DESIGN AIR UNIVERSITY 1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

Transcript of DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of...

Page 1: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 1

Evacuation Clinic

This presentation is excerpted from ROBINAIR'S library of air

conditioning educational material.

Page 2: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 2

Vacuum: How It Relates to Air

Conditioning Service

Page 3: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 3

Introduction

This slide show is designed to inform HVAC service technicians about the physics of the evacuation process and vacuum pump selection so that they may excel at their profession & prosper.

Produced by DESIGN AIR UNIVERSITY with considerable help from ROBINAIR.

Page 4: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 4

Outline

Fundamentals of Dehydrating a Refrigerant System

Moisture in a refrigerant system

How acid affects metals

Tools needed

Page 5: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 5

The two most frequent questions service technicians ask about dehydration are:

What size vacuum pump should be used be used to perform a good refrigeration / air conditioning system dehydration job?

How long should the pump be left on the system to assure a good removal of all moisture from the system?

Page 6: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 6

Before we can answer: To give specific answers to these

questions, you need to know: The cubic capacity of the system to

be dehydrated. The amount of moisture both visible

and invisible present in the system. The diameter and length of the line

set as well as restrictions within the system itself (cap tubes, valves,etc.) which might cause back pressures.

Page 7: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 7

Let's do this:

Rather than supplying fast, pat answers to these important questions and then trying to justify them, let's start by covering the basic fundamentals of dehydrating a refrigerant system.

Page 8: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 8

Moisture In A Refrigerant System

While it is important to realize that moisture in a refrigerant system is the underlying cause of many problems and complaints, it is equally important to learn why.

Page 9: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 9

Moisture In A Refrigerant Systemcontinued

Basically, moisture can be classified as visible and invisible. Invisible moisture or water vapor is the culprit which causes the greatest trouble in refrigeration and air conditioning systems.

Page 10: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 10

Moisture In A Refrigerant System continued

A single drop of water may look harmless, but to a refrigerant system, it is a monster, the number one enemy of service technicians.

What makes it so formidable is the fact that moisture enters a system easily and is hard to remove.

Page 11: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 11

Here is what it does to a system: First, it creates "freeze-ups." Moisture will be picked up by the

refrigerant and be transported through the refrigerant lines in a fine mist which forms ice crystals at the point of expansion (piston, or TXV).

Page 12: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 12

Here is what it does to a system:continued

Ice crystals retard or stop the flow of the refrigerant, causing loss of cooling.

As the expansion valve warms, due to the lack of refrigerant, the ice melts and passes through the metering device.

Page 13: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 13

Here is what it does to a system: continued

The refrigerant will then start to flow again until the moisture returns, to the metering device and once more builds ice crystals.

The result is intermittent cooling.

Page 14: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 14

"Freeze-ups"

Whether a "freeze-up" actually occurs depends primarily upon the amount of water and the size of the ice particles formed.

But a "freeze-up" is not the only problem caused by moisture!

Page 15: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 15

Moisture and Corrosion

Moisture can also cause corrosion, which can present serious trouble!

Page 16: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 16

Moisture and Corrosion continued

Moisture mixed with refrigerant creates much more trouble.

Refrigerants such as R-12 containing chlorine will slowly hydrolyze with water and form hydrochloric acids.

These acids greatly increase the corrosion of metals and could corrode copper plating.

Page 17: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 17

Moisture & Corrosion continued

Heat increases the rate of corrosion due to acids because higher temperatures accelerate the acid-forming process.

This acid attacks all the materials it contacts.

Page 18: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 18

Moisture & Refrigerant Oil Refrigerant oil presents another

problem caused by moisture.

Refrigerant oil is an exception to the rule that "water and oil don't mix."

In fact, refrigerant oil attracts moisture and will absorb it rapidly if left open to the atmosphere.

Page 19: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 19

Moisture & Refrigerant Oil continued

Water-formed acid mixes with refrigerant oil, forming a closely bonded mixture of fine globules.

The effect is called "sludging" and

greatly reduces the oil's lubricating ability.

Page 20: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 20

Corrosion & "Sludge" Corrosion becomes troublesome

from the operating standpoint when metallic surfaces are eaten away and a solid, detachable product is formed.

This formation is also known as a "sludge."

Page 21: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 21

The Effects of "Sludge" It will plug fine strainers, expansion

valves and capillary tubes.

Because it contains acids, sludge corrodes whatever it clings to, accelerating system damage.

Page 22: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 22

The most effective way to remove moisture from a system

is with a vacuum pump.

Page 23: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 23

Other tools needed:

Page 24: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 24

Other tools needed:

Page 25: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 25

The Effects of Pressure & Temperature On The Boiling Points Of Water

"A high vacuum pump is capable of removing all moisture from a hermetic system by reducing the internal system pressures to the boiling point of water at normal temperatures."

Page 26: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 26

How It Works.

A vacuum pump does not "suck out" the liquid moisture.

Rather, it causes the moisture to boil into a vapor state which can be harmlessly removed from the system and exhausted through the vacuum pump.

Page 27: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 27

The planet earth is surrounded by matter in a gaseous state.

78% Nitrogen 21% Oxygen 1% other gases

Extends approximately 600 miles above the earth.

Held by gravity. Has weight. Measured in pounds per

square inch.

Page 28: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 28

Atmospheric Pressure

If you were to take a square inch column of the air extending 600 miles above the earth, its weight and pressure exerted on the earth at sea level would be 14.7 pounds.

This is called atmospheric pressure.

Page 29: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 29

Pressure vs. Vacuum

Any pressure above atmospheric pressure is referred to as gauge pressure.

Pressures below atmospheric are referred to as vacuum.

Page 30: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 30

Measuring Pressures

This same square inch column of air exerting 14.7 psi can support a one inch square column of mercury (Hg) 29.92 inches high.

Page 31: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 31

Atmospheric pressure & elevation

Atmospheric pressure decreases at higher elevations.

Going above sea level, to the summit of Mount Whitney for example, eliminates some of the 600 miles of atmosphere and, consequently, some of the pressure.

Page 32: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 32

Pressure's effect on boiling point

Atmospheric pressure determines the boiling point of water.

At sea level, water boils at 212o F. On the summit of Mt. Whitney,

where atmospheric pressure is 8.32 psi, water boils at 184o F.

The lower the atmospheric pressure is, the lower the boiling point of water.

Page 33: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 33

Pressure's effect on boiling point

Therefore, if we can significantly reduce the atmospheric pressure inside a sealed refrigerant system, we can vaporize (or boil) moisture at even –90o F.

This principle is illustrated in the following chart:

Page 34: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 34

Pressure's effect on boiling point

Page 35: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 35

Three ways to eliminate moisture from a refrigerant system by the boiling process.

1. Transport the system to a higher elevation where the ambient temperature is sufficient to boil water at the existing psi.

2. Apply heat to the system causing the moisture to boil.

3. Employ a high vacuum pump to reduce the pressure and boiling point of water.

Page 36: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 36

There is only one choice!

The first two choices are impractical.

Thus, a high vacuum pump is an essential aid to every service technician.

Page 37: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 37

High Vacuum / Deep Vacuum

The purpose of a vacuum pump is to reduce the internal system pressure of a refrigeration / air conditioning system so moisture and other contaminants can be removed.

Page 38: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 38

"High Vacuum"

The term "high vacuum" describes a condition where the internal system pressure is extremely low, or close to a perfect vacuum.

The higher the vacuum is in a system, the closer the micron reading is to zero microns.

Page 39: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 39

"Deep Vacuum"

"Deep vacuum" can be thought of in the same way.

The deeper a vacuum is, the closer the micron reading is to zero microns.

High Vacuum = Deep Vacuum

Page 40: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 40

Selecting High Vacuum Pumps While any pump pulling within one

inch of atmospheric pressure can eliminate moisture, it must also be capable of holding that vacuum throughout the dehydration process.

In addition, it must pull that vacuum on the entire system and not simply at the intake of the pump.

Page 41: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 41

What is "gas ballast"? The gas ballast or vented exhaust

feature of some vacuum pumps permits relatively dry air from the atmosphere to enter the second stage of the pump.

This air reduces the compression in the final stage which helps to prevent moisture from condensing into a liquid and mixing with the vacuum pump oil.

Page 42: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 42

How Gas Ballast Works

The process of the gas ballast arrangement permits the moisture-laden air passing through the pump to mix with relatively dry air to such degree that compression does not cause condensation inside the pump

Page 43: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 43

Limits of Gas Ballast Cannot handle large amounts of

moisture. Some pumps are designed to run

with high internal temperatures. This reduces condensation in the oil. Supplements the gas ballast feature. Regular oil changes are still

essential, sometimes daily ! Check the sight glass!

Page 44: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 44

Factors Affecting Pump Speed

Cubic feet of the refrigerant system

The amount of moisture in the system.

The ambient temperature.

Internal & external restrictions.

The size of the pump.

Page 45: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 45

The only two factors the service technician can control are:

External restrictions.

Pump size.

Page 46: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 46

Some pumps are faster than others!

Page 47: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 47

How to make any pump faster:

The speed at which the evacuation occurs is controlled by the i.d. and length of the connecting line.

Use large diameter, short length hoses.

Page 48: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 48

Is a bigger pump really better?

It is perfectly acceptable to use a 4 cfm pump on a small system.

Using too small of a pump on a large system could cause the pump to operate in a "free air" condition for an extended period of time, thus risking premature pump wear.

Page 49: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 49

Choosing the right size vacuum pump:

Page 50: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 50

How long should the pump run?

Use a thermistor vacuum gauge, also called a micron gauge.

Prevents wasting time by running the pump too long or by risking inadequate dehydration.

Page 51: DESIGN AIR UNIVERSITY1 Evacuation Clinic This presentation is excerpted from ROBINAIR'S library of air conditioning educational material.

DESIGN AIR UNIVERSITY 51

Conclusion

We thank you for joining our class today!