2526397 EN 1110 Defensor PH15/PH15A OPERATING INSTRUCTIONS Adiabatic Humidifiers

Transcript of Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter...

Page 1: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

2526

397

EN

111

0

Defensor PH15/PH15A

OPErAtiNg iNstructiONs

Adiabatic Humidifiers

Page 2: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator
Page 3: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

3

1 Introduction 41.1 To the very beginning 41.2 Notes on the operating instructions 4

2 For your safety 6

3 Product Overview 83.1 Unit versions 83.2 Unit construction 83.3 Operating panel 93.4 Identificationoftheunit 103.5 Functional description/Operating modes 103.6 Options 113.7 Accessories 123.8 Standard delivery 12

4 Commissioning 134.1 Unpackingtheunitandcheckingthescopeof

delivery 134.2 Transporting/storing the unit 134.3 Choose location 144.4 Connecting the water supply (PH15A only) 154.5 Putting the unit into operation 16

5 Operation 175.1 Filling the water tank (PH15 only) 175.2 Switchingtheunitonandoff 185.3 Menu overview 195.4 Unit settings (normal operating mode) 205.4.1 Setting the desired humidity value 205.4.2Settingthefanstep 215.4.3 Selecting the operating mode 225.4.4 Switchingthebuzzeronandoff 225.4.5 Calling timer level 235.5 Program operation 245.5.1 Calling the timer level 245.5.2 Activating/Deactivating the program mode 255.4.3 Setting the current time 255.5.4 Setting the starting points and the

operating programs 265.6 Locking/unlocking the keyboard 27

6 Maintenance 286.1 Maintenance intervals 286.2 Maintenance work 296.2.1 Disassembling the unit 296.2.2 Cleaning work 306.3 Notes on cleaning agent 326.4 Reassemblyoftheunit 336.5 Resettingthefilterchangingmessage 34

7 Fault elimination 357.1 Event messages 357.2 Warning messages 357.3 Error messages 367.4 What,if...? 377.5 Notesonfaultelimination 38

8 Taking out of service/Disposal 398.1 Takingoutofservice 398.2 Disposal/Recycling 39

9 Unitspecifications 40

10 Appendix 4110.1 Wiring diagram 4110.2 Spare parts list PH15 4210.3 Spare parts list PH15A 44

Contents

Page 4: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

4

LimitationThesubjectofthisoperatinginstructionsaretheairpurifiers/airhumidifiersDefensor PH15 and PH15A.Thevariousaccessoriesareonlydescribedinsofarasthisisnecessaryforproperoperationoftheequipment.Furtherinformationonaccessoriescanbeobtainedintherespective instructions.

This operating instructions are restricted to the installation, commissioning, operation, servic-ing and trouble shootingoftheairpurifier/airhumidifierDefensorPH15/PH15Aandismeantforwelltrainedpersonnelbeingsufficientlyqualifiedfortheirrespectivework.

Theoperatinginstructionsaresupplementedbyvariousseparateitemsofdocumentation(e.g.manualsforaccessories).Wherenecessary,appropriatecross-referencesaremadetothesepub-lications in the operating instructions.

1 Introduction

Wethankyouforhavingpurchasedanairpurifier/airhumidifierDefensor PH15 or PH15A.

Theairpurifier/airhumidifierDefensor PH15/PH15A incorporates the latest technical ad van ces andmeetsallrecognizedsafetystandards.Nevertheless,improperuseoftheDefensor PH15/PH15Amayresultindangertotheuserorthirdpartiesand/orimpairmentofmaterialassets.

Toensureasafe,proper,andeconomicaloperationoftheairpurifier/airhumidifierDefensor PH15/PH15A,pleaseobserveandcomplywithallinformationandsafetyinstructionscontainedinthepresentoperatinginstructionsaswellastheinstructionsgiveninthemanualsforthecompo-nentsusedinthehumidificationsystem.

Ifyouhavequestions,whicharenotorinsufficientlyansweredinthisdocumentation,pleasecon-tact your Defensor supplier. They will be glad to assist you.

1.2 Notes on the operating instructions

1.1 To the very beginning

Page 5: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

5

Symbols used in this manual

CAUTION!Thecatchword“CAUTION”designatesnotesinthisoperatinginstructionsthat,ifneglected,maycause damage and/or malfunction of the unit or other material assets.

WARNING!Thecatchword“WARNING”usedinconjunctionwiththegeneralcautionsymboldesignatessafetyanddangernotesinthisoperatinginstructionsthat,ifneglected,maycausetoinjury to persons.

DANGER!Thecatchword“DANGER””usedinconjunctionwiththegeneralcautionsymboldesignatessafetyanddangernotesinthisoperatinginstructionsthat,ifneglected,mayleadtosevere injury or even death of persons.

SafekeepingPleasesafeguardthisoperatinginstructionsinasafeplace,whereitcanbeimmediatelyac-cessed.Iftheequipmentchangeshands,thedocumentationshouldbepassedontothenewoperator.

Ifthedocumentationgetsmislaid,pleasecontactyourDefensor supplier.

Language versionsThis operating instructions are available in various languages. Please contact your Defensor sup-plierforinformation.

Copyright protectionThepresentoperatinginstructionsareprotectedundertheCopyrightAct.Passing-onandrepro-ductionofthemanual(orpartthereof)aswellasexploitationandcommunicationofthecontentsareprohibitedwithoutwrittenpermissionbythemanufacturer.Violationofcopyrighttermsissub-jecttolegalprosecutionandarisesliabilityforindemnification.

Themanufacturerreservestherighttofullyexploitcommercialpatentrights.

Page 6: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

6

2 For your safety

GeneralEvery person working with the Defensor PH15/PH15A must have read and understood the Oper-atinginstructionsbeforecarryingoutanywork.KnowingandunderstandingthecontentsoftheOperatinginstructionsisabasicrequirementforprotectingthepersonnelagainstanykindofdanger,topreventfaultyoperation,andtooperatetheunitsafelyandcorrectly.

All ideograms, signs and markings applied to the unit must be observed and kept in readable state.

QualificationofpersonnelAll actions described in the present Operating instructions (installation, operation, maintenance, etc.) must be carried out only by welltrainedandsufficientlyqualifiedpersonnelauthorisedby the owner.ForsafetyandwarrantyreasonsanyactionbeyondthescopeofthismanualsmustbecarriedoutonlybyqualifiedpersonnelauthorisedbyyourDefensor supplier.

It is assumed that all persons working with the DefensorPH15/PH15Aarefamiliarandcomplywiththeappropriateregulationsonworksafetyandthepreventionofaccidents.

This unit may not be used by persons (including children) with reduced physical, sensory or men-talabilitiesorpersonswithlackingexperienceand/orknowledge,unlesstheyaresupervisedbyapersonresponsiblefortheirsafetyortheyreceivedinstructionsonhowtooperatetheunit.Children must be supervised to make sure that they do not play with unit.

Intended useTheairpurifier/airhumidifierDefensorPH15/PH15Aisintendedexclusivelyforairpurificationandairhumidificationwithinthespecifiedoperatingconditions (see chapter 9 “Product specifications”).Anyothertypeofapplicationwithouttheexpresswrittenconsentofthemanu-facturerisconsideredasnotconformingwiththeintendedpurposeandmayleadtotheDefensor PH15/PH15A becoming dangerous.Operationoftheequipmentintheintendedmannerrequiresthat all the information in these instructions are observed (in particular the safety instructions).

Page 7: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

7

Danger that may arise from the unit

DANGER! Danger of electric hazard!The Defensor PH15/PH15A is mains powered. One may get in touch with live parts when the unit is open. Touching live parts may cause severe injury or danger to life.Prevention: BeforecarryingoutanyworksettheDefensorPH15/PH15Aoutofoperation(switchofftheunit,disconnectitfromthemains,closewatersupply)andsecuretheunitagainstinadvert-entpower-up.

WARNING!Poorlymaintainedhumidifierscanendangeryourhealth. If the Defensor PH15/PH15A is insufficientlymaintainedharmfulgermscanbuildupinthewaterandthefiltersancanaf-fect the ambient air.Prevention: TheDefensorPH15/PH15Ahastobecleanedinregularintervalsaccordingtochap-ter 6 “Maintenance”. The cleaning work has to be carried out correctly and the evaporator mat as wellasthefiltershavetobereplacedafterthespecifiedlifetime.

Handling the mains cableHandlethemainscablewithcare:keepitawayfromsharpedgesanddonotjamorstrainit.

Never remove the mains plug by pulling the mains cable. Make sure your hands are absolutely dry whenpullingtheplugoutofthesocket.

Lay out the mains cable so that it does not become a stumbling trap.

Connectmainscableonlytoamainssocketwithprotectionearth.Anyextensioncableusedmustbeequippedwithaprotectionearthtoo.

Behaviour in case of dangerIfitissuspectedthatsafe operation is no longer possible, then the Defensor PH15/PH15A should immediately be disconnected from the mains (disconnect mains connector) and se-cured against accidental power-up.Thiscanbethecaseunderthefollowingcircumstances:– iftheDefensor PH15/PH15A is damaged– iftheDefensor PH15/PH15A is no longer operating correctly– ifconnectionsand/orpipingarenotsealed– ifthemainscableisdamaged

All persons working with the Defensor PH15/PH15A must report any alterations to the unit that mayaffectsafetytotheownerwithoutdelay.

ProhibitedmodificationstotheunitNomodificationsmustbeundertaken on the DefensorPH15/PH15Awithouttheexpresswrit-tenconsentofthemanufacturer.

Forthereplacementofdefectivecomponentsuseexclusivelyoriginal accessories and spare partsavailablefromyourDefensor supplier.

Page 8: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

8

3 Product Overview

3.1 Unit versions

The DefensorPH15/PH15Aairpurifier/airhumidifierisavailableintwobasicversions:

– PH15: version with integrated water tank

– PH15A: versionwithinletvalvefortheconnectiontothedrinkingwatersystem

Bothversionsareequippedasstandardwithacoarsedustfilterandevaporatormattooperatetheunitasahumidifier(wintertimeoperation).

1 Air inlet lattice 2 Coarsefilter 3 Radialfan 4 Centrifuge 5 Mobile base with cover 6 Flock-coatedevaporatormatoractivated

carbon evaporator mat 7 Droplet trap

3.2 Unit construction

PH15

8 CoarsedustfilterorQuattrofilter 9 Carriage with water tank 10 Operating panel with display 11 Type plate 12 3 pole mains cable 13 Silver ionisation electrodes (option) 14 Level switch15 Safetyswitch

1

2

3

4

5

6

7

8

10

9

13

119

14

12

15

Page 9: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

9

1 Air inlet lattice 2 Coarsefilter 3 Radialfan 4 Centrifuge 5 Mobile base with cover 6 Flock-coatedevaporatormatoractivated

carbon evaporator mat 7 Droplet trap 8 CoarsedustfilterorQuattrofilter

9 Carriage 10 Operating panel 11 Type plate 12 3 pole mains cable 13 Silver ionisation electrodes (option) 14 Level switch15 Safetyswitch16 Waterfilter 17 Inlet valve

PH15A

3.3 Operating panel

1 LC display 2 <ESC> key 3 Arrow keys

4 Error indicator 5 <On/Off>key(On/Off) 6 <Enter> key

1

2

3 16174

5

6

7

8

10

9

13

119

14

15

12

PH15

1

2

3

4

5

6

Page 10: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

10

Functional descriptionTheradialfan(1)takesintheairfromthetopviathecoarsefilter(2).Afterpassingthroughtheevaporatormat(3)(ortheactivatedcarbonevaporatormat)andthecoarsedustfilter(4)(ortheQuattrofilter)theairisblownoutviatheoutletlatticeonbothsidesoftheunit.

The unit continuously measures the air humidity in the room with the integrated humidity sensor andcomparesitwiththesetreferencehumidityvalue.Iftheactualvalue(e.g.40%rh)isbelowthereferencevalue(e.g.45%rh)thecentrifuge(5)startsandprojectsfinedropstowardstheevaporator mat. The air passing through the evaporator mat absorbs the humidity.Thecoarsedustfilterretainsdustparticlesupto100µm.IftheDefensor PH15/PH15A is equippedwithaQuattrofilteritcanretaindustparticlesupto0.1µm.InadditiontheactivatedcharcoallayerintheQuattrofilterremovesunpleasantodour.

The water level in the base tub is monitored by the level regulating valve in the water tank (Defen-sor PH15) or by the level controlled inlet valve (Defensor PH15A).

3.5 Functional description/Operating modes

3.4 Identificationoftheunit

Theidentificationoftheunitisfoundonthetypeplate(forthelocationofthetypeplateseeunitoverview):

Type designation Serial number Month/Year

Unit voltage

Admissible water supply pressure (PH15A only)

Fieldwithcertificationsymbols

Power consumption

Walter Meier (Climate International) Ltd. 8808 PfäffikonType: PH15A Serial: XXXXXXX 07.11Voltage: 220...240VAC / 50...60 Hz Power: max. 72 WWater pressure: 0.5...6 bar

Made in Switzerland

PH15

2

1

3

5

6

4

Page 11: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

11

Operating modes The DefensorPH15/PH15Acanbeoperatedinthefollowingoperatingmodes:

– OperationasairhumidifierInthehumidifiermodetheventilatorandthecentrifugearerunningonly,iftheactualhumidityvalueisbelowthesetreferencevalue.Note:iftheactualhumidityvalueremainsbelowthereferencevalueforaprolongedperiodoftime,thefanmustbeswitchedtothenexthighestlevel.

– OperationasairpurifierwithhumidificationInthisoperatingmodethefanisrunningcontinuously.Thecentrifugeisonlyswitchedoniftheactualhumidityvalueisbelowthesetreferencevalue.

– OperationasairpurifierwithouthumidificationInthisoperatingmodethefanisrunningcontinuously.Thecentrifugeremainsswitchedoff.

3.6 Options

Defensor PH15 Defensor PH15A

Silver ionisationAssemblykittoequiptheunitwithsilverionisationelectrodesto degerminate the water in the base tub with silver ions.Note:Thesilverionisationkitmustbeinstalledandconfig-uredonlybyaservicetechnicianofyourDefensor repre-sentative.

• •

Radio humidity sensorThe radio humidity sensorcanbeusedinsteadoftheinte-grated humidity sensor.Themaximumrangeoftheradio humidity sensor in an open room is 25 mNote: the radio humidity sensor as well as the receiver board mustbeinstalledandconfiguredonlybyaservicetechnicianofyourDefensor representative.

• •

Leakage sensorAssembly kit to equip theDefensor PH15/PH15A with a leakagesensor.If theleakagesensordetectsaleakage,the inlet valve (PH15A only) is closed and error message is triggered.Note:TheleakagesensormustbeinstalledandconfiguredonlybyaservicetechnicianofyourDefensor representa-tive.

• •

Page 12: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

12

Theairpurifier/airhumidifierDefensorPH15/PH15Aisdeliveredinacardboardbox(B:816mmxH:684mmT:456mm,transportweight:28kg),readyforuse.Thestandard delivery includes:– Airpurifier/AirhumidifierDefensor PH15 or PH15A,equippedwiththe“Winter”filterset

(coarsedustfilter,flock-coatedevaporatormat)andtheoptionsasordered.– Cleaning brush– Filling hoseapprox.1,2m(PH15only)– Operating instructions (this document)

The ordered accessories with operating instructions according chapter 3.6 are packed separately.

3.7 Accessories

Defensor PH15 Defensor PH15A

Filter set “Winter”Filtersetfortheoperationoftheunitduringwinterseason.Thesetconsistof:–Coarsefilter(airintake)–Flock-coatedevaporatormat–Coarsedustfilter

• •

Filter set “Summer”Filtersetfortheoperationoftheunitduringsummerseason.Thesetconsistof:–Coarsefilter(airintake)– Activated carbon evaporator mat–Quattrofilter

• •

Filter valve “Z261”Filtervalvetouseasashut-offvalveinthewatersupplyline (PH15A only)

3.8 Standard delivery

Page 13: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

13

4.1 Unpacking the unit and checking the scope of delivery

Unpacking the unitOpenthepackingandremovetheunitandtheaccessories.Checkthedeliveryforcompleteness(standard delivery, see chapter 3.8). Please contact your Defensor supplier in case something is lacking, they will be glad to send you the missing part without delay.

Pleasechecktheequipmentfordamage.PleasereportanydamagetoyourDefensor supplier andtothecarriers,asrequired.

PackagingTheoriginalpackagingoftheDefensorPH15/PH15Awasdesignedforoptimumsafetyduringtransportation. Please preserve the original packing material in case you once have to return the unitforsomereason.

Incaseyouwishtodisposeofthepackaging,observethelocalregulationsonwastedisposal.Neverdisposeofthepackagingtotheenvironment.

4 Commissioning

4.2 Transporting/storing the unit

TransportThe DefensorPH15/PH15Aisequippedwithbuilt-inrollersforeffortlessdisplacement.Ifyouhavetolifttheunitfordisplacementorrelocationaskanotherpersonforassistance(weightoftheempty unit: 25 kg).

Important!Topreventthewaterfromrunningoutmakesurethewatertankandthebasetubareemptybeforemovingtheunit.

StoringStoretheunitinaprotectedareameetingthefollowingrequirements:

– room temperature: 1 ... 40 °C– roomhumidity:10...75%rh

Page 14: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

14

4.3 Choose location

PleaseobservethefollowingnotesforthecorrectpositioningoftheDefensor PH15/PH15A:

– Placetheunitonasolidhorizontalsurface,ifpossiblefree-standingandfreelyaccessible(ob-serve minimal distances).

– A mains socket should be located close to the unit.

– Toensuretheentirevolumeofairisfullyrecirculated,donotplacetheunitinrecessedcom-partments, closed corridors, behind curtains, etc.

– Donotplaceanyobjectsontheunit(performancereduction).

– Makesuretheairflowisnotdirectedtowardsobstacles(pillars,furniture,etc.)orcoldouterwalls(riskofcondensation).

– Continuousdirectsunlightisharmfulfortheunitandcanaffectthecorrectfunctionoftheinte-gratedhumiditysensor.Thereforedonotexposetheunittocontinuousdirectsunlight.

– The unit must not be installed in hazardous loca tions and in rooms where water splashes may occur.

min. 100 mm

min. 150 mm

min

. 150

mm

min. 400 mm

PH15

Page 15: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

15

Afterlocatingtheunit:

• Completelyunwindthemainscable(atthepointofthedeliverythemainscableiswindedupintheunit)andtakeitoutoftheunitasshownbelow.

4.4 Connecting the water supply (PH15A only)

Thewatersupplyhastobeconnectedtotheunitbyaqualifiedspecialistaccordingtotheillustra-tion below. The installation data has to be maintained.Important! The local regulationsregardingtheconnectionofunitstodrinkingwatersystemsmust be observed.

Drinking water without additives:– Admissible water pressure: 0.5...6.0 bar– Admissible water temperature: 5...40 °C

Filter valve (accessory “Z261”)

Water pipe with G 3/4" connector

Page 16: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

16

4.5 Putting the unit into operation

ProceedasfollowstoputtheDefensor PH15/PH15A into operation:• PH15:fillthewatertank(seechapter5.1)

PH15A:opentheshut-offvalveinthewatersupplyline.• Connectunittothemains.

CAUTION!Makesuretherequiredsupplyvoltage(seetypeplate)matchesthelocalmainsvoltage,oth-erwisedonotconnecttheDefensorPH15/PH15Atothemains!

CAUTION!TheDefensorPH15/PH15Amustbeconnected only to grounded mains. Never connect the unit to an outlet without protective earthing.

The DefensorPH15/PH15Aisnowreadyforoperation.Thenextchapterprovidesdetailedinfor-mationontheoperationoftheunit.

Page 17: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

17

2.

1. 3.

1.

3.

2.

4.

3.

4.

2.

1.

5 Operation

5.1 Filling the water tank (PH15 only)

3

1 2

4

Place an absorbent cloth below the unit.

Drinking water without additives

To maintain the monitor-ingoftheunitduringfilling,neitherswitchoffthe unit nor disconnect it fromthemains!

Important! Screw on tank cap until it comes to a stop!

Afterreinstallingthewatertankwaitbytheunituntilthefillingsoundstops.

Ifthelockisnotreleased(step3),thecarriageremainsfixedtotheunitinopenposition.

Page 18: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

18

5.2 Switching the unit on and off

Switching the unit on• Pressthe<On/Off> key.

The unit loads the settings that were active when the device was shut down last. Upon completion the operating displayappears.ThelookoftheoperatingdisplaydependswhethertheDefensorPH15/PH15A is operated in “Normal operating mode” or in “Program mode”.

Normal operating mode Program mode

Status humidity sensor (active=^)

Actual humidity value in %rhNote: The actual humidity value is always dis-played(eveninairpurificationmode)andupdatedevery 5 seconds.

Operating modeH:airhumidificationP:Airpurification(withouthumidification)C:Combinedmode(purification/humdification)

Fan step1, 2, 3, 4 or A1, A2, A3, A4

^Act 38%rH HA3

Set 45%rH

^Act 38%rH HA3

Fr 12:28

Day of the weekFormat: “Mo”, “Tu”, “We”, “Th”, “Fr”, “Sa”, “Su”(appears only in program mode)

HourFormat “hh:mm”(appears only in program mode)

Set humidity setpoint

Thefanstartsinalloperatingmodeswithadelayofapprox.1minute.Untilthefanstartstheoperat-ingmodeandthefanstepareblinking.

If,afterswitchingontheunitawarningorerrormessageisdisplayed,pleaseobservethenotesinchapter 7.

Switching the unit off• Pressthe<On/Off> key.

The currently active settings will be stored upon shutdown.

Page 19: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

19

Timer

On

Time

Mo 12:00

Monday 1

18:00 45%rH HA3

Monday 2

--:-- 45%rH HA0

Sunday 1

--:-- 45%rH HA0

Sunday 2

22:00 45%rH HA0

^Act 38%rH HA3

Set 45%rH

Set value

42%rH

Fan power

Auto1

Operating mode

Humidify

Buzzer

On

Timer

Adjust

5.3 Menu overview

ThefollowingdiagramshowsthemenuoverviewoftheDefensorPH15/PH15A.Afterswitchingon,the unit is in the user level.

User level Timer levelIn the user level you can define the set-tings for the normal operating mode (see chapter 5.4).

In the timer level you can defineandactivatethe program mode (see chapter 5.5).

Page 20: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

20

5.4 Unit settings (normal operating mode)

5.4.1 Setting the desired humidity value

modify

confirm

cancel

Note:Thereferencehumidityvaluecanbemodifiedonlyifprogrammodeisdeactivated(seechap-ter 5.5).

Settingrange: 30...90%rH

Factorysetting: 45%rH

Notesonsetting: Theoptimumreferencevaluedependsonvariousfactors.Forapartmentswerecommendavalueof40–45%rH.

Note:After initialcommissioningorreplacementof thevaporizermat thehumidificationperform-anceof theDefensorPH15/PH15Awillbeslightly reducedbecause theevaporatormat takesafewdaystobecomefullysaturatedwithwater.Maximumperformanceisavailableafteroneweek,approximately.Furthermore,thehumidificationperformancedependsontheambienttemperature.

30...90%rH

Standard operating display

(see chapter 5.4.2)

Set value

45%rHSet value

New Value

Set value

Old Value

Set value

45%rH

Page 21: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

21

Note:Thefanstepcanbemodifiedonlyifprogrammodeisdeactivated(seechapter5.5).

Available settings: 1, 2, 3, 4 or Auto1, Auto2, Auto3, Auto4

Operating mode Fan step Behaviour

“H”(Humidification) Auto 1 runsfixedwithfanstep1

Auto 2 automatic switching between fansteps1..2

Auto 3 automatic switching between fansteps1..3

Auto 4 automatic switching between fansteps1..4

“P”(Purification)“C” (Combined mode)

1 runsfixedwithfanstep1

2 runsfixedwithfanstep2

3 runsfixedwithfanstep3

4 runsfixedwithfanstep4

Factory setting: 1

Notesonsetting: Thefansteptobeselecteddependsontheoperatingmodeandthesizeoftheroom.Thetablebelowismeanttoassistyouinfindingtheoptimumfanstep.

Fan step max.roomvolumeinm3for purification(withouthumidification)

max.roomvolumeinm3 forhumidification

Air changes per hour

1 2 3 4

1 155 77 52 39 155

2 195 97 65 49 195

3 280 140 93 70 280

4 340 170 113 85 340

The following recirculation cycles per hour are recommended for airpuri-fication:

– Normal load: 1 – 2 – heavily polluted air (e.g. pollen, smoke, etc.): 3 – 4

5.4.2 Setting the fan step

Fan power

Auto1Fan power

New Value

Fan power

Old Value

Fan power

Auto1

(see chapter 5.4.1)

(see chapter 5.4.3)

modify

confirm

cancel1...4 or

Auto1...Auto4

Page 22: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

22

Buzzer

OffBuzzer

New Value

Buzzer

Old Value

Buzzer

Off

5.4.4 Switching the buzzer on and off

(see chapter 5.4.3)

(see chapter 5.4.5)

modify

confirm

cancelOnorOff

Availablesettings: On(buzzeron)orOff(buzzeroff)

Factorysetting: Off

Notesonsetting: Ifthebuzzerisonanacousticsignalistriggeredincaseofamalfunctionoran irregularity during operation.

Operating mode

HumidifyOperating mode

New Value

Operating mode

Old Value

Operating mode

Humidify

5.4.3 Selecting the operating mode

(see chapter 5.4.2)

(see chapter 5.4.4)

modify

confirm

cancelHumidify,Purify,

Combi mode

Note: The operating modecanbemodifiedonlyifprogrammodeisdeactivated(seechapter5.5).

Availablesettings: Humidify(airhumidification),Purify(airpurificationwithouthumidification)andCombimode(airpurificationwithhumidification)

Factorysetting: Humidify

Notesonsetting: Theselectionoftheoperating modedependsonwhethertheDefensorPH15/PH15Ashallbeoperatedashumidifier,aspurifierwithouthumidificationoraspurifierwithhumidification.Iftheunitshallbeoperatedaspurifierwithouthumidificationthebasetubandthewatertankshouldbeemptied.

Page 23: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

23

Timer

On

Timer

Adjust

5.4.5 Calling timer level

(see chapter 5.4.4)

(see chapter 5.4.6)

Calling timer level

Leaving timer level

Fordetailedinformationregardingthesettingsinthetimerlevelseechapter5.5“programopera-tion”.

Page 24: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

24

5.5 Program operation

TheoperationoftheDefensorPH15/PH15Acanbecontrolledviacustomisableoperatingprograms.Theseprogramsallowtooperatetheunitatapresettimewiththerequestedoperatingmodeandfanstep.ThisgreatlyfacilitatestheadaptionoftheDefensorPH15/PH15Atoyourparticularrequire-ments (e.g. adjusted to the business hours and/or working time).

Everyprogramconsistsofastarting point(dayoftheweekandhour),areference humidity value, the operating mode and the desired fan step. Up to 2 starting points with individual programs may be set up per day. Inprogrammodethecurrentprogramremainsactiveuntilthefollowingprogramstarts(onthesameor on any other day).

Examplediagram:

Theprogramsettingsandtheactivationoftheprogrammodetakesplaceinthe“Timerlevel”.

5.5.1 Calling the timer level

Within the user level call the timer level (see chapter 5.4.5). In the timer level:– you can activate and deactivate the program mode (see chapter 5.5.2)– youcansetthedayoftheweekandthehour(seechapter5.5.3)– youcandefinetheindividualoperatingprogramswiththeirstartingpoints(seechapter5.5.4)

Note:Ifnokeyispressedinthetimerlevelforacertaintime,theunitautomaticallyreturnstostand-ard operation.

Monday 1 ––:–– 45%rH HA0

Monday 2 ––:–– 45%rH HA0

Tuesday 1 06:00 45%rH HA3

Tuesday 2 ––:–– 45%rH HA0

Wednesday 1 ––:–– 45%rH HA0

Wednesday 2 18:00 40%rH P1

Thursday 1 ––:–– 45%rH HA0

Thursday 2 ––:–– 45%rH HA0

Friday 1 06:00 45%rH HA1

Friday 2 ––:–– 45%rH HA0

Saturday 1 ––:–– 45%rH HA0

Saturday 2 12:00 45%rH HA0

Sunday 1 ––:–– 45%rH HA0

Sunday 2 ––:–– 45%rH HA0

Saturday 2 Tuesday 1 Wednesday 2 Friday 1 Saturday 2

OffRef.hum.value45%rH

HumidificationFan step 3

Ref.hum.value40%rHPurificationFan step 1

Ref.value45%rHHumidification

Fan step 1Off

Monday Tuesday Wednesday Thursday Friday Saturday Sunday

00:0

0

12:0

0

00:0

0

12:0

0

00:0

0

12:0

0

00:0

0

12:0

0

00:0

0

12:0

0

00:0

0

12:0

0

00:0

0

12:0

0

Page 25: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

25

5.5.2 Activating/Deactivating the program mode

Availablesettings: On(programmodeactivated)orOff(programmodedeactivated)

Factorysetting: Off

Notesonsetting: IfprogrammodeisactivatedtheDefensorPH15/PH15Aoperatestime-controlledwiththeoperatingprograms(seechapter4.3.4).Ifnoprogramsorstartingpointsaredefinedtheunitoperateswiththesettingsofthenormaloperatingmode.

Timer

OnTimer

New Value

Timer

Old Value

Timer

On

(see chapter 5.5.4)

modify

confirm

(see chapter 5.5.3)cancel

On/Off

5.4.3 Setting the current time

(see chapter 5.5.2)

(see chapter 5.5.4)

modify

confirm

cancel

Availablesettings: Dayoftheweek(Mo,Tu,We,Th,Fr,Sa,Su) Hour (Format: hh) Minute (Format: mm)

Factorysetting: ---

Notesonsetting: Thecurrentdayoftheweekandthecurrenttimeserveasbasisfortheprogrammode.Ifthesesettingsarenotsetcorrectlytheprogramtimingiswrong.

Aftercallingthemodificationmodesetthecurrentdayoftheweek,thecurrenthourandthecurrentminute.Confirmeachsettingwiththe<Enter> key.

Note:IftheDefensorPH15/PH15Ahaslostthetimesettingsduetopowerfailure,thetimeindication(--:--)intheoperatingdisplayflashes.

Time

Mo 12:00Time

New Value

Time

Old Value

Time

Mo 12:00

see notes on setting

Page 26: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

26

Monday 1

--.-- 45%rH HA0Monday 1

New Value

Monday 1

Old Value

Monday 1

--.-- 45%rH HA0

Monday 2

--.-- 45%rH HA0

Sunday 2

--.-- 45%rH HA0

5.5.4 Setting the starting points and the operating programs

Firstselectthedesireddayoftheweekorthestartingpoint,respectively(Monday1,Monday2.....Sunday1,Sunday2),thendefinetheoperationsettingswhichshouldbecomeactiveatthestartingpoint.

Available settings: Hours (Format: hh) Minutes (Format: mm) Referencehumidityvaluein%rH Operatingmode(“H”:forhumidification,“P”:forpurification(withouthumidi-

fication)and“C”:forcombinedmode(purificationandhumidification)) Fan step (0, 1, 2, 3, 4)

Factorysetting: “––:––45%rHHA0”

Notesonsetting: Aftercalling themodificationmodeset thehour, theminute, thereferencehumidityvalue,theoperatingmodeandthefanstepfortheselectedstartingpoint.Confirmeachsettingwiththe<Enter> key.

To deactivate a starting point (display: – – : – –) press both arrow keys simul-taneouslywhenthehourfieldflashes.Confirmwiththe<Enter> key. Repeat thisprocedurewiththeminutefield.

Theswitchofftheunitatacertaintimeselectfanstep“0”.

(see chapter 5.5.3)

(see chapter 5.5.2)

modify

confirm

cancelsee notes on setting

Page 27: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

27

5.6 Locking/unlocking the keyboard

ThekeyboardoftheDefensorPH15/PH15Acanbelockedtopreventunauthorizedaccesstothestored settings.

• Tolockthekeyboard,press<ESC>keyuntil(approx.4seconds)theadjacent message appears in the display. The keyboard is locked now. Each time you press any key the adjacent message appears again.

• Tounlockthekeyboard,press<ESC>keyuntil(approx.4seconds)the message “Key lock” disappears and the operating display is shown.

Key lock

Set 50%rH

Act 30%rH HA3

Set 50%rH

Page 28: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

28

6 Maintenance

6.1 Maintenance intervals

The DefensorPH15/PH15Acanonlyprovidefullhumidificationandpurificationperformanceiftheunit is regularly cleaned and the wearing parts are replaced. The maintenance intervals mostly dependontheloadoftheambientair,thewaterqualityandtheoperatingtime.

Pleaseconsidertheintervalsforcleaningandreplacingtheindividualcomponentsinthetablebelowasapproximatevalues.Iftheroomairisheavilycontaminatedthefiltersmustbecleaned/replacedmoreoften.Ifthewaterisveryhardthepartsincontactwithwatermustbecleanedmoreoften.

Month1 2 3 4 5 6 7 8 9 10 11 12

Note:Ifyourunitisequippedwithsilverionisationelectrodesandiftheyareworn,slimewillaccu-mulateinthebasetubandonthecentrifuge.Inthiscasereplacethesilverionisationelectrodes.

Warning 6

Filter change

Page 29: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

29

6.2 Maintenance work

6.2.1 Disassembling the unit

1 2

3 4

5 6

Press in the lock latches on bothsidesoftheunit.

Disconnect unit fromthemains

Place an absorbent cloth below the unit.

3.

4.

2.

1.

Page 30: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

30

Unit component What to clean and how to clean

Centrifuge Droplet trapMat holderBase tub coverBase tub

• Washpartswithalukewarmsoapsolutionandrinsewellwithtapwater.Additionallycleanthecentrifugeinsidewith the brush supplied.

• Occasionally removescalecoatingwithahouseholddecalcifyagent(observe safety notes in chapter 6.6). Finally rinse the parts well with tap water.

Water tank • Flushwater tankwitha lukewarmsoapsolutionandrinse well with tap water.

• Washscrewcapwitha lukewarmsoap solutionandrinse well with tap water.Occasionally remove scale coating with a household decalcifyagent(observe safety notes in chapter 6.3). Finally rinse the screw cap well with tap water.

Flock-coated evaporator mat (activated carbon evaporator mat)

• Rinsetheevaporatormatthoroughlywithlukewarmwater without any additives.

Note:Assoonasthefilterreplacingmessageappearsin the display (see error messages in chapter 7) replace theevaporatormattogetherwiththefilters.

Air intake and air outlet lattices • Cleantheairintakeandairoutletlatticesonbothsideswith a vacuum cleaner.

6.2.2 Cleaning work

Page 31: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

31

Unit component What to clean and how to clean

CoarsefilterCoarsedustfilter(orQuattrofilter,respectively

• Cleancoarsefilterontheairinletsideandthecoarsedustfilter(ortheQuattrofilter)ontheinnersidewithavacuum cleaner (lowest power step). Note:Assoonasthefilterreplacingmessageappearsin the display (see error messages in chapter 7) replace coarsefilter,coarsedustfilter(Quattrofilter)togetherwith the evaporator mat.

CAUTION! Makesurethefiltersdonotgetwet.Wetfiltersmustbedrybeforereinstalling.

Waterfilter(PH15Aonly) • Cleanwaterfilterwithabrush,thenrinsefilterwellwithtap water.

Level switchSafety switch

• Carefullywipe the level switchand thesafetyswitchwith a damp cloth.

Page 32: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

32

6.3 Notes on cleaning agent

Only use cleaning agents stated in the table above.Theuseofdisinfectantsisonlypermittediftheydonotleaveanytoxicresidues.Inanycasethepartsmustbethoroughlyrinsedwithwateraftercleaning.

DANGER!Householddecalcifyagentattacksthemucousmembranesandtheskin.Protectthehands,eyesandrespiratorytractsthereforefromcontactwiththeagentanditsvapour(weargloves,gogglesand work in a well ventilated room or outside).

CAUTION!Do not use any solvents, aromatised or halogenised hydrocarbons or other aggressive substances, they may damage the unit components.

Theinformationandinstructionsregardingcleaningagentsaretobeunconditionallyobservedandimplemented.Inparticular:Informationrelatingtotheprotectionofpersonnel,environmentalcon-servation and restrictions regarding usage.

Page 33: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

33

1 2

3 4

5

1.

3.

2.

4. 6

6.4 Reassembly of the unit

CAUTION!BeforereassemblingtheDefensorPH15checkallcomponentsforpossibledamage.Donotreusedamagedpartsbutreplacethembeforereassemblingtheunit

Reassembletheunitasfollows:

Thecentrifugemustcatchinthecentering!

Afterpositioningoftheupperpartoftheunitclosethelocklatchesonbothsidesoftheunit

Lower carefully

Page 34: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

34

6.5 Resettingthefilterchangingmessage

Afterthereplacementofthefiltersandtheevaporatormatthefilterchangingmessagecanberesetasfollows:

1. Switchontheunit(thefilterchangingmessageappears).

2. Press the <ESC> and <Enter> keys simultaneously until the op-posite message appears.

3. Press the <Enter>keytoresetthefilterchangingmessageandthe interval counter. The standard operating display appears.Note: By pressing the <ESC> key the reset procedure can be cancelledwithoutaction.Thefilterchangingmessageisthendis-played again.

Warning 6

Filter change

Filter change

ESC OK

Page 35: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

35

7 Fault elimination

Display Description

Radio sensor K1

Install.? ESC/E

Cause: Ifanewbatteryisinsertedintotheradio humidity sensor (op-tion)andtheradiochanneloftheradio humidity sensor does notcorrespond to theactivechannelof theDefensor PH15/PH15Aabeepsoundsbriefly(ifthebuzzerisactivated)andanew radio channel (e.g. K1) will be proposed.

Action: Press the <Enter>keyifyouwanttoconfirmthesuggestedchannel. The Defensor PH15/PH15A switches to the new chan-nel and returns to the standard operating display.

Press the <ESC> key if you want to reject the suggestedchannel. The Defensor PH15/PH15A returns to the standard operating display and uses the old signal source.

Radio sensor K1

Test

Cause: Ifanewbatteryisinsertedintotheradio humidity sensor (op-tion)andtheradiochanneloftheradio humidity sensor does correspondtotheactivechanneloftheDefensor PH15/PH15A abeepsoundsbriefly(ifthebuzzerisactivated)andtheunitconfirmsthecorrectchannel.

Action: To reset the message and to return to the standard operating display press the <Enter> or the <ESC> key.

7.1 Event messages

7.2 Warning messages

Display green LED Buzzer Error relay Resetting

Warning 6

Filter changeWarning message is alter-nating with the standard operating display.

lights ––– activated see chapter 6.5.

Cause: Maximumlifetimeofthefiltersetexpired.Action/Remedy:Replacefilterset(seechapter6“Maintenance”),thenresetwarningmessage.

Warning 7

No waterWarning message is dis-played until the water level in the base tub is ok. again.

lights ––– activated Automatic resetting as soon as the water level in the base tub is at normal level again.

Note: This message is displayed only on the Defensor PH15Cause: The water level in the base tub is too low, level switch has triggered.Action/Remedy:Check/refillwatertank.

Warning 8

Battery radio Warning message is alter-nating with the standard operating display.

lights beepsbrieflyevery 30 min-utes

activated Automaticresettingafterreplacement of the bat-tery.

Cause: Battery in radio humidity sensor (option) is empty.Action/Remedy:Replacebatteryof the radio humidity sensor (seeseparate instructionsof radio humidity

sensor).

Page 36: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

36

7.3 Error messages

Display green LED Buzzer Error relay Resetting

Error 1

Cover openError message is displayed until the carriage is inserted correctly and locked.

flashes ––– activated Automatic resetting as soon as the carriage is inserted correctly and locked.

Cause: Carriage not inserted and locked.Action/Remedy:Correctlyinsertthecarriageandflapdownthehandle.

Error 2

Max NiveauError message is displayed until reset.

flashes buzzes loudly (can not be switchedoff)

activated Switchunitoff,thenonagain.

Cause: Maximumwaterlevelinthebasetubexceeded.Safetyswitchhastriggered. PH15: water tank not tight (tank cap not tight and/or level regulating valve in the tank cap

blockedordefective). PH15A:inletvalvedefective.Action/Remedy:PH15:Removethetankimmediately.Check/cleanfillerneck,tankcapandlevelregulating

valveintankcap(replacetankcapifnecessary),thenclosetankcapcorrectly. PH15A: check/replace inlet valve.

Error 3

Filltime Error message is displayed until reset.

flashes buzzes activated Switchunitoff,thenonagain.

Note: This message is displayed only on the Defensor PH15ACause: Shut-offvalveinthewatersupplylineclosed.Internalwaterfilter(neartotheinletvalve)

blocked.Inletvalvedefective.Action/Remedy:openshut-offvalveinthewatersupplyline.Cleanwaterfilter(seechapter6.3).Check/replace

inlet valve.

Error 4

No signal Error message is alternating with the standard operating display.

flashes beepsbrieflyevery 6 min-utes

activated Automatic resetting as soon as the unit re-ceivesasignalfromtheradio humidity sensor.

Cause: The DefensorPH15/PH15Adoesnotreceiveanysignalfromtheradio humidity sensor (op-tion).Batteryoftheradio humidity sensor soon empty or radio humidity sensordefective.Radio humidity sensorinstalledoutsidethesignalrangeof25m.

Note:Aslongastheunitdoesnotreceiveanysignalfromtheradio humidity sensor it switches to the internal humidity sensor.

Action/Remedy:Replacethebatteryoftheradio humidity sensor. Check/replace radio humidity sensor. Install radio humidity sensor inside the signal range.

Error 5

Leakage sensor Error message is displayed until reset.

flashes buzzes loudly (can not be switchedoff)

activated Switchunitoff,thenonagain.

Cause: PH15: Water tank not tight (tank cap not tight and/or level regulating valve in the tank cap blockedordefective).Unitisnotplacedonahorizontalsurface.Safetyswitchdefective.

PH15A:Inletvalvedefective.Levelswitchdefective.Safetyswitchdefective.Action/Remedy:PH15:Check/cleanfillerneck,tankcapandlevelregulatingvalveintankcap(replacetank

capifnecessary),thenclosetankcapcorrectly.Placeunitonahorizontalsurface.Check/replacesafetyswitch.

PH15A: Check/replace inlet valve. Check/replace level switch. Check/replace safetyswitch.

Page 37: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

37

7.4 What, if...?

ThefollowingtablelistssymptomsofmalfunctionthatmayoccurindailyoperationoftheDefensor PH15/PH15A, together with possible causes and suggested remedies.

Symptom Cause RemedyUnit does not work, LC display remains dark

Unit is not connected to the mains.

Connect unit to the mains.

Unitfuseblown. Have a service technician ofyour Defensor supplier check the unit.

Unit does not humidify. Ambient air humidity is higher thanselectedreferencevalue.

No remedy required, changereferencehumidityvalueifnec-essary.

Levelswitchisdefective.There-fore no error message is dis-played even though the water level in the base tub is too low.

Have a service technician ofyour Defensor supplier replace the level switch

Room air does not reach the set reference humidity value.

Evaporator mat not installed. Install evaporator mat.Room temperature too high. Reduce room temperature to

20-22°C.Unit very dirty. Performmaintenance(see

chapter 6)Doors or windows are open. Close doors and windows.Prolonged ventilation of theroom. Therefore continuousreplacement of the humidifiedroom air by dry outdoor air.

Ventilate room only a shorttime!

Room to large. Contact your Defensor supplier.Actual humidity much higher than the reference value.

The actual humidity is higher than the set reference air hu-midity.

Letunitrunningasairpurifier.

Fan does not run Humidification mode “Humidi-fication”selected.Ambienthu-midity is higher than selected referencevalue.

None. Unit is working properly.

Unit is in program mode. The currently active program sets thefanstepto“0”.

None. Unit is working properly.

Fandefective. Contact your Defensor supplier.Base tub and evaporator mat have heavy slime accumula-tion.

Silver coating on the water ioni-sation electrodes is worn.

Haveaservicetechnicianofyour Defensor supplier replace the water ionisation elec-trodes.

Page 38: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

38

7.5 Notes on fault elimination

DANGER!Fortheeliminationoffaultsset the Defensor PH15/PH15A out of operation, separate the unit from the mains and secure it against inadvertent power-up.

Theeliminationoffaultsmustbecarriedoutonlybyqualifiedandwelltrainedprofessionals.Malfunctionsrelatingtotheelectricalinstallationmustonlyberepairedbyauthorizedpersonnelorby your Defensor representative’s service technician.

RepairworkandthereplacementoffaultycomponentsmustbecarriedoutonlybyyourDefensor representative’sservicetechnician!

Page 39: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

39

8 Taking out of service/Disposal

IftheDefensorPH15/PH15Amustbereplacedoriftheunitisnotneededanymore,proceedasfollows:

1. Switchofftheunit,separateitfromthemainsandsecureitagainstinadvertentpower-up.Closeshut-offvalveinthewatersupplyline(PH15Aonly).

2. Havetheunit(andallothersystemcomponents,ifnecessary)unmountedbyaqualifiedserv-ice technician.

8.1 Taking out of service

8.2 Disposal/Recycling

Attheendofthelife-spantheunitanditscomponentsmustbereturnedtothemanufacturerorbroughttoanauthorisedcollectionpointforcorrectdisposaland/orrecyclingaccordingtothelocalregulations.

IncaseofdoubtpleasecontactyourlocaladministrationoryourDefensor supplier.

Page 40: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

40

9 Unitspecifications

Dimensions(BxHxT) 730x610x370mm

Weight (empty) 25 kg

Water tank capacity 20 l

Mains voltage 220…240VAC/50…60Hzor90…110VAC/50…60Hz

Power consumption max.72Watt

Capacity levels 1) 1 2 3 4

Air circulation rate 155 m3/h 195 m3/h 280 m3/h 340 m3/h

Humidificationcapacity(at25°Cand20%rh)

0.8 l/h 1.1 l/h 1.5 l/h 1.7 l/h

Humidificationcapacity(at23°Cand45%rh)

0.6 l/h 0.8 l/h 1.0 l/h 1.3 l/h

Forroomsuptoamax.of 280 m3 380 m3 510 m3 580 m3

Sound pressure level 33 dBA 38 dBA 45 dBA 50 dBA

Sound power level(according EN ISO 3741)

47 dBA 52 dBA 59 dBA 64 dBA

Admissible ambient temperature 5…40 °C

Admissible ambient humidity 0…85%rhnoncondensing

Unit version PH15A

– Water supply connector G3/4"(femaleconnector)

– Admissible water pressure 0.5…6.0 bar

– Admissible water temperature 5…40 °C

Certificates VDE,CE,GS,GOST

1) Theperfomancedataarebasedonaunitwithbasicequipmentforhumidifieroperation

Page 41: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

41

PH15

X14

X15

X17

+5V4321

U1P1

T1

T2

B3

B1 B2

X5

F1

M1

M2

X21

X9X9

7 1

X10

2 1

1

+24

V

X12

2 1

X6 X5

1 2 1 2 3

+24

V

X13

5 4 3 2 1

+24

V

+24V

X1L1LNPE

X3

123

54

X16

1 110

St. 1 (ws)St. 2 (rt)St. 3 (gu)

C2 (bn)C1 (ge)

St. 4 (sw)

N (bl)8

PE

PEPE (gn/ge)

X4

123

56

4

789

10

1.25 AT

S1

C (bn)P (bl)N (sw)

PE (gn/ge)

L1LNPE

LN 230 VACPE

L1LNPE

LN 100 VACPE

M

M

110V110V

230V

230V/410mA

230V/240mA

N

NN

S2Y1

Y2

Keypad&LED

Ste

uerp

rint

PH

1530

0000

382.

000

Inde

x X

XA

rt.N

r. X

XX

XX

XX

U3

U2

S3D

ispl

ay

10 Appendix

10.1 Wiring diagram

B1, B2 Ionisation electrodesB3 Level switchF1 Fuse control board (1.25 A, slow acting)M1 4-stepfanM2 CentrifugemotorP1 Potentiometer display contrastS1 SafetyswitchS2 Leakage sensor (option)S3 Micro switch carriage

U1 Internal humidity sensorU2 Radio receiver (option)U3 Externalradio humidity sensor (option)T1 TransformercontrolboardT2 Transformer100VversionX5 Errorcontact,max.250VACX9 ProgramminginterfaceY1 Inlet valveY2 Inletvalve(safetyvalve)

100Vversiononly

Page 42: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

42

10.2 Spare parts list PH15

20

9

20

28

19

44

24

27

32

34

5

1

23

35

6

37

3839

1

30

17

40

16

8

26

47

294

25

7

22

3

41

31

42

43

48

33

45

36

Page 43: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

43

Pos. Art.-No. Spare parts designation1 2525254 Air outlet grill3 2525318 Top cover grill4 2525255 Frame5 1103777 Motor support6 2525306 Side board7 2525256 Protecting grill cpl.8 2525257 Handle9 2525258 Roll water carriage (2 pcs)

16 2527094 Water tank17 1104450 Level control valve19 2525273 Mobile base cpl.20 2525275 Double roll (2 pcs)22 2525277 Swash chicane (2 pcs)23 1103179 Base cover24 1104457 Droplet trap25 1102319 Coarsedustfilter(5pcs)26 2525692 Water carriage27 1100465 Evaporator mat

1100398 Activated charcoal evaporator mat28 1102685 Connecting bars with support29 2525278 Float cover30 1104462 Level switch31 1103785 Levelsafetyswitch32 1104467 Impeller33 1115356 Ionisation electrode (2 pcs)34 2525279 Impeller motor35 2525280 Fan cpl.36 2525281 Control panel37 1115515 Display LCD38 2525304 Control PCB39 1103719 Humidity sensor cpl.40 1113552 Gasket level control valve41 2524759 Radio humidity sensor42 2525353 Reiceiver module43 2525305 TransformerJapan44 1101225 Coarsedustfilter

1100259 Quattrofilter45 2525859 Support ionisation electrode cpl. (2 pcs)47 2544589 Base water carriage48 2549653 Door switch-- 1110326 Brushforimpeller-- 2527171 Leakage sensor-- 2529755 Salt pill leakage sensor (5 pcs)-- 1119520 Ionisation cable

Page 44: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

44

10.3 Spare parts list PH15A

20

9

10

20

28

19

44

24

27

32

34

5

22

23

35

6

37

3839

1

30

31 15

294

25

7

3

1

41

22

8

46

47

42

43

48

33

45

11

36

Page 45: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

45

Pos. Art.-No. Spare parts designation1 2525254 Air outlet grill3 2525318 Top cover grill4 2525255 Frame5 1103777 Motor support6 2525306 Side board7 2525256 Protecting grill cpl.8 2525257 Handle9 2525258 Roll water carriage (2 pcs)

10 2525260 Valveunitcpl.11 2558173 Water connection hose15 2525263 Inlet hose19 2525349 Mobile baseA-typecpl.20 2525275 Double roll (2 pcs)22 2525277 Swash chicane (2 pcs)23 1103179 Base cover24 1104457 Droplet trap25 1102319 Coarsedustfilter(5pcs)27 1100465 Evaporator mat

1100398 Activated charcoal evaporator mat28 1102685 Connecting bars with support29 2525278 Float cover30 1104462 Level switch31 1103785 Levelsafetyswitch32 1104467 Impeller33 1115356 Electrodes ionisation34 2525279 Impeller motor35 2525280 Fan cpl.36 2525281 Control panel37 1115515 Display LCD38 2525304 Control PCB39 1103719 Humidity sensor cpl.41 2524759 Radio humidity sensor42 2525353 Reiceiver module43 2525305 TransformerJapan44 1101225 Coarsedustfilter

1100259 Quattrofilter45 2525859 Support ionisation electrode cpl. (2 pcs)46 2543815 WatercarriageA-type47 2544589 Base water carriage48 2549653 Door switch-- 1110326 Brushforimpeller-- 2527171 Leakage sensor-- 2529755 Salt pill leakage sensor (5 pcs)-- 1119520 Ionisation cable

Page 46: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

Notes

Page 47: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

© Walter Meier (climate international) Ltd. 2007, Printed in switzerlandtechnical modifications reserved

Page 48: Defensor PH15/PH15A · The radial fan (1) takes in the air from the top via the coarse filter (2).After passing through the evaporator mat (3) (or the activated carbon evaporator

Manufacturer:Walter Meier (climate international) Ltd.talstr. 35-37, P.O. Box, cH-8808 Pfäffikon (switzerland)Phone +41 55 416 61 11, Fax +41 55 416 62 62www.waltermeier.com, [email protected]