DEPRESSURIZATION TEST REPORT

2
Municipality: Make and Model Address: 1) Pa 2) Pa Name: 3) Pa Company: 4) Pa Address: 5) Pa Phone: Lowest Depressurization Limit Pa E-mail: Date of Test: YY/MM/DD Make and Model: Note: Test to be carried out when house is substantially complete Wind: Designed by: Note: Wind conditions should be less than 15 km/h (9 mph) Installed by: Des g i ned to: CSA F326 NBC Other Tested to: CSA F326 CGSB 51.71 CSA F300 Starting "Rest" Pressure Pa Principal Ventilation Fan Pressure @ TVCC Pa Location: Pressure @ CEC Pa Manufacturer: Ending "Rest" Pressure Pa Model: Capacity Low/Principal Ventilation Capacity: High/Total Ventilation Capacity: (b) minus (a) = Pa If the principal ventilation fan is a H /ERV, RV it is : On (b) minus (d) = Pa Largest of (e) or (f) Make and Model Capacity = Dep. @ TVCC Pa TVCC CEC Note: The depressurization limit is from Section 6, but no more 1) than 10 Pa under F326. 2) 3) 4) (c) minus (a) = Pa 5) (c) minus (d) = Pa 6) Largest of (g) or (h) 7) Pa 8) Note: The depressurization limit is from Section 6. Furnace Fan conforms does not conform Name: Signature: Date: HRAI #: to the depressurization test requirements identified above. The dwelling unit and systems at the time of test: 10. CERTIFICATION 9. TEST RESULTS I CERTIFY THAT THE TEST HAS BEEN PERFORMED IN ACCORDANCE WITH THE TEST PROCEDURE IDENTIFIED ABOVE. Off 5. OTHER EXHAUST APPLIANCES On at ON OFF (h) = Dep. @ CEC 8. DEPRESSURIZATION @ CEC 1 2 3 (g) 3 (e) (f) Zone Dep. Limit 7. MEASUREMENTS (a) (b) (c) (d) 1 Zone 2 3 8. DEPRESSURIZATION @ TVCC 1. BUILDING 2. TECHNICIAN 3. TEST EQUIPMENT EPRESSURIZATION D EST T EPORT R 6. COMBUSTION APPLIANCES 4. VENTILATION DESIGN 1 2 © Copyright HRAI Depressurization Testing of Residential Systems r 12/19

Transcript of DEPRESSURIZATION TEST REPORT

Page 1: DEPRESSURIZATION TEST REPORT

Municipality: Make and Model

Address: 1) Pa

2) Pa

Name: 3) Pa

Company: 4) Pa

Address: 5) Pa

Phone: Lowest Depressurization Limit Pa

E-mail:

Date of Test: YY/MM/DD

Make and Model: Note: Test to be carried out when house is substantially complete

Wind:

Designed by: Note: Wind conditions should be less than 15 km/h (9 mph)

Installed by:

Des gi ned to: CSA F326 NBC Other

Tested to: CSA F326 CGSB 51.71 CSA F300 Starting "Rest" Pressure Pa

Principal Ventilation Fan Pressure @ TVCC Pa

Location: Pressure @ CEC Pa

Manufacturer: Ending "Rest" Pressure Pa

Model:

Capacity Low/Principal Ventilation Capacity:

High/Total Ventilation Capacity: (b) minus (a) = Pa

If the principal ventilation fan is a H /ERV,RV it is : On (b) minus (d) = Pa

Largest of (e) or (f)

Make and Model Capacity = Dep. @ TVCC Pa

TVCC CEC Note: The depressurization limit is from Section 6, but no more

1) than 10 Pa under F326.

2)

3)

4) (c) minus (a) = Pa

5) (c) minus (d) = Pa

6) Largest of (g) or (h)

7) Pa Note: The depressurization limit is from Section 6, but no more

8) Note: The depressurization limit is from Section 6.

Furnace Fan

conforms does not conform Name:

Signature:

Date: HRAI #:

to the depressurization test requirements identified above.

The dwelling unit and systems at the time of test:

10. CERTIFICATION9. TEST RESULTS

I CERTIFY THAT THE TEST HAS BEEN PERFORMED IN ACCORDANCE

WITH THE TEST PROCEDURE IDENTIFIED ABOVE.

Off

5. OTHER EXHAUST APPLIANCES

On at

ON OFF

(h)

= Dep. @ CEC

8. DEPRESSURIZATION @ CEC

1 2 3

(g)

3

(e)

(f)

Zone Dep. Limit

7. MEASUREMENTS

(a)

(b)

(c)

(d)

1

Zone

2 3

8. DEPRESSURIZATION @ TVCC

1. BUILDING

2. TECHNICIAN

3. TEST EQUIPMENT

EPRESSURIZATIOND ESTT EPORTR6. COMBUSTION APPLIANCES

4. VENTILATION DESIGN

1 2

© Copyright HRAI Depressurization Testing of Residential Systems r 12 /19

Page 2: DEPRESSURIZATION TEST REPORT

Component CSA F326 CGSB 51.71 CSA F300

Windows and exterior doors Close Close CloseInterior doors Open Open (1) Leave as isAttic hatch Close Close CloseFlue with damper (e.g. fireplace) Close Close CloseFireplace Seal (2) Close doors

Fireplace combustion air damper Close CloseDoors on enclosed furnace room Close Close (1) Open(1)Vented fuel-fired appliances Off Off Off

Flues without dampers; e.g. furnace, boiler, water heater, stove, etc. Seal (note 2) Leave as is Leave as isFurnace combustion air intake Seal

Air intake and exhaust vents for make-up or relief airNormal operating

modeClose (3) Close (3)

Floor drains, plumbing traps Fill Fill FillClothes dryer Off Off OffOther exhaust fans that are not part of the ventilation system Off Off OffVentilation system supply and exhaust fans that are part of the TVC

system

Normal operating

modeOff Off

Air intake and exhaust openings that are part of the TVC system No preparationVentilation system exhaust fans designed to operate intermittently

and any associated supply fansOff

Intake and exhaust openings for above No Preparation

Furnace blower when part of the TVC systemOperate in

ventilation mode

Greatest

depressurization

Greatest

depressurization

Furnace blower when not part of the TVC system OffGreatest

depressurization

Greatest

depressurization

Openings for future equipment SealAir conditioning Off OffCrawl space vents Close Close

Broken w indows and other short term openings Seal SealSub slab ventilation systems Off Off

Note 1: Doors that provide access to the combustion equipment, including basement doors when the equipment is in the basement, shall be tested both open and closed and left in the position that creates the most depresurization.

Combustion Equipment CSA F326 CGSB 51.71 CSA F300

Natural draft 5 5 5

Sidewall vented oil - without sealed supply air Note 1 5 5

Pellet stoves with exhaust fans and sealed vents Note 1 15 15

Sealed combustion No Limit 20 20

Power vented appliance Note 1 20 20

No combustion appliances 10 No Limit No Limit

Note 1: CSA F326 requires a 5 Pa limit for all combustion appliances unless there is a rated limit set by the manufacturer

or a certification agency.

Depressurization Limits (Pa)

DEPRESSURIZATION TEST SETUP AND LIMITS

House Setup

Note 2: Sealing is not required when testing for positive pressure.Note 3: If there is no damper, leave as is.

© Copyright HRAI Depressurization Testing of Residential Systems r 12 /19