DCSentral
1
Made by :
Etiennette AuffrayAndrea Barisone
Last Revision : June 27, 2013
Central DCS Tutorial-Shutdown edition-
2
Central DCS TeamCentral DCS Expert Team:
Frank Glege (71688, 163919)Robert Gomez-Reino Garrido (71654, 162366)Lorenzo Masetti (165820)Giovanni Polese (165807)DCS expert on Call : 162229
Central DCS Operation:Central DCS desk : 75140Etiennette Auffray >> Shift organisation, Tutorial, Twiki : (75844, 163646)Andrea Barisone >> Tutorial, Twiki
DCSentral
Central DCS shift requirements:• CERN ID card and access to P5 and USC ( request done by EDH)• All safety trainings up-to-date, including the Biocell training. For more information, please visit: http://cms-safety.web.cern.ch ;• At least the token.
CMS Slice View
33
DCSentral
4
DSS Screens
Cavern Access
DCSentral
Racks Panel
Cooling Panel
Main DCS Panel
DCS alarm PanelSubdetectors Panel
Sensors 4 CMS Panel
GTPM Panel
DCS Workstation : Screens
DCSentral
55
Cavern Access Displays
Experimental Cavern Doors
Telephone
Speaker for the UXC and USC
Cavern
WP Display
Intercom
Cavern Access : Screens
DCSentral
6
UXC 55 USC 55
DSS Screens
7
DCSentral
DCS Mobile Phone
DCS Mobile Phone
DCSentral
8
As a general guideline all variables controlled and monitored by central DCS should be GREEN
If not green, a corresponding alarm will be raised and will appear in the central DCS Alarm Screen;
Therefore it is very important to monitor the alarm screen during your shift and have prompt action in case of any alarm;
In the next transparencies, the central DCS shifter tasks will be visited one by one, keeping in mind this general guideline.
Central DCS General Guideline
9
Main DCS Tasks
1. What to do when a DCS alarm occur during the Shift (Concerned Screen : DCS Alarm Panel )
3. What to do when a DSS alarm occur during the Shift (Concerned Screen : DSS Alarm Panels)
4. Monitoring Operation: Services (Racks and Cooling)
5. Underground Cavern Access Management6. DCS Elog : (When and How use it)
DCSentral
DCSentral
10
DCS Alarm Screen
This screen should be : Checked regularly Empty
Each time an important problem occurs (subdetectors, services, etc…) an alarm (together with an audible alert) should appear on this screen
DCSentral
11
DCS Alarm Screen
Read Instructions to correctly handle the alert :
In case you don’t know how to solve it call the responsible
If there is no instruction send an email to us
On the first line of the page you can see which subdetector is affected by the problem : the alarm will continue blinking until handled by the DCS shifter
Below you find a row where there are several information regarding the alarm : select and right click on it and a pop up window will appear
DCSentral
12
DCS Alarm Screen
Direction box :CAME :The condition which triggered the alarm is still presentWENT :The condition which triggered the alarm has disappeared
Time stamp (when shifter has clicked on Alarm Help)
SUBDETECTORS MAIN LINE:Colors meaning list :LIGHT BLUE : No errors RED: Fatal alertORANGE: ErrorYELLOW: WarningGREY: Alert acknowledgeable
DCSentral
13
Monitor Services
14
Color code:Grey – Not usedGreen – OK------------------------Blue – OFF -> Red – ERROR -> requires intervention!
Rack Power Status per underground area
S1-S4 = Service CavernX0-X5 = Exp. Cavern
Service Screens (Rack Panel )
Racks Cooling Station.
If you click on 1 rack you
get details on it
Take actions on racks. Follow the
instructions
DCSentral
Racks summary
15
Service Screens (Rack Panel )
Rack details
DCSentral
DCSentralTOP PART OF THE SCHEME Cooling Panel
BOTTOM PART OF THE SCHEME
Copper circuit leakWarning: 1 l/h > 60 min
Alarm: 4 l/h >30 min or 8 l/h >1 min
Rack circuit leakWarning: 2 l/h > 60 min
Alarm: 6 l/h >30 minmin or 8 l/h >1 min
Aluminum circuit leakWarning: 1 l/h > 60 min
Alarm: 4 l/h >30 min min or 8 l/h >1 min
During working hours (8h30/17h30) no matter which doubt or change of color: CMS cooling support, 163021
Outside working hours: TOP PART of the screen: ORANGE, write on DCS e-log, RED - Call CCC 72201BOTTOM PART of the screen (flow & tank levels) :ORANGE : 17h30/24h00 call 165000 24h00/7h00 ignore, RED, call 165000
Service Screens (Cooling)
Color code:Green – OK--------------------------Yellow – warningOrange – ErrorRed – FATAL ERRORBlinking Valuesrequires intervention!
DCSentral
17
Blinking values
• If a value is blinking:
you should verify at http://dipg.cern.ch/dipg if there are invalid CMS cooling values. In case the bullet corresponding to CMS Cooling is red, it is very likely to be a problem on the CCC side.
You should call the CCC (72201) to inform them there is a problem with their publications and point to them what you see from the link above.
If there are no invalid values in the link above, call the central DCS expert and inform about the problem.
The interface from above is slow, so you should wait about 10 minutes to make sure it is updating, before reporting the problem.
Service Screens (Cooling)
DCSentral
Front End warning light : should be always green. If not, call Alain Meynet, between 7:00 and 22:00. If red during the night, call Alain Meynet in following the morning.
Right-click on the alarm and select ‘Show’ to obtain more information. If the alarm’s “Triggered” state is red, it cannot be acknowledged.
To acknowledge an alarm:
1. click on the ALARM column, on the DSS ALARMS list;
2. Then click on the ACTIONS column of the DSS ACTIONS list.
User should always be set to ‘user’. If not, click on Logout. The panel will restart automatically.
Stop Siren button: stops the siren in the DSS hardware panel when there is an alarm. Only works from the DSS USC55 panel!
DSS Alive. Should blink.
If there is a DSS Alarm with Siren and light, the DCS shifter should
immediately call the Technical coordination number 165000
DSS :Detector Safety System
DCSentral
19
DSS :Detector Safety System
In case of alarms: read the alarm description and contact the
responsible person (e.g. Magnet, subdetectors, etc.);
In case the alarm description is not clear: during working hours: call DSS expert,
Alain Meynet: 163146; out of working hours: call Christoph
Schaefer: 160202 or Wolfram Zeuner: 162541 and at last 165000 (in case the other numbers failed).
Check the DSS display is Alive: These buttons should blink. If not, restart
the panel (instructions in the DSS binder). If restart does not work, call : 162082
DCSentral
20
DSS :Detector Safety System
DSS Hardware Piquet: 162082
DCSentral
21
Every person going underground (Service and Experimental caverns) is required to fill in the paper version of the 'Access to Experimental and Service Caverns' list that can be found in a binder by the Shift Leader's desk;
The central DCS shifter has to check that the person fills this form when he/she goes into the cavern and when he/she returns;
The person has to have a mobile phone;
If after some time the person is not back in the control room, call him/her to check everything is ok.
You can find detailed information on underground access in the cDCS twiki:https://twiki.cern.ch/twiki/pub/CMS/OnlineWBCentralDCSInstructions/DCScavernAccess1.3.pdf
Underground Cavern Access
DCSentral
2222
Cavern Access Displays
Experimental Cavern Doors
Telephone
Speaker for the UXC and USC
Cavern
WP Display
Intercom
Cavern Access : Screens
DCSentral
2) The Access management software Work Packages (WP) is reachable
from the CMS Online Page ( clicking on ACT ) or directly from
this url : http://cmsonline.cern.ch/portal/p
age/portal/CMS%20online%20system/ACT
1. Each person that wants to access the experimental cavern has to be properly registered in a WP;
Underground Cavern Access
DCSentral
3) Once inside DCS Shifter has to select : “Document Database “
Underground Cavern Access
DCSentral
25
4. go up on the left side of the page and select “Shifter Page”)
4
Underground Cavern Access
DCSentral
26
5. Enter the name of the person willing to enter of the cavern6. The list of assigned WP will appear 7. Select the WP to see its status.8. To start the WP Select in the menu status : Ongoing
5
6, 7
8
Underground Cavern Access
DCSentral
27
Point 10 to 13
9. Turn the dosimeter ON; (Push the black button three times : once for each message will pop up on its little screen (CHANGE >> ENTER >> 1mv) : then a red light will flash few seconds and also you will hear a “bip”)
10. Select the dosimeter number in the ‘Operational Dosimeter’ field;
11. Read the initial dose from the dosimeter and fill it in the appropriate field of the Shift Operation page;
12. Click ‘Ok’ to grant access to the person;
13. By the return of the dosimeter, fill in the final dose and click ‘Ok’;
14. Turn the dosimeter OFF (simply push the black button on top of the dosimeter, the word “CHANGE” will appear, keep on holding the black button until the word “GO OFF” shows up. Then immediately release the black button. If one waits for too long to release the black button, the dosimeter will not switch off).
Underground Cavern Access
DCSentral
28
9. Turn the dosimeter ON; (to do that, push the black button three times : once for each message will pop up on its little screen (CHANGE >> ENTER >> 1mv) : then a red light will start flashing)
10. Select the dosimeter number in the ‘Operational Dosimeter’ field;
11. Read the initial dose from the dosimeter and fill it in the appropriate field of the Shift Operation page;
12. Click ‘Ok’ to grant access to the person;
13. By the return of the dosimeter, fill in the final dose and click ‘Ok’;
14. Turn the dosimeter OFF (simply push the black button on top of the dosimeter, the word “CHANGE” will appear, keep on holding the black button until the word “GO OFF” shows up. Then immediately release the black button. If one waits for too long to release the black button, the dosimeter will not switch off).
9-14
After an access: DCS shifter has to make sure the lights in UXC are
switched OFF.
Dosimeter numberButton
Red flashing light Dosimeter display
9-14
Underground Cavern Access
DCSentral
29
15. Click on edit button16. The WP summary page will appear17. In the list of name click on edit
15
17
16
Underground Cavern Access
DCSentral
30
18. Insert the name of the person you want to register (previously authorized by the WP leader)19. Select his role 20. save changes21. The new name will appear in the name list
9
18
19
20
21
Underground Cavern Access
DCSentral
Once the authorized person has received his dosimeter (s)he can finally access to the cavern, and in the two displays here below the DCS Shifter can check all the cameras pointing at the different doors in the cavern : When the person reach the entrance (21) there are still few steps to be execute …
21
Underground Cavern Access
DCSentral
… he needs to pass his badge over the card reader in the yellow underground cabinet (22) : Then on the DCS screen his name will appear in the dedicated window (23 and the DCS Shifter has first to select the line and then click the button “Give the Key” (24) in order to let the drawer in the underground rack opening (25) and delivering the access key to him.
The name will appear here ….
Once selected the name the button will became clickable
25
22
23
24
Underground Cavern Access
DCSentral
33
DCS ELOG address : cmsonline > Common > Elog > Subsystems > DCS At the beginning the shift: write an elog with the summary
status of all the central DCS systems;During your shift : Write only a short elog with specific
information when you have any problem with subdetectors, cooling, racks, etc... with indication on your elog Title of the problem
At the end of the shift: Write an elog with a summary of all the relevant events that happened during your shift.
Shift Instructions are available online at:https://twiki.cern.ch/twiki/bin/view/CMS/OnlineWBCentralDCSInstructions
DCS Elog
DCSentral
• Emergency, accident, fire : 74444 • Any technical problem (Siren Alarm): 165000• Rack Problem :Rack becomes off or in error :1. Tracker (Pixel) : 165502 2. Tracker (Strip) : 165503 3. ECAL : 70130 or 1655044. HCAL : 165505,5. CSC :1655096. DT : 1655077. RPC :165508During the day you can also call Silverio : 163706• Cooling Problem : 1. ECAL cooling: 70130/1655042. One (other the ECAL) of the box is not green : During the day : Cooling piquet 163021
Outside working hours : • Top part : call CCC 72201 • Bottom part : call 165000 if red• Screen blinking : Call CCC 72201
Magnet Problem : Call Magnet piquet 162082• Cryogenic problem : Call Cryogenic piquet
160124• Gaz Problem : Call Gaz Piquet 162516
• DCS Problem:• Central DCS :Call DCS expert on call 162229• Subdetector DCS :
1. Tracker (Pixel) : 165502 2. Tracker (Strip) : 165503 3. ECAL :72606 or 1655044. HCAL : 165505,5. CSC :1655096. DT : 1655077. RPC :165508
• DSS Problem : • Alarm : Alain Meynet during the day 163146Christoph Schaefer 160202• Technical Problem : 165000 • Hardware Problem : 162082
Useful Contacts (1)
DCSentral
Useful Contacts (2)
TS Technical control room (CCC): 72201IN CASE OF ANY TECHNICAL PROBLEM CALL: 16 5000Backup: Austin BALL: 160408, Christoph SCHAEFER:160202, Wolfram ZEUNER: 162541, Martin GASTAL: 163702DCS expert on call : 16 2229Backup : Frank : 163919, Bobby : 162366, Lorenzo : 165820DSS expert on call : 162082
CASTOR: 162875
TOTEM (Green Barrack): 77534
BRM/BCM: 165501
Fireman at P5 (working hours ) : 164812
(still call directly the 74444 in case of DSS alarms)Online Web Contact List : https://twiki.cern.ch/twiki/bin/viewauth/CMS/OnlineWBContactList