DCIM_Linkedin

31
Log In Upon opening VDC 3D client, User will be prompt to log in

Transcript of DCIM_Linkedin

Page 1: DCIM_Linkedin

Log In

•Upon opening VDC 3D client, User will be prompt to log in

Page 2: DCIM_Linkedin

Main floor plan:

•Total device in alarm/warning/unreachable status

•PUE

•Total power consumption

•Estimated yearly consumption

•Estimated yearly cost

•Estimated yearly CO2 emission

•Floor Area – Total usable floor space

•White Area – Total used space

•Grey Area – Area reserved on going projects.

Page 3: DCIM_Linkedin

Accessing to Ground floor layout Accessing to 2nd floor layout

Page 4: DCIM_Linkedin

Gnd Floor DCIM Monitoring

•Genset & Battery charger

•RMU A&B

•Transformer 1A, 2A, 3A, 1B, 2B, & 3B

•Switch board - Genset sync board A&B, LV Board A1, A2, B1 & B2, SSB Chiller A & B

•FCU – FCU 1A, 1B, 2A, 2B

•Exhaust Fan – EX-G1, EX-G2, EX-G3, EX-G4, EX-G5 & EX-G6

•Temp & Humidity sensors for facility room

• Active Harmonics Filter

TR1A TR2A TR3A TR1B TR2B TR3B

RMU A RMU B

LV

Ro

om

A LV Room B

Ge

n S

ync A

G

en S

ync B

SSB Chiller B

SSB Chiller A

Genset 1A

Genset 1B

Page 5: DCIM_Linkedin

RMU A & B – Expendable to 3 more screen

• On/Off Status - DI

Page 6: DCIM_Linkedin

Transformer 1A, 2A, 3A, 1B, 2B & 3B –

Expendable to 3 more screen

• On/off status –DI

• Over temp alarm - DI

Page 7: DCIM_Linkedin

LV Board A1 & B1

• 2x Incoming DPM – Modbus

• 2x ACB input breakers – DI

• 1x ACB output breaker – DI

• 2x change over circuit – DI

• Surge protection – DI

Page 8: DCIM_Linkedin

LV Board A2 & B2

• 2x Incoming DPM – Modbus

• 2x ACB input breakers – DI

• 7x ACB output breaker – DI

• 1x change over circuit – DI

• 2x Surge protection – DI

IT
Polygon
Page 9: DCIM_Linkedin

SSB Chiller A & B

• 1x Incoming DPM – Modbus

• 1x input breakers – DI

• 6x outgoing breaker – DI

• 1x Surge protection – DI

IT
Polygon
Page 10: DCIM_Linkedin

FCU G1A, G1B, G2A, G2B

FCU status from DDC via MODBUS

• On/off status

• Trip status

• Dirty filter alarm

• Start/stop status

Page 11: DCIM_Linkedin

Fan G1, G2, G3, G4, G5 , G6

Fan Status from DDC via Modbus

• On/off status

• Trip status

• Dirty filter alarm

• Start/stop status

Page 12: DCIM_Linkedin

Genset Panel A & B

• 2x Output DPM – Modbus

• 2x Output breakers – DI

• 2x Genset breaker – DI

Page 13: DCIM_Linkedin

Genset 1A & 1B

Genset status from genset control panel (Power

Wizard 2.1) Via Modbus

• Battery Voltage • Engine RPM • Generator average AC RMS current • Generator average AC RMS frequency • Generator average line-line AC RMS voltage • Generator average line-neutral AC RMS voltage • Generator total apparent power • Generator total % kVA • Generator total % kVAr • Generator total % kW • Generator total reactive power • Generator total real power

Page 14: DCIM_Linkedin

2nd Floor DCIM Monitoring

• Chiller A/1, A/2, A/3, B/1, B/2, B/3

• CRAC

• Primary & Secondary Pump – PCHWP A/1, A/2, A/3, B1, B2, B3, SCHWP A1, A2, B1, B2

• Switch board – UPS I/P Board A&B, UPS O/P Board A&B, SSB A/C A&B, Chill Water Pump

Control Panel A&B

• UPS – A1, A2, A3, B1, B2, B3

• AHU A&B

• FCU – FCU S30, S31, S32, S33

• Exhaust Fan – FAE-S1, GEF 1, GEF 2, GEF UPS A, GEF UPS B

• Fire Panel, VESDA, WLDS, Temp/Hum Sensor

Page 15: DCIM_Linkedin

UPS Input DB A & B

• 1x DPM – Modbus

• 9x Input breakers – DI

• 1x Maintenance bypass breaker – DI

• 1x Surge protection – DI

Page 16: DCIM_Linkedin

• Output Power [%], phase 1, 2, 3 • Input Voltage [V], phase 1, 2, 3

• Battery Voltage [V]

• Alarm "Battery Bad“, "On Battery“, "Low

Battery" • Alarm "Depleted Battery“, "Temperature Bad"

• Alarm "Input Bad“, "Output Bad“, "Overload" • Alarm "On Bypass“, “Charger Failed“, "Ups

Output Off" • Alarm "Fan Failure""Fuse Failure""General

Fault" • Alarm "Awaiting Power"

UPS 1A, 2A, 3A, 1B, 2B, 3B

• UPS status obtained Via Modbus

Page 17: DCIM_Linkedin

UPS Output DB A & B

• 13x DPM – Modbus

• 6x Outgoing breakers – DI

• 1x Maintenance bypass breaker – DI

• 1x Surge protection – DI

Page 18: DCIM_Linkedin

Notifier IG55 Panel

• Fire alarm - DI

• Smoke alarm – DI

• Fault alarm – DI

Page 19: DCIM_Linkedin

VESDA Panel

• Action alarm - DI

• Smoke alarm #1 – DI

• Smoke alarm #2 - DI

• Fault alarm – DI

Page 20: DCIM_Linkedin

Water Leak Detection System

• Cable break alarm - Modbus

• Leak alarm – Modbus

Page 21: DCIM_Linkedin

Chiller A/1, A/2, A/3, B/1, B/2, B/3

• Chiller status obtained via Modbus

• On/off status, alarm status, start/stop status

• CHWS/CHWR Temp, Water flow status

• Motorized open/closed status, on/off status

• Header pressure, temp, flow rate

• Expansion tank HL level alarm, Trip status

• Control Chiller On/Off

Page 22: DCIM_Linkedin

Chilled Water Pump Control Panel

A&B

•7x Incoming DPM – Modbus

Page 23: DCIM_Linkedin

PCHWP – A/1, A/2, A/3, B/1, B/2, B/3

• Primary pump status obtained via Modbus

• On/off status, trip status, switch status

• Bypass valve control

• VSD control, feedback

Page 24: DCIM_Linkedin

SCHWP – A/1, A/2, B/1, B/2

• Secondary pump status obtained via Modbus

• On/off status, trip status, switch status

• Bypass valve control

• VSD control, feedback

Page 25: DCIM_Linkedin

SSB A/C A&B

•2x Incoming DPM – Modbus

• 2x ACB input breakers – DI

• 17x outgoing breaker – DI

• 2x Surge protection – DI

Page 26: DCIM_Linkedin

• Unit (Evaporating Fan) ON

• Cold water temperature sensor failure • High room temperature • Low room temperature • High room humidity • Low room humidity • General Alarm • Maintenance Signaling • Room temperature • Room relative humidity • Supply air temperature • Cold water temperature • Control CRAC On/Off (Fan only)

• Monitor ATS for side A or B power – Via DI

CRAC Units – Total 31 units

• CRAC status obtained Via Modbus

Page 27: DCIM_Linkedin

• AHU FA/1-On/Off, Trip, Switch Mode, Gas Detection

Status, Start/Stop, Damper Open/close Status, Off-Coil

Air Temperature, Supply Air Humidity Status

• Room Air Temp/Hum

• EF-1-On/Off, Trip, Switch Mode, Damper Open/close

Status

• Under Flr Exh Dam 1&2 - Damper Open/closed Status

• Freash Air Temp/Hum

• Pri/Secondary, HEPA Filter Dirty Alarm

• Chilled Water Valve Ctrl

• Heater Valve Ctrl

AHU A&B

• AHU status obtained Via Modbus

Page 28: DCIM_Linkedin

FCU S30, S31, S32, S33

• FCU status obtained Via Modbus

• On/off status – DI

• Trip status – DI

• Dirty filter alarm – DI

• Start/stop status - DI

Page 29: DCIM_Linkedin

Fan FAE-S1, GEF UPS A, GEF UPS B, GEF 1, GEF 2

Fan Status via Modbus

• On/off status

• Trip status

• Dirty filter alarm

• Start/stop status

Page 30: DCIM_Linkedin
Page 31: DCIM_Linkedin