Designing For a Critical Load using a Spot Network
© 2007 Eaton Corporation. All rights reserved.
Tony Oruga, P.E. – Product and Sales Manager
Network Protectors
![Page 2: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/2.jpg)
2 2
Network Systems
• Who?
• When?
• What?
• How?
• Why?
• Where?
![Page 3: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/3.jpg)
3 3
Network Systems
• Who knows what distribution network systems
are?
• When?
• What?
• How?
• Why?
• Where?
![Page 4: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/4.jpg)
4 4
Network Systems
• Who?
• When were they first used?
• What?
• How?
• Why?
• Where?
1882 – DC networks
1907 – Memphis; AC network
1921 – Seattle
1922 – NY; first system
![Page 5: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/5.jpg)
5 5
When were they first used?
• 1922
Westinghouse Electric developed first Network System
Union Electric in New York, now called Consolidated Edison.
Con Ed - 25,000 Network Protectors on their system.
85% of Con Ed load supplied by Networks.
• Today
Commercial areas of most major cities over 200,000 have network
systems.
• Secondary Network voltages are 216, 480, and 600VAC
![Page 6: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/6.jpg)
6 6
When were they first used?
![Page 7: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/7.jpg)
7 7
Network Systems
• Who?
• When?
• What is a Network System?
• How?
• Why?
• Where?
![Page 8: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/8.jpg)
8 8
What is a Network System?
• Radial
• Primary
Selective
• Secondary
Selective
• Network System
• Spot
• Grid
Alternative to traditional power distribution topologies
“That’s the way we have always done it…”
![Page 9: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/9.jpg)
9 9
1 2 3
Spot Network System
Network
Transformers
Network
Protector
Utility Substation
Feeder Breaker
Load
Collector
Bus
Network
Breaker Fuse
What is a Network System?
Utility Substation
Cable Limiter
*2 or more parallel feeders to a load supply allow uninterrupted power during contingency
![Page 10: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/10.jpg)
10 10
Grid Network System
What is a Network System?
![Page 11: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/11.jpg)
11 11
Grid Network System 3 Feeder Distributed
1 2 3
What is a Network System?
![Page 12: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/12.jpg)
12 12
What is a Network System?
• Highest level of reliability for power distribution systems
• Most desirable for critical loads
• Two main topologies:
• Spot – One dedicated customer
• Grid – Several customers; i.e. City block…
![Page 13: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/13.jpg)
13 13
Substation and Primary Feeders
• Nominal Voltages 4.16 kV to 34.5 kV
• Dedicated primary feeders- supply only network transformers
What is a Network System?
![Page 14: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/14.jpg)
14 14
Network Systems
• Who?
• When?
• What?
• How does it work?
• Why?
• Where?
![Page 15: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/15.jpg)
15 15
1 2 3
Spot Network - Fault on Primary Feeder
Collector Bus
Fault on Primary side which causes breaker to open
How does it work? Spot Network
Cable Limiters
Network Transformer
Network breaker fuse
Network protector
![Page 16: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/16.jpg)
16 16
1 2 3
Spot Network - Station Breaker “1” is Opened
Network Relay Trips Upon the Flow of Reverse Magnetizing Current of its Associated Network Transformer.
Collector Bus
Station Breaker opens which causes NP to open
How does it work? Spot Network
![Page 17: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/17.jpg)
17 17
1 2 3
Spot Network – Continues operation at N-1 contingency
Customer never experiences interruption of service
Collector Bus
Station Breaker opens which causes NP to open
How does it work? Spot Network
![Page 18: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/18.jpg)
18 18
MPCV Relay Family
• Robust design for extreme temperatures (-40C to 125C)
• .25” Thick Solid Brass Case
• Submersible
• Communication activated
• Advanced Safety Algorithms
• Only sequence based relay
• Replaces any Electro-Mechanical Network relay, solid state, or digital relays regardless of vintage or
protector type.
• Specification preferred for foreign and domestic utilities
![Page 19: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/19.jpg)
19 19
LV Secondary Network System Philosophy
• Underground Systems
Reference Book, EEI
T&D Committee (1957)
• Page 5-2: Operation is
based on 3 principles:
• Westinghouse Electric
Reference Book: Vol 3
Distribution Systems (1965)
1. The self-clearing of faults on the
secondary grid either by burning-off faults
or clearing by use of limiters.
2. Automatic opening of network protectors
when a feeder breaker is opened or in
event of a fault on a primary feeder cable
or in a network transformer.
3. Automatic closing of network protectors to
connect the network transformers to the
secondary grid when the primary feeder is
energized.
(Page 167)
![Page 20: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/20.jpg)
20 20
Sample – SLD 2-Unit Spot Network
![Page 21: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/21.jpg)
21 21
Sample – Network Floor Plan (Switchgear)
![Page 22: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/22.jpg)
22 22
Sample – SLD 3-Unit Spot Network
![Page 23: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/23.jpg)
23 23
Sample – Network Floor Plan (Switchgear)
![Page 24: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/24.jpg)
24 24
Sample – Profile Network view (submersible)
Network Protector
Visual Disconnect
Collector Bus
Primary
Disconnect Switch
Sudden Pressure Relay
Visual Status
Indicator
Network Transformer
Bulkhead
Source
Bus
*Throat or Wall mount
![Page 25: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/25.jpg)
25 25
Vault Vision
• Vault protection
• Family of sensors that
seamlessly integrate into
communication platform
• Multi-platform
communication
• Heat detection systems
![Page 26: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/26.jpg)
26 26
Today’s Product Suite for Underground
![Page 27: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/27.jpg)
27 27
How does it work? Spot Network
Submersible model CM-52 shown Switchgear Line-Up
![Page 28: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/28.jpg)
28 28
Network Systems
• Who?
• When?
• What?
• How?
• Why use a Network System?
• Where?
![Page 29: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/29.jpg)
29 29
Advantages of Network System Design
• Outage on primary feeder does NOT cause customer outage
![Page 30: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/30.jpg)
30 30
Advantages of Network System Design
• Outage on primary feeder does NOT cause customer outage
• Less transformer capacity is required
![Page 31: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/31.jpg)
31 31
Advantages of Network System Design
• Outage on primary feeder does NOT cause customer outage
• Less transformer capacity is required
• Lower peak loads on transformers - diversity of demand
![Page 32: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/32.jpg)
32 32
Advantages of Network System Design
• Outage on primary feeder does NOT cause customer outage
• Less transformer capacity is required
• Lower peak loads on transformers - diversity of demand
• Transformer losses are typically less
![Page 33: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/33.jpg)
33 33
Advantages of Network System Design
• Outage on primary feeder does NOT cause customer outage
• Less transformer capacity is required
• Lower peak loads on transformers - diversity of demand
• Transformer losses are typically less
• Protectors assure positive power into load
![Page 34: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/34.jpg)
34 34
Advantages of Network System Design
• Outage on primary feeder does NOT cause customer outage
• Less transformer capacity is required
• Lower peak loads on transformers - diversity of demand
• Transformer losses are typically less
• Protectors assure positive power into load
• System provides improved voltage regulation
![Page 35: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/35.jpg)
35 35
Advantages of Network System Design
• Outage on primary feeder does NOT cause customer outage
• Less transformer capacity is required
• Lower peak loads on transformers - diversity of demand
• Transformer losses are typically less
• Protectors assure positive power into load
• System provides improved voltage regulation
• Less voltage sag on Motor starting (up to 70% less than a radial system)
![Page 36: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/36.jpg)
36 36
Advantages of Network System Design
• Outage on primary feeder does NOT cause customer outage
• Less transformer capacity is required
• Lower peak loads on transformers - diversity of demand
• Transformer losses are typically less
• Protectors assure positive power into load
• System provides improved voltage regulation
• Less voltage sag on Motor starting (up to 70% less than a radial system)
• Automatic open and close operation
![Page 37: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/37.jpg)
37 37
Advantages of Network System Design
• Outage on primary feeder does NOT cause customer outage
• Less transformer capacity is required
• Lower peak loads on transformers - diversity of demand
• Transformer losses are typically less
• Protectors assure positive power into load
• System provides improved voltage regulation
• Less voltage sag on Motor starting (up to 70% less than a radial system)
• Automatic open and close operation
• LV Network Customer outage rate
• Approaching zero
• Radial systems – once every year.
BEST SOLUTION FOR
CRITICAL LOAD
APPLICATIONS!
![Page 38: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/38.jpg)
38 38
Design Considerations
Spot Network
Radial
Double-Ended
Primary Selective
Primary Loop
Investment Cost
Re
lia
bil
ity
Nu
mb
er
of
Ou
tag
es
Costs associate with outages
Spot Network
Radial
Double-Ended
Primary Selective
Primary Loop
![Page 39: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/39.jpg)
39 39
Network Systems
• Who?
• When?
• What?
• How?
• Why?
• Where are they used today?
![Page 40: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/40.jpg)
40 40
Where are they used today?
![Page 41: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/41.jpg)
41 41
Where are they used today?
*Selected example utilities
![Page 42: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/42.jpg)
42 42
Where are they used today?
Network Systems are also widely used in other parts
of the world such as:
• Canada
• Asia and Asia Pacific
• Australia
• Latin America – Central and South America
Mexico Columbia Brazil Venezuela
Philippines Thailand South Korea
![Page 43: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/43.jpg)
43 43
Example Installations
Electrical Room Installation
Subsurface Vault Installation
![Page 44: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/44.jpg)
44 44
Example Installations
Platform installation
Roof installation
![Page 45: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/45.jpg)
45 45
Example Installations
Detroit Edison Design
![Page 46: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/46.jpg)
46 46
Example Installations
Subsurface Vault Installation
![Page 47: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/47.jpg)
47 47
3 Unit 480Y/277 V Spot Network- Seattle, WA- Building Vault
Example Installations
![Page 48: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/48.jpg)
48 48
480V Spot Network Example (1-4 Feeders at 12.47 kV)
• Load Estimation Study
• Maximum Short Term Peak Load: 1250 kVA
• Continuous Average Load: 800 kVA
• Minimum Baseline Load: 275 kVA
• All above loading conditions at 0.87 Lagging PF
• 3 Standardized 480V Transformer Options
• 1000 kVA (1200A)
• 1500 kVA (1800A)
• 2500 kVA (3000A)
• Network Unit Options
• 2-Unit through 6-Unit Spot Networks
![Page 49: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/49.jpg)
49 49
Optimal Transformer / “#-Unit” Combination (N-1 Contingency)?
![Page 50: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/50.jpg)
50 50
Transformer Calculations
![Page 51: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/51.jpg)
51 51
Network Protector Selection
![Page 52: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/52.jpg)
52 52
Network Protector Selection Rationale
• Choose 1000kVA 5% Impedance Transformers (125% Maximum Short Term =
1504A)
• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin,
a good fit.
• 1875A NWP 156% Rating also utilizes 1600:5 CTs but unnecessary higher
amperage fuses.
• Select 1600A CM52 NWP for a 2-Unit 1000kVA Spot Network.
• Notice that a 2-Unit 1500kVA Spot would yield: Higher Transformer $, Higher
NWP $ (4-Pole CM52), for undesired excess load capacity.
![Page 53: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/53.jpg)
53 53
IEEE Standards & References
• IEEE – C57.12.40
Secondary Network Transformers Subway and Vault Type (Liquid
Immersed) – Requirements
• IEEE – C57.12.44.2014
Standard Requirement for Secondary Network Protectors
• EPRI Bronze Book – Underground Distribution Systems Reference Book
![Page 54: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/54.jpg)
54 54
Additional Network System Training
• Electrical Networks Systems Conference
(ENSC)
• Annual Conference
• Guest Speakers and Vendor Trade Show
16th Annual ENSC
Tempe, AZ
March 30th to April 2nd 2015
• Troubleshooting Training (3-day)- covers all
brands of NWPs
• Factory or Onsite Classes are available
• Greenwood Seminar to be held 2x per year, 4.0 CEU
credits awarded
• NWP Engineer Application Training (2 days)
Greenwood and On-Site
![Page 55: Designing For a Critical Load using a Spot Networkcce.umn.edu/documents/CPE-Conferences/MIPSYCON-Power...• 1600A NWP Rating Provides 133% Transformer Nameplate Overload Margin, a](https://reader036.fdocuments.us/reader036/viewer/2022070920/5fb9325da220087d38355ad7/html5/thumbnails/55.jpg)
55 55
Questions?