W A Y N E S T A T E U N I V E R S I T Y
V I C I N I T Y P L A N
SCALE: NTS
A R C H I T E C T U R A L
PRENTIS BUILDING RENOVATION
L O C A T I O N P L A N
SCALE: NTS
T-1
DETROIT, MI 48202
2215 Cole Street
BIRMINGHAM, MICHIGAN 48009
P (248)646-5765 F (248)646-5813
No code variance requests are anticipated.
Contractor to coordinate WORK SCOPE and constructionactivities with WSU construction Project Manager :
W O R K S C O P E
RENOVATE PORTION OF PRENTIS BUILDING (BASEMENT, FIRST FLOOR, MEZZANINE, AND THIRDFLOOR) INTO NEW OFFICES, CLASSROOMS, AND LABS, RENOVATE THIRD FLOOR RESTROOM INTOUNISEX ADA COMPLIANT RESTROOM.
PRENTIS BUILDING RENOVATION
A P P L I C A B L E C O D E S
BUILDING CODE:
P R O J E C T A R E A S U M M A R Y
MECHANICAL CODE:
PLUMBING CODE:
FIRE SAFETY CODE:
(FOR CONTRACT DOCUMENTS)
ELECTRICAL CODE:
NFPA 101 LIFE SAFETY CODE
NFPA 13/ 2007 STANDARD FOR THEINSTALLATION OF SPRINKLERSYSTEMS
MICHIGAN REHABILITATION CODE FOR EXISTING BUILDING/ 2015
STATE OF MICHIGAN MECHANICAL CODE/ 2015
STATE OF MICHIGAN ELECTRICAL CODE /2014
MICHIGAN PLUMBING CODE/ 2015
GROSS AREA - 13,000 GSF ±
USE GROUP:
CONSTRUCTION TYPE:
PUBLIC HEALTH CODE:
BARRIER FREE CODES:
MDCIS MINIMUM DESIGN STANDARDS FORCONSTRUCTION AND EQUIPMENT FORHEALTHCARE FACILITIES IN MICHIGAN
UFAS, AMERICANS WITH DISABILITIES ACT ACCESSIBILITYGUIDELINES, MICHIGAN BARRIER FREE - 2010
BUSINESS - B
1A NON-COMBUSTIBLE
Title Sheet, Drawing Index andLocation & Vicinity Maps
WAYNE STATE UNIVERSITY
PROJECT SITE :
PRENTIS BUILDING
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
T-1 TITLE SHEET, DRAWING INDEX & LOCATION & VICINITY MAPSA-002 ABBREVIATIONS, DRAWING SYMBOLS STANDARDS& STANDARD MOUNTING HEIGHTSA-20 ROOM FINISH SCHEDULEA-30 DOOR SCHEDULE & WALL TYPESAD-101-B PRENTIS BUILDING BASEMENT FLOOR PLAN - DEMOLITION WORKAD-101 PRENTIS BUILDING 1ST FLOOR PLAN - DEMOLITION WORKAD-101-M PRENTIS BUILDING MEZZANINE FLOOR PLAN - DEMOLITION WORKAD-103 PRENTIS BUILDING 3RD FLOOR PLAN - DEMOLITION WORKAD-104-B PRENTIS BUILDING BASEMENT FLOOR REFLECTED CEILING PLAN - DEMOLITION WORKAD-105 PRENTIS BUILDING 3RD FLOOR REFLECTED CEILING PLAN - DEMOLITION WORKA-201-B PRENTIS BUILDING BASEMENT FLOOR PLAN - NEW WORKA-201 PRENTIS BUILDING 1ST FLOOR PLAN -NEW WORKA-201-M PRENTIS BUILDING MEZZANINE FLOOR PLAN - NEW WORKA-203 PRENTIS BUILDING 3RD FLOOR PLAN - NEW WORKA-301-B PRENTIS BUILDING BASEMENT FLOOR REFLECTED CEILING PLAN - NEW WORKA-303 PRENTIS BUILDING 3RD FLOOR REFLECTED CEILING PLAN - NEW WORKA-701 PRENTIS BUILDING INTERIOR ELEVATIONS, SECTIONS, AND DETAILS
E L E C T R I C A LM E C H A N I C A L
MH000 VENTILATION COVER SHEETMHD101B BASEMENT FLOOR DEMOLITION - VENTILATIONMHD103 THIRD FLOOR DEMOLITION - VENTILATIONMH101B BASEMENT FLOOR PLAN - VENTILATIONMH103 THIRD FLOOR PLAN - VENTILATIONMH300 VENTILATION SCHEDULES & DETAILSP000 PLUMBING COVER SHEETPD103 THIRD FLOOR DEMOLITION - PLUMBINGP101B BASEMENT FLOOR PLAN - PLUMBINGP101M MEZZANINE FLOOR PLAN - PLUMBINGP103 SECOND AND THIRD FLOOR PLAN - PLUMBINGP300 PLUMBING DETAILSP500 PLUMBING SCHEDULES
E000 ELECTRICAL COVER SHEETED101B BASEMENT FLOOR DEMOLITION - ELECTRICALED-101 FIRST FLOOR DEMOLITION- ELECTRICALED101M MEZZANINE FLOOR DEMOLITION - ELECTRICALED103 THIRD FLOOR DEMOLITION - ELECTRICALEL101B BASEMENT FLOOR PLAN - LIGHTINGEL-101 FIRST FLOOR PLAN- LIGHTINGEL101M MEZZANINE FLOOR PLAN - LIGHTINGEL103 THIRD FLOOR PLAN - LIGHTINGEP101B BASEMENT FLOOR - POWEREP-101 FIRST FLOOR - POWEREP101M MEZZANINE FLOOR PLAN - POWEREP103 THIRD FLOOR PLAN - POWEREP-300 POWER DETAILSES101B BASEMENT FLOOR - SYSTEMSES101 FIRST FLOOR PLAN - SYSTEMSES101M MEZZANINE FLOOR PLAN - SYSTEMSES103 THIRD FLOOR - SYSTEMSES300 SYSTEM DETAILST000 TECHNOLOGY COVER SHEETTD101B BASEMENT FLOOR DEMOLITION - TECHNOLOGYTD103 THIRD FLOOR DEMOLITION - TECHNOLOGYT101B BASEMENT FLOOR PLAN - TECHNOLOGYT101 FIRST FLOOR PLAN - TECHNOLOGYT103 THIRD FLOOR PLAN - TECHNOLOGYT200 TECHNOLOGY DETAILS, RISERS AND SCHEDULES
26200 Town center Drive
NOVI, MICHIGAN 48375
P (248)313-6902 F (248)344-1650
26200 Town center Drive
NOVI, MICHIGAN 48375
P (248)313-6902 F (248)344-1650
MP000 PIPING COVER SHEETMPD101B BASEMENT FLOOR DEMOLITION - PIPINGMP101B BASEMENT FLOOR - PIPINGMP103 SECOND AND THIRD FLOOR PLAN - PIPINGF000 FIRE PROTECTION COVER SHEETF101B BASEMENT FLOOR - FIRE PROTECTION
ALTERNATES
· REPLACE ALL CEILING TILE THROUGH OUT PROJECT
· DEDUCT NEW CEILING IN TEACHING LAB 304. PROVIDE FORREPAIR OF GRID AND NEW TILE AS NEEDED.
· DEDUCT NEW COUNTER TOPS IN WORK ROOM 300.01. REUSEEXISTING COUNTER TOPS FROM RACKHAM
FO
R U
P
TO
4
0 L
BS
FO
R M
OR
E
TH
AN
4
0 L
BS
42" M
AX
60" M
AX
48" M
AX
2'-10
" MAX
MOUNTING HEIGHT FORDISPENSERS IS TO TOP OFDISPENSER OR HIGHESTOPERABLE PART
TO
WE
L D
IS
PE
NS
ER
S
& D
IS
PO
SE
RS
SO
AP
D
IS
PE
NS
ER
/ H
AN
D
SA
NIT
IZ
ER
TD
SD
4" MAX
48" T
YPIC
AL
1'-3"
MIN
MOUNTING HEIGHT FOR MIRROR:
BOTTOM EDGE OF MIRROR
PO
WE
R/D
AT
A/
PH
ON
E R
EC
EP
TA
CL
ES
LIG
HT
S
WIT
CH
ES
MIN 1 1/2" BETWEENTOP OF TP HOLDERAND BOT. OF GRABBAR
3'-0"
MAX
34"
HD
HA
ND
D
RY
ER
SND
SA
NIT
AR
Y N
AP
KIN
DIS
PE
NS
ER
FIR
E A
LA
RM
P
UL
L
IN
TE
RC
OM
HV
AC
C
ON
TR
OL
MOUNTINGHEIGHT IS TO TOPOF HIGHESTOPERABLE PARTOR RECEPTACLE
3'-8"
MAX
1'-5"
MAX
1'-3" MIN
SHELF,
WHERE
SPECIFIED
44
" O
VE
R
CO
UN
TE
R O
R
OB
ST
RU
CT
IO
N
WH
EN
OP
EN
TO
C
AB
IN
ET
HA
ND
LE
FILMILLUMINATOR
3'-6"
U.N
.O.
4'-6"
7'-2"
X"
4'-6"
4'-0"
2'-0"
5'-0"
4128
"
5'-0"
2'-0"
6'-6"
1'-6"
6'-0"
MONITOR &BRACKET
REMOTE MONITOR& BRACKET(@ CORRIDORLOCATIONS)
TVBRACKET
OTOSCOPE/SPHYGMOM-ANOMETER
SHARPSCONTAINER
GLOVE &APRON RACK
(S
IN
GL
E
BR
AC
KE
T)
(S
IN
GL
E
BR
AC
KE
T)
ADDITIONAL
BRACKET
SEGMENTS ADDED
AS REQUIRED
IV PUMP BAR(NON-FERROUS)
WALL-MOUNTEDWORKSTATION
FLIP DOWNWORKSTATION
SHOWER CURTAINROD, HOOKS, ANDCURTAIN
SHOWERNICHE
FOLDINGSHOWERSEAT
MOP & BROOMHOLDER - NOSHELF
MARKER BOARD/TACK BOARD
CHART ORMAGAZINERACK
HAIRDRYER
BED PANHOLDER
COATBRACKET& SHELF
SURFACEMOUNTEDPROJECTIONSCREEN
36"X48"
U.N.O.
44
" @
A
DA
48
" A
T
AC
CE
SS
IB
LE
BARRIER FREEEWC & DRINKINGFOUNTAIN
SINKS &LAVATORIES
URINALACCESSIBLE
TOILET, GRAB BAR &TOILET PAPERHOLDER
FOLD DOWNBABY CHANGINGTABLE
WALL MOUNTEDSEMI-RECESSEDFIREEXTINGUISHERCABINET
WALL MOUNTEDFIREEXTINGUISHER
MIRRORS
3'-8" 5'-
0"
3'-6"
48
" M
AX
A
T
AC
CE
SS
IB
LE
TOWEL BAR HOOK
GLOVEDISPENSER
SPECIMENPASS-THRU
6'-2"
3'-4"
3'-6"
3'-6"
3'-8"
MAX
3'-6"
MAX
3'-8"
MAX
4'-10
"
4'-0"
MAX
TO
B
OT
TO
M
OF
T
V
6" MAX9" MIN
9" M
IN
2'-3"
MIN
960"
MOUNTING
HEIGHT IS TO
SPOUT OUTLET
HEIGHT
8"
1 1/2
"
840"
1'-0" 3'-6"
1584
"
1920
"86
4"
6"3'-5"
1'-6"
3'-0"
1'-0"
INTERIOR ELEVATIONS LEGEND
6"
3'-9"
NOTE:REFER TO ARCH PLANS FOR ACCESSORIES AND THEIRLOCATIONS. THIS SHEET IS FOR STANDARD MOUNTING HEIGHTSONLY UNLESS NOTED ELSEWHERE IN THIS DRAWING SET
ABHR
MA
X.
FLOOR
ABHR
LEGEND
1. NO PROJECTION CAN EXTEND OUT MORE THAN 4" INTO
CORRIDOR OR WALKWAY.
2. ALCOHOL BASED HAND RUB SANITIZERS CANNOT BE LOCATED
ABOVE A POTENTIAL IGNITION SOURCE
3. ABHR MUST BE OFFSET A MINIMUM OF 1" HORIZONTALLY FROM
ANY LIGHT SWITCH, ELECTRICAL OR DATA RECEPTACLE,
THERMOSTAT OR OTHER POTENTIAL IGNITION SOURCE.
4. ABHR SANITIZERS CANNOT BE INSTALLED IN A CORRIDOR LESS
THAN 6' WIDE
5. ABHR MUST BE AT LEAST 4' APART
6. ABHR CANNOT BE INSTALLED OVER CARPET IN NON-SPRINKLED
SPACES.
7. MAX. CAPACITY OF DISPENSERS IN CORRIDORS: 0.3 GALLONS
NOTES
ALCOHOL BASED HAND RUB SANITIZER DISPENSER
LIGHT SWITCH/RECEPTACLE OR OTHER POTENTIAL IGNITION SOURCE
44"1"
MIN.
1"MIN.
MA
X.
IF ABHR IS NEXTTO POTENTIALIGNITION SOURCE,IT MUST BEOFFSET 1"HORIZONTALLY.
ABHR CAN BEBELOWPOTENTIALIGNITION SOURCE,NO ISSUES.
ABHR CANNOT BEABOVE POTENTIALIGNITION SOURCE.
ABHR
ABHR
44"
ALCOHOL BASED HAND RUB SANITIZERSMOUNTING REQUIREMENTS
FLOOR
FLOOR
FLOOR
FLOOR
A-002
PLANS
EXISTING WALLS TO REMAIN
NEW WALLS
ACROVYN CORNER GUARD - FULL HEIGHT
END CAP - FULL HEIGHTACG
ECFIRE EXTINGUISHER CABINET -SEMI-RECESSED (ADA)
FEC
EXISTING WALLS TO BE REMOVED
NEW DOOR W/ DOOR NUMBER
EXISTING DOOR TO BE REMOVED
CUBICLE CURTAIN TRACK
2'x2' FLUORESCENT LIGHT FIXTURE
2'x4' FLUORESCENT LIGHT FIXTURE
NEW SUSPENDED ACOUSTICAL CEILING @ 8'-0" AFFU.N.O.
GYPSUM BOARD CEILING @ 7'-6" AFF U.N.O.
RECESSED DOWN LIGHT FIXTURE
TREATMENT ROOM LIGHT FIXTURE
EXIT LIGHT (CEILING MOUNTED)
SMOKE DETECTOR
FIRE SPRINKLER HEAD - NEW SPRINKLER HEADS ARESHOWN FOR COORDINATION PURPOSES ONLY. FINALSPRINKLER HEAD LOCATIONS SHALL BE DETERMINEDBY A CERTIFIED FIRE PROTECTION FIRM, ANDCOORDINATED WITH ARCHITECT & ENGINEERS.
FIRE ALARM - SEE ELECTRICAL DWG.
WIRELESS ANTENNA - SEE ELECTRICAL DWG.
SPEAKER
EXISTING DOOR TO REMAIN
RETURN GRILLE - SEE MECHANICAL DWG.
EXHAUST GRILLE - SEE MECHANICAL DWG.
SUPPLY GRILLE - SEE MECHANICAL DWG.
PLAN IDENTIFICATIONW/NORTH ARROW
SECTION LOCATION IDENTIFICATION
DETAIL LOCATION IDENTIFICATION ATENLARGED SCALE
ELEVATION LOCATION IDENTIFICATION
KEYNOTE IDENTIFICATIONDEMO / NEW / MISC
BULLETIN IDENTIFICATION W/CLOUD
ROOM NAME & NUMBER
1. DO NOT SCALE DRAWING REPRODUCTIONS.2. THIS DRAWING REPRESENTS TYPICALLY ENCOUNTERED
ITEMS. NOT ALL ITEMS SHOWN MAY OCCUR WITHIN THESCOPE OF THIS PROJECT. REFER TO COMPLETESPECIFICATIONS AND DRAWING DOCUMENTATION SET.
GRID BUBBLE
DOOR NUMBER TAG
CEILING HEIGHT TAGEXISTING / NEW
EXISTING SUSPENDED ACOUSTICAL CEILING TO BEREMOVED
ACOUSTICAL CEILING TILEACT
CEILING HEIGHTCH
CEILINGCLG
EXISTING(X)
EXPANSION JOINTEJ
GAUGEGA
HARDWAREHDWR
HOLLOW METALHM
HEIGHTHT
INTERIOR DESIGNID
LAVATORYLAV
MAXIMUMMAX
MANUFACTURERMFR
MINIMUMMIN
MASONRY OPENINGMO
PLASTIC LAMINATEPLAM
SQUARE FEETSF
SIMILARSIM
SPECIFICATIONSSPEC
UNLESS NOTED OTHERWISEUNO
WATER CLOSETWC
WITH
W/O WITHOUT
RO ROUGH OPENING
NTS NOT TO SCALE
CENTER LINECL
OH OVERHEAD
GYPSUM BOARDGB
TYPICALTYP
CONTROL JOINTCJ
VINYL WALL COVERINGVWC
STAINLESS STEELSSTL
GLASSGL
WALL PROTECTIONWP
JC JANITORS CLOSET
RB RESILIENT BASE
CERAMIC TILECT
PT PAINT
CONTRACTOR FURNISHED/ INSTALLEDCFI
CAPITAL EQUIPMENTCE
ABOVE FINISH FLOORAFF
WOODWD
CARPETCPT
VINYL COMPOSITION TILEVCT
LIGHTLT
LINEAL FEETLF
EQUALEQ
BUREAU OF FIRE SAFETYBFS
HEALTH FACILITIES ENGINEERING SECTIONHFES
HOUR, HAND RAILHR
OPPOSITE HANDOPP
W/
FIRE ALARMFA
CJ CONTROL JOINT
KP KICK PLATE
JT JOINT
EACHEA
ELEVATOR, ELEVATIONELEV
FLOOR DRAINFD
UNDERWRITERS LABORATORY INCUL
PVC POLYVINYL CHLORIDE
QTY QUANTITY
CORNER GUARDCG
CARD READERCR
FV FIELD VERIFY
ARCHITECTURAL SYMBOLS LEGEND
FLOOR PLAN LEGEND
SOLID SURFACESSRF
REFLECTED CEILING PLAN LEGEND
GENERAL NOTESABBREVIATIONS LIST
EXISTING SUSPENDED ACOUSTICAL CEILING
DATUM/ELEVATION LOCATION ID
1
EXISTING WINDOW SYSTEM
NEW WINDOW SYSTEM
2'x2' FLUORESCENT INDIRECT LIGHT FIXTURE
~
S
FA
WA
EXISTING DOUBLE DOOR TO BE REMOVED
EXISTING DOUBLE DOOR TO REMAIN
NEW DOUBLE DOOR W/ DOOR NUMBER
TEMPORARY 1-HR PARTITION AND DOOR
LAVATORY SINK
CLINICAL SINK
SQUARE SINK
ROUND SINK
MOP/CORNER SINK
FLOOR TOILET
WALL HUNG TOILET
URINAL
TANK STYLE TOILET
GRAB BAR
XX
XXXX
X'-X"
XXXX
C3
D4
A1
B2
Main Floor LevelEL:100'-0"
0001
XX
XXXX
GRIDGRID
NewExist
NEWROOM NAME000
DXXXX
DXX
XX
DXX
XX
00 06
EQUIPMENT TAG
00 WALL TYPE TAG
CT-1 INTERIOR FINISH TAG
SSTL
RSF
STAINLESS STEEL
RESILIENT SHEET FLOORING
DOOR OPENINGDO
(R) RELOCATE
01Axxxx Scale: 1/8" = 1'-0"
Plan Name - Bottom LinePlan Name - Top Line
DRINKING FOUNTAIN
PTM PATCH TO MATCH
CAM CAMERA - SEE ELECTRICAL DWG.
OS OCCUPANCY SENSOR (CEILING MOUNTED)
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFVI OWNER FURNISHED VENDOR INSTALLED
OFOI OWNER FURNISHED OWNER INSTALLED
Abbreviations, Drawing SymbolsStandard & Standard MountingHeights
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
CEILINGFINISH
ROOM FINISH SCHEDULE
DW
G #
ROOM NAMEROOM NO. TRANSITIONMAT.
ROOM FLOORMAT.
EAST WALL
MAT. FINISH MAT. MAT.FINISH FINISH
NORTH WALLBASE SOUTH WALL
MATERIALMAT.FINISH FINISH TYPE MATERIAL
WINDOW SILLWEST WALL
CABINETS
MILLWORKFINISH MOUNT HEIGHT MATERIAL FINISH
BULKHEADROOM #
REMARKS
A-20
A-2
01-B
COUNTER
INDEX OF FINISH MANUFACTURERS
PAINT- PT-1MANUFACTURER: SHERWIN WILLIAMSTYPE: PAINTCOLOR: SW7568 NEUTRAL GROUNDFINISH: SEMI-GLOSS
FIRE-RATED
CEILING DATA
PLASTER
ACOUSTIC LAY-IN TILEACOUSTIC TEGULAR TILE
GYPSUM WALLBOARDGYPSUM PLASTER
FIBER REINFORCED GYPSUM PANELFIBER REINFORCED GYPSUM PANEL
HUMIDITY RESISTANT LAY IN TILEABUSE RESISTANT LAY IN TILE
TF
CLN
CSH
ST&VS&L
PT
S&V
PREW
S
GRAN
S&W
WDSRF
N
RSF
RTRCONQT
RTFCTSV
CP
TERR
WD
RFRTRCON
RBRSB
SEAL & VARNISHSEAL & LACQUERSTAIN & VARNISH
CONCRETE SEALER/HARDENERTEXTURE FINISH
CLEANPREFINISHED
PAINT
SEAL
WAX
RESILIENT SHEET FLOORINGRESILIENT TILE FLOORING
RUBBER TREAD & RISERRUBBER FLOORING
GRANITE TILE
SEAL & WAXFINISH
SLATEWOODNONE
CERAMIC & PORCELAIN TILE
QUARRY TILECONCRETE
RNS
QT
RUBBER FLOORINGRUBBER TREAD & RISER
RESILIENT BASERESILIENT SHEET BASEQUARRY TILE
RUBBER
WOODSLATE
NONE
CONCRETE
AMCT
FLOOR DATA
SHEET VINYL
CARPET
TERRAZZO
MATERIAL
CPTERR
BASE DATA
CERAMIC TILEAGGLOMERATED MARBLETERRAZZOCARPET
ARCHBARCBCARCBDBARCBSBARCB2ARCB1
CONCRETE MASONRY UNITS
AGGLOMERATED MARBLEACOUSTIC BLOCK - SOUND ABSORBING
FACE BRICK TRIM COURSING
GROUND FACE MASONRY UNITS
FBTCEXISTING FACE BRICK
WALL FABRICQUARRY TILECERAMIC & PORCELAIN TILE
SLATENONE
SN
AMCTQT
EFB
WF
GMFU
FACE BRICKPOLY-RESIN
LIGHTWEIGHT BLOCKPOURED CONCRETE
PRFB
AB
CMU
LBPC
PCPGB
ARCB
VC
FIBER REINFORCED GYPSUM PANEL FIRE-RATEDFIBER REINFORCED GYPSUM PANELGYPSUM WALLBOARD FIRE-RATED
WALL DATA
GYPSUM WALLBOARD-LEAD LINEDGWFRF
GW-LL
FFR
ARCHITECTURAL BLOCK - DOUBLE BULLNOSEARCHITECTURAL BLOCK - SINGLE BULLNOSEARCHITECTURAL BLOCK #2 - SINGLE SCORED FACEARCHITECTURAL BLOCK #1 - SPLIT RIB1 SR-1ARCHITECTURAL BLOCK TYPE "D" TRIM COURSING
ARCHITECTURAL HALF BLOCKARCHITECTURAL BLOCK CAP
GLASS BLOCKPORTLAND CEMENT PLASTER
VINYL COVERED
ARLITHRLIT
PL
ATTACT
GSP
FFFR
GW
MIRROR, FIXED
ROOM ACCESSORIES
TOILET TISSUE DISPENSER
MOP & BROOM HOLDERSSHOWER CURTAIN RODS
GRAB BAR ASSEMBLYROBE HOOKS
FRAMED TILTED MIRROR, FIXEDFRAMED MIRROR, FIXED
SANITARY NAPKIN VENDOR
WASTE RECEPTACLETOWEL BARS
ELECTRIC HAND DRYERPAPER TOWEL DISPENSER
SOAP DISPENSER
SANITARY NAPKIN DISPOSAL
FOLDING SHOWER SEATCERAMIC SOAP DISH
W/ ACOUSTIC BATTSCERAMIC TILE
MOUNTING
SUSPENDEDFURSUS
NCT
FURRED
NONE
EXPOSED STRUCTUREEXPOSED ACOUSTIC DECKEXPOSED METAL DECKACOUSTICAL METAL DECKAMDAB
EADEMD
ES
WR
CSD
SNV SND
FS
GBA RH CR
MF
MBHFTMF FMF
TBSD
TTD HD TD
ITEM
LEGEND OF ABBREVIATIONS
MATERIAL MATERIAL MATERIAL
VCB VINYL COMPOSITE BASE
WOODWD
STAINLESS STEELSSTLGRANITEGRANGLASSGLCURTAIN WALLCWFABRIC SCRIMFAB
GYPSUM WALLBOARDGW
WOODMETAL PRIMEDMETAL PRE-FINISHEDANODIZED ALUMINUM
STAIN GRADEVARNISH GRADE
PREFINISHEDPLASTIC LAMINATEANODIZED ALUMINUMPERMANODICPAINTFACTORY FINISHMATCH EXISTING
HARDBOARD
LOUVREDOOR FINISH
TEMPERED INSULATED
INSULATED HOLLOW METALGEORGIAN POLISHED WIRE
REFLECTIVE INSULATED
TICLEAR INSULATED
RICI
HOLLOW CORE WOODSOLID CORE WOODALUMINUMHOLLOW METAL
GAUGECLEAR FLOATTEMPERED
LAMINATEDREFLECTIVETINTED
GLASS
G
TRL
TCF#
PER
MEFFPT
PLAMPRE
AA
VGSG
HB MP/FAA
MPW HOLLOW METAL WELDED
SEAL & VARNISHS&V
FIXED MULLIONREMOVABLE MULLION
SEAL & LACQUERS&L
RMFM
ALUMINUMTHERMALLY BROKENSOLID WOODHOLLOW METAL
WELDEDSTANDARD
STAIN & VARNISH
PERMANODICANODIZED ALUMINUM
FINISHES
KNOCKDOWN
AA
ST&V
PERP
STD
PAINTSW
WEL
HMKD
HMW
TBAL
REMOVABLE MULLION
THRESHOLDWEATHER STRIPSOUND STRIP
WEATHER CAP
LOCK SEAMWELD SEAM WINDOW TREATMENTS
BARRIER FREE OPERATORBFORM
WSTLS
WS
ASTRAGAL
HARDWAREFRAME CONSTRUCTION
FRAME DATA
SSAWC
HOLLOW METAL WELDED (LEAD)HMW-L
HMIHM
SCWHCW
DOOR CONSTRUCTION
PL PLASTIC LAMINATE
WALL PROTECTION (ACROVYN)WP
PTM PATCH TO MATCHNW NO WORKX EXISTING
AL
CPT CARPET TILEGYPSUM VENEER PLASTERGVPPORTLAN CEMENT PLASTERPCP
GYPSUM PLASTERGSPGYPSUM VENEER PLASTERGVP
FIBERGLASS REINF'D POLYMERFRP
FIBERGLASS REINF'D POLYMERFRP
(SHOP DRAWINGS AND SAMPLES MUST BE SUBMITTED FOR FINAL APPROVAL ON ALL INTERIOR FINISHES)
PAINT- PT-2
WALL BASE - RB-1MANUFACTURER: ROPPETYPE: PINNACLE RUBBER BASECOLOR: 193 BLACK BROWNSIZE: 4"
Room Finish Schedule
021 COMPUTER LAB - - - - - GW - GW GW GW - - - - - CLNG PLAN - - - 021
A-2
01
MANUFACTURER: SHERWIN WILLIAMSTYPE: PAINTCOLOR: SW7693 STONEBRIARFINISH: SEMI-GLOSS
PAINT- PT-3MANUFACTURER: SHERWIN WILLIAMSTYPE: PAINTCOLOR: SW7006 EXTRA WHITEFINISH: EXTRA WHITE
CARPET TILE - CPT-1MANUFACTURER: BENTLEYTYPE: TECH UPD8 AFIRMA HARDBACKCOLOR: GEOMETRY 400005SIZE: 18"x36"
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
006 OPEN OFFICE RTF-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 006
A-2
01-M
ACOUSTIC CEILING TILE - ACT-1MANUFACTURER: ARMSTRONGMODEL: ULTIMA 1951 BEVELED TEGULARCOLOR: WHITESIZE: 24" x 24" (15
16" Grid)
RESILENT TILE FLOORING - RTF-1MANUFACTURER: ARMSTRONGTYPE: TBDCOLOR: TBDSIZE: 12" x 12"
006.1 CLOSET RTF-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 006.1
006.2 OFFICE RTF-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 006.2
006.3 OFFICE RTF-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 006.3
A-2
03
006.4 OFFICE RTF-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 006.4
005 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 005
005.1 HEARING FITTING ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 005.1
005.2 LAB STROAGE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 005.2
005.3 SUPERVISOR OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 005.3
005.4 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 005.4
013 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 013
013.1 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 013.1
013.2 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 013.2
015 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 015
023 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 023
023.1 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 023.1
025 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 025
103 RECEPTION CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 103
103.1 TYPICAL OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 103.1
103.3 STROAGE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 103.3
105 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 105
105.1 TYPICAL OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 105.1
105.3 WORK ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 105.3
300 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 300
300.01 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 300.01
300.02 TYPICAL OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 300.02
300.05 TREATMENT CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 300.05
300.06 TYPICAL OBSERVATION CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 300.06
300.11 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 300.11
304 TEACHING LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 304
322.1 UNISEX ADA EXST - - EXST - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 322.1
326 UNISEX ADA EXST - - EXST - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 326
325 OBSERVATION CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 325
328 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 328
328.01 TYPICAL OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 328.01
328.1 WORK ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 328.1
327 TREATMENT CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 327
variesse
e sc
hedu
lesee schedule
hollow metalframe
F1
see
sche
dule
variessee schedule
D1
provide acousticfirestop sealant allthrough-wallpenetrations - typical
SECTION AT DECK
acoustic tile ceiling onmetal suspensionsystem
base refer to roomfinish schedule
PLAN
7 1/4"6"
(actual)
SECTION AT FLOOR
SECTION AT CEILING
provide acousticfirestop sealant bothsides of partition asshown
runner stud atbase of partition
W1
Wall Composite:5
8" type x gyp bd, each side6" metal studs @ 16" o.c.w/ 5 1/2" sound attenuating batt
continuous firestop sealanteach side (typ)
existing structure
runner
1/2"
SMOKE TIGHTWALL
SECTION AT FLOOR
5/8" Soundbreak gyp bd, each side on1" Z channels @ 24" o.c.on existing wall construction
1 5/8"(actual)
provide acousticsealant both sides ofpartition as shown
base refer to roomfinish schedule
W2
PLAN
SECTION AT CEILING
2" (nominal)
runner stud atbase of partition
existing wall
existing structure
runner
continuous acoustic sealant
SECTION AT DECK
acoustic tile ceiling onmetal suspensionsystem
1 5/8"
2"
note: provide acousticsealant around allelectrical outlets andother wall penetrations
CARPET
TRANSITION STRIP
CERAMIC TILE
T1
refe
r to
plan
2"
1 2"
hollow metal frameattach/anchor per mfgrrecommendations
16 guage doublestuds at doorframes typicalexisting wall1/4" min shimspace (all sides)
continuous sealantall sides of frame
door (refer toschedule)
provide doorsilencers (3 perjamb min)
refer to plan
2"
12"
hollow metalframeattach/anchorper mfgrrecommendations
16 guage doublestuds at doorhead typical
existing wall
continuoussealant allsides of frame
door (refer toschedule)
provide doorsilencers (3 perjamb min)
SERIESDOORMAT.
DOOR AND FRAME SCHEDULE
WIDTH
DOOR DATADW
G. N
o.No. QTY.DOOR DOOR
THICK.HEIGHT TYPESIZE DOOR
LOUVERGAUGESERIES HRS.RATING
TRANSOMGLASS DETAILJAMB
FRAME DATA
FINISH TYPEFRAME
MAT.FRAME No.
DOORHARDWARE
FINISHGLASSHRS.
RATING No.GROUP
REMARKS
Door
Unde
rcut
A-30
03A-100 Scale: 1/4" = 1'-0"
Door Types
NOTE: GENERAL CONTRACTOR TO REVIEW DOOR HARDWARE WITH OWNER PRIOR TO ANY INSTALLATION
DETAILHEAD
D001.1 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 1 DOOR TO BE SMOKE TIGHT - - D001.1
DOOR REMARKS:
1. Contractor to coordinate with WSU reuse of existing doors and frames from
storage. Verify quantity, size, fire rating and condition of existing doors prior
to any installation.
02A-100 Scale: 1/4" = 1'-0"
Frame Types
HARDWARE GENERAL NOTES:
General notes:
1. Contractor shall verify all existing field conditions and notify architect
immediately if that which exists differs from that which is shown on
drawings.
2. All work to comply with Federal, State and Local codes, laws and
ordinances.The requirements of ICC/ANSI A117.1 and the Americans with
disabilities act (ADA) are to be fully satisfied. All work shall meet the most
stringent requirements of both including, but not limited to clearances,
limitations, accessories, etc.
3. These drawings are prepared in accordance with the limited services for
which the architect was contracted. The architect makes no representation
that the interpretation of these documents will result in complete compliance
with the ADA.
4. All doors required to be labeled shall be set in labeled frames and identified
with UL label and be provided with approved self-closing devices and
positive latching hardware.
5. All designated exit doors shall be equipped with the required egress
hardware.
6. Supplier shall meet with owner to establish MK keying system and provide a
combinated cylinder for each locking device as direct by owner. Supplier
shall submit key schedule for final approval. Furnish 2 change keys per
cylinder and 2 master keys total.
7. Supplier shall furnish and provide all necessary reinforcements, brackets,
fasteners, spacers and fillers to provide a complete functioning opening.
8. Supplier shall furnish complete shop drawings including; vertical typed
hardware schedule, product data sheets and warranty information following
DHI prescribed methods.
DOOR HARDWARE:
Hardware Set 1 (Classroom)
1 set Smoke Seal 797B Blk Reese
Hardware Set 2 - Passage set (Always Unlocked)
3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ
1 ea. Passage Set MR 126 DJSJ 32D PDQ
1 ea. Wall Stop 102 26D PDQ
Hardware Set 3 - Classroom Lock (Lock/Unlock)
3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ
1 ea. Classroom lock MR 148 DJSJ-SFL 32D PDQ
1 ea. Wall Stop 102 26D PDQ
Hardware Set 4 - Office Lock (Lock/Unlock)
3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ
1 ea. Office Lock MR 116 DJSJ-SFL 32D PDQ
1 ea. Wall Stop 102 26D PDQ
Hardware Set 5 - Classroom Lock (Lock/Unlock) + Closer
3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ
1 ea. Classroom Lock MR 148 DJSJ-SFL 32D PDQ
1 ea. Closer 7101 BC EDA (Pull side Mount) AL PDQ
1 ea. Wall Stop 102 26D PDQ
1 ea. Kickplate 98 10 x 2" LDW 32D PDQ
Hardware Set 6 - Add Smoke Seal
1 set Smoke Seal 797B Blk Reese
1 set Flex Smoke Astragal 103C x 103C AL Reese
Hardware Set 7 - Classroom Lock (Lock/Unlock) + Closer
3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ
1 ea. Classroom Lock MR 148 DJSJ-SFL 32D PDQ
1 ea. Closer 7101 BC PA Regular Arm (Pull side Mount) AL PDQ
1 ea. Wall Stop 102 26D PDQ
1 ea. Kickplate 98 10 x 2" LDW 32D PDQ
Hardware Set 8 -Privacy Set w/ indicator (Lock/Unlock) + Closer
3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ
1 ea. Privacy Set w/ indicator MR 148 DJSJ-SFL 32D PDQ
1 ea. Closer 7101 BC PA Regular Arm (Pull side Mount) AL PDQ
1 ea. Wall Stop 102 26D PDQ
1 ea. Kickplate 98 10 x 2" LDW 32D PDQ
Door Schedule & Wall Types01
A-30 Scale: 1 1/2" = 1'-0"
W-2 WALL TYPE 01A-30 Scale: 1 1/2" = 1'-0"
W-1 WALL TYPE
A-2
01-B
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
D001.2 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 1 SOOR TO BE SMOKE TIGHT - - D001.2
D001.3 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 1 DOOR TO BE SMOKE TIGHT - - D001.3
D001.4 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 1 DOOR TO BE SMOKE TIGHT - - D001.4
D001.5 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 1 DOOR TO BE SMOKE TIGHT - - D001.5
D001.6 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 1 DOOR TO BE SMOKE TIGHT - - D001.6
D005.1 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - PASSAGE 2 - - - D005.1
D005.2 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - CLASSROOM 3 - - - D005.2
D005.3 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - OFFICE 4 - - - D005.3
D005.4 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - OFFICE 4 - - - D005.4
D023.1 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - CLASSROOM 5 - - - D023.1
D025 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - CLASSROOM 5 DOOR TO BE RELOCATED FROM RCKHAM - - D025
D030 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 6 DOOR TO BE SMOKE TIGHT - - D030
D040 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 6 DOOR TO BE SMOKE TIGHT - - D040
D300 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - CLASSROOM 7 - - - D300
D322.1 1 3'-6" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - PRIVACY 8 - - - D022.1
D327 1 3'-6" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - CLASSROOM 7 - - - D327
D330 1 3'-0" 7'-0" - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 6 DOOR TO BE SMOKE TIGHT - - D330
D340 1 3'-0" 7'-0" - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 6 DOOR TO BE SMOKE TIGHT - - D340
03A-002 Scale: NTS
Floor Transition
UP
Storage103.3
Office103.4
Office103.5
Recept103
Office103.1
Office103.2
Mech
Lobby
UP
Lounge100
Jan100.2
Mech100.1
UP
DN
DN
DN
EXTERIORCIRCULATION
SECONDFLOOR ABOVE
BASEMENTFLOOR BELOW
BASEMENTFLOOR BELOW
ELEV
NIC NIC
NIC
NIC
AD-101
01A-101 Scale: 1/8" = 1'-0"
First Floor Plan - Demolition WorkPrentis Building
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building 1st Floor Plan -Demolition Work
LEGEND
Remove existing gypsum and metal stud wall full height
walls
floors
01
GENERAL DEMOLITION NOTES
A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.
B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.
C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.
D. room numbers and room names on all existing drawings relate only to demolitionsheets.
E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.
F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.
G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.
H. repair all surfaces and components damaged during demolition and construction.
I. coordinate scope and extent of demolition work with new work plans and details.
items to be removed
existing items to remain
remove existing door & frame assembly, including all relatedhardware.40
doors
50
misc items
DEMOLITION NOTES
all existing furniture, file cabinets, and other movable equipmentthat is not tagged to remain is to be removed by WSU
30
ceilings
remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.
51 Remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.Remove portion of existing gypsum & metal stud wall for new door02
21Existing flooring and wall base to be removed. Prep floor fornew finish per specifications. Patch and repair existingconcrete floor slab.
22 Existing flooring to remain.
52 Remove existing toilet partition.
Remove portion of existing gypsum & metal stud wall for new one-way mirror03
31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.
I. coordinate scope and extent of demolition work with new work plans and details.
J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.
K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.
L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications
53 Remove existing millwork
54 Remove existing signage
Remove portion of existing block wall. provide temporary structural support03
21
21 21 21
21 21
21
54
5050 50
50
50 50
Teaching Lab027
Lab025
Lab023
ComputerLab021
Classroom017
Classroom019
PLC016.11
Tele016.10
Mech016
Mech016.2
Mech016.3
Mech016.4
Lab015
Lab013
Classroom010
Classroom008
Office006
Office006.2
Office006.3
Office006.4
Classroom004
Classroom002
Women031
Men029
Jan012
EngOffice014
Storage020
Storage007
C&IT030
2'-0"10'-8"9'-4" 6'-8"
STAIR001
STAIR030
STAIR040
Mech016
Mech016
AD-101-B
01A-101 Scale: 1/8" = 1'-0"
Basement Plan - Demolition WorkPrentis Building
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building Basement FloorPlan - Demolition Work
LEGEND
Remove existing gypsum and metal stud wall full height
walls
floors
01
GENERAL DEMOLITION NOTES
A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.
B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.
C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.
D. room numbers and room names on all existing drawings relate only to demolitionsheets.
E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.
F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.
G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.
H. repair all surfaces and components damaged during demolition and construction.
I. coordinate scope and extent of demolition work with new work plans and details.
items to be removed
existing items to remain
remove existing door & frame assembly, including all relatedhardware.40
doors
50
misc items
DEMOLITION NOTES
all existing furniture, file cabinets, and other movable equipmentthat is not tagged to remain is to be removed by WSU
30
ceilings
remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.
51 Remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.Remove portion of existing gypsum & metal stud wall for new door02
21Existing flooring and wall base to be removed. Prep floor fornew finish per specifications. Patch and repair existingconcrete floor slab.
22 Existing flooring to remain.
52 Remove existing toilet partition.
Remove portion of existing gypsum & metal stud wall for new one-way mirror03
31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.
I. coordinate scope and extent of demolition work with new work plans and details.
J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.
K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.
L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications
53 Remove existing millwork
54 Remove existing signage
Remove portion of existing block wall. provide temporary structural support03
21 5021 50
21 50
21 50
21 50
21 50
21 50
21 50
21 50
21 50
04 04
53 5340
40404040
404040
40
40
21 50
Open to Below
OpenOffice105
WorkRoom105.3
Office105.4
Office105.5
Office105.2
Office105.1
DN DNUP
Elev
Open to Below
UP
DN
Jan102.1
Lounge102
DN
NIC NIC
NIC
NIC
NIC
AD-101-M
01A-101 Scale: 1/8" = 1'-0"
Mezzanine Floor Plan - Demolition WorkPrentis Building
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building Mezzanine FloorPlan - Demolition Work
LEGEND
Remove existing gypsum and metal stud wall full height
walls
floors
01
GENERAL DEMOLITION NOTES
A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.
B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.
C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.
D. room numbers and room names on all existing drawings relate only to demolitionsheets.
E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.
F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.
G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.
H. repair all surfaces and components damaged during demolition and construction.
I. coordinate scope and extent of demolition work with new work plans and details.
items to be removed
existing items to remain
remove existing door & frame assembly, including all relatedhardware.40
doors
50
misc items
DEMOLITION NOTES
all existing furniture, file cabinets, and other movable equipmentthat is not tagged to remain is to be removed by WSU
30
ceilings
remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.
51 Remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.Remove portion of existing gypsum & metal stud wall for new door02
21Existing flooring and wall base to be removed. Prep floor fornew finish per specifications. Patch and repair existingconcrete floor slab.
22 Existing flooring to remain.
52 Remove existing toilet partition.
Remove portion of existing gypsum & metal stud wall for new one-way mirror03
31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.
I. coordinate scope and extent of demolition work with new work plans and details.
J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.
K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.
L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications
53 Remove existing millwork
54 Remove existing signage
Remove portion of existing block wall. provide temporary structural support03
21 50 21 50
21 50
21 5021 50
21 50
53
53
54
Observation300.1
Treatment300.09
Office300.08
Treatment300.05
Observation300.06
Office300.07
OpenOffice300.11
OpenOffice300
Office300.04
Office300.03
Office300.02
TEACHINGLAB304
Office303
WORKROOM300.01
UNISEX ADARESTROOM322.1
WOMEN'SRESTROOM326
Office328.01
Office328.02
Office328.03
Office328.04
Office328.05
COPY328.06
Office328.07
OpenOffice328
Office328.08
Office328.09
WorkRoom328.10
Observation325
Treatment327
STAIR330
STAIR340
6'-8"
3'-5"5'-0"
1'-8"
5'-0"
A701
05
03
04
AD-103
01A-101 Scale: 1/8" = 1'-0"
Third Floor Plan - Demolition WorkPrentis Building
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building 3rd Floor Plan -Demolition Work
LEGEND
Remove existing gypsum and metal stud wall full height
walls
floors
01
GENERAL DEMOLITION NOTES
A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.
B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.
C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.
D. room numbers and room names on all existing drawings relate only to demolitionsheets.
E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.
F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.
G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.
H. repair all surfaces and components damaged during demolition and construction.
I. coordinate scope and extent of demolition work with new work plans and details.
items to be removed
existing items to remain
remove existing door & frame assembly, including all relatedhardware.40
doors
50
misc items
DEMOLITION NOTES
all existing furniture, file cabinets, and other movable equipmentthat is not tagged to remain is to be removed by WSU
30
ceilings
remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.
51 Remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.Remove portion of existing gypsum & metal stud wall for new door02
21Existing flooring and wall base to be removed. Prep floor fornew finish per specifications. Patch and repair existingconcrete floor slab.
22 Existing flooring to remain.
52 Remove existing toilet partition.
Remove portion of existing gypsum & metal stud wall for new one-way mirror03
31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.
I. coordinate scope and extent of demolition work with new work plans and details.
J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.
K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.
L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications
53 Remove existing millwork
54 Remove existing signage
Remove portion of existing block wall. provide temporary structural support03
5021 5021 5021 5021 5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
5021
50215021
01
01 0101
01
02
0303
22
22
40
40
40 40 40
40
40
40
51
52
5152
22
53
Teaching Lab027
Lab025
Lab023
ComputerLab021
Classroom017
Classroom019
PLC016.11
Tele016.10
Mech016
Mech016.2
Mech016.3
Mech016.4
Lab015
Lab013
Classroom010
Classroom008
Office006
Office006.2
Office006.3
Office006.4
Classroom004
Classroom002
Women031
Men029
Jan012
EngOffice014
Storage020
Storage007
C&IT030
STAIR001
STAIR030
STAIR040
Mech016
Mech016
EXST EXST
EXST
EXSTEXST
EXST
xLFxLFxLFxLF
xLF
xLF xLF
xLF xLF xLF
xLFxLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF xLF
xLFxLF
xLF xLF
xLFxLF
xLF xLF
xLFxLF
LF
LF
LF
LFLF
LF
LF LF
LF LF
LFLF
LF
AD-104-B
01A-101 Scale: 1/8" = 1'-0"
Basement RC Plan - Demolition WorkPrentis Building
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building Basement ReflectedCeiling Plan - Demolition Work
LEGEND
Remove existing gypsum and metal stud wall full height
walls
floors
01
GENERAL DEMOLITION NOTES
A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.
B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.
C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.
D. room numbers and room names on all existing drawings relate only to demolitionsheets.
E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.
F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.
G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.
H. repair all surfaces and components damaged during demolition and construction.
I. coordinate scope and extent of demolition work with new work plans and details.
items to be removed
existing items to remain
remove existing door & frame assembly, including all relatedhardware.40
doors
50
misc items
DEMOLITION NOTES
all existing furniture, file cabinets, and other movable equipmentthat is not tagged to remain is to be removed by WSU
30
ceilings
remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.
51 Remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.Remove portion of existing gypsum & metal stud wall for new door02
21Existing flooring and wall base to be removed. Prep floor fornew finish per specifications. Patch and repair existingconcrete floor slab.
22 Existing flooring to remain.
52 Remove existing toilet partition.
Remove portion of existing gypsum & metal stud wall for new one-way mirror03
31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.
I. coordinate scope and extent of demolition work with new work plans and details.
J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.
K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.
L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications
53 Remove existing millwork
54 Remove existing signage
Remove portion of existing block wall. provide temporary structural support03
3050
30
30
31 31
3131
31
31
31
31
31
31
31
31
31
31
31
31
31
31
31
Observation300.1
Treatment300.09
Office300.08
Treatment300.05
Observation300.06
Office300.07
OpenOffice300.11
OpenOffice300
Office300.04
Office300.03
Office300.02
TEACHINGLAB304
Office303
WORKROOM300.01
UNISEX ADARESTROOM322.1
WOMEN'SRESTROOM326
Office328.01
Office328.02
Office328.03
Office328.04
Office328.05
COPY328.06
Office328.07
OpenOffice328
Office328.08
Office328.09
WorkRoom328.10
Observation325
Treatment327
STAIR330
STAIR340
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXSTEXST
EXST EXST
EXST
EXSTEXSTEXST
EXST
EXST
EXST
EXST EXST EXST EXST
EXST
EXST EXSTEXST
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF xLF
xLFxLF
xLF xLF
xLFxLF
xLF xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF xLF xLF
xLF
xLF
xLF xLF xLF
xLF xLF xLF
xLF xLF
xLF xLF
xLF
xLF xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF xLF
xLF
xLF xLF
xLF
xLF
xLF
xLF xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLFxLFxLF
xLFxLFxLF
xLF
AD-105
01A-101 Scale: 1/8" = 1'-0"
Third Floor Plan - Demolition WorkPrentis Building
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building 3rd Floor reflectedCeiling Plan - Demolition Work
LEGEND
Remove existing gypsum and metal stud wall full height
walls
floors
01
GENERAL DEMOLITION NOTES
A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.
B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.
C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.
D. room numbers and room names on all existing drawings relate only to demolitionsheets.
E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.
F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.
G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.
H. repair all surfaces and components damaged during demolition and construction.
I. coordinate scope and extent of demolition work with new work plans and details.
items to be removed
existing items to remain
remove existing door & frame assembly, including all relatedhardware.40
doors
50
misc items
DEMOLITION NOTES
all existing furniture, file cabinets, and other movable equipmentthat is not tagged to remain is to be removed by WSU
30
ceilings
remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.
51 Remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.Remove portion of existing gypsum & metal stud wall for new door02
21Existing flooring and wall base to be removed. Prep floor fornew finish per specifications. Patch and repair existingconcrete floor slab.
22 Existing flooring to remain.
52 Remove existing toilet partition.
Remove portion of existing gypsum & metal stud wall for new one-way mirror03
31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.
I. coordinate scope and extent of demolition work with new work plans and details.
J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.
K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.
L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications
53 Remove existing millwork
54 Remove existing signage
Remove portion of existing block wall. provide temporary structural support03
30
40
30
3030
31
31
31
31
31
31
31
31
31
31
UP
Storage103.3
Office103.4
Office103.5
Recept103
Office103.1
Office103.2
Mech
Lobby
UP
Lounge100
Jan100.2
Mech100.1
UP
DN
DN
DN
EXTERIORCIRCULATION
SECONDFLOOR ABOVE
BASEMENTFLOOR BELOW
BASEMENTFLOOR BELOW
ELEV
NIC NIC
NIC
NIC
A-201
01A-101 Scale: 1/8" = 1'-0"
First Floor Plan - New WorkPrentis Building
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building 1st Floor Plan -New Work
GENERAL NOTES
1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.
2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.
3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.
4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.
5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER
NEW WORK NOTES:
FLOORS
INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE
DOORS AND WINDOWS
WALLS
NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11
31
32
NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.
01
CEILINGS
PREP AND PAINT GYPSUM CEILING41
CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL, AND VERTICALBLINDS AS NECESSARY
42
NEW FLOOR BASE, REFER TO FINISH SCHEDULE12
PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE
33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS
34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE
INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING
13
MISC.
72
LIGHTING
74
RELOCATED PROJECTION SCREEN
INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.
51
75
INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST
77
INSTALL NEW WHITE BOARD
INSTALL NEW FLAT SCREEN
78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW
71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS
79 INSTALL NEW SIGNAGE. COORDINATE WITH WSUFACILITIES MANAGER
70 INSTALL NEW MILLWORK, REFER TO INTERIORELEVATIONS
35 NEW 72" CABINET STYLE DOOR ON CONCEALED HINGES.
43 EXISTING CEILING TILE AND GRID TO REMAIN. REPLACE ANY DAMAGEDCEILING TILES OR GRID.
36 RE-CODE EXISTING DOOR SECURITY
1112
1112
1112
1112
1112
1112
32 32
32
32
32 32
79
7474
74
74
7474
74
DN
UP
DN
UP
UP
UP
soundbooth#2
soundbooth#1
soundbooth#1
soundbooth#2
EP
soundbooth#1
EP
soundbooth#1
future soundbooth
Teaching Lab027
Lab025
Lab023
ComputerLab021
Classroom017
Classroom019
PLC016.11
Tele016.10
Mech016
Mech016.2
Mech016.3
Mech016.4
Lab015
Lab013
Office013.2
Office013.1
Classroom010
Classroom008
Office006
Office006.2
Office006.3
Office006.4
Classroom004
Classroom002
Women031
Men029
Jan012
EngOffice014
Lab023.1
Storage020
Storage007
Lab005
Hearing AidFitting005.1
LabStorage005.2
SupervisorOffice005.3
Office005.4
C&IT030
NIC
NIC
NIC
NICNICNICNIC
NICNIC
NIC
NIC
NIC
NIC
NIC NIC
NIC
NIC
NIC
W1
W1
W1
D013.2
W1
W1
W1
W1
W1
W1
W1
W1
D013.2
STAIR001
STAIR030
STAIR040
D040
D005.3
D005.4
D005.1 D005.2
D001.4
D001.5
D001.6
D001.3
D001.2
D001.1
D030
D025
D023.1
W1 W1
W1 W1
W1
W1
10'-9"
12'-1
1/2
"6'-
1 1/
2"10
'-4"
9'-1"
10'-0
"v.i
.f.2'-
0"v.i
.f.
9'-0"
eq.
eq.
10'-8"v.i.f.
17'-5
"
5'-5" 5'-6"
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2W2
W2
W2
W2
A701 02
W2
W2
W2
W2
Mech016NIC
Mech016NIC
A-201-B
01A-101 Scale: 1/8" = 1'-0"
Basement Plan - New WorkPrentis Building
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building Basement FloorPlan - New Work
GENERAL NOTES
1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.
2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.
3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.
4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.
5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER
NEW WORK NOTES:
FLOORS
INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE
DOORS AND WINDOWS
WALLS
NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11
31
32
NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.
01
CEILINGS
PREP AND PAINT GYPSUM CEILING41
CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL, AND VERTICALBLINDS AS NECESSARY
42
NEW FLOOR BASE, REFER TO FINISH SCHEDULE12
PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE
33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS
34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE
INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING
13
MISC.
72
LIGHTING
74
RELOCATED PROJECTION SCREEN
INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.
51
75
INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST
77
INSTALL NEW WHITE BOARD
INSTALL NEW FLAT SCREEN
78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW
71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS
79 INSTALL NEW SIGNAGE. COORDINATE WITH WSUFACILITIES MANAGER
70 INSTALL NEW MILLWORK, REFER TO INTERIORELEVATIONS
35 NEW 72" CABINET STYLE DOOR ON CONCEALED HINGES.
43 EXISTING CEILING TILE AND GRID TO REMAIN. REPLACE ANY DAMAGEDCEILING TILES OR GRID.
36 RE-CODE EXISTING DOOR SECURITY
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
11 12
1112
1112
1112
1112
31
3131
31
31
3131
31313131
31 31 31
35
71
71
70
72
72
74
74
74
74
74
74
74
74
74
74 74
74
74
74
74
74
74
74
74
74
78
01
01
01
01
01
01
01
01
0101
0101
01
01
36 36 36
36
36
36
36
36
1112
74 74
74 74
Open to Below
OpenOffice105
WorkRoom105.3
Office105.4
Office105.5
Ref
Office105.2
Office105.1
DN DNUP
Elev
Open to Below
UP
DN
Jan102.1
Lounge102
DN
NIC NIC
NIC
NIC
NIC
A70101
A-201-M
01A-101 Scale: 1/8" = 1'-0"
Mezzanine Floor Plan - New WorkPrentis Building
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building Mezzanine Plan -New Work
GENERAL NOTES
1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.
2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.
3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.
4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.
5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER
NEW WORK NOTES:
FLOORS
INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE
DOORS AND WINDOWS
WALLS
NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11
31
32
NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.
01
CEILINGS
PREP AND PAINT GYPSUM CEILING41
CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL, AND VERTICALBLINDS AS NECESSARY
42
NEW FLOOR BASE, REFER TO FINISH SCHEDULE12
PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE
33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS
34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE
INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING
13
MISC.
72
LIGHTING
74
RELOCATED PROJECTION SCREEN
INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.
51
75
INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST
77
INSTALL NEW WHITE BOARD
INSTALL NEW FLAT SCREEN
78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW
71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS
79 INSTALL NEW SIGNAGE. COORDINATE WITH WSUFACILITIES MANAGER
70 INSTALL NEW MILLWORK, REFER TO INTERIORELEVATIONS
35 NEW 72" CABINET STYLE DOOR ON CONCEALED HINGES.
43 EXISTING CEILING TILE AND GRID TO REMAIN. REPLACE ANY DAMAGEDCEILING TILES OR GRID.
36 RE-CODE EXISTING DOOR SECURITY
1112
1112
1112
111211
1211
1270
71
MECHANICAL AREA
MECH SHAFT
DNDN
COOLING TOWER
NIC
300
305303
ELEV
NIC NIC NIC NIC
NIC NIC
NIC
NIC
NIC NIC NIC NIC NIC NIC NIC NICObservation300.1
Treatment300.09
Office300.08
Treatment300.05
Observation300.06
Office300.07
OpenOffice300.11
OpenOffice300
Office300.04
Office300.03
Office300.02
TEACHINGLAB304
Office303
WORKROOM300.01
UNISEX ADARESTROOM322.1
WOMEN'SRESTROOM326
Office328.01
Office328.02
Office328.03
Office328.04
Office328.05
COPY328.06
Office328.07
OpenOffice328
Office328.08
Office328.09
NIC
NIC
WorkRoom328.10
Observation325
Treatment327
W1D30
0
W2
W2
W1
W1W1
D33
0
STAIR330
STAIR340
D34
0
D32
7
D32
2.1
9"
W2
W2
W2
W2
W2
A701
05
03
04
A-203
01A-101 Scale: 1/8" = 1'-0"
Third Floor Plan - New WorkPrentis Building
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building 3rd Floor Plan - NewWork
GENERAL NOTES
1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.
2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.
3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.
4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.
5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER
NEW WORK NOTES:
FLOORS
INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE
DOORS AND WINDOWS
WALLS
NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11
31
32
NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.
01
CEILINGS
PREP AND PAINT GYPSUM CEILING41
CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL, AND VERTICALBLINDS AS NECESSARY
42
NEW FLOOR BASE, REFER TO FINISH SCHEDULE12
PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE
33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS
34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE
INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING
13
MISC.
72
LIGHTING
74
RELOCATED PROJECTION SCREEN
INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.
51
75
INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST
77
INSTALL NEW WHITE BOARD
INSTALL NEW FLAT SCREEN
78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW
71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS
79 INSTALL NEW SIGNAGE. COORDINATE WITH WSUFACILITIES MANAGER
70 INSTALL NEW MILLWORK, REFER TO INTERIORELEVATIONS
35 NEW 72" CABINET STYLE DOOR ON CONCEALED HINGES.
43 EXISTING CEILING TILE AND GRID TO REMAIN. REPLACE ANY DAMAGEDCEILING TILES OR GRID.
36 RE-CODE EXISTING DOOR SECURITY
1112
01 01
01
01
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
1112
111211
1211
12
1112
1112
1112
1112
1112
1112
1112
13
13
31
31
31
31 31
32323232323232323232
32
32
32
32
32 32 32 32 32 32 32
32 32 32 32 32
32
32
32
32
323232323232323232
32
34
34
34
7070
70
70
71
71
74
7474747474
74
74
7474
74
74
74
74
74
74
74
74
74
74
74
74
74
74
74
7474 74
74
74
74
74
74
74
74
74
747474
77
75
78
7878
DN
UP
DN
UP
UP
UP
soundbooth#2
soundbooth#1
soundbooth#1
soundbooth#2
EP
soundbooth#1
EP
soundbooth#1
future soundbooth
Teaching Lab027
Lab025
Lab023
ComputerLab021
Classroom017
Classroom019
PLC016.11
Tele016.10
Mech016
Mech016.2
Mech016.3
Mech016.4
Lab015
Lab013
Office013.2
Office013.1
Classroom010
Classroom008
Office006
Office006.2
Office006.3
Office006.4
Classroom004
Classroom002
Women031
Men029
Jan012
EngOffice014
Lab023.1
Storage020
Storage007
Lab005
Hearing AidFitting005.1
LabStorage005.2
SupervisorOffice005.3
Office005.4
C&IT030
NIC
NIC
NIC
NICNICNICNIC
NICNIC
NIC
NIC
NIC
NIC
NIC NIC
NIC
NIC
NIC
STAIR001
STAIR030
STAIR040
Mech016NIC
Mech016NIC
EXST EXST
EXST
EXSTEXST
EXST
xLFxLFxLFxLF
xLF
xLF xLF
xLF xLF xLF
xLFxLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF xLF
xLFxLF
xLF xLF
xLFxLF
xLF xLF
xLFxLF
LF
LF
LF
LFLF
LF
LF LF
LF LF
09
A701
LFLF
LF
A-301-B
01A-101 Scale: 1/8" = 1'-0"
Basement Plan - New WorkPrentis Building
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building Basement FloorRC Plan - New Work
GENERAL NOTES
1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.
2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.
3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.
4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.
5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER
NEW WORK NOTES:
FLOORS
INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE
DOORS AND WINDOWS
WALLS
NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11
31
32
NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.
01
CEILINGS
PREP AND PAINT GYPSUM CEILING41
CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL, AND VERTICALBLINDS AS NECESSARY
42
NEW FLOOR BASE, REFER TO FINISH SCHEDULE12
PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE
33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS
34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE
INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING
13
MISC.
72
LIGHTING
74
RELOCATED PROJECTION SCREEN
INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.
51
75
INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST
77
INSTALL NEW WHITE BOARD
INSTALL NEW FLAT SCREEN
78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW
71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS
79 INSTALL NEW SIGNAGE. COORDINATE WITH WSUFACILITIES MANAGER
70 INSTALL NEW MILLWORK, REFER TO INTERIORELEVATIONS
35 NEW 72" CABINET STYLE DOOR ON CONCEALED HINGES.
43 EXISTING CEILING TILE AND GRID TO REMAIN. REPLACE ANY DAMAGEDCEILING TILES OR GRID.
36 RE-CODE EXISTING DOOR SECURITY
4141
42
42
42
42
51
5151
51
51
51
51 51
51 51
43
43
43
43
43
43
43
43
43
43
43
43
43
43
43
MECHANICAL AREA
MECH SHAFT
DNDN
COOLING TOWER
NIC
300
305303
ELEV
NIC NIC NIC NIC
NIC NIC
NIC
NIC
NIC NIC NIC NIC NIC NIC NIC NICObservation300.1
Treatment300.09
Office300.08
Treatment300.05
Observation300.06
Office300.07
OpenOffice300.11
OpenOffice300
Office300.04
Office300.03
Office300.02
TEACHINGLAB304
Office303
WORKROOM300.01
UNISEX ADARESTROOM322.1
WOMEN'SRESTROOM326
Office328.01
Office328.02
Office328.03
Office328.04
Office328.05
COPY328.06
Office328.07
OpenOffice328
Office328.08
Office328.09
NIC
NIC
WorkRoom328.10
Observation325
Treatment327
STAIR330
STAIR340
EXST
EXST
EXST
EXST
EXST
EXST
EXST
EXSTEXST
EXST EXST
EXST
EXSTEXSTEXST
EXST
EXST
EXST
EXST EXST EXST EXST
EXST
EXST EXSTEXST
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF xLF
xLFxLF
xLF xLF
xLFxLF
LF
LF LF
LF LF
LF LF
LF LF
LF
xLF xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF xLF xLF
xLF
xLF
xLF xLF xLF
xLF xLF xLF
xLF xLF
xLF xLF
xLF
xLF xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF xLF
xLF
xLF xLF
xLF
xLF
xLF
xLF xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLF
xLFxLFxLF
xLFxLFxLF
xLF
A-303
01A-101 Scale: 1/8" = 1'-0"
Third Floor RC Plan - New WorkPrentis Building
FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building 3rd Floor reflectedCeiling Plan - New Work
GENERAL NOTES
1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.
2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.
3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.
4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.
5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER
NEW WORK NOTES:
FLOORS
INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE
DOORS AND WINDOWS
WALLS
NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11
31
32
NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.
01
CEILINGS
PREP AND PAINT GYPSUM CEILING41
CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL, AND VERTICALBLINDS AS NECESSARY
42
NEW FLOOR BASE, REFER TO FINISH SCHEDULE12
PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE
33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS
34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE
INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING
13
MISC.
72
LIGHTING
74
RELOCATED PROJECTION SCREEN
INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.
51
75
INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST
77
INSTALL NEW WHITE BOARD
INSTALL NEW FLAT SCREEN
78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW
71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS
79 INSTALL NEW SIGNAGE. COORDINATE WITH WSUFACILITIES MANAGER
70 INSTALL NEW MILLWORK, REFER TO INTERIORELEVATIONS
35 NEW 72" CABINET STYLE DOOR ON CONCEALED HINGES.
43 EXISTING CEILING TILE AND GRID TO REMAIN. REPLACE ANY DAMAGEDCEILING TILES OR GRID.
36 RE-CODE EXISTING DOOR SECURITY
43
43
434343
43
43
43
43
43 43
43
43 43
43
42
43
43
43
43
43 43
43
43
43
43
4343
51
51
51
51
51
51 51
51 51
51
Ceiling8'-0"
Fin Flr0'-0"
06
A701
6 eq8'-9 1/2"
3'-0"
2'-0"
3'-0"
6 eq
8'-9 1/2"3'-0"
2 eq
3'-0"2 eq
base cabinet w/ incounter sstl sink
upper cabinets w/adjustable shelves
2'-10
"
07
A701
3'-0"
relocated millwork fromRackham, coordinatemove with WSU projectmanager
new p-lam countertopand back splash
relocated upper cabinetsfrom Rackham, coordinatemove with WSU projectmanager
relocated millwork fromRackham, coordinatemove with WSU projectmanager
new p-lam countertopand back splash
relocated open shelvingfrom Rackham, coordinatemove with WSU projectmanager
3'-0"
3'-0"
new p-lam countertopand back splash
relocated millwork fromRackham, coordinatemove with WSU projectmanager
new p-lam countertopand back splash
relocated open shelvingfrom Rackham, coordinatemove with WSU projectmanager
relocated millwork fromRackham, coordinatemove with WSU projectmanager
3'-0"
2 eq
3'-0"2 eq
2'-10
"
07
A701
Ceiling8'-0"
Fin Flr0'-0"
base cabinet w/ in countersstl sink
upper cabinets w/adjustable shelves
p-lam end panel
wire pull
wire pull
2 1/2"
4"
2'-2"
3/4" veneer coreplywood cabinet base
cont. sealanttypical
1'-2 1/8"
2'-6"
16 gauge sheetmetal or provide firerated wood blocking
wood blocking
melamine finish on1/2" veneer coreplywood
16 gauge sheet metalor provide fire ratedwood blocking
adjustable p lam shelf
P-Lam on 3/4" veneer plywood doorpanel, provide HD concealed hinges(TYP), refer to elevations for locations
provide fire ratedwood blocking (TYP)
34" veneer core door panel,
(TYP), refer to elevations forlocations
4"
Fin Floor100'-0"
7'-6"
cabi
net d
oor
4" wall base (refer toroom finish schedule)
side wall backsplashbeyond
white melaminefinished interiorcabinet construction
P-lam drawer face, refer toelevation for locations &quantity in base cabinet,provide lockingmechanism
3/4" p-lam back splashat wet locations only
p-lam on 3/4" plywood,refer to finish schedule
1 1/
2"
2'-0"
3'-0"
wire pull
2 1/2"
4"
2'-10
"
2'-2"
3/4" veneer coreplywood cabinet base
cont. sealanttypical
wood blocking
melamine finish on1/2" veneer coreplywood
16 gauge sheet metalor provide fire ratedwood blocking
adjustable shelf
P-Lam on 3/4" veneerplywood door panel,provide HD concealedhinges (TYP), refer toelevations for locations
paint new gyp bd, refer toroom finish schedule (typ)
4"
Fin Floor100'-0"
cabi
net d
oor
p-lam on 3/4" plywood,refer to finish schedule
SS-1 bull-nosing w/ 3/4"radius
4" wall base (refer toroom finish schedule)
side wall backsplashbeyond
3/4" p-lam back splashat wet locations only
1 1/
2"
surface mounted sstl sink(Kohler Stacatto, K-3362-1-NA)
single hole faucet (KohlerForte' K-10415-CP,brushed chrome)
wire pull
1'-2 1/8"
2'-6"
16 gauge sheetmetal or provide firerated wood blocking
provide fire ratedwood blocking (TYP)
34" veneer core door panel,
(TYP), refer to elevations forlocationswhite melamine
finished interiorcabinet construction
2'-2"
Bottom of Beam9'-1"Ceiling Height
9'-0"new suspendedceiling system
exst CMU infill between W8sections.5/8" gyp board on metal stud at16" o.c. typ.
new W8 steel lintel, bear on exstCMU min 16" each end.
new gyp bdbulkhead
±10"
08
A701
location of new W8'sabove, Provide 61/2"x16"x3/8" metal plateat each end.
10'-8"
#4 vert. rebar in centerof CMU cells, grout cellssolid. rebar to extend 12"min. into existing/newfoundation
location of new W8'sabove, Provide 61/2"x16"x3/8" metal plateat each end.
6'-8"
A-701 FOR
BID
S
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
designed
issue: date:
key plan:
Prentis Building - RackhamRelocation
Nov. 13, 2018Owner Review 60% CD's
NM Project Number - 18113.0
WAYNE STATEUNIVERSITY
Facilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
Prentis Building
JK
JK
JK
DB
AG
WSU : 00
consultants:
Nov. 27, 2018Owner Review 90% CD's
Dec. 04, 2018Review 100% CD's
Dec. 11, 2018For Bids
Prentis Building Interior Elevations,Sections and Details
01A701 Scale: 3/8" = 1'-0"
Work Room 105.3 Millwork Detail
02A701 Scale: 3/8" = 1'-0"
005.1 Millwork DetailHearing Aid Fitting Room
03A701 Scale: 3/8" = 1'-0"
Work Room 300.01 Millwork Detail
04A701 Scale: 3/8" = 1'-0"
Work Room 300.01 Millwork Detail
05A701 Scale: 3/8" = 1'-0"
Work Room 300.01 Millwork Detail
06A701 Scale: 1" = 1'-0"
Millwork Section
07A701 Scale: 1" = 1'-0"
Millwork Section
08A701 Scale: 3/4" = 1'-0"
Lab 005 Header Detail
09A701 Scale: 3/4" = 1'-0"
Lab 005 Header Section
DIRECTION OF AIR FLOW
FLEXIBLE DUCT
MANUAL VOLUME DAMPER
RISE IN DIRECTION OF AIR FLOWR
DUCT CAP
DROP IN DIRECTION OF AIR FLOWD
DUCT DOWN
DUCT UP
SUPPLY/OUTSIDE AIR DUCT SECTION
RETURN AIR DUCT SECTION
EXHAUST/RELIEF AIR DUCT SECTION
4-WAY DIFFUSER WITH BLANKOFF IN ONE DIRECTION
CD-16/115
AIR TERMINAL PROPERTIES SYMBOLNECK SIZE/CFM
TERMINAL AIR BOX (REFER TO SCHEDULE)###
### TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)
OPPOSED BLADE DAMPER (REFER TO SCHEDULE)
PARALLEL BLADE DAMPER (REFER TO SCHEDULE)
DIFFERENTIAL PRESSURE SENSOR
CARBON MONOXIDE SENSORC
CARBON DIOXIDE SENSORC2
HUMIDISTAT SENSORH
HUMIDISTAT/SENSOR (DUCT MOUNTED)H
OCCUPANCY SENSORO
PRESSURE SENSOR/MONITORP
PRESSURE SENSOR (DUCT MOUNTED)P
THERMOSTAT/SENSORT
TEMPERATURE SENSOR (DUCT MOUNTED)T
THERMOSTAT/SENSOR WITH HEAVY DUTY ENCLOSURET
VENTILATION SYMBOL LIST
SYMBOL: DESCRIPTION:
AIRFLOW MEASUREMENT SYMBOLXX - AHU SYMBOLY - SEQUENTIAL NUMBER
XX-Y
NOT ALL SYMBOLS MAY APPLY.
SERIES FAN POWERED TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)
PARALLEL FAN POWERED TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)
VENTILATION ABBREVIATION KEY
ABBR: DESCRIPTION:
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
NC NEW CONNECTION
CFSD CONTROL/FIRE/SMOKE DAMPER
EA EXHAUST/RELIEF AIR
FD FIRE DAMPER
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
FSD FIRE/SMOKE DAMPER
MA MIXED AIR
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
SD SMOKE DAMPER
TRANSFER DUCTTD
EFD EXISTING FIRE DAMPER
TERMINAL AIR BOXTAB
TYPICALTYP
UNO UNLESS NOTED OTHERWISE
CEILING DIFFUSER - EXISTINGCD-E
N.C. NORMALLY CLOSED
NOT IN CONTRACTNIC
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
NAME
1VIEW NAME1/8" = 1'-0"
LEVEL NAME
10' - 0" HEIGHT ABOVE PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL
NO R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
LINE TYPE KEY:
MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE.PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR
STARTERS, SWITCHES, AND DISCONNECTS.16. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE GENERAL CONTRACTOR CONSTRUCTION MANAGER. ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.
1. THE SIZE OF EACH BRANCH DUCT TO A TERMINAL AIR BOX (TAB) SHALL MATCH THE TAB’S INLET SIZE UNLESS THE BRANCH IS GREATER THAN 6 FEET IN LENGTH, IN WHICH CASE THE BRANCH SHOULD BE INCREASED ONE DUCT SIZE, OR NOTED OTHERWISE.
2. ALIGN TEMPERATURE SENSORS WITH LIGHT SWITCHES AND WHEN IN CLOSE PROXIMITY TO EACH OTHER.
3. PROVIDE ACCESS DOORS AT ALL DUCT MOUNTED EQUIPMENT.4. EXISTING AIR INLET AND OUTLET CFM SHOWN ON DRAWINGS ARE FROM EXISTING
DRAWINGS, AND ARE FOR REFERENCE ONLY. CONTRACTOR SHALL USE PRE-BALANCE VALUES, AND NOT EXISTING CFM SHOWN ON DRAWINGS.
5. CONTRACTOR MAY REUSE PORTIONS OF EXISTING DUCT PROVIDED SIZES AND PRESSURE CLASSES ARE CORRECT, DUCT IS THOROUGHLY CLEANED AND FREE OF DEFECTS, AND ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS ARE SEALED AS SPECIFIED FOR NEW DUCTWORK.
6. CLEAN ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK UPSTREAM OF ALL NEW CONNECTIONS PER SPECIFICATION SECTION 23 31 00.
VENTILATION GENERAL NOTES:
1. BEFORE ANY DEMOLITION WORK IS BEGUN A COMPLETE AIR BALANCE TEST SHALL BE PERFORMED BY THE TESTING, ADJUSTING AND BALANCING (TAB) CONTRACTOR ON EXISTING AIR HANDLERS AND EXHAUST FANS SERVING THE AREAS AFFECTED BY CONSTRUCTION. EQUIPMENT TO BE DEMOLISHED DOES NOT REQUIRE TESTING. PROVIDE AIR BALANCE TESTING ONLY ON EQUIPMENT THAT WILL CONTINUE TO BE USED TO SERVE RENOVATED AREAS AFTER THE CONSTRUCTION PHASE IS COMPLETED.
2. PROVIDE DUCT TRAVERSE READINGS AT LOCATIONS DESIGNATED ON THE DRAWINGS BY THE "AIRFLOW MEASUREMENT SYMBOL". THOSE MEASUREMENTS SHALL BE INCLUDED IN THE PRE DEMOLITION REPORT AND SHALL BE DESIGNATED WITH THE IDENTIFIER AS MARKED ON THE DRAWINGS. READINGS SHALL BE DESIGNATED WITH THE ROOM NAME AND NUMBER AS MARKED ON THE DRAWINGS. IF FLOOR PLANS DO NOT HAVE UNIQUE ROOM NAMES AND NUMBERS, TAB CONTRACTOR SHALL INCLUDE FLOOR PLAN WITH UNIQUE NUMBER DESIGNATIONS ASSIGNED TO READINGS THAT MATCH THOSE USED IN THE FINAL PRE-DEMOLITION REPORT. DRAWINGS THAT ARE HAND-MARKED WITH RED INK ARE ACCEPTABLE, PROVIDED THEY ARE LEGIBLE.
3. IN THE EVENT A DUCT TRAVERSE LOCATION AS MARKED ON THIS PLAN IS INACCESSIBLE FOR MEASUREMENT, THE TAB CONTRACTOR SHALL PERFORM THE TRAVERSE AT AN ALTERNATE LOCATION OR SHALL TAKE MULTIPLE DUCT TRAVERSES AND/OR READINGS AS REQUIRED TO DETERMINE THE AIRFLOW READING WHERE THE DUCT TRAVERSE SYMBOL IS SHOWN. IN THE EVENT TRAVERSES ARE TAKEN AT ALTERNATE LOCATION(S), TAB CONTRACTOR SHALL INCLUDE A DRAWING THAT SHOWS THE LOCATIONS WHERE THE ACTUAL MEASUREMENTS WERE TAKEN.
4. TAKE A DUCT STATIC PRESSURE READING AT EACH LOCATION WHERE A DUCT TRAVERSE READING IS TAKEN AND INCLUDE IN THE FINAL PRE-DEMOLITION TAB REPORT.
5. TAB CONTRACTOR SHALL COMPILE AND SUBMIT FOUR COPIES OF THE FINAL PRE-DEMOLITION REPORT WITHIN 10 WORKING DAYS AFTER THE FIELD MEASUREMENTS ARE COMPLETED. FINAL TAB REPORT SHALL BE SUBMITTED FOR REVIEW TO THE ARCHITECT/ENGINEER. TESTING SHALL INCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.
6. TAB CONTRACTOR SHALL PROVIDE DUCT TRAVERSE READINGS AT LOCATIONS DESIGNATED ON THE DRAWINGS BY THE "AIRFLOW MEASUREMENT SYMBOL". THOSE MEASUREMENTS SHALL BE INCLUDED IN THE POST-CONSTRUCTION REPORT AND SHALL BE DESIGNATED WITH THE IDENTIFIER AS MARKED ON THE CONSTRUCTION DRAWINGS. GRILLE AND DIFFUSER READINGS SHALL BE DESIGNATED WITH THE ROOM NAME AND NUMBER AS MARKED ON THE DRAWINGS. IF THE DRAWINGS DO NOT HAVE UNIQUE ROOM NAMES AND NUMBERS, TAB CONTRACTOR SHALL INCLUDE FLOOR PLANS WITH UNIQUE NUMBER DESIGNATIONS ASSIGNED TO TRAVERSES, GRILLES, AND DIFFUSERS THAT MATCH THOSE USED IN THE FINAL PRE-DEMOLITION REPORT. SIMILAR ROOM NAMES, NUMBERS, OR DESIGNATIONS SHALL BE USED TO SIMPLIFY THE CROSS- REFERENCING OF READINGS TAKEN BETWEEN PRE-DEMOLITION AND POST-CONSTRUCTION REPORTS.
7. BALANCING CONTRACTOR SHALL PRE-BALANCE ALL EXISTING SYSTEMS TO REMAIN PER SPECIFICATION SECTION 23 05 93. BALANCE READINGS WILL BE REQUIRED AT AIR OUTLETS AND DUCT TRAVERSES TO VERIFY EXISTING AIRFLOW TO UNAFFECTED SPACES.
TAB PRE-DEMOLITION NOTES:
1. AFTER CONSTRUCTION ACTIVITIES ARE COMPLETE, TESTING, ADJUSTING (TAB) AND BALANCING CONTRACTOR SHALL REBALANCE AIR HANDLING UNITS AND EXHAUST FANS AS REQUIRED TO ACHIEVE THE NEW AIRFLOW VALUES SHOWN ON THE CONSTRUCTION DRAWINGS.
2. AREAS SERVED BY THIS EQUIPMENT WHICH WERE NOT RENOVATED SHALL BE RE-BALANCED TO THE AIRFLOW RATES MEASURED BEFORE THE RENOVATION OCCURRED (REFER TO THE FINAL PRE- DEMOLITION REPORT).
3. IF DUCT TRAVERSE LOCATION AS MARKED ON THE DRAWINGS IS INACCESSIBLE FOR MEASUREMENT, THE TAB CONTRACTOR SHALL PERFORM THE TRAVERSE AT AN ALTERNATE LOCATION OR SHALL TAKE MULTIPLE DUCT TRAVERSES AND/OR GRILLE READINGS AS REQUIRED TO DETERMINE THE FLOW RATE. IN THE EVENT TRAVERSES ARE TAKEN AT AN ALTERNATE LOCATION(S), TAB CONTRACTOR SHALL INCLUDE A DRAWING THAT SHOWS THE LOCATIONS WHERE THE ACTUAL MEASUREMENTS WERE TAKEN.
4. A DUCT STATIC PRESSURE READING SHALL BE TAKEN AT EACH LOCATION WHERE A DUCT TRAVERSE READING IS TAKEN AND SHALL BE INCLUDED IN THE FINAL POST-CONSTRUCTION TAB REPORT.
5. TAB CONTRACTOR SHALL COMPILE AND SUBMIT COPIES OF THE FINAL POST-CONSTRUCTION TAB REPORT AS REQUIRED BY SECTION 23 05 93.
6. THE FINAL POST CONSTRUCTION REPORT SHALL INCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.
TAB POST-CONSTRUCTION NOTES:
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
CONSTRUCTION MANAGERC.M.
PLUMBING CONTRACTORP.C.
ELECTRICAL CONTRACTORE.C.
VENTILATION CONTRACTORV.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
FIRE PROTECTION CONTRACTORF.P.C.
HEATING CONTRACTORH.C.
MECHANICAL CONTRACTORM.C.
AUDIO/VISUAL CONTRACTORA.V.C.
ASBESTOS ABATEMENT CONTRACTORA.C.
BUILDING CODE: MBC 2015 EDITION
FIRE CODE: NFPA 13: 2013 EDITION
PLUMBING CODE: MBC 2015 EDITION
MECHANICAL CODE: MMC 2015 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2016EDITION
LIFE SAFETY CODE: NFPA 101 2015 EDITION
ENERGY CONSERVATION CODE: ASHRAE 90.1 2013
HEALTH DEPARTMENT CODE: CURRENT EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
VENTILATION SHEET INDEXMH-000 VENTILATION COVERSHEET
MHD-101-B BASEMENT FLOOR DEMOLITION - VENTILATION
MHD-103 THIRD FLOOR DEMOLITION - VENTILATION
MH-101-B BASEMENT FLOOR - VENTILATION
MH-103 THIRD FLOOR PLAN - VENTILATION
MH-300 VENTILATION SCHEDULES & DETAILS
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
1:1
7 A
M
MH-000
VENTILATION COVERSHEET
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
001
013
015
040
030
030
007
020
014
012
029
031
002004
006.4
006.3
006.2
006008010
016.31
016.4
016.3
016.2
016
016.10
016.11
019017021
023
025
027
STAIR
Lab
Lab
STAIR
STAIR
C&IT
Storage
Storage
EngOffice
Jan
Men
Women
ClassroomClassroom
Office
Office
Office
OfficeClassroomClassroom
Mech
Mech
Mech
Mech
Mech
Tele
PLC
ClassroomClassroom ComputerLab
Lab
Lab
Teaching Lab
T
T
T
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
TB-E
TB-E
TB-E
TB-E
TB-E
TB-E TB-E TB-E
TB-E
TB-ETB-ETB-E TB-E
TB-E
TB-E
TB-E
TB-E
42x28 SA 37x28 SA 23x30 SA
22ø
SA
19x1
0 S
A
12x10 SA
22x10 SA
10x14 RA
10x14 SA
10x8 SA
10x8 SA
10x8 SA UP
10x8 SA UP
SR-E
24x12/320(TYP.2)
RR-E
36x10/0(TYP.2)
ST-1
ST-1
18x10 SA9ø SA10ø SA
11x10 SA
20x10 SA13x10 SA 13x10 SA
28x10 SA16x10 SA
16x10 SA
36x5
36x5
36x5
36x5
24x524x5
12x10 SA
19x10 SA
12x12 RA UP
11x10 SA
SR-E
14x8/400(TYP.2)
13x10 SA
13x10
12ø SA
10ø SA28x10 SA
16x10 SA
16x10 SA15ø SA
12ø SA
SR-E
14x8/400(TYP.2)
30x6
SR-E
14x8/0(TYP.2)
30x630x630x630x6
12x10 SA
12x10 SA
24x10 SA14x10 SA
14x10 SA
10ø SA
13ø SA 10ø SA
11ø SA
20ø SA 18ø SA
18ø
SA
20x8
SA
16x8 SA
18x6
8x8 SA12x8 SA
26x6
4x4 EA UP
4x6 EA
8x4 EA
EG-E
8x6/90
EG-E
18x3/170
6x11 EA6x14 EA
30x630x6
30x630x6
30x623x28 SA UP
88x28 RA UP
20ø SA17ø SA
TB-E
RHC-E
SR-E
32x12/910
RR-E
24x12/600
RR-E
24x12/600
SR-E
32x12/910
TB-E
RHC-E
11ø SA
22x1
0 S
A
RR-E
24x12/600
SR-E
36x10/910
RR-E
30x12/910
22x1
0 S
A
22x1
0 S
A
11ø SA
11ø SA
SR-E
24x12/320
RR-E
24x12/600 RR-E
36x10/0SR-E
36x8/910
RHC-E
TB-E
11ø SA
14ø SA
24"x8" LINED
WITH 1"ACOUSE
INSULATION
24"x8" LINED
WITH 1"ACOUSE
INSULATION
11x10 SA11x10 SA
10ø SA
12ø SA
CRAC
1
3
CRAC
2
2
2
3
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
1:2
4 A
M
MHD-101-B
BASEMENT FLOOR DEMOLITION
- VENTILATION
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR DEMOLITION - VENTILATION
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
SHEET VENTILATION NOTES :
1. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
2. CAP ALL OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.
KEYNOTES:
1. REMOVE EXISTING COMPUTER ROOM AIR CONDITIONING (CRAC) UNIT, AND ITS ASSOCIATED DUCT, DIFFUSERS, PIPING, CONTROLS, SENSORS & WIRING IN ITS ENTIRETY. REMOVE PIPING BACK TO THE MAIN AND CAP AT MAIN. SALVAGE UNIT AND RETURN TO OWNER. CONFIRM WITH THE OWNER REGARDING THE SCOPE OF DEMO & SALVAGE.
2. PRIOR TO DEMOLITION, MEASURE SUPPLY/ RETURN/ EXHAUST AIR FLOWS AT ALL EXISTING TERMINAL AIR DEVICES AND AIR INLETS/ OUTLETS. LABEL ALL DEVICES AND AND CREATE AN AIR BALANCE REPORT DESCRIBED ON SHEET MH-000.
3. REMOVE EXISTING RETURN AIR GILLE. CLEAN & PREPARE TO EXTEND THE DUCT TO MOUNT GRILLE ON THE NEW SHAFT WALL. COORDINATE W/ ARCH.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
T
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
28”x8” LINED
DUCT CONN. TO
CL’G SPACE OVER
RM.*355 (DET
“B” SIMILAR)
13ø SA
10ø SA
10ø SA
10x7 EA
6x4 EA
10x7 EA
18x9 SA
13x9 SA 10x9 SA 10x6 SA
SD-E
SD-ESD-E
26x9 SA
TB-ERHC-E
11ø SA
11ø SA
11"⌀ DN
10ø SA
10ø SA
11ø SA
EG-E
15x3/165(typ-2)
EG-E
10x3/110(typ-2)
SD-E
SD-E
SD-E
18x9 SA21x9 SA
26x9
SA
10x8 SA
14x8 SA
10x8 SA
10x6 SA10x6 SA
10x9 SA
2 3
1
44
4
4
4
4
4
4 4 4 4 4
4 4 4 44 4 4
44
4 4 4 4 4 4
4
4
4
4
4
444
44
5
55
5
5
5
55
5
5 5 5 5 5 5
5
5
5
5
5
55
66
EG-E
24x10/300
EG-E
14x8/300
EG-E
6x4/50
5
5
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
1:2
5 A
M
MHD-103
THIRD FLOOR DEMOLITION -
VENTILATION
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
NO R HT
1/8" = 1'-0"2 THIRD FLOOR DEMOLITION - VENTILATION
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
SHEET GENERAL NOTES :
1. COORDINATE ALL DEMOLITION WORK WITH ARCHITECTURAL AND ELECTRICAL AND ELECTRICAL DEMOLITION WITH OWNER'S PROJECT REPRESENTATIVE.
2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
3. REMOVE ALL INDICATED DUCTWORK AND EQUIPMENT COMPLETELY INCLUDING ALL RELATED ITEMS INCLUDING HANGERS, SUPPORTS, CONTROLS AND ACCESSORIES.
4. CAP ALL THE OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.
KEYNOTES:
1. DEMOLISH EXISTING DUCTWORK, CEILING SUPPLY & RETURN DIFFUSERS AND ASSOCIATED ACCESSORIES BACK TO THE POINT AS SHOWN.
2. REMOVE EXISTING VAV BOX TEMPERATURE SENSOR, DISCONNECT CONTROL AND PREPARE TO MOUNT THE SENSOR AT NEW LOCATION.
3. REMOVE EXISTING SUPPLY DIFFUSER, CLEAN AND PREPARE TO INSTALL AT NEW LOCATION.
4. REMOVE EXISTING SUPPLY AIR FLOOR REGISTER. CLEAN AND PREPARE FOR INSTALLATION OF NEW FLOOR REGISTERS. CONFIRM W/ THE OWNER & ARCH FOR THE EXISTING REGISTERS TO BE CLEANED & REUSED IN LIEU OF NEW REGISTERS.
5. DISCONNECT AND REMOVE EXISTING RETURN AIR GRILLE. CLEAN AND PREPARE FOR REINSTALLATION.
6. PRIOR TO DEMOLITION, MEASURE SUPPLY/ RETURN/ EXHAUST AIR FLOWS AT ALL EXISTING TERMINAL AIR DEVICES AND AIR INLETS/ OUTLETS. LABEL ALL DEVICES AND AND CREATE AN AIR BALANCE REPORT DESCRIBED ON SHEET MH-000.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
013.1
013.2 005.4
005.3
005.2
005.1005
023.1
sound
booth
#2
sound
booth
#1
sound
booth
#1
sound
booth
#2
sound
booth
#1
sound
booth
#1
future sound
booth
Office
Office Office
SupervisorOffice
LabStorage
Hearing AidFitting
Lab
Lab
001
013
015
040
030
030
007
020
014
012
029
031
002004
006.4
006.3
006.2
006008010
016.31
016.4
016.3
016.2
016
016.10
016.11
019017021
023
025
027
STAIR
Lab
Lab
STAIR
STAIR
C&IT
Storage
Storage
EngOffice
Jan
Men
Women
ClassroomClassroom
Office
Office
Office
OfficeClassroomClassroom
Mech
Mech
Mech
Mech
Mech
Tele
PLC
ClassroomClassroom ComputerLab
Lab
Lab
Teaching Lab
T
T
T
T
T
T
T
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
TB-E
TB-E
TB-E
TB-E
TB-E
TB-E TB-E TB-E
TB-E
TB-ETB-ETB-E TB-E
TB-E
TB-E
TB-E
TB-E
42x28 SA 37x28 SA 23x30 SA
22ø
SA
19x1
0 S
A
12x10 SA
22x10 SA
10x14 RA
10x14 SA
10x8 SA
10x8 SA
10x8 SA UP
10x8 SA UP
SR-E
24x12/320(TYP.2)
RR-E
36x10/0(TYP.2)
ST-1
ST-1
18x10 SA9ø SA10ø SA
11x10 SA
20x10 SA13x10 SA
13x10 SA
28x10 SA
16x10 SA
16x10 SA
36x5
36x5
36x5
36x5
24x524x5
12x10 SA
19x10 SA
12x12 RA UP
11x10 SA
SR-E
14x8/400(TYP.2)
13x10 SA
12ø SA
10ø SA 28x10 SA
16x10 SA
16x10 SA
15ø SA
12ø SA
SR-E
14x8/400(TYP.2)
30x6
SR-E
14x8/0(TYP.2)
30x630x630x630x6
12x10 SA
12x10 SA
24x10 SA14x10 SA
14x10 SA
10ø SA
13ø SA 10ø SA
11ø SA
20ø SA 18ø SA
18ø
SA
20x8
SA
16x8 SA
18x6
8x8 SA12x8 SA
26x6
4x4 EA UP
4x6 EA
8x4 EA
EG-E
8x6/90
EG-E
18x3/170
6x11 EA6x14 EA
30x6
30x630x630x6
23x28 SA UP
88x28 RA UP
SR-E
14x8/200
CD-1
8/130
NEW VAV - B-1
8x8
NC
NCCD-1
8/130NEW VAV - B-2 8x8
NC
CD-1
8/100
10x10
NEW VAV-B-6
NC
CD-1
8/150
NEWVAV - B-5
8x86ø
6ø
CD-1
8/150
CD-1
8/100
NEWVAV - B-4 8x8
6ø
6ø
NC
CD-1
8/100
NEWVAV - B-3
1
1
1
1
5
2
2
2
2
2
1
NC
NC
SR-E
14x8/400
NC
3
8ø
SA
8ø
SA4
NEW VAV-B-7
1 8x8 SA
4
8ø SA
NC
4
8ø
SA
10ø
SA
8ø
SA 8
ø S
A
NEWVAV - B-8
4
4
8ø
SA
8ø
SA
28x10/19x10
100 CFM150 CFM
4
150 CFM
100 CFM
100 CFM
150 CFM
5
6 6
6
NC
1
77
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
1:1
9 A
M
MH-101-B
BASEMENT FLOOR -
VENTILATION
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
SHEET GENERAL NOTES :
1. COORDINATE FINAL DUCT AND PIPING ROUTES WITH EXISTING DUCT, PIPING ON SITE.
2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
3. CAP ALL OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.
KEYNOTES:
1. INSTALL AIR TERMINAL BOXES AND THEIR ASSOCIATED TEMPERATURE SENSORS, CONTROLS AND SUPPLY/ RETURN/ EXHAUST INLETS/OUTLETS AS SHOWN. INSTALLATION SHALL PER DETAILS ON MH-300. AIR TERMINAL BOX INSTALLATION SHALL PER MANUFACTURER INSTRUCTION AND PROVIDE SUFFICIENT CLEARANCE & SERVICE SPACES. UNIT CONTROLLER SHALL BE COMPATIABLE W/ EXISTING BUILDING CONTROL SYSTEM AND SHALL BE CONFIRMED BY THE OWNER.
2. RR-1 WITH SOUND TRAP. DUCT SIZE 24X12.3. CAP DUCTWORK IF THE DEMOED CRAC UNIT IS CONNECTED TO MAIN AIR SUPPLY DUCT.4. CONTRACTOR IS TO VERIFY AND REPORT TO ENGINEER/ ARCH IF THE EXISTING RELOCATED SOUND BOOTH
HAS ITS OWN VENTILATION FANS INSTALLED ON THE BOOTH TO PROVIDE A CIRCULATION AIR OR BOOTH REQUIRES FACILITY TO PROVIDE VENTILATION AIR. IF THE RELOCATED BOOTH REQUIRES FACILITY AIR, BALANCE THE SUPPLY AIR TO THE BOOTH TO CFM SHOWN.
5. REINSTALL EXISTING WALL SUPPLY GRILLE & DUCT FITTINGS AT NEW LOCATION SHOWN TO ACCOMODATE NEW WALL.
6. REBALANCE TO EXISTING AIR FLOW INDICATED ON PREDEMOLITION AIR BALANCE REPORT WHERE NO NEW AIR FLOW INFORMATION IS INDICATED ON THE DRAWING.
7. CLEAN & REINSTALL EXISTING AIR GRILLE. EXTEND EXISTING DUCT TO ACCOMODATE NEW SHAFT. COORDINATE W/ ARCH.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
327
325
328.10
328.09
328.08
328
328.07
328.06
328.05
328.04
328.03
328.02
328.01
326
322.1
300.01
303
304 300.02 300.03
300.04
300
300.11 300.07
300.06
300.05
300.08
300.09300.1
Treatment
Observation
WorkRoom
Office
Office
OpenOffice
Office
COPY
Office
Office
Office
Office
Office
WOMEN'SRESTROOM
UNISEX ADARESTROOM
WORKROOM
Office
TEACHINGLAB Office Office
Office
OpenOffice
OpenOffice Office
Observation
Treatment
Office
TreatmentObservation
T
T
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
28”x8” LINED
DUCT CONN. TO
CL’G SPACE OVER
RM.*355 (DET
“B” SIMILAR)
13ø SA
10ø SA
10ø SA
10x7 EA
6x4 EA
10x7 EA
18x9 SA
13x9 SA 10x9 SA 10x6 SA
SD-E
SD-ESD-E
26x9 SA
TB-E RHC-E
11ø SA
11ø SA
11"⌀ DN
10ø SA
10ø SA
11ø SA
EG-E
15x3/165(typ-2)
EG-E
10x3/110(typ-2)
10x6 SA
10x9 SA
18x9 SA21x9 SA
26x9
SA
18x8 SA 10x8 SASD-E
SD-E
SD-E
SD-E
CD-1
8/160
CD-1
8/160
10x88ø
NEW VAV-3-1
1
2
NC -TYPICAL OF 4
2
NC
2
NC
2
NC
2
NC -TYPICAL OF 4
2
NC -TYPICAL OF 2
2 NC
2
NC -TYPICAL OF 4
2
NC
2
NC2
NC
2
NC - TYPICAL OF 4
2
NC -TYPICAL OF 2
2
NC -TYPICAL OF 2
2
NC -TYPICAL OF 4
2
NC
2
NC
2
NC
2
NC2
NC
2
NC
2
NC -TYPICAL OF 4
44
NC
8ø
SA
(N) CAP
(N) RG-1 12X24 W/ SOUND BOOT
5
6
3
33
3
3
3
33
3
3 3 3
3
3
3
3
3
3
3
3
33
3
3
3
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
1:2
1 A
M
MH-103
THIRD FLOOR PLAN -
VENTILATION
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
NO R
HT
1/8" = 1'-0"1 THIRD FLOOR PLAN - VENTILATION
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
SHEET GENERAL NOTES :
1. COORDINATE FINAL DUCT AND PIPING ROUTES WITH EXISTING DUCT, PIPING ON SITE.
2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
3. CAP ALL OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.
4. PROVIDE ACCESS DOOR IN HARD CEILINGS WHERE NECESSARY TO PROVIDE ACCESS TO TERMINAL AIR BOXES AND OTHER EQUIPMENT LOCATED ABOVE CEILING.
5. PROVIDE ACCESS PANELS WHERE REQUIRED TO ALLOW ACCESS TO BALANCING DAMPER.
KEYNOTES:
1. INSTALL AIR TERMINAL BOXES AND THEIR ASSOCIATED TEMPERATURE SENSORS, CONTROLS AND SUPPLY/RETURN/EXHAUST INLETS/OUTLETS AS SHOWN. INSTALL PER DETAILS ON MH-300. AIR TERMINAL BOX INSTALLATION SHALL BE PER MANUFACTURER AND PROVIDE SUFFICIENT CLEARANCE & SERVICE SPACES. UNIT CONTROLLER SHALL BE COMPATIABLE W/ EXISTING BUILDING CONTROL SYSTEM AND SHALL BE CONFIRMED BY THE OWNER.
2. PROVIDE AND INSTALL NEW SUPPLY AIR REGISTER AT EXISTING LOCATION. REGISTER SHALL MATCH EXISTING SIZE, LOCATION, AND FINISH. CONFIRM W/ THE OWNER & ARCH FOR THE EXISTING REGISTERS TO BE CLEANED & REUSED IN LIEU OF NEW REGISTERS.
3. CLEAN & REINSTALL EXISTING RETURN AIR GRILLE TO EXISTING LOCATION. 4. REBALANCE TO EXISTING AIR FLOW INDICATED ON PREDEMOLITION AIR BALANCE
REPORT WHERE NO NEW AIR FLOW INFORMATION IS INDICATED ON THE DRAWING.5. REINSTALL EXISTING VAV BOX TEMPERATURE SENSOR, RECONNECT CONTROL BACK
TO EXISTING VAV AND CHECK THE VAV CONTROLS.6. CLEAN & REINSTALL EXISTING SUPPLY DIFFUSER AT THE NEW LOCATION. CAP THE
EXISTING DUCT AT THE DEMO POINT.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
NOTES:
1. THIS DETAIL APPLIES ONLY TO TAPS OFF WRAPPED DUCTS.2. THIS DETAIL APPLIES TO TERMINAL AIR BOXES WITH ROUND INLETS AND
RECTANGULAR OUTLETS.3. DUCT LEADING TO TAB INLET MUST BE STRAIGHT FOR 1.5 DIAMETER
UPSTREAM.4. MAINTAIN VAPOR BARRIER FROM MAIN TO BRANCH DUCT.
NYLON TIE WRAP, TWO REQUIREDFOR EACH END OF FLEXIBLE DUCT(TOTAL 4). INSTALL ONE TIE WRAPTO SECURE THE INNER LINER ANDONE TO SECURE THE OUTER SHELL.(TYP.)
PRE-MANUFACTURED CONICALTAKE-OFF WITH SELF-ADHESIVE NEOPRENE GASKET (EQUAL TO SHEET METAL CONNECTORS CONICAL E-Z TAP)
FASTEN WITH SELF-TAPPINGSHEETMETAL SCREWS (MIN. 4)
CUT DUCT OPENING TO MATCHLARGER TAKEOFF DIAMETER
INSULATED GALVANIZED DUCT
CUT HELIX AND INNER FABRIC HERE. SECURE WITH NYLON TIE. OVERLAP FLEX DUCT MINIMUM OF 2" ONTO RIGID DUCT. PROVIDE DUCT SEALER AT CONNECTION BETWEEN FLEX DUCT AND RIGID DUCT.
AIR FLOWTERMINAL AIR BOX
RECTANGULAR INSULATED DUCT
INSULATEDFLEX DUCT
INSULATED TRANSITION
REHEAT COIL (IF SCHEDULED),INSULATE PER SPECIFICATIONS.
3' MAX.
6" MIN.
. D
MAINTAIN MINIMUM WORKING CLEARANCE TO ELECTRICAL CONNECTIONS AS REQUIRED BY NFPA 70 (NATIONAL ELECTRIC CODE)
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
1:2
2 A
M
MH-300
VENTILATION SCHEDULES &
DETAILS
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
NOTES:1. SIZES INIDCATED ARE TYPICAL. REFER TO PLANS FOR ADDITIONAL REQUIRED SIZES AND CFM.
24 X 24 201-2000 22x22 24X24 30
RG-1 RETURN AIR GRILLE
12 X 12 0-200 10X10 12x12 30
CEILING MOUNTED SEE FLOOR PLAN ALUMINUM CONSTRUCTION
SG-1 SUPPLY AIR REGISTERSAME AS DUCT CONNECTION PLUS
FRAME1-450 12 X 8 30 DOUBLE DEFLECTION BLADES WALL MOUNTED
ALUMINUM CONSTRUCTION NECK MOUNTEDOPPOSED BLADE DAMPER
201-345 8" 8" 30
CD-1 SUPPLY AIR CEILING DIFFUSER 24 X 241-200 6" 6" 30
SQUARE LAY -IN CEILING MOUNTINGALUMINUM CONSTRUCTION NECK MOUNTEDOPPOSED BLADE DAMPER
MARK SERVICE MODULE SIZE CFM RANGEMIN DUCT
CONNECTION (IN)
NOMINALNECK SIZE
(IN)MAX NC DESCRIPTION REMARKS
DIFFUSER-REGISTER-GRILLE SCHEDULE
NO SCALE1 TERMINAL AIR BOX DETAIL
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
4. INSTALL A SIGN ON THE EXTERIOR OF THE AIR TERMINAL UNITS AT THE SERVICE ACCESS LOCATION INDICATING THE SOURCE AHU THAT IS PROVIDING THE SUPPLY AIR AND THE ROOMS THAT ARE BEING SERVED.
3. COIL ENTERING AIR TEMPS AND HEATING CAPACITIES BASED ON 48F PRIMARY AIR, 68F PLENUM AIR AND 72F ROOM HEATING SETPOINT.
2. FOR SINGLE DUCT VAV/CAV TERMINAL UNITS - DISCHARGE SOUND POWER DATA FOR 100% PRIMARY AIR VALVE FLOW IS TO BE ARI CERTIFIED AND IS NOT TO EXCEED 74 DB (REFERENCE 10 -12 WATTS) IN THE 2ND OCTAVE BAND AT THE MAXIMUM PRIMARY AIR FLOW INDICATED IN THE SCHEDULE AND WITH 1.5" W.C. INLET STATIC PRESSURE.
1. FOR SINGLE DUCT VAV/CAV TERMINAL UNITS - RADIATED SOUND POWER DATA FOR 100% PRIMARY AIR VALVE FLOW IS TO BE ARI CERTIFIED AND IS NOT TO EXCEED 66 DB (REFERENCE 10 -12 WATTS) IN THE 2ND OCTAVE BAND AT THE MAXIMUM PRIMARY AIR FLOW INDICATED IN THE SCHEDULE AND WITH 1.5" W.C. INLET STATIC PRESSURE.
NOTES:
VAV-3-1 OPEN OFFICE 300.11 320 150 8 <30 <30 SEE MFGR. 150 6.5 55 95 <0.1 180 160 0.6 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL
VAV-B-8 LAB 025 SOUND BOOTH 300 200 6 <30 <30 SEE MFGR. 200 7.6 55 90 <0.1 180 160 0.8 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL
VAV-B-7 LAB 015 SOUND BOOTH 150 100 6 <30 <30 SEE MFGR. 100 3.8 55 90 <0.1 180 160 0.4 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL
VAV-B-6 OFFICE 005.4 300 100 6 <30 <30 SEE MFGR. 200 7.6 55 90 <0.1 180 160 0.8 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL
VAV-B-5 SUPERVIOR OFFICE 005.3 200 60 6 <30 <30 SEE MFGR. 100 3.8 55 90 <0.1 180 160 0.4 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL
VAV-B-4 HEARING AID FITTING005.1 250 75 6 <30 <30 SEE MFGR. 100 3.8 55 90 <0.1 180 160 0.4 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL
VAV-B-3 LAB 023.1 200 100 6 <30 <30 SEE MFGR. 100 3.8 55 90 <0.1 180 160 0.4 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL
VAV-B-2 OFFICE 013.2 150 50 6 <30 <30 SEE MFGR. 75 2.8 55 90 <0.1 180 160 0.3 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL
VAV-B-1 OFFICE 013.1 150 50 6 <30 <30 SEE MFGR. 75 2.8 55 90 <0.1 180 160 0.3 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL
CLG MAX. CLG. MIN. RADIATED NC DISCH. NC HTG. AIR FLOW HTG. MBH EAT ºF LAT ºF APD IN. WG. EWT ºF LWT ºF FLUID GPM MAX. WPD FT.MARK SERVICE
CFM RANGE
INLET SIZE (IN.)
SOUND LEVELSMINIMUM INLET
PRESSURE IN. WG.
HOT WATER HEATING INFORMATION
BASIS OF DESIGN NOTES
NEW VARIABLE AIR VOLUME BOX SCHEDULE - HOT WATER HEATING
PLUMBING SYMBOL LIST
SYMBOL: DESCRIPTION:
PIPE SERVING FIXTURE ON FLOOR ABOVE(EXAMPLE: FD = FLOOR DRAIN)FD
PITCH PIPE IN DIRECTION
RD-16"(1000)
ROOF DRAIN PROPERTIES SYMBOLSIZE (ROOF SQ. FT.)
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)GPM
CHECK VALVE
REDUCER - REFERENCE SPECIFICATIONFOR CONCENTRIC/ECCENTRIC AND FOT/FOB
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
NEW CONNECTION
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
ACID VENTAV
ACID WASTEAW
COLD WATER - POTABLECW
DT DRAIN TILE
SANITARY DRAINAGE (GREASE SANITARY DRAINAGE)GSAN
HOT WATER - POTABLEHW
HOT WATER CIRCULATING - POTABLEHWC
HOT WATER - POTABLE NUMBER INDICATES TEMPHW140
HOT WATER CIRC. - POTABLE NUMBER INDICATES TEMPHWC140
PUMPED DISCHARGEPD
GREASE VENTGV
COMPRESSED AIRCA
DEIONIZED WATERDI
DRAIND
G NATURAL GAS
NOT ALL SYMBOLS MAY APPLY.
SAFETY/RELIEF VALVE
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
TEMPERATURE SENSOR WITH WELLT
THERMOMETER WITH WELL (DIAL TYPE)T
THERMOMETER WITH WELL (FILLED TYPE)
GRV GAS REGULATOR VENT
PIPE CONTINUATION
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P
ROUTE TO DRAIN
PLUMBING ABBREVIATION KEY
BATHTUBBT
CO CLEANOUT
CLINICAL SINKCS
DRINKING FOUNTAINDF
EMERGENCY EYEWASHEE
FLOOR CLEANOUTFCO
FLOOR DRAINFD
GARBAGE DISPOSERGD
GREASE INTERCEPTORGI
I.E. INVERT ELEVATION (FOR REFERENCE ONLY)
LAVATORYLAV
MOP BASINMB
MIXING VALVEMV
SINKSK
TRAP PRIMERTP
WATER CLOSETWC
WALL CLEANOUTWCO
WATER HEATERWH
EMERGENCY SHOWERES
EMERGENCY SHOWER/EYEWASHESE
ELECTRIC WATER COOLEREWC
VENT THROUGH ROOFVTR
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
BFP BACKFLOW PREVENTER
NC NEW CONNECTION
NOT IN CONTRACTNIC
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS NOTED OTHERWISEUNO
EXISTINGE
DIALYSIS BOXDB
CATCH BASINCB
CAST IRONCI
DUCTILE IRONDI
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
NAME
1VIEW NAME1/8" = 1'-0"
LEVEL NAME
10' - 0" HEIGHT ABOVE PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL
NO R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
LINE TYPE KEY:
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
ASBESTOS ABATEMENT CONTRACTOR
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
MECHANICAL PHASING NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO GENERAL CONTRACTOR'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE.PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR
STARTERS, SWITCHES, AND DISCONNECTS.16. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE GENERAL CONTRACTOR CONSTRUCTION MANAGER. ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.
3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.
4. ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.38745. INVERT ELEVATIONS ARE FROM EXISTING DRAWINGS AND MAY NOT BE ACCURATE. VERIFY
ALL ELEVATIONS BEFORE BEGINNING WORK.6. VERIFY UNDERGROUND PIPE SIZES, INVERT ELEVATIONS, AND LOCATIONS PRIOR TO
BEGINNING ANY WORK.7. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO
PLUMBING FIXTURES.8. FOR CLARITY, NOT ALL VALVES HAVE BEEN SHOWN. PROVIDE SHUTOFF VALVES IN
DOMESTIC WATER PIPING SERVING EACH ROOM WITH FIXTURES. ANGLE STOPS SHALL NOT BE CONSIDERED SHUTOFF VALVES.
9. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL SCOPE OF ITEMS TO BE REMOVED. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL DEMOLITION INFORMATION.
10. P.C. SHALL CUT AND PATCH EXISTING AS REQUIRED FOR NEW OR DEMOLITION WORK UNLESS NOTED OTHERWISE. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL INFORMATION.
PLUMBING GENERAL NOTES:
PLUMBING SHEET INDEXP-000 PLUMBING COVERSHEET
PD-103 THIRD FLOOR DEMOLITION - PLUMBING
P-101-B BASEMENT FLOOR PLAN - PLUMBING
P-101-M MEZZANINE FLOOR PLAN - PLUMBING
P-103 SECOND AND THIRD FLOOR PLAN - PLUMBING
P-300 ENLARGED PLUMBING PLANS
P-500 PLUMBING SCHEDULES
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
7:4
0 A
M
P-000
PLUMBING COVERSHEET
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
P-300
1
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
7:4
7 A
M
PD-103
THIRD FLOOR DEMOLITION -
PLUMBING
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
NO R HT
1/8" = 1'-0"2 THIRD FLOOR DEMOLITION - PLUMBING
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
013.1
013.2 005.4
005.3
005.2
005.1005
023.1
sound
booth
#2
sound
booth
#1
sound
booth
#1
sound
booth
#2
sound
booth
#1
sound
booth
#1
future sound
booth
Office
Office Office
SupervisorOffice
LabStorage
Hearing AidFitting
Lab
Lab
001
013
015
040
030
030
007
020
014
012
029
031
002004
006.4
006.3
006.2
006008010
016.31
016.4
016.3
016.2
016
016.10
016.11
019017021
023
025
027
STAIR
Lab
Lab
STAIR
STAIR
C&IT
Storage
Storage
EngOffice
Jan
Men
Women
ClassroomClassroom
Office
Office
Office
OfficeClassroomClassroom
Mech
Mech
Mech
Mech
Mech
Tele
PLC
ClassroomClassroom ComputerLab
Lab
Lab
Teaching Lab
DN
UP
DN
UP
UP
UP
EPEP
NIC
NIC
NIC
NICNICNICNIC
NIC
NIC
NIC
NIC
NIC
NIC
NIC
NIC
NIC NIC
NIC
NIC
NIC
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
NC2 1/2"SAN
2-1/2" SANITARY DOWN FROM MEZZANINE ABOVE
1
SK-1
SP-001
3
SLOPE PIPE
3/4" HW &
1" CW UP
3" V UP
3" W UP
6" R.C. UP
C.O
2 1/2"CW1 1/4"HW3/4"HWR
1/2" HW & CW DN TO OWNER PROVIDED SALON SINK
CO
2" PUMPED SAN UP TO FIRSTFLOOR JANITOR'SCLOSET MOP SINK
3"V3/4"HWR
1"HW2 1/2"CW
4"SAN
3"V
2"SAN
1"CW1"HW
1/2"HW
1/2"CW
1/2"HW1/2"CW
3/4"CW3/4"HW
NC
SP-001
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
7:4
2 A
M
P-101-B
BASEMENT FLOOR PLAN -
PLUMBING
ApproverChecker
Author
18004050.00
Checker
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
Checker
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR PLAN - PLUMBING
KEYNOTES:
1. CONTRACTOR TO FIELD ROUTE NEW 2-1/2" SANITARY LINE. CONNECT TO EXISTING SANITARY IN JANITOR'S CLOSET.
2. WH-1 LOCATED IN CABINET BELOW SINK. 3. SP-1 LOCATED IN CABINET SPACE BELOW SINK.
PROVIDE AIR ADMITTANCE VALVE TO VENT SINK. ROUTE DRAIN TO JANITOR'S CLOSET MOP BASIN ON FIRST FLOOR.
#
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
102
102.1
105.1105.2
105.5105.4105.3
105
DN
Lounge
Jan
DN
UP
Open to Below
Elev
UPDNDN
OfficeOffice
OfficeOfficeWorkRoom
OpenOffice
Open to Below
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
NC
NC1/2"CW
1 1/2"V
2-1/12" SAN DOWN TO BASEMENT
SK-1
1/2"HW
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
7:4
3 A
M
P-101-M
MEZZANINE FLOOR PLAN -
PLUMBING
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
SHEET GENERAL NOTES :
1. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
NO R HT
1/8" = 1'-0"1 MEZZANINE FLOOR PLAN - PLUMBING
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
327
325
328.10
328.09
328.08
328
328.07
328.06
328.05
328.04
328.03
328.02
328.01
326
322.1
300.01
303
304 300.02 300.03
300.04
300
300.11 300.07
300.06
300.05
300.08
300.09300.1
Treatment
Observation
WorkRoom
Office
Office
OpenOffice
Office
COPY
Office
Office
Office
Office
Office
WOMEN'SRESTROOM
UNISEX ADARESTROOM
WORKROOM
Office
TEACHINGLAB Office Office
Office
OpenOffice
OpenOffice Office
Observation
Treatment
Office
TreatmentObservation
MECHANICAL AREA
MECH SHAFT
MECH
DNDN
COOLING TOWER
NIC
305
301
ELEV
NIC NIC NIC NIC
NIC NIC
NIC
NIC
NIC NIC NIC NIC NIC NIC NIC NIC
NIC
NIC
CONFERENCE
MECH
MEN WOMEN
MECHSHAFT
JAN
CONFERENCE
MECH
DN
UPUP
DN
224226.7
226.6
226.5
226
226.8226.42
226.41
226.4 226.3226.2
226.1
219.1
219
219.3219.2
223
222
220
218 216 214 212 210 208 206 204
202
202.1
200
200.2 200.1
201
204.1206.1
209.11
209.1
209.2
209
209.4
209.3
208.1210.1212.1214.1
217.1
216.1218.1
217.2
217
217.4 217.3
211
ELEV
275
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
P-300
2
1/2"CW
1/2"HW
1/2"CW
NC
SK-1
2 1/2" SAN DN TO SECOND FLOOR CEILING SPACE
NC
2"V
WH-1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16 17
18 19 20
b
c
d
NC
2-1/2" SAN DN FROM THIRD FLOOR WORK ROOM.
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
7:4
3 A
M
P-103
SECOND AND THIRD FLOOR
PLAN - PLUMBING
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
NO R HT
1/8" = 1'-0"1 THIRD FLOOR PLAN - PLUMBING
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
NO R HT
1/8" = 1'-0"2 SECOND FLOOR PLAN - PLUMBING
328.01
326
322.1
Office
WOMEN'SRESTROOM
UNISEX ADARESTROOM
MECH SHAFT
ELEVNIC
4 5 6 7
d
LAV-E
WC-E WC-E
3/4" S DN3/4" R DN
4"SAN
2"V
3/4"HW
3/4"CW
3/4"HW
3/4"CW
CO
CO
12
4 5 6 7
d
3
NC
NC
L-1
NC
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
7:4
5 A
M
P-300
ENLARGED PLUMBING PLANS
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
1/4" = 1'-0"1 THIRD FLOOR ENLARGE PLAN DEMOLITION
1/4" = 1'-0"2 THIRD FLOOR ENLARGE PLAN
KEYNOTES:
1. DEMOLISH EXISTING LAV, REWORK EXISTING PLUMBING TO PREPARE FOR NEW FIXTURE INSTALLATION.
2. DEMOLISH EXISTING URINAL. CUT AND CAP ASSOCIATED PIPING AT WALL. PATCH WALL AS REQUIRED.
3. PROVIDE AND INSTALL NEW LAV. CONNECT NEW 1/2" DHW,DCW ISOLATION VALVE, 1-1/2" SANITARY AND VENT.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
SHEET GENERAL NOTES :
1. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:5
7:4
6 A
M
P-500
PLUMBING SCHEDULES
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
2 BASED ON LIBERTY PUMPS MODEL 405 WITH 14" DIA. X14" H , 5.5 GALLON POLYOLEFIN BASIN.
1ABOVE GRADE SUBMERSIBLE, SIMPLEX, NON-CLOG CENTRIFUGAL PUMPS. FURNISH AS PACKAGED PREWIRED, PREPIPED WITH VENTED 14 DIAMETER FIBERGLASSBASIN WITH BOLTED SEALING COVER, CONTROL PANEL, AND ALL CONTROL/ALARM DEVICES FOR A TURN-KEY SYSTEM. REFER TO SPECIFICATION AND DRAWINGDETAIL.
NOTES:
SP-001 BENCH SINK FLOOR PACKAGED SUMP 32 20 WATER 0.980 1.000 120 7.3 1/2 115 1 FLOAT SEE NOTE 1 & 2
MARK AREA/SYSTEM SERVED LOCATION TYPESHAFTSEAL
DESIGNFLOW(GPM)
TOTALDYNAMIC
HEADNPSHR TYPE
DYNAMICVISCOSITY
(CP)
SPECIFICGRAVITY
TEMP(OF)
%EFF AMPSHP
(NOTE 1 )RPM VOLT PH
MOTORENCLOSURE
MOTORCONTROL
REMARKS
MARK AREA/SYSTEM SERVED LOCATION TYPESHAFTSEAL
DESIGNFLOW...
FEET OF LIQUID LIQUID HANDLED %EFFMOTOR DATA
(ENERGY EFFICIENT T-FRAME)REMARKS
PUMP SCHEDULE
For Bids Dec. 11, 2018
NOTES: 1) SANITARY RISER UP IN WALL TO FIXTURE SHALL BE A MINUMUM OF 2". 2) 1/2" CW ANDHW APPLIES ONLY TO THE FINAL VERTICAL RISE-DROP TO EACH FIXTURE, BRANCH PIPING TOVERTICAL RISE-DROP SHALL BE A MINIMUM OF 3/4" UNLESS NOTED OTHERWISE. 3) SIZES SHOWNARE MINIMUMS. SIZES SHOWN ON THE DRAWING THAT ARE LARGER THAN THE SIZES LISTED IN THESCHEDULE SHALL DICTATE THE ROUGH-IN SIZE.
PLUMBING FIXTURE ROUGH-IN SCHEDULE
FIXTUREDESCRIPTION
DOMESTICCW
(NOTE 3)
DOMESTICHW
(NOTE 3)SANITARY(NOTE 3)
VENT(NOTE 3) REMARKS
LAVATORY 1/2" 1/2" 1 1/4" 1 1/4" NOTE 1 & 2
URINAL 1" - 2" 1 1/2" -
WATERCLOSET
1" - 4" 2" -
WH-1
WATER HEATER - ELECTRIC INSTANTANEOUS POINT-OF-USE (FOR SINGLE LOW FLOW FIXTURE), HIGH STRENGTHREINFORCED PLASTIC BODY, 3/8" COMPRESSION FITTINGS, REPLACEABLE ELEMENT, NEMA 4 PAINTED STEELWATERPROOF ENCLOSURE, HIGH TEMPERATURE LIMIT SWITCH, FLOW RESTRICTING AERATOR FOR FAUCET OUTLET, 150PSI WORKING PRESSURE, 1-YEAR WARRANTY ON ELEMENT, 5-YEAR WARRANTY ON HEATER BODY/ELEMENT ASSEMBLY,UL LISTED.
25°F RISE AT 0.5 GPM, 1.8 KW ELEMENT
ELECTRICAL REQUIREMENTS -120V- 1 PHASE, HARD-WIRED
MOUNT WATER HEATER ON WALL BELOW SINK OR LAVATORY. SET OUTPUT WATER TEMPERATURE AT 110°F.
EEMAX (SP), BRADFORD WHITE (ES), CHRONOMITE (SR)
WC-1
WATER CLOSET - ADA WALL MOUNTED, FLUSH VALVE TYPE, WHITE VITREOUS CHINA, SIPHON JET, WATER SAVING,ELONGATED BOWL, 1-1/2" TOP SPUD.
FLUSH VALVE -FLUSH VALVE - EXPOSED, SENSOR OPERATION, HARD-WIRED, 1.6 GALLONS PER FLUSH, 11-1/2" ROUGH-IN,CHROME PLATED, 1" I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH VANDAL RESISTANT CAP, HIGH BACK PRESSUREVACUUM BREAKER, ADJUSTABLE TAILPIECE, SPUD COUPLING AND FLANGE, WALL FLANGE WITH SET SCREW,MECHANICAL OVER-RIDE BUTTON, CHLORAMINE RESISTANT MATERIALS, ADA COMPLIANT, 3 YEAR WARRANTY.
SEAT - WHITE, EXTRA HEAVY, OPEN FRONT, INJECTION MOLDED SOLID PLASTIC, SELF-SUSTAINING HINGE, STAINLESSSTEEL OR PLATED STEEL POSTS AND NUTS.
ACCESSORIES - WATER CLOSET SUPPORT CARRIER RATED FOR 500 LBS.
MOUNT WATER CLOSET WITH CARRIER BOLTED SECURELY TO FLOOR. TOP OF SEAT SHALL BE AT 16"-17" ABOVEFINISHED FLOOR (VERIFY EXACT MOUNTING HEIGHT WITH MANUFACTURER). FLUSH HANDLE SHALL BE LOCATED ONTHE WIDE SIDE OF THE TOILET STALL AND BE AT 12" (MAXIMUM) ABOVE BOWL RIM AND OPERATE WITH NO GREATERTHAN 5 LB FORCE IN COMPLIANCE WITH LATEST ADA STANDARDS. VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-INLOCATIONS.
WATER CLOSET - AMERICAN STANDARD (2257.101)
FLUSH VALVE - AMERICAN STANDARD 6065.161
SEAT -BEMIS (3155C), CHURCH (3155C), BENEKE (533PC), OLSONITE (95), SAME AS WATER CLOSETMANUFACTURER
SK-1
SINK - SELF-RIMMING SINGLE COMPARTMENT WITH FAUCET DECK, 18 GAUGE TYPE 304 STAINLESS STEEL, 20"(SIDE-TO-SIDE) x 18" (FRONT-TO-BACK) OVERALL SIZE,20" x 18" x [D]" DEEP BOWL, COMPLETELY UNDERCOATED, 3-1/2"DIAMETER DRAIN OUTLET LOCATION CENTERED IN BOWL, PERFORATED TYPE 316 STAINLESS STEEL GRID STRAINER.
SINK TRIM - TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION, CHROME-PLATED FINISH, GOOSENECK RIGIDSPOUT,NOMINAL 4" REACH, AERATOR, HANDLES AT 8" CENTERS, 1/4-TURN OPERATION CERAMIC DISC CARTRIDGE.
ACCESSORIES - 1-1/2" 17 GAUGE CHROME-PLATED BRASS TAILPIECE AND P-TRAP, QUARTER-TURN BALL VALVE TYPE 3/8"CHROME-PLATED BRASS ANGLE SUPPLIES WITH LOOSE KEY STOPS, CHROME-PLATED SOFT COPPER SUPPLY LINES.
SINK - ELKAY (LR/LK18B)
SINK TRIM - AMERICAN STANDARD (7230.000)
L-1
LAVATORY - ADA WALL MOUNTED, WHITE VITREOUS CHINA, 20"x18", 4" HIGH CONTOURED BACKSPLASH, SINGLE FAUCETHOLE, DRILLED FOR CONCEALED ARM CARRIER.
INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES AND SUPPLY LINES.
LAVATORY TRIM - SENSOR ACTIVATED MIXING FAUCET, HARD-WIRED, BRASS CONSTRUCTION, CHROME-PLATED FINISH,CONVENTIONAL SPOUT WITH VANDAL RESISTANT AERATOR, SINGLE HOLE DECK PLATE, PERFORATED GRID STRAINERWITH 1-1/4" 17 GAUGE TAILPIECE, SOLID BRASS SOLENOID WITH BUILT-IN FILTER, SOLID BRASS THERMOSTATIC MIXINGVALVE MEETING ASSE 1070 REQUIREMENTS WITH ADJUSTABLE TEMPERATURE LIMIT STOP AND INTEGRAL CHECKVALVES, WATERPROOF CONNECTORS AND CABLE, UL APPROVED TRANSFORMER.
ELECTRICAL REQUIREMENTS - 120 VAC INPUT
MOUNT CONTROLS IN WATERPROOF VANDAL-RESISTANT ENCLOSURE BELOW LAVATORY. PROVIDE TRANSFORMER WITHCABLE EXTENSIONS (AS REQUIRED) OR PLUG-IN TRANSFORMER. MOUNT TRANSFORMER ABOVE CEILING OR INACCESSIBLE PIPE CHASE. COORDINATE LOCATION WITH ELECTRICAL CONTRACTOR. SELECT TRANSFORMER TO SERVEMAXIMUM NUMBER OF ELECTRONIC VALVES TO REDUCE AMOUNT OF TRANSFORMERS.
MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 2005 AND ASME/ANSI STANDARDA112.18.1M. FAUCET SHALL COMPLY WITH FEDERAL ACT S.3874. PROVIDE RESTRICTIVE DEVICE AS REQUIRED. MOUNTMIXING VALVE UNDER COUNTER/LAVATORY. MIXING VALVE SHALL NOT BE WYE PATTERN STYLE.
PROGRAMMING UNIT - HAND HELD, CAPABLE OF CHANGING SETTINGS, RUNNING DIAGNOSTICS, AND SCAN FAUCETSWITH ISSUES. PROVIDE ONE CONTROLLER FOR EVERY 6 FAUCETS.
ACCESSORIES - QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE SUPPLY STOPS, CHROME PLATED SOFTCOPPER SUPPLY LINES, DRAIN AND OFFSET TAILPIECE, 1-1/4" 17 GAUGE CAST BRASS P-TRAP, SUPPORT CARRIER.
IN COMPLIANCE WITH LATEST ADA STANDARD. PROVIDE 29" MINIMUM CLEARANCE FROM FLOOR TO BOTTOM OF APRONIN COMPLIANCE WITH LATEST ANSI A117.1 AND ADA STANDARDS. ARMAFLEX WITH TAPE IS NOT ACCEPTABLE IN LIEU OFINSULATION KIT.
LAVATORY -KOHLER (K-2007)
INSULATION KIT - TRUEBRO
LAV TRIM -AMERICAN STANDARD (775B.205/PK00.HAC)
TAG DESCRIPTION ACCEPTABLE MANUFACTURERS
THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRATCOR. THE CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQURED FOR FULLY OPERATIONAL SYSTEMS,WHETHERSPECIFICED OR NOT.CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRATCTOR IS RESPONSIBLE FOR COMPLETE DESCRIPTION OFMATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.CONTRATCTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874.
PLUMBING MATERIAL LIST
PIPING ABBREVIATION KEY
ABBR: DESCRIPTION:
DIFFERENTIAL PRESSURE GAUGE (RANGE)DPG (0-2")
DIFFERENTIAL PRESSURE SWITCHDPS
PRESSURE SWITCHPS
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
CO CLEANOUT
MIXING VALVEMV
NC NEW CONNECTION
N.C. NORMALLY CLOSED
NOT IN CONTRACTNIC
NORMALLY OPENN.O.
ELECTRICAL TO PNEUMATIC VALVEEP
TYPICAL TYP
UNLESS NOTED OTHERWISEUNO
MA MIXED AIR
OA OUTSIDE AIR
RA RETURN AIR
SA SUPPLY AIR
EXHAUST/RELIEF AIREA
C COMMON
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
NAME
1VIEW NAME1/8" = 1'-0"
LEVEL NAME
10' - 0" HEIGHT ABOVE PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL
NO R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
LINE TYPE KEY:
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
ASBESTOS ABATEMENT CONTRACTOR
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE.PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR
STARTERS, SWITCHES, AND DISCONNECTS.16. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE GENERAL CONTRACTOR CONSTRUCTION MANAGER. ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.
MECHANICAL PHASING NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO GENERAL CONTRACTOR'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
1. THE SIZE OF BRANCH PIPING TO TERMINAL HEATING DEVICES AND COILS SHALL BE 3/4" UNLESS NOTED OTHERWISE.
2. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST FLOOR DRAIN.3. INSTALL ALL REFRIGERANT LIQUID AND SUCTION PIPING SIZED PER EQUIPMENT
MANUFACTURER RECOMMENDATIONS.
PIPING GENERAL NOTES:
PIPING SHEET INDEXMP-000 PIPING COVERSHEET
MPD-101-B BASEMENT FLOOR DEMOLITION - PIPING
MP-101-B BASEMENT FLOOR - PIPING
MP-103 THIRD FLOOR PLAN - PIPING
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:4
9:4
4 A
M
MP-000
PIPING COVERSHEET
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
001
013
015
040
030
030
007
020
014
012
029
031
002004
006.4
006.3
006.2
006008010
016.31
016.4
016.3
016.2
016
016.10
016.11
019017021
023
025
027
STAIR
Lab
Lab
STAIR
STAIR
C&IT
Storage
Storage
EngOffice
Jan
Men
Women
ClassroomClassroom
Office
Office
Office
OfficeClassroomClassroom
Mech
Mech
Mech
Mech
Mech
Tele
PLC
ClassroomClassroom ComputerLab
Lab
Lab
Teaching Lab
T
T
T
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
3/4" S & R UP
1 1/4"HWS
1"HWS
1 1/4"HWR
3/4"HWR
3/4"HWS
3/4"HWS
3/4"HWR
3/4"HWR3/4"HWS
3/4"HWS3/4"HWR
1"HWR
3/4"HWS
1 1/4"HWR
3"HWR
1"HWS 3/4"HWS3/4"HWR
3/4"HWS3/4"HWR
1 1/4"HWS
3"HWR
3/4"HWR
3/4"HWS3/4"HWR
3/4"HWS
3/4"HWR
3/4"HWS 3/4"HWS3/4"HWR
1"HWS
1"HWR
1 1
/2"H
WS
2"H
WR
1 1
/4"H
WS
2"H
WR
1 1
/2"H
WS
3/4"HWR
3/4"HWS
1"HWR
3/4"HWS
3/4"HWR
3/4"HWR
3/4"HWS3/4"HWS
3/4"HWS
3/4"HWS
3/4"HWR
3/4"HWR
1"HWR
1"HWS
2 1/2"HWS
2 1/2"HWR
1"HWR
3/4"HWS
3/4"HWR
3/4"HWS3/4"HWS3/4"HWS
3/4"HWR
3/4"HWR
3/4"HWR
3/4"HWR
1
1
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:4
9:4
9 A
M
MPD-101-B
BASEMENT FLOOR DEMOLITION
- PIPING
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR DEMOLITION - PIPING
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
SHEET GENERAL NOTES :
1. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
2. CAP ALL OPEN ENDED HHW PIPING. DO NOT LEAVE ANY ABONDONED PIPING IN THE AREA OF WORK. COORDINATE WITH OWNER'S CURRENT HHW RENOVATION PROJECT.
KEYNOTES:
1. DISCONNECT AND REMOVE EXISTING COMPUTER ROOM AIR CONDITIONING (CRAC) UNIT, AND ASSOCIATED PIPING. SALVAGE UNIT AND RETURN TO OWNER. CAP DUCT MAIN, CUT AND CAP HHW BACK TO MAIN. VERFY WITH OWNER PRIOR TO COMMENCEMENT OF WORK.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
013.1
013.2 005.4
005.3
005.2
005.1005
023.1
sound
booth
#2
sound
booth
#1
sound
booth
#1
sound
booth
#2
sound
booth
#1
sound
booth
#1
future sound
booth
Office
Office Office
SupervisorOffice
LabStorage
Hearing AidFitting
Lab
Lab
001
013
015
040
030
030
007
020
014
012
029
031
002004
006.4
006.3
006.2
006008010
016.31
016.4
016.3
016.2
016
016.10
016.11
019017021
023
025
027
STAIR
Lab
Lab
STAIR
STAIR
C&IT
Storage
Storage
EngOffice
Jan
Men
Women
ClassroomClassroom
Office
Office
Office
OfficeClassroomClassroom
Mech
Mech
Mech
Mech
Mech
Tele
PLC
ClassroomClassroom ComputerLab
Lab
Lab
Teaching Lab
T
T
T
T
T
T
T
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
1
1
1
1
1
1
3/4"HWR3/4"HWS
NC
1
NC
3/4"HWR3/4"HWS
3/4"HWR3/4"HWS
NC
3/4"HWS3/4"HWR
3/4"HWR3/4"HWS
3/4"HWS3/4"HWR
3/4"HWR3/4"HWS
NC
NC3/4"HWS3/4"HWR 3/4"HWR
3/4"HWS
1
NC
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:4
9:4
7 A
M
MP-101-B
BASEMENT FLOOR - PIPING
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR - PIPING
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
SHEET GENERAL NOTES :
1. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
2. COORDINATE HHW INSTALLATION & ROUTING FOR THIS PROJECT WITH OWNER'S HHW PIPING REPLACEMENT PROJECT CURRENTLY UNDER CONSTRUCTION.
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
KEYNOTES:
1. NEW 3/4" HHWS/R PIPE TO NEW TERMINAL AIR BOX FROM EXISTING HHWS & R MAINS. PROVIDE ISOLATION VALVES ON SUPPLY AND RETURN PIPING, TWO-WAY CONTROL VALVE & BALANCE VALVE ON RETURN PIPING. SEE DETAIL.
#
327
325
328.10
328.09
328.08
328
328.07
328.06
328.05
328.04
328.03
328.02
328.01
326
322.1
300.01
303
304 300.02 300.03
300.04
300
300.11 300.07
300.06
300.05
300.08
300.09300.1
Treatment
Observation
WorkRoom
Office
Office
OpenOffice
Office
COPY
Office
Office
Office
Office
Office
WOMEN'SRESTROOM
UNISEX ADARESTROOM
WORKROOM
Office
TEACHINGLAB Office Office
Office
OpenOffice
OpenOffice Office
Observation
Treatment
Office
TreatmentObservation
T
T
T
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
1
NC
3/4"HWR3/4"HWS
2"HWR2"HWS
3/4"HWS3/4"HWR
3/4"HWS
3/4"HWR
3/4"HWR3/4"HWS
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:4
9:4
7 A
M
MP-103
THIRD FLOOR PLAN - PIPING
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
NO R
HT
1/8" = 1'-0"1 THIRD FLOOR PLAN - PIPING
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
KEYNOTES:
1. NEW 3/4" HHWS/R PIPE TO NEW TERMINAL AIR BOX FROM EXISTING HHWS & R MAINS. PROVIDE ISOLATION VALVES ON SUPPLY AND RETURN PIPING, TWO-WAY CONTROL VALVE & BALANCE VALVE ON RETURN PIPING. SEE DETAIL.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
SHEET GENERAL NOTES :
1. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.
2. COORDINATE HHW INSTALLATION & ROUTING FOR THIS PROJECT WITH OWNER'S HHW PIPING REPLACEMENT PROJECT CURRENTLY UNDER CONSTRUCTION.
FIRE PROTECTION SYMBOL LIST
SYMBOL: DESCRIPTION:
FIRE PROTECTIONFP
FIRE PROTECTION - DRY SYSTEMFPD
SERVICE WATER - POTABLEW
NO HATCH LIGHT HAZARD
ORDINARY GROUP 1
ORDINARY GROUP 2
EXTRA GROUP 1
EXTRA GROUP 2
SPRINKLER - WALL MOUNTED
SPRINKLER
SPRINKLER - CONCEALED
SPRINKLER
SPRINKLER
SPRINKLER
SPRINKLERA
SPRINKLERA
COMPRESSED AIR - FIRE PROTECTIONCAF
PIPE CAP
PIPE DOWN
NEW CONNECTION
PIPE UP OR UP/DOWN
DEMOLITION
DRAINDFP
NOT ALL SYMBOLS MAY APPLY.
UNION/FLANGE
DIRECTION OF FLOW IN PIPE
AREA BOUNDARY
FIRE PROTECTION ABBREVIATION KEY
AD ACCESS DOOR
BFP BACKFLOW PREVENTER
N.C. NORMALLY CLOSED
ABOVE FINISHED FLOORAFF
NC NEW CONNECTION
NOT IN CONTRACTNIC
NORMALLY OPENN.O.
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS NOTED OTHERWISEUNO
I.E. INVERT ELEVATION
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
NAME
1VIEW NAME1/8" = 1'-0"
LEVEL NAME
10' - 0" HEIGHT ABOVE PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL
NO R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
LINE TYPE KEY:
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER IS THE BASIS OF DESIGN.
3. FIRE PROTECTION PIPE ROUTING IS SHOWN FOR GENERAL LAYOUT. DETERMINE EXACT NUMBER OF SPRINKLERS, PIPE SIZING, AND PIPE ROUTING.
4. CENTER SPRINKLERS IN CEILING TILES IN BOTH DIRECTIONS IN ALL AREAS. IN AREAS WITH 2’X4’ CEILING TILES CENTERING USING A 2’X2’ CEILING PATTERN IS ACCEPTABLE.
5. NEW SPRINKLERS SHALL BE QUICK RESPONSE TYPE, UNLESS OTHERWISE NOTED. CONTRACTOR SHALL NOT MIX STANDARD RESPONSE SPRINKLERS WITH QUICK RESPONSE SPRINKLERS IN UNPARTITIONED SPACES.
6. PROVIDE COVERAGE ABOVE AND BELOW ALL DUCTWORK GREATER THAN 48" WIDE. 7. PROVIDE COVERAGE ABOVE AND BELOW FLOATING CEILINGS. REFER TO ARCHITECTURAL
PLANS.
FIRE PROTECTION GENERAL NOTES:
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
CONSTRUCTION MANAGERC.M.
PLUMBING CONTRACTORP.C.
ELECTRICAL CONTRACTORE.C.
VENTILATION CONTRACTORV.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
FIRE PROTECTION CONTRACTORF.P.C.
HEATING CONTRACTORH.C.
MECHANICAL CONTRACTORM.C.
MECHANICAL PHASING NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO CONSTRUCTION MANAGER'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE CONSTRUCTION MANAGER AND ARCHITECT/ ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.
MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE. PENETRATIONS THROUGH ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR
STARTERS, SWITCHES, AND DISCONNECTS.16. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
FIRE PROTECTION SHEET INDEXF-000 FIRE PROTECTION COVERSHEET
F-101-B BASEMENT FLOOR - FIRE PROTECTION
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:4
7:0
4 A
M
F-000
FIRE PROTECTION
COVERSHEET
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
NOTES: 1. SEE FLOOR PLANS FOR ZONING REQUIREMENTS. 2. SPRINKLER SHALL HAVE COLOR CODED BULB THERMAL ELEMENT. 3. ALL SPRINKLERS SHALL BE UL AND FM LISTED. 4. CONTRACTOR TO VERIFY SPRINKLER REQUIREMENTS BASED ON ACTUAL INSTALLATION, USAGE, ARCHITECTURAL CEILING PLAN AND NFPA 13
REQUIREMENTS. 5. TAG NAME IS PRIMARILY FOR IDENTIFIYING SPRINKLERS IN SUBMITTALS. IT MAY OR MAY NOT BE FOUND ELSEWHERE ON THE DRAWINGS.
CONTRACTOR TO SUBMIT ALL SPRINKLER TYPES TO BE USED. 6. AREAS ARE GENERAL IN NATURE. CONTRACTOR TO MATCH UNSCHEDULED AREAS TO SIMILAR SPACES....
FIRE SPRINKLER USAGE SCHEDULE
AREA TYPE(NOTE 1 & 6)
AREAHAZARD
SPRINKLER
TEMPERATURERATING MANUFACTURER & MODEL NOTES
TAG NAME(NOTE 4 & 5)
SPRINKLERTYPE
RESPONSECATEGORY FINISH
SEE PLANS SEE PLANS SPR-1 RECESSEDPENDENT
QUICK CHROMEPLATED
155 VIKING VK, RELIABLE F1FR, TYCO TY-FRB,VICTAULIC V2708
NOTES 2,3
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
013.1
013.2 005.4
005.3
005.2
005.1005
023.1
sound
booth
#2
sound
booth
#1
sound
booth
#1
sound
booth
#2
sound
booth
#1
sound
booth
#1
future sound
booth
Office
Office Office
SupervisorOffice
LabStorage
Hearing AidFitting
Lab
Lab
001
013
015
040
030
030
007
020
014
012
029
031
002004
006.4
006.3
006.2
006008010
016.31
016.4
016.3
016.2
016
016.10
016.11
019017021
023
025
027
STAIR
Lab
Lab
STAIR
STAIR
C&IT
Storage
Storage
EngOffice
Jan
Men
Women
ClassroomClassroom
Office
Office
Office
OfficeClassroomClassroom
Mech
Mech
Mech
Mech
Mech
Tele
PLC
ClassroomClassroom ComputerLab
Lab
Lab
Teaching Lab
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
1
1
1
1
1
1
BOUNDARY INDICATES AREA OF WORK. REMOVE EXISTING SPRINKLERS AND ASSOCIATED BRANCH AND MAIN PIPING WITH AREA OF WORK. EXISTING FIRE PROTECTION PIPING MAY BE RE-USED IF SIZED PROPERLY PER CONTRACTORS' HYDRAULIC CALCULATIONS AND LOCATED PROPERLY FOR COORDINATION WITH OTHER TRADES. RE-USED FIRE PROTECTION PIPING MUST BE INSPECTED AND CONTRACTOR MUST DOCUMENT ACCEPTANCE PRIOR TO RE-USING. PROVIDE NEW SPRINKLERS AND COVERAGE PER NFPA 13. EXISTING SPRINKLER HEADS IN THE CORRECT LOCATIONS MAY BE LEFT IN PLACE, BUT ONLY IF THEY ARE QUICK RESPONSE. NEW SPRINKLERS WILL MATCH EXISTING.
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:4
7:0
5 A
M
F-101-B
BASEMENT FLOOR - FIRE
PROTECTION
PETPAPPETPAP
KIRSAI
18004050.00
PETPAP
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
PETPAP
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR - FIRE PROTECTION
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
SHEET GENRAL NOTES :
1. COORDINATE ALL DEMOLITION AND NEW WORK WITH ARCHITECTURAL DEMOLITION AND PHASING PLANS.2. REMOVE ALL PIPING, EQUIPMENT, HANGERS, SUPPORTS, CONTROLS AND ACCESSORIES WITHIN SCOPE BOUNDARY AS SHOWN ON THIS PLAN3. EXISTING PIPING IS SHOWN FOR REFERENCE. CONTRACTOR TO FIELD VERIFY PIPING AND DEMOLITION WORK PRIOR TO CONSTRUCTION START.4. RELOCATE EXISTING UTILITIES AS REQUIRED TO COORDINATE WITH OTHER TRADES.5. CONTRACTOR SHALL SHUTDOWN AND DRAIN SYSTEM AS REQUIRED TO MAKE MODIFICATIONS.SYSTEM SHUTDOWN SHALL BE COORDINATED WITH OWNER
PRIOR TO PROCEEDING.6. CONTRACTOR SHALL TURN SPRINKLERS UPRIGHT DURING CONSTRUCTION TO MAINTAIN ADEQUATE COVERAGE PER NFPA13.7. CONTRACTOR SHALL EXTEND AND REWORK EXISTING FIRE PROTECTION PIPING AS REQUIRED TO MAINTAIN COVRAGE PER NFPA13.8. PROVIDE TEMPORARY CONNECTIONS TO KEEP SYSTEM SERVING AREAS OUT OF SCOPE ACTIVE DURING CONSTRUCTION.9. FIRE PROTECTION CONTRACTOR RESPONSIBLE FOR COMPLETE SYSTEM.10. REFER TO ARCHITECTURAL LIFE SAFETY PLANS FOR LOCATIONS OF ALL FIRE BARRIERS.REFER TO 2/FP00 FOR FIRE RATED BARRIER PENETRATION DETAIL.
REFER TO 1/FP000 FOR TYPICAL ARMOVER SUPPORT DETAIL.
KEYNOTES:
1. CONNECT TO SPRINKLER HEAD IN SOUND BOOTH. COORDINATE WITH OWNER REGARDING THE WORK. CONTRACTOR SHALL INCLUDE THIS WORK IN THE CALCULATION.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
NAME
1VIEW NAME1/8" = 1'-0"
LEVEL NAME
10' - 0" HEIGHT ABOVE PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL
NO R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
LINE TYPE KEY:
1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.
2. {L###} INDICATES THE LIGHTING SEQUENCE OF OPERATION FOR THE SPACE. REFER TO THE
LIGHTING SEQUENCE OF OPERATION MATRIX ON SHEET E-000.
LUMINAIRE KEY:
DEVICE KEY:
ELECTRICAL MOUNTING SUBSCRIPT KEY:A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASHC MOUNT AT CEILING
ELECTRICAL GENERAL NOTES:
LUMINAIRE
F1 = FIXTURE TAG1 = CIRCUIT NUMBERa = SWITCH DESIGNATION
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS INFORMATION. EX: F1 / 1 / a / SE
DEVICEA = MOUNTING (IF APPLICABLE)1 = CIRCUIT NUMBER
*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS INFORMATION. EX: A / 1
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CONDUITS BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.
7. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, LIGHTING, POWER, AND SYSTEMS.
1. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH PHASE.
2. CIRCUITS SERVING EMERGENCY LUMINAIRES WILL BE RUN IN A SEPARATE RACEWAY FROM ALL OTHER CIRCUITS.
3. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
4. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.
5. CONTRACTOR SHALL VERIFY ALL FURNITURE AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE AND EQUIPMENT.
6. ELECTRICAL EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF, OPERATION OF, AND ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF ELECTRICAL EQUIPMENT, ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: LIGHTING SWITCHES 4'-0" RECEPTACLES (GENERAL AREAS) 1'-6" RECEPTACLES (UTILITY AREAS) 4'-0" TELECOMMUNICATION OUTLETS 1'-6" WALL PHONE 4'-0" FIRE ALARM STATIONS 4'-0" FIRE ALARM SIGNALS 7'-6" CLOCKS/CLOCK OUTLETS 1’-6” BELOW FIN. CEIL. SAFETY SWITCHES 5'-0" TO TOP
ELECTRICAL INSTALLATION NOTES:
MCC-# MOTOR CONTROL CENTER
ELECTRICAL EQUIPMENT TAGS
TAG: DESCRIPTION:RELATED
SPECIFICATION
SW-1P 26 09 33 SWITCH - SINGLE POLE
OC SW-OC-D OCCUPANCY SENSOR - DUAL TECHNOLOGYD
26 09 33
F# TROFFER
F# DOWNLIGHT LUMINAIRE
ECONN ELECTRICAL CONNECTIONE
E
PANEL '###' PANELBOARD - SURFACE MOUNT
SW-LV SWITCH - LOW VOLTAGELV
26 09 33
REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V
REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V
ELECTRICAL SYMBOL LIST
SYMBOL: TAG:SPEC
SECTION:DESCRIPTION:
F# LINEAR LUMINAIRES
SW-3W 26 09 33 SWITCH - THREE WAY3
REC-QUAD 26 27 26 QUAD RECEPTACLE, 125V
DB DOOR BELLDB
DP-# DISTRIBUTION PANEL
SB-# SWITCHBOARD
FA-211 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE - WALL MOUNTED
A1 A3
A7 AH
AS
FA-201 28 31 00 FIRE ALARM VISUAL NOTIFICATION DEVICE - CEILING MOUNTED
V1 V3
V7 VH
FA-231 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE - CEILING MOUNTED
A1 A3
A7 AH
FA-230 28 31 00 FIRE ALARM AUDIO NOTIFICATION DEVICE - CEILING MOUNTED
A
SD FA-120 28 31 00 FIRE ALARM SMOKE DETECTOR - CEILING MOUNTED
FA-130 28 31 00 FIRE ALARM MANUAL PULL STATIONF
VS
AS
28 31 00FAP-# FIRE ALARM - CONTROL PANEL
JB JUNCTION BOXJ
J
MX-#/MS-#/FCS-# MANUAL SWITCH / STARTER / COMBINATION STARTER
SW WALL CONTROL STATIONSW
XM# EMERGENCY UNIT
26 27 26
ELECTRICAL SHEET INDEXE-000 ELECTRICAL COVERSHEET
ED-101-B BASEMENT FLOOR DEMOLITION - ELECTRICAL
ED-101 FIRST FLOOR DEMOLITION - ELECTRICAL
ED-101-M MEZZANINE FLOOR DEMOLITION - ELECTRICAL
ED-103 THIRD FLOOR DEMOLITION - ELECTRICAL
EL-101-B BASEMENT FLOOR - LIGHTING
EL-101 FIRST FLOOR PLAN - LIGHTING
EL-101-M MEZZANINE FLOOR PLAN - LIGHTING
EL-103 THIRD FLOOR PLAN - LIGHTING
EP-101-B BASEMENT FLOOR - POWER
EP-101 FIRST FLOOR PLAN - POWER
EP-101-M MEZZANINE FLOOR PLAN - POWER
EP-103 THIRD FLOOR PLAN - POWER
EP-300 POWER DETAILS
ES-101-B BASEMENT FLOOR - SYSTEM
ES-101 FIRST FLOOR PLAN - SYSTEMS
ES-101-M MEZZANINE FLOOR PLAN - SYSTEMS
ES-103 THIRD FLOOR PLAN - SYSTEMS
ES-300 SYSTEM DETAILS
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:3
5 A
M
E-000
ELECTRICAL COVERSHEET
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
LIGHTING SEQUENCE OF OPERATIONPLAN ID LIGHTING SWITCHED
{LS1} Sequence: Switched lights are occupancy controlled in this space.ON: The lights are turn on by occupancy sensor.OFF: After the space has been vacant for 20 minutes, the lights will automatically turn off.
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
REFER TO SPECIFICATION SECTIONS LIGHTING 26 51 00 AND EMERGENCY LIGHTING EQUIPMENT 26 52 00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.INTERIOR CORRELATED COLOR TEMPERATURE 4100K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.
CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THESPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE FIRST MANUFACTURER LISTED IS THE BASIS OFDESIGN.
VERIFY AND COORDINATE ALL CEILING TYPES WITH LUMINAIRE MOUNTING AND TRIM REQUIREMENTS PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.CONFIRM ALL COLORS AND FINISHES OF ALL LUMINAIRE COMPONENTS WITH ARCHITECT AND INTERIOR DESIGNER PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.UNLESS INDICATED ON LIGHTING PLANS OR BELOW, REFER TO ARCHITECTURAL AND INTERIOR DESIGN ELEVATIONS, SECTIONS AND DETAILS FOR ALL SUSPENDED AND WALL MOUNTED LUMINAIREMOUNTING HEIGHTS.
EM - EMERGENCY BATTERY
EB - ELECTRONIC
(TYPE) BALLAST/DRIVER:
(WATT) PER: FIX - FIXTURE, FT - FOOT, LAMP
FL - FLUORESCENT RE - RECESSED
LED - LIGHT EMITTING DIODE CL - CEILING SURFACE
(TYPE) LIGHT SOURCE TECHNOLOGY: (MTG) MOUNTING:
CFSA - COLOR-FINISH SELECTION BY ARCHITECT
FINISH:
O - OTHER (SEE DESCRIPTION)
FS - FLAT STEEL A - .125" ACRYLIC
(DESC) DOOR: (L/L) LENS/LOUVER:
LUMINAIRE SCHEDULE
ITEM DESCRIPTION L/L MTG
DIMENSIONS WATTLIGHT SOURCETECHNOLOGY BALLAST/DRIVER
APPROVED MANUFACTURERL W H DIA.MAXANSI PER TYPE QTY
MODEL/ABSOLUTE
LUMENS (MIN) VOLTS TYPE
EM1 EMERGENCY UNIT, TWO ADJUSTABLE LEDHEADS, WHITE THERMOPLASTIC HOUSING.SELF TEST & DIAGNOSTICS OF INVERTERAND LAMPS
O CL 11" 3 1/2" 7 1/2" 3 W FIX LED 2 6 VOLT (2INCLUDED)
120 V EM DUAL-LITE EVHCLITHONIA ELML4
F1 RECESSED STATIC GRID TROFFER WITH FSDOOR.
K RE 4'-0" 1'-0" 4 1/2" 64 W FIX FL 2 32WATTF32T8
120 V EB LITHONIA SP8COLUMBIA 4PSMETALUX GC
001
013
015
040
030
030
007
020
014
012
029
031
002004
006.4
006.3
006.2
006008010
016.31
016.4
016.3
016.2
016
016.10
016.11
019017021
023
025
027
STAIR
Lab
Lab
STAIR
STAIR
C&IT
Storage
Storage
EngOffice
Jan
Men
Women
ClassroomClassroom
Office
Office
Office
OfficeClassroomClassroom
Mech
Mech
Mech
Mech
Mech
Tele
PLC
ClassroomClassroom ComputerLab
Lab
Lab
Teaching Lab
F F F
F
E E E E
E E E E
JJ
OC
J
OC
E
E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
EXISTING RP-BD
EXISTING LP-BB
EXISTING LP-BAEXISTING MCC EXISTING LP-BC
EXISTING EMERGENCY
LP-E
EXISTING FIREALARM CABINET
EXISTING MASTER
CLOCK & PROGRAM
MACHINEC
C
C
C
EXISTING DP-1
EXISTING SB-1
+72
CLOCK
+72
CLOCK
+72
CLOCK
A
A
+96A
A
R
+42 R R R
EXISTING RP-BF
/+72CLOCK
+42R+42R
+42
+42R+42R
+42
R
/+72
+30R+30R
CLOCK
R
R
R
R R R
EXISTING RP-BG
RR
EXISTING RP-BH
RRRRRRRR
R R R R R
R R
/+72CLOCK
C
/+72CLOCK
C
EXISTING SECURITY
CONTROL PANELS
EXISTING SECURITY
CONTROL PANELS
1
1
1
1
1
1
3
1
1
1
1
1
1
CRAC
CRAC2
2
3
3
3
3
3
3
3
FURNITURE FEEDFURNITURE FEED FURNITURE FEEDFURNITURE FEED
FURNITURE FEEDFURNITURE FEEDFURNITURE FEEDFURNITURE FEED
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:3
7 A
M
ED-101-B
BASEMENT FLOOR DEMOLITION
- ELECTRICAL
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR DEMOLITION - ELECTRICAL
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
KEYNOTES:
1. FIXTURE TO BE RELOCATED, REFER TO SHEET EL-101-B.
2. CONFIRM DEMOLITION WORK WITH OWNER.3. DISCONNECT AND REMOVE WIRE-WAYS,
OUTLETS AND JUNCTION BOXES DRAWN IN DOTTED SYMBOLS, REMOVE UNUSED BRANCH CIRCUITS BACK TO SOURCE PANEL AND MARK THEM AS A SPARES.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
100.1100.2
100
103.2 103.1
103
103.5103.4103.3
BASEMENTFLOOR BELOW
ELEV
BASEMENTFLOOR BELOW
SECONDFLOOR ABOVE
EXTERIORCIRCULATION
DN
DN
DN
UP
MechJan
Lounge
UP
Lobby
Mech
Office Office
Recept
OfficeOfficeStorage
UP DNUP
SD
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
O O O
OO
EXISTING LP-1A
1
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:3
6 A
M
ED-101
FIRST FLOOR DEMOLITION -
ELECTRICAL
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R HT
1/8" = 1'-0"1 FIRST FLOOR DEMOLITION - ELECTRICAL
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
SHEET NOTES :
1. UNLESS OTHERWISE NOTED, ALL ELECTRICAL DEVICES SHOWN ON THIS DRAWING ARE EXISTING TO REMAIN.
KEYNOTES:
1. DEVICE WILL BE REPLACED, MAINTAIN WIRING, COORDINATE WORK WITH FACILITY FIRE DEPARTMENT AND FIRE ALARM VENDOR BEFORE START OF WORK. REFER TO DRAWING ES-101.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
102
102.1
105.1105.2
105.5105.4105.3
105
DN
Lounge
Jan
DN
UP
Open to Below
Elev
UPDNDN
OfficeOffice
OfficeOfficeWorkRoom
OpenOffice
Open to Below
J
J
J
SD
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
A
/+72CLOCK
O O O
O O
1
1
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:3
8 A
M
ED-101-M
MEZZANINE FLOOR
DEMOLITION - ELECTRICAL
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R HT
1/8" = 1'-0"1 MEZZANINE FLOOR DEMOLITION - ELECTRICAL
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
KEYNOTES:
1. DEVICE TO BE REPLACED, MAINTAIN WIRING, REFER TO DRAWINGS ES-101-M.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
J
J
J
J
J
JJ
J
DB
J
J
SD
F
J
J
J
J
J
J
J
J
J J
JJ
J
J
J
J
F
DB
J
J J
J
J
J
J
J
OC
J
J
J
J
J
JJ
J
J
J
JJ
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
1
OO
O
O
O
OO
O O OO O
O
O
O
OO OOO
O
OO
EXISTING LP-3A
EXISTING RP-3BEXISTING LP-3B
+72CLOCK
H
+72CLOCK
H
2
2
2
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:3
9 A
M
ED-103
THIRD FLOOR DEMOLITION -
ELECTRICAL
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R
HT
1/8" = 1'-0"1 THIRD FLOOR DEMOLITION - ELECTRICAL
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
KEYNOTES:
1. FIXTURE TO BE RELOCATED, REFER TO SHEET EL-103. REMOVE BRANCH CIRCUIT BACK TO SOURCE.
2. DEVICE WILL BE REPLACED, MAINTAIN WIRING, COORDINATE WORK WITH FACILITY FIRE DEPARTMENT AND FIRE ALARM VENDOR BEFORE START OF WORK. REFER TO DRAWING ES-103.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
013.1
013.2 005.4
005.3
005.2
005.1005
023.1
sound
booth
#2
sound
booth
#1
sound
booth
#1
sound
booth
#2
sound
booth
#1
sound
booth
#1
future sound
booth
Office
Office Office
SupervisorOffice
LabStorage
Hearing AidFitting
Lab
Lab
001
013
015
040
030
030
007
020
014
012
029
031
002004
006.4
006.3
006.2
006008010
016.31
016.4
016.3
016.2
016
016.10
016.11
019017021
023
025
027
STAIR
Lab
Lab
STAIR
STAIR
C&IT
Storage
Storage
EngOffice
Jan
Men
Women
ClassroomClassroom
Office
Office
Office
OfficeClassroomClassroom
Mech
Mech
Mech
Mech
Mech
Tele
PLC
ClassroomClassroom ComputerLab
Lab
Lab
Teaching Lab
OC
OC
OC
OC
OC
{LS1}
{LS1}
{LS1}
{LS1}
{LS1}
{LS1}
{LS1}
{LS1}
{LS1}
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
OM
O
O
1
1
1
1
12
2
M
2
M
2
2
2
O
O
O
O
1
1
1
1
1
1
3
3
3
3
3
3
4
4
4
4 4
4
1
EM1
F1
5
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
1 A
M
EL-101-B
BASEMENT FLOOR - LIGHTING
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR - LIGHTING
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
KEYNOTES:
1. RELOCATED 2-LAMP PARABOLIC FIXTURES, EXTEND EXISTING BRANCH CIRCUIT. CLEAN AND RELAMP FIXTURE.
2. MODIFY LIGHTING CONTROLS AS REQUIRED FOR NEW DEVICES.
3. CLEAN AND RELAMP LIGHT FIXTURES IN THIS ROOM.
4. RELOCATED PRE-WIRED EXISTING SOUND BOOTH.
5. EXTEND UNSWITCHED PORTION OF BRANCH CIRCUIT SERVING THIS ROOM TO EMERGENCY FIXTURE.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
SHEET NOTES :
1. REPLACE LAMPS AND BATTERIES IN EXISTING EXIT SIGNS AND EMERGENCY BATTERY UNITS.
100.1100.2
100
103.2 103.1
103
103.5103.4103.3
BASEMENTFLOOR BELOW
ELEV
BASEMENTFLOOR BELOW
SECONDFLOOR ABOVE
EXTERIORCIRCULATION
DN
DN
DN
UP
MechJan
Lounge
UP
Lobby
Mech
Office Office
Recept
OfficeOfficeStorage
UP DNUP
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
O O O
OO
1 1 1
1
1 1
EM12
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
0 A
M
EL-101
FIRST FLOOR PLAN - LIGHTING
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R HT
1/8" = 1'-0"1 FIRST FLOOR PLAN - LIGHTING
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
KEYNOTES:
1. CLEAN AND RELAMP 2-LAMP PARABOLIC FIXTURES IN THIS ROOM.
2. EXTEND UNSWITCHED PORTION OF BRANCH CIRCUIT SERVING THIS ROOM TO EMERGENCY FIXTURE.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
Ref
102
102.1
105.1105.2
105.5105.4105.3
105
DN
Lounge
Jan
DN
UP
Open to Below
Elev
UPDNDN
OfficeOffice
OfficeOfficeWorkRoom
OpenOffice
Open to Below
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
O O O
O O
1 1 1
1
1 1
EM12
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
1 A
M
EL-101-M
MEZZANINE FLOOR PLAN -
LIGHTING
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R
HT
1/8" = 1'-0"1 MEZZANINE FLOOR PLAN - LIGHTING
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
KEYNOTES:
1. CLEAN AND RELAMP 2-LAMP PARABOLIC FIXTURES IN THIS ROOM.
2. EXTEND UNSWITCHED PORTION OF BRANCH CIRCUIT SERVING THIS ROOM TO EMERGENCY FIXTURE.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
327
325
328.10
328.09
328.08
328
328.07
328.06
328.05
328.04
328.03
328.02
328.01
326
322.1
300.01
303
304 300.02 300.03
300.04
300
300.11 300.07
300.06
300.05
300.08
300.09300.1
Treatment
Observation
WorkRoom
Office
Office
OpenOffice
Office
COPY
Office
Office
Office
Office
Office
WOMEN'SRESTROOM
UNISEX ADARESTROOM
WORKROOM
Office
TEACHINGLAB Office Office
Office
OpenOffice
OpenOffice Office
Observation
Treatment
Office
TreatmentObservation
MECHANICAL AREA
MECH SHAFT
MECH
DNDN
COOLING TOWER
NIC
305
301
ELEV
NIC NIC NIC NIC
NIC NIC
NIC
NIC
NIC NIC NIC NIC NIC NIC NIC NIC
NIC
NIC
OC OC
OC
OCOC
{LS1}
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
M2 O O O
OO
O
O
M
11
M
M
22
2
O
O
3
22
22
2
2
3EM1
EM1
EM1
EM1
EM1
EM1
EM1 EM1
3
3
3
3 3
3
3
3
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
2 A
M
EL-103
THIRD FLOOR PLAN - LIGHTING
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R
HT
1/8" = 1'-0"1 THIRD FLOOR PLAN - LIGHTING
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
KEYNOTES:
1. RELOCATED FIXTURE. EXTEND BRANCH CIRCUITS FROM ADJACENT FIXTURES. MODIFY WIRING WITH NEW CONTROLS SO THAT ALL FIXTURES ARE SWITCHED TOGETHER.
2. MODIFY WIRING AS REQUIRED IN THIS ROOM FOR NEW CONTROLS.
3. EXTEND UNSWITCHED PORTION OF BRANCH CIRCUIT SERVING THIS ROOM TO EMERGENCY FIXTURE.
#
SHEET NOTES :
1. CLEAN AND RELAMP 2-LAMP PARABOLIC FIXTURES INDICATED IN AREAS OF WORK. CLEAN AND RELAMP FIXTURES IN RESTROOMS.
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
013.1
013.2 005.4
005.3
005.2
005.1005
023.1
sound
booth
#2
sound
booth
#1
sound
booth
#1
sound
booth
#2
sound
booth
#1
sound
booth
#1
future sound
booth
Office
Office Office
SupervisorOffice
LabStorage
Hearing AidFitting
Lab
Lab
001
013
015
040
030
030
007
020
014
012
029
031
002004
006.4
006.3
006.2
006008010
016.31
016.4
016.3
016.2
016
016.10
016.11
019017021
023
025
027
STAIR
Lab
Lab
STAIR
STAIR
C&IT
Storage
Storage
EngOffice
Jan
Men
Women
ClassroomClassroom
Office
Office
Office
OfficeClassroomClassroom
Mech
Mech
Mech
Mech
Mech
Tele
PLC
ClassroomClassroom ComputerLab
Lab
Lab
Teaching Lab
E E E E
E E E E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
EXISTING RP-BD
A
A
A
SOUNDBOOTH
A
A
A
A
A
A
A
PUMP (SP-001)
EXISTING MCC
EXISTING LP-BC
EXISTING EMERGENCY
LP-E
EXISTING MASTER
CLOCK & PROGRAM
MACHINE
EXISTING LP-BB
EXISTING LP-BA
C
C
C
C
EXISTING DP-1
EXISTING SB-1
+72
CLOCK
+72CLOCK
+72
CLOCKEXISTING RP-BG
EXISTING RP-BH
EXISTING RP-BF
EXISTING SECURITY
CONTROL PANELS
EXISTING SECURITY
CONTROL PANELS
1
1
96"
2
SOUNDBOOTH
96"
3
SOUNDBOOTH96"
4
5
6
7
8
SOUNDBOOTH96"
SOUNDBOOTH96"
SOUNDBOOTH96"
9
10
10
11
12
13 13
10
14
14
14
14
14
14
141414
14
14
14
14
A A A
13
14
A1314A
SOUNDBOOTH96"9
PUMP (SP-001)
15
VAV-B-6
VAV-B-4
VAV-B-5
VAV-B-3
VAV-B-8
VAV-B-7
VAV-B-2
VAV-B-1
16
16
16
17
17
18
20
19
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
4 A
M
EP-101-B
BASEMENT FLOOR - POWER
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR - POWER
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
10. CIRCUIT TO SPARE 20A BREAKER IN PANEL RP-BD.
11. CIRCUIT RECEPTACLES IN THIS ROOM TO SPARE 20A BREAKER IN PANEL RP-BH, U.N.O.
12. CIRCUIT NEW RECEPTACLES IN THIS ROOM TO SPARE 20A BREAKER IN PANEL RP-BH.
13. CIRCUIT NEW RECEPTACLES IN THIS ROOM TO SPARE 20A BREAKER IN PANEL RP-BD.
14. PROVIDE SURFACE RACEWAY FOR RECEPTACLES INDICATED, REFER TO DETAIL 2 ON SHEET EP-300.
15. CIRCUIT TO SPARE 20A BREAKER IN PANEL RP-BG.
16. CIRCUIT VAV CONNECTIONS TO SPARE 20A BREAKER IN PANEL RP-BG.
17. CIRCUIT VAV CONNECTIONS TO SPARE 20A BREAKER IN PANEL LP-BB.
KEYNOTES:
1. CIRCUIT RECEPTACLES IN THIS ROOM TO SPARE 20A BREAKER IN PANEL LP-BB.
2. CIRCUIT TO SPARE 20A BREAKER IN PANEL LP-BA.
3. CIRCUIT TO SPARE 20A BREAKER IN PANEL RP-BF.
4. CIRCUIT TO SPARE 20A BREAKER IN PANEL RP-BG.
5. EXTEND EXISTING CIRCUIT TO NEW RECEPTACLES.
6. CIRCUIT RECEPTACLES IN THIS ROOM TO SPARE 20A BREAKER IN PANEL RP-BF.
7. CIRCUIT RECEPTACLES TO SPARE 20A BREAKER IN PANEL RP-BF.
8. CIRCUIT RECEPTACLES IN THIS ROOM TO SPARE 20A BREAKER IN PANEL RP-BG, U.N.O.
9. CIRCUIT TO SPARE 20A BREAKER IN PANEL RP-BH.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
18. CIRCUIT VAV CONNECTION TO SPARE 20A BREAKER IN PANEL LP-BA.
19. CIRCUIT VAV CONNECTION TO SPARE 20A BREAKER IN PANEL RP-BH20. CIRCUIT VAV CONNECTION TO SPARE 20A BREAKER IN PANEL RP-BD.
100.1100.2
100
103.2 103.1
103
103.5103.4103.3
BASEMENTFLOOR BELOW
ELEV
BASEMENTFLOOR BELOW
SECONDFLOOR ABOVE
EXTERIORCIRCULATION
DN
DN
DN
UP
MechJan
Lounge
UP
Lobby
Mech
Office Office
Recept
OfficeOfficeStorage
UP DNUP
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
EXISTING LP-1A
EXISTING LP-1B
FAP-1
VCC-11
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
3 A
M
EP-101
FIRST FLOOR PLAN - POWER
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R HT
1/8" = 1'-0"1 FIRST FLOOR PLAN - POWER
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
KEYNOTES:
1. CIRCUIT FAP-1 AND VCC-1 TO LP-E.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
Ref
102
102.1
105.1105.2
105.5105.4105.3
105
DN
Lounge
Jan
DN
UP
Open to Below
Elev
UPDNDN
OfficeOffice
OfficeOfficeWorkRoom
OpenOffice
Open to Below
J
J
J
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
A
COFFEE
MICROWAVE
REFRIGERATOR
/+72CLOCK
1
2
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
5 A
M
EP-101-M
MEZZANINE FLOOR PLAN -
POWER
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R HT
1/8" = 1'-0"1 MEZZANINE FLOOR PLAN - POWER
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
KEYNOTES:
1. CONNECT TO EXISTING CIRCUIT.2. PROVIDE SURFACE RACEWAY FOR
RECEPTACLE, REFER TO DETAIL 2 ON SHEET EP-300. CIRCUIT TO SPARE BREAKER IN LP-1A.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
327
325
328.10
328.09
328.08
328
328.07
328.06
328.05
328.04
328.03
328.02
328.01
326
322.1
300.01
303
304 300.02 300.03
300.04
300
300.11 300.07
300.06
300.05
300.08
300.09300.1
Treatment
Observation
WorkRoom
Office
Office
OpenOffice
Office
COPY
Office
Office
Office
Office
Office
WOMEN'SRESTROOM
UNISEX ADARESTROOM
WORKROOM
Office
TEACHINGLAB Office Office
Office
OpenOffice
OpenOffice Office
Observation
Treatment
Office
TreatmentObservation
MECHANICAL AREA
MECH SHAFT
MECH
DNDN
COOLING TOWER
NIC
305
301
ELEV
NIC NIC NIC NIC
NIC NIC
NIC
NIC
NIC NIC NIC NIC NIC NIC NIC NIC
NIC
NIC
J
J
J
J
J
JJ
J
DB
J
J
J
J
J
J
J
J
J
J J
JJ
J
J
DB
J
J
J
J
J
J
J
J
J
J
J
J
JJ
J
J
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
PROJECTOR
C
EXISTING LP-3A EXISTING LP-3B
H
R
R
R
CLOCK
+72
H
+72
A
A
EXISTING RP-3B
H
H
A A A A
A
A A A
A
A 1
22
1
1
3
3
44
4
4
4
4
1
1 4
4
5 WATER HEATER (WH-1)
6
INTERCOM POWER SUPPLY
VAV-3-1
7
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
6 A
M
EP-103
THIRD FLOOR PLAN - POWER
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R
HT
1/8" = 1'-0"1 THIRD FLOOR PLAN - POWER
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
KEYNOTES:
1. EXTEND EXISTING BRANCH CIRCUIT TO NEW RECEPTACLE.
2. CIRCUIT (2) QUADS EACH TO A SPARE 20A BREAKER IN PANEL LP-3B.
3. CIRCUIT (3) RECEPTS EACH TO A SPARE 20A BREAKER IN PANEL LP-3B.
4. PROVIDE SURFACE RACEWAY FOR RECEPTACLES. REFER TO DETAIL 2 ON SHEET EP-300.
5. CIRCUIT WATER HEATER TO SPARE 20A BREAKER IN PANEL LP-3B.
6. CIRCUIT RECEPTACLE TO SPARE 20A BREAKER IN PANEL LP-3B.
7. CIRCUIT VAV CONNECTION TO SPARE 20A BREAKER IN PANEL LP-3B.
#
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
SEE ARCHITECTURALPLANS FOR WALL CONSTRUCTION
PLASTER RING TO COMEWITHIN 1/8" OF FINAL SURFACE
STUD
MOUNTING BRACKET SHALL PROVIDESUPPORT FROM STUD AND BACK OFWALL OR TWO STUDS.
NOTES :
1. THE INTENT OF THE DETAIL IS TO ENSURE DEVICE ROUGH-INS ARE ALIGNED, SOLIDLY MOUNTED AND THE SURFACE OF THE TRIM IS EITHER FLUSH WITH THE WALL SURFACE OR WITHIN 1/8" OF THE WALL SURFACE. JUNCTION BOXES LARGER THAN 4" SQUARE SHALL BE MOUNTED IN A MANNER THAT IS SIMILAR TO THE SYSTEM NOTED ABOVE OR ACHIEVES THE SAME RESULTS.
2. PLASTER RINGS DEPTH SHALL BE 1/8" DEEPER THAN THE GYP BOARD APPLIED TO THE WALL. PLASTER RING SHALL BE 3/4" FOR USE WITH 5/8" GYP BOARD.
3. MOUNTING BRACKET FOR 2 1/2" OR 3 1/2" STUDS SHALL BE CADDY #H23, OR B-LINE BB4-23. MOUNTING BRACKET FOR FOR 4" OR 6" STUDS SHALL BE CADDY #H46TC OR B-LINE BB4-# . FOR MULTIPLE BOXES BETWEEN STUDS, BRACKET SHALL BE CADDY #RBS16/#RBS24 OR B-LINE BB6-# OR BBF# FLOOR MOUNT SUPPORT WITH BBFC.
4. WHERE RECEPTACLE AND TECHNOLOGY DEVICES ARE SHOWN SERVING A COMMON COMPUTER OR EQUIPMENT, OR SHOWN IN SIMILAR LOCATIONS ON THE DRAWINGS THE DEVICES SHALL BE INSTALLED ON OPPOSITE SIDES OF A COMMON STUD OR IN ADJACENT OPENINGS WITH MOUNTING BRACKETS.
RATED WALL (CONSTRUCTION VARIES)
NOTE 2
FIRE SEALANT
NOTE 3
FIRE SEALANT
PENETRATING ITEM
NOTE 4
NOTE 3
NOTE 2
PENETRATING ITEM
NOTE 4
NOTE 3
RATED FLOOR (CONSTRUCTION VARIES)
NOTES :
1. THIS GENERAL DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL MOVEMENT. REFER TO SPECIFICATION SECTION 07840 (16080) FOR SELECTION OF THROUGH PENETRATION FIRE STOPPING.
2. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL. EACH CONTRACTOR FURNISHES SLEEVE TO G.C., COORDINATES SLEEVE LOCATIONS AND DEBURS SLEEVE. G.C. BUILDS SLEEVE INTO WALL OR FLOOR ALLOWING NO GAP AROUND SLEEVE. IF SLEEVE IS NOT PROVIDED WHEN WALL OR FLOOR IS BUILT, CONTRACTOR SHALL INSTALL SLEEVE. SLEEVE SIZE SHALL ALLOW ANNULAR SPACE REQUIRED BY THE SELECTED FIRE STOP SYSTEM.
3. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION LISTING. SECURE TO WALL OR FLOOR TO ALLOW LONGITUDINAL MOVEMENT OF PENETRATING ITEM WITHOUT MOVEMENT OF FIRE BARRIER.
4. WATER-TIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET METAL ANGLE FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF WATERPROOF SEALANT BETWEEN FLOOR AND BOTTOM OF ANGLE FRAME. SECURE TO FLOOR WITH MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS. MULTIPLE PENETRATING ITEMS MAY BE ENCLOSED IN ONE FRAME.
DUPLEX RECEPTACLE(DESIGNATED ON PLANS)
1 1/4" TELECOMM CONDUIT(S) AS REQUIRED
BRANCH CIRCUIT CONDUIT(S)
SURFACE RACEWAY TOABOVE ACCESSIBLE CEILING
WW-#4 3/4" HIGH X 1 3/4" DEEP SURFACEMETAL RACEWAY WITH LOW VOLTAGE DIVIDER.LENGTH AS SHOWN ON DRAWINGS.
TR
CLASS II LOW VOLTAGE TRANSFORMER, WITH PRIMARY AND SECONDARY FUSING. MOUNT IN NEMA 1 ENCLOSURE ABOVE ACCESSIBLE CEILING.
H
GND
2#14 & 1#14 GND IN 1/2" FLEXFOR LOW VOLTAGE CLASS IIWIRING TO CONTROL MODULES.
MOUNTED ONWALL, BEHINDWATER CLOSET.
MAXIMUM OF SIX MODULESPER TRANSFORMER. MAXIMUM 50' WIRING LENGTH.
LOW VOLTAGESOLENOID VALVE.
WATER CLOSET LOWVOLTAGE SENSOR /CONTROL
N
NOTES :
1. PROVIDE DOUBLE GANG BACKBOXES AND PLASTER RINGS AT LOCATIONS COORDINATED WITH PLUMBING CONTRACTOR (P.C.)
2. E.C. SHALL FIELD VERIFY EXACT SENSOR LOCATION WITH P.C. PRIOR TO ROUGH-IN.
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
6 A
M
EP-300
POWER DETAILS
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
NO SCALE1 BACKBOX MOUNTING DETAIL
NO SCALE3 FIRE BARRIER PENETRATION
NO SCALE2 SURFACE WIREWAY DETAIL
Owner Review 60% CD's Nov. 13, 2018
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
NO SCALE4 ELECTRONIC SENSOR WIRING
013.1
013.2 005.4
005.3
005.2
005.1005
023.1
sound
booth
#2
sound
booth
#1
sound
booth
#1
sound
booth
#2
sound
booth
#1
sound
booth
#1
future sound
booth
Office
Office Office
SupervisorOffice
LabStorage
Hearing AidFitting
Lab
Lab
001
013
015
040
030
030
007
020
014
012
029
031
002004
006.4
006.3
006.2
006008010
016.31
016.4
016.3
016.2
016
016.10
016.11
019017021
023
025
027
STAIR
Lab
Lab
STAIR
STAIR
C&IT
Storage
Storage
EngOffice
Jan
Men
Women
ClassroomClassroom
Office
Office
Office
OfficeClassroomClassroom
Mech
Mech
Mech
Mech
Mech
Tele
PLC
ClassroomClassroom ComputerLab
Lab
Lab
Teaching Lab
F FF
F
HD
SD
AH
AH
A1 A3
A1
A7
A1A1 A1
A1 A1A1
A1
A1A1
A7 A7 A7
A7
A7
A7
A1
V1
V1
A1
V1
A7 A7 A7 A7
A1
V1
A7
A3
A3
A3
A1
A1
MM
MM
AR
A1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
?
SPRINKLERFLOW ANDTAMPER
RECALL
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
8 A
M
ES-101-B
BASEMENT FLOOR - SYSTEM
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR - SYSTEM
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
100.1100.2
100
103.2 103.1
103
103.5103.4103.3
BASEMENTFLOOR BELOW
ELEV
BASEMENTFLOOR BELOW
SECONDFLOOR ABOVE
EXTERIORCIRCULATION
DN
DN
DN
UP
MechJan
Lounge
UP
Lobby
Mech
Office Office
Recept
OfficeOfficeStorage
UP DNUP
F
F
A3A1
SD
A1
FF
F F
FF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
FAA-1
FAP-1
VCC-1
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
7 A
M
ES-101
FIRST FLOOR PLAN - SYSTEMS
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R HT
1/8" = 1'-0"1 FIRST FLOOR PLAN - SYSTEMS
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
Ref
102
102.1
105.1105.2
105.5105.4105.3
105
DN
Lounge
Jan
DN
UP
Open to Below
Elev
UPDNDN
OfficeOffice
OfficeOfficeWorkRoom
OpenOffice
Open to Below
F
A3
V1
A3
SD
A1
F
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
8 A
M
ES-101-M
MEZZANINE FLOOR PLAN -
SYSTEMS
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R HT
1/8" = 1'-0"1 MEZZANINE FLOOR PLAN - SYSTEMS
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
327
325
328.10
328.09
328.08
328
328.07
328.06
328.05
328.04
328.03
328.02
328.01
326
322.1
300.01
303
304 300.02 300.03
300.04
300
300.11 300.07
300.06
300.05
300.08
300.09300.1
Treatment
Observation
WorkRoom
Office
Office
OpenOffice
Office
COPY
Office
Office
Office
Office
Office
WOMEN'SRESTROOM
UNISEX ADARESTROOM
WORKROOM
Office
TEACHINGLAB Office Office
Office
OpenOffice
OpenOffice Office
Observation
Treatment
Office
TreatmentObservation
SD
F FA7
V1
V1
A3
A3
A3
A1
A1 A1
A1
A
A
V1
A1
A1
AH
A1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
9 A
M
ES-103
THIRD FLOOR PLAN - SYSTEMS
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
NO R
HT
1/8" = 1'-0"1 THIRD FLOOR PLAN - SYSTEMS
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
J
NEPCI
CI
CI
CIC
I
NETWORK CONNECTIONSEE SPECIFICATIONS
SIGNAL LINE CIRCUIT (SLC)
NOTIFICATION APPLIANCE CIRCUIT (NAC)
EVACUATION - SIGNALING ZONE #
NOTIFICATION APPLIANCE CIRCUIT (NAC)
FAA-1
NEW FAP-1
VCC-1
SIGNAL LINE CIRCUIT(SLC)
CIRCUIT INTEGRITY WIRING. (TYPICAL)
MM
AR TO ELEVATOR SHUNT TRIP BREAKER
MM
MM
MS
FS
F FT H SD
2 31
SD MM
HF
MM
HX
V
A
F
2
J
V1 V1 V11
3
A A MH HW
A1 A11 A11
KEYNOTES:
PROVIDE NOTIFICATION APPLIANCE EXTENDER PANELS AS REQUIRED. DETERMINATION OF NEED TO BE MADE BY FIRE ALARM VENDOR. REFER TO SPECIFICATIONS FOR REQUIREMENTS AND ACCEPTABLE MOUNTING LOCATIONS.
REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH INITIATION LOOP AND WIRING STYLE. REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.
REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH NOTIFICATION APPLIANCE CIRCUIT AND WIRING STYLE. REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.
1
2
3
NOTES :
1. THE RISER DIAGRAM IS INTENDED TO CONVEY THE TYPES OF FIRE ALARM CONNECTIONS AND SPECIFICALLY DOES NOT INDICATE QUANTITIES, NUMBER OF CIRCUITS REQUIRED OR DISTANCES.
2. THE COMPLETE FIRE ALARM SYSTEM SHALL MEET ALL APPLICABLE CODES AND MANUFACTURER'S RECOMMENDATIONS.
3. CONTRACTOR SHALL COORDINATE ALL WIRE SIZES, TYPES AND REQUIREMENTS WITH THE VENDOR PRIOR TO BID. REFER TO SPECIFICATIONS TO DETERMINE CIRCUIT STYLES AND IF CONDUIT IS REQUIRED OR PLENUM RATED CABLE IS ACCEPTABLE.
4. ALL +120VAC WIRING REQUIRED FOR OPERATION OF THE SYSTEM AS DESCRIBED IN THE CONSTRUCTION DOCUMENTS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.
5. ALL NECESSARY RELAYS MAY NOT BE SHOWN ON THIS PLAN, BUT WHERE REQUIRED FOR PROPER OPERATION OF THE SYSTEM THEY SHALL BE PROVIDED BY THE CONTRACTOR.
6. PARTIAL EVACUATION OR RELOCATION OF OCCUPANTS IS THE STANDARD OPERATING PROCEDURE FOR THIS FACILITY IN THE EVENT OF AN ALARM. THEREFORE, ALL NOTIFICATION APPLIANCE CIRCUITS MUST BE INSTALLED AND PROTECTED IN ACCORDANCE WITH THE CIRCUIT SURVIVABILITY REQUIREMENTS DESCRIBED IN NFPA 72. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
7. PROVIDE CONNECTIONS FOR WORK ON SECOND FLOOR (NIC), COORDINATE WITH OWNER.
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:0
9:4
9 A
M
ES-300
SYSTEM DETAILS
JEFGLAJALJAL
MARABR
18004050.00
JALJAL
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
JALJAL
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
NO SCALE1 FIRE ALARM RISER
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
TECHNOLOGY SYMBOL LIST
SYMBOL: DESCRIPTION: NOTE:EQUIPMENT
LIST ABBREV.:
C#
C#1.INFORMATION OUTLET (CEILING)SC-IO-C
1.INFORMATION OUTLET (WALL)SC-IO-W
.EXISTING INFORMATION OUTLET (WALL)N/A
WAP .EXISTING WIRELESS ACCESS POINT DEVICE (CEILING)N/A
C .EXISTING CLOCK (WALL)N/A
CR .EXISTING CREDENTIAL READERN/A
KP EXISTING KEYPADN/A .
IS1
IM1 .INTERCOM MASTER STATION - TYPE 1 (WALL)IC-IM1-W
.INTERCOM STATION - TYPE 1 (WALL)IC-IS1-W
TECHNOLOGY ABBREVIATION KEY
TELECOMMUNICATIONS ROOMTR-#
ABOVE FINISHED FLOORAFF
BELOW FINISHED CEILINGBFC
CONDUITC
SIMILARSIM
TYPICALTYP
MOUNTING HEIGHT ABOVE FINISHED FLOOR+#
JUNCTION BOXJ-BOX
ABBR: DESCRIPTION:
UNLESS NOTED OTHERWISEUNO
TECHNOLOGY GENERAL NOTES:1. ###-### INDICATES GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ITEM LABELED AS
"EQUIPMENT LIST ABBREVIATION"2. REFER TO GENERAL TECHNOLOGY EQUIPMENT SCHEDULE AND SPECIFICATIONS FOR FULL
DESCRIPTIONS AND MANUFACTURERS OF ALL DEVICES.
TECHNOLOGY MOUNTING SUBSCRIPT KEY:A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASHH MOUNT ORIENTED HORIZONTALLYL MOUNT IN CASEWORKM MOUNT IN MODULAR FURNITURES MOUNT IN SURFACE RACEWAY
A SLASH IS USED BETWEEN TWO SUBSCRIPTS, E.G., A/H.
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON THIS PAGE FOR ADDITIONAL INFORMATION.
2. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, IN FLOOR SLAB, ETC. UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT IN MECHANICAL ROOMS AND STORAGE ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON BUILDING STRUCTURE.
3. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE OFFSET A MINIMUM OF 6" HORIZONTALLY. BOXES ON OPPOSITE SIDES OF FIRE RATED WALLS SHALL BE OFFSET A MINIMUM OF 24" HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.
4. VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL TELECOMMUNICATIONS INSTALLATION, ADJUST OUTLETS OR CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE AND/OR EQUIPMENT.
5. TELECOMMUNICATIONS EQUIPMENT SHALL BE MOUNTED TO ALLOW ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF TELECOMMUNICATION DEVICES ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR SHALL BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR SEALED INTO OPENINGS.
7. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
8. REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE EXECUTION OF TELECOMMUNICATIONS WORK THAT IS OUTSIDE THE CONTRACT LIMITS OF CONSTRUCTION. REPLACE CEILING TILES WITH IDENTICAL MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.
9. FLUSH MOUNT ALL TELECOMMUNICATION OUTLETS AT +18" FROM FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.
10. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: LIGHTING SWITCHES 4'-0" RECEPTACLES (GENERAL AREAS) 1'-6" RECEPTACLES (UTILITY AREAS) 4'-0" TELECOMMUNICATION OUTLETS 1'-6" WALL PHONE 4'-0" FIRE ALARM STATIONS 4'-0" FIRE ALARM SIGNALS 7'-6" CLOCKS/CLOCK OUTLETS 1’-6” BELOW FIN. CEIL. SAFETY SWITCHES 5'-0" TO TOP
TECHNOLOGY INSTALLATION NOTES:
GENERAL NOTES:
1. ALL SYMBOLS AND ABBREVIATIONS LISTED MAY NOT BE APPLICABLE TO THIS PROJECT. REFER TO THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE COMPLETE DESCRIPTION AND ITEMS.
2. ALL SYMBOLS AND ABBREVIATIONS REFER TO TECHNOLOGY SHEETS ONLY AS DEFINED ON THE SHEET INDEX. REFER TO THE GENERAL TECHNOLOGY NOTES FOR ADDITIONAL INFORMATION.
3. ALL SYMBOLS LISTED ABOVE ARE FOR REFERENCE ONLY. REFER TO PLANS AND LINE TYPE KEY FOR NEW, EXISTING TO REMAIN AND TO BE REMOVED ITEMS FOR ADDITIONAL INFORMATION.
TECHNOLOGY SYMBOL NOTES:
1. "C#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION. REFER TO INFORMATION OUTLET SCHEDULE ON T-200 FOR ADDITIONAL INFORMATION.
DIAMETERø C CONDUIT
CONDUIT DOWN
CONDUIT UP OR UP/DOWN
CONDUIT SLEEVE
CONTINUATION
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
NAME
1VIEW NAME1/8" = 1'-0"
LEVEL NAME
10' - 0" HEIGHT ABOVE PROJECT 0' - 0"
1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL
NO R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
LINE TYPE KEY:
BUILDING CODE: MBC 2015 EDITION
FIRE CODE: NFPA 13: 2013 EDITION
PLUMBING CODE: MBC 2015 EDITION
MECHANICAL CODE: MMC 2015 EDITION
ELECTRICAL CODE: NFPA 70 (NEC) 2016EDITION
LIFE SAFETY CODE: NFPA 101 2015 EDITION
ENERGY CONSERVATION CODE: ASHRAE 90.1 2013
HEALTH DEPARTMENT CODE: CURRENT EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
ASBESTOS ABATEMENT CONTRACTOR
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
48
" M
AX
.
20" MAX.
44
" M
AX
.
20"-25" MAX.
48
" M
AX
.
15
" M
IN. 48
" M
AX
.
46
" M
AX
.
10" MAX. 10"-24" MAX.
ADA GUIDELINES - FRONT ACCESS
ADA STANDARDS FOR ACCESSIBLE DESIGN
INSTALL ABOVE COUNTER DEVICE AT 44" ABOVE FINISHED FLOOR.
INSTALL ABOVE COUNTER DEVICE AT 40" ABOVE FINISHED FLOOR.
INSTALL DEVICE AT 18" ABOVE FINISHED FLOOR.
ADA GUIDELINES - SIDE ACCESS
INSTALL DEVICE AT 44" ABOVE FINISHED FLOOR.
INSTALL DEVICE AT 42" ABOVE FINISHED FLOOR.
TECHNOLOGY SHEET INDEXT-000 TECHNOLOGY COVERSHEET
TD-101-B BASEMENT FLOOR DEMOLITION - TECHNOLOGY
TD-103 THIRD FLOOR DEMOLITION - TECHNOLOGY
T-101-B BASEMENT FLOOR - TECHNOLOGY
T-101 FIRST FLOOR PLAN - TECHNOLOGY
T-103 THIRD FLOOR PLAN - TECHNOLOGY
T-200 TECHNOLOGY DETAILS, RISERS AND SCHEDULES
SUGGESTED MATRIX OF RESPONSIBILITY
ITEM: SHOWN ON:FURNISHED
BY:INSTALLED
BY: NOTES:
TECHNOLOGY ROUGH-IN, REFER TOGENERAL TECHNOLOGY EQUIPMENTSCHEDULE AND SPECIFICATIONS FORDEFINITION
T-SERIES E.C. E.C. 3. 4.
INFORMATION OUTLET FACEPLATES,JACKS, AND TERMINATIONS
T-SERIES T.C. T.C.
CONDUIT SLEEVES (WHEN SHOWN ONDRAWINGS)
T-SERIES E.C. E.C.
CONDUIT SLEEVES (NOT SHOWN BUTREQUIRED FOR PROPER INSTALLATIONOF SYSTEM)
N/A T.C. T.C. 2. 4.
TELECOMMUNICATION SYSTEMSROUGH-IN
T-SERIES E.C. E.C. 1.
TELECOMMUNICATION EQUIPMENT,CABLING, AND TERMINATIONS
T-SERIES T.C. T.C.
GROUNDING LUGS ON TECHNOLOGYEQUIPMENT
T-SERIES T.C. E.C. 6.
LINE VOLTAGE POWER (+120V ORGREATER)
E-SERIES E.C. E.C.
LINE VOLTAGE POWER (NOT SHOWNBUT REQUIRED FOR PROPERINSTALLATION OF SYSTEM)
N/A T.C. E.C. 2. 4.
LOW VOLTAGE CABLING FORTECHNOLOGY SYSTEMS
T-SERIES T.C. T.C.
CABLE HANGERS AND SUPPORTS OROTHER CABLE ROUTING METHODS(OTHER THAN CONDUIT AND CABLETRAY)
T-SERIES T.C. T.C. 5.
FLOOR BOX (ROUGH-IN) T & E SERIES E.C. E.C.
SUGGESTED MATRIX OF RESPONSIBILITY NOTES
1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATIONOUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FORADDITIONAL INFORMATION.
2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALLREQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLEMANUFACTURERS.
3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMSINSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THECONTRACT DOCUMENTS.
4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OFTHE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEMCONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE CONTRACTOR SHALL BE INCLUDEDIN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN.
5. UNLESS TRADE RULES DICTATE OTHERWISE.
6. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FORINSTALLATION IN THE FIELD.
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:1
1:5
8 A
M
T-000
TECHNOLOGY COVERSHEET
JEFGILTIMADA
POOVYA
18004050.00
TIMADA
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
TIMADA
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
001
013
015
040
030
030
007
020
014
012
029
031
002004
006.4
006.3
006.2
006008010
016.31
016.4
016.3
016.2
016
016.10
016.11
019017021
023
025
027
STAIR
Lab
Lab
STAIR
STAIR
C&IT
Storage
Storage
EngOffice
Jan
Men
Women
ClassroomClassroom
Office
Office
Office
OfficeClassroomClassroom
Mech
Mech
Mech
Mech
Mech
Tele
PLC
ClassroomClassroom ComputerLab
Lab
Lab
Teaching Lab
CRC
C
C
WAP
CR
KP
CR
KP
C
C
WAP
C
C
CR
KPKP
WAP
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
EXISTING TELECOM ROOM
EXISTING
EQUIPMENT
RACK TYP.
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:1
2:0
2 A
M
TD-101-B
BASEMENT FLOOR DEMOLITION
- TECHNOLOGY
JEFGILTIMADA
POOVYA
18004050.00
TIMADA
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
TIMADA
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR DEMOLITION - TECHNOLOGY
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
GENERAL NOTES :
1. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND LINE TYPE KEY.
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
C
WAP
WAP
CR
WAP
CR
WAP
WAP
C
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
EXISTING TELECOM ROOM
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:1
2:0
3 A
M
TD-103
THIRD FLOOR DEMOLITION -
TECHNOLOGY
JEFGILTIMADA
POOVYA
18004050.00
TIMADA
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
TIMADA
NO R
HT
1/8" = 1'-0"1 THIRD FLOOR DEMOLITION - TECHNOLOGY
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
GENERAL NOTES :
1. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND LINE TYPE KEY.
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
013.1
013.2 005.4
005.3
005.2
005.1005
023.1
sound
booth
#2
sound
booth
#1
sound
booth
#1
sound
booth
#2
sound
booth
#1
sound
booth
#1
future sound
booth
Office
Office Office
SupervisorOffice
LabStorage
Hearing AidFitting
Lab
Lab
D0
01
.1
D0
01
.2
D0
01
.3
D0
01
.6
D0
01
.5
D0
01
.4
D013.2
D013.2
D0
23
.1
D0
25
D0
30
D0
05
.2D005.1
D005.4
D005.3
D040
001
013
015
040
030
030
007
020
014
012
029
031
002004
006.4
006.3
006.2
006008010
016.31
016.4
016.3
016.2
016
016.10
016.11
019017021
023
025
027
STAIR
Lab
Lab
STAIR
STAIR
C&IT
Storage
Storage
EngOffice
Jan
Men
Women
ClassroomClassroom
Office
Office
Office
OfficeClassroomClassroom
Mech
Mech
Mech
Mech
Mech
Tele
PLC
ClassroomClassroom ComputerLab
Lab
Lab
Teaching Lab
C2-1
C2-1
C2-1
C2-1
C2-1
CRC
C
C
WAP
CR
KP
CR
KP
CR
KPKP
WAP
C2-1
C2-1
/A
C2-1
/A
C2-1
/A
C2-1
/A
C2-1
/A
C2-1
/A
C2-1 /A
C2-1
/A
C2-1 /A
C2-1
/AC
2-1
/A
C2-1 /A
C2-1 /A
C2-1
/A
C2-1
/A
C2-1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
EXISTING TELECOM ROOM
EXISTING
EQUIPMENT
RACK TYP.
11
1
1
1
1
1
1
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:1
2:0
0 A
M
T-101-B
BASEMENT FLOOR -
TECHNOLOGY
JEFGILTIMADA
POOVYA
18004050.00
TIMADA
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
TIMADA
NO R
HT
1/8" = 1'-0"1 BASEMENT FLOOR - TECHNOLOGY
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
GENERAL NOTES :
1. ALL NEW INFORMATION OUTLET ON THIS SHEET SHALL BE SERVED FROM THE EXISTING TELECOMMUNICATIONS ROOM UNLESS OTHERWISE NOTED.
2. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND GENERAL TECHNOLOGY INSTALLATION NOTES.
3. REFER TO T-200 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.
4. REFER TO 1/T-200 FOR CONNECTIVITY DIAGRAM AND ADDITIONAL REQUIREMENTS.
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
KEYNOTES:
1. PROVIDE SURFACE RACEWAY FOR TECHNOLOGY OUTLETS INDICATED.
#
100.1100.2
100
103.2 103.1
103
103.5103.4103.3
BASEMENTFLOOR BELOW
ELEV
BASEMENTFLOOR BELOW
SECONDFLOOR ABOVE
EXTERIORCIRCULATION
DN
DN
DN
UP
MechJan
Lounge
UP
Lobby
Mech
Office Office
Recept
OfficeOfficeStorage
UP DNUP
C2-1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
a
b
c
d
e
1
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:1
1:5
9 A
M
T-101
FIRST FLOOR PLAN -
TECHNOLOGY
JEFGILTIMADA
POOVYA
18004050.00
TIMADA
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
TIMADA
NO R HT
1/8" = 1'-0"1 FIRST FLOOR PLAN - TECHNOLOGY
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
GENERAL NOTES :
1. ALL NEW INFORMATION OUTLET ON THIS SHEET SHALL BE SERVED FROM THE EXISTING BASEMENT FLOOR TELECOMMUNICATIONS ROOM UNLESS OTHERWISE NOTED.
2. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND GENERAL TECHNOLOGY INSTALLATION NOTES.
3. REFER TO T-200 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.
4. REFER TO 1/T-200 FOR CONNECTIVITY DIAGRAM AND ADDITIONAL REQUIREMENTS.
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
KEYNOTES:
1. PROVIDE SURFACE RACEWAY FOR TECHNOLOGY OUTLETS.
#
327
325
328.10
328.09
328.08
328
328.07
328.06
328.05
328.04
328.03
328.02
328.01
326
322.1
300.01
303
304 300.02 300.03
300.04
300
300.11 300.07
300.06
300.05
300.08
300.09300.1
Treatment
Observation
WorkRoom
Office
Office
OpenOffice
Office
COPY
Office
Office
Office
Office
Office
WOMEN'SRESTROOM
UNISEX ADARESTROOM
WORKROOM
Office
TEACHINGLAB Office Office
Office
OpenOffice
OpenOffice Office
Observation
Treatment
Office
TreatmentObservation
MECHANICAL AREA
MECH SHAFT
MECH
DNDN
COOLING TOWER
NIC
305
301
ELEV
NIC NIC NIC NIC
NIC NIC
NIC
NIC
NIC NIC NIC NIC NIC NIC NIC NIC
NIC
NIC
C2-1
C
WAP
WAP
CR
WAP
CR
WAP
WAP
C
IM1
IS1
IS1
IM1
IM1
IS1
C1 C1
C2-1
C2-1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
b
c
d
1
2
EXISTING TELECOM ROOM
INTERCOM SYSTEM POWER SUPPLY
3
3
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:1
2:0
0 A
M
T-103
THIRD FLOOR PLAN -
TECHNOLOGY
JEFGILTIMADA
POOVYA
18004050.00
TIMADA
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
TIMADA
NO R
HT
1/8" = 1'-0"1 THIRD FLOOR PLAN - TECHNOLOGY
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
GENERAL NOTES :
1. ALL NEW INFORMATION OUTLET ON THIS SHEET SHALL BE SERVED FROM THE EXISTING BASEMENT FLOOR TELECOMMUNICATIONS ROOM UNLESS OTHERWISE NOTED.
2. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND GENERAL TECHNOLOGY INSTALLATION NOTES.
3. REFER TO T-200 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.
4. REFER TO 1/T-200 FOR CONNECTIVITY DIAGRAM AND ADDITIONAL REQUIREMENTS.
KEYNOTES:
1. PROVIDED FOR OWNER FURNISHED VIDEO PROJECTOR.
2. PROVIDED FOR OWNER FURNISHED WIRELESS ACCESS POINT. COORDINATE SPECIFIC LOCATION WITH OWNER PRIOR TO INSTALLATION.
3. PROVIDE SURFACE RACEWAY FOR TECHNOLOGY OUTLETS.
#
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018
EXISTING
VOICE PATCH
PANEL
EXISTING
VOICE PATCH
PANEL
EXISTING
PATCH PANEL
OWNER
PROVIDED
NETWORK
EQUIPMENT
EXISTING FIBER
PANEL
1
2
2-Port Faceplate
2
3-Port Faceplate
IDENTIFICATION
IDENTIFICATION
IDENTIFICATION
IDENTIFICATION
3
1
PAIR 3
PAIR 1PAIR 2 PAIR 4
WO WGO BL WBL G WBR BR
1 32 4 5 6 7 8
ANSI/TIA/EIA T568BPIN/PAIR ASSIGNMENT
C#
C#2
2
1
4
EXISTING COPPER
VOICE BACKBONE
EXISTING FIBER
BACKBONE
3
EXISTING TELECOM ROOM
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CABLE TYPE. ALL INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR MORE SPECIFIC ROUTING AND QUANTITY INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. REFER TO T-200 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.
KEYNOTES:
1. 23 GAUGE, 4-PAIR, CATEGORY 6, UNSHIELDED TWISTED PAIR CABLE, SEE SPECIFICATIONS.2. REFER TO INFORMATION OUTLET SCHEDULE ON T-200 AND THE FLOOR PLANS FOR QUANTITY OF
CABLES AND JACKS TO BE INSTALLED AT EACH INFORMATION OUTLET.3. EXISTING RJ-45 TO RJ-45 CATEGORY CAT 6 UTP PATCH CORD.4. EXISTING FIBER PATCH CORD.5. NEW INFORMATION OUTLETS (SC-IO-W) TO TERMINATE TO AVAILABLE OPEN SPACES ON EXISTING
MODULAR PATCH PANELS AND VOICE TERMINATION BLOCKS.
#
EXISTING VOICE
CROSS CONNECT
NOTES:
1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CONDUCTOR TYPE. ALL CONNECTIONS AND SYSTEM DEVICES SHOWN ARE TYPICAL AND NOT REPRESENTATIVE OF ACTUAL PROJECT QUANTITIES.REFER TO FLOOR PLANS AND ENLARGED FLOOR PLANS FOR ACTUAL QUANTITIES AND LOCATIONS OF DEVICES AND MORE SPECIFIC ROUTING INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
IM1 IS1
3C, 18 AWG SHIELDED CABLE
POWER SUPPLY (AIPHONE PS-1225UL) LOCATED WITHIN TELECOM ROOM. REFER TO FLOOR PLANS.
REFER TO SPECIFICATIONS FOR IDENTIFICATION REQUIREMENTS (TYP.)
NUMBER INDICATES FACEPLATE POSITION (TYP.)
FO
R B
IDS
AREA OF WORKNO SCALE
FLOOR LEVEL
project number:
sheet title:
sheet number:
approved
project:
coordination checked
location
drawn
checked
WAYNE STATE
UNIVERSITYFacilities Planning and Management
5454 Cass Avenue
Detroit, MI 48202
key plan:
date:issue:
designed
consultants:
NM Project Number - 18113.0
Prentis Building
IMEG Project Number -
WSU : 00
Prentis Building - Rackham
Relocation
- -
12/1
0/2
018 1
1:1
2:0
1 A
M
T-200
TECHNOLOGY DETAILS, RISERS
AND SCHEDULES
JEFGILTIMADA
POOVYA
18004050.00
TIMADA
WS
U P
ren
tis B
ldg
Rackh
am
Relo
cati
on
18004050.0
0
TIMADA
REFERENCE SCALE IN INCHES
0 1 2 3
PROJECT #
IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
18004050.00
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com
NO SCALE1
EXISTING TELECOMMUNICATIONSROOM - CONNECTIVITY DIAGRAM
NO SCALE2 INTERCOM RISER DIAGRAM
BLANK BLANK FILLER MODULE
2. REFER TO SPECIFICAITONS SECTION 27 05 53 FOR ADDITIONAL INFORMATION ON LABELING REQUIREMENTS. VOICE CAT 6 RJ-45 (WHITE)
1. PROVIDE REMOVABLE BLANK INSERT(S) FOR ALL UNUSED PORTS. DATA CAT 6 RJ-45 (ORANGE)
NOTES: LEGEND
SINGLE GANG WALLPLATES
INFORMATION OUTLET SCHEDULE
CONFIGURATION FA
CE
PL
AT
E P
OR
TS
FACEPLATE PORT IDENTIFICATION
NOTESPO
SIT
ION
1 J
AC
K T
YP
E
PO
SIT
ION
2 J
AC
K T
YP
E
PO
SIT
ION
3 J
AC
K T
YP
E
PO
SIT
ION
4 J
AC
K T
YP
E
PO
SIT
ION
5 J
AC
K T
YP
E
PO
SIT
ION
6 J
AC
K T
YP
E
C1 2 DATA BLANK
C2-1 3 DATA DATA VOICE
THE MATERIAL LIST ABBREVIATIONS AND THE TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BERESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKINGSYSTEM.
CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BEORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGSAND SPECIFICATIONS. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN. "STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE.
GENERAL TECHNOLOGY EQUIPMENT SCHEDULE
EQUIPMENT LISTABBREVIATION EQUIPMENT LIST DESCRIPTION
EQUIPMENT LISTMANUFACTURER AND MODEL
IC-IM1 INTERCOM MASTER STATION. DESK OR WALL MOUNT WITH ABS HOUSING AND LED, CALL TONE INDICATORS. 300 mAPOWER CONSUMPTION. INSTALL WITHIN 4" SQUARE BACKBOX WITH PLASTER RING AND PROVIDE (!) 1" C TO NEARESTACCESSIBLE CEILING.
AIPHONE LEF-3
OR PRE-APPROVED EQUAL
IC-IS1 INTERCOMM DOOR STATION. WALL MOUNT. ABS PLASTIC HOUSING. PUSH TO TALK OR OPEN VOICE HANDSFREECOMMUNICATION. INSTALL WITHIN 4" SQUARE BACKBOX WITH PLASTER RING. PROVIDE 1" CONDUIT TO NEARESTACCESSIBLE CEILING.
AIPHONE LE-B
OR PRE-APPROVED EQUAL
SC-IO-C INFORMATION OUTLET, CEILING MOUNT, 2 PORT COVERPLATE AS INDICATED ON DRAWINGS.
"#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO T-200 FORINFORMATION OUTLET SCHEDULE FOR PIN CONFIGURATION.
INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMTCONDUIT 6" BEYOND BOX AND TERMINATE WITH A NYLON BUSHING. PROVIDE REMOVABLE BLANK INSERTS FORUNUSED PORTS (SYSTIMAX M20AP SERIES OR APPROVED EQUAL)
COVERPLATE:COMMSCOPE SYSTIMAX M12L - 262
JACK:COMMSCOPE SYSTIMAX CAT6 UNJ600-OR (ORANGE)
HUBBELLORTRONICS
SC-IO-W INFORMATION OUTLET, WALL MOUNT, 3 PORT COVERPLATE AS INDICATED ON DRAWINGS.
"#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO T-200 FORINFORMATION OUTLET SCHEDULE FOR PIN CONFIGURATION.
INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMTCONDUIT TO TELECOM ROOM. PROVIDE REMOVABLE BLANK INSERTS FOR UNUSED PORTS (SYSTIMAX M20AP SERIESOR APPROVED EQUAL)
COVERPLATE:COMMSCOPE SYSTIMAX M13L - 262
JACK:COMMSCOPE SYSTIMAX CAT6 UNJ600-OR (ORANGE) UNJ600-WH (WHITE)
HUBBELLORTRONICS
Owner Review 90% CD's Nov. 27, 2018
100% CD's Dec. 04, 2018
For Bids Dec. 11, 2018