Demo LHMI EXERCISES
Setting exercises for REF615 by using thelocal HMI
Use the navigation push buttons (up, down, left, right) to navigate in the menustructure. To change a setting, press the Enter button.
Change the following parameters
Check that the date and time in the relay are correct. You should find thesetting via the following menu: Configuration - Time - System timeIf time or date is wrong, you should give the correct values.
Change the short circuit protection 3I>>> settings (setting group 1). Youshould find the setting via the following menu:
Settings - Settings - Edit Group 1 - Current protection - 3I>>>(1)
Operation: OnNum of start phases: 2 out of 3Start value: 1.55 x InOperate delay time: 50 ms
Change the circuit breaker control settings. You should find the settings viathe following menu:Configuration - Control - I 0 CB
Select timeout: 10 000 msPulse length: 150 ms
ABB Oy
-
8/18/2019 Demo Box Guide 615
2/25
Demo LHMI EXERCISES
Change the current measurement settings. You should find the settings viathe following menu:Configuration - Measurements - 3I
Measurement mode: RMS
Demand interval: 15 min
Change the settings of the trip logic. You should find the settings via thefollowing menu:Configuration - Trip logic - Master Trip(1)
Trip pulse time: 160 msTrip output mode: Non-latched
Set the threshold voltage for the binary inputs.
Main Menu/Configuration/ I/O modules / Common settingsThreshold voltage: 18V
Return to main menu. Commit the settings when the relay asks.
Inject current to the relay by using the simulator. Verify the operation of thestart and trip leds and indications on the display. Use Clear button to clear theIndications, LEDs and Alarm LEDs after each trip. Read also the fault records.
Main Menu/Monitoring / Recorded data / Fault record 1....4
Tip: Clear button can be used as a shortcut for clearing. The first three-secondpress clears the indications. The second three-second press clears thealarm LEDs.
Open and close the circuit breaker by using the local HMI:
At first set the Local / Remote button to Local mode (L). The interlocking rulesin REF615 are programmable. In the demo relay the interlocking areprogrammed as follows:
Open the CB: Always possibleClose the CB: Earth-switch has to in open position
Try to open and close the circuit breaker by using Open (0) and Close (I)buttons in the relay HMI. Try also close the circuit breaker when the earth-switch is closed. First you have to close earth-switch by using simulator.
ABB Oy
-
8/18/2019 Demo Box Guide 615
3/25
Demo LHMI EXERCISES
ABB Oy
Arc protection simulat ion
Change the arc protection settings as follows:
Settings - Settings - Edit Group 1 – Other protection – ARC(1)
Operation: OnPhase start value: 0.50 x InGround start value: 0.25 x InOperation mode: Light + current
Simulate an arc fault as follows:1) Open the CB2) Set phase current (or Io) to maximum3) Press and hold ARC button4) Close CB
Note! You can simulate the light only mode by simply pressing ARC button. Inthat case, change the operation mode to “Light only”.
-
8/18/2019 Demo Box Guide 615
4/25
Demo WHMI EXERCISE
Web HMI exercises for REF615
1. Read the IP address of the relay
Read the IP address (rear port) of the relay. You can check the IP address forthe rear port via relay menu
Main menu / Configuration / Communication / Ethernet / Rear port(s)Default IP is 192.168.2.10
Check that Web HMI is active.Main menu / Configuration / HMI / Web HMI mode
- set mode to "Active"
Set Web HMI timeout to 60 min.Main menu / Configuration / HMI / Web HMI timeout
Return to main menu. Commit the settings when the relay asks.
If you changed the Web HMI mode, it comes valid only when you restart therelay. The restart can be done in:
Main menu / Configuration / General / Software reset
2. Set TCP/IP properties in PC and open Internet Explorer 7.0 browser
Use the following TCP/IP settings in PC when using rear port: “Use thefollowing IP address”.
Note: In the IP address the first three numbers must be the same as the IPaddress in the relay. The last number must be different!
Start the internet browser and write the IP address of the relay to the address
field. Login as ADMINISTRATOR.
ABB Oy
-
8/18/2019 Demo Box Guide 615
5/25
-
8/18/2019 Demo Box Guide 615
6/25
Demo WHMI EXERCISE
In this demo use the WHMI to
- Change protection settings- View alarm leds- View and clear Events- View Phasor diagrams (Adobe SVG Viewer need to be installed to PC)- Clear Indications and Alarm LEDs- Read disturbance recorder files
- Save the both files in the same folder on your computer, and open thedisturbance recorder files with a suitable program (e.g. Wavewin).- Note. You must trig the disturbance recorder first. You can alsomanually trig the disturbance recorder via WHMI.
ABB Oy
-
8/18/2019 Demo Box Guide 615
7/25
Demo WHMI EXERCISE
ABB Oy
Some screen shots from WEB HMI.
-
8/18/2019 Demo Box Guide 615
8/25
Demo EXERCISES WITH PCM600
Setting Exercise for REF615 with PCM600
This exercise shows the basic steps for getting started with PCM600.
Start PCM600. Select File - New Project. Fill in the project name anddescription. Click Create.
Drag and drop the objects Substation, Voltage level and Bay to PlantStructure. You can also rename the objects by using mouse right click. If you
do not see the Object Types in PCM600, select View - Object Types.
ABB Oy 1
-
8/18/2019 Demo Box Guide 615
9/25
Demo EXERCISES WITH PCM600
Drag and drop REF615 under a Bay. Select "Online configuration" and clicknext.
IED protocol shall be IEC 61850 and communication provider PCM600. ClickNext.
Select "Rear port (X1/LAN)". Check the rear port IP address of the relay andwrite it to IP address field.
ABB Oy 2
-
8/18/2019 Demo Box Guide 615
10/25
Demo EXERCISES WITH PCM600
Click scan to read the order code and functions from the relay.
ABB Oy 3
-
8/18/2019 Demo Box Guide 615
11/25
Demo EXERCISES WITH PCM600
Now it is possible to use different tools within PCM600. Right click the relay inthe tree and select the tool you want to use.
ABB Oy 4
-
8/18/2019 Demo Box Guide 615
12/25
Demo EXERCISES WITH PCM600
You should first select "Read from IED..." to read all data from the relay(configuration and parameter settings). Note that reading takes some minutes.Without "Read from IED...", you will have the default settings andconfiguration in PCM600 project (i.e. online configuration does not read thesetting parameters and Signal Matrix Tool connections).
Use Parameter setting tool for changing and viewing the relay settings. Use
"Read" button for reading the parameters. When you change some
parameters, use "Write" button to send the parameters to the relay. Youcan (for example) change some protection function setting parameters.
ABB Oy 5
-
8/18/2019 Demo Box Guide 615
13/25
Demo EXERCISES WITH PCM600
Use Signal monitoring tool for viewing the status of inputs, outputs, LEDs andmeasurements.
ABB Oy 6
-
8/18/2019 Demo Box Guide 615
14/25
Demo EXERCISES WITH PCM600
ABB Oy 7
In Signal monitoring the continuous reading is active when icon is green.
-
8/18/2019 Demo Box Guide 615
15/25
Demo DR EXERCISE
Disturbance recorder exercise for REF615
First check that the disturbance recorder operation is on. Other generalparameters you can set as follows by using Parameter Setting tool. You can
find the disturbance recorder general configuration settings from menuConfiguration - Disturbance recorder.
Note. If you do not see all the parameters as in the picture below, select View- Parameter layer - Advanced Parameters.
ABB Oy1
-
8/18/2019 Demo Box Guide 615
16/25
Demo DR EXERCISE
Then set the analog channels for example as follows. If you have a relaywithout voltage inputs, you can skip the settings of voltage analog channels(or check that operation is “off”)
ABB Oy2
-
8/18/2019 Demo Box Guide 615
17/25
Demo DR EXERCISE
The disturbance recorder has 64 digital inputs, of which 35 are connected asdefault in standard configuration F. All connected signals can be used eitherto trigger the disturbance recorder or to be recorded by the disturbancerecorder depending on the parameter settings.
The next picture shows how some of the signals in the disturbance recorderare connected. All the default connections in different standard configurations
are listed in the Application manual. The default connections can be changed(if needed) in Signal Matrix Tool.
ABB Oy3
-
8/18/2019 Demo Box Guide 615
18/25
Demo DR EXERCISE
Check that at least some of the digital channels will trigger the disturbancerecorder (for example ovecurrent protection trip signal).
ABB Oy4
-
8/18/2019 Demo Box Guide 615
19/25
-
8/18/2019 Demo Box Guide 615
20/25
-
8/18/2019 Demo Box Guide 615
21/25
Demo DR EXERCISE
* Now you can use WAVEWIN program to analyze the disturbance recorder
file. WAVEWIN is delivered with PCM600.
It is also possible to create a report about the disturbance recorder file. Selectone recording and right click with mouse. Select "Create Report".
Select "default" as a template and click OK.
ABB Oy7
-
8/18/2019 Demo Box Guide 615
22/25
Demo DR EXERCISE
ABB Oy8
-
8/18/2019 Demo Box Guide 615
23/25
DEMO SMT EXERCISE
Extra exercise: Signal Matrix Tool
Select the relay from the tree and right click with mouse. Open Signal Matrixtool.
As a first exercise, change the functionality of the alarm LEDs. By default theLEDs are connected as follows (in F std. conf).
Use Signal Matrix Tool to change the functionality of the LED 10 and 11.Program the LED 10 to be "Circuit breaker open position" and LED 11 to be"Circuit Breaker closed position". LEDs are available in "Binary Outputs"page.
ABB Oy
-
8/18/2019 Demo Box Guide 615
24/25
-
8/18/2019 Demo Box Guide 615
25/25
DEMO SMT EXERCISE
As the second exercise, connect binary input X120 - input 1 (input 1 insimulator) to change between setting group one and setting group two i.e.connect X120 - input 1 to "Protection: 0 ActSG" in SMT. This can be done inBinary Inputs page.
By default, X120 input 1 is used for blocking the over current instantaneousstage (PHIPTOC1, I>>>). Remove that default connection.
When you are ready with the connections, close the SMT tool, save andselect "Write to IED".
Note that you have to change also the setting parameter Configuration -System - SG follow input to "True".
Test by using the simulator (activate and de-activate input 1). You can monitorthe active setting group from the relay menu Settings - Setting group. When
the input 1 is active, the setting group in use should be 2. When the input 1 isnot active, the setting group in use should be one.