Sheet1SYSTEM DESIGN SUMMARY FOR ELECTRIC HEAT TRACING FOR 'PIPE LINE'
CLIENT : M/S PRIME STAR PETROLEUM & INFRASTRUCTURE PVT. LTD.PROJECT : ELECTRIC HEAT TRACING FOR BITUMEN PLANT IN MUMBAI (BHIWANDI)DESIGN VOLTAGE : 216 VACTHER ('K' VALUE IN W/MOC) RW :0.043MAX. EXPOSURE TEMP. PIPE40MAINTENANCE TEMPERATURE: AS MENTIONED IN SHEET BELOWSAFETY FACTOR (%) : 10MIN. AMBIENT TEMPERATURE(IN OC) :10STANDARDS : As Per BS 6351 PART II 1983 & IEEE 515-2004AREA CLASSIFICATION : SAFE AREASR NO.LINE NO. PIPE SIZE (NB)PIPE SIZE (OD)PIPE LENGTH (MTR)ROCKWOOL INSULATION THICKNESS (MM)NO OF VALVES (NOS.)NO OF FLANGE (NOS.)NO OF SUPPORTS (NOS.)MAINTENANCE TEMP ( OC)HEAT LOSS (W/M)TRACER OUTPUT (W/M)TRACER MODELTRACER PER UNIT LENGTH OF PIPETRACER PER NO OF VALVETRACER PER NO OF FLANGETRACER PER NO OF SUPPORTTOTAL TRACER LENGTH (MTR)OPERATING CURRENT(A)1A200.7518.010024061406.9149.0020VPL2-CT1.00.210.041.330.97.02B8036.010001221409.1749.0020VPL2-CT1.00.280.066.319.34.43D100442.01002060141409.8349.0020VPL2-CT1.00.300.067.3153.834.94E1506576.0100661529614010.9349.0020VPL2-CT1.00.330.078.31405.0318.75F200896.01002131614011.8649.0020VPL2-CT1.00.360.079.3246.555.9
738.01855.5
S.NO.SPECIFICATIONTRACER MODELLENGTH AS PER DESIGN SHEET (MTR)SITE TERMINATION CONTENGENCIES (MTR)TOTAL TRACER LENGTH (MTR)1PIPING20VPL2-CT18551855
RRL/HT/14-15/DE-00524-Apr-12R0HBKPNCOFFER REFERENCEDATEREVISIONPREPARED BY.CHECKED BY.APPROVED BY.