DESIGN OF COOLING TOWER.docx
-
Upload
mohan-varkey -
Category
Documents
-
view
219 -
download
0
Transcript of DESIGN OF COOLING TOWER.docx
-
8/14/2019 DESIGN OF COOLING TOWER.docx
1/17
DESIGN OF COOLING TOWER
DESIGN CONDITIONS:
Cooling Tower Type COUNTER FLOW INDUCED DRAFT
Water Temperature
Leaving C25
Entering C30
Air Condition
Leaving WBCDBC 98,38
Entering RHDBC %65,26
Make-up Water
Temperature C26
Barometric Pressure kPa325.101
Note:
(1)The practical cooling range 21 tt is C 7.166.5 (Morse, 1990) p 122(2)For cooling towers the rating conditions are C35 entering water, C4.29
leaving water, and C9.23 wet bulb of the outdoor air (Wang, 2001) p 10.50
(3) In most cases, the temperature of the water leaving the tower will be Fto 107
above wet bulb temperature of the entering air (Dossat, 1978)p 333
-
8/14/2019 DESIGN OF COOLING TOWER.docx
2/17
Calculation Procedure:
Amount of water to be handled by the cooling tower, mcw
sec74.13
sec78.1096.2
kgm
kgm
mmm
cw
cw
condensercw
compressorcwcw
Air Properties Using Psychometrics Chart
At RHandC %6526
airdryofkgmoistureofkg
HRkg
KJh 0136.0;61 44
At RHandC %9832
-
8/14/2019 DESIGN OF COOLING TOWER.docx
3/17
airdryofkg
moistureofkgHR
kgKJh
0297.0;108 55
Mass of Air, ,am
Energy Balance on the cooling tower
3421
4321 &
hhmtCpmttCpm
mmmmmm
amwwmwcwcw
acw
mww
cwcwamw
tCp
ttCpmhhmm 2134
1.642.243174.0
26187.4
2530187.4sec
74.1361108
00
00
eqmm
CCkg
KJ
CCkg
KJkgkg
KJm
m
amw
a
mw
Mass Balance
Mass entering = Mass leaving
2.0161.0
)0136.00297.0()..(
..
34
43
eqmm
mRHRHmm
RHmmRHmmm
amw
aamw
awawmw
-
8/14/2019 DESIGN OF COOLING TOWER.docx
4/17
Substituting eq.1 to eq.2
642.243174.00161.0 aa mm
aa mm 0161.04317.0642.2
sec36.6 kg
ma
Mass of Make-up water, 5wm
From Equation 2
waterofkgkg
m
mm
w
aw
sec1023.0
sec36.60161.0
0161.0
5
5
Volume flow rate of air, aV
KPaKPaPsatRHPsKPaPsatRHandCAt
18595.2363.365.0
363.3,%6526
MRTPV
3
0
0
18595.2325.101
273262871.0sec
36.6
mKNorKPa
KKkg
KJkg
PP
TRmV
SB
aaaa
sec507.5 3m
Va
Where: R.H= relative humidity
vaporwaterofpressurepartialP
CatpressuresaturationP
V
Sat
26
-
8/14/2019 DESIGN OF COOLING TOWER.docx
5/17
Volume flow rate of air, wV
From Refrigeration Engineering by Mc Intire P. 495. cross-sectional area of
induced draft fan is found by allowing gpm/ft3.0 2
t =2
3025= 27.5 C @ 27.5 C
3512.996
m
kgw
Therefore,
Volume flow rate ( w ) =3
512.996
sec74.13
m
kg
kgM
w
w
=min1
sec60
003785.0
1
sec0138.0
3
3
xm
galx
m
= 218.57 gpm
Cooling tower range, C.T.R.
C.T.R. = Ctt o521
Cooling tower approach, C.T.A.
At 26 Co and 65% RH ; Ct owb 75.18
C.T.A. = Ctt owb 25.675.18251
-
8/14/2019 DESIGN OF COOLING TOWER.docx
6/17
Cooling tower efficiency, C.T.E.
C.T.R. = %10075.1830
2530%100
1
21 xxtt
tt
wb
= 44.4 %
-
8/14/2019 DESIGN OF COOLING TOWER.docx
7/17
PIPING SYSTEM FOR COOLING TOWER
Design Condition:
Mass flow rate cooling water
Compressor sec96.2 kg
Condenser sec78.10 kg
water = 996.512 kg/ 3m ; f @ Ct
o
ave 5.27
Water Velocity, v = 1.83 m/sec (range: 1.5 to 2.1m/sec)
Solving for the total amount of cooling water, TcwQ
sec/1097.2/512.996
sec/96.2 333
mxmkg
kgQcompressor
sec/1082.10/512.996sec/78.10 333 mxmkg
kgQcondenser
condensercompressorTcw QQQ
sec/)1082.101097.2( 333 mxxQTcw
sec/01379.0 3mQTcw
-
8/14/2019 DESIGN OF COOLING TOWER.docx
8/17
PIPE SIZE FOR THE SUPPLY AND RETURN PIPES
From cooling tower pool to tee-run
vDQTcw2
4
sec83.1
4sec01379.0 2
3 mD
m
D= 0.0979 m = 97.9 mm
USE: 100 mm NPS schedule 40 (from Table 7-2 Dimensions of steel pipe by
Wilbert F. Stoeker, P 136)
OD = 114.3 mm ID = 102.3 mm
From tee-run to condenser inlet
vDQcondenser2
4
sec83.1
4sec1082.10 2
33 mDm
x
D= 0.08676 m = 86.76 mm
USE: 100 mm NPS schedule 40 (from Table 7-2 Dimensions of steel pipe by
Wilbert F. Stoeker, P 136)
OD = 114.3 mm ID = 102.3 mm
-
8/14/2019 DESIGN OF COOLING TOWER.docx
9/17
From tee-run to compressor inlet
vDQcompressor2
4
sec83.1
4sec1097.2 2
33 mDm
x
D= 0.04545 m = 45.45 mm
USE: 50 mm NPS schedule 40 (from M.E.T.C. Steel Pipe Dimensions, P 114.)
OD = 73.03 mm ID = 62.65 mm
-
8/14/2019 DESIGN OF COOLING TOWER.docx
10/17
COOLING WATER PUMP
Design Data:
Type Centrifugal
Capacity, QP 0.01379 m3/sec
Average water temperature, tave 27.50C
Water density, 996.4129 kg/m3
Main pipe 100 mm NPS
Capacity, QT 0.01379 m3/sec
Condenser pipe 100 mm NPS
Capacity, Qcond
0.01082 m
3
/sec
Compressor pipe 50 mm NPS
Capacity, Qcomp 0.00297 m3/sec
Static head, hS 2 m
-
8/14/2019 DESIGN OF COOLING TOWER.docx
11/17
Friction Heads,hf
kpLfactorcorrectioneTemperaturdropessurelengthequivalentTotalh ef Pr
For the main line, 100 mm NPS, Schedule 40, from cooling tower to Tee of
condenser
Straight Pipe ------------------------------------------------------------ 6.42 m
2 900elbow ------------------------------------------------------------ 6 m
1 Standard tee ------------------------------------------------------------ 4.16 m
1 Gate valve ------------------------------------------------------------ 0.52 m
1 Check valve ------------------------------------------------------------ 9.15 m
__________
Total length 26.25 m
For the condenser line, 100 mm NPS, Schedule 40, from condenser tee to
condenser inlet
Straight Pipe ------------------------------------------------------------ 2.23 m
1 Standard tee ------------------------------------------------------------ 5.18 m
1 gate valve (open) --------------------------------------------------- 0.52 m
-
8/14/2019 DESIGN OF COOLING TOWER.docx
12/17
1 900elbow ------------------------------------------------------------ 3.0 m
____________
Total length 10.93 m
For the condenser tubes, 25 mm NPS, Schedule 40
Straight Pipe ------------------------------------------------------ 279 m
3 Close return bend --------------------------------------------- 49.41 m
____________
Total length 328.41 m
For the compressor line, 50 mm NPS, Schedule 40, from condenser tee to
compressor tee
Straight Pipe ------------------------------------------------------------ 3.8 m
1 Standard tee ------------------------------------------------------------ 0.9 m
1 gate valve (open) --------------------------------------------------- 0.09 m
1 900elbow ------------------------------------------------------------ 0.6 m
-
8/14/2019 DESIGN OF COOLING TOWER.docx
13/17
____________
Total length 5.39 m
From Compressor Tee to compressor inlet, 50 mm NPS, Schedule 40
Straight Pipe ------------------------------------------------------------ 3.0 m
1 Standard tee ------------------------------------------------------------ 0.9 m
1 gate valve (open) --------------------------------------------------- 0.09 m
____________
Total length 3.99 m
For the compressor jacket water line, assume equivalent length of 2 m inside
the compressor cooling water system.
From Figure 76, Pressure drop for water flowing in schedule 40 steel pipes,
Refr igeration and Ai r-conditioning by Stoecker & Jones, page 138.
For 100 mm pipe & 7.89 L/sec, p= 220 Pa / m
-
8/14/2019 DESIGN OF COOLING TOWER.docx
14/17
For 100 mm pipe & 7.65 L/sec, p= 370 Pa / m
For 50 mm pipe & 2.97 L/sec, p= 400 Pa / m
For 25 mm pipe & 0.24 L/sec, p= 1300 Pa / m
From Figure 7 7, Multiplying factors for pressure drops to correct for
temperature, Refri gerati on and Air -conditioning by Stoecker & Jones, page 139.
For taveof 27.50C & 1.52 m/sec water velocity, k= 0.98
Therefore the friction heads hf, are equal to,
ofmkPa
OHofmxkPaPax
m
Paxmhf
21 5756.01017.06595.55.659,598.0
22025.26
omkPa
OHofmxkPaPax
m
Paxmhf
22 403.01017.0963.3218.963,398.0
37093.10
mkPa
OHofmxkPaPax
m
Paxmhf
23 55.421017.039.4184.394,41898.0
130041.328
ofmkPa
OHofmxkPaPax
m
Paxmhf
24 2148.01017.0112.288.211298.0
40039.5
-
8/14/2019 DESIGN OF COOLING TOWER.docx
15/17
HofmkPa
OHofmxkPaPax
m
Paxmhf
25 159.01017.0564.108.156498.0
40099.3
OHofmkPa
OHofmxkPaPax
m
Paxmhf 2
26 3.01017.098.2298998.0
15252
Also the total friction head hfT,is equal to,
hhhhhhh ffffffSf 654321 443.0159.02148.055.42403.05756.0
Total friction head,hfT
Assuming the supply line equal to the discharge line,
SfTf hh 2
Therefore,
OHofmOHofmh Tf 22 4.882.442
Total Pumping Head,HT
OHofmhhH SfTT 24.9024.88
-
8/14/2019 DESIGN OF COOLING TOWER.docx
16/17
Water Horsepower,Whp
hp
hpkW
mmkNmHQW TwaterPhp 4.16
746.0
4.9081.9sec01379.0
746.0
33
Motor Power,Pm
p
hpm
m
hpp
WPPW
;
Using 75 % pump efficiency,
hphp
Pm 86.2175.0
4.16
For standard motor sizes, use 25 hp electric motor for the cooling water pump.
-
8/14/2019 DESIGN OF COOLING TOWER.docx
17/17