Detail Booklet StoTherm ® ci over Masonry Series 19.xx Masonry Frame Construction February 2019 ® ATTENTION Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components. STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com. www.stocorp.com Property of Sto Corp. All Rights Reserved. 3800 Camp Creek Pkwy. SW Bldg. 1400 • Suite 120 Atlanta, GA 30331 Tel: (800) 221-2397 Fax: (404) 346-3119 helpdesk.stocorp.com Sto Corp.

Transcript of Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019...

Page 1: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

Detail BookletStoTherm®ci over MasonrySeries 19.xxMasonry Frame ConstructionFebruary 2019

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

www.stocorp.comProperty of Sto Corp.All Rights Reserved.

3800 Camp Creek Pkwy. SWBldg. 1400 • Suite 120Atlanta, GA 30331Tel: (800) 221-2397Fax: (404) 346-3119helpdesk.stocorp.com

Sto Corp.

Page 2: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

System ComonentsDetail No.: 19.00Date: February 2019

Mansory Substrate

StoGuard®

Sto Adhesive

Sto Insulation Board

Sto Mesh

Sto Base Coat

Sto Finish

Pre-wrapped or back wrapped Sto Insulation Board

Notes:

Detail shows the components of StoTherm® ciContinuous Insulation System:

1) StoGuard® Waterproof Air Barrier (2 coats minimum) 2) Sto Adhesive

3) Sto Insulation Board

4) Sto Base Coat

5) Sto Mesh

6) Sto Finish

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 3: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

Termination at GradeDetail No.: 19.01aDate: February 2019

Mansory Substrate

Sto Adhesive

Sto Insulation Board

Sto Base Coat and Mesh

Sto Finish

StoGuard® Waterproof Air Barrier (2 coats minimum)

Pre-wrapped or back wrapped Sto Insulation Board

Maintain min. 6 inches (152mm) above finished grade.

Protective Coating

Cementitious Damp-proofing or Water- proofing as needed

Notes:

1) Provide minimum 6 inches (152 mm) clearance between StoTherm® ci termination and finished grade. Increase distance above grade for snow regions.

2) Provide cementitious damp proofing or waterproofing as needed below grade and on exposed masonry above grade. Counter flash StoTherm® ci over damp- proofing/waterproofing. WhereStoTherm® ci is installed over non-cementi- tious dampproofing/ waterproofing verify compatibility of StoTherm® ci components.

3) Provide adequate slope of finished grade away from structure for drainage.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 4: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

Termination at Sidewalk with Expansion JointDetail No.: 19.01bDate: February 2019

Masonry Substrate

Sto Adhesive

Sto Insulation Board

Sto Base Coat and Mesh

Sto Finish

StoGuard®

Waterproof Air Barrier (2 coats minimum)

Pre-wrapped or back wrapped Sto Insulation Board

Backer Rod and Sealant

Cementitious Damp-proofing or Water- proofing as needed

Notes:

1) Detail is intended for areas of construction protected from weather - covered walk ways, balconies or decks under cover, or areas protected with large projecting eaves or soffit overhangs. Refer to Sto Detail 19.01a for weather exposed areas.

2) Provide cementitious damp proofing or waterproofing as needed below grade and on exposed masonry above grade. Counter flash StoTherm® ci over damp- proofing/waterproofing. WhereStoTherm® ci is installed over non-cementi- tious dampproofing/ waterproofing verify compatibility of StoTherm® ci components.

3) Provide adequate slope of finished grade away from structure for drainage.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 5: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

Mansory Substrate

StoGuard® RapidSeal™

StoGuard® Waterproof Air Barrier (2 coats minimum)

StoTherm® ci Over Masonry

Window Head/Jamb: Rough Opening ProtectionDetail No.: 19.24a1Date: February 2019

Notes:

1) Protect masonry with StoGuard® RapidSeal™. Fold up minimum 2 inches (51mm) at head and at ends onto face of masonry.

2) Refer to Sto detail 19.24a2 for window installation and Sto detail 19.24a3 for complete assembly.

3) Test the final assembly using materials and sub-trades associated with the project to verify performance.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 6: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

Mansory Substrate

StoGuard® Waterproof Air Barrier (2 coats minimum)

StoGuard® RapidSeal™

1/2"(13 mm) gap forperimeter air seal

StoGuard® RapidSeal™

1/2"(13 mm) gap for perimeter weather seal

StoTherm® ci Over Masonry

Window Head/Jamb: Window InstalledDetail No.: 19.24a2Date: February 2019

Notes:

1) Provide gap for continuous exterior perimeter weather seal.

2) Provide gap for continuous interior perimeter air seal.

3) Consult with window and sealant manufacturers to verify installation detailing.

4) Refer to Sto detail 19.24a1 for rough opening protec- tion and Sto detail 19.24a3 for complete assembly.

5) Test the final assembly using materials and sub-trades associated with the project to verify performance.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 7: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

Sto Finish

StoGuard® Waterproof Air Barrier (2 coats minimum)

Sto Insulation Board

Sto Base Coat with Sto Mesh embedded

Pre-wrapped or back wrapped Sto Insulation Board

Mansory Substrate

StoGuard® RapidSeal™

Backer rod and sealant (continuous perimeter air seal).

Gap (1/4"-1/2") for drainage. Seal with backer rod and sealant. Provide weeps approxi-mately 3 inches (76mm) from corner and16 inches (406mm) O.C.

Backer rod and sealant (continuous perimeter weather seal).

Mechanical fastener (required only at return where StoTherm® ci is installed over StoGuard® RapidSeal™).

StoTherm® ci Over Masonry

Window Head/Jamb: StoTherm® ci Return and Perimeter SealsDetail No.: 19.24a3Date: February 2019

Notes:

1) Provide continuous exterior perimeter weather seal.

2) Provide continuous interior perimeter air seal.

3) Consult with window and sealant manufacturer to verify installation detailing.

4) Refer to Sto detail 19.24a1 for rough opening protec tion and Sto detail 19.24a2 for window installation.

5) Test the final assembly using materials and sub-trades associated with the project to verify performance.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 8: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

Mansory Substrate

StoGuard® RapidSea™l(for slope)

StoGuard® RapidSeal™

Pre-fabricated Pan Flashing

StoGuard® RapidSeal™

StoGuard®

Waterproof Air Barrier (2 coats minimum)

StoTherm® ci Over Masonry

Window Sill: Rough Opening Protection and Pan Flashing at Sill

Detail No.: 19.26a1Date: February 2019

Notes:

1) Protect masonry sill with StoGuard® RapidSeal™. Fold up minimum 4 inches (102mm) at jamb. Fold down 2 inches (51mm) at sill and at ends onto face of masonry.

2) Install StoGuard® Rapid- Seal™ strip at back of opening to create slope and fold up nailer.

3) Secure pre-fabricated pan flashing by others into place.

4) Provide pan flashing with thermal break in cold climate zones.

5) Refer to Detail 19.26a2 for protection at jamb and Sto details 19.24a1 and 19.24a2 for protection at head. Refer to Sto detail 19.26a3 for complete sill / jamb assembly.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 9: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

Mansory Substrate

Window Frame

StoGuard® RapidSeal™(for slope)

StoGuard® RapidSeal™

Pre-fabricated Pan Flashing

StoGuard® RapidSeal™

StoGuard®

Waterproof Air Barrier (2 coats minimum)

StoTherm® ci Over Masonry

Window Sill/Jamb: Rough Opening Protection and Pan Flashing with Window Installed

Detail No.: 19.26a2Date: February 2019

Notes:

1) Provide gap for continuous exterior perimeter weather seal.

2) Provide gap for continuous interior perimeter air seal. 3) Consult with window and sealant manufacturers to verify installation detailing.

4) See Sto detail 19.26a1 for rough opening protection and pan flashing at sill. See Sto detail 19.24a1 and 19.24a2 for protection at head. See Sto detail 19.26a3 for complete sill/jamb assembly.

5) Test the final assembly using materials and sub-trades associated with the project to verify performance.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 10: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoGuard® RapidSeal™

Masonry Substrate

StoGuard® Waterproof Air Barrier (2 coats minimum)

Sto Insulation Board

Sto Base Coat with Sto Mesh embedded

Sto Finish

Mechanical fastener (required only at return where StoTherm® ci isinstalled over StoGuard® RapidSeal™).

Backer rod and sealant (continuous perimeter weather seal).

Backer rod and Sealant with weeps

Backer rod and sealant (continuous perimeter air seal).

Back wrapped or pre-wrapped Sto Insulation Board

Sealant

StoTherm® ci Over Masonry

Window Sill/Jamb: Window Installed withStoTherm® ci Return and Perimeter Seals

Detail No.: 19.26a3Date: February 2019

Notes:

1) Provide gap for continuous exterior perimeter weather seal.

2) Provide gap for continuous interior perimeter air seal.

3) Consult with window and sealant manufacturer to verify installation detailing.

4) See Sto detail 19.26a1 and 19.26a2 for rough opening protection and pan flashing at sill. See Sto details 19.24a1 and 19.24a2 for protection at head and 19.24a3 for complete head / jamb assembly. 5) Test the final assembly using material and sub-trades associated with the project to verify performance.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 11: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

Floor Line with JointDetail No.: 19.41Date: February 2019

Floor Slab

Masonry Substrate

Sto Adhesive

Pre-wrapped or back wrapped Sto Insulation Board

Backer rod and Sealant

StoGuard® Transition Membrane

Sto Finish

Sto Base Coat and Mesh

Sto Insulation Board

StoGuard® Waterproof Air Barrier (2 coats minimum)

Notes:

1) Provide joint at floor line to coincide with line where masonry adjoins under side of concrete floor slab.

2) Back joint with StoGuard® Transition Membrane.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 12: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

Horizontal Joint at Dissimilar MaterialDetail No.: 19.42Date: February 2019

Floor Slab

Masonry Substrate

Sto Adhesive

Sto Finish

StoGuard® Waterproof Air Barrier (2 coats minimum)

Sto Insulation Board

StoGuard® RapidSeal™

Sto Base Coat and Mesh

Flashing

Pre-wrapped or back wrapped Sto Insulation Board

StoGuard® Transition Membrane

Alternate cladding assembly

Notes:

1) Provide flashing minimum 4 inches (100mm) behind StoTherm® ci and project flashing with drip edge beyond face of alternate cladding below.

2) Determine installation sequence in advance of construction.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 13: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

Vertical Joint at Dissimilar MaterialDetail No.: 19.50Date: February 2019

StoGuard® Waterproof Air Barrier (2 coats minimum)

Masonry Substrate

Sto Adhesive

Sto Insulation Board

Pre-wrapped or back wrapped Sto Insulation Board

Sto Base Coat and Mesh

StoGuard® Transition Membrane

Backer rod with sealant

Sto Finish

StoGuard® Waterproof Air Barrier (2 coats minimum)

Alternate cladding assembly

Notes:

1) Determine installation sequence in advance of construction. Coordinate subtrades to ensure the proper installation of materials.

2) StoGuard® Transition Membrane isolates the potentially wet environment behind the alternate cladding from StoTherm® ci.

3) Provide minimum 3/4" (20mm) joint between the StoTherm® ci and the alternate cladding. Provide drainage for the joint assembly.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 14: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

Masonry Substrate

StoTherm® ci Over Masonry

Vertical Expansion JointDetail No.: 19.51Date: February 2019

StoGuard® Air and Moisture Barrier

Sto EPS Insulation Board(Pre-wrapped or back wrapped)

Sto Base Coat and Mesh

Notes:

1) Provide minimum 3/4" (20mm) joint.

2) Refer to StoTherm ci System Bulletins and Specifications, Sto Product Bulletins, Tech Hotlines, and Sto Installation and Maint- nance Guides for complete information.

3) Refer to applicable ICC or CCMC Evaluation Report for building code compliance information.

Sto Adhesive

Sto Finish

Sealant and Backer Rod

Sto Primer(optional)

Backer Rod(To support Sto Transition Membrane

but not restrict its movement)

StoGuard® Transition Membrane(Embedded in StoGuard® Air and

Moisture Barrier)

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 15: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

Masonry Substrate

Sto Adhesive

Sto base Coat and Mesh

Pre-wrapped or back wrapped Sto Insulation Board

Metal Flashing

Roof Membrane

Roof Sheathing

Sto Finish

Sto Insulation Board

StoGuard® Waterproof Air Barrier (2 coats minimum)

StoTherm® ci assembly over fabricated metal support structure and sheathing.

Backer rod with sealant

StoTherm® ci Over Masonry

Termination at Built-Out FeatureDetail No.: 19.53Date: February 2019

Notes:

1) Terminate StoTherm® ci minimum 2 inches (51mm) above metal flashing with minimum 2 inch (51mm) overlap of flashing.

2) Provide sealant beneath flashing drip edge.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 16: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

Termination at Flat Roof with Gravel StopDetail No.: 19.60aDate: February 2019

Gravel Stop(min. 2-1/2"[64mm] overlap of StoTherm® ci termination)

Roof Membrane

Backer rod with sealant

Pre-wrapped or back wrapped Sto Insulation Board

StoGuard® Waterproof Air Barrier (2 coats minimum)

Sto Finish

Sto Base Coat and Mesh

Sto Insulation Board

Masonry Substrate

Notes:

1) Provide continuity of roofing membrane with StoTherm® ci for air tight and water tight condition beneath gravel stop. Verify compatibility of materials where they overlap or interface.

2) Provide minimum 2-1/2 inch (64mm) overlap of gravel stop over terminating edge of StoTherm® ci for single story construction. Increase overlap with building height.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 17: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

Termination at Parapet CapDetail No.: 19.60bDate: February 2019

Masonry Substrate

Roof Membrane

Sealant

Pre-wrapped or back wrappedSto Insulation Board

Sto Adhesive

Sto Finish

Sto Base Coat and Mesh

Sto Insulation Board

StoGuard® Waterproof Air Barrier (2 coats minimum)

Notes:

1) Provide continuity of roof membrane along back of parapet with base coat for air barrier continui- ty and verify compatibility of roof membrane if in contact with base coat.

2) Completely insulate back side of parapet if necessary to prevent condensation within parapet based on climate conditions.

3) Provide minimum 2.5 inch (65mm) overlap of parapet coping over face of StoTherm® ci. Increase overlap with building height.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 18: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

Termination at EaveDetail No.: 19.63Date: February 2019

Roof Assembly

Masonry Substrate

Backer rod and Sealant

Pre-wrapped or back wrappedSto Insulation Board

Sto Adhesive

Sto Finish

Sto Base Coat and Mesh

Sto Insulation Board

StoGuard® Waterproof Air Barrier (2 coats minimum)

Notes:

1) Install soffit board prior to installation StoTherm® ci to provide bearing surface for sealant and backer rod.

2) Provide air tight connection with roof / eave air barrier material with StoGuard®.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 19: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

Termination at Fixture Penetration through StoTherm® ci

Detail No.: 19.73Date: February 2019

Masonry Substrate

StoGuard® Waterproof Air Barrier (2 coats minimum)

Sto Adhesive

Back-wrap Termination

Wood Blocking with spray foam around perimeter

Backer rod with Sealant

Light Fixture

Sto Finish

Sto Base Coat and Mesh

Sto Insulation Board

Notes:

1) For some penetrations a fillet bead of sealant over bond breaker around perimeter of penetration may also be acceptable. Consult with sealant manufacturer.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 20: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

Surface Mount Fixture Attachment Through StoTherm® ciDetail No.: 19.74Date: February 2019

Sto AdhesiveSto Insulation BoardPVC Sleeve lined with SealantSto Base Coat and MeshSto FinishGutter StrapWasher bedded in SealantFastener

Masonry Substrate

Sto Adhesive

Sto Insulation Board

Sto Base Coat and Mesh

Sto Finish

Pre-wrapped or back wrapped Sto Insulation Board

Cementitious Damp-proofing or Water- proofing as needed

Notes:

1) Provide minimum 6 inches (152 mm) clearance between StoTherm® ci termination and finished grade. Increase distance above grade for snow regions.

2) Provide cementitious damp proofing or waterproofing as needed below grade and on exposed masonry above grade. Counter flash StoTherm® ci over damp- proofing/waterproofing. Where StoTherm® ci and non-cementitious damp- proofing/waterproofing meet, verify compatibility of StoTherm® ci components.

3) Provide adequate slope of finished grade away from structure for drainage.

Sto Guard® Waterproof Air Barrier (2 coats minimum)

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 21: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

Termination at Scupper PenetrationDetail No.: 19.75Date: February 2019

Masonry Substrate

StoGuard® Waterproof Air Barrier (2 coats minimum)

Back-wrap Termination

Waterproof membrane

Backer rod with Sealant entire perimeter

Scupper Assembly

Sto Finish

Sto Base Coat and Mesh

Sto Insulation Board

Roof or deck assembly

Notes:

1) Provide leakproof scupper assembly and installation to direct water away from the wall surface.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.

Page 22: Detail Booklet StoTherm ci over Masonry - Sto Corp. · Detail No.: 19.01b Date: February 2019 Masonry Substrate Sto Adhesive Sto Insulation Board Sto Base Coat and Mesh Sto Finish

StoTherm® ci Over Masonry

Termination at Pipe PenetrationDetail No.: 19.76Date: February 2019

Masonry Substrate

StoGuard® Waterproof Air Barrier (2 coats minimum)

Sto Adhesive

Spray foam around perimeter of penetrating element.

Backer rod with Sealant entire perimeter

Pipe Penetration

Back-wrap Termination

Sto Finish

Sto Base Coat and Mesh

Sto Insulation Board

Notes:

1) For some penetrations a fillet bead of sealant over bond breaker around perimeter of penetration may also be acceptable. Consult with sealant manufacturer.

®

ATTENTION

Sto products are intended for use by qualified professional contractors, not consumers, as a component of a larger construction assembly as specified by a qualified design professional, general contractor or builder. They should be installed in accordance with those specifications and Sto’s instructions. Sto Corp. disclaims all, and assumes no, liability for on-site inspections, for its products applied improperly, or by unqualified persons or entities, or as part of an improperly designed or constructed building, for the nonperformance of adjacent building components or assemblies, of for other construction activities beyond Sto’s control. Improper use of Sto products or use as part of an improperly designed or constructed larger assembly or building may result in serious damage to Sto products, and to the structure of the building or its components.

STO CORP. DISCLAIMS ALL WARRANTIES EXPRESSED OR IMPLIED EXCEPT FOR EXPLICIT LIMITED WRITTEN WARRANTIES ISSUED TO AND ACCEPTED BY BUILDING OWNERS IN ACCORDANCE WITH STO’S WARRANTY PROGRAMS WHICH ARE SUBJECT TO CHANGE FROM TIME TO TIME. For the fullest, most current information on proper application, clean-up, mixing and other specifications and warranties, cautions and disclaimers, please refer to the Sto Corp. website, www.stocorp.com.

IMPORTANT: Components not identified as Sto are furnished by other manufactur-ers and are not necessarily installed by trades who install the Sto products. Refer to project specific contract documents.

www.stocorp.com

Property of Sto Corp. All Rights Reserved.