DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan -...

62
W A Y N E S T A T E U N I V E R S I T Y V I C I N I T Y P L A N SCALE: NTS A R C H I T E C T U R A L PRENTIS BUILDING RENOVATION L O C A T I O N P L A N SCALE: NTS T-1 DETROIT, MI 48202 2215 Cole Street BIRMINGHAM, MICHIGAN 48009 P (248)646-5765 F (248)646-5813 No code variance requests are anticipated. Contractor to coordinate WORK SCOPE and construction activities with WSU construction Project Manager : W O R K S C O P E RENOVATE PORTION OF PRENTIS BUILDING (BASEMENT, FIRST FLOOR, MEZZANINE, AND THIRD FLOOR) INTO NEW OFFICES, CLASSROOMS, AND LABS, RENOVATE THIRD FLOOR RESTROOM INTO UNISEX ADA COMPLIANT RESTROOM. PRENTIS BUILDING RENOVATION A P P L I C A B L E C O D E S BUILDING CODE: P R O J E C T A R E A S U M M A R Y MECHANICAL CODE: PLUMBING CODE: FIRE SAFETY CODE: (FOR CONTRACT DOCUMENTS) ELECTRICAL CODE: NFPA 101 LIFE SAFETY CODE NFPA 13/ 2007 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS MICHIGAN REHABILITATION CODE FOR EXISTING BUILDING/ 2015 STATE OF MICHIGAN MECHANICAL CODE/ 2015 STATE OF MICHIGAN ELECTRICAL CODE /2014 MICHIGAN PLUMBING CODE/ 2015 GROSS AREA - 13,000 GSF ± USE GROUP: CONSTRUCTION TYPE: PUBLIC HEALTH CODE: BARRIER FREE CODES: MDCIS MINIMUM DESIGN STANDARDS FOR CONSTRUCTION AND EQUIPMENT FOR HEALTHCARE FACILITIES IN MICHIGAN UFAS, AMERICANS WITH DISABILITIES ACT ACCESSIBILITY GUIDELINES, MICHIGAN BARRIER FREE - 2010 BUSINESS - B 1A NON-COMBUSTIBLE Title Sheet, Drawing Index and Location & Vicinity Maps WAYNE STATE UNIVERSITY PROJECT SITE : PRENTIS BUILDING FOR BIDS project number: sheet title: sheet number: approved project: coordination checked location drawn checked designed issue: date: key plan: Prentis Building - Rackham Relocation Nov. 13, 2018 Owner Review 60% CD's NM Project Number - 18113.0 WAYNE STATE UNIVERSITY Facilities Planning and Management 5454 Cass Avenue Detroit, MI 48202 Prentis Building JK JK JK DB AG WSU : 00 consultants: Nov. 27, 2018 Owner Review 90% CD's Dec. 04, 2018 Review 100% CD's Dec. 11, 2018 For Bids T-1 TITLE SHEET, DRAWING INDEX & LOCATION & VICINITY MAPS A-002 ABBREVIATIONS, DRAWING SYMBOLS STANDARDS& STANDARD MOUNTING HEIGHTS A-20 ROOM FINISH SCHEDULE A-30 DOOR SCHEDULE & WALL TYPES AD-101-B PRENTIS BUILDING BASEMENT FLOOR PLAN - DEMOLITION WORK AD-101 PRENTIS BUILDING 1ST FLOOR PLAN - DEMOLITION WORK AD-101-M PRENTIS BUILDING MEZZANINE FLOOR PLAN - DEMOLITION WORK AD-103 PRENTIS BUILDING 3RD FLOOR PLAN - DEMOLITION WORK AD-104-B PRENTIS BUILDING BASEMENT FLOOR REFLECTED CEILING PLAN - DEMOLITION WORK AD-105 PRENTIS BUILDING 3RD FLOOR REFLECTED CEILING PLAN - DEMOLITION WORK A-201-B PRENTIS BUILDING BASEMENT FLOOR PLAN - NEW WORK A-201 PRENTIS BUILDING 1ST FLOOR PLAN -NEW WORK A-201-M PRENTIS BUILDING MEZZANINE FLOOR PLAN - NEW WORK A-203 PRENTIS BUILDING 3RD FLOOR PLAN - NEW WORK A-301-B PRENTIS BUILDING BASEMENT FLOOR REFLECTED CEILING PLAN - NEW WORK A-303 PRENTIS BUILDING 3RD FLOOR REFLECTED CEILING PLAN - NEW WORK A-701 PRENTIS BUILDING INTERIOR ELEVATIONS, SECTIONS, AND DETAILS E L E C T R I C A L M E C H A N I C A L MH000 VENTILATION COVER SHEET MHD101B BASEMENT FLOOR DEMOLITION - VENTILATION MHD103 THIRD FLOOR DEMOLITION - VENTILATION MH101B BASEMENT FLOOR PLAN - VENTILATION MH103 THIRD FLOOR PLAN - VENTILATION MH300 VENTILATION SCHEDULES & DETAILS P000 PLUMBING COVER SHEET PD103 THIRD FLOOR DEMOLITION - PLUMBING P101B BASEMENT FLOOR PLAN - PLUMBING P101M MEZZANINE FLOOR PLAN - PLUMBING P103 SECOND AND THIRD FLOOR PLAN - PLUMBING P300 PLUMBING DETAILS P500 PLUMBING SCHEDULES E000 ELECTRICAL COVER SHEET ED101B BASEMENT FLOOR DEMOLITION - ELECTRICAL ED-101 FIRST FLOOR DEMOLITION- ELECTRICAL ED101M MEZZANINE FLOOR DEMOLITION - ELECTRICAL ED103 THIRD FLOOR DEMOLITION - ELECTRICAL EL101B BASEMENT FLOOR PLAN - LIGHTING EL-101 FIRST FLOOR PLAN- LIGHTING EL101M MEZZANINE FLOOR PLAN - LIGHTING EL103 THIRD FLOOR PLAN - LIGHTING EP101B BASEMENT FLOOR - POWER EP-101 FIRST FLOOR - POWER EP101M MEZZANINE FLOOR PLAN - POWER EP103 THIRD FLOOR PLAN - POWER EP-300 POWER DETAILS ES101B BASEMENT FLOOR - SYSTEMS ES101 FIRST FLOOR PLAN - SYSTEMS ES101M MEZZANINE FLOOR PLAN - SYSTEMS ES103 THIRD FLOOR - SYSTEMS ES300 SYSTEM DETAILS T000 TECHNOLOGY COVER SHEET TD101B BASEMENT FLOOR DEMOLITION - TECHNOLOGY TD103 THIRD FLOOR DEMOLITION - TECHNOLOGY T101B BASEMENT FLOOR PLAN - TECHNOLOGY T101 FIRST FLOOR PLAN - TECHNOLOGY T103 THIRD FLOOR PLAN - TECHNOLOGY T200 TECHNOLOGY DETAILS, RISERS AND SCHEDULES 26200 Town center Drive NOVI, MICHIGAN 48375 P (248)313-6902 F (248)344-1650 26200 Town center Drive NOVI, MICHIGAN 48375 P (248)313-6902 F (248)344-1650 MP000 PIPING COVER SHEET MPD101B BASEMENT FLOOR DEMOLITION - PIPING MP101B BASEMENT FLOOR - PIPING MP103 SECOND AND THIRD FLOOR PLAN - PIPING F000 FIRE PROTECTION COVER SHEET F101B BASEMENT FLOOR - FIRE PROTECTION ALTERNATES · REPLACE ALL CEILING TILE THROUGH OUT PROJECT · DEDUCT NEW CEILING IN TEACHING LAB 304. PROVIDE FOR REPAIR OF GRID AND NEW TILE AS NEEDED. · DEDUCT NEW COUNTER TOPS IN WORK ROOM 300.01. REUSE EXISTING COUNTER TOPS FROM RACKHAM

Transcript of DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan -...

Page 1: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

W A Y N E S T A T E U N I V E R S I T Y

V I C I N I T Y P L A N

SCALE: NTS

A R C H I T E C T U R A L

PRENTIS BUILDING RENOVATION

L O C A T I O N P L A N

SCALE: NTS

T-1

DETROIT, MI 48202

2215 Cole Street

BIRMINGHAM, MICHIGAN 48009

P (248)646-5765 F (248)646-5813

No code variance requests are anticipated.

Contractor to coordinate WORK SCOPE and constructionactivities with WSU construction Project Manager :

W O R K S C O P E

RENOVATE PORTION OF PRENTIS BUILDING (BASEMENT, FIRST FLOOR, MEZZANINE, AND THIRDFLOOR) INTO NEW OFFICES, CLASSROOMS, AND LABS, RENOVATE THIRD FLOOR RESTROOM INTOUNISEX ADA COMPLIANT RESTROOM.

PRENTIS BUILDING RENOVATION

A P P L I C A B L E C O D E S

BUILDING CODE:

P R O J E C T A R E A S U M M A R Y

MECHANICAL CODE:

PLUMBING CODE:

FIRE SAFETY CODE:

(FOR CONTRACT DOCUMENTS)

ELECTRICAL CODE:

NFPA 101 LIFE SAFETY CODE

NFPA 13/ 2007 STANDARD FOR THEINSTALLATION OF SPRINKLERSYSTEMS

MICHIGAN REHABILITATION CODE FOR EXISTING BUILDING/ 2015

STATE OF MICHIGAN MECHANICAL CODE/ 2015

STATE OF MICHIGAN ELECTRICAL CODE /2014

MICHIGAN PLUMBING CODE/ 2015

GROSS AREA - 13,000 GSF ±

USE GROUP:

CONSTRUCTION TYPE:

PUBLIC HEALTH CODE:

BARRIER FREE CODES:

MDCIS MINIMUM DESIGN STANDARDS FORCONSTRUCTION AND EQUIPMENT FORHEALTHCARE FACILITIES IN MICHIGAN

UFAS, AMERICANS WITH DISABILITIES ACT ACCESSIBILITYGUIDELINES, MICHIGAN BARRIER FREE - 2010

BUSINESS - B

1A NON-COMBUSTIBLE

Title Sheet, Drawing Index andLocation & Vicinity Maps

WAYNE STATE UNIVERSITY

PROJECT SITE :

PRENTIS BUILDING

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

T-1 TITLE SHEET, DRAWING INDEX & LOCATION & VICINITY MAPSA-002 ABBREVIATIONS, DRAWING SYMBOLS STANDARDS& STANDARD MOUNTING HEIGHTSA-20 ROOM FINISH SCHEDULEA-30 DOOR SCHEDULE & WALL TYPESAD-101-B PRENTIS BUILDING BASEMENT FLOOR PLAN - DEMOLITION WORKAD-101 PRENTIS BUILDING 1ST FLOOR PLAN - DEMOLITION WORKAD-101-M PRENTIS BUILDING MEZZANINE FLOOR PLAN - DEMOLITION WORKAD-103 PRENTIS BUILDING 3RD FLOOR PLAN - DEMOLITION WORKAD-104-B PRENTIS BUILDING BASEMENT FLOOR REFLECTED CEILING PLAN - DEMOLITION WORKAD-105 PRENTIS BUILDING 3RD FLOOR REFLECTED CEILING PLAN - DEMOLITION WORKA-201-B PRENTIS BUILDING BASEMENT FLOOR PLAN - NEW WORKA-201 PRENTIS BUILDING 1ST FLOOR PLAN -NEW WORKA-201-M PRENTIS BUILDING MEZZANINE FLOOR PLAN - NEW WORKA-203 PRENTIS BUILDING 3RD FLOOR PLAN - NEW WORKA-301-B PRENTIS BUILDING BASEMENT FLOOR REFLECTED CEILING PLAN - NEW WORKA-303 PRENTIS BUILDING 3RD FLOOR REFLECTED CEILING PLAN - NEW WORKA-701 PRENTIS BUILDING INTERIOR ELEVATIONS, SECTIONS, AND DETAILS

E L E C T R I C A LM E C H A N I C A L

MH000 VENTILATION COVER SHEETMHD101B BASEMENT FLOOR DEMOLITION - VENTILATIONMHD103 THIRD FLOOR DEMOLITION - VENTILATIONMH101B BASEMENT FLOOR PLAN - VENTILATIONMH103 THIRD FLOOR PLAN - VENTILATIONMH300 VENTILATION SCHEDULES & DETAILSP000 PLUMBING COVER SHEETPD103 THIRD FLOOR DEMOLITION - PLUMBINGP101B BASEMENT FLOOR PLAN - PLUMBINGP101M MEZZANINE FLOOR PLAN - PLUMBINGP103 SECOND AND THIRD FLOOR PLAN - PLUMBINGP300 PLUMBING DETAILSP500 PLUMBING SCHEDULES

E000 ELECTRICAL COVER SHEETED101B BASEMENT FLOOR DEMOLITION - ELECTRICALED-101 FIRST FLOOR DEMOLITION- ELECTRICALED101M MEZZANINE FLOOR DEMOLITION - ELECTRICALED103 THIRD FLOOR DEMOLITION - ELECTRICALEL101B BASEMENT FLOOR PLAN - LIGHTINGEL-101 FIRST FLOOR PLAN- LIGHTINGEL101M MEZZANINE FLOOR PLAN - LIGHTINGEL103 THIRD FLOOR PLAN - LIGHTINGEP101B BASEMENT FLOOR - POWEREP-101 FIRST FLOOR - POWEREP101M MEZZANINE FLOOR PLAN - POWEREP103 THIRD FLOOR PLAN - POWEREP-300 POWER DETAILSES101B BASEMENT FLOOR - SYSTEMSES101 FIRST FLOOR PLAN - SYSTEMSES101M MEZZANINE FLOOR PLAN - SYSTEMSES103 THIRD FLOOR - SYSTEMSES300 SYSTEM DETAILST000 TECHNOLOGY COVER SHEETTD101B BASEMENT FLOOR DEMOLITION - TECHNOLOGYTD103 THIRD FLOOR DEMOLITION - TECHNOLOGYT101B BASEMENT FLOOR PLAN - TECHNOLOGYT101 FIRST FLOOR PLAN - TECHNOLOGYT103 THIRD FLOOR PLAN - TECHNOLOGYT200 TECHNOLOGY DETAILS, RISERS AND SCHEDULES

26200 Town center Drive

NOVI, MICHIGAN 48375

P (248)313-6902 F (248)344-1650

26200 Town center Drive

NOVI, MICHIGAN 48375

P (248)313-6902 F (248)344-1650

MP000 PIPING COVER SHEETMPD101B BASEMENT FLOOR DEMOLITION - PIPINGMP101B BASEMENT FLOOR - PIPINGMP103 SECOND AND THIRD FLOOR PLAN - PIPINGF000 FIRE PROTECTION COVER SHEETF101B BASEMENT FLOOR - FIRE PROTECTION

ALTERNATES

· REPLACE ALL CEILING TILE THROUGH OUT PROJECT

· DEDUCT NEW CEILING IN TEACHING LAB 304. PROVIDE FORREPAIR OF GRID AND NEW TILE AS NEEDED.

· DEDUCT NEW COUNTER TOPS IN WORK ROOM 300.01. REUSEEXISTING COUNTER TOPS FROM RACKHAM

Page 2: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

FO

R U

P

TO

4

0 L

BS

FO

R M

OR

E

TH

AN

4

0 L

BS

42" M

AX

60" M

AX

48" M

AX

2'-10

" MAX

MOUNTING HEIGHT FORDISPENSERS IS TO TOP OFDISPENSER OR HIGHESTOPERABLE PART

TO

WE

L D

IS

PE

NS

ER

S

& D

IS

PO

SE

RS

SO

AP

D

IS

PE

NS

ER

/ H

AN

D

SA

NIT

IZ

ER

TD

SD

4" MAX

48" T

YPIC

AL

1'-3"

MIN

MOUNTING HEIGHT FOR MIRROR:

BOTTOM EDGE OF MIRROR

PO

WE

R/D

AT

A/

PH

ON

E R

EC

EP

TA

CL

ES

LIG

HT

S

WIT

CH

ES

MIN 1 1/2" BETWEENTOP OF TP HOLDERAND BOT. OF GRABBAR

3'-0"

MAX

34"

HD

HA

ND

D

RY

ER

SND

SA

NIT

AR

Y N

AP

KIN

DIS

PE

NS

ER

FIR

E A

LA

RM

P

UL

L

IN

TE

RC

OM

HV

AC

C

ON

TR

OL

MOUNTINGHEIGHT IS TO TOPOF HIGHESTOPERABLE PARTOR RECEPTACLE

3'-8"

MAX

1'-5"

MAX

1'-3" MIN

SHELF,

WHERE

SPECIFIED

44

" O

VE

R

CO

UN

TE

R O

R

OB

ST

RU

CT

IO

N

WH

EN

OP

EN

TO

C

AB

IN

ET

HA

ND

LE

FILMILLUMINATOR

3'-6"

U.N

.O.

4'-6"

7'-2"

X"

4'-6"

4'-0"

2'-0"

5'-0"

4128

"

5'-0"

2'-0"

6'-6"

1'-6"

6'-0"

MONITOR &BRACKET

REMOTE MONITOR& BRACKET(@ CORRIDORLOCATIONS)

TVBRACKET

OTOSCOPE/SPHYGMOM-ANOMETER

SHARPSCONTAINER

GLOVE &APRON RACK

(S

IN

GL

E

BR

AC

KE

T)

(S

IN

GL

E

BR

AC

KE

T)

ADDITIONAL

BRACKET

SEGMENTS ADDED

AS REQUIRED

IV PUMP BAR(NON-FERROUS)

WALL-MOUNTEDWORKSTATION

FLIP DOWNWORKSTATION

SHOWER CURTAINROD, HOOKS, ANDCURTAIN

SHOWERNICHE

FOLDINGSHOWERSEAT

MOP & BROOMHOLDER - NOSHELF

MARKER BOARD/TACK BOARD

CHART ORMAGAZINERACK

HAIRDRYER

BED PANHOLDER

COATBRACKET& SHELF

SURFACEMOUNTEDPROJECTIONSCREEN

36"X48"

U.N.O.

44

" @

A

DA

48

" A

T

AC

CE

SS

IB

LE

BARRIER FREEEWC & DRINKINGFOUNTAIN

SINKS &LAVATORIES

URINALACCESSIBLE

TOILET, GRAB BAR &TOILET PAPERHOLDER

FOLD DOWNBABY CHANGINGTABLE

WALL MOUNTEDSEMI-RECESSEDFIREEXTINGUISHERCABINET

WALL MOUNTEDFIREEXTINGUISHER

MIRRORS

3'-8" 5'-

0"

3'-6"

48

" M

AX

A

T

AC

CE

SS

IB

LE

TOWEL BAR HOOK

GLOVEDISPENSER

SPECIMENPASS-THRU

6'-2"

3'-4"

3'-6"

3'-6"

3'-8"

MAX

3'-6"

MAX

3'-8"

MAX

4'-10

"

4'-0"

MAX

TO

B

OT

TO

M

OF

T

V

6" MAX9" MIN

9" M

IN

2'-3"

MIN

960"

MOUNTING

HEIGHT IS TO

SPOUT OUTLET

HEIGHT

8"

1 1/2

"

840"

1'-0" 3'-6"

1584

"

1920

"86

4"

6"3'-5"

1'-6"

3'-0"

1'-0"

INTERIOR ELEVATIONS LEGEND

6"

3'-9"

NOTE:REFER TO ARCH PLANS FOR ACCESSORIES AND THEIRLOCATIONS. THIS SHEET IS FOR STANDARD MOUNTING HEIGHTSONLY UNLESS NOTED ELSEWHERE IN THIS DRAWING SET

ABHR

MA

X.

FLOOR

ABHR

LEGEND

1. NO PROJECTION CAN EXTEND OUT MORE THAN 4" INTO

CORRIDOR OR WALKWAY.

2. ALCOHOL BASED HAND RUB SANITIZERS CANNOT BE LOCATED

ABOVE A POTENTIAL IGNITION SOURCE

3. ABHR MUST BE OFFSET A MINIMUM OF 1" HORIZONTALLY FROM

ANY LIGHT SWITCH, ELECTRICAL OR DATA RECEPTACLE,

THERMOSTAT OR OTHER POTENTIAL IGNITION SOURCE.

4. ABHR SANITIZERS CANNOT BE INSTALLED IN A CORRIDOR LESS

THAN 6' WIDE

5. ABHR MUST BE AT LEAST 4' APART

6. ABHR CANNOT BE INSTALLED OVER CARPET IN NON-SPRINKLED

SPACES.

7. MAX. CAPACITY OF DISPENSERS IN CORRIDORS: 0.3 GALLONS

NOTES

ALCOHOL BASED HAND RUB SANITIZER DISPENSER

LIGHT SWITCH/RECEPTACLE OR OTHER POTENTIAL IGNITION SOURCE

44"1"

MIN.

1"MIN.

MA

X.

IF ABHR IS NEXTTO POTENTIALIGNITION SOURCE,IT MUST BEOFFSET 1"HORIZONTALLY.

ABHR CAN BEBELOWPOTENTIALIGNITION SOURCE,NO ISSUES.

ABHR CANNOT BEABOVE POTENTIALIGNITION SOURCE.

ABHR

ABHR

44"

ALCOHOL BASED HAND RUB SANITIZERSMOUNTING REQUIREMENTS

FLOOR

FLOOR

FLOOR

FLOOR

A-002

PLANS

EXISTING WALLS TO REMAIN

NEW WALLS

ACROVYN CORNER GUARD - FULL HEIGHT

END CAP - FULL HEIGHTACG

ECFIRE EXTINGUISHER CABINET -SEMI-RECESSED (ADA)

FEC

EXISTING WALLS TO BE REMOVED

NEW DOOR W/ DOOR NUMBER

EXISTING DOOR TO BE REMOVED

CUBICLE CURTAIN TRACK

2'x2' FLUORESCENT LIGHT FIXTURE

2'x4' FLUORESCENT LIGHT FIXTURE

NEW SUSPENDED ACOUSTICAL CEILING @ 8'-0" AFFU.N.O.

GYPSUM BOARD CEILING @ 7'-6" AFF U.N.O.

RECESSED DOWN LIGHT FIXTURE

TREATMENT ROOM LIGHT FIXTURE

EXIT LIGHT (CEILING MOUNTED)

SMOKE DETECTOR

FIRE SPRINKLER HEAD - NEW SPRINKLER HEADS ARESHOWN FOR COORDINATION PURPOSES ONLY. FINALSPRINKLER HEAD LOCATIONS SHALL BE DETERMINEDBY A CERTIFIED FIRE PROTECTION FIRM, ANDCOORDINATED WITH ARCHITECT & ENGINEERS.

FIRE ALARM - SEE ELECTRICAL DWG.

WIRELESS ANTENNA - SEE ELECTRICAL DWG.

SPEAKER

EXISTING DOOR TO REMAIN

RETURN GRILLE - SEE MECHANICAL DWG.

EXHAUST GRILLE - SEE MECHANICAL DWG.

SUPPLY GRILLE - SEE MECHANICAL DWG.

PLAN IDENTIFICATIONW/NORTH ARROW

SECTION LOCATION IDENTIFICATION

DETAIL LOCATION IDENTIFICATION ATENLARGED SCALE

ELEVATION LOCATION IDENTIFICATION

KEYNOTE IDENTIFICATIONDEMO / NEW / MISC

BULLETIN IDENTIFICATION W/CLOUD

ROOM NAME & NUMBER

1. DO NOT SCALE DRAWING REPRODUCTIONS.2. THIS DRAWING REPRESENTS TYPICALLY ENCOUNTERED

ITEMS. NOT ALL ITEMS SHOWN MAY OCCUR WITHIN THESCOPE OF THIS PROJECT. REFER TO COMPLETESPECIFICATIONS AND DRAWING DOCUMENTATION SET.

GRID BUBBLE

DOOR NUMBER TAG

CEILING HEIGHT TAGEXISTING / NEW

EXISTING SUSPENDED ACOUSTICAL CEILING TO BEREMOVED

ACOUSTICAL CEILING TILEACT

CEILING HEIGHTCH

CEILINGCLG

EXISTING(X)

EXPANSION JOINTEJ

GAUGEGA

HARDWAREHDWR

HOLLOW METALHM

HEIGHTHT

INTERIOR DESIGNID

LAVATORYLAV

MAXIMUMMAX

MANUFACTURERMFR

MINIMUMMIN

MASONRY OPENINGMO

PLASTIC LAMINATEPLAM

SQUARE FEETSF

SIMILARSIM

SPECIFICATIONSSPEC

UNLESS NOTED OTHERWISEUNO

WATER CLOSETWC

WITH

W/O WITHOUT

RO ROUGH OPENING

NTS NOT TO SCALE

CENTER LINECL

OH OVERHEAD

GYPSUM BOARDGB

TYPICALTYP

CONTROL JOINTCJ

VINYL WALL COVERINGVWC

STAINLESS STEELSSTL

GLASSGL

WALL PROTECTIONWP

JC JANITORS CLOSET

RB RESILIENT BASE

CERAMIC TILECT

PT PAINT

CONTRACTOR FURNISHED/ INSTALLEDCFI

CAPITAL EQUIPMENTCE

ABOVE FINISH FLOORAFF

WOODWD

CARPETCPT

VINYL COMPOSITION TILEVCT

LIGHTLT

LINEAL FEETLF

EQUALEQ

BUREAU OF FIRE SAFETYBFS

HEALTH FACILITIES ENGINEERING SECTIONHFES

HOUR, HAND RAILHR

OPPOSITE HANDOPP

W/

FIRE ALARMFA

CJ CONTROL JOINT

KP KICK PLATE

JT JOINT

EACHEA

ELEVATOR, ELEVATIONELEV

FLOOR DRAINFD

UNDERWRITERS LABORATORY INCUL

PVC POLYVINYL CHLORIDE

QTY QUANTITY

CORNER GUARDCG

CARD READERCR

FV FIELD VERIFY

ARCHITECTURAL SYMBOLS LEGEND

FLOOR PLAN LEGEND

SOLID SURFACESSRF

REFLECTED CEILING PLAN LEGEND

GENERAL NOTESABBREVIATIONS LIST

EXISTING SUSPENDED ACOUSTICAL CEILING

DATUM/ELEVATION LOCATION ID

1

EXISTING WINDOW SYSTEM

NEW WINDOW SYSTEM

2'x2' FLUORESCENT INDIRECT LIGHT FIXTURE

~

S

FA

WA

EXISTING DOUBLE DOOR TO BE REMOVED

EXISTING DOUBLE DOOR TO REMAIN

NEW DOUBLE DOOR W/ DOOR NUMBER

TEMPORARY 1-HR PARTITION AND DOOR

LAVATORY SINK

CLINICAL SINK

SQUARE SINK

ROUND SINK

MOP/CORNER SINK

FLOOR TOILET

WALL HUNG TOILET

URINAL

TANK STYLE TOILET

GRAB BAR

XX

XXXX

X'-X"

XXXX

C3

D4

A1

B2

Main Floor LevelEL:100'-0"

0001

XX

XXXX

GRIDGRID

NewExist

NEWROOM NAME000

DXXXX

DXX

XX

DXX

XX

00 06

EQUIPMENT TAG

00 WALL TYPE TAG

CT-1 INTERIOR FINISH TAG

SSTL

RSF

STAINLESS STEEL

RESILIENT SHEET FLOORING

DOOR OPENINGDO

(R) RELOCATE

01Axxxx Scale: 1/8" = 1'-0"

Plan Name - Bottom LinePlan Name - Top Line

DRINKING FOUNTAIN

PTM PATCH TO MATCH

CAM CAMERA - SEE ELECTRICAL DWG.

OS OCCUPANCY SENSOR (CEILING MOUNTED)

OFCI OWNER FURNISHED CONTRACTOR INSTALLED

OFVI OWNER FURNISHED VENDOR INSTALLED

OFOI OWNER FURNISHED OWNER INSTALLED

Abbreviations, Drawing SymbolsStandard & Standard MountingHeights

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Page 3: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

CEILINGFINISH

ROOM FINISH SCHEDULE

DW

G #

ROOM NAMEROOM NO. TRANSITIONMAT.

ROOM FLOORMAT.

EAST WALL

MAT. FINISH MAT. MAT.FINISH FINISH

NORTH WALLBASE SOUTH WALL

MATERIALMAT.FINISH FINISH TYPE MATERIAL

WINDOW SILLWEST WALL

CABINETS

MILLWORKFINISH MOUNT HEIGHT MATERIAL FINISH

BULKHEADROOM #

REMARKS

A-20

A-2

01-B

COUNTER

INDEX OF FINISH MANUFACTURERS

PAINT- PT-1MANUFACTURER: SHERWIN WILLIAMSTYPE: PAINTCOLOR: SW7568 NEUTRAL GROUNDFINISH: SEMI-GLOSS

FIRE-RATED

CEILING DATA

PLASTER

ACOUSTIC LAY-IN TILEACOUSTIC TEGULAR TILE

GYPSUM WALLBOARDGYPSUM PLASTER

FIBER REINFORCED GYPSUM PANELFIBER REINFORCED GYPSUM PANEL

HUMIDITY RESISTANT LAY IN TILEABUSE RESISTANT LAY IN TILE

TF

CLN

CSH

ST&VS&L

PT

S&V

PREW

S

GRAN

S&W

WDSRF

N

RSF

RTRCONQT

RTFCTSV

CP

TERR

WD

RFRTRCON

RBRSB

SEAL & VARNISHSEAL & LACQUERSTAIN & VARNISH

CONCRETE SEALER/HARDENERTEXTURE FINISH

CLEANPREFINISHED

PAINT

SEAL

WAX

RESILIENT SHEET FLOORINGRESILIENT TILE FLOORING

RUBBER TREAD & RISERRUBBER FLOORING

GRANITE TILE

SEAL & WAXFINISH

SLATEWOODNONE

CERAMIC & PORCELAIN TILE

QUARRY TILECONCRETE

RNS

QT

RUBBER FLOORINGRUBBER TREAD & RISER

RESILIENT BASERESILIENT SHEET BASEQUARRY TILE

RUBBER

WOODSLATE

NONE

CONCRETE

AMCT

FLOOR DATA

SHEET VINYL

CARPET

TERRAZZO

MATERIAL

CPTERR

BASE DATA

CERAMIC TILEAGGLOMERATED MARBLETERRAZZOCARPET

ARCHBARCBCARCBDBARCBSBARCB2ARCB1

CONCRETE MASONRY UNITS

AGGLOMERATED MARBLEACOUSTIC BLOCK - SOUND ABSORBING

FACE BRICK TRIM COURSING

GROUND FACE MASONRY UNITS

FBTCEXISTING FACE BRICK

WALL FABRICQUARRY TILECERAMIC & PORCELAIN TILE

SLATENONE

SN

AMCTQT

EFB

WF

GMFU

FACE BRICKPOLY-RESIN

LIGHTWEIGHT BLOCKPOURED CONCRETE

PRFB

AB

CMU

LBPC

PCPGB

ARCB

VC

FIBER REINFORCED GYPSUM PANEL FIRE-RATEDFIBER REINFORCED GYPSUM PANELGYPSUM WALLBOARD FIRE-RATED

WALL DATA

GYPSUM WALLBOARD-LEAD LINEDGWFRF

GW-LL

FFR

ARCHITECTURAL BLOCK - DOUBLE BULLNOSEARCHITECTURAL BLOCK - SINGLE BULLNOSEARCHITECTURAL BLOCK #2 - SINGLE SCORED FACEARCHITECTURAL BLOCK #1 - SPLIT RIB1 SR-1ARCHITECTURAL BLOCK TYPE "D" TRIM COURSING

ARCHITECTURAL HALF BLOCKARCHITECTURAL BLOCK CAP

GLASS BLOCKPORTLAND CEMENT PLASTER

VINYL COVERED

ARLITHRLIT

PL

ATTACT

GSP

FFFR

GW

MIRROR, FIXED

ROOM ACCESSORIES

TOILET TISSUE DISPENSER

MOP & BROOM HOLDERSSHOWER CURTAIN RODS

GRAB BAR ASSEMBLYROBE HOOKS

FRAMED TILTED MIRROR, FIXEDFRAMED MIRROR, FIXED

SANITARY NAPKIN VENDOR

WASTE RECEPTACLETOWEL BARS

ELECTRIC HAND DRYERPAPER TOWEL DISPENSER

SOAP DISPENSER

SANITARY NAPKIN DISPOSAL

FOLDING SHOWER SEATCERAMIC SOAP DISH

W/ ACOUSTIC BATTSCERAMIC TILE

MOUNTING

SUSPENDEDFURSUS

NCT

FURRED

NONE

EXPOSED STRUCTUREEXPOSED ACOUSTIC DECKEXPOSED METAL DECKACOUSTICAL METAL DECKAMDAB

EADEMD

ES

WR

CSD

SNV SND

FS

GBA RH CR

MF

MBHFTMF FMF

TBSD

TTD HD TD

ITEM

LEGEND OF ABBREVIATIONS

MATERIAL MATERIAL MATERIAL

VCB VINYL COMPOSITE BASE

WOODWD

STAINLESS STEELSSTLGRANITEGRANGLASSGLCURTAIN WALLCWFABRIC SCRIMFAB

GYPSUM WALLBOARDGW

WOODMETAL PRIMEDMETAL PRE-FINISHEDANODIZED ALUMINUM

STAIN GRADEVARNISH GRADE

PREFINISHEDPLASTIC LAMINATEANODIZED ALUMINUMPERMANODICPAINTFACTORY FINISHMATCH EXISTING

HARDBOARD

LOUVREDOOR FINISH

TEMPERED INSULATED

INSULATED HOLLOW METALGEORGIAN POLISHED WIRE

REFLECTIVE INSULATED

TICLEAR INSULATED

RICI

HOLLOW CORE WOODSOLID CORE WOODALUMINUMHOLLOW METAL

GAUGECLEAR FLOATTEMPERED

LAMINATEDREFLECTIVETINTED

GLASS

G

TRL

TCF#

PER

MEFFPT

PLAMPRE

AA

VGSG

HB MP/FAA

MPW HOLLOW METAL WELDED

SEAL & VARNISHS&V

FIXED MULLIONREMOVABLE MULLION

SEAL & LACQUERS&L

RMFM

ALUMINUMTHERMALLY BROKENSOLID WOODHOLLOW METAL

WELDEDSTANDARD

STAIN & VARNISH

PERMANODICANODIZED ALUMINUM

FINISHES

KNOCKDOWN

AA

ST&V

PERP

STD

PAINTSW

WEL

HMKD

HMW

TBAL

REMOVABLE MULLION

THRESHOLDWEATHER STRIPSOUND STRIP

WEATHER CAP

LOCK SEAMWELD SEAM WINDOW TREATMENTS

BARRIER FREE OPERATORBFORM

WSTLS

WS

ASTRAGAL

HARDWAREFRAME CONSTRUCTION

FRAME DATA

SSAWC

HOLLOW METAL WELDED (LEAD)HMW-L

HMIHM

SCWHCW

DOOR CONSTRUCTION

PL PLASTIC LAMINATE

WALL PROTECTION (ACROVYN)WP

PTM PATCH TO MATCHNW NO WORKX EXISTING

AL

CPT CARPET TILEGYPSUM VENEER PLASTERGVPPORTLAN CEMENT PLASTERPCP

GYPSUM PLASTERGSPGYPSUM VENEER PLASTERGVP

FIBERGLASS REINF'D POLYMERFRP

FIBERGLASS REINF'D POLYMERFRP

(SHOP DRAWINGS AND SAMPLES MUST BE SUBMITTED FOR FINAL APPROVAL ON ALL INTERIOR FINISHES)

PAINT- PT-2

WALL BASE - RB-1MANUFACTURER: ROPPETYPE: PINNACLE RUBBER BASECOLOR: 193 BLACK BROWNSIZE: 4"

Room Finish Schedule

021 COMPUTER LAB - - - - - GW - GW GW GW - - - - - CLNG PLAN - - - 021

A-2

01

MANUFACTURER: SHERWIN WILLIAMSTYPE: PAINTCOLOR: SW7693 STONEBRIARFINISH: SEMI-GLOSS

PAINT- PT-3MANUFACTURER: SHERWIN WILLIAMSTYPE: PAINTCOLOR: SW7006 EXTRA WHITEFINISH: EXTRA WHITE

CARPET TILE - CPT-1MANUFACTURER: BENTLEYTYPE: TECH UPD8 AFIRMA HARDBACKCOLOR: GEOMETRY 400005SIZE: 18"x36"

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

006 OPEN OFFICE RTF-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 006

A-2

01-M

ACOUSTIC CEILING TILE - ACT-1MANUFACTURER: ARMSTRONGMODEL: ULTIMA 1951 BEVELED TEGULARCOLOR: WHITESIZE: 24" x 24" (15

16" Grid)

RESILENT TILE FLOORING - RTF-1MANUFACTURER: ARMSTRONGTYPE: TBDCOLOR: TBDSIZE: 12" x 12"

006.1 CLOSET RTF-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 006.1

006.2 OFFICE RTF-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 006.2

006.3 OFFICE RTF-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 006.3

A-2

03

006.4 OFFICE RTF-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 006.4

005 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 005

005.1 HEARING FITTING ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 005.1

005.2 LAB STROAGE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 005.2

005.3 SUPERVISOR OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 005.3

005.4 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 005.4

013 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 013

013.1 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 013.1

013.2 OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 013.2

015 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 015

023 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 023

023.1 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 023.1

025 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 025

103 RECEPTION CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 103

103.1 TYPICAL OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 103.1

103.3 STROAGE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 103.3

105 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 105

105.1 TYPICAL OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 105.1

105.3 WORK ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 105.3

300 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 300

300.01 LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 300.01

300.02 TYPICAL OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 300.02

300.05 TREATMENT CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 300.05

300.06 TYPICAL OBSERVATION CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 300.06

300.11 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 300.11

304 TEACHING LAB CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 304

322.1 UNISEX ADA EXST - - EXST - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 322.1

326 UNISEX ADA EXST - - EXST - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 326

325 OBSERVATION CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 325

328 OPEN OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 328

328.01 TYPICAL OFFICE CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 328.01

328.1 WORK ROOM CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 328.1

327 TREATMENT CPT-1 - - RB-1 - GW PT-1 GW PT-1 GW PT-1 GW PT-1 - - - - - CLNG PLAN - - - 327

Page 4: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

variesse

e sc

hedu

lesee schedule

hollow metalframe

F1

see

sche

dule

variessee schedule

D1

provide acousticfirestop sealant allthrough-wallpenetrations - typical

SECTION AT DECK

acoustic tile ceiling onmetal suspensionsystem

base refer to roomfinish schedule

PLAN

7 1/4"6"

(actual)

SECTION AT FLOOR

SECTION AT CEILING

provide acousticfirestop sealant bothsides of partition asshown

runner stud atbase of partition

W1

Wall Composite:5

8" type x gyp bd, each side6" metal studs @ 16" o.c.w/ 5 1/2" sound attenuating batt

continuous firestop sealanteach side (typ)

existing structure

runner

1/2"

SMOKE TIGHTWALL

SECTION AT FLOOR

5/8" Soundbreak gyp bd, each side on1" Z channels @ 24" o.c.on existing wall construction

1 5/8"(actual)

provide acousticsealant both sides ofpartition as shown

base refer to roomfinish schedule

W2

PLAN

SECTION AT CEILING

2" (nominal)

runner stud atbase of partition

existing wall

existing structure

runner

continuous acoustic sealant

SECTION AT DECK

acoustic tile ceiling onmetal suspensionsystem

1 5/8"

2"

note: provide acousticsealant around allelectrical outlets andother wall penetrations

CARPET

TRANSITION STRIP

CERAMIC TILE

T1

refe

r to

plan

2"

1 2"

hollow metal frameattach/anchor per mfgrrecommendations

16 guage doublestuds at doorframes typicalexisting wall1/4" min shimspace (all sides)

continuous sealantall sides of frame

door (refer toschedule)

provide doorsilencers (3 perjamb min)

refer to plan

2"

12"

hollow metalframeattach/anchorper mfgrrecommendations

16 guage doublestuds at doorhead typical

existing wall

continuoussealant allsides of frame

door (refer toschedule)

provide doorsilencers (3 perjamb min)

SERIESDOORMAT.

DOOR AND FRAME SCHEDULE

WIDTH

DOOR DATADW

G. N

o.No. QTY.DOOR DOOR

THICK.HEIGHT TYPESIZE DOOR

LOUVERGAUGESERIES HRS.RATING

TRANSOMGLASS DETAILJAMB

FRAME DATA

FINISH TYPEFRAME

MAT.FRAME No.

DOORHARDWARE

FINISHGLASSHRS.

RATING No.GROUP

REMARKS

Door

Unde

rcut

A-30

03A-100 Scale: 1/4" = 1'-0"

Door Types

NOTE: GENERAL CONTRACTOR TO REVIEW DOOR HARDWARE WITH OWNER PRIOR TO ANY INSTALLATION

DETAILHEAD

D001.1 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 1 DOOR TO BE SMOKE TIGHT - - D001.1

DOOR REMARKS:

1. Contractor to coordinate with WSU reuse of existing doors and frames from

storage. Verify quantity, size, fire rating and condition of existing doors prior

to any installation.

02A-100 Scale: 1/4" = 1'-0"

Frame Types

HARDWARE GENERAL NOTES:

General notes:

1. Contractor shall verify all existing field conditions and notify architect

immediately if that which exists differs from that which is shown on

drawings.

2. All work to comply with Federal, State and Local codes, laws and

ordinances.The requirements of ICC/ANSI A117.1 and the Americans with

disabilities act (ADA) are to be fully satisfied. All work shall meet the most

stringent requirements of both including, but not limited to clearances,

limitations, accessories, etc.

3. These drawings are prepared in accordance with the limited services for

which the architect was contracted. The architect makes no representation

that the interpretation of these documents will result in complete compliance

with the ADA.

4. All doors required to be labeled shall be set in labeled frames and identified

with UL label and be provided with approved self-closing devices and

positive latching hardware.

5. All designated exit doors shall be equipped with the required egress

hardware.

6. Supplier shall meet with owner to establish MK keying system and provide a

combinated cylinder for each locking device as direct by owner. Supplier

shall submit key schedule for final approval. Furnish 2 change keys per

cylinder and 2 master keys total.

7. Supplier shall furnish and provide all necessary reinforcements, brackets,

fasteners, spacers and fillers to provide a complete functioning opening.

8. Supplier shall furnish complete shop drawings including; vertical typed

hardware schedule, product data sheets and warranty information following

DHI prescribed methods.

DOOR HARDWARE:

Hardware Set 1 (Classroom)

1 set Smoke Seal 797B Blk Reese

Hardware Set 2 - Passage set (Always Unlocked)

3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ

1 ea. Passage Set MR 126 DJSJ 32D PDQ

1 ea. Wall Stop 102 26D PDQ

Hardware Set 3 - Classroom Lock (Lock/Unlock)

3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ

1 ea. Classroom lock MR 148 DJSJ-SFL 32D PDQ

1 ea. Wall Stop 102 26D PDQ

Hardware Set 4 - Office Lock (Lock/Unlock)

3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ

1 ea. Office Lock MR 116 DJSJ-SFL 32D PDQ

1 ea. Wall Stop 102 26D PDQ

Hardware Set 5 - Classroom Lock (Lock/Unlock) + Closer

3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ

1 ea. Classroom Lock MR 148 DJSJ-SFL 32D PDQ

1 ea. Closer 7101 BC EDA (Pull side Mount) AL PDQ

1 ea. Wall Stop 102 26D PDQ

1 ea. Kickplate 98 10 x 2" LDW 32D PDQ

Hardware Set 6 - Add Smoke Seal

1 set Smoke Seal 797B Blk Reese

1 set Flex Smoke Astragal 103C x 103C AL Reese

Hardware Set 7 - Classroom Lock (Lock/Unlock) + Closer

3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ

1 ea. Classroom Lock MR 148 DJSJ-SFL 32D PDQ

1 ea. Closer 7101 BC PA Regular Arm (Pull side Mount) AL PDQ

1 ea. Wall Stop 102 26D PDQ

1 ea. Kickplate 98 10 x 2" LDW 32D PDQ

Hardware Set 8 -Privacy Set w/ indicator (Lock/Unlock) + Closer

3 ea. Butt Hinge 35STBB 4545 NRP 26D PDQ

1 ea. Privacy Set w/ indicator MR 148 DJSJ-SFL 32D PDQ

1 ea. Closer 7101 BC PA Regular Arm (Pull side Mount) AL PDQ

1 ea. Wall Stop 102 26D PDQ

1 ea. Kickplate 98 10 x 2" LDW 32D PDQ

Door Schedule & Wall Types01

A-30 Scale: 1 1/2" = 1'-0"

W-2 WALL TYPE 01A-30 Scale: 1 1/2" = 1'-0"

W-1 WALL TYPE

A-2

01-B

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

D001.2 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 1 SOOR TO BE SMOKE TIGHT - - D001.2

D001.3 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 1 DOOR TO BE SMOKE TIGHT - - D001.3

D001.4 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 1 DOOR TO BE SMOKE TIGHT - - D001.4

D001.5 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 1 DOOR TO BE SMOKE TIGHT - - D001.5

D001.6 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 1 DOOR TO BE SMOKE TIGHT - - D001.6

D005.1 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - PASSAGE 2 - - - D005.1

D005.2 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - CLASSROOM 3 - - - D005.2

D005.3 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - OFFICE 4 - - - D005.3

D005.4 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - OFFICE 4 - - - D005.4

D023.1 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - CLASSROOM 5 - - - D023.1

D025 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - CLASSROOM 5 DOOR TO BE RELOCATED FROM RCKHAM - - D025

D030 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 6 DOOR TO BE SMOKE TIGHT - - D030

D040 1 EX EX - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 6 DOOR TO BE SMOKE TIGHT - - D040

D300 1 3'-0" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - CLASSROOM 7 - - - D300

D322.1 1 3'-6" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - PRIVACY 8 - - - D022.1

D327 1 3'-6" 7'-0" D1 SCW - - - - - - - F1 - HM - - - - - CLASSROOM 7 - - - D327

D330 1 3'-0" 7'-0" - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 6 DOOR TO BE SMOKE TIGHT - - D330

D340 1 3'-0" 7'-0" - - - - - - - - - F1 - HM - - - - - SMOKE SEAL 6 DOOR TO BE SMOKE TIGHT - - D340

03A-002 Scale: NTS

Floor Transition

Page 5: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

UP

Storage103.3

Office103.4

Office103.5

Recept103

Office103.1

Office103.2

Mech

Lobby

UP

Lounge100

Jan100.2

Mech100.1

UP

DN

DN

DN

EXTERIORCIRCULATION

SECONDFLOOR ABOVE

BASEMENTFLOOR BELOW

BASEMENTFLOOR BELOW

ELEV

NIC NIC

NIC

NIC

AD-101

01A-101 Scale: 1/8" = 1'-0"

First Floor Plan - Demolition WorkPrentis Building

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building 1st Floor Plan -Demolition Work

LEGEND

Remove existing gypsum and metal stud wall full height

walls

floors

01

GENERAL DEMOLITION NOTES

A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.

B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.

C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.

D. room numbers and room names on all existing drawings relate only to demolitionsheets.

E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.

F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.

G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.

H. repair all surfaces and components damaged during demolition and construction.

I. coordinate scope and extent of demolition work with new work plans and details.

items to be removed

existing items to remain

remove existing door & frame assembly, including all relatedhardware.40

doors

50

misc items

DEMOLITION NOTES

all existing furniture, file cabinets, and other movable equipmentthat is not tagged to remain is to be removed by WSU

30

ceilings

remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.

51 Remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.Remove portion of existing gypsum & metal stud wall for new door02

21Existing flooring and wall base to be removed. Prep floor fornew finish per specifications. Patch and repair existingconcrete floor slab.

22 Existing flooring to remain.

52 Remove existing toilet partition.

Remove portion of existing gypsum & metal stud wall for new one-way mirror03

31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.

I. coordinate scope and extent of demolition work with new work plans and details.

J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.

K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.

L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications

53 Remove existing millwork

54 Remove existing signage

Remove portion of existing block wall. provide temporary structural support03

21

21 21 21

21 21

21

54

5050 50

50

50 50

Page 6: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

Teaching Lab027

Lab025

Lab023

ComputerLab021

Classroom017

Classroom019

PLC016.11

Tele016.10

Mech016

Mech016.2

Mech016.3

Mech016.4

Lab015

Lab013

Classroom010

Classroom008

Office006

Office006.2

Office006.3

Office006.4

Classroom004

Classroom002

Women031

Men029

Jan012

EngOffice014

Storage020

Storage007

C&IT030

2'-0"10'-8"9'-4" 6'-8"

STAIR001

STAIR030

STAIR040

Mech016

Mech016

AD-101-B

01A-101 Scale: 1/8" = 1'-0"

Basement Plan - Demolition WorkPrentis Building

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building Basement FloorPlan - Demolition Work

LEGEND

Remove existing gypsum and metal stud wall full height

walls

floors

01

GENERAL DEMOLITION NOTES

A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.

B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.

C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.

D. room numbers and room names on all existing drawings relate only to demolitionsheets.

E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.

F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.

G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.

H. repair all surfaces and components damaged during demolition and construction.

I. coordinate scope and extent of demolition work with new work plans and details.

items to be removed

existing items to remain

remove existing door & frame assembly, including all relatedhardware.40

doors

50

misc items

DEMOLITION NOTES

all existing furniture, file cabinets, and other movable equipmentthat is not tagged to remain is to be removed by WSU

30

ceilings

remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.

51 Remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.Remove portion of existing gypsum & metal stud wall for new door02

21Existing flooring and wall base to be removed. Prep floor fornew finish per specifications. Patch and repair existingconcrete floor slab.

22 Existing flooring to remain.

52 Remove existing toilet partition.

Remove portion of existing gypsum & metal stud wall for new one-way mirror03

31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.

I. coordinate scope and extent of demolition work with new work plans and details.

J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.

K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.

L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications

53 Remove existing millwork

54 Remove existing signage

Remove portion of existing block wall. provide temporary structural support03

21 5021 50

21 50

21 50

21 50

21 50

21 50

21 50

21 50

21 50

04 04

53 5340

40404040

404040

40

40

21 50

Page 7: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

Open to Below

OpenOffice105

WorkRoom105.3

Office105.4

Office105.5

Office105.2

Office105.1

DN DNUP

Elev

Open to Below

UP

DN

Jan102.1

Lounge102

DN

NIC NIC

NIC

NIC

NIC

AD-101-M

01A-101 Scale: 1/8" = 1'-0"

Mezzanine Floor Plan - Demolition WorkPrentis Building

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building Mezzanine FloorPlan - Demolition Work

LEGEND

Remove existing gypsum and metal stud wall full height

walls

floors

01

GENERAL DEMOLITION NOTES

A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.

B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.

C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.

D. room numbers and room names on all existing drawings relate only to demolitionsheets.

E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.

F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.

G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.

H. repair all surfaces and components damaged during demolition and construction.

I. coordinate scope and extent of demolition work with new work plans and details.

items to be removed

existing items to remain

remove existing door & frame assembly, including all relatedhardware.40

doors

50

misc items

DEMOLITION NOTES

all existing furniture, file cabinets, and other movable equipmentthat is not tagged to remain is to be removed by WSU

30

ceilings

remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.

51 Remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.Remove portion of existing gypsum & metal stud wall for new door02

21Existing flooring and wall base to be removed. Prep floor fornew finish per specifications. Patch and repair existingconcrete floor slab.

22 Existing flooring to remain.

52 Remove existing toilet partition.

Remove portion of existing gypsum & metal stud wall for new one-way mirror03

31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.

I. coordinate scope and extent of demolition work with new work plans and details.

J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.

K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.

L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications

53 Remove existing millwork

54 Remove existing signage

Remove portion of existing block wall. provide temporary structural support03

21 50 21 50

21 50

21 5021 50

21 50

53

53

54

Page 8: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

Observation300.1

Treatment300.09

Office300.08

Treatment300.05

Observation300.06

Office300.07

OpenOffice300.11

OpenOffice300

Office300.04

Office300.03

Office300.02

TEACHINGLAB304

Office303

WORKROOM300.01

UNISEX ADARESTROOM322.1

WOMEN'SRESTROOM326

Office328.01

Office328.02

Office328.03

Office328.04

Office328.05

COPY328.06

Office328.07

OpenOffice328

Office328.08

Office328.09

WorkRoom328.10

Observation325

Treatment327

STAIR330

STAIR340

6'-8"

3'-5"5'-0"

1'-8"

5'-0"

A701

05

03

04

AD-103

01A-101 Scale: 1/8" = 1'-0"

Third Floor Plan - Demolition WorkPrentis Building

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building 3rd Floor Plan -Demolition Work

LEGEND

Remove existing gypsum and metal stud wall full height

walls

floors

01

GENERAL DEMOLITION NOTES

A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.

B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.

C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.

D. room numbers and room names on all existing drawings relate only to demolitionsheets.

E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.

F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.

G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.

H. repair all surfaces and components damaged during demolition and construction.

I. coordinate scope and extent of demolition work with new work plans and details.

items to be removed

existing items to remain

remove existing door & frame assembly, including all relatedhardware.40

doors

50

misc items

DEMOLITION NOTES

all existing furniture, file cabinets, and other movable equipmentthat is not tagged to remain is to be removed by WSU

30

ceilings

remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.

51 Remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.Remove portion of existing gypsum & metal stud wall for new door02

21Existing flooring and wall base to be removed. Prep floor fornew finish per specifications. Patch and repair existingconcrete floor slab.

22 Existing flooring to remain.

52 Remove existing toilet partition.

Remove portion of existing gypsum & metal stud wall for new one-way mirror03

31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.

I. coordinate scope and extent of demolition work with new work plans and details.

J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.

K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.

L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications

53 Remove existing millwork

54 Remove existing signage

Remove portion of existing block wall. provide temporary structural support03

5021 5021 5021 5021 5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

5021

50215021

01

01 0101

01

02

0303

22

22

40

40

40 40 40

40

40

40

51

52

5152

22

53

Page 9: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

Teaching Lab027

Lab025

Lab023

ComputerLab021

Classroom017

Classroom019

PLC016.11

Tele016.10

Mech016

Mech016.2

Mech016.3

Mech016.4

Lab015

Lab013

Classroom010

Classroom008

Office006

Office006.2

Office006.3

Office006.4

Classroom004

Classroom002

Women031

Men029

Jan012

EngOffice014

Storage020

Storage007

C&IT030

STAIR001

STAIR030

STAIR040

Mech016

Mech016

EXST EXST

EXST

EXSTEXST

EXST

xLFxLFxLFxLF

xLF

xLF xLF

xLF xLF xLF

xLFxLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF xLF

xLFxLF

xLF xLF

xLFxLF

xLF xLF

xLFxLF

LF

LF

LF

LFLF

LF

LF LF

LF LF

LFLF

LF

AD-104-B

01A-101 Scale: 1/8" = 1'-0"

Basement RC Plan - Demolition WorkPrentis Building

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building Basement ReflectedCeiling Plan - Demolition Work

LEGEND

Remove existing gypsum and metal stud wall full height

walls

floors

01

GENERAL DEMOLITION NOTES

A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.

B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.

C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.

D. room numbers and room names on all existing drawings relate only to demolitionsheets.

E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.

F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.

G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.

H. repair all surfaces and components damaged during demolition and construction.

I. coordinate scope and extent of demolition work with new work plans and details.

items to be removed

existing items to remain

remove existing door & frame assembly, including all relatedhardware.40

doors

50

misc items

DEMOLITION NOTES

all existing furniture, file cabinets, and other movable equipmentthat is not tagged to remain is to be removed by WSU

30

ceilings

remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.

51 Remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.Remove portion of existing gypsum & metal stud wall for new door02

21Existing flooring and wall base to be removed. Prep floor fornew finish per specifications. Patch and repair existingconcrete floor slab.

22 Existing flooring to remain.

52 Remove existing toilet partition.

Remove portion of existing gypsum & metal stud wall for new one-way mirror03

31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.

I. coordinate scope and extent of demolition work with new work plans and details.

J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.

K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.

L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications

53 Remove existing millwork

54 Remove existing signage

Remove portion of existing block wall. provide temporary structural support03

3050

30

30

31 31

3131

31

31

31

31

31

31

31

31

31

31

31

31

31

31

31

Page 10: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

Observation300.1

Treatment300.09

Office300.08

Treatment300.05

Observation300.06

Office300.07

OpenOffice300.11

OpenOffice300

Office300.04

Office300.03

Office300.02

TEACHINGLAB304

Office303

WORKROOM300.01

UNISEX ADARESTROOM322.1

WOMEN'SRESTROOM326

Office328.01

Office328.02

Office328.03

Office328.04

Office328.05

COPY328.06

Office328.07

OpenOffice328

Office328.08

Office328.09

WorkRoom328.10

Observation325

Treatment327

STAIR330

STAIR340

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXSTEXST

EXST EXST

EXST

EXSTEXSTEXST

EXST

EXST

EXST

EXST EXST EXST EXST

EXST

EXST EXSTEXST

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF xLF

xLFxLF

xLF xLF

xLFxLF

xLF xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF xLF xLF

xLF

xLF

xLF xLF xLF

xLF xLF xLF

xLF xLF

xLF xLF

xLF

xLF xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF xLF

xLF

xLF xLF

xLF

xLF

xLF

xLF xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLFxLFxLF

xLFxLFxLF

xLF

AD-105

01A-101 Scale: 1/8" = 1'-0"

Third Floor Plan - Demolition WorkPrentis Building

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building 3rd Floor reflectedCeiling Plan - Demolition Work

LEGEND

Remove existing gypsum and metal stud wall full height

walls

floors

01

GENERAL DEMOLITION NOTES

A. Demolition contractor shall be familiar with entire scope of new work prior to startingdemolition work.

B. all demolition floor plans, wall layouts, door and window locations, patterns havebeen shown for reference only. The General Contractor must field verify alldimensions and room layouts prior to new work and notify the architect of anydeviations from what is shown. All site visits must be coordinated with WSUConstruction Project Manager minimum 24 hours in advance of the site visit(s). Allwork outside of defined construction zone must be coordinated with WSUConstruction manager.

C. refer to electrical and mechanical drawings for extent of electrical and mechanicaldemolition work and for additional information.

D. room numbers and room names on all existing drawings relate only to demolitionsheets.

E. all existing items removed shall be returned to the owner for re-use or disposed ofoff site if rejected by the owner. do not damage any millwork during demolition.

F. owner is responsible for removing any loose equipment such as furniture, movableequipment, trash cans, etc.

G. all door hardware shall be removed from demolished doors, cleaned and turnedover to the owner.

H. repair all surfaces and components damaged during demolition and construction.

I. coordinate scope and extent of demolition work with new work plans and details.

items to be removed

existing items to remain

remove existing door & frame assembly, including all relatedhardware.40

doors

50

misc items

DEMOLITION NOTES

all existing furniture, file cabinets, and other movable equipmentthat is not tagged to remain is to be removed by WSU

30

ceilings

remove existing acoustic tile ceiling, grid to reamin. Coordinateremoval of mechanical, plumbing and electrical items with M&Edemolition drawings.

51 Remove existing plumbing fixture. Refer or MEP dwgs for demo plumbing work.Remove portion of existing gypsum & metal stud wall for new door02

21Existing flooring and wall base to be removed. Prep floor fornew finish per specifications. Patch and repair existingconcrete floor slab.

22 Existing flooring to remain.

52 Remove existing toilet partition.

Remove portion of existing gypsum & metal stud wall for new one-way mirror03

31 remove existing light fixtures. Coordinate removal of othermechanical, plumbing and electrical items with M&E demolitiondrawings.

I. coordinate scope and extent of demolition work with new work plans and details.

J. demolition work required is not necessarily limited to what is shown on thedemolition plans. the intent is to remove all mechanical, electrical, and architecturalitems required to facilitate new construction.

K. unless noted otherwise when removing existing suspended lay-in ceiling assembly,including furring channels, wall angles and suspension wires.

L. where new plumbing is indicated, saw cut & remove existing concrete floor slab forinstallation of new plumbing. coordinate with mechanical and plumbing drawingsfor locations. Contractor must take precautions not to damage existing structuralfloor slab and is responsible to repair any damage due to new work. All slabremoval work must be coordinated with EMU for allowable time of work and perspecifications

53 Remove existing millwork

54 Remove existing signage

Remove portion of existing block wall. provide temporary structural support03

30

40

30

3030

31

31

31

31

31

31

31

31

31

31

Page 11: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

UP

Storage103.3

Office103.4

Office103.5

Recept103

Office103.1

Office103.2

Mech

Lobby

UP

Lounge100

Jan100.2

Mech100.1

UP

DN

DN

DN

EXTERIORCIRCULATION

SECONDFLOOR ABOVE

BASEMENTFLOOR BELOW

BASEMENTFLOOR BELOW

ELEV

NIC NIC

NIC

NIC

A-201

01A-101 Scale: 1/8" = 1'-0"

First Floor Plan - New WorkPrentis Building

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building 1st Floor Plan -New Work

GENERAL NOTES

1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.

2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.

3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.

4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.

5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER

NEW WORK NOTES:

FLOORS

INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE

DOORS AND WINDOWS

WALLS

NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11

31

32

NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.

01

CEILINGS

PREP AND PAINT GYPSUM CEILING41

CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL, AND VERTICALBLINDS AS NECESSARY

42

NEW FLOOR BASE, REFER TO FINISH SCHEDULE12

PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE

33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS

34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE

INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING

13

MISC.

72

LIGHTING

74

RELOCATED PROJECTION SCREEN

INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.

51

75

INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST

77

INSTALL NEW WHITE BOARD

INSTALL NEW FLAT SCREEN

78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW

71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS

79 INSTALL NEW SIGNAGE. COORDINATE WITH WSUFACILITIES MANAGER

70 INSTALL NEW MILLWORK, REFER TO INTERIORELEVATIONS

35 NEW 72" CABINET STYLE DOOR ON CONCEALED HINGES.

43 EXISTING CEILING TILE AND GRID TO REMAIN. REPLACE ANY DAMAGEDCEILING TILES OR GRID.

36 RE-CODE EXISTING DOOR SECURITY

1112

1112

1112

1112

1112

1112

32 32

32

32

32 32

79

7474

74

74

7474

74

Page 12: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

DN

UP

DN

UP

UP

UP

soundbooth#2

soundbooth#1

soundbooth#1

soundbooth#2

EP

soundbooth#1

EP

soundbooth#1

future soundbooth

Teaching Lab027

Lab025

Lab023

ComputerLab021

Classroom017

Classroom019

PLC016.11

Tele016.10

Mech016

Mech016.2

Mech016.3

Mech016.4

Lab015

Lab013

Office013.2

Office013.1

Classroom010

Classroom008

Office006

Office006.2

Office006.3

Office006.4

Classroom004

Classroom002

Women031

Men029

Jan012

EngOffice014

Lab023.1

Storage020

Storage007

Lab005

Hearing AidFitting005.1

LabStorage005.2

SupervisorOffice005.3

Office005.4

C&IT030

NIC

NIC

NIC

NICNICNICNIC

NICNIC

NIC

NIC

NIC

NIC

NIC NIC

NIC

NIC

NIC

W1

W1

W1

D013.2

W1

W1

W1

W1

W1

W1

W1

W1

D013.2

STAIR001

STAIR030

STAIR040

D040

D005.3

D005.4

D005.1 D005.2

D001.4

D001.5

D001.6

D001.3

D001.2

D001.1

D030

D025

D023.1

W1 W1

W1 W1

W1

W1

10'-9"

12'-1

1/2

"6'-

1 1/

2"10

'-4"

9'-1"

10'-0

"v.i

.f.2'-

0"v.i

.f.

9'-0"

eq.

eq.

10'-8"v.i.f.

17'-5

"

5'-5" 5'-6"

W2

W2

W2

W2

W2

W2

W2

W2

W2

W2

W2

W2

W2

W2W2

W2

W2

W2

A701 02

W2

W2

W2

W2

Mech016NIC

Mech016NIC

A-201-B

01A-101 Scale: 1/8" = 1'-0"

Basement Plan - New WorkPrentis Building

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building Basement FloorPlan - New Work

GENERAL NOTES

1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.

2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.

3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.

4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.

5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER

NEW WORK NOTES:

FLOORS

INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE

DOORS AND WINDOWS

WALLS

NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11

31

32

NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.

01

CEILINGS

PREP AND PAINT GYPSUM CEILING41

CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL, AND VERTICALBLINDS AS NECESSARY

42

NEW FLOOR BASE, REFER TO FINISH SCHEDULE12

PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE

33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS

34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE

INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING

13

MISC.

72

LIGHTING

74

RELOCATED PROJECTION SCREEN

INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.

51

75

INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST

77

INSTALL NEW WHITE BOARD

INSTALL NEW FLAT SCREEN

78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW

71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS

79 INSTALL NEW SIGNAGE. COORDINATE WITH WSUFACILITIES MANAGER

70 INSTALL NEW MILLWORK, REFER TO INTERIORELEVATIONS

35 NEW 72" CABINET STYLE DOOR ON CONCEALED HINGES.

43 EXISTING CEILING TILE AND GRID TO REMAIN. REPLACE ANY DAMAGEDCEILING TILES OR GRID.

36 RE-CODE EXISTING DOOR SECURITY

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

11 12

1112

1112

1112

1112

31

3131

31

31

3131

31313131

31 31 31

35

71

71

70

72

72

74

74

74

74

74

74

74

74

74

74 74

74

74

74

74

74

74

74

74

74

78

01

01

01

01

01

01

01

01

0101

0101

01

01

36 36 36

36

36

36

36

36

1112

74 74

74 74

Page 13: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

Open to Below

OpenOffice105

WorkRoom105.3

Office105.4

Office105.5

Ref

Office105.2

Office105.1

DN DNUP

Elev

Open to Below

UP

DN

Jan102.1

Lounge102

DN

NIC NIC

NIC

NIC

NIC

A70101

A-201-M

01A-101 Scale: 1/8" = 1'-0"

Mezzanine Floor Plan - New WorkPrentis Building

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building Mezzanine Plan -New Work

GENERAL NOTES

1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.

2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.

3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.

4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.

5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER

NEW WORK NOTES:

FLOORS

INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE

DOORS AND WINDOWS

WALLS

NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11

31

32

NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.

01

CEILINGS

PREP AND PAINT GYPSUM CEILING41

CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL, AND VERTICALBLINDS AS NECESSARY

42

NEW FLOOR BASE, REFER TO FINISH SCHEDULE12

PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE

33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS

34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE

INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING

13

MISC.

72

LIGHTING

74

RELOCATED PROJECTION SCREEN

INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.

51

75

INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST

77

INSTALL NEW WHITE BOARD

INSTALL NEW FLAT SCREEN

78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW

71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS

79 INSTALL NEW SIGNAGE. COORDINATE WITH WSUFACILITIES MANAGER

70 INSTALL NEW MILLWORK, REFER TO INTERIORELEVATIONS

35 NEW 72" CABINET STYLE DOOR ON CONCEALED HINGES.

43 EXISTING CEILING TILE AND GRID TO REMAIN. REPLACE ANY DAMAGEDCEILING TILES OR GRID.

36 RE-CODE EXISTING DOOR SECURITY

1112

1112

1112

111211

1211

1270

71

Page 14: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

MECHANICAL AREA

MECH SHAFT

DNDN

COOLING TOWER

NIC

300

305303

ELEV

NIC NIC NIC NIC

NIC NIC

NIC

NIC

NIC NIC NIC NIC NIC NIC NIC NICObservation300.1

Treatment300.09

Office300.08

Treatment300.05

Observation300.06

Office300.07

OpenOffice300.11

OpenOffice300

Office300.04

Office300.03

Office300.02

TEACHINGLAB304

Office303

WORKROOM300.01

UNISEX ADARESTROOM322.1

WOMEN'SRESTROOM326

Office328.01

Office328.02

Office328.03

Office328.04

Office328.05

COPY328.06

Office328.07

OpenOffice328

Office328.08

Office328.09

NIC

NIC

WorkRoom328.10

Observation325

Treatment327

W1D30

0

W2

W2

W1

W1W1

D33

0

STAIR330

STAIR340

D34

0

D32

7

D32

2.1

9"

W2

W2

W2

W2

W2

A701

05

03

04

A-203

01A-101 Scale: 1/8" = 1'-0"

Third Floor Plan - New WorkPrentis Building

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building 3rd Floor Plan - NewWork

GENERAL NOTES

1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.

2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.

3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.

4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.

5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER

NEW WORK NOTES:

FLOORS

INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE

DOORS AND WINDOWS

WALLS

NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11

31

32

NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.

01

CEILINGS

PREP AND PAINT GYPSUM CEILING41

CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL, AND VERTICALBLINDS AS NECESSARY

42

NEW FLOOR BASE, REFER TO FINISH SCHEDULE12

PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE

33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS

34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE

INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING

13

MISC.

72

LIGHTING

74

RELOCATED PROJECTION SCREEN

INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.

51

75

INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST

77

INSTALL NEW WHITE BOARD

INSTALL NEW FLAT SCREEN

78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW

71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS

79 INSTALL NEW SIGNAGE. COORDINATE WITH WSUFACILITIES MANAGER

70 INSTALL NEW MILLWORK, REFER TO INTERIORELEVATIONS

35 NEW 72" CABINET STYLE DOOR ON CONCEALED HINGES.

43 EXISTING CEILING TILE AND GRID TO REMAIN. REPLACE ANY DAMAGEDCEILING TILES OR GRID.

36 RE-CODE EXISTING DOOR SECURITY

1112

01 01

01

01

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

1112

111211

1211

12

1112

1112

1112

1112

1112

1112

1112

13

13

31

31

31

31 31

32323232323232323232

32

32

32

32

32 32 32 32 32 32 32

32 32 32 32 32

32

32

32

32

323232323232323232

32

34

34

34

7070

70

70

71

71

74

7474747474

74

74

7474

74

74

74

74

74

74

74

74

74

74

74

74

74

74

74

7474 74

74

74

74

74

74

74

74

74

747474

77

75

78

7878

Page 15: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

DN

UP

DN

UP

UP

UP

soundbooth#2

soundbooth#1

soundbooth#1

soundbooth#2

EP

soundbooth#1

EP

soundbooth#1

future soundbooth

Teaching Lab027

Lab025

Lab023

ComputerLab021

Classroom017

Classroom019

PLC016.11

Tele016.10

Mech016

Mech016.2

Mech016.3

Mech016.4

Lab015

Lab013

Office013.2

Office013.1

Classroom010

Classroom008

Office006

Office006.2

Office006.3

Office006.4

Classroom004

Classroom002

Women031

Men029

Jan012

EngOffice014

Lab023.1

Storage020

Storage007

Lab005

Hearing AidFitting005.1

LabStorage005.2

SupervisorOffice005.3

Office005.4

C&IT030

NIC

NIC

NIC

NICNICNICNIC

NICNIC

NIC

NIC

NIC

NIC

NIC NIC

NIC

NIC

NIC

STAIR001

STAIR030

STAIR040

Mech016NIC

Mech016NIC

EXST EXST

EXST

EXSTEXST

EXST

xLFxLFxLFxLF

xLF

xLF xLF

xLF xLF xLF

xLFxLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF xLF

xLFxLF

xLF xLF

xLFxLF

xLF xLF

xLFxLF

LF

LF

LF

LFLF

LF

LF LF

LF LF

09

A701

LFLF

LF

A-301-B

01A-101 Scale: 1/8" = 1'-0"

Basement Plan - New WorkPrentis Building

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building Basement FloorRC Plan - New Work

GENERAL NOTES

1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.

2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.

3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.

4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.

5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER

NEW WORK NOTES:

FLOORS

INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE

DOORS AND WINDOWS

WALLS

NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11

31

32

NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.

01

CEILINGS

PREP AND PAINT GYPSUM CEILING41

CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL, AND VERTICALBLINDS AS NECESSARY

42

NEW FLOOR BASE, REFER TO FINISH SCHEDULE12

PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE

33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS

34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE

INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING

13

MISC.

72

LIGHTING

74

RELOCATED PROJECTION SCREEN

INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.

51

75

INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST

77

INSTALL NEW WHITE BOARD

INSTALL NEW FLAT SCREEN

78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW

71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS

79 INSTALL NEW SIGNAGE. COORDINATE WITH WSUFACILITIES MANAGER

70 INSTALL NEW MILLWORK, REFER TO INTERIORELEVATIONS

35 NEW 72" CABINET STYLE DOOR ON CONCEALED HINGES.

43 EXISTING CEILING TILE AND GRID TO REMAIN. REPLACE ANY DAMAGEDCEILING TILES OR GRID.

36 RE-CODE EXISTING DOOR SECURITY

4141

42

42

42

42

51

5151

51

51

51

51 51

51 51

43

43

43

43

43

43

43

43

43

43

43

43

43

43

43

Page 16: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

MECHANICAL AREA

MECH SHAFT

DNDN

COOLING TOWER

NIC

300

305303

ELEV

NIC NIC NIC NIC

NIC NIC

NIC

NIC

NIC NIC NIC NIC NIC NIC NIC NICObservation300.1

Treatment300.09

Office300.08

Treatment300.05

Observation300.06

Office300.07

OpenOffice300.11

OpenOffice300

Office300.04

Office300.03

Office300.02

TEACHINGLAB304

Office303

WORKROOM300.01

UNISEX ADARESTROOM322.1

WOMEN'SRESTROOM326

Office328.01

Office328.02

Office328.03

Office328.04

Office328.05

COPY328.06

Office328.07

OpenOffice328

Office328.08

Office328.09

NIC

NIC

WorkRoom328.10

Observation325

Treatment327

STAIR330

STAIR340

EXST

EXST

EXST

EXST

EXST

EXST

EXST

EXSTEXST

EXST EXST

EXST

EXSTEXSTEXST

EXST

EXST

EXST

EXST EXST EXST EXST

EXST

EXST EXSTEXST

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF xLF

xLFxLF

xLF xLF

xLFxLF

LF

LF LF

LF LF

LF LF

LF LF

LF

xLF xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF xLF xLF

xLF

xLF

xLF xLF xLF

xLF xLF xLF

xLF xLF

xLF xLF

xLF

xLF xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF xLF

xLF

xLF xLF

xLF

xLF

xLF

xLF xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLF

xLFxLFxLF

xLFxLFxLF

xLF

A-303

01A-101 Scale: 1/8" = 1'-0"

Third Floor RC Plan - New WorkPrentis Building

FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building 3rd Floor reflectedCeiling Plan - New Work

GENERAL NOTES

1) GENERAL CONTRACTOR AND SUB TRADES ARERESPONSIBLE TO VERIFY ALL EXISTING DIMENSIONSAND NOTIFY THE ARCHITECT OF ANY AND ALLDISCREPANCIES.

2) GENERAL CONTRACTOR SHALL BE FAMILIAR WITHENTIRE SCOPE OF NEW WORK AND PROCEED WITHWORK IN ACCORDANCE WITH NEW WORK.

3) NEW WORK FLOOR PLANS, WALL LAYOUTS, DOORAND WINDOW LOCATIONS AND PATTERNS HAVE BEENSHOWN FOR REFERENCE ONLY. THIS DRAWING ISNOT INTENDED TO SHOW ALL CONDITIONS, MATERIALPATTERNS AND LAYOUTS. INSPECT SITE PRIOR TOSTART OF CONSTRUCTION TO DETERMINE THE FULLSCOPE OF WORK.

4) REFER TO ELECTRICAL / MECHANICAL DRAWINGS FOREXTENT OF NEW ELECTRICAL AND MECHANICALWORK. COORDINATE BETWEEN ALL DISCIPLINES.REPORT DISCREPANCIES TO ARCHITECT.

5) ALL PATCH PAINTING TO INCLUDE ENTIRE/COMPLETEWALL - EDGE TO EDGE & CORNER TO CORNER

NEW WORK NOTES:

FLOORS

INSTALL NEW DOOR, REFER TO DOOR SCHEDULE. PROVIDEHARDWARE PER SCHEDULE

DOORS AND WINDOWS

WALLS

NEW FLOOR FINISH, REFER TO FINISH SCHEDULE11

31

32

NEW WALL CONSTRUCTION, PREP AND PAINT, REFER TO WALL TYPESAND DETAILS.

01

CEILINGS

PREP AND PAINT GYPSUM CEILING41

CLEAN EXISTING WINDOW SYSTEM, REPAIR WINDOW SILL, AND VERTICALBLINDS AS NECESSARY

42

NEW FLOOR BASE, REFER TO FINISH SCHEDULE12

PROVIDE NEW ACOUSTIC CEILING TILE AND GRID, REFER TO FINISHSCHEDULE

33 DOOR TO RECEIVE NEW CARD READER, REFER TO ELECTRICAL DRAWINGS

34 WINDOW TO RECEIVE NEW BLACK-OUT SHADE

INFILL AREA WHERE WALL WAS REMOVED WITH NEWFLOORING TO MATCH EXISTING

13

MISC.

72

LIGHTING

74

RELOCATED PROJECTION SCREEN

INSTALL NEW LIGHTING FIXTURES, REFER TO ELECTRICALDRAWINGS FOR FULL EXTENT OF WORK.

51

75

INSTALL NEW LOOSE FURNITURE, REFER WSUFUNITURE LIST

77

INSTALL NEW WHITE BOARD

INSTALL NEW FLAT SCREEN

78 INSTALL NEW ONE-WAY MIRROR. ARROW INDICATESDIRECTION OF VIEW

71 INSTALL NEW PLUMBING FIXTURE, REFER TO MEPDRAWINGS

79 INSTALL NEW SIGNAGE. COORDINATE WITH WSUFACILITIES MANAGER

70 INSTALL NEW MILLWORK, REFER TO INTERIORELEVATIONS

35 NEW 72" CABINET STYLE DOOR ON CONCEALED HINGES.

43 EXISTING CEILING TILE AND GRID TO REMAIN. REPLACE ANY DAMAGEDCEILING TILES OR GRID.

36 RE-CODE EXISTING DOOR SECURITY

43

43

434343

43

43

43

43

43 43

43

43 43

43

42

43

43

43

43

43 43

43

43

43

43

4343

51

51

51

51

51

51 51

51 51

51

Page 17: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

Ceiling8'-0"

Fin Flr0'-0"

06

A701

6 eq8'-9 1/2"

3'-0"

2'-0"

3'-0"

6 eq

8'-9 1/2"3'-0"

2 eq

3'-0"2 eq

base cabinet w/ incounter sstl sink

upper cabinets w/adjustable shelves

2'-10

"

07

A701

3'-0"

relocated millwork fromRackham, coordinatemove with WSU projectmanager

new p-lam countertopand back splash

relocated upper cabinetsfrom Rackham, coordinatemove with WSU projectmanager

relocated millwork fromRackham, coordinatemove with WSU projectmanager

new p-lam countertopand back splash

relocated open shelvingfrom Rackham, coordinatemove with WSU projectmanager

3'-0"

3'-0"

new p-lam countertopand back splash

relocated millwork fromRackham, coordinatemove with WSU projectmanager

new p-lam countertopand back splash

relocated open shelvingfrom Rackham, coordinatemove with WSU projectmanager

relocated millwork fromRackham, coordinatemove with WSU projectmanager

3'-0"

2 eq

3'-0"2 eq

2'-10

"

07

A701

Ceiling8'-0"

Fin Flr0'-0"

base cabinet w/ in countersstl sink

upper cabinets w/adjustable shelves

p-lam end panel

wire pull

wire pull

2 1/2"

4"

2'-2"

3/4" veneer coreplywood cabinet base

cont. sealanttypical

1'-2 1/8"

2'-6"

16 gauge sheetmetal or provide firerated wood blocking

wood blocking

melamine finish on1/2" veneer coreplywood

16 gauge sheet metalor provide fire ratedwood blocking

adjustable p lam shelf

P-Lam on 3/4" veneer plywood doorpanel, provide HD concealed hinges(TYP), refer to elevations for locations

provide fire ratedwood blocking (TYP)

34" veneer core door panel,

(TYP), refer to elevations forlocations

4"

Fin Floor100'-0"

7'-6"

cabi

net d

oor

4" wall base (refer toroom finish schedule)

side wall backsplashbeyond

white melaminefinished interiorcabinet construction

P-lam drawer face, refer toelevation for locations &quantity in base cabinet,provide lockingmechanism

3/4" p-lam back splashat wet locations only

p-lam on 3/4" plywood,refer to finish schedule

1 1/

2"

2'-0"

3'-0"

wire pull

2 1/2"

4"

2'-10

"

2'-2"

3/4" veneer coreplywood cabinet base

cont. sealanttypical

wood blocking

melamine finish on1/2" veneer coreplywood

16 gauge sheet metalor provide fire ratedwood blocking

adjustable shelf

P-Lam on 3/4" veneerplywood door panel,provide HD concealedhinges (TYP), refer toelevations for locations

paint new gyp bd, refer toroom finish schedule (typ)

4"

Fin Floor100'-0"

cabi

net d

oor

p-lam on 3/4" plywood,refer to finish schedule

SS-1 bull-nosing w/ 3/4"radius

4" wall base (refer toroom finish schedule)

side wall backsplashbeyond

3/4" p-lam back splashat wet locations only

1 1/

2"

surface mounted sstl sink(Kohler Stacatto, K-3362-1-NA)

single hole faucet (KohlerForte' K-10415-CP,brushed chrome)

wire pull

1'-2 1/8"

2'-6"

16 gauge sheetmetal or provide firerated wood blocking

provide fire ratedwood blocking (TYP)

34" veneer core door panel,

(TYP), refer to elevations forlocationswhite melamine

finished interiorcabinet construction

2'-2"

Bottom of Beam9'-1"Ceiling Height

9'-0"new suspendedceiling system

exst CMU infill between W8sections.5/8" gyp board on metal stud at16" o.c. typ.

new W8 steel lintel, bear on exstCMU min 16" each end.

new gyp bdbulkhead

±10"

08

A701

location of new W8'sabove, Provide 61/2"x16"x3/8" metal plateat each end.

10'-8"

#4 vert. rebar in centerof CMU cells, grout cellssolid. rebar to extend 12"min. into existing/newfoundation

location of new W8'sabove, Provide 61/2"x16"x3/8" metal plateat each end.

6'-8"

A-701 FOR

BID

S

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

designed

issue: date:

key plan:

Prentis Building - RackhamRelocation

Nov. 13, 2018Owner Review 60% CD's

NM Project Number - 18113.0

WAYNE STATEUNIVERSITY

Facilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

Prentis Building

JK

JK

JK

DB

AG

WSU : 00

consultants:

Nov. 27, 2018Owner Review 90% CD's

Dec. 04, 2018Review 100% CD's

Dec. 11, 2018For Bids

Prentis Building Interior Elevations,Sections and Details

01A701 Scale: 3/8" = 1'-0"

Work Room 105.3 Millwork Detail

02A701 Scale: 3/8" = 1'-0"

005.1 Millwork DetailHearing Aid Fitting Room

03A701 Scale: 3/8" = 1'-0"

Work Room 300.01 Millwork Detail

04A701 Scale: 3/8" = 1'-0"

Work Room 300.01 Millwork Detail

05A701 Scale: 3/8" = 1'-0"

Work Room 300.01 Millwork Detail

06A701 Scale: 1" = 1'-0"

Millwork Section

07A701 Scale: 1" = 1'-0"

Millwork Section

08A701 Scale: 3/4" = 1'-0"

Lab 005 Header Detail

09A701 Scale: 3/4" = 1'-0"

Lab 005 Header Section

Page 18: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

DIRECTION OF AIR FLOW

FLEXIBLE DUCT

MANUAL VOLUME DAMPER

RISE IN DIRECTION OF AIR FLOWR

DUCT CAP

DROP IN DIRECTION OF AIR FLOWD

DUCT DOWN

DUCT UP

SUPPLY/OUTSIDE AIR DUCT SECTION

RETURN AIR DUCT SECTION

EXHAUST/RELIEF AIR DUCT SECTION

4-WAY DIFFUSER WITH BLANKOFF IN ONE DIRECTION

CD-16/115

AIR TERMINAL PROPERTIES SYMBOLNECK SIZE/CFM

TERMINAL AIR BOX (REFER TO SCHEDULE)###

### TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)

OPPOSED BLADE DAMPER (REFER TO SCHEDULE)

PARALLEL BLADE DAMPER (REFER TO SCHEDULE)

DIFFERENTIAL PRESSURE SENSOR

CARBON MONOXIDE SENSORC

CARBON DIOXIDE SENSORC2

HUMIDISTAT SENSORH

HUMIDISTAT/SENSOR (DUCT MOUNTED)H

OCCUPANCY SENSORO

PRESSURE SENSOR/MONITORP

PRESSURE SENSOR (DUCT MOUNTED)P

THERMOSTAT/SENSORT

TEMPERATURE SENSOR (DUCT MOUNTED)T

THERMOSTAT/SENSOR WITH HEAVY DUTY ENCLOSURET

VENTILATION SYMBOL LIST

SYMBOL: DESCRIPTION:

AIRFLOW MEASUREMENT SYMBOLXX - AHU SYMBOLY - SEQUENTIAL NUMBER

XX-Y

NOT ALL SYMBOLS MAY APPLY.

SERIES FAN POWERED TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)

PARALLEL FAN POWERED TERMINAL AIR BOX w/REHEAT COIL (REFER TO SCHEDULE)

VENTILATION ABBREVIATION KEY

ABBR: DESCRIPTION:

AD ACCESS DOOR

ABOVE FINISHED FLOORAFF

NC NEW CONNECTION

CFSD CONTROL/FIRE/SMOKE DAMPER

EA EXHAUST/RELIEF AIR

FD FIRE DAMPER

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FSD FIRE/SMOKE DAMPER

MA MIXED AIR

OA OUTSIDE AIR

RA RETURN AIR

SA SUPPLY AIR

SD SMOKE DAMPER

TRANSFER DUCTTD

EFD EXISTING FIRE DAMPER

TERMINAL AIR BOXTAB

TYPICALTYP

UNO UNLESS NOTED OTHERWISE

CEILING DIFFUSER - EXISTINGCD-E

N.C. NORMALLY CLOSED

NOT IN CONTRACTNIC

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

NAME

1VIEW NAME1/8" = 1'-0"

LEVEL NAME

10' - 0" HEIGHT ABOVE PROJECT 0' - 0"

1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL

NO R HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)

NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)

EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)

LINE TYPE KEY:

MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.

2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.

3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.

4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.

5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.

6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.

8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.

9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.

10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE.PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.

11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.

12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.

13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.

14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR

STARTERS, SWITCHES, AND DISCONNECTS.16. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL

EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER

NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.

MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE GENERAL CONTRACTOR CONSTRUCTION MANAGER. ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.

5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.

6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.

7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN ACTIVE.

9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.

10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.

11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.

1. THE SIZE OF EACH BRANCH DUCT TO A TERMINAL AIR BOX (TAB) SHALL MATCH THE TAB’S INLET SIZE UNLESS THE BRANCH IS GREATER THAN 6 FEET IN LENGTH, IN WHICH CASE THE BRANCH SHOULD BE INCREASED ONE DUCT SIZE, OR NOTED OTHERWISE.

2. ALIGN TEMPERATURE SENSORS WITH LIGHT SWITCHES AND WHEN IN CLOSE PROXIMITY TO EACH OTHER.

3. PROVIDE ACCESS DOORS AT ALL DUCT MOUNTED EQUIPMENT.4. EXISTING AIR INLET AND OUTLET CFM SHOWN ON DRAWINGS ARE FROM EXISTING

DRAWINGS, AND ARE FOR REFERENCE ONLY. CONTRACTOR SHALL USE PRE-BALANCE VALUES, AND NOT EXISTING CFM SHOWN ON DRAWINGS.

5. CONTRACTOR MAY REUSE PORTIONS OF EXISTING DUCT PROVIDED SIZES AND PRESSURE CLASSES ARE CORRECT, DUCT IS THOROUGHLY CLEANED AND FREE OF DEFECTS, AND ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS ARE SEALED AS SPECIFIED FOR NEW DUCTWORK.

6. CLEAN ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK UPSTREAM OF ALL NEW CONNECTIONS PER SPECIFICATION SECTION 23 31 00.

VENTILATION GENERAL NOTES:

1. BEFORE ANY DEMOLITION WORK IS BEGUN A COMPLETE AIR BALANCE TEST SHALL BE PERFORMED BY THE TESTING, ADJUSTING AND BALANCING (TAB) CONTRACTOR ON EXISTING AIR HANDLERS AND EXHAUST FANS SERVING THE AREAS AFFECTED BY CONSTRUCTION. EQUIPMENT TO BE DEMOLISHED DOES NOT REQUIRE TESTING. PROVIDE AIR BALANCE TESTING ONLY ON EQUIPMENT THAT WILL CONTINUE TO BE USED TO SERVE RENOVATED AREAS AFTER THE CONSTRUCTION PHASE IS COMPLETED.

2. PROVIDE DUCT TRAVERSE READINGS AT LOCATIONS DESIGNATED ON THE DRAWINGS BY THE "AIRFLOW MEASUREMENT SYMBOL". THOSE MEASUREMENTS SHALL BE INCLUDED IN THE PRE DEMOLITION REPORT AND SHALL BE DESIGNATED WITH THE IDENTIFIER AS MARKED ON THE DRAWINGS. READINGS SHALL BE DESIGNATED WITH THE ROOM NAME AND NUMBER AS MARKED ON THE DRAWINGS. IF FLOOR PLANS DO NOT HAVE UNIQUE ROOM NAMES AND NUMBERS, TAB CONTRACTOR SHALL INCLUDE FLOOR PLAN WITH UNIQUE NUMBER DESIGNATIONS ASSIGNED TO READINGS THAT MATCH THOSE USED IN THE FINAL PRE-DEMOLITION REPORT. DRAWINGS THAT ARE HAND-MARKED WITH RED INK ARE ACCEPTABLE, PROVIDED THEY ARE LEGIBLE.

3. IN THE EVENT A DUCT TRAVERSE LOCATION AS MARKED ON THIS PLAN IS INACCESSIBLE FOR MEASUREMENT, THE TAB CONTRACTOR SHALL PERFORM THE TRAVERSE AT AN ALTERNATE LOCATION OR SHALL TAKE MULTIPLE DUCT TRAVERSES AND/OR READINGS AS REQUIRED TO DETERMINE THE AIRFLOW READING WHERE THE DUCT TRAVERSE SYMBOL IS SHOWN. IN THE EVENT TRAVERSES ARE TAKEN AT ALTERNATE LOCATION(S), TAB CONTRACTOR SHALL INCLUDE A DRAWING THAT SHOWS THE LOCATIONS WHERE THE ACTUAL MEASUREMENTS WERE TAKEN.

4. TAKE A DUCT STATIC PRESSURE READING AT EACH LOCATION WHERE A DUCT TRAVERSE READING IS TAKEN AND INCLUDE IN THE FINAL PRE-DEMOLITION TAB REPORT.

5. TAB CONTRACTOR SHALL COMPILE AND SUBMIT FOUR COPIES OF THE FINAL PRE-DEMOLITION REPORT WITHIN 10 WORKING DAYS AFTER THE FIELD MEASUREMENTS ARE COMPLETED. FINAL TAB REPORT SHALL BE SUBMITTED FOR REVIEW TO THE ARCHITECT/ENGINEER. TESTING SHALL INCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.

6. TAB CONTRACTOR SHALL PROVIDE DUCT TRAVERSE READINGS AT LOCATIONS DESIGNATED ON THE DRAWINGS BY THE "AIRFLOW MEASUREMENT SYMBOL". THOSE MEASUREMENTS SHALL BE INCLUDED IN THE POST-CONSTRUCTION REPORT AND SHALL BE DESIGNATED WITH THE IDENTIFIER AS MARKED ON THE CONSTRUCTION DRAWINGS. GRILLE AND DIFFUSER READINGS SHALL BE DESIGNATED WITH THE ROOM NAME AND NUMBER AS MARKED ON THE DRAWINGS. IF THE DRAWINGS DO NOT HAVE UNIQUE ROOM NAMES AND NUMBERS, TAB CONTRACTOR SHALL INCLUDE FLOOR PLANS WITH UNIQUE NUMBER DESIGNATIONS ASSIGNED TO TRAVERSES, GRILLES, AND DIFFUSERS THAT MATCH THOSE USED IN THE FINAL PRE-DEMOLITION REPORT. SIMILAR ROOM NAMES, NUMBERS, OR DESIGNATIONS SHALL BE USED TO SIMPLIFY THE CROSS- REFERENCING OF READINGS TAKEN BETWEEN PRE-DEMOLITION AND POST-CONSTRUCTION REPORTS.

7. BALANCING CONTRACTOR SHALL PRE-BALANCE ALL EXISTING SYSTEMS TO REMAIN PER SPECIFICATION SECTION 23 05 93. BALANCE READINGS WILL BE REQUIRED AT AIR OUTLETS AND DUCT TRAVERSES TO VERIFY EXISTING AIRFLOW TO UNAFFECTED SPACES.

TAB PRE-DEMOLITION NOTES:

1. AFTER CONSTRUCTION ACTIVITIES ARE COMPLETE, TESTING, ADJUSTING (TAB) AND BALANCING CONTRACTOR SHALL REBALANCE AIR HANDLING UNITS AND EXHAUST FANS AS REQUIRED TO ACHIEVE THE NEW AIRFLOW VALUES SHOWN ON THE CONSTRUCTION DRAWINGS.

2. AREAS SERVED BY THIS EQUIPMENT WHICH WERE NOT RENOVATED SHALL BE RE-BALANCED TO THE AIRFLOW RATES MEASURED BEFORE THE RENOVATION OCCURRED (REFER TO THE FINAL PRE- DEMOLITION REPORT).

3. IF DUCT TRAVERSE LOCATION AS MARKED ON THE DRAWINGS IS INACCESSIBLE FOR MEASUREMENT, THE TAB CONTRACTOR SHALL PERFORM THE TRAVERSE AT AN ALTERNATE LOCATION OR SHALL TAKE MULTIPLE DUCT TRAVERSES AND/OR GRILLE READINGS AS REQUIRED TO DETERMINE THE FLOW RATE. IN THE EVENT TRAVERSES ARE TAKEN AT AN ALTERNATE LOCATION(S), TAB CONTRACTOR SHALL INCLUDE A DRAWING THAT SHOWS THE LOCATIONS WHERE THE ACTUAL MEASUREMENTS WERE TAKEN.

4. A DUCT STATIC PRESSURE READING SHALL BE TAKEN AT EACH LOCATION WHERE A DUCT TRAVERSE READING IS TAKEN AND SHALL BE INCLUDED IN THE FINAL POST-CONSTRUCTION TAB REPORT.

5. TAB CONTRACTOR SHALL COMPILE AND SUBMIT COPIES OF THE FINAL POST-CONSTRUCTION TAB REPORT AS REQUIRED BY SECTION 23 05 93.

6. THE FINAL POST CONSTRUCTION REPORT SHALL INCLUDE ALL ITEMS REQUIRED IN THE SPECIFICATIONS.

TAB POST-CONSTRUCTION NOTES:

TEMPERATURE CONTROLS CONTRACTORT.C.C.

SECURITY CONTRACTORS.C.

CONSTRUCTION MANAGERC.M.

PLUMBING CONTRACTORP.C.

ELECTRICAL CONTRACTORE.C.

VENTILATION CONTRACTORV.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

FIRE PROTECTION CONTRACTORF.P.C.

HEATING CONTRACTORH.C.

MECHANICAL CONTRACTORM.C.

AUDIO/VISUAL CONTRACTORA.V.C.

ASBESTOS ABATEMENT CONTRACTORA.C.

BUILDING CODE: MBC 2015 EDITION

FIRE CODE: NFPA 13: 2013 EDITION

PLUMBING CODE: MBC 2015 EDITION

MECHANICAL CODE: MMC 2015 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2016EDITION

LIFE SAFETY CODE: NFPA 101 2015 EDITION

ENERGY CONSERVATION CODE: ASHRAE 90.1 2013

HEALTH DEPARTMENT CODE: CURRENT EDITION

LOCAL BUILDING CODE: CURRENT EDITION

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.

VENTILATION SHEET INDEXMH-000 VENTILATION COVERSHEET

MHD-101-B BASEMENT FLOOR DEMOLITION - VENTILATION

MHD-103 THIRD FLOOR DEMOLITION - VENTILATION

MH-101-B BASEMENT FLOOR - VENTILATION

MH-103 THIRD FLOOR PLAN - VENTILATION

MH-300 VENTILATION SCHEDULES & DETAILS

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

1:1

7 A

M

MH-000

VENTILATION COVERSHEET

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 19: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

001

013

015

040

030

030

007

020

014

012

029

031

002004

006.4

006.3

006.2

006008010

016.31

016.4

016.3

016.2

016

016.10

016.11

019017021

023

025

027

STAIR

Lab

Lab

STAIR

STAIR

C&IT

Storage

Storage

EngOffice

Jan

Men

Women

ClassroomClassroom

Office

Office

Office

OfficeClassroomClassroom

Mech

Mech

Mech

Mech

Mech

Tele

PLC

ClassroomClassroom ComputerLab

Lab

Lab

Teaching Lab

T

T

T

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

TB-E

TB-E

TB-E

TB-E

TB-E

TB-E TB-E TB-E

TB-E

TB-ETB-ETB-E TB-E

TB-E

TB-E

TB-E

TB-E

42x28 SA 37x28 SA 23x30 SA

22ø

SA

19x1

0 S

A

12x10 SA

22x10 SA

10x14 RA

10x14 SA

10x8 SA

10x8 SA

10x8 SA UP

10x8 SA UP

SR-E

24x12/320(TYP.2)

RR-E

36x10/0(TYP.2)

ST-1

ST-1

18x10 SA9ø SA10ø SA

11x10 SA

20x10 SA13x10 SA 13x10 SA

28x10 SA16x10 SA

16x10 SA

36x5

36x5

36x5

36x5

24x524x5

12x10 SA

19x10 SA

12x12 RA UP

11x10 SA

SR-E

14x8/400(TYP.2)

13x10 SA

13x10

12ø SA

10ø SA28x10 SA

16x10 SA

16x10 SA15ø SA

12ø SA

SR-E

14x8/400(TYP.2)

30x6

SR-E

14x8/0(TYP.2)

30x630x630x630x6

12x10 SA

12x10 SA

24x10 SA14x10 SA

14x10 SA

10ø SA

13ø SA 10ø SA

11ø SA

20ø SA 18ø SA

18ø

SA

20x8

SA

16x8 SA

18x6

8x8 SA12x8 SA

26x6

4x4 EA UP

4x6 EA

8x4 EA

EG-E

8x6/90

EG-E

18x3/170

6x11 EA6x14 EA

30x630x6

30x630x6

30x623x28 SA UP

88x28 RA UP

20ø SA17ø SA

TB-E

RHC-E

SR-E

32x12/910

RR-E

24x12/600

RR-E

24x12/600

SR-E

32x12/910

TB-E

RHC-E

11ø SA

22x1

0 S

A

RR-E

24x12/600

SR-E

36x10/910

RR-E

30x12/910

22x1

0 S

A

22x1

0 S

A

11ø SA

11ø SA

SR-E

24x12/320

RR-E

24x12/600 RR-E

36x10/0SR-E

36x8/910

RHC-E

TB-E

11ø SA

14ø SA

24"x8" LINED

WITH 1"ACOUSE

INSULATION

24"x8" LINED

WITH 1"ACOUSE

INSULATION

11x10 SA11x10 SA

10ø SA

12ø SA

CRAC

1

3

CRAC

2

2

2

3

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

1:2

4 A

M

MHD-101-B

BASEMENT FLOOR DEMOLITION

- VENTILATION

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR DEMOLITION - VENTILATION

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

SHEET VENTILATION NOTES :

1. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

2. CAP ALL OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.

KEYNOTES:

1. REMOVE EXISTING COMPUTER ROOM AIR CONDITIONING (CRAC) UNIT, AND ITS ASSOCIATED DUCT, DIFFUSERS, PIPING, CONTROLS, SENSORS & WIRING IN ITS ENTIRETY. REMOVE PIPING BACK TO THE MAIN AND CAP AT MAIN. SALVAGE UNIT AND RETURN TO OWNER. CONFIRM WITH THE OWNER REGARDING THE SCOPE OF DEMO & SALVAGE.

2. PRIOR TO DEMOLITION, MEASURE SUPPLY/ RETURN/ EXHAUST AIR FLOWS AT ALL EXISTING TERMINAL AIR DEVICES AND AIR INLETS/ OUTLETS. LABEL ALL DEVICES AND AND CREATE AN AIR BALANCE REPORT DESCRIBED ON SHEET MH-000.

3. REMOVE EXISTING RETURN AIR GILLE. CLEAN & PREPARE TO EXTEND THE DUCT TO MOUNT GRILLE ON THE NEW SHAFT WALL. COORDINATE W/ ARCH.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 20: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

T

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

28”x8” LINED

DUCT CONN. TO

CL’G SPACE OVER

RM.*355 (DET

“B” SIMILAR)

13ø SA

10ø SA

10ø SA

10x7 EA

6x4 EA

10x7 EA

18x9 SA

13x9 SA 10x9 SA 10x6 SA

SD-E

SD-ESD-E

26x9 SA

TB-ERHC-E

11ø SA

11ø SA

11"⌀ DN

10ø SA

10ø SA

11ø SA

EG-E

15x3/165(typ-2)

EG-E

10x3/110(typ-2)

SD-E

SD-E

SD-E

18x9 SA21x9 SA

26x9

SA

10x8 SA

14x8 SA

10x8 SA

10x6 SA10x6 SA

10x9 SA

2 3

1

44

4

4

4

4

4

4 4 4 4 4

4 4 4 44 4 4

44

4 4 4 4 4 4

4

4

4

4

4

444

44

5

55

5

5

5

55

5

5 5 5 5 5 5

5

5

5

5

5

55

66

EG-E

24x10/300

EG-E

14x8/300

EG-E

6x4/50

5

5

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

1:2

5 A

M

MHD-103

THIRD FLOOR DEMOLITION -

VENTILATION

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

NO R HT

1/8" = 1'-0"2 THIRD FLOOR DEMOLITION - VENTILATION

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

SHEET GENERAL NOTES :

1. COORDINATE ALL DEMOLITION WORK WITH ARCHITECTURAL AND ELECTRICAL AND ELECTRICAL DEMOLITION WITH OWNER'S PROJECT REPRESENTATIVE.

2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

3. REMOVE ALL INDICATED DUCTWORK AND EQUIPMENT COMPLETELY INCLUDING ALL RELATED ITEMS INCLUDING HANGERS, SUPPORTS, CONTROLS AND ACCESSORIES.

4. CAP ALL THE OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.

KEYNOTES:

1. DEMOLISH EXISTING DUCTWORK, CEILING SUPPLY & RETURN DIFFUSERS AND ASSOCIATED ACCESSORIES BACK TO THE POINT AS SHOWN.

2. REMOVE EXISTING VAV BOX TEMPERATURE SENSOR, DISCONNECT CONTROL AND PREPARE TO MOUNT THE SENSOR AT NEW LOCATION.

3. REMOVE EXISTING SUPPLY DIFFUSER, CLEAN AND PREPARE TO INSTALL AT NEW LOCATION.

4. REMOVE EXISTING SUPPLY AIR FLOOR REGISTER. CLEAN AND PREPARE FOR INSTALLATION OF NEW FLOOR REGISTERS. CONFIRM W/ THE OWNER & ARCH FOR THE EXISTING REGISTERS TO BE CLEANED & REUSED IN LIEU OF NEW REGISTERS.

5. DISCONNECT AND REMOVE EXISTING RETURN AIR GRILLE. CLEAN AND PREPARE FOR REINSTALLATION.

6. PRIOR TO DEMOLITION, MEASURE SUPPLY/ RETURN/ EXHAUST AIR FLOWS AT ALL EXISTING TERMINAL AIR DEVICES AND AIR INLETS/ OUTLETS. LABEL ALL DEVICES AND AND CREATE AN AIR BALANCE REPORT DESCRIBED ON SHEET MH-000.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 21: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

013.1

013.2 005.4

005.3

005.2

005.1005

023.1

sound

booth

#2

sound

booth

#1

sound

booth

#1

sound

booth

#2

sound

booth

#1

sound

booth

#1

future sound

booth

Office

Office Office

SupervisorOffice

LabStorage

Hearing AidFitting

Lab

Lab

001

013

015

040

030

030

007

020

014

012

029

031

002004

006.4

006.3

006.2

006008010

016.31

016.4

016.3

016.2

016

016.10

016.11

019017021

023

025

027

STAIR

Lab

Lab

STAIR

STAIR

C&IT

Storage

Storage

EngOffice

Jan

Men

Women

ClassroomClassroom

Office

Office

Office

OfficeClassroomClassroom

Mech

Mech

Mech

Mech

Mech

Tele

PLC

ClassroomClassroom ComputerLab

Lab

Lab

Teaching Lab

T

T

T

T

T

T

T

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

TB-E

TB-E

TB-E

TB-E

TB-E

TB-E TB-E TB-E

TB-E

TB-ETB-ETB-E TB-E

TB-E

TB-E

TB-E

TB-E

42x28 SA 37x28 SA 23x30 SA

22ø

SA

19x1

0 S

A

12x10 SA

22x10 SA

10x14 RA

10x14 SA

10x8 SA

10x8 SA

10x8 SA UP

10x8 SA UP

SR-E

24x12/320(TYP.2)

RR-E

36x10/0(TYP.2)

ST-1

ST-1

18x10 SA9ø SA10ø SA

11x10 SA

20x10 SA13x10 SA

13x10 SA

28x10 SA

16x10 SA

16x10 SA

36x5

36x5

36x5

36x5

24x524x5

12x10 SA

19x10 SA

12x12 RA UP

11x10 SA

SR-E

14x8/400(TYP.2)

13x10 SA

12ø SA

10ø SA 28x10 SA

16x10 SA

16x10 SA

15ø SA

12ø SA

SR-E

14x8/400(TYP.2)

30x6

SR-E

14x8/0(TYP.2)

30x630x630x630x6

12x10 SA

12x10 SA

24x10 SA14x10 SA

14x10 SA

10ø SA

13ø SA 10ø SA

11ø SA

20ø SA 18ø SA

18ø

SA

20x8

SA

16x8 SA

18x6

8x8 SA12x8 SA

26x6

4x4 EA UP

4x6 EA

8x4 EA

EG-E

8x6/90

EG-E

18x3/170

6x11 EA6x14 EA

30x6

30x630x630x6

23x28 SA UP

88x28 RA UP

SR-E

14x8/200

CD-1

8/130

NEW VAV - B-1

8x8

NC

NCCD-1

8/130NEW VAV - B-2 8x8

NC

CD-1

8/100

10x10

NEW VAV-B-6

NC

CD-1

8/150

NEWVAV - B-5

8x86ø

CD-1

8/150

CD-1

8/100

NEWVAV - B-4 8x8

NC

CD-1

8/100

NEWVAV - B-3

1

1

1

1

5

2

2

2

2

2

1

NC

NC

SR-E

14x8/400

NC

3

SA

SA4

NEW VAV-B-7

1 8x8 SA

4

8ø SA

NC

4

SA

10ø

SA

SA 8

ø S

A

NEWVAV - B-8

4

4

SA

SA

28x10/19x10

100 CFM150 CFM

4

150 CFM

100 CFM

100 CFM

150 CFM

5

6 6

6

NC

1

77

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

1:1

9 A

M

MH-101-B

BASEMENT FLOOR -

VENTILATION

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

SHEET GENERAL NOTES :

1. COORDINATE FINAL DUCT AND PIPING ROUTES WITH EXISTING DUCT, PIPING ON SITE.

2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

3. CAP ALL OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.

KEYNOTES:

1. INSTALL AIR TERMINAL BOXES AND THEIR ASSOCIATED TEMPERATURE SENSORS, CONTROLS AND SUPPLY/ RETURN/ EXHAUST INLETS/OUTLETS AS SHOWN. INSTALLATION SHALL PER DETAILS ON MH-300. AIR TERMINAL BOX INSTALLATION SHALL PER MANUFACTURER INSTRUCTION AND PROVIDE SUFFICIENT CLEARANCE & SERVICE SPACES. UNIT CONTROLLER SHALL BE COMPATIABLE W/ EXISTING BUILDING CONTROL SYSTEM AND SHALL BE CONFIRMED BY THE OWNER.

2. RR-1 WITH SOUND TRAP. DUCT SIZE 24X12.3. CAP DUCTWORK IF THE DEMOED CRAC UNIT IS CONNECTED TO MAIN AIR SUPPLY DUCT.4. CONTRACTOR IS TO VERIFY AND REPORT TO ENGINEER/ ARCH IF THE EXISTING RELOCATED SOUND BOOTH

HAS ITS OWN VENTILATION FANS INSTALLED ON THE BOOTH TO PROVIDE A CIRCULATION AIR OR BOOTH REQUIRES FACILITY TO PROVIDE VENTILATION AIR. IF THE RELOCATED BOOTH REQUIRES FACILITY AIR, BALANCE THE SUPPLY AIR TO THE BOOTH TO CFM SHOWN.

5. REINSTALL EXISTING WALL SUPPLY GRILLE & DUCT FITTINGS AT NEW LOCATION SHOWN TO ACCOMODATE NEW WALL.

6. REBALANCE TO EXISTING AIR FLOW INDICATED ON PREDEMOLITION AIR BALANCE REPORT WHERE NO NEW AIR FLOW INFORMATION IS INDICATED ON THE DRAWING.

7. CLEAN & REINSTALL EXISTING AIR GRILLE. EXTEND EXISTING DUCT TO ACCOMODATE NEW SHAFT. COORDINATE W/ ARCH.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 22: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

327

325

328.10

328.09

328.08

328

328.07

328.06

328.05

328.04

328.03

328.02

328.01

326

322.1

300.01

303

304 300.02 300.03

300.04

300

300.11 300.07

300.06

300.05

300.08

300.09300.1

Treatment

Observation

WorkRoom

Office

Office

OpenOffice

Office

COPY

Office

Office

Office

Office

Office

WOMEN'SRESTROOM

UNISEX ADARESTROOM

WORKROOM

Office

TEACHINGLAB Office Office

Office

OpenOffice

OpenOffice Office

Observation

Treatment

Office

TreatmentObservation

T

T

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

28”x8” LINED

DUCT CONN. TO

CL’G SPACE OVER

RM.*355 (DET

“B” SIMILAR)

13ø SA

10ø SA

10ø SA

10x7 EA

6x4 EA

10x7 EA

18x9 SA

13x9 SA 10x9 SA 10x6 SA

SD-E

SD-ESD-E

26x9 SA

TB-E RHC-E

11ø SA

11ø SA

11"⌀ DN

10ø SA

10ø SA

11ø SA

EG-E

15x3/165(typ-2)

EG-E

10x3/110(typ-2)

10x6 SA

10x9 SA

18x9 SA21x9 SA

26x9

SA

18x8 SA 10x8 SASD-E

SD-E

SD-E

SD-E

CD-1

8/160

CD-1

8/160

10x88ø

NEW VAV-3-1

1

2

NC -TYPICAL OF 4

2

NC

2

NC

2

NC

2

NC -TYPICAL OF 4

2

NC -TYPICAL OF 2

2 NC

2

NC -TYPICAL OF 4

2

NC

2

NC2

NC

2

NC - TYPICAL OF 4

2

NC -TYPICAL OF 2

2

NC -TYPICAL OF 2

2

NC -TYPICAL OF 4

2

NC

2

NC

2

NC

2

NC2

NC

2

NC

2

NC -TYPICAL OF 4

44

NC

SA

(N) CAP

(N) RG-1 12X24 W/ SOUND BOOT

5

6

3

33

3

3

3

33

3

3 3 3

3

3

3

3

3

3

3

3

33

3

3

3

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

1:2

1 A

M

MH-103

THIRD FLOOR PLAN -

VENTILATION

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

NO R

HT

1/8" = 1'-0"1 THIRD FLOOR PLAN - VENTILATION

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

SHEET GENERAL NOTES :

1. COORDINATE FINAL DUCT AND PIPING ROUTES WITH EXISTING DUCT, PIPING ON SITE.

2. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

3. CAP ALL OPEN ENDED DUCTWORK. DO NOT LEAVE ANY ABONDONED DUCT WORK IN THE AREA OF WORK.

4. PROVIDE ACCESS DOOR IN HARD CEILINGS WHERE NECESSARY TO PROVIDE ACCESS TO TERMINAL AIR BOXES AND OTHER EQUIPMENT LOCATED ABOVE CEILING.

5. PROVIDE ACCESS PANELS WHERE REQUIRED TO ALLOW ACCESS TO BALANCING DAMPER.

KEYNOTES:

1. INSTALL AIR TERMINAL BOXES AND THEIR ASSOCIATED TEMPERATURE SENSORS, CONTROLS AND SUPPLY/RETURN/EXHAUST INLETS/OUTLETS AS SHOWN. INSTALL PER DETAILS ON MH-300. AIR TERMINAL BOX INSTALLATION SHALL BE PER MANUFACTURER AND PROVIDE SUFFICIENT CLEARANCE & SERVICE SPACES. UNIT CONTROLLER SHALL BE COMPATIABLE W/ EXISTING BUILDING CONTROL SYSTEM AND SHALL BE CONFIRMED BY THE OWNER.

2. PROVIDE AND INSTALL NEW SUPPLY AIR REGISTER AT EXISTING LOCATION. REGISTER SHALL MATCH EXISTING SIZE, LOCATION, AND FINISH. CONFIRM W/ THE OWNER & ARCH FOR THE EXISTING REGISTERS TO BE CLEANED & REUSED IN LIEU OF NEW REGISTERS.

3. CLEAN & REINSTALL EXISTING RETURN AIR GRILLE TO EXISTING LOCATION. 4. REBALANCE TO EXISTING AIR FLOW INDICATED ON PREDEMOLITION AIR BALANCE

REPORT WHERE NO NEW AIR FLOW INFORMATION IS INDICATED ON THE DRAWING.5. REINSTALL EXISTING VAV BOX TEMPERATURE SENSOR, RECONNECT CONTROL BACK

TO EXISTING VAV AND CHECK THE VAV CONTROLS.6. CLEAN & REINSTALL EXISTING SUPPLY DIFFUSER AT THE NEW LOCATION. CAP THE

EXISTING DUCT AT THE DEMO POINT.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 23: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

NOTES:

1. THIS DETAIL APPLIES ONLY TO TAPS OFF WRAPPED DUCTS.2. THIS DETAIL APPLIES TO TERMINAL AIR BOXES WITH ROUND INLETS AND

RECTANGULAR OUTLETS.3. DUCT LEADING TO TAB INLET MUST BE STRAIGHT FOR 1.5 DIAMETER

UPSTREAM.4. MAINTAIN VAPOR BARRIER FROM MAIN TO BRANCH DUCT.

NYLON TIE WRAP, TWO REQUIREDFOR EACH END OF FLEXIBLE DUCT(TOTAL 4). INSTALL ONE TIE WRAPTO SECURE THE INNER LINER ANDONE TO SECURE THE OUTER SHELL.(TYP.)

PRE-MANUFACTURED CONICALTAKE-OFF WITH SELF-ADHESIVE NEOPRENE GASKET (EQUAL TO SHEET METAL CONNECTORS CONICAL E-Z TAP)

FASTEN WITH SELF-TAPPINGSHEETMETAL SCREWS (MIN. 4)

CUT DUCT OPENING TO MATCHLARGER TAKEOFF DIAMETER

INSULATED GALVANIZED DUCT

CUT HELIX AND INNER FABRIC HERE. SECURE WITH NYLON TIE. OVERLAP FLEX DUCT MINIMUM OF 2" ONTO RIGID DUCT. PROVIDE DUCT SEALER AT CONNECTION BETWEEN FLEX DUCT AND RIGID DUCT.

AIR FLOWTERMINAL AIR BOX

RECTANGULAR INSULATED DUCT

INSULATEDFLEX DUCT

INSULATED TRANSITION

REHEAT COIL (IF SCHEDULED),INSULATE PER SPECIFICATIONS.

3' MAX.

6" MIN.

. D

MAINTAIN MINIMUM WORKING CLEARANCE TO ELECTRICAL CONNECTIONS AS REQUIRED BY NFPA 70 (NATIONAL ELECTRIC CODE)

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

1:2

2 A

M

MH-300

VENTILATION SCHEDULES &

DETAILS

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

NOTES:1. SIZES INIDCATED ARE TYPICAL. REFER TO PLANS FOR ADDITIONAL REQUIRED SIZES AND CFM.

24 X 24 201-2000 22x22 24X24 30

RG-1 RETURN AIR GRILLE

12 X 12 0-200 10X10 12x12 30

CEILING MOUNTED SEE FLOOR PLAN ALUMINUM CONSTRUCTION

SG-1 SUPPLY AIR REGISTERSAME AS DUCT CONNECTION PLUS

FRAME1-450 12 X 8 30 DOUBLE DEFLECTION BLADES WALL MOUNTED

ALUMINUM CONSTRUCTION NECK MOUNTEDOPPOSED BLADE DAMPER

201-345 8" 8" 30

CD-1 SUPPLY AIR CEILING DIFFUSER 24 X 241-200 6" 6" 30

SQUARE LAY -IN CEILING MOUNTINGALUMINUM CONSTRUCTION NECK MOUNTEDOPPOSED BLADE DAMPER

MARK SERVICE MODULE SIZE CFM RANGEMIN DUCT

CONNECTION (IN)

NOMINALNECK SIZE

(IN)MAX NC DESCRIPTION REMARKS

DIFFUSER-REGISTER-GRILLE SCHEDULE

NO SCALE1 TERMINAL AIR BOX DETAIL

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

4. INSTALL A SIGN ON THE EXTERIOR OF THE AIR TERMINAL UNITS AT THE SERVICE ACCESS LOCATION INDICATING THE SOURCE AHU THAT IS PROVIDING THE SUPPLY AIR AND THE ROOMS THAT ARE BEING SERVED.

3. COIL ENTERING AIR TEMPS AND HEATING CAPACITIES BASED ON 48F PRIMARY AIR, 68F PLENUM AIR AND 72F ROOM HEATING SETPOINT.

2. FOR SINGLE DUCT VAV/CAV TERMINAL UNITS - DISCHARGE SOUND POWER DATA FOR 100% PRIMARY AIR VALVE FLOW IS TO BE ARI CERTIFIED AND IS NOT TO EXCEED 74 DB (REFERENCE 10 -12 WATTS) IN THE 2ND OCTAVE BAND AT THE MAXIMUM PRIMARY AIR FLOW INDICATED IN THE SCHEDULE AND WITH 1.5" W.C. INLET STATIC PRESSURE.

1. FOR SINGLE DUCT VAV/CAV TERMINAL UNITS - RADIATED SOUND POWER DATA FOR 100% PRIMARY AIR VALVE FLOW IS TO BE ARI CERTIFIED AND IS NOT TO EXCEED 66 DB (REFERENCE 10 -12 WATTS) IN THE 2ND OCTAVE BAND AT THE MAXIMUM PRIMARY AIR FLOW INDICATED IN THE SCHEDULE AND WITH 1.5" W.C. INLET STATIC PRESSURE.

NOTES:

VAV-3-1 OPEN OFFICE 300.11 320 150 8 <30 <30 SEE MFGR. 150 6.5 55 95 <0.1 180 160 0.6 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL

VAV-B-8 LAB 025 SOUND BOOTH 300 200 6 <30 <30 SEE MFGR. 200 7.6 55 90 <0.1 180 160 0.8 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL

VAV-B-7 LAB 015 SOUND BOOTH 150 100 6 <30 <30 SEE MFGR. 100 3.8 55 90 <0.1 180 160 0.4 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL

VAV-B-6 OFFICE 005.4 300 100 6 <30 <30 SEE MFGR. 200 7.6 55 90 <0.1 180 160 0.8 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL

VAV-B-5 SUPERVIOR OFFICE 005.3 200 60 6 <30 <30 SEE MFGR. 100 3.8 55 90 <0.1 180 160 0.4 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL

VAV-B-4 HEARING AID FITTING005.1 250 75 6 <30 <30 SEE MFGR. 100 3.8 55 90 <0.1 180 160 0.4 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL

VAV-B-3 LAB 023.1 200 100 6 <30 <30 SEE MFGR. 100 3.8 55 90 <0.1 180 160 0.4 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL

VAV-B-2 OFFICE 013.2 150 50 6 <30 <30 SEE MFGR. 75 2.8 55 90 <0.1 180 160 0.3 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL

VAV-B-1 OFFICE 013.1 150 50 6 <30 <30 SEE MFGR. 75 2.8 55 90 <0.1 180 160 0.3 0.5 TITUS ESV CONTROLLER TO BE CONFIRM W/ OWNER, UNIT WITH TWO ROW COIL

CLG MAX. CLG. MIN. RADIATED NC DISCH. NC HTG. AIR FLOW HTG. MBH EAT ºF LAT ºF APD IN. WG. EWT ºF LWT ºF FLUID GPM MAX. WPD FT.MARK SERVICE

CFM RANGE

INLET SIZE (IN.)

SOUND LEVELSMINIMUM INLET

PRESSURE IN. WG.

HOT WATER HEATING INFORMATION

BASIS OF DESIGN NOTES

NEW VARIABLE AIR VOLUME BOX SCHEDULE - HOT WATER HEATING

Page 24: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

PLUMBING SYMBOL LIST

SYMBOL: DESCRIPTION:

PIPE SERVING FIXTURE ON FLOOR ABOVE(EXAMPLE: FD = FLOOR DRAIN)FD

PITCH PIPE IN DIRECTION

RD-16"(1000)

ROOF DRAIN PROPERTIES SYMBOLSIZE (ROOF SQ. FT.)

DIELECTRIC CONNECTION

UNION/FLANGE

BALANCING VALVE (NUMBER INDICATES GPM)GPM

CHECK VALVE

REDUCER - REFERENCE SPECIFICATIONFOR CONCENTRIC/ECCENTRIC AND FOT/FOB

PIPE CAP

PIPE DOWN

PIPE UP OR UP/DOWN

DIRECTION OF FLOW IN PIPE

NEW CONNECTION

SHUTOFF VALVE NORMALLY OPEN

SHUTOFF VALVE NORMALLY CLOSED

ACID VENTAV

ACID WASTEAW

COLD WATER - POTABLECW

DT DRAIN TILE

SANITARY DRAINAGE (GREASE SANITARY DRAINAGE)GSAN

HOT WATER - POTABLEHW

HOT WATER CIRCULATING - POTABLEHWC

HOT WATER - POTABLE NUMBER INDICATES TEMPHW140

HOT WATER CIRC. - POTABLE NUMBER INDICATES TEMPHWC140

PUMPED DISCHARGEPD

GREASE VENTGV

COMPRESSED AIRCA

DEIONIZED WATERDI

DRAIND

G NATURAL GAS

NOT ALL SYMBOLS MAY APPLY.

SAFETY/RELIEF VALVE

PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P

TEMPERATURE SENSOR WITH WELLT

THERMOMETER WITH WELL (DIAL TYPE)T

THERMOMETER WITH WELL (FILLED TYPE)

GRV GAS REGULATOR VENT

PIPE CONTINUATION

PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P

ROUTE TO DRAIN

PLUMBING ABBREVIATION KEY

BATHTUBBT

CO CLEANOUT

CLINICAL SINKCS

DRINKING FOUNTAINDF

EMERGENCY EYEWASHEE

FLOOR CLEANOUTFCO

FLOOR DRAINFD

GARBAGE DISPOSERGD

GREASE INTERCEPTORGI

I.E. INVERT ELEVATION (FOR REFERENCE ONLY)

LAVATORYLAV

MOP BASINMB

MIXING VALVEMV

SINKSK

TRAP PRIMERTP

WATER CLOSETWC

WALL CLEANOUTWCO

WATER HEATERWH

EMERGENCY SHOWERES

EMERGENCY SHOWER/EYEWASHESE

ELECTRIC WATER COOLEREWC

VENT THROUGH ROOFVTR

AD ACCESS DOOR

ABOVE FINISHED FLOORAFF

BFP BACKFLOW PREVENTER

NC NEW CONNECTION

NOT IN CONTRACTNIC

ABBR: DESCRIPTION:

TYPICALTYP

UNLESS NOTED OTHERWISEUNO

EXISTINGE

DIALYSIS BOXDB

CATCH BASINCB

CAST IRONCI

DUCTILE IRONDI

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

NAME

1VIEW NAME1/8" = 1'-0"

LEVEL NAME

10' - 0" HEIGHT ABOVE PROJECT 0' - 0"

1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL

NO R

HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)

NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)

EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)

LINE TYPE KEY:

TEMPERATURE CONTROLS CONTRACTORT.C.C.

SECURITY CONTRACTORS.C.

AUDIO/VISUAL CONTRACTORA.V.C.

ASBESTOS ABATEMENT CONTRACTOR

HEATING CONTRACTORH.C.

PLUMBING CONTRACTORP.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

VENTILATION CONTRACTORV.C.

ELECTRICAL CONTRACTORE.C.

A.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

MECHANICAL PHASING NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO GENERAL CONTRACTOR'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.

2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.

3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.

4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.

5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.

6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.

8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.

9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.

10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE.PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.

11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.

12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.

13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.

14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR

STARTERS, SWITCHES, AND DISCONNECTS.16. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL

EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER

NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.

MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE GENERAL CONTRACTOR CONSTRUCTION MANAGER. ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.

5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.

6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.

7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN ACTIVE.

9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.

10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.

11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.

1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.

2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.

3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.

4. ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.38745. INVERT ELEVATIONS ARE FROM EXISTING DRAWINGS AND MAY NOT BE ACCURATE. VERIFY

ALL ELEVATIONS BEFORE BEGINNING WORK.6. VERIFY UNDERGROUND PIPE SIZES, INVERT ELEVATIONS, AND LOCATIONS PRIOR TO

BEGINNING ANY WORK.7. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO

PLUMBING FIXTURES.8. FOR CLARITY, NOT ALL VALVES HAVE BEEN SHOWN. PROVIDE SHUTOFF VALVES IN

DOMESTIC WATER PIPING SERVING EACH ROOM WITH FIXTURES. ANGLE STOPS SHALL NOT BE CONSIDERED SHUTOFF VALVES.

9. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL SCOPE OF ITEMS TO BE REMOVED. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL DEMOLITION INFORMATION.

10. P.C. SHALL CUT AND PATCH EXISTING AS REQUIRED FOR NEW OR DEMOLITION WORK UNLESS NOTED OTHERWISE. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL INFORMATION.

PLUMBING GENERAL NOTES:

PLUMBING SHEET INDEXP-000 PLUMBING COVERSHEET

PD-103 THIRD FLOOR DEMOLITION - PLUMBING

P-101-B BASEMENT FLOOR PLAN - PLUMBING

P-101-M MEZZANINE FLOOR PLAN - PLUMBING

P-103 SECOND AND THIRD FLOOR PLAN - PLUMBING

P-300 ENLARGED PLUMBING PLANS

P-500 PLUMBING SCHEDULES

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

7:4

0 A

M

P-000

PLUMBING COVERSHEET

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 25: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

P-300

1

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

7:4

7 A

M

PD-103

THIRD FLOOR DEMOLITION -

PLUMBING

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

NO R HT

1/8" = 1'-0"2 THIRD FLOOR DEMOLITION - PLUMBING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 26: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

013.1

013.2 005.4

005.3

005.2

005.1005

023.1

sound

booth

#2

sound

booth

#1

sound

booth

#1

sound

booth

#2

sound

booth

#1

sound

booth

#1

future sound

booth

Office

Office Office

SupervisorOffice

LabStorage

Hearing AidFitting

Lab

Lab

001

013

015

040

030

030

007

020

014

012

029

031

002004

006.4

006.3

006.2

006008010

016.31

016.4

016.3

016.2

016

016.10

016.11

019017021

023

025

027

STAIR

Lab

Lab

STAIR

STAIR

C&IT

Storage

Storage

EngOffice

Jan

Men

Women

ClassroomClassroom

Office

Office

Office

OfficeClassroomClassroom

Mech

Mech

Mech

Mech

Mech

Tele

PLC

ClassroomClassroom ComputerLab

Lab

Lab

Teaching Lab

DN

UP

DN

UP

UP

UP

EPEP

NIC

NIC

NIC

NICNICNICNIC

NIC

NIC

NIC

NIC

NIC

NIC

NIC

NIC

NIC NIC

NIC

NIC

NIC

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

NC2 1/2"SAN

2-1/2" SANITARY DOWN FROM MEZZANINE ABOVE

1

SK-1

SP-001

3

SLOPE PIPE

3/4" HW &

1" CW UP

3" V UP

3" W UP

6" R.C. UP

C.O

2 1/2"CW1 1/4"HW3/4"HWR

1/2" HW & CW DN TO OWNER PROVIDED SALON SINK

CO

2" PUMPED SAN UP TO FIRSTFLOOR JANITOR'SCLOSET MOP SINK

3"V3/4"HWR

1"HW2 1/2"CW

4"SAN

3"V

2"SAN

1"CW1"HW

1/2"HW

1/2"CW

1/2"HW1/2"CW

3/4"CW3/4"HW

NC

SP-001

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

7:4

2 A

M

P-101-B

BASEMENT FLOOR PLAN -

PLUMBING

ApproverChecker

Author

18004050.00

Checker

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

Checker

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR PLAN - PLUMBING

KEYNOTES:

1. CONTRACTOR TO FIELD ROUTE NEW 2-1/2" SANITARY LINE. CONNECT TO EXISTING SANITARY IN JANITOR'S CLOSET.

2. WH-1 LOCATED IN CABINET BELOW SINK. 3. SP-1 LOCATED IN CABINET SPACE BELOW SINK.

PROVIDE AIR ADMITTANCE VALVE TO VENT SINK. ROUTE DRAIN TO JANITOR'S CLOSET MOP BASIN ON FIRST FLOOR.

#

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 27: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

102

102.1

105.1105.2

105.5105.4105.3

105

DN

Lounge

Jan

DN

UP

Open to Below

Elev

UPDNDN

OfficeOffice

OfficeOfficeWorkRoom

OpenOffice

Open to Below

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

NC

NC1/2"CW

1 1/2"V

2-1/12" SAN DOWN TO BASEMENT

SK-1

1/2"HW

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

7:4

3 A

M

P-101-M

MEZZANINE FLOOR PLAN -

PLUMBING

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

SHEET GENERAL NOTES :

1. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

NO R HT

1/8" = 1'-0"1 MEZZANINE FLOOR PLAN - PLUMBING

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 28: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

327

325

328.10

328.09

328.08

328

328.07

328.06

328.05

328.04

328.03

328.02

328.01

326

322.1

300.01

303

304 300.02 300.03

300.04

300

300.11 300.07

300.06

300.05

300.08

300.09300.1

Treatment

Observation

WorkRoom

Office

Office

OpenOffice

Office

COPY

Office

Office

Office

Office

Office

WOMEN'SRESTROOM

UNISEX ADARESTROOM

WORKROOM

Office

TEACHINGLAB Office Office

Office

OpenOffice

OpenOffice Office

Observation

Treatment

Office

TreatmentObservation

MECHANICAL AREA

MECH SHAFT

MECH

DNDN

COOLING TOWER

NIC

305

301

ELEV

NIC NIC NIC NIC

NIC NIC

NIC

NIC

NIC NIC NIC NIC NIC NIC NIC NIC

NIC

NIC

CONFERENCE

MECH

MEN WOMEN

MECHSHAFT

JAN

CONFERENCE

MECH

DN

UPUP

DN

224226.7

226.6

226.5

226

226.8226.42

226.41

226.4 226.3226.2

226.1

219.1

219

219.3219.2

223

222

220

218 216 214 212 210 208 206 204

202

202.1

200

200.2 200.1

201

204.1206.1

209.11

209.1

209.2

209

209.4

209.3

208.1210.1212.1214.1

217.1

216.1218.1

217.2

217

217.4 217.3

211

ELEV

275

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

P-300

2

1/2"CW

1/2"HW

1/2"CW

NC

SK-1

2 1/2" SAN DN TO SECOND FLOOR CEILING SPACE

NC

2"V

WH-1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

16 17

18 19 20

b

c

d

NC

2-1/2" SAN DN FROM THIRD FLOOR WORK ROOM.

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

7:4

3 A

M

P-103

SECOND AND THIRD FLOOR

PLAN - PLUMBING

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

NO R HT

1/8" = 1'-0"1 THIRD FLOOR PLAN - PLUMBING

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

NO R HT

1/8" = 1'-0"2 SECOND FLOOR PLAN - PLUMBING

Page 29: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

328.01

326

322.1

Office

WOMEN'SRESTROOM

UNISEX ADARESTROOM

MECH SHAFT

ELEVNIC

4 5 6 7

d

LAV-E

WC-E WC-E

3/4" S DN3/4" R DN

4"SAN

2"V

3/4"HW

3/4"CW

3/4"HW

3/4"CW

CO

CO

12

4 5 6 7

d

3

NC

NC

L-1

NC

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

7:4

5 A

M

P-300

ENLARGED PLUMBING PLANS

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

1/4" = 1'-0"1 THIRD FLOOR ENLARGE PLAN DEMOLITION

1/4" = 1'-0"2 THIRD FLOOR ENLARGE PLAN

KEYNOTES:

1. DEMOLISH EXISTING LAV, REWORK EXISTING PLUMBING TO PREPARE FOR NEW FIXTURE INSTALLATION.

2. DEMOLISH EXISTING URINAL. CUT AND CAP ASSOCIATED PIPING AT WALL. PATCH WALL AS REQUIRED.

3. PROVIDE AND INSTALL NEW LAV. CONNECT NEW 1/2" DHW,DCW ISOLATION VALVE, 1-1/2" SANITARY AND VENT.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

SHEET GENERAL NOTES :

1. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

Page 30: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:5

7:4

6 A

M

P-500

PLUMBING SCHEDULES

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

2 BASED ON LIBERTY PUMPS MODEL 405 WITH 14" DIA. X14" H , 5.5 GALLON POLYOLEFIN BASIN.

1ABOVE GRADE SUBMERSIBLE, SIMPLEX, NON-CLOG CENTRIFUGAL PUMPS. FURNISH AS PACKAGED PREWIRED, PREPIPED WITH VENTED 14 DIAMETER FIBERGLASSBASIN WITH BOLTED SEALING COVER, CONTROL PANEL, AND ALL CONTROL/ALARM DEVICES FOR A TURN-KEY SYSTEM. REFER TO SPECIFICATION AND DRAWINGDETAIL.

NOTES:

SP-001 BENCH SINK FLOOR PACKAGED SUMP 32 20 WATER 0.980 1.000 120 7.3 1/2 115 1 FLOAT SEE NOTE 1 & 2

MARK AREA/SYSTEM SERVED LOCATION TYPESHAFTSEAL

DESIGNFLOW(GPM)

TOTALDYNAMIC

HEADNPSHR TYPE

DYNAMICVISCOSITY

(CP)

SPECIFICGRAVITY

TEMP(OF)

%EFF AMPSHP

(NOTE 1 )RPM VOLT PH

MOTORENCLOSURE

MOTORCONTROL

REMARKS

MARK AREA/SYSTEM SERVED LOCATION TYPESHAFTSEAL

DESIGNFLOW...

FEET OF LIQUID LIQUID HANDLED %EFFMOTOR DATA

(ENERGY EFFICIENT T-FRAME)REMARKS

PUMP SCHEDULE

For Bids Dec. 11, 2018

NOTES: 1) SANITARY RISER UP IN WALL TO FIXTURE SHALL BE A MINUMUM OF 2". 2) 1/2" CW ANDHW APPLIES ONLY TO THE FINAL VERTICAL RISE-DROP TO EACH FIXTURE, BRANCH PIPING TOVERTICAL RISE-DROP SHALL BE A MINIMUM OF 3/4" UNLESS NOTED OTHERWISE. 3) SIZES SHOWNARE MINIMUMS. SIZES SHOWN ON THE DRAWING THAT ARE LARGER THAN THE SIZES LISTED IN THESCHEDULE SHALL DICTATE THE ROUGH-IN SIZE.

PLUMBING FIXTURE ROUGH-IN SCHEDULE

FIXTUREDESCRIPTION

DOMESTICCW

(NOTE 3)

DOMESTICHW

(NOTE 3)SANITARY(NOTE 3)

VENT(NOTE 3) REMARKS

LAVATORY 1/2" 1/2" 1 1/4" 1 1/4" NOTE 1 & 2

URINAL 1" - 2" 1 1/2" -

WATERCLOSET

1" - 4" 2" -

WH-1

WATER HEATER - ELECTRIC INSTANTANEOUS POINT-OF-USE (FOR SINGLE LOW FLOW FIXTURE), HIGH STRENGTHREINFORCED PLASTIC BODY, 3/8" COMPRESSION FITTINGS, REPLACEABLE ELEMENT, NEMA 4 PAINTED STEELWATERPROOF ENCLOSURE, HIGH TEMPERATURE LIMIT SWITCH, FLOW RESTRICTING AERATOR FOR FAUCET OUTLET, 150PSI WORKING PRESSURE, 1-YEAR WARRANTY ON ELEMENT, 5-YEAR WARRANTY ON HEATER BODY/ELEMENT ASSEMBLY,UL LISTED.

25°F RISE AT 0.5 GPM, 1.8 KW ELEMENT

ELECTRICAL REQUIREMENTS -120V- 1 PHASE, HARD-WIRED

MOUNT WATER HEATER ON WALL BELOW SINK OR LAVATORY. SET OUTPUT WATER TEMPERATURE AT 110°F.

EEMAX (SP), BRADFORD WHITE (ES), CHRONOMITE (SR)

WC-1

WATER CLOSET - ADA WALL MOUNTED, FLUSH VALVE TYPE, WHITE VITREOUS CHINA, SIPHON JET, WATER SAVING,ELONGATED BOWL, 1-1/2" TOP SPUD.

FLUSH VALVE -FLUSH VALVE - EXPOSED, SENSOR OPERATION, HARD-WIRED, 1.6 GALLONS PER FLUSH, 11-1/2" ROUGH-IN,CHROME PLATED, 1" I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH VANDAL RESISTANT CAP, HIGH BACK PRESSUREVACUUM BREAKER, ADJUSTABLE TAILPIECE, SPUD COUPLING AND FLANGE, WALL FLANGE WITH SET SCREW,MECHANICAL OVER-RIDE BUTTON, CHLORAMINE RESISTANT MATERIALS, ADA COMPLIANT, 3 YEAR WARRANTY.

SEAT - WHITE, EXTRA HEAVY, OPEN FRONT, INJECTION MOLDED SOLID PLASTIC, SELF-SUSTAINING HINGE, STAINLESSSTEEL OR PLATED STEEL POSTS AND NUTS.

ACCESSORIES - WATER CLOSET SUPPORT CARRIER RATED FOR 500 LBS.

MOUNT WATER CLOSET WITH CARRIER BOLTED SECURELY TO FLOOR. TOP OF SEAT SHALL BE AT 16"-17" ABOVEFINISHED FLOOR (VERIFY EXACT MOUNTING HEIGHT WITH MANUFACTURER). FLUSH HANDLE SHALL BE LOCATED ONTHE WIDE SIDE OF THE TOILET STALL AND BE AT 12" (MAXIMUM) ABOVE BOWL RIM AND OPERATE WITH NO GREATERTHAN 5 LB FORCE IN COMPLIANCE WITH LATEST ADA STANDARDS. VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-INLOCATIONS.

WATER CLOSET - AMERICAN STANDARD (2257.101)

FLUSH VALVE - AMERICAN STANDARD 6065.161

SEAT -BEMIS (3155C), CHURCH (3155C), BENEKE (533PC), OLSONITE (95), SAME AS WATER CLOSETMANUFACTURER

SK-1

SINK - SELF-RIMMING SINGLE COMPARTMENT WITH FAUCET DECK, 18 GAUGE TYPE 304 STAINLESS STEEL, 20"(SIDE-TO-SIDE) x 18" (FRONT-TO-BACK) OVERALL SIZE,20" x 18" x [D]" DEEP BOWL, COMPLETELY UNDERCOATED, 3-1/2"DIAMETER DRAIN OUTLET LOCATION CENTERED IN BOWL, PERFORATED TYPE 316 STAINLESS STEEL GRID STRAINER.

SINK TRIM - TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION, CHROME-PLATED FINISH, GOOSENECK RIGIDSPOUT,NOMINAL 4" REACH, AERATOR, HANDLES AT 8" CENTERS, 1/4-TURN OPERATION CERAMIC DISC CARTRIDGE.

ACCESSORIES - 1-1/2" 17 GAUGE CHROME-PLATED BRASS TAILPIECE AND P-TRAP, QUARTER-TURN BALL VALVE TYPE 3/8"CHROME-PLATED BRASS ANGLE SUPPLIES WITH LOOSE KEY STOPS, CHROME-PLATED SOFT COPPER SUPPLY LINES.

SINK - ELKAY (LR/LK18B)

SINK TRIM - AMERICAN STANDARD (7230.000)

L-1

LAVATORY - ADA WALL MOUNTED, WHITE VITREOUS CHINA, 20"x18", 4" HIGH CONTOURED BACKSPLASH, SINGLE FAUCETHOLE, DRILLED FOR CONCEALED ARM CARRIER.

INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES AND SUPPLY LINES.

LAVATORY TRIM - SENSOR ACTIVATED MIXING FAUCET, HARD-WIRED, BRASS CONSTRUCTION, CHROME-PLATED FINISH,CONVENTIONAL SPOUT WITH VANDAL RESISTANT AERATOR, SINGLE HOLE DECK PLATE, PERFORATED GRID STRAINERWITH 1-1/4" 17 GAUGE TAILPIECE, SOLID BRASS SOLENOID WITH BUILT-IN FILTER, SOLID BRASS THERMOSTATIC MIXINGVALVE MEETING ASSE 1070 REQUIREMENTS WITH ADJUSTABLE TEMPERATURE LIMIT STOP AND INTEGRAL CHECKVALVES, WATERPROOF CONNECTORS AND CABLE, UL APPROVED TRANSFORMER.

ELECTRICAL REQUIREMENTS - 120 VAC INPUT

MOUNT CONTROLS IN WATERPROOF VANDAL-RESISTANT ENCLOSURE BELOW LAVATORY. PROVIDE TRANSFORMER WITHCABLE EXTENSIONS (AS REQUIRED) OR PLUG-IN TRANSFORMER. MOUNT TRANSFORMER ABOVE CEILING OR INACCESSIBLE PIPE CHASE. COORDINATE LOCATION WITH ELECTRICAL CONTRACTOR. SELECT TRANSFORMER TO SERVEMAXIMUM NUMBER OF ELECTRONIC VALVES TO REDUCE AMOUNT OF TRANSFORMERS.

MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 2005 AND ASME/ANSI STANDARDA112.18.1M. FAUCET SHALL COMPLY WITH FEDERAL ACT S.3874. PROVIDE RESTRICTIVE DEVICE AS REQUIRED. MOUNTMIXING VALVE UNDER COUNTER/LAVATORY. MIXING VALVE SHALL NOT BE WYE PATTERN STYLE.

PROGRAMMING UNIT - HAND HELD, CAPABLE OF CHANGING SETTINGS, RUNNING DIAGNOSTICS, AND SCAN FAUCETSWITH ISSUES. PROVIDE ONE CONTROLLER FOR EVERY 6 FAUCETS.

ACCESSORIES - QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE SUPPLY STOPS, CHROME PLATED SOFTCOPPER SUPPLY LINES, DRAIN AND OFFSET TAILPIECE, 1-1/4" 17 GAUGE CAST BRASS P-TRAP, SUPPORT CARRIER.

IN COMPLIANCE WITH LATEST ADA STANDARD. PROVIDE 29" MINIMUM CLEARANCE FROM FLOOR TO BOTTOM OF APRONIN COMPLIANCE WITH LATEST ANSI A117.1 AND ADA STANDARDS. ARMAFLEX WITH TAPE IS NOT ACCEPTABLE IN LIEU OFINSULATION KIT.

LAVATORY -KOHLER (K-2007)

INSULATION KIT - TRUEBRO

LAV TRIM -AMERICAN STANDARD (775B.205/PK00.HAC)

TAG DESCRIPTION ACCEPTABLE MANUFACTURERS

THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRATCOR. THE CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQURED FOR FULLY OPERATIONAL SYSTEMS,WHETHERSPECIFICED OR NOT.CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRATCTOR IS RESPONSIBLE FOR COMPLETE DESCRIPTION OFMATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.CONTRATCTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874.

PLUMBING MATERIAL LIST

Page 31: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

PIPING ABBREVIATION KEY

ABBR: DESCRIPTION:

DIFFERENTIAL PRESSURE GAUGE (RANGE)DPG (0-2")

DIFFERENTIAL PRESSURE SWITCHDPS

PRESSURE SWITCHPS

AD ACCESS DOOR

ABOVE FINISHED FLOORAFF

CO CLEANOUT

MIXING VALVEMV

NC NEW CONNECTION

N.C. NORMALLY CLOSED

NOT IN CONTRACTNIC

NORMALLY OPENN.O.

ELECTRICAL TO PNEUMATIC VALVEEP

TYPICAL TYP

UNLESS NOTED OTHERWISEUNO

MA MIXED AIR

OA OUTSIDE AIR

RA RETURN AIR

SA SUPPLY AIR

EXHAUST/RELIEF AIREA

C COMMON

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

NAME

1VIEW NAME1/8" = 1'-0"

LEVEL NAME

10' - 0" HEIGHT ABOVE PROJECT 0' - 0"

1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL

NO R HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)

NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)

EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)

LINE TYPE KEY:

TEMPERATURE CONTROLS CONTRACTORT.C.C.

SECURITY CONTRACTORS.C.

AUDIO/VISUAL CONTRACTORA.V.C.

ASBESTOS ABATEMENT CONTRACTOR

HEATING CONTRACTORH.C.

PLUMBING CONTRACTORP.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

VENTILATION CONTRACTORV.C.

ELECTRICAL CONTRACTORE.C.

A.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.

2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.

3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.

4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.

5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.

6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.

8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.

9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.

10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE.PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.

11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.

12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.

13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.

14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR

STARTERS, SWITCHES, AND DISCONNECTS.16. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL

EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.17. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER

NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.

MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE GENERAL CONTRACTOR CONSTRUCTION MANAGER. ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.

5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED WITH HIS WORK.

6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.

7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN ACTIVE.

9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.

10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.

11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.

MECHANICAL PHASING NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO GENERAL CONTRACTOR'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT

5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

1. THE SIZE OF BRANCH PIPING TO TERMINAL HEATING DEVICES AND COILS SHALL BE 3/4" UNLESS NOTED OTHERWISE.

2. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST FLOOR DRAIN.3. INSTALL ALL REFRIGERANT LIQUID AND SUCTION PIPING SIZED PER EQUIPMENT

MANUFACTURER RECOMMENDATIONS.

PIPING GENERAL NOTES:

PIPING SHEET INDEXMP-000 PIPING COVERSHEET

MPD-101-B BASEMENT FLOOR DEMOLITION - PIPING

MP-101-B BASEMENT FLOOR - PIPING

MP-103 THIRD FLOOR PLAN - PIPING

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:4

9:4

4 A

M

MP-000

PIPING COVERSHEET

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 32: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

001

013

015

040

030

030

007

020

014

012

029

031

002004

006.4

006.3

006.2

006008010

016.31

016.4

016.3

016.2

016

016.10

016.11

019017021

023

025

027

STAIR

Lab

Lab

STAIR

STAIR

C&IT

Storage

Storage

EngOffice

Jan

Men

Women

ClassroomClassroom

Office

Office

Office

OfficeClassroomClassroom

Mech

Mech

Mech

Mech

Mech

Tele

PLC

ClassroomClassroom ComputerLab

Lab

Lab

Teaching Lab

T

T

T

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

3/4" S & R UP

1 1/4"HWS

1"HWS

1 1/4"HWR

3/4"HWR

3/4"HWS

3/4"HWS

3/4"HWR

3/4"HWR3/4"HWS

3/4"HWS3/4"HWR

1"HWR

3/4"HWS

1 1/4"HWR

3"HWR

1"HWS 3/4"HWS3/4"HWR

3/4"HWS3/4"HWR

1 1/4"HWS

3"HWR

3/4"HWR

3/4"HWS3/4"HWR

3/4"HWS

3/4"HWR

3/4"HWS 3/4"HWS3/4"HWR

1"HWS

1"HWR

1 1

/2"H

WS

2"H

WR

1 1

/4"H

WS

2"H

WR

1 1

/2"H

WS

3/4"HWR

3/4"HWS

1"HWR

3/4"HWS

3/4"HWR

3/4"HWR

3/4"HWS3/4"HWS

3/4"HWS

3/4"HWS

3/4"HWR

3/4"HWR

1"HWR

1"HWS

2 1/2"HWS

2 1/2"HWR

1"HWR

3/4"HWS

3/4"HWR

3/4"HWS3/4"HWS3/4"HWS

3/4"HWR

3/4"HWR

3/4"HWR

3/4"HWR

1

1

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:4

9:4

9 A

M

MPD-101-B

BASEMENT FLOOR DEMOLITION

- PIPING

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR DEMOLITION - PIPING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

SHEET GENERAL NOTES :

1. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

2. CAP ALL OPEN ENDED HHW PIPING. DO NOT LEAVE ANY ABONDONED PIPING IN THE AREA OF WORK. COORDINATE WITH OWNER'S CURRENT HHW RENOVATION PROJECT.

KEYNOTES:

1. DISCONNECT AND REMOVE EXISTING COMPUTER ROOM AIR CONDITIONING (CRAC) UNIT, AND ASSOCIATED PIPING. SALVAGE UNIT AND RETURN TO OWNER. CAP DUCT MAIN, CUT AND CAP HHW BACK TO MAIN. VERFY WITH OWNER PRIOR TO COMMENCEMENT OF WORK.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 33: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

013.1

013.2 005.4

005.3

005.2

005.1005

023.1

sound

booth

#2

sound

booth

#1

sound

booth

#1

sound

booth

#2

sound

booth

#1

sound

booth

#1

future sound

booth

Office

Office Office

SupervisorOffice

LabStorage

Hearing AidFitting

Lab

Lab

001

013

015

040

030

030

007

020

014

012

029

031

002004

006.4

006.3

006.2

006008010

016.31

016.4

016.3

016.2

016

016.10

016.11

019017021

023

025

027

STAIR

Lab

Lab

STAIR

STAIR

C&IT

Storage

Storage

EngOffice

Jan

Men

Women

ClassroomClassroom

Office

Office

Office

OfficeClassroomClassroom

Mech

Mech

Mech

Mech

Mech

Tele

PLC

ClassroomClassroom ComputerLab

Lab

Lab

Teaching Lab

T

T

T

T

T

T

T

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

1

1

1

1

1

1

3/4"HWR3/4"HWS

NC

1

NC

3/4"HWR3/4"HWS

3/4"HWR3/4"HWS

NC

3/4"HWS3/4"HWR

3/4"HWR3/4"HWS

3/4"HWS3/4"HWR

3/4"HWR3/4"HWS

NC

NC3/4"HWS3/4"HWR 3/4"HWR

3/4"HWS

1

NC

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:4

9:4

7 A

M

MP-101-B

BASEMENT FLOOR - PIPING

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR - PIPING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

SHEET GENERAL NOTES :

1. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

2. COORDINATE HHW INSTALLATION & ROUTING FOR THIS PROJECT WITH OWNER'S HHW PIPING REPLACEMENT PROJECT CURRENTLY UNDER CONSTRUCTION.

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

KEYNOTES:

1. NEW 3/4" HHWS/R PIPE TO NEW TERMINAL AIR BOX FROM EXISTING HHWS & R MAINS. PROVIDE ISOLATION VALVES ON SUPPLY AND RETURN PIPING, TWO-WAY CONTROL VALVE & BALANCE VALVE ON RETURN PIPING. SEE DETAIL.

#

Page 34: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

327

325

328.10

328.09

328.08

328

328.07

328.06

328.05

328.04

328.03

328.02

328.01

326

322.1

300.01

303

304 300.02 300.03

300.04

300

300.11 300.07

300.06

300.05

300.08

300.09300.1

Treatment

Observation

WorkRoom

Office

Office

OpenOffice

Office

COPY

Office

Office

Office

Office

Office

WOMEN'SRESTROOM

UNISEX ADARESTROOM

WORKROOM

Office

TEACHINGLAB Office Office

Office

OpenOffice

OpenOffice Office

Observation

Treatment

Office

TreatmentObservation

T

T

T

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

1

NC

3/4"HWR3/4"HWS

2"HWR2"HWS

3/4"HWS3/4"HWR

3/4"HWS

3/4"HWR

3/4"HWR3/4"HWS

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:4

9:4

7 A

M

MP-103

THIRD FLOOR PLAN - PIPING

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

NO R

HT

1/8" = 1'-0"1 THIRD FLOOR PLAN - PIPING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

KEYNOTES:

1. NEW 3/4" HHWS/R PIPE TO NEW TERMINAL AIR BOX FROM EXISTING HHWS & R MAINS. PROVIDE ISOLATION VALVES ON SUPPLY AND RETURN PIPING, TWO-WAY CONTROL VALVE & BALANCE VALVE ON RETURN PIPING. SEE DETAIL.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

SHEET GENERAL NOTES :

1. COORDINATE ANY SHUTDOWNS OF EXISTING SERVICES OR EQUIPMENT WITH OWNER. PERFORM SHUTDOWNS AT A SCHEDULED TIME AS TO MINIMIZE DISRUPTION OF BUILDING OPERATIONS.

2. COORDINATE HHW INSTALLATION & ROUTING FOR THIS PROJECT WITH OWNER'S HHW PIPING REPLACEMENT PROJECT CURRENTLY UNDER CONSTRUCTION.

Page 35: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

FIRE PROTECTION SYMBOL LIST

SYMBOL: DESCRIPTION:

FIRE PROTECTIONFP

FIRE PROTECTION - DRY SYSTEMFPD

SERVICE WATER - POTABLEW

NO HATCH LIGHT HAZARD

ORDINARY GROUP 1

ORDINARY GROUP 2

EXTRA GROUP 1

EXTRA GROUP 2

SPRINKLER - WALL MOUNTED

SPRINKLER

SPRINKLER - CONCEALED

SPRINKLER

SPRINKLER

SPRINKLER

SPRINKLERA

SPRINKLERA

COMPRESSED AIR - FIRE PROTECTIONCAF

PIPE CAP

PIPE DOWN

NEW CONNECTION

PIPE UP OR UP/DOWN

DEMOLITION

DRAINDFP

NOT ALL SYMBOLS MAY APPLY.

UNION/FLANGE

DIRECTION OF FLOW IN PIPE

AREA BOUNDARY

FIRE PROTECTION ABBREVIATION KEY

AD ACCESS DOOR

BFP BACKFLOW PREVENTER

N.C. NORMALLY CLOSED

ABOVE FINISHED FLOORAFF

NC NEW CONNECTION

NOT IN CONTRACTNIC

NORMALLY OPENN.O.

ABBR: DESCRIPTION:

TYPICALTYP

UNLESS NOTED OTHERWISEUNO

I.E. INVERT ELEVATION

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

NAME

1VIEW NAME1/8" = 1'-0"

LEVEL NAME

10' - 0" HEIGHT ABOVE PROJECT 0' - 0"

1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL

NO R

HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)

NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)

EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)

LINE TYPE KEY:

1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.

2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER IS THE BASIS OF DESIGN.

3. FIRE PROTECTION PIPE ROUTING IS SHOWN FOR GENERAL LAYOUT. DETERMINE EXACT NUMBER OF SPRINKLERS, PIPE SIZING, AND PIPE ROUTING.

4. CENTER SPRINKLERS IN CEILING TILES IN BOTH DIRECTIONS IN ALL AREAS. IN AREAS WITH 2’X4’ CEILING TILES CENTERING USING A 2’X2’ CEILING PATTERN IS ACCEPTABLE.

5. NEW SPRINKLERS SHALL BE QUICK RESPONSE TYPE, UNLESS OTHERWISE NOTED. CONTRACTOR SHALL NOT MIX STANDARD RESPONSE SPRINKLERS WITH QUICK RESPONSE SPRINKLERS IN UNPARTITIONED SPACES.

6. PROVIDE COVERAGE ABOVE AND BELOW ALL DUCTWORK GREATER THAN 48" WIDE. 7. PROVIDE COVERAGE ABOVE AND BELOW FLOATING CEILINGS. REFER TO ARCHITECTURAL

PLANS.

FIRE PROTECTION GENERAL NOTES:

TEMPERATURE CONTROLS CONTRACTORT.C.C.

SECURITY CONTRACTORS.C.

CONSTRUCTION MANAGERC.M.

PLUMBING CONTRACTORP.C.

ELECTRICAL CONTRACTORE.C.

VENTILATION CONTRACTORV.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

FIRE PROTECTION CONTRACTORF.P.C.

HEATING CONTRACTORH.C.

MECHANICAL CONTRACTORM.C.

MECHANICAL PHASING NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO CONSTRUCTION MANAGER'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE PHASING CRITERIA.

2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH AFFECTED ADJACENT AREAS.

3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.

4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.

MECHANICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE CONSTRUCTION MANAGER AND ARCHITECT/ ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.

5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.

6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.

7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT REMAIN ACTIVE.

9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.

10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.

11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.

MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, FIRE PROTECTION, PLUMBING, MEDICAL GAS, VENTILATION, PIPING AND TEMPERATURE CONTROL.

1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.

2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.

3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.

4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.

5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.

6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.

8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.

9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.

10. SEAL ALL FLOOR, WALL AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE. PENETRATIONS THROUGH ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.

11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.

12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.

13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.

14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 15. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR

STARTERS, SWITCHES, AND DISCONNECTS.16. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER

NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.

FIRE PROTECTION SHEET INDEXF-000 FIRE PROTECTION COVERSHEET

F-101-B BASEMENT FLOOR - FIRE PROTECTION

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:4

7:0

4 A

M

F-000

FIRE PROTECTION

COVERSHEET

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

NOTES: 1. SEE FLOOR PLANS FOR ZONING REQUIREMENTS. 2. SPRINKLER SHALL HAVE COLOR CODED BULB THERMAL ELEMENT. 3. ALL SPRINKLERS SHALL BE UL AND FM LISTED. 4. CONTRACTOR TO VERIFY SPRINKLER REQUIREMENTS BASED ON ACTUAL INSTALLATION, USAGE, ARCHITECTURAL CEILING PLAN AND NFPA 13

REQUIREMENTS. 5. TAG NAME IS PRIMARILY FOR IDENTIFIYING SPRINKLERS IN SUBMITTALS. IT MAY OR MAY NOT BE FOUND ELSEWHERE ON THE DRAWINGS.

CONTRACTOR TO SUBMIT ALL SPRINKLER TYPES TO BE USED. 6. AREAS ARE GENERAL IN NATURE. CONTRACTOR TO MATCH UNSCHEDULED AREAS TO SIMILAR SPACES....

FIRE SPRINKLER USAGE SCHEDULE

AREA TYPE(NOTE 1 & 6)

AREAHAZARD

SPRINKLER

TEMPERATURERATING MANUFACTURER & MODEL NOTES

TAG NAME(NOTE 4 & 5)

SPRINKLERTYPE

RESPONSECATEGORY FINISH

SEE PLANS SEE PLANS SPR-1 RECESSEDPENDENT

QUICK CHROMEPLATED

155 VIKING VK, RELIABLE F1FR, TYCO TY-FRB,VICTAULIC V2708

NOTES 2,3

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 36: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

013.1

013.2 005.4

005.3

005.2

005.1005

023.1

sound

booth

#2

sound

booth

#1

sound

booth

#1

sound

booth

#2

sound

booth

#1

sound

booth

#1

future sound

booth

Office

Office Office

SupervisorOffice

LabStorage

Hearing AidFitting

Lab

Lab

001

013

015

040

030

030

007

020

014

012

029

031

002004

006.4

006.3

006.2

006008010

016.31

016.4

016.3

016.2

016

016.10

016.11

019017021

023

025

027

STAIR

Lab

Lab

STAIR

STAIR

C&IT

Storage

Storage

EngOffice

Jan

Men

Women

ClassroomClassroom

Office

Office

Office

OfficeClassroomClassroom

Mech

Mech

Mech

Mech

Mech

Tele

PLC

ClassroomClassroom ComputerLab

Lab

Lab

Teaching Lab

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

1

1

1

1

1

1

BOUNDARY INDICATES AREA OF WORK. REMOVE EXISTING SPRINKLERS AND ASSOCIATED BRANCH AND MAIN PIPING WITH AREA OF WORK. EXISTING FIRE PROTECTION PIPING MAY BE RE-USED IF SIZED PROPERLY PER CONTRACTORS' HYDRAULIC CALCULATIONS AND LOCATED PROPERLY FOR COORDINATION WITH OTHER TRADES. RE-USED FIRE PROTECTION PIPING MUST BE INSPECTED AND CONTRACTOR MUST DOCUMENT ACCEPTANCE PRIOR TO RE-USING. PROVIDE NEW SPRINKLERS AND COVERAGE PER NFPA 13. EXISTING SPRINKLER HEADS IN THE CORRECT LOCATIONS MAY BE LEFT IN PLACE, BUT ONLY IF THEY ARE QUICK RESPONSE. NEW SPRINKLERS WILL MATCH EXISTING.

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:4

7:0

5 A

M

F-101-B

BASEMENT FLOOR - FIRE

PROTECTION

PETPAPPETPAP

KIRSAI

18004050.00

PETPAP

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

PETPAP

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR - FIRE PROTECTION

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

SHEET GENRAL NOTES :

1. COORDINATE ALL DEMOLITION AND NEW WORK WITH ARCHITECTURAL DEMOLITION AND PHASING PLANS.2. REMOVE ALL PIPING, EQUIPMENT, HANGERS, SUPPORTS, CONTROLS AND ACCESSORIES WITHIN SCOPE BOUNDARY AS SHOWN ON THIS PLAN3. EXISTING PIPING IS SHOWN FOR REFERENCE. CONTRACTOR TO FIELD VERIFY PIPING AND DEMOLITION WORK PRIOR TO CONSTRUCTION START.4. RELOCATE EXISTING UTILITIES AS REQUIRED TO COORDINATE WITH OTHER TRADES.5. CONTRACTOR SHALL SHUTDOWN AND DRAIN SYSTEM AS REQUIRED TO MAKE MODIFICATIONS.SYSTEM SHUTDOWN SHALL BE COORDINATED WITH OWNER

PRIOR TO PROCEEDING.6. CONTRACTOR SHALL TURN SPRINKLERS UPRIGHT DURING CONSTRUCTION TO MAINTAIN ADEQUATE COVERAGE PER NFPA13.7. CONTRACTOR SHALL EXTEND AND REWORK EXISTING FIRE PROTECTION PIPING AS REQUIRED TO MAINTAIN COVRAGE PER NFPA13.8. PROVIDE TEMPORARY CONNECTIONS TO KEEP SYSTEM SERVING AREAS OUT OF SCOPE ACTIVE DURING CONSTRUCTION.9. FIRE PROTECTION CONTRACTOR RESPONSIBLE FOR COMPLETE SYSTEM.10. REFER TO ARCHITECTURAL LIFE SAFETY PLANS FOR LOCATIONS OF ALL FIRE BARRIERS.REFER TO 2/FP00 FOR FIRE RATED BARRIER PENETRATION DETAIL.

REFER TO 1/FP000 FOR TYPICAL ARMOVER SUPPORT DETAIL.

KEYNOTES:

1. CONNECT TO SPRINKLER HEAD IN SOUND BOOTH. COORDINATE WITH OWNER REGARDING THE WORK. CONTRACTOR SHALL INCLUDE THIS WORK IN THE CALCULATION.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 37: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

NAME

1VIEW NAME1/8" = 1'-0"

LEVEL NAME

10' - 0" HEIGHT ABOVE PROJECT 0' - 0"

1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL

NO R

HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)

NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)

EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)

LINE TYPE KEY:

1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.

2. {L###} INDICATES THE LIGHTING SEQUENCE OF OPERATION FOR THE SPACE. REFER TO THE

LIGHTING SEQUENCE OF OPERATION MATRIX ON SHEET E-000.

LUMINAIRE KEY:

DEVICE KEY:

ELECTRICAL MOUNTING SUBSCRIPT KEY:A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASHC MOUNT AT CEILING

ELECTRICAL GENERAL NOTES:

LUMINAIRE

F1 = FIXTURE TAG1 = CIRCUIT NUMBERa = SWITCH DESIGNATION

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS INFORMATION. EX: F1 / 1 / a / SE

DEVICEA = MOUNTING (IF APPLICABLE)1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS INFORMATION. EX: A / 1

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CONDUITS BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK AND SHALL NOTIFY THE ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF WORK.

5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.

6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.

7. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

ELECTRICAL RENOVATION NOTES:THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO, LIGHTING, POWER, AND SYSTEMS.

1. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH PHASE.

2. CIRCUITS SERVING EMERGENCY LUMINAIRES WILL BE RUN IN A SEPARATE RACEWAY FROM ALL OTHER CIRCUITS.

3. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.

4. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN GRILLE.

5. CONTRACTOR SHALL VERIFY ALL FURNITURE AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL ADJUST RECEPTACLES, OUTLETS, OR CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE AND EQUIPMENT.

6. ELECTRICAL EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF, OPERATION OF, AND ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF ELECTRICAL EQUIPMENT, ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.

7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.

8. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: LIGHTING SWITCHES 4'-0" RECEPTACLES (GENERAL AREAS) 1'-6" RECEPTACLES (UTILITY AREAS) 4'-0" TELECOMMUNICATION OUTLETS 1'-6" WALL PHONE 4'-0" FIRE ALARM STATIONS 4'-0" FIRE ALARM SIGNALS 7'-6" CLOCKS/CLOCK OUTLETS 1’-6” BELOW FIN. CEIL. SAFETY SWITCHES 5'-0" TO TOP

ELECTRICAL INSTALLATION NOTES:

MCC-# MOTOR CONTROL CENTER

ELECTRICAL EQUIPMENT TAGS

TAG: DESCRIPTION:RELATED

SPECIFICATION

SW-1P 26 09 33 SWITCH - SINGLE POLE

OC SW-OC-D OCCUPANCY SENSOR - DUAL TECHNOLOGYD

26 09 33

F# TROFFER

F# DOWNLIGHT LUMINAIRE

ECONN ELECTRICAL CONNECTIONE

E

PANEL '###' PANELBOARD - SURFACE MOUNT

SW-LV SWITCH - LOW VOLTAGELV

26 09 33

REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V

REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V

ELECTRICAL SYMBOL LIST

SYMBOL: TAG:SPEC

SECTION:DESCRIPTION:

F# LINEAR LUMINAIRES

SW-3W 26 09 33 SWITCH - THREE WAY3

REC-QUAD 26 27 26 QUAD RECEPTACLE, 125V

DB DOOR BELLDB

DP-# DISTRIBUTION PANEL

SB-# SWITCHBOARD

FA-211 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE - WALL MOUNTED

A1 A3

A7 AH

AS

FA-201 28 31 00 FIRE ALARM VISUAL NOTIFICATION DEVICE - CEILING MOUNTED

V1 V3

V7 VH

FA-231 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION DEVICE - CEILING MOUNTED

A1 A3

A7 AH

FA-230 28 31 00 FIRE ALARM AUDIO NOTIFICATION DEVICE - CEILING MOUNTED

A

SD FA-120 28 31 00 FIRE ALARM SMOKE DETECTOR - CEILING MOUNTED

FA-130 28 31 00 FIRE ALARM MANUAL PULL STATIONF

VS

AS

28 31 00FAP-# FIRE ALARM - CONTROL PANEL

JB JUNCTION BOXJ

J

MX-#/MS-#/FCS-# MANUAL SWITCH / STARTER / COMBINATION STARTER

SW WALL CONTROL STATIONSW

XM# EMERGENCY UNIT

26 27 26

ELECTRICAL SHEET INDEXE-000 ELECTRICAL COVERSHEET

ED-101-B BASEMENT FLOOR DEMOLITION - ELECTRICAL

ED-101 FIRST FLOOR DEMOLITION - ELECTRICAL

ED-101-M MEZZANINE FLOOR DEMOLITION - ELECTRICAL

ED-103 THIRD FLOOR DEMOLITION - ELECTRICAL

EL-101-B BASEMENT FLOOR - LIGHTING

EL-101 FIRST FLOOR PLAN - LIGHTING

EL-101-M MEZZANINE FLOOR PLAN - LIGHTING

EL-103 THIRD FLOOR PLAN - LIGHTING

EP-101-B BASEMENT FLOOR - POWER

EP-101 FIRST FLOOR PLAN - POWER

EP-101-M MEZZANINE FLOOR PLAN - POWER

EP-103 THIRD FLOOR PLAN - POWER

EP-300 POWER DETAILS

ES-101-B BASEMENT FLOOR - SYSTEM

ES-101 FIRST FLOOR PLAN - SYSTEMS

ES-101-M MEZZANINE FLOOR PLAN - SYSTEMS

ES-103 THIRD FLOOR PLAN - SYSTEMS

ES-300 SYSTEM DETAILS

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:3

5 A

M

E-000

ELECTRICAL COVERSHEET

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

LIGHTING SEQUENCE OF OPERATIONPLAN ID LIGHTING SWITCHED

{LS1} Sequence: Switched lights are occupancy controlled in this space.ON: The lights are turn on by occupancy sensor.OFF: After the space has been vacant for 20 minutes, the lights will automatically turn off.

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

REFER TO SPECIFICATION SECTIONS LIGHTING 26 51 00 AND EMERGENCY LIGHTING EQUIPMENT 26 52 00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.INTERIOR CORRELATED COLOR TEMPERATURE 4100K, COLOR RENDERING INDEX (CRI) AT OR ABOVE 80, UNLESS NOTED OTHERWISE.

CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THESPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE FIRST MANUFACTURER LISTED IS THE BASIS OFDESIGN.

VERIFY AND COORDINATE ALL CEILING TYPES WITH LUMINAIRE MOUNTING AND TRIM REQUIREMENTS PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.CONFIRM ALL COLORS AND FINISHES OF ALL LUMINAIRE COMPONENTS WITH ARCHITECT AND INTERIOR DESIGNER PRIOR TO THE RELEASE OF THE LUMINAIRE ORDER.UNLESS INDICATED ON LIGHTING PLANS OR BELOW, REFER TO ARCHITECTURAL AND INTERIOR DESIGN ELEVATIONS, SECTIONS AND DETAILS FOR ALL SUSPENDED AND WALL MOUNTED LUMINAIREMOUNTING HEIGHTS.

EM - EMERGENCY BATTERY

EB - ELECTRONIC

(TYPE) BALLAST/DRIVER:

(WATT) PER: FIX - FIXTURE, FT - FOOT, LAMP

FL - FLUORESCENT RE - RECESSED

LED - LIGHT EMITTING DIODE CL - CEILING SURFACE

(TYPE) LIGHT SOURCE TECHNOLOGY: (MTG) MOUNTING:

CFSA - COLOR-FINISH SELECTION BY ARCHITECT

FINISH:

O - OTHER (SEE DESCRIPTION)

FS - FLAT STEEL A - .125" ACRYLIC

(DESC) DOOR: (L/L) LENS/LOUVER:

LUMINAIRE SCHEDULE

ITEM DESCRIPTION L/L MTG

DIMENSIONS WATTLIGHT SOURCETECHNOLOGY BALLAST/DRIVER

APPROVED MANUFACTURERL W H DIA.MAXANSI PER TYPE QTY

MODEL/ABSOLUTE

LUMENS (MIN) VOLTS TYPE

EM1 EMERGENCY UNIT, TWO ADJUSTABLE LEDHEADS, WHITE THERMOPLASTIC HOUSING.SELF TEST & DIAGNOSTICS OF INVERTERAND LAMPS

O CL 11" 3 1/2" 7 1/2" 3 W FIX LED 2 6 VOLT (2INCLUDED)

120 V EM DUAL-LITE EVHCLITHONIA ELML4

F1 RECESSED STATIC GRID TROFFER WITH FSDOOR.

K RE 4'-0" 1'-0" 4 1/2" 64 W FIX FL 2 32WATTF32T8

120 V EB LITHONIA SP8COLUMBIA 4PSMETALUX GC

Page 38: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

001

013

015

040

030

030

007

020

014

012

029

031

002004

006.4

006.3

006.2

006008010

016.31

016.4

016.3

016.2

016

016.10

016.11

019017021

023

025

027

STAIR

Lab

Lab

STAIR

STAIR

C&IT

Storage

Storage

EngOffice

Jan

Men

Women

ClassroomClassroom

Office

Office

Office

OfficeClassroomClassroom

Mech

Mech

Mech

Mech

Mech

Tele

PLC

ClassroomClassroom ComputerLab

Lab

Lab

Teaching Lab

F F F

F

E E E E

E E E E

JJ

OC

J

OC

E

E

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

EXISTING RP-BD

EXISTING LP-BB

EXISTING LP-BAEXISTING MCC EXISTING LP-BC

EXISTING EMERGENCY

LP-E

EXISTING FIREALARM CABINET

EXISTING MASTER

CLOCK & PROGRAM

MACHINEC

C

C

C

EXISTING DP-1

EXISTING SB-1

+72

CLOCK

+72

CLOCK

+72

CLOCK

A

A

+96A

A

R

+42 R R R

EXISTING RP-BF

/+72CLOCK

+42R+42R

+42

+42R+42R

+42

R

/+72

+30R+30R

CLOCK

R

R

R

R R R

EXISTING RP-BG

RR

EXISTING RP-BH

RRRRRRRR

R R R R R

R R

/+72CLOCK

C

/+72CLOCK

C

EXISTING SECURITY

CONTROL PANELS

EXISTING SECURITY

CONTROL PANELS

1

1

1

1

1

1

3

1

1

1

1

1

1

CRAC

CRAC2

2

3

3

3

3

3

3

3

FURNITURE FEEDFURNITURE FEED FURNITURE FEEDFURNITURE FEED

FURNITURE FEEDFURNITURE FEEDFURNITURE FEEDFURNITURE FEED

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:3

7 A

M

ED-101-B

BASEMENT FLOOR DEMOLITION

- ELECTRICAL

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR DEMOLITION - ELECTRICAL

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

KEYNOTES:

1. FIXTURE TO BE RELOCATED, REFER TO SHEET EL-101-B.

2. CONFIRM DEMOLITION WORK WITH OWNER.3. DISCONNECT AND REMOVE WIRE-WAYS,

OUTLETS AND JUNCTION BOXES DRAWN IN DOTTED SYMBOLS, REMOVE UNUSED BRANCH CIRCUITS BACK TO SOURCE PANEL AND MARK THEM AS A SPARES.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 39: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

100.1100.2

100

103.2 103.1

103

103.5103.4103.3

BASEMENTFLOOR BELOW

ELEV

BASEMENTFLOOR BELOW

SECONDFLOOR ABOVE

EXTERIORCIRCULATION

DN

DN

DN

UP

MechJan

Lounge

UP

Lobby

Mech

Office Office

Recept

OfficeOfficeStorage

UP DNUP

SD

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

O O O

OO

EXISTING LP-1A

1

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:3

6 A

M

ED-101

FIRST FLOOR DEMOLITION -

ELECTRICAL

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R HT

1/8" = 1'-0"1 FIRST FLOOR DEMOLITION - ELECTRICAL

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

SHEET NOTES :

1. UNLESS OTHERWISE NOTED, ALL ELECTRICAL DEVICES SHOWN ON THIS DRAWING ARE EXISTING TO REMAIN.

KEYNOTES:

1. DEVICE WILL BE REPLACED, MAINTAIN WIRING, COORDINATE WORK WITH FACILITY FIRE DEPARTMENT AND FIRE ALARM VENDOR BEFORE START OF WORK. REFER TO DRAWING ES-101.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 40: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

102

102.1

105.1105.2

105.5105.4105.3

105

DN

Lounge

Jan

DN

UP

Open to Below

Elev

UPDNDN

OfficeOffice

OfficeOfficeWorkRoom

OpenOffice

Open to Below

J

J

J

SD

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

A

/+72CLOCK

O O O

O O

1

1

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:3

8 A

M

ED-101-M

MEZZANINE FLOOR

DEMOLITION - ELECTRICAL

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R HT

1/8" = 1'-0"1 MEZZANINE FLOOR DEMOLITION - ELECTRICAL

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

KEYNOTES:

1. DEVICE TO BE REPLACED, MAINTAIN WIRING, REFER TO DRAWINGS ES-101-M.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 41: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

J

J

J

J

J

JJ

J

DB

J

J

SD

F

J

J

J

J

J

J

J

J

J J

JJ

J

J

J

J

F

DB

J

J J

J

J

J

J

J

OC

J

J

J

J

J

JJ

J

J

J

JJ

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

1

OO

O

O

O

OO

O O OO O

O

O

O

OO OOO

O

OO

EXISTING LP-3A

EXISTING RP-3BEXISTING LP-3B

+72CLOCK

H

+72CLOCK

H

2

2

2

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:3

9 A

M

ED-103

THIRD FLOOR DEMOLITION -

ELECTRICAL

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R

HT

1/8" = 1'-0"1 THIRD FLOOR DEMOLITION - ELECTRICAL

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

KEYNOTES:

1. FIXTURE TO BE RELOCATED, REFER TO SHEET EL-103. REMOVE BRANCH CIRCUIT BACK TO SOURCE.

2. DEVICE WILL BE REPLACED, MAINTAIN WIRING, COORDINATE WORK WITH FACILITY FIRE DEPARTMENT AND FIRE ALARM VENDOR BEFORE START OF WORK. REFER TO DRAWING ES-103.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 42: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

013.1

013.2 005.4

005.3

005.2

005.1005

023.1

sound

booth

#2

sound

booth

#1

sound

booth

#1

sound

booth

#2

sound

booth

#1

sound

booth

#1

future sound

booth

Office

Office Office

SupervisorOffice

LabStorage

Hearing AidFitting

Lab

Lab

001

013

015

040

030

030

007

020

014

012

029

031

002004

006.4

006.3

006.2

006008010

016.31

016.4

016.3

016.2

016

016.10

016.11

019017021

023

025

027

STAIR

Lab

Lab

STAIR

STAIR

C&IT

Storage

Storage

EngOffice

Jan

Men

Women

ClassroomClassroom

Office

Office

Office

OfficeClassroomClassroom

Mech

Mech

Mech

Mech

Mech

Tele

PLC

ClassroomClassroom ComputerLab

Lab

Lab

Teaching Lab

OC

OC

OC

OC

OC

{LS1}

{LS1}

{LS1}

{LS1}

{LS1}

{LS1}

{LS1}

{LS1}

{LS1}

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

OM

O

O

1

1

1

1

12

2

M

2

M

2

2

2

O

O

O

O

1

1

1

1

1

1

3

3

3

3

3

3

4

4

4

4 4

4

1

EM1

F1

5

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

1 A

M

EL-101-B

BASEMENT FLOOR - LIGHTING

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR - LIGHTING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

KEYNOTES:

1. RELOCATED 2-LAMP PARABOLIC FIXTURES, EXTEND EXISTING BRANCH CIRCUIT. CLEAN AND RELAMP FIXTURE.

2. MODIFY LIGHTING CONTROLS AS REQUIRED FOR NEW DEVICES.

3. CLEAN AND RELAMP LIGHT FIXTURES IN THIS ROOM.

4. RELOCATED PRE-WIRED EXISTING SOUND BOOTH.

5. EXTEND UNSWITCHED PORTION OF BRANCH CIRCUIT SERVING THIS ROOM TO EMERGENCY FIXTURE.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

SHEET NOTES :

1. REPLACE LAMPS AND BATTERIES IN EXISTING EXIT SIGNS AND EMERGENCY BATTERY UNITS.

Page 43: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

100.1100.2

100

103.2 103.1

103

103.5103.4103.3

BASEMENTFLOOR BELOW

ELEV

BASEMENTFLOOR BELOW

SECONDFLOOR ABOVE

EXTERIORCIRCULATION

DN

DN

DN

UP

MechJan

Lounge

UP

Lobby

Mech

Office Office

Recept

OfficeOfficeStorage

UP DNUP

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

O O O

OO

1 1 1

1

1 1

EM12

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

0 A

M

EL-101

FIRST FLOOR PLAN - LIGHTING

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R HT

1/8" = 1'-0"1 FIRST FLOOR PLAN - LIGHTING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

KEYNOTES:

1. CLEAN AND RELAMP 2-LAMP PARABOLIC FIXTURES IN THIS ROOM.

2. EXTEND UNSWITCHED PORTION OF BRANCH CIRCUIT SERVING THIS ROOM TO EMERGENCY FIXTURE.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 44: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

Ref

102

102.1

105.1105.2

105.5105.4105.3

105

DN

Lounge

Jan

DN

UP

Open to Below

Elev

UPDNDN

OfficeOffice

OfficeOfficeWorkRoom

OpenOffice

Open to Below

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

O O O

O O

1 1 1

1

1 1

EM12

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

1 A

M

EL-101-M

MEZZANINE FLOOR PLAN -

LIGHTING

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R

HT

1/8" = 1'-0"1 MEZZANINE FLOOR PLAN - LIGHTING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

KEYNOTES:

1. CLEAN AND RELAMP 2-LAMP PARABOLIC FIXTURES IN THIS ROOM.

2. EXTEND UNSWITCHED PORTION OF BRANCH CIRCUIT SERVING THIS ROOM TO EMERGENCY FIXTURE.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 45: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

327

325

328.10

328.09

328.08

328

328.07

328.06

328.05

328.04

328.03

328.02

328.01

326

322.1

300.01

303

304 300.02 300.03

300.04

300

300.11 300.07

300.06

300.05

300.08

300.09300.1

Treatment

Observation

WorkRoom

Office

Office

OpenOffice

Office

COPY

Office

Office

Office

Office

Office

WOMEN'SRESTROOM

UNISEX ADARESTROOM

WORKROOM

Office

TEACHINGLAB Office Office

Office

OpenOffice

OpenOffice Office

Observation

Treatment

Office

TreatmentObservation

MECHANICAL AREA

MECH SHAFT

MECH

DNDN

COOLING TOWER

NIC

305

301

ELEV

NIC NIC NIC NIC

NIC NIC

NIC

NIC

NIC NIC NIC NIC NIC NIC NIC NIC

NIC

NIC

OC OC

OC

OCOC

{LS1}

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

M2 O O O

OO

O

O

M

11

M

M

22

2

O

O

3

22

22

2

2

3EM1

EM1

EM1

EM1

EM1

EM1

EM1 EM1

3

3

3

3 3

3

3

3

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

2 A

M

EL-103

THIRD FLOOR PLAN - LIGHTING

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R

HT

1/8" = 1'-0"1 THIRD FLOOR PLAN - LIGHTING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

KEYNOTES:

1. RELOCATED FIXTURE. EXTEND BRANCH CIRCUITS FROM ADJACENT FIXTURES. MODIFY WIRING WITH NEW CONTROLS SO THAT ALL FIXTURES ARE SWITCHED TOGETHER.

2. MODIFY WIRING AS REQUIRED IN THIS ROOM FOR NEW CONTROLS.

3. EXTEND UNSWITCHED PORTION OF BRANCH CIRCUIT SERVING THIS ROOM TO EMERGENCY FIXTURE.

#

SHEET NOTES :

1. CLEAN AND RELAMP 2-LAMP PARABOLIC FIXTURES INDICATED IN AREAS OF WORK. CLEAN AND RELAMP FIXTURES IN RESTROOMS.

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 46: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

013.1

013.2 005.4

005.3

005.2

005.1005

023.1

sound

booth

#2

sound

booth

#1

sound

booth

#1

sound

booth

#2

sound

booth

#1

sound

booth

#1

future sound

booth

Office

Office Office

SupervisorOffice

LabStorage

Hearing AidFitting

Lab

Lab

001

013

015

040

030

030

007

020

014

012

029

031

002004

006.4

006.3

006.2

006008010

016.31

016.4

016.3

016.2

016

016.10

016.11

019017021

023

025

027

STAIR

Lab

Lab

STAIR

STAIR

C&IT

Storage

Storage

EngOffice

Jan

Men

Women

ClassroomClassroom

Office

Office

Office

OfficeClassroomClassroom

Mech

Mech

Mech

Mech

Mech

Tele

PLC

ClassroomClassroom ComputerLab

Lab

Lab

Teaching Lab

E E E E

E E E E

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

EXISTING RP-BD

A

A

A

SOUNDBOOTH

A

A

A

A

A

A

A

PUMP (SP-001)

EXISTING MCC

EXISTING LP-BC

EXISTING EMERGENCY

LP-E

EXISTING MASTER

CLOCK & PROGRAM

MACHINE

EXISTING LP-BB

EXISTING LP-BA

C

C

C

C

EXISTING DP-1

EXISTING SB-1

+72

CLOCK

+72CLOCK

+72

CLOCKEXISTING RP-BG

EXISTING RP-BH

EXISTING RP-BF

EXISTING SECURITY

CONTROL PANELS

EXISTING SECURITY

CONTROL PANELS

1

1

96"

2

SOUNDBOOTH

96"

3

SOUNDBOOTH96"

4

5

6

7

8

SOUNDBOOTH96"

SOUNDBOOTH96"

SOUNDBOOTH96"

9

10

10

11

12

13 13

10

14

14

14

14

14

14

141414

14

14

14

14

A A A

13

14

A1314A

SOUNDBOOTH96"9

PUMP (SP-001)

15

VAV-B-6

VAV-B-4

VAV-B-5

VAV-B-3

VAV-B-8

VAV-B-7

VAV-B-2

VAV-B-1

16

16

16

17

17

18

20

19

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

4 A

M

EP-101-B

BASEMENT FLOOR - POWER

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR - POWER

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

10. CIRCUIT TO SPARE 20A BREAKER IN PANEL RP-BD.

11. CIRCUIT RECEPTACLES IN THIS ROOM TO SPARE 20A BREAKER IN PANEL RP-BH, U.N.O.

12. CIRCUIT NEW RECEPTACLES IN THIS ROOM TO SPARE 20A BREAKER IN PANEL RP-BH.

13. CIRCUIT NEW RECEPTACLES IN THIS ROOM TO SPARE 20A BREAKER IN PANEL RP-BD.

14. PROVIDE SURFACE RACEWAY FOR RECEPTACLES INDICATED, REFER TO DETAIL 2 ON SHEET EP-300.

15. CIRCUIT TO SPARE 20A BREAKER IN PANEL RP-BG.

16. CIRCUIT VAV CONNECTIONS TO SPARE 20A BREAKER IN PANEL RP-BG.

17. CIRCUIT VAV CONNECTIONS TO SPARE 20A BREAKER IN PANEL LP-BB.

KEYNOTES:

1. CIRCUIT RECEPTACLES IN THIS ROOM TO SPARE 20A BREAKER IN PANEL LP-BB.

2. CIRCUIT TO SPARE 20A BREAKER IN PANEL LP-BA.

3. CIRCUIT TO SPARE 20A BREAKER IN PANEL RP-BF.

4. CIRCUIT TO SPARE 20A BREAKER IN PANEL RP-BG.

5. EXTEND EXISTING CIRCUIT TO NEW RECEPTACLES.

6. CIRCUIT RECEPTACLES IN THIS ROOM TO SPARE 20A BREAKER IN PANEL RP-BF.

7. CIRCUIT RECEPTACLES TO SPARE 20A BREAKER IN PANEL RP-BF.

8. CIRCUIT RECEPTACLES IN THIS ROOM TO SPARE 20A BREAKER IN PANEL RP-BG, U.N.O.

9. CIRCUIT TO SPARE 20A BREAKER IN PANEL RP-BH.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

18. CIRCUIT VAV CONNECTION TO SPARE 20A BREAKER IN PANEL LP-BA.

19. CIRCUIT VAV CONNECTION TO SPARE 20A BREAKER IN PANEL RP-BH20. CIRCUIT VAV CONNECTION TO SPARE 20A BREAKER IN PANEL RP-BD.

Page 47: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

100.1100.2

100

103.2 103.1

103

103.5103.4103.3

BASEMENTFLOOR BELOW

ELEV

BASEMENTFLOOR BELOW

SECONDFLOOR ABOVE

EXTERIORCIRCULATION

DN

DN

DN

UP

MechJan

Lounge

UP

Lobby

Mech

Office Office

Recept

OfficeOfficeStorage

UP DNUP

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

EXISTING LP-1A

EXISTING LP-1B

FAP-1

VCC-11

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

3 A

M

EP-101

FIRST FLOOR PLAN - POWER

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R HT

1/8" = 1'-0"1 FIRST FLOOR PLAN - POWER

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

KEYNOTES:

1. CIRCUIT FAP-1 AND VCC-1 TO LP-E.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 48: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

Ref

102

102.1

105.1105.2

105.5105.4105.3

105

DN

Lounge

Jan

DN

UP

Open to Below

Elev

UPDNDN

OfficeOffice

OfficeOfficeWorkRoom

OpenOffice

Open to Below

J

J

J

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

A

COFFEE

MICROWAVE

REFRIGERATOR

/+72CLOCK

1

2

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

5 A

M

EP-101-M

MEZZANINE FLOOR PLAN -

POWER

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R HT

1/8" = 1'-0"1 MEZZANINE FLOOR PLAN - POWER

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

KEYNOTES:

1. CONNECT TO EXISTING CIRCUIT.2. PROVIDE SURFACE RACEWAY FOR

RECEPTACLE, REFER TO DETAIL 2 ON SHEET EP-300. CIRCUIT TO SPARE BREAKER IN LP-1A.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 49: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

327

325

328.10

328.09

328.08

328

328.07

328.06

328.05

328.04

328.03

328.02

328.01

326

322.1

300.01

303

304 300.02 300.03

300.04

300

300.11 300.07

300.06

300.05

300.08

300.09300.1

Treatment

Observation

WorkRoom

Office

Office

OpenOffice

Office

COPY

Office

Office

Office

Office

Office

WOMEN'SRESTROOM

UNISEX ADARESTROOM

WORKROOM

Office

TEACHINGLAB Office Office

Office

OpenOffice

OpenOffice Office

Observation

Treatment

Office

TreatmentObservation

MECHANICAL AREA

MECH SHAFT

MECH

DNDN

COOLING TOWER

NIC

305

301

ELEV

NIC NIC NIC NIC

NIC NIC

NIC

NIC

NIC NIC NIC NIC NIC NIC NIC NIC

NIC

NIC

J

J

J

J

J

JJ

J

DB

J

J

J

J

J

J

J

J

J

J J

JJ

J

J

DB

J

J

J

J

J

J

J

J

J

J

J

J

JJ

J

J

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

PROJECTOR

C

EXISTING LP-3A EXISTING LP-3B

H

R

R

R

CLOCK

+72

H

+72

A

A

EXISTING RP-3B

H

H

A A A A

A

A A A

A

A 1

22

1

1

3

3

44

4

4

4

4

1

1 4

4

5 WATER HEATER (WH-1)

6

INTERCOM POWER SUPPLY

VAV-3-1

7

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

6 A

M

EP-103

THIRD FLOOR PLAN - POWER

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R

HT

1/8" = 1'-0"1 THIRD FLOOR PLAN - POWER

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

KEYNOTES:

1. EXTEND EXISTING BRANCH CIRCUIT TO NEW RECEPTACLE.

2. CIRCUIT (2) QUADS EACH TO A SPARE 20A BREAKER IN PANEL LP-3B.

3. CIRCUIT (3) RECEPTS EACH TO A SPARE 20A BREAKER IN PANEL LP-3B.

4. PROVIDE SURFACE RACEWAY FOR RECEPTACLES. REFER TO DETAIL 2 ON SHEET EP-300.

5. CIRCUIT WATER HEATER TO SPARE 20A BREAKER IN PANEL LP-3B.

6. CIRCUIT RECEPTACLE TO SPARE 20A BREAKER IN PANEL LP-3B.

7. CIRCUIT VAV CONNECTION TO SPARE 20A BREAKER IN PANEL LP-3B.

#

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 50: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

SEE ARCHITECTURALPLANS FOR WALL CONSTRUCTION

PLASTER RING TO COMEWITHIN 1/8" OF FINAL SURFACE

STUD

MOUNTING BRACKET SHALL PROVIDESUPPORT FROM STUD AND BACK OFWALL OR TWO STUDS.

NOTES :

1. THE INTENT OF THE DETAIL IS TO ENSURE DEVICE ROUGH-INS ARE ALIGNED, SOLIDLY MOUNTED AND THE SURFACE OF THE TRIM IS EITHER FLUSH WITH THE WALL SURFACE OR WITHIN 1/8" OF THE WALL SURFACE. JUNCTION BOXES LARGER THAN 4" SQUARE SHALL BE MOUNTED IN A MANNER THAT IS SIMILAR TO THE SYSTEM NOTED ABOVE OR ACHIEVES THE SAME RESULTS.

2. PLASTER RINGS DEPTH SHALL BE 1/8" DEEPER THAN THE GYP BOARD APPLIED TO THE WALL. PLASTER RING SHALL BE 3/4" FOR USE WITH 5/8" GYP BOARD.

3. MOUNTING BRACKET FOR 2 1/2" OR 3 1/2" STUDS SHALL BE CADDY #H23, OR B-LINE BB4-23. MOUNTING BRACKET FOR FOR 4" OR 6" STUDS SHALL BE CADDY #H46TC OR B-LINE BB4-# . FOR MULTIPLE BOXES BETWEEN STUDS, BRACKET SHALL BE CADDY #RBS16/#RBS24 OR B-LINE BB6-# OR BBF# FLOOR MOUNT SUPPORT WITH BBFC.

4. WHERE RECEPTACLE AND TECHNOLOGY DEVICES ARE SHOWN SERVING A COMMON COMPUTER OR EQUIPMENT, OR SHOWN IN SIMILAR LOCATIONS ON THE DRAWINGS THE DEVICES SHALL BE INSTALLED ON OPPOSITE SIDES OF A COMMON STUD OR IN ADJACENT OPENINGS WITH MOUNTING BRACKETS.

RATED WALL (CONSTRUCTION VARIES)

NOTE 2

FIRE SEALANT

NOTE 3

FIRE SEALANT

PENETRATING ITEM

NOTE 4

NOTE 3

NOTE 2

PENETRATING ITEM

NOTE 4

NOTE 3

RATED FLOOR (CONSTRUCTION VARIES)

NOTES :

1. THIS GENERAL DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL MOVEMENT. REFER TO SPECIFICATION SECTION 07840 (16080) FOR SELECTION OF THROUGH PENETRATION FIRE STOPPING.

2. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL. EACH CONTRACTOR FURNISHES SLEEVE TO G.C., COORDINATES SLEEVE LOCATIONS AND DEBURS SLEEVE. G.C. BUILDS SLEEVE INTO WALL OR FLOOR ALLOWING NO GAP AROUND SLEEVE. IF SLEEVE IS NOT PROVIDED WHEN WALL OR FLOOR IS BUILT, CONTRACTOR SHALL INSTALL SLEEVE. SLEEVE SIZE SHALL ALLOW ANNULAR SPACE REQUIRED BY THE SELECTED FIRE STOP SYSTEM.

3. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION LISTING. SECURE TO WALL OR FLOOR TO ALLOW LONGITUDINAL MOVEMENT OF PENETRATING ITEM WITHOUT MOVEMENT OF FIRE BARRIER.

4. WATER-TIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET METAL ANGLE FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF WATERPROOF SEALANT BETWEEN FLOOR AND BOTTOM OF ANGLE FRAME. SECURE TO FLOOR WITH MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS. MULTIPLE PENETRATING ITEMS MAY BE ENCLOSED IN ONE FRAME.

DUPLEX RECEPTACLE(DESIGNATED ON PLANS)

1 1/4" TELECOMM CONDUIT(S) AS REQUIRED

BRANCH CIRCUIT CONDUIT(S)

SURFACE RACEWAY TOABOVE ACCESSIBLE CEILING

WW-#4 3/4" HIGH X 1 3/4" DEEP SURFACEMETAL RACEWAY WITH LOW VOLTAGE DIVIDER.LENGTH AS SHOWN ON DRAWINGS.

TR

CLASS II LOW VOLTAGE TRANSFORMER, WITH PRIMARY AND SECONDARY FUSING. MOUNT IN NEMA 1 ENCLOSURE ABOVE ACCESSIBLE CEILING.

H

GND

2#14 & 1#14 GND IN 1/2" FLEXFOR LOW VOLTAGE CLASS IIWIRING TO CONTROL MODULES.

MOUNTED ONWALL, BEHINDWATER CLOSET.

MAXIMUM OF SIX MODULESPER TRANSFORMER. MAXIMUM 50' WIRING LENGTH.

LOW VOLTAGESOLENOID VALVE.

WATER CLOSET LOWVOLTAGE SENSOR /CONTROL

N

NOTES :

1. PROVIDE DOUBLE GANG BACKBOXES AND PLASTER RINGS AT LOCATIONS COORDINATED WITH PLUMBING CONTRACTOR (P.C.)

2. E.C. SHALL FIELD VERIFY EXACT SENSOR LOCATION WITH P.C. PRIOR TO ROUGH-IN.

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

6 A

M

EP-300

POWER DETAILS

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

NO SCALE1 BACKBOX MOUNTING DETAIL

NO SCALE3 FIRE BARRIER PENETRATION

NO SCALE2 SURFACE WIREWAY DETAIL

Owner Review 60% CD's Nov. 13, 2018

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

NO SCALE4 ELECTRONIC SENSOR WIRING

Page 51: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

013.1

013.2 005.4

005.3

005.2

005.1005

023.1

sound

booth

#2

sound

booth

#1

sound

booth

#1

sound

booth

#2

sound

booth

#1

sound

booth

#1

future sound

booth

Office

Office Office

SupervisorOffice

LabStorage

Hearing AidFitting

Lab

Lab

001

013

015

040

030

030

007

020

014

012

029

031

002004

006.4

006.3

006.2

006008010

016.31

016.4

016.3

016.2

016

016.10

016.11

019017021

023

025

027

STAIR

Lab

Lab

STAIR

STAIR

C&IT

Storage

Storage

EngOffice

Jan

Men

Women

ClassroomClassroom

Office

Office

Office

OfficeClassroomClassroom

Mech

Mech

Mech

Mech

Mech

Tele

PLC

ClassroomClassroom ComputerLab

Lab

Lab

Teaching Lab

F FF

F

HD

SD

AH

AH

A1 A3

A1

A7

A1A1 A1

A1 A1A1

A1

A1A1

A7 A7 A7

A7

A7

A7

A1

V1

V1

A1

V1

A7 A7 A7 A7

A1

V1

A7

A3

A3

A3

A1

A1

MM

MM

AR

A1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

?

SPRINKLERFLOW ANDTAMPER

RECALL

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

8 A

M

ES-101-B

BASEMENT FLOOR - SYSTEM

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR - SYSTEM

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 52: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

100.1100.2

100

103.2 103.1

103

103.5103.4103.3

BASEMENTFLOOR BELOW

ELEV

BASEMENTFLOOR BELOW

SECONDFLOOR ABOVE

EXTERIORCIRCULATION

DN

DN

DN

UP

MechJan

Lounge

UP

Lobby

Mech

Office Office

Recept

OfficeOfficeStorage

UP DNUP

F

F

A3A1

SD

A1

FF

F F

FF

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

FAA-1

FAP-1

VCC-1

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

7 A

M

ES-101

FIRST FLOOR PLAN - SYSTEMS

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R HT

1/8" = 1'-0"1 FIRST FLOOR PLAN - SYSTEMS

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 53: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

Ref

102

102.1

105.1105.2

105.5105.4105.3

105

DN

Lounge

Jan

DN

UP

Open to Below

Elev

UPDNDN

OfficeOffice

OfficeOfficeWorkRoom

OpenOffice

Open to Below

F

A3

V1

A3

SD

A1

F

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

8 A

M

ES-101-M

MEZZANINE FLOOR PLAN -

SYSTEMS

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R HT

1/8" = 1'-0"1 MEZZANINE FLOOR PLAN - SYSTEMS

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 54: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

327

325

328.10

328.09

328.08

328

328.07

328.06

328.05

328.04

328.03

328.02

328.01

326

322.1

300.01

303

304 300.02 300.03

300.04

300

300.11 300.07

300.06

300.05

300.08

300.09300.1

Treatment

Observation

WorkRoom

Office

Office

OpenOffice

Office

COPY

Office

Office

Office

Office

Office

WOMEN'SRESTROOM

UNISEX ADARESTROOM

WORKROOM

Office

TEACHINGLAB Office Office

Office

OpenOffice

OpenOffice Office

Observation

Treatment

Office

TreatmentObservation

SD

F FA7

V1

V1

A3

A3

A3

A1

A1 A1

A1

A

A

V1

A1

A1

AH

A1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

9 A

M

ES-103

THIRD FLOOR PLAN - SYSTEMS

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

NO R

HT

1/8" = 1'-0"1 THIRD FLOOR PLAN - SYSTEMS

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 55: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

J

NEPCI

CI

CI

CIC

I

NETWORK CONNECTIONSEE SPECIFICATIONS

SIGNAL LINE CIRCUIT (SLC)

NOTIFICATION APPLIANCE CIRCUIT (NAC)

EVACUATION - SIGNALING ZONE #

NOTIFICATION APPLIANCE CIRCUIT (NAC)

FAA-1

NEW FAP-1

VCC-1

SIGNAL LINE CIRCUIT(SLC)

CIRCUIT INTEGRITY WIRING. (TYPICAL)

MM

AR TO ELEVATOR SHUNT TRIP BREAKER

MM

MM

MS

FS

F FT H SD

2 31

SD MM

HF

MM

HX

V

A

F

2

J

V1 V1 V11

3

A A MH HW

A1 A11 A11

KEYNOTES:

PROVIDE NOTIFICATION APPLIANCE EXTENDER PANELS AS REQUIRED. DETERMINATION OF NEED TO BE MADE BY FIRE ALARM VENDOR. REFER TO SPECIFICATIONS FOR REQUIREMENTS AND ACCEPTABLE MOUNTING LOCATIONS.

REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH INITIATION LOOP AND WIRING STYLE. REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.

REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH NOTIFICATION APPLIANCE CIRCUIT AND WIRING STYLE. REFER TO FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.

1

2

3

NOTES :

1. THE RISER DIAGRAM IS INTENDED TO CONVEY THE TYPES OF FIRE ALARM CONNECTIONS AND SPECIFICALLY DOES NOT INDICATE QUANTITIES, NUMBER OF CIRCUITS REQUIRED OR DISTANCES.

2. THE COMPLETE FIRE ALARM SYSTEM SHALL MEET ALL APPLICABLE CODES AND MANUFACTURER'S RECOMMENDATIONS.

3. CONTRACTOR SHALL COORDINATE ALL WIRE SIZES, TYPES AND REQUIREMENTS WITH THE VENDOR PRIOR TO BID. REFER TO SPECIFICATIONS TO DETERMINE CIRCUIT STYLES AND IF CONDUIT IS REQUIRED OR PLENUM RATED CABLE IS ACCEPTABLE.

4. ALL +120VAC WIRING REQUIRED FOR OPERATION OF THE SYSTEM AS DESCRIBED IN THE CONSTRUCTION DOCUMENTS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR.

5. ALL NECESSARY RELAYS MAY NOT BE SHOWN ON THIS PLAN, BUT WHERE REQUIRED FOR PROPER OPERATION OF THE SYSTEM THEY SHALL BE PROVIDED BY THE CONTRACTOR.

6. PARTIAL EVACUATION OR RELOCATION OF OCCUPANTS IS THE STANDARD OPERATING PROCEDURE FOR THIS FACILITY IN THE EVENT OF AN ALARM. THEREFORE, ALL NOTIFICATION APPLIANCE CIRCUITS MUST BE INSTALLED AND PROTECTED IN ACCORDANCE WITH THE CIRCUIT SURVIVABILITY REQUIREMENTS DESCRIBED IN NFPA 72. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

7. PROVIDE CONNECTIONS FOR WORK ON SECOND FLOOR (NIC), COORDINATE WITH OWNER.

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:0

9:4

9 A

M

ES-300

SYSTEM DETAILS

JEFGLAJALJAL

MARABR

18004050.00

JALJAL

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

JALJAL

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

NO SCALE1 FIRE ALARM RISER

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 56: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

TECHNOLOGY SYMBOL LIST

SYMBOL: DESCRIPTION: NOTE:EQUIPMENT

LIST ABBREV.:

C#

C#1.INFORMATION OUTLET (CEILING)SC-IO-C

1.INFORMATION OUTLET (WALL)SC-IO-W

.EXISTING INFORMATION OUTLET (WALL)N/A

WAP .EXISTING WIRELESS ACCESS POINT DEVICE (CEILING)N/A

C .EXISTING CLOCK (WALL)N/A

CR .EXISTING CREDENTIAL READERN/A

KP EXISTING KEYPADN/A .

IS1

IM1 .INTERCOM MASTER STATION - TYPE 1 (WALL)IC-IM1-W

.INTERCOM STATION - TYPE 1 (WALL)IC-IS1-W

TECHNOLOGY ABBREVIATION KEY

TELECOMMUNICATIONS ROOMTR-#

ABOVE FINISHED FLOORAFF

BELOW FINISHED CEILINGBFC

CONDUITC

SIMILARSIM

TYPICALTYP

MOUNTING HEIGHT ABOVE FINISHED FLOOR+#

JUNCTION BOXJ-BOX

ABBR: DESCRIPTION:

UNLESS NOTED OTHERWISEUNO

TECHNOLOGY GENERAL NOTES:1. ###-### INDICATES GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ITEM LABELED AS

"EQUIPMENT LIST ABBREVIATION"2. REFER TO GENERAL TECHNOLOGY EQUIPMENT SCHEDULE AND SPECIFICATIONS FOR FULL

DESCRIPTIONS AND MANUFACTURERS OF ALL DEVICES.

TECHNOLOGY MOUNTING SUBSCRIPT KEY:A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASHH MOUNT ORIENTED HORIZONTALLYL MOUNT IN CASEWORKM MOUNT IN MODULAR FURNITURES MOUNT IN SURFACE RACEWAY

A SLASH IS USED BETWEEN TWO SUBSCRIPTS, E.G., A/H.

1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON THIS PAGE FOR ADDITIONAL INFORMATION.

2. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, IN FLOOR SLAB, ETC. UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT IN MECHANICAL ROOMS AND STORAGE ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON BUILDING STRUCTURE.

3. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE OFFSET A MINIMUM OF 6" HORIZONTALLY. BOXES ON OPPOSITE SIDES OF FIRE RATED WALLS SHALL BE OFFSET A MINIMUM OF 24" HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.

4. VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL TELECOMMUNICATIONS INSTALLATION, ADJUST OUTLETS OR CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE AND/OR EQUIPMENT.

5. TELECOMMUNICATIONS EQUIPMENT SHALL BE MOUNTED TO ALLOW ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF TELECOMMUNICATION DEVICES ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR SHALL BE APPROVED IN ADVANCE BY THE OTHER CONTRACTOR.

6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR SEALED INTO OPENINGS.

7. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF THROUGH-PENETRATION FIRESTOPS. REFER TO 26 05 03 FOR ADDITIONAL INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.

8. REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE EXECUTION OF TELECOMMUNICATIONS WORK THAT IS OUTSIDE THE CONTRACT LIMITS OF CONSTRUCTION. REPLACE CEILING TILES WITH IDENTICAL MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.

9. FLUSH MOUNT ALL TELECOMMUNICATION OUTLETS AT +18" FROM FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.

10. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: LIGHTING SWITCHES 4'-0" RECEPTACLES (GENERAL AREAS) 1'-6" RECEPTACLES (UTILITY AREAS) 4'-0" TELECOMMUNICATION OUTLETS 1'-6" WALL PHONE 4'-0" FIRE ALARM STATIONS 4'-0" FIRE ALARM SIGNALS 7'-6" CLOCKS/CLOCK OUTLETS 1’-6” BELOW FIN. CEIL. SAFETY SWITCHES 5'-0" TO TOP

TECHNOLOGY INSTALLATION NOTES:

GENERAL NOTES:

1. ALL SYMBOLS AND ABBREVIATIONS LISTED MAY NOT BE APPLICABLE TO THIS PROJECT. REFER TO THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE COMPLETE DESCRIPTION AND ITEMS.

2. ALL SYMBOLS AND ABBREVIATIONS REFER TO TECHNOLOGY SHEETS ONLY AS DEFINED ON THE SHEET INDEX. REFER TO THE GENERAL TECHNOLOGY NOTES FOR ADDITIONAL INFORMATION.

3. ALL SYMBOLS LISTED ABOVE ARE FOR REFERENCE ONLY. REFER TO PLANS AND LINE TYPE KEY FOR NEW, EXISTING TO REMAIN AND TO BE REMOVED ITEMS FOR ADDITIONAL INFORMATION.

TECHNOLOGY SYMBOL NOTES:

1. "C#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION. REFER TO INFORMATION OUTLET SCHEDULE ON T-200 FOR ADDITIONAL INFORMATION.

DIAMETERø C CONDUIT

CONDUIT DOWN

CONDUIT UP OR UP/DOWN

CONDUIT SLEEVE

CONTINUATION

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

NAME

1VIEW NAME1/8" = 1'-0"

LEVEL NAME

10' - 0" HEIGHT ABOVE PROJECT 0' - 0"

1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL

NO R HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)

NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN (LIGHT SOLID LINE)

EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)

LINE TYPE KEY:

BUILDING CODE: MBC 2015 EDITION

FIRE CODE: NFPA 13: 2013 EDITION

PLUMBING CODE: MBC 2015 EDITION

MECHANICAL CODE: MMC 2015 EDITION

ELECTRICAL CODE: NFPA 70 (NEC) 2016EDITION

LIFE SAFETY CODE: NFPA 101 2015 EDITION

ENERGY CONSERVATION CODE: ASHRAE 90.1 2013

HEALTH DEPARTMENT CODE: CURRENT EDITION

LOCAL BUILDING CODE: CURRENT EDITION

APPLICABLE CODES

CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.

TEMPERATURE CONTROLS CONTRACTORT.C.C.

SECURITY CONTRACTORS.C.

AUDIO/VISUAL CONTRACTORA.V.C.

ASBESTOS ABATEMENT CONTRACTOR

HEATING CONTRACTORH.C.

PLUMBING CONTRACTORP.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

VENTILATION CONTRACTORV.C.

ELECTRICAL CONTRACTORE.C.

A.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

48

" M

AX

.

20" MAX.

44

" M

AX

.

20"-25" MAX.

48

" M

AX

.

15

" M

IN. 48

" M

AX

.

46

" M

AX

.

10" MAX. 10"-24" MAX.

ADA GUIDELINES - FRONT ACCESS

ADA STANDARDS FOR ACCESSIBLE DESIGN

INSTALL ABOVE COUNTER DEVICE AT 44" ABOVE FINISHED FLOOR.

INSTALL ABOVE COUNTER DEVICE AT 40" ABOVE FINISHED FLOOR.

INSTALL DEVICE AT 18" ABOVE FINISHED FLOOR.

ADA GUIDELINES - SIDE ACCESS

INSTALL DEVICE AT 44" ABOVE FINISHED FLOOR.

INSTALL DEVICE AT 42" ABOVE FINISHED FLOOR.

TECHNOLOGY SHEET INDEXT-000 TECHNOLOGY COVERSHEET

TD-101-B BASEMENT FLOOR DEMOLITION - TECHNOLOGY

TD-103 THIRD FLOOR DEMOLITION - TECHNOLOGY

T-101-B BASEMENT FLOOR - TECHNOLOGY

T-101 FIRST FLOOR PLAN - TECHNOLOGY

T-103 THIRD FLOOR PLAN - TECHNOLOGY

T-200 TECHNOLOGY DETAILS, RISERS AND SCHEDULES

SUGGESTED MATRIX OF RESPONSIBILITY

ITEM: SHOWN ON:FURNISHED

BY:INSTALLED

BY: NOTES:

TECHNOLOGY ROUGH-IN, REFER TOGENERAL TECHNOLOGY EQUIPMENTSCHEDULE AND SPECIFICATIONS FORDEFINITION

T-SERIES E.C. E.C. 3. 4.

INFORMATION OUTLET FACEPLATES,JACKS, AND TERMINATIONS

T-SERIES T.C. T.C.

CONDUIT SLEEVES (WHEN SHOWN ONDRAWINGS)

T-SERIES E.C. E.C.

CONDUIT SLEEVES (NOT SHOWN BUTREQUIRED FOR PROPER INSTALLATIONOF SYSTEM)

N/A T.C. T.C. 2. 4.

TELECOMMUNICATION SYSTEMSROUGH-IN

T-SERIES E.C. E.C. 1.

TELECOMMUNICATION EQUIPMENT,CABLING, AND TERMINATIONS

T-SERIES T.C. T.C.

GROUNDING LUGS ON TECHNOLOGYEQUIPMENT

T-SERIES T.C. E.C. 6.

LINE VOLTAGE POWER (+120V ORGREATER)

E-SERIES E.C. E.C.

LINE VOLTAGE POWER (NOT SHOWNBUT REQUIRED FOR PROPERINSTALLATION OF SYSTEM)

N/A T.C. E.C. 2. 4.

LOW VOLTAGE CABLING FORTECHNOLOGY SYSTEMS

T-SERIES T.C. T.C.

CABLE HANGERS AND SUPPORTS OROTHER CABLE ROUTING METHODS(OTHER THAN CONDUIT AND CABLETRAY)

T-SERIES T.C. T.C. 5.

FLOOR BOX (ROUGH-IN) T & E SERIES E.C. E.C.

SUGGESTED MATRIX OF RESPONSIBILITY NOTES

1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATIONOUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FORADDITIONAL INFORMATION.

2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALLREQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLEMANUFACTURERS.

3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMSINSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THECONTRACT DOCUMENTS.

4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OFTHE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEMCONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE CONTRACTOR SHALL BE INCLUDEDIN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN.

5. UNLESS TRADE RULES DICTATE OTHERWISE.

6. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FORINSTALLATION IN THE FIELD.

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:1

1:5

8 A

M

T-000

TECHNOLOGY COVERSHEET

JEFGILTIMADA

POOVYA

18004050.00

TIMADA

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

TIMADA

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 57: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

001

013

015

040

030

030

007

020

014

012

029

031

002004

006.4

006.3

006.2

006008010

016.31

016.4

016.3

016.2

016

016.10

016.11

019017021

023

025

027

STAIR

Lab

Lab

STAIR

STAIR

C&IT

Storage

Storage

EngOffice

Jan

Men

Women

ClassroomClassroom

Office

Office

Office

OfficeClassroomClassroom

Mech

Mech

Mech

Mech

Mech

Tele

PLC

ClassroomClassroom ComputerLab

Lab

Lab

Teaching Lab

CRC

C

C

WAP

CR

KP

CR

KP

C

C

WAP

C

C

CR

KPKP

WAP

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

EXISTING TELECOM ROOM

EXISTING

EQUIPMENT

RACK TYP.

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:1

2:0

2 A

M

TD-101-B

BASEMENT FLOOR DEMOLITION

- TECHNOLOGY

JEFGILTIMADA

POOVYA

18004050.00

TIMADA

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

TIMADA

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR DEMOLITION - TECHNOLOGY

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

GENERAL NOTES :

1. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND LINE TYPE KEY.

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 58: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

C

WAP

WAP

CR

WAP

CR

WAP

WAP

C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

EXISTING TELECOM ROOM

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:1

2:0

3 A

M

TD-103

THIRD FLOOR DEMOLITION -

TECHNOLOGY

JEFGILTIMADA

POOVYA

18004050.00

TIMADA

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

TIMADA

NO R

HT

1/8" = 1'-0"1 THIRD FLOOR DEMOLITION - TECHNOLOGY

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

GENERAL NOTES :

1. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND LINE TYPE KEY.

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 59: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

013.1

013.2 005.4

005.3

005.2

005.1005

023.1

sound

booth

#2

sound

booth

#1

sound

booth

#1

sound

booth

#2

sound

booth

#1

sound

booth

#1

future sound

booth

Office

Office Office

SupervisorOffice

LabStorage

Hearing AidFitting

Lab

Lab

D0

01

.1

D0

01

.2

D0

01

.3

D0

01

.6

D0

01

.5

D0

01

.4

D013.2

D013.2

D0

23

.1

D0

25

D0

30

D0

05

.2D005.1

D005.4

D005.3

D040

001

013

015

040

030

030

007

020

014

012

029

031

002004

006.4

006.3

006.2

006008010

016.31

016.4

016.3

016.2

016

016.10

016.11

019017021

023

025

027

STAIR

Lab

Lab

STAIR

STAIR

C&IT

Storage

Storage

EngOffice

Jan

Men

Women

ClassroomClassroom

Office

Office

Office

OfficeClassroomClassroom

Mech

Mech

Mech

Mech

Mech

Tele

PLC

ClassroomClassroom ComputerLab

Lab

Lab

Teaching Lab

C2-1

C2-1

C2-1

C2-1

C2-1

CRC

C

C

WAP

CR

KP

CR

KP

CR

KPKP

WAP

C2-1

C2-1

/A

C2-1

/A

C2-1

/A

C2-1

/A

C2-1

/A

C2-1

/A

C2-1 /A

C2-1

/A

C2-1 /A

C2-1

/AC

2-1

/A

C2-1 /A

C2-1 /A

C2-1

/A

C2-1

/A

C2-1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

EXISTING TELECOM ROOM

EXISTING

EQUIPMENT

RACK TYP.

11

1

1

1

1

1

1

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:1

2:0

0 A

M

T-101-B

BASEMENT FLOOR -

TECHNOLOGY

JEFGILTIMADA

POOVYA

18004050.00

TIMADA

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

TIMADA

NO R

HT

1/8" = 1'-0"1 BASEMENT FLOOR - TECHNOLOGY

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

GENERAL NOTES :

1. ALL NEW INFORMATION OUTLET ON THIS SHEET SHALL BE SERVED FROM THE EXISTING TELECOMMUNICATIONS ROOM UNLESS OTHERWISE NOTED.

2. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND GENERAL TECHNOLOGY INSTALLATION NOTES.

3. REFER TO T-200 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.

4. REFER TO 1/T-200 FOR CONNECTIVITY DIAGRAM AND ADDITIONAL REQUIREMENTS.

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

KEYNOTES:

1. PROVIDE SURFACE RACEWAY FOR TECHNOLOGY OUTLETS INDICATED.

#

Page 60: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

100.1100.2

100

103.2 103.1

103

103.5103.4103.3

BASEMENTFLOOR BELOW

ELEV

BASEMENTFLOOR BELOW

SECONDFLOOR ABOVE

EXTERIORCIRCULATION

DN

DN

DN

UP

MechJan

Lounge

UP

Lobby

Mech

Office Office

Recept

OfficeOfficeStorage

UP DNUP

C2-1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

a

b

c

d

e

1

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:1

1:5

9 A

M

T-101

FIRST FLOOR PLAN -

TECHNOLOGY

JEFGILTIMADA

POOVYA

18004050.00

TIMADA

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

TIMADA

NO R HT

1/8" = 1'-0"1 FIRST FLOOR PLAN - TECHNOLOGY

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

GENERAL NOTES :

1. ALL NEW INFORMATION OUTLET ON THIS SHEET SHALL BE SERVED FROM THE EXISTING BASEMENT FLOOR TELECOMMUNICATIONS ROOM UNLESS OTHERWISE NOTED.

2. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND GENERAL TECHNOLOGY INSTALLATION NOTES.

3. REFER TO T-200 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.

4. REFER TO 1/T-200 FOR CONNECTIVITY DIAGRAM AND ADDITIONAL REQUIREMENTS.

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

KEYNOTES:

1. PROVIDE SURFACE RACEWAY FOR TECHNOLOGY OUTLETS.

#

Page 61: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

327

325

328.10

328.09

328.08

328

328.07

328.06

328.05

328.04

328.03

328.02

328.01

326

322.1

300.01

303

304 300.02 300.03

300.04

300

300.11 300.07

300.06

300.05

300.08

300.09300.1

Treatment

Observation

WorkRoom

Office

Office

OpenOffice

Office

COPY

Office

Office

Office

Office

Office

WOMEN'SRESTROOM

UNISEX ADARESTROOM

WORKROOM

Office

TEACHINGLAB Office Office

Office

OpenOffice

OpenOffice Office

Observation

Treatment

Office

TreatmentObservation

MECHANICAL AREA

MECH SHAFT

MECH

DNDN

COOLING TOWER

NIC

305

301

ELEV

NIC NIC NIC NIC

NIC NIC

NIC

NIC

NIC NIC NIC NIC NIC NIC NIC NIC

NIC

NIC

C2-1

C

WAP

WAP

CR

WAP

CR

WAP

WAP

C

IM1

IS1

IS1

IM1

IM1

IS1

C1 C1

C2-1

C2-1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

b

c

d

1

2

EXISTING TELECOM ROOM

INTERCOM SYSTEM POWER SUPPLY

3

3

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:1

2:0

0 A

M

T-103

THIRD FLOOR PLAN -

TECHNOLOGY

JEFGILTIMADA

POOVYA

18004050.00

TIMADA

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

TIMADA

NO R

HT

1/8" = 1'-0"1 THIRD FLOOR PLAN - TECHNOLOGY

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

GENERAL NOTES :

1. ALL NEW INFORMATION OUTLET ON THIS SHEET SHALL BE SERVED FROM THE EXISTING BASEMENT FLOOR TELECOMMUNICATIONS ROOM UNLESS OTHERWISE NOTED.

2. REFER TO T-000 FOR TECHNOLOGY SYMBOL LIST AND GENERAL TECHNOLOGY INSTALLATION NOTES.

3. REFER TO T-200 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.

4. REFER TO 1/T-200 FOR CONNECTIVITY DIAGRAM AND ADDITIONAL REQUIREMENTS.

KEYNOTES:

1. PROVIDED FOR OWNER FURNISHED VIDEO PROJECTOR.

2. PROVIDED FOR OWNER FURNISHED WIRELESS ACCESS POINT. COORDINATE SPECIFIC LOCATION WITH OWNER PRIOR TO INSTALLATION.

3. PROVIDE SURFACE RACEWAY FOR TECHNOLOGY OUTLETS.

#

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018

Page 62: DETROIT, MI 48202 · ed103 third floor demolition - electrical el101b basement floor plan - lighting el-101 first floor plan- lighting el101m mezzanine floor plan - lighting el103

EXISTING

VOICE PATCH

PANEL

EXISTING

VOICE PATCH

PANEL

EXISTING

PATCH PANEL

OWNER

PROVIDED

NETWORK

EQUIPMENT

EXISTING FIBER

PANEL

1

2

2-Port Faceplate

2

3-Port Faceplate

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

IDENTIFICATION

3

1

PAIR 3

PAIR 1PAIR 2 PAIR 4

WO WGO BL WBL G WBR BR

1 32 4 5 6 7 8

ANSI/TIA/EIA T568BPIN/PAIR ASSIGNMENT

C#

C#2

2

1

4

EXISTING COPPER

VOICE BACKBONE

EXISTING FIBER

BACKBONE

3

EXISTING TELECOM ROOM

NOTES:

1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS SHOWN. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CABLE TYPE. ALL INFORMATION OUTLETS ARE TYPICAL OF THE OUTLETS IN THE AREA SHOWN. REFER TO FLOOR PLANS FOR MORE SPECIFIC ROUTING AND QUANTITY INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2. REFER TO T-200 FOR GENERAL TECHNOLOGY EQUIPMENT SCHEDULE.

KEYNOTES:

1. 23 GAUGE, 4-PAIR, CATEGORY 6, UNSHIELDED TWISTED PAIR CABLE, SEE SPECIFICATIONS.2. REFER TO INFORMATION OUTLET SCHEDULE ON T-200 AND THE FLOOR PLANS FOR QUANTITY OF

CABLES AND JACKS TO BE INSTALLED AT EACH INFORMATION OUTLET.3. EXISTING RJ-45 TO RJ-45 CATEGORY CAT 6 UTP PATCH CORD.4. EXISTING FIBER PATCH CORD.5. NEW INFORMATION OUTLETS (SC-IO-W) TO TERMINATE TO AVAILABLE OPEN SPACES ON EXISTING

MODULAR PATCH PANELS AND VOICE TERMINATION BLOCKS.

#

EXISTING VOICE

CROSS CONNECT

NOTES:

1. THIS RISER IS DIAGRAMMATIC AND MAY NOT SHOW ACTUAL ROUTING OR QUANTITIES OF MATERIALS. THIS RISER IS SHOWN FOR CLARIFICATION OF CONNECTION LOCATIONS AND CONDUCTOR TYPE. ALL CONNECTIONS AND SYSTEM DEVICES SHOWN ARE TYPICAL AND NOT REPRESENTATIVE OF ACTUAL PROJECT QUANTITIES.REFER TO FLOOR PLANS AND ENLARGED FLOOR PLANS FOR ACTUAL QUANTITIES AND LOCATIONS OF DEVICES AND MORE SPECIFIC ROUTING INFORMATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

IM1 IS1

3C, 18 AWG SHIELDED CABLE

POWER SUPPLY (AIPHONE PS-1225UL) LOCATED WITHIN TELECOM ROOM. REFER TO FLOOR PLANS.

REFER TO SPECIFICATIONS FOR IDENTIFICATION REQUIREMENTS (TYP.)

NUMBER INDICATES FACEPLATE POSITION (TYP.)

FO

R B

IDS

AREA OF WORKNO SCALE

FLOOR LEVEL

project number:

sheet title:

sheet number:

approved

project:

coordination checked

location

drawn

checked

WAYNE STATE

UNIVERSITYFacilities Planning and Management

5454 Cass Avenue

Detroit, MI 48202

key plan:

date:issue:

designed

consultants:

NM Project Number - 18113.0

Prentis Building

IMEG Project Number -

WSU : 00

Prentis Building - Rackham

Relocation

- -

12/1

0/2

018 1

1:1

2:0

1 A

M

T-200

TECHNOLOGY DETAILS, RISERS

AND SCHEDULES

JEFGILTIMADA

POOVYA

18004050.00

TIMADA

WS

U P

ren

tis B

ldg

Rackh

am

Relo

cati

on

18004050.0

0

TIMADA

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2018 IMEG CORP.

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

18004050.00

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

26200 TOWN CENTER DRIVENOVI, MI 48375248.344.2800 FAX: 248.344.1650www.imegcorp.com

NO SCALE1

EXISTING TELECOMMUNICATIONSROOM - CONNECTIVITY DIAGRAM

NO SCALE2 INTERCOM RISER DIAGRAM

BLANK BLANK FILLER MODULE

2. REFER TO SPECIFICAITONS SECTION 27 05 53 FOR ADDITIONAL INFORMATION ON LABELING REQUIREMENTS. VOICE CAT 6 RJ-45 (WHITE)

1. PROVIDE REMOVABLE BLANK INSERT(S) FOR ALL UNUSED PORTS. DATA CAT 6 RJ-45 (ORANGE)

NOTES: LEGEND

SINGLE GANG WALLPLATES

INFORMATION OUTLET SCHEDULE

CONFIGURATION FA

CE

PL

AT

E P

OR

TS

FACEPLATE PORT IDENTIFICATION

NOTESPO

SIT

ION

1 J

AC

K T

YP

E

PO

SIT

ION

2 J

AC

K T

YP

E

PO

SIT

ION

3 J

AC

K T

YP

E

PO

SIT

ION

4 J

AC

K T

YP

E

PO

SIT

ION

5 J

AC

K T

YP

E

PO

SIT

ION

6 J

AC

K T

YP

E

C1 2 DATA BLANK

C2-1 3 DATA DATA VOICE

THE MATERIAL LIST ABBREVIATIONS AND THE TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BERESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKINGSYSTEM.

CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BEORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGSAND SPECIFICATIONS. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN. "STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE.

GENERAL TECHNOLOGY EQUIPMENT SCHEDULE

EQUIPMENT LISTABBREVIATION EQUIPMENT LIST DESCRIPTION

EQUIPMENT LISTMANUFACTURER AND MODEL

IC-IM1 INTERCOM MASTER STATION. DESK OR WALL MOUNT WITH ABS HOUSING AND LED, CALL TONE INDICATORS. 300 mAPOWER CONSUMPTION. INSTALL WITHIN 4" SQUARE BACKBOX WITH PLASTER RING AND PROVIDE (!) 1" C TO NEARESTACCESSIBLE CEILING.

AIPHONE LEF-3

OR PRE-APPROVED EQUAL

IC-IS1 INTERCOMM DOOR STATION. WALL MOUNT. ABS PLASTIC HOUSING. PUSH TO TALK OR OPEN VOICE HANDSFREECOMMUNICATION. INSTALL WITHIN 4" SQUARE BACKBOX WITH PLASTER RING. PROVIDE 1" CONDUIT TO NEARESTACCESSIBLE CEILING.

AIPHONE LE-B

OR PRE-APPROVED EQUAL

SC-IO-C INFORMATION OUTLET, CEILING MOUNT, 2 PORT COVERPLATE AS INDICATED ON DRAWINGS.

"#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO T-200 FORINFORMATION OUTLET SCHEDULE FOR PIN CONFIGURATION.

INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMTCONDUIT 6" BEYOND BOX AND TERMINATE WITH A NYLON BUSHING. PROVIDE REMOVABLE BLANK INSERTS FORUNUSED PORTS (SYSTIMAX M20AP SERIES OR APPROVED EQUAL)

COVERPLATE:COMMSCOPE SYSTIMAX M12L - 262

JACK:COMMSCOPE SYSTIMAX CAT6 UNJ600-OR (ORANGE)

HUBBELLORTRONICS

SC-IO-W INFORMATION OUTLET, WALL MOUNT, 3 PORT COVERPLATE AS INDICATED ON DRAWINGS.

"#" INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS. REFER TO T-200 FORINFORMATION OUTLET SCHEDULE FOR PIN CONFIGURATION.

INSTALL INFORMATION OUTLET IN A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1" EMTCONDUIT TO TELECOM ROOM. PROVIDE REMOVABLE BLANK INSERTS FOR UNUSED PORTS (SYSTIMAX M20AP SERIESOR APPROVED EQUAL)

COVERPLATE:COMMSCOPE SYSTIMAX M13L - 262

JACK:COMMSCOPE SYSTIMAX CAT6 UNJ600-OR (ORANGE) UNJ600-WH (WHITE)

HUBBELLORTRONICS

Owner Review 90% CD's Nov. 27, 2018

100% CD's Dec. 04, 2018

For Bids Dec. 11, 2018