•Upon opening VDC 3D client, User will be prompt to log in
![Page 2: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/2.jpg)
Main floor plan:
•Total device in alarm/warning/unreachable status
•PUE
•Total power consumption
•Estimated yearly consumption
•Estimated yearly cost
•Estimated yearly CO2 emission
•Floor Area – Total usable floor space
•White Area – Total used space
•Grey Area – Area reserved on going projects.
![Page 3: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/3.jpg)
Accessing to Ground floor layout Accessing to 2nd floor layout
![Page 4: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/4.jpg)
Gnd Floor DCIM Monitoring
•Genset & Battery charger
•RMU A&B
•Transformer 1A, 2A, 3A, 1B, 2B, & 3B
•Switch board - Genset sync board A&B, LV Board A1, A2, B1 & B2, SSB Chiller A & B
•FCU – FCU 1A, 1B, 2A, 2B
•Exhaust Fan – EX-G1, EX-G2, EX-G3, EX-G4, EX-G5 & EX-G6
•Temp & Humidity sensors for facility room
• Active Harmonics Filter
TR1A TR2A TR3A TR1B TR2B TR3B
RMU A RMU B
LV
Ro
om
A LV Room B
Ge
n S
ync A
G
en S
ync B
SSB Chiller B
SSB Chiller A
Genset 1A
Genset 1B
![Page 5: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/5.jpg)
RMU A & B – Expendable to 3 more screen
• On/Off Status - DI
![Page 6: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/6.jpg)
Transformer 1A, 2A, 3A, 1B, 2B & 3B –
Expendable to 3 more screen
• On/off status –DI
• Over temp alarm - DI
![Page 7: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/7.jpg)
LV Board A1 & B1
• 2x Incoming DPM – Modbus
• 2x ACB input breakers – DI
• 1x ACB output breaker – DI
• 2x change over circuit – DI
• Surge protection – DI
![Page 8: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/8.jpg)
LV Board A2 & B2
• 2x Incoming DPM – Modbus
• 2x ACB input breakers – DI
• 7x ACB output breaker – DI
• 1x change over circuit – DI
• 2x Surge protection – DI
![Page 9: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/9.jpg)
SSB Chiller A & B
• 1x Incoming DPM – Modbus
• 1x input breakers – DI
• 6x outgoing breaker – DI
• 1x Surge protection – DI
![Page 10: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/10.jpg)
FCU G1A, G1B, G2A, G2B
FCU status from DDC via MODBUS
• On/off status
• Trip status
• Dirty filter alarm
• Start/stop status
![Page 11: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/11.jpg)
Fan G1, G2, G3, G4, G5 , G6
Fan Status from DDC via Modbus
• On/off status
• Trip status
• Dirty filter alarm
• Start/stop status
![Page 12: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/12.jpg)
Genset Panel A & B
• 2x Output DPM – Modbus
• 2x Output breakers – DI
• 2x Genset breaker – DI
![Page 13: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/13.jpg)
Genset 1A & 1B
Genset status from genset control panel (Power
Wizard 2.1) Via Modbus
• Battery Voltage • Engine RPM • Generator average AC RMS current • Generator average AC RMS frequency • Generator average line-line AC RMS voltage • Generator average line-neutral AC RMS voltage • Generator total apparent power • Generator total % kVA • Generator total % kVAr • Generator total % kW • Generator total reactive power • Generator total real power
![Page 14: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/14.jpg)
2nd Floor DCIM Monitoring
• Chiller A/1, A/2, A/3, B/1, B/2, B/3
• CRAC
• Primary & Secondary Pump – PCHWP A/1, A/2, A/3, B1, B2, B3, SCHWP A1, A2, B1, B2
• Switch board – UPS I/P Board A&B, UPS O/P Board A&B, SSB A/C A&B, Chill Water Pump
Control Panel A&B
• UPS – A1, A2, A3, B1, B2, B3
• AHU A&B
• FCU – FCU S30, S31, S32, S33
• Exhaust Fan – FAE-S1, GEF 1, GEF 2, GEF UPS A, GEF UPS B
• Fire Panel, VESDA, WLDS, Temp/Hum Sensor
![Page 15: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/15.jpg)
UPS Input DB A & B
• 1x DPM – Modbus
• 9x Input breakers – DI
• 1x Maintenance bypass breaker – DI
• 1x Surge protection – DI
![Page 16: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/16.jpg)
• Output Power [%], phase 1, 2, 3 • Input Voltage [V], phase 1, 2, 3
• Battery Voltage [V]
• Alarm "Battery Bad“, "On Battery“, "Low
Battery" • Alarm "Depleted Battery“, "Temperature Bad"
• Alarm "Input Bad“, "Output Bad“, "Overload" • Alarm "On Bypass“, “Charger Failed“, "Ups
Output Off" • Alarm "Fan Failure""Fuse Failure""General
Fault" • Alarm "Awaiting Power"
UPS 1A, 2A, 3A, 1B, 2B, 3B
• UPS status obtained Via Modbus
![Page 17: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/17.jpg)
UPS Output DB A & B
• 13x DPM – Modbus
• 6x Outgoing breakers – DI
• 1x Maintenance bypass breaker – DI
• 1x Surge protection – DI
![Page 18: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/18.jpg)
Notifier IG55 Panel
• Fire alarm - DI
• Smoke alarm – DI
• Fault alarm – DI
![Page 19: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/19.jpg)
VESDA Panel
• Action alarm - DI
• Smoke alarm #1 – DI
• Smoke alarm #2 - DI
• Fault alarm – DI
![Page 20: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/20.jpg)
Water Leak Detection System
• Cable break alarm - Modbus
• Leak alarm – Modbus
![Page 21: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/21.jpg)
Chiller A/1, A/2, A/3, B/1, B/2, B/3
• Chiller status obtained via Modbus
• On/off status, alarm status, start/stop status
• CHWS/CHWR Temp, Water flow status
• Motorized open/closed status, on/off status
• Header pressure, temp, flow rate
• Expansion tank HL level alarm, Trip status
• Control Chiller On/Off
![Page 22: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/22.jpg)
Chilled Water Pump Control Panel
A&B
•7x Incoming DPM – Modbus
![Page 23: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/23.jpg)
PCHWP – A/1, A/2, A/3, B/1, B/2, B/3
• Primary pump status obtained via Modbus
• On/off status, trip status, switch status
• Bypass valve control
• VSD control, feedback
![Page 24: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/24.jpg)
SCHWP – A/1, A/2, B/1, B/2
• Secondary pump status obtained via Modbus
• On/off status, trip status, switch status
• Bypass valve control
• VSD control, feedback
![Page 25: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/25.jpg)
SSB A/C A&B
•2x Incoming DPM – Modbus
• 2x ACB input breakers – DI
• 17x outgoing breaker – DI
• 2x Surge protection – DI
![Page 26: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/26.jpg)
• Unit (Evaporating Fan) ON
• Cold water temperature sensor failure • High room temperature • Low room temperature • High room humidity • Low room humidity • General Alarm • Maintenance Signaling • Room temperature • Room relative humidity • Supply air temperature • Cold water temperature • Control CRAC On/Off (Fan only)
• Monitor ATS for side A or B power – Via DI
CRAC Units – Total 31 units
• CRAC status obtained Via Modbus
![Page 27: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/27.jpg)
• AHU FA/1-On/Off, Trip, Switch Mode, Gas Detection
Status, Start/Stop, Damper Open/close Status, Off-Coil
Air Temperature, Supply Air Humidity Status
• Room Air Temp/Hum
• EF-1-On/Off, Trip, Switch Mode, Damper Open/close
Status
• Under Flr Exh Dam 1&2 - Damper Open/closed Status
• Freash Air Temp/Hum
• Pri/Secondary, HEPA Filter Dirty Alarm
• Chilled Water Valve Ctrl
• Heater Valve Ctrl
AHU A&B
• AHU status obtained Via Modbus
![Page 28: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/28.jpg)
FCU S30, S31, S32, S33
• FCU status obtained Via Modbus
• On/off status – DI
• Trip status – DI
• Dirty filter alarm – DI
• Start/stop status - DI
![Page 29: DCIM_Linkedin](https://reader030.fdocuments.us/reader030/viewer/2022020314/589ee98f1a28abe97f8b5455/html5/thumbnails/29.jpg)
Fan FAE-S1, GEF UPS A, GEF UPS B, GEF 1, GEF 2
Fan Status via Modbus
• On/off status
• Trip status
• Dirty filter alarm
• Start/stop status