Detection and measurement system for toxic and explosive gases
Version 3.0 English / September 2009
SIEMENS CC62P INTEGRATION
Page 2
SIEMENS CC62P Integration
SIEMENS CC62P allows unidirectional integration to BMS or similar using:
1. OPC Server
2. MODBUS RTU
3. MODBUS TCP/IP*
*This option is not compatible with MM8000
Page 3
SIEMENS CC62P-MM8000 Integration OPC (1/2)
OPC Server satisfy the OPC Data Access 1.0A and 2.0
PC with Windows XP or equivalent.
MM8000 is the software to install in the management post acting as MM8000 Client
OPC-DE1 is the OPC server for SIEMENS CC62P developed by DURANELECTRONICA
Connection with SIEMENS CC62P through RS232 Serial port.
RS232 cable
>15 m
4 Module line x 16 detectors MM8000 CLIENT OPC
& OPC-DE1 SERVER
Page 4
1 to 16 control units
4 module line x 16 detectors
RS23216/1 ports
RS232 cable
RS485 cableConversorRS232-RS485
>15 m
<15m
Maximum capacity of 16 panels per license.
If the distance between SIEMENS CC62P and PC is longer than 15 m, is advisable touse a RS232/RS485 conversor to get a maximum distance of 1,200m.
SIEMENS CC62P-MM8000 Integration OPC (2/2)
MM8000 CLIENT OPC &
OPC-DE1 SERVER
Page 5
Information displayed as OPC items by OPC server.
The control unit must be set in Reading Mode: SEQUENTIAL
OPC server offer you all tags for each set control unit.
Tags indicate gas type, analogue measurement, alarm status, etc.
SIEMENS CC62P-OPC Integration
Page 6
1 INTESISBOX per control unit.
Allows Modbus 03 and 04 functions for Modbus register reading.
Allows poll records for multiple register reading. Modbus memory map. It ispossible to configure speed and slave number.
2 bytes register (MSB. LSB, 16 bits format unsigned).
SIEMENS CC62P-MM8000 Integration MODBUS RTU
1 to 128 control units
4 module lines x 16 detectors
RS232 cable
MM8000 CLIENT MODBUS
RS232 or RS485 cable
INTESISBOX
NK8223
Ethernet or RS232 cable
Page 7
This option is not compatible with MM8000
1 INTESISBOX per control unit
Allows Modbus 03 and 04 functions for Modbus register reading
Allows poll records for multiple register reading. Modbus memory map. IP address, subred mask and configurable TCP port.
2 bytes register (MSB..LSB format 16 bits format unsigned)
Ethernet
1 to 254 control units
4 Module lines x 16 detectors
RS232 cable INTESISBOX
SIEMENS CC62P Integration MODBUS TCP/IP