Design of Compression members - University of Al...
Transcript of Design of Compression members - University of Al...
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-26
Design Compression members
Design procedure of columns
The design of steel columns is a trial and error process.
1. The factored load is computed.
2. The effective slenderness ratio (kL/r) can be assumed to be generally between (40 to 60) for
lengths between 10ft to 15ft.
3. Based on the assumed (kL/r), an estimated value of the design buckling stress can be
obtained either by using AISC equations or by using AISC tables (4.22, page 4.318 of AISC
Manual).
4. The estimated column area can be obtained by :-
Fcrassumed
PuA esitm φ−
=.)(
5. Using the estimated column area, a trial column section can be selected.
6. The actual effective slenderness ratio can now be computed and the design buckling stress
can be obtained for the selected section and then the column design strength (ØPn) can be
calculated by ØPn = ØFcr ×Ag
7. The design strength ØPn is compared with the factored load and it must be ≥ (Pu)
8. Check the local buckling for the selected section.
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-27
Example 5:
a) Using Fy= 50 ksi, select the lightest W14 section available for the service column loads
PD= 130 k and PL= 210 k. Assume kL= 10 ft.
b) Repeat (a) using the AISC column design tables
Sol.
Factored load, Pu=1.2PD+1.6PL= 1.2(130) +1.6(210) = 492k
a). Assume 50=r
kL , ØFcr from Table 4.22, p 381 of AISC Manual = 37.5ksi
212.135.37
492).( inA atedesitm ==∴
from AISC Manual , selected W14×48 (A=14.1 in2, rx=5.85in, ry=1.91in).
Check the selected section
82.6291.1
1210
min
=×=r
kL From Table 4.22, p 381 of AISC Manual, ØFcr=33.75ksi
ØPn = ØFcr ×Ag=33.75×14.1= 476k < 492k Not Ok
Select W14×53 (A=15.6 in2, rx=5.84in, ry=1.92in).
5.6292.1
1210
min
=×=r
kL , ØFcr=33.85ksi
ØPn = ØFcr ×Ag=33.85×15.6=528k> 492k Ok ∴Use W14×53
b).For kL=10ft, From Table 4.1, p.4.14 of AISC Manual,
W14×48 ØPn=477 < 492k Not Ok
W14×53 ØPn=528k > 492k Ok ∴Use W14×53
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-28
yr
kLx
r
kL)()( >
Check ( width/thickness) ratio for local buckling
For W14×53 (bf=8.06”, tf=.66”, k=1.25”, d=13.9”, tw=0.37”)
1. For unstiffened element (flange)
11.666.02
06.8
2=
×=
f
f
t
b
< yF
E56.0
=13.9 ( case 3 , Table B4.1) OK
2. For stiffened element (web)
81.3037.0
)25.129.13( =×−=wt
h <
yF
E49.1
=35.82 ( case 10 , Table B4.1) OK
∴ No local buckling occurs
• Design of columns if the effective length is different
o The column design tables (4.1 to 4.20) of AISC Manual provides design strength of columns with respect to y-
axis assuming that (r
kL )y is longer than (
r
kL )x.
o For the case of (r
kL )x.> (
r
kL )y, or if (kL)X > (kL)y, two
approaches can be used:
1. Trial and error procedure
� Select a trial section assuming (r
kL )=50
� Compute of (r
kL )x and (
r
kL )y
� Determine ØFcr based on the larger values of (r
kL)
and multiply by Ag to determine ØPn
� Check the ØPn with factored load and select another size if necessary.
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-29
)(
)()( )(
x
yEquivalent
r
rxkL
ykL =
2. AISC Design tables
� A section size is to be selected from table (4.1 to 420 ) based on (kL)y
� Take y
x
r
rvalue from the table for that shape size and calculate kL)y Equivalent and
compare with (kL)y actual.
I. If (kL) y Equivalent < (kL)y actual, then (kL) y actual controls the design and the selected shape is correct.
II. If (kL) y Equivalent > (kL)y actual, then (kL)x controls the design and another section must be selected based on the value of kL) y Equivalent
Example 6: Select the lightest satisfactory W12 for the following conditions: Fy= 50 ksi, PD =
250k, PL = 400k, KxLx= 26 ft, and KyLy = 13 ft.
a. By trial and error procedure.
b. Using LRFD tables.
Sol.
a. Using trial and error:
Factored load, Pu=1.2Pd+1.6PL= 1.2(250)+1.6(400)=940k
a). Assume 50=r
kL ØFcr from Table 4.22, p 381 of AISC Manual =37.5ksi
2067.255.37
900).( inA atedesitm ==∴
from AISC Manual , selected W12×78 (A=25.6 in2, rx=5.38in, ry=3.07in).
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-30
ftyKLft
r
rxkL
ykL
x
yEquivalent 13)(8.14
75.1
26
)(
)()( )( =>===
Check the selected section
94.5738.5
1226)( =×=x
r
kL
Control
81.50
07.3
1213)( =×=y
r
kL
From Table 4.22, p 381 of AISC Manual, ØFcr=35.2 ksi
ØPn = ØFcr ×Ag=35.2×25.6=901k< 940k Not Ok
Selected larger section , say W12×96 (A=28.2 in2, rx=5.44in, ry=3.09in).
Check the selected section
35.5744.5
1226)( =×=x
r
kL
Control
48.50
09.3
1213)( =×=y
r
kL
from Table 4.22, p 381 of AISC Manual, ØFcr=35.55 ksi
ØPn = ØFcr ×Ag=33.55×28.2=1002.5k> 940k Ok ∴Use W12×96
b). Using LRFD tables (Table 4.1 of AISC Manual)
Based on (KL)y=13ft, Select W 12×87 from Table 4.1, p.4.17 of AISC Manual
From same table, y
x
r
r =1.75. Since (KL)x=26 >( KL)y=13, calculate the equivalent (KL)y from
the equation:
∴Use (kL)y Equivalent to determine the section size
Based on kL)y Equivalent =14.8ft, Select W 12×96 , ØPn=994.5 k > 940k Ok
Use W12×96
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-31
Check (width/thickness) ratio for local buckling
For W12×96 (bf=12.2”, tf=.9”, k=1.5”, d=12.7”, tw=0.55”)
1. For unstiffened element (flange)
76.69.02
2.12
2=
×=
f
f
t
b
< yF
E56.0
=13.9 ( case 3 , Table B4.1) OK
2. For stiffened element (web)
7.1755.0
)5.127.12( =×−=wt
h <
yF
E49.1
=35.82 ( case 10 , Table B4.1) OK
∴ No local buckling occurs
• Design of built up compression members
Built –up compression members sections are constructed with more than one shape
built-up into a single member. They include:
1. They may consist of parts in contact with each other, such as cover-plated
sections.
2. they may consist of parts in near contact with each other, such as pair of
angles: These pairs of angles may be separated by a small distance from each
other equal the thickness of the end connection or gusset plates between them.
3. They may consist of parts that are spread well apart, such as pairs of channels:
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-32
For long columns, it may be suitable to use built-up sections where the parts of the columns are
widely separated from each other to give higher moment of inertia such as towers.
General Notes
• When a pair angles are used as a compression member, they need to be fastened together so
they will act as a unit. Welds may be used at intervals or they may be connected with bolts.
• The widely spaced parts of these types must be carefully laced or tied together.
• The built -up section must have sufficient connection between its parts to prevent slippage on
each other and produce high moment of inertia.
• Connections are usually placed at column ends and column mid-span.
For Example
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-33
Connections requirements for built up columns
a. Components are in contact with each other (AISC Specification (Sec. E6):
The design strength of compressive built-up members whose components are in contact
with each other is the same as the usual columns with ONE exception as follows:
• If the members tends to buckle about an axis parallel to the direction of connection between
the W-shape and the plates, the connections are subjected to shear force, )(r
kLhave to
modified by AISC equations ( E6-1 and E6-2) as follows:
1. For intermediate connector that are made by high strength bolts
( snug-tight):
22 )()()(i
om r
a
r
kL
r
kL +=
(E6-1)
2. For intermediate connector that are welded or have pre-tensioned
bolts
22
22 )(
)1(82.0)()(
ib
om r
a
r
kL
r
kL
αα+
+=
(E6-2)
mr
kL)( is the modified slenderness ratio of the built-up compressive members.
or
kL)( is the original slenderness ratio of the built-up compressive members in the buckling
direction.
a is the distance between connections ( in the long direction).
ri is the minimum radius of gyration of the individual components
X-axis
Y-
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-34
rib is the radius of gyration of the individual components in the axis parallel to the axis of
buckling ( i.e. if moment about x -axis we take rx and . if moment about y- axis we take ry).
α is the separation ration = ibr
h
2 where h is the distance between centroids of the individual
components perpendicular to the axis of buckling.
(AISC Specification ( Sec . E7):
)(4
3)(
r
kL
r
ka
i
≤ Whole members
Example 6
You are to design a column for PD=750k and PL=1000k, using Fy=50ksi and Kl=14ft. A
W12×120 is on hand. Design cover plates to snug- tight bolted at 6” spacing to the W section.
Sol.
For W12×120, ( A=35.3in2, d=13.1”, bf=12.3”, Ix=1070in4, Iy=345in4).
Pu=1.2×750+1.6×1000= 2500k
Using trial and error:
a). Assume 50=r
kL ØFcr from Table 4.22, p 381 of AISC Manual =37.5ksi
267.665.37
2500).( inA atedesitm ==∴
Aplates=66.67-35.5=31.36in2 ( Area for each plate =15.68in2)
Try Two cover plates PL1×16
Check the selected section
A= 35.3+2(1×16) = 67.3 in2
Ix=1070+2×16×
2)2
0.11.13(
+=2660in4
X-axis
Y-axis
W12×120
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-35
"29.63.67
2660==xr
Iy=345+2× )12
161(
3+
=1027.7in4
"91.33.67
3.1027 ==yr
97.4291.3
1214)( max =×=
r
kL
Calculate the modified slenderness ratio for x-axis ( parallel to the connection plane)
22 )()()(i
om r
a
r
kL
r
kL +=
(Snug- tight bolted connections are used)
a= 6”
ri=rx= A
I x plates ( minimum radius of gyration of individual member)
Ix=4
3
33.112
116in=×
A=16in2 . ri =rx =0.289”
76.20289.0
6 ==∴ir
a, 71.26
29.6
1214)( =×=xr
kL
22 )76.20()71.26()( +=∴ mr
kL= 33.83< 42.97 does not control the design
Check slenderness ratio limit of the plates
23.3297.424
3)(
4
376.20)( ==≤=
r
kL
r
ka
i Ok
For yr
kL)( = 42.97 , from Table 4.22, p 381 of AISC Manual, ØFcr=39.31 ksi
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-36
ØPn = ØFcr ×Ag=39.31 ×67.3=2646 k< 2500k Ok Use W12×120 steel section with two cover plates PL1×16, Fy = 50ksi
b. Components are Not in contact with each other- Design of lacing and tie plates
(AISC Specification (Sec. E6):
1. Design of tie plates ( discussed in tension members)
2. Design of lacing
a. memberwholememebrindivitual r
kL
r −−
≤ )(4
3)
sconnection lacingbetween distance The(
)min(
b. Vu (on the lacing )=0.02Pu (whole compression member)
perpendicular to the compression member
140)( ≤lacingr
kL for single lacing
200)( ≤lacingr
kL for double lacing
If l ≤ 15in , it is ok to use single lacing made with angles.
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-37
Example 7
a) Using AISC LRFD specifications and Select a pair of 12-in standard channels for the
column and load shown using Fy= 50 ksi. For connection purposes, the back-to-back
distance of the channels is to be 12 in. PD=100k and PL=300k.
b) Using Fy =36ksi, design bolted single lacing for the
column assume that ¾” bolts are used.
Sol.
Pu=1.2PD+1.6PL=1.2(100)+1.6(300)=600k
a). Assume 50=r
kL ØFcr from Table 4.22, p 381 of AISC
Manual =37.5ksi
20.165.37
600).( inA atedesitm ==∴
A (required for each section) =8in2
From AISC-Specification( Table 1.-5 , P1-34), Select C12×30 : (A=8.81in2, d=12”,x′ =0.674”,
Ix=162in2, Iy=5.12in2) Check the selected section
A= 17.62in2
Ix=2×162=324in4 Iy=2[5.12+8.81×(2
12-0.674)2]=510in4
lAtotal
Ixr x 63.17
324== =4.29” lAtotal
Iyr y 63.17
510== =5.38”
"38.5min ==∴ yrr , k=1.0 (from table C2.2.1, pinned ends)
94.5529.4
12201)( max =××=
r
kL
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-38
From Table 4.22, p 381 of AISC Manual, ØFcr=35.82 ksi (By interpolation)
ØPn = ØFcr ×Ag=35.82 ×17.62=631k >600k Ok Check ( width/thickness) ratio for local buckling
For C12×30 (d=12”, bf=3.17”, tf=.501”,TW=0.510 k=1.25”)
1. For unstiffened element (flange)
33.6501.0
17.3 ==f
f
t
b
< yF
E56.0
=13.9 (case 3, Table B4.1) OK
2. For stiffened element (web)
12.19510.0
)25.1212( =×−=wt
h <
yF
E49.1
=35.82 (case 14 , Table B4.1) OK
∴ No local buckling occurs
Use 2C12 × 30 steel sections
b).Design the lacing
� The distance between lines of bolts
=l=8.5”< 15” it is ok to use single lacing
� Check the slenderness limit for individual
member
Assume 60ͦ inclination with longitudinal axis of
the compression member:
∴Length of channel between the lacing connections =2×8.5×tan30=9.81”
� The slenderness limits
memberwholer
kL
r memebrindivitual
−≤−
)(4
3)
sconnection lacingbetween distance The(
)min(
30 ͦ
30 ͦ
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-39
96.41)94.55(4
39.12)
761.0
9.81( =≤= Ok
� Calculation the force on the lacing channel
Vu=0.02×Pu=0.02×631=12.62k ∴2
1Vu=6.31 (shear force on each plane of lacing)
∴Compression force on the lacing section = )30cos(
2
1Vu
=7.28 k
� Calculation the dimensions of the lacing flat bar
ttb
tb
A
Ir 289.0
12/)( 3
=×
×==
Assume r
L= minimum value of the single lacing =140
07.0140
81.9140
=== Lr
∴r= 0.289t= 0.07 t=0.242” Try (¼)” flat bar 1364/1289.0
81.9 =×
=r
L
< 140 ok
From table 4.22 of AISC Manual ØFcr=12.2 ksi for 136=r
L
2597.02.12
28.7)( inA erequired == ∴(¼” ×2.39”) is needed
� Total length of the lacing =length of lacing between connections + 2×minimum edge
distance
=9.81+2×1 ¼ =12.3” say 14” (Min. edge distance for ¾ bolt is 1 ¼ from table J3.4 of AISC manual)
∴Use (¼” ×2 ⅜× 1’ 2”) flat bar
t
b
30 ͦ
P
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-40
Column used in steel frames
• The effective length of a column is a property of whole structure of which the column is a apart. • The most common method of obtaining the effective
length is to use the alignment charts for column braced
or un-braced against sidesway, using Tables C.C2.3
and C.C2.4 of AISC manual part 2 or table 7.2 ( a and
b) Page 201 of textbook.
• To determine k factor by alignment charts, the
following steps are followed:
1. Compute (G) value at each end of the column (GA
and GB) from the following equations:
beams
columns
L
IL
I
forbeamsL
EI
forcolumnsL
EI
G)(
)(
)4
(
)4
(
∑
∑
∑
∑==
2. Select the appropriate alignment chart [sidesway
prevented ( braced ) and sidesway un-prevented ( un-
braced )] and draw a straight line on the chart between
GA and GB values and read k value.
3. For the column bases the following G values can be
used
a) For pinned column, G=10
b) For rigid connection to footing ( fixed ) , G=1.0
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-41
o The most important assumptions based on which the alignment charts are
made are:
1. The members are elastic.
2. All columns buckle simultaneously.
3. For braced frames , θ 1=θ2 for each beam , (single curvature)
4. For un-braced frames , θ 1=- θ2 for each beam , (double curvature)
� For frames at which assumptions 3 and 4 are not satisfy, used the following multiplier can be
used for (G) values such as the following frames
(L
I)BC×1.5 for sidesway prevented ( braced- or pinned)
(L
I)BC×0.5 for sidesway not prevented (un-braced or rolled)
(L
I)BC×2.0 for sidesway prevented ( braced )
(L
I)BC×0.67 for sidesway not prevented (un-
braced or guided support)
M2 M1
θ1 θ2
θ 1=θ2 , single curvature
M2 M1
θ1
θ2
θ 1=-θ2, double curvature
Depending on the direction of ends moments M1 and M2
Depending on the direction of ends moments M1 and M2
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-42
� If the column behaviour is inelastic (assumption 1 is not valid), the column stiffness factor
will be smallerL
IEτ, and the G value will be smaller and k values will be smaller ( i.e high
column resistance)
• For an inelastic column situation
inelasticG = elasticG ×stiffness reduction factor (SRF), aτ
Table 4.21 of AISC Manual, page 4.317, or table 7.2 page 211 of textbook provides values of
stiffness reduction factor aτ for different values of A
Pu
• To design columns to consider inelastic columns behaviour in frames, the following
steps should be followed:
1. Calculate Pu , assume r
kL and select a trial section size.
2. Calculate A
Pu and select aτ from table 4.21 in Manual or table 7.2 in textbook.
3. Compute values of G elastic and multiply by aτ and find k value.
4. Compute the r
kL actual and the find ØFcr then determine Pu= ØFcr×Ag and compare
it with Pu.
Example 8:
a) Select a W section for column AB
of the un-braced frame shown in
Fig. below assuming that we have
elastic behaviour , PD=450k and
PL=700k, Fy=50ksi
b) Repeat part (b) if inelastic column
behaviour is considered.
Assume that columns above and below column AB are the same size as AB
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-43
Sol.
Pu=1.2PD+1.6PL=1.2(450)+1.6(700)=1660k
a). Assume 50=r
kL ØFcr from Table 4.22, p 381 of AISC Manual =37.5ksi
2267.445.37
1660).( inA atedesitm ==∴
From AISC-Specification( Table 1.1),the following selects are available W14×176 : (A=51.8in2) W12×170 : (A=50.07in2) we have to use a larger section to account for the increasing in k
values
W14×159 : (A=46.7in2) W12×152 : (A=44.7in2)
W12×136: (A=39.9in2)
∴For W12×170 : (A=50in2,,, Ix=1650in4, rx=5.74in) we assume that the columns are bent about x- direction
16.5)
1230
800(2
)1212
1650(2
)(
)(=
×
×==∑
∑
beams
columns
A
L
IL
I
G
GB=GA=5.16 (Same columns and beams dimensions) From alignment chart ( Table C.C2.4) ( un-braced frame) k=2.3
7.5774.5
12123.2)( =××=∴
r
kL
From Table 4.22, p 381 of AISC Manual ØFc=35.29ksi
ØPn = ØFcr ×Ag=35.29 ×50=1764 >1660k Ok b).Inelastic design Because the inelastic resistance of steel column is greater than the elastic resistance, we select a
lighter section than the elastic behavior section.
Try W12×136: (A=39.9in2 , Ix=1240in4 , rx=5.58”)
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-44
6.419.39
1660==A
Puin2 aτ = 0.1974 from table 4.21 in Manual or table 7.2 in
textbook.
765.0)
1230
800(2
)1212
1240(2
=×
×
×= aAG τ
From alignment chart ( Table C.C2.4) ( un-braced frame) k=1.27
77.3258.5
121227.1)( =××=∴
r
kL
From Table 4.22, p 381 of AISC Manual ØFc=41.7ksi
ØPn = ØFcr ×Ag=41.7×39.9=1663 >1660k Ok
Example 9:
We desire to select a W14 section for column CD in the figure shown for which PD=300k and
PL=600k, and Fy =50ksi, Only in-plane behaviour is considered. Furthermore, assume that the
columns immediately above and below CD are approximately the same size as CD, and also
that all the other assumptions on which the alignment charts are met.
a) Assume elastic behaviour.
b) Assume inelastic behaviour.
Sol.
Pu=1.2PD+1.6PL=1.2(300)+1.6(600)=1320k
a). Assume 50=r
kL ØFcr from Table 4.22, p 381 of AISC
Manual =37.5ksi
22.355.37
1320).( inA atedesitm ==∴
From AISC-Specification( Table 1.1),the following selects are available
36ft 36ft
15ft
W30×99 W30×99
W30×99
Ix=3990 Ix=3990
15ft
15ft
D W30×99
C
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-45
W14×120 : (A=35.3in2, Ix=1380in4, rx=6.24in) Because beam dimensions are large; we expect k value will be small. From AISC Manual and for W30×99, Ix=3999
83.0)
1236
3999(2
)1215
1380(2
)(
)(=
×
×==∑
∑
beams
columns
A
L
IL
I
G
GB=GA =0.83 Same columns and beams dimensions From alignment chart ( Table C.C2.4) ( isedsway uninhibited ( un-braced frame)) k=1.25
055.3624.6
121525.1)( =××=∴ xr
kL
From Table 4.22, p 381 of AISC Manual ØFc=40.9ksi
ØPn = ØFcr ×Ag=40.9×35.3=1443.77k >Pu=1330k Ok b).Inelastic design Because the inelastic resistance of steel column is greater than the elastic resistance, we select a
lighter section than the elastic behavior section.
Try W12×109: (A=32in2 , Ix=1240in4 , rx=6.22”)
25.4132
1330==A
Puin2 aτ = 0.217 by interpolation from table 4.21 in Manual
or table 7.2 in textbook.
162.0217.0)
1230
3990(2
)1215
1240(2
=×
×
×=TopG
Gtop=Gbottom=0.162 From alignment chart ( Table C.C2.4) ( un-braced frame) k=1.1
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-46
31.832 22.6
12151.1)( =××=∴
r
kL
From Table 4.22, p 381 of AISC Manual ØFc=41.75ksi
ØPn = ØFcr ×Ag=41.75×32.0=1336k >1330k Ok
Design of Base Plate • Design procedure for column base plate. 1. Determine the required area of the base plate
according to the design bearing strength of
concrete beneath the base plate. The
following equation can be used:
1
2
1
)85.0(A
Acf
PuA
c′
=φ
cφ =0.6,
1
2
A
A≤2.0 ( in this equation only )
Notes: Base plate area must be larger than
the area of the column section (b×d)
2. Determine the base plate dimensions (N×B)
from the following equations:
∆=0.5(0.95d-0.8bf)
N= 1A +∆
B=N
A1
d and bf are the depth and flange width of
the column cross section.
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-47
Notes: values of B and N are selected to nearest 1“ or 2” so that values of m and n shown
in the figure are roughly equal and the cantilever moment are equals too.
3. Determine the base plate thickness from the following equation:
NBFy
Pult req ×××=
9.0
2
l is the largest values of m , n and n′
m and n are shown in the figure which are the cantilever dimensions from the base edge in x
and y axes respectively.
4
fdbn =′
Example 10: Design a base plate of A36 steel for a W 12×65 column with Fy=50ksi that
supports loads 0f PD=200k and PL=300k. The concrete has a compressive strength of fc’=3ksi
and the footing has dimensions of 9ft×9ft.
Sol.
Pu=1.2×200+1.6×300=720k
For W 12×65 (d=12.1”, bf=12.0”
Assume 1
2
A
A
=2 (the maximum value)
2
1
2
1 3.2352)385.0(6.0
720
)85.0(
in
A
Acf
PuA
c
=××
=′
=∴φ
235.2in2> d×bf=145.2 in2 ok
∆=0.5(0.95d-0.8bf)= 0.5(0.95×12.1-0.8×12)=0.9475”
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-48
N= 1A +∆= 13.235 +0.9475=16.3” say 16”
B=N
A1 = =16
3.23514.7”
Use 16”×16” square base plate.
• Check the bearing strength of the concrete
ØPn=Øc(0.85fc’)A1 1
2
A
A
=0.6×(0.85×3) ×(16)2×2=783.4k > 720 ok
• Determine the thickness of the base plate
m= (16-0.95×d)/2= (16-0.95×12.1)/2=2.25”
n= (16-0.8×bf)/2=(16-0.8×12)/2=3.2”
"01.34
121.12 =×=′n
l = the largest value =3.2”
"38.11616369.0
72022.3 =
×××××=reqt say 1 ½”
Use PL1 ½” ×16”× 1’ 4” A36 base plate
Example 11( Prob 7.15 page 235 of texbook): Design a base plate of A36 steel for a W 14×120
column with Fy=50ksi that supports loads 0f PD=150k and PL=350k. The footing size is 10ft
by 10 ft and fc’=3ksi and
Sol.
Pu=1.2×150+1.6×350=740k
For W 12×65 (d=14.5”, bf=14.7”
Assume 1
2
A
A
=2 (the maximum value)
Structural Steel Design 2015-2016 Dr. Haitham A. Bady
2-49
2
1
2
1 83.2412)385.0(6.0
740
)85.0(
in
A
Acf
PuA
c
=××
=′
=∴φ
241.83in2> d×bf=213 in2 ok
∆=0.5(0.95d-0.8bf)= 0.5(0.95×14.51-0.8×14.7)=1.01”
N= 1A +∆= 83.241 +1.01=16.55” say 17”
B=N
A1 = =17
83.24114.22” say 15”
Use 17”×15” rectangular base plate.
• Check the bearing strength of the concrete
ØPn=Øc(0.85fc’)A1 1
2
A
A
=0.6×(0.85×3) ×(15×17)×2=780.3k > 740 ok
• Determine the thickness of the base plate
m= (16-0.95×d)/2= (17-0.95×14.5)/2=1.6125”
n= (16-0.8×bf)/2=(15-0.8×14.7)/2=1.2525”
"65.34
7.145.14 =×=′n
l = the largest value =3.65”
"544.11715369.0
740265.3 =
×××××=reqt say 1⅝”
Use PL 1⅝”×15”× 1’ 5” A36 base plate