy of Sciences, Engineering and Technology, Vol. 29, pp.192-197, 2008.

7. Cupertino, F. and Marinelli, M. “EKF and Wavelet-based Algorithms Applied to Harmonic Detection for Active Shunt Filters”, 11th International Conference on Harmonics and Quality of Power, pp.721-727, 2004.

8. Dwivedi, U.D, and Singh, S.N. “A Wavelet-based Denoising Technique for Improved Monitoring and Characterization of Power Quality Disturbances”, Electric Power Components and Systems, Vol. 37, pp. 753-769, 2009.

Page 93: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

93

REFERENCES

9. Edson, H. Watanabe, Mauriclo Aredes and Hirofumi Akagi, “The p-q theory for Active filter control: some problems and solutions”, Revista Control & Automacao, Vol. 15, pp.78-84, 2001.

10. Firouzjah, K.G., Sheikholeslami, A., Karami-Mollaei, M.R. and Khateghi, M. “A new Harmonic Detection Method for Shunt Active Filter Based on Wavelet Transform”, Journal of Applied Science Research, Vol. 4, No. 11, pp.1561-1568, 2008.

11. Herrera, R.S., Salmeron, P. and Hyosung Kim, “Insantaneous Reactive Power Theory Applied to Active Power Filter Compensation: Different Approaches, Assessment and Experimental Results”, IEEE Transactions Industrial Electronics, Vol. 55, No. 1, pp.184-196, 2008.

12. Hui Liu, Guohai Liu and Yue Shen, “A Novel Harmonics Detection Method based on Wavelet Algorithm for Active Power Filter”, Proceedings of the 6 th World Congress on Intelligent Control and Automation, pp. 21-23, 2006.

13. Joao Afonso, Carlos Couto and Julio Martins, “Active Filters with Control Based on the p-q Theory”, IEEE Industrial Electronics Society Newsletter, Vol. 47, No.3, pp.5-10, 2000.

14. Lucian Asiminoaei, Frede Blaabjerg and Steffan Hansen, “Evaluation of Harmonic Detection Methods for Active Power Filter Applications”, Applied Power Electronics Conference, Vol. 1, pp. 635-641, 2005.

15. Mehmet Ucar, Engin Ozdemir, “Control of a 3-phase 4-leg Active Power Filter under non-ideal mains voltage condition”, Electric Power System Research, Vol. 78, pp. 58-73, 2008.

16. Vardar, K., Akpinar, E. and Surgevil, T. “Evaluation of reference current extraction methods for DSP implementation in Active Power Filters”, Electric Power Systems Research, Vol. 79, pp. 1342-1352, 2009.

05/07/11

Page 94: Development and Implementation of Novel Techniques for the Control of Shunt Active Filter By P.Rathika, Asso.Prof, Cape Institute of Technology Levengipuram,

Thank You !