Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 1
Design and Safety Considerations for existing LNG Peak Shaving Plants
Hans – Joachim GrossmannGOC Engineering GmbH
Gastech 2005 March 13-17, Bilbao Spain
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 2
Design and Safety Considerations for existing LNG Peak Shaving Plants
-A Project Example-
The plantBrief plant descriptionProject phasesPre-StudiesConformity studyCosting study
The projectDesign aspectsProject executionProject statusProject organizationSummary/conclusions
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 3
The Plant
LNG Peak Shaving PlantLocated at DormagenNievenheim, GermanyPart of ~ 4,000 km HP Gas Pipeline Grid of RWE EnergyMainly cavern storage
Start up in 1976Built by CBI GermanyOnly two cryogenic LNG installations in Germany
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 4
Brief Plant Description
Gas Treatment and Liquefaction
Gas treatment with two adsorber systemsTo remove moisture, aromatics, CO2Liquefaction with MRL cycleMRL Methane/PropaneLiquefaction capacity2,400 Nm³/h
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 5
Brief Plant Description
LNG Storage
Double wall steel tank (API 620 Q)Inner tank 9% nickel suspended deckOuter tank CSBottom/shell penetrationsGeo. V. 22,700 m³
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 6
Brief Plant Description
BOG Handling (exist.)Partly re-circulated back to tankPartly send to pipeline
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 7
Brief Plant Description
NG Send Out SystemTwo HP Pumps , outside tanks, 2 x 80m³/h LNGTwo submerged combustion vaporizersSend out rate: 2 x 50,000 Nm³/hConditioning with LN2Truck loading system
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 10
Pre- Studies
I. First Study to check the Compliance of the plant with actual rules & regulationsE.g. EN 1473/NFPA 59ASafety Study to review actual installed safety featuresActive & passive safety equipment
II. TargetLife Extension of the plantIncreased level of automation Alternative peak shaving concepts
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 12
Pre- Studies
III. ResultsEN 1473 allows no penetrations of the primary and secondary container walls ( >> submerged tank pumps)NFPA 59A allows penetrations, however the design spill shall be defined as the full liquids content of the tank ( >> with submerged pumps the design spill reduced to 10min. Nom. Pump capacity)Entire revamping needed instrumentation & control system Partly revamping needed for mechanical equipment
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 13
Pre- Studies
IV. Costing studyCosting of various alternatives
Revamping of plant + submerged pumpsRevamping of plant with additional safety features ( water curtains, foam systems, thermal insulation of impoundment area )
Other alternatives such as close down of plant
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 14
The Project Overview
Client decided to take out the plant for one winter season to: Empty and warm up the LNG tank
Install submerged pumpsInstall new instrumentation &control systemRevamp partly mechanical equipment/ piping, control building etc. Install new BOG handling system ( was added to the project 2Q/2004)
Project duration 1Q/04 – 4Q/05
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 15
Design Aspects Process
Process simulation Change in gas compositionOptimization due to input from operatorsE.g. gas treatment &liquefaction process Level of automation New BOG System
SafetyHazop StudySIL Allocation
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 16
Design Aspects LNG Tank
Tank Decommissioning Data assessment after 30 years operation
Static calculations of existing tankInstall new pumps/pump platformRecalculated the tank due to change in rules & regulationsInstall additional outer shell stiffeners
Local authorities/ Environmental Change in Rules & RegulationsSafety Report
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 20
Project Execution Emptying Tank
Decommissioning of tank starts at approx. 2,5 m liquid level ( April 2004)Temporary connection between RT Loading pumps and HP send out pumps Result : Tank more or less 100 % liquid emptied Warming upPurging with nitrogenPurging with air Opening the tank
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 22
Project Execution Tank Opening – Suspend. Deck
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 26
Project Execution -Laser Scanning (Test Project)
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 27
Project Execution -Laser Scanning (Test Project)
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 28
Project Execution -Laser Scanning (Test Project)
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 29
Project Execution -Laser Scanning (Test Project)
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 30
Project Execution -Laser Scanning (Test Project)
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 31
Project Organisation
Entire project execution with one Engineering company including:
pre studiesbasic, detailed engineeringprocurement assistancesupervision and start up
Direct procurement of equipment
Grossmann/Gastech2005 Revamping LNG Peak Shaving Plant 32
Summary /Conclusions
Detailed Pre Studies requiredClose cooperation between Client/ Engineering companyDetailed planning of activities Tailor made solutions requiredNo critical findings after 30 years of useFindings/results can be used for other projects too ( LNG/LEG)