DC Power Supply System Integrated Applicationscomsv.ru › data › Catalog › storage › position...

4
356824.103 Quick Installation Guide DC Power Supply System Integrated Applications Minipack 1U System, Integrated DC Distribution Torque Recommendations Type & Size Torque (Nm) T1 Screws M6 2.5 T2 Screws M3 0.3 T3 AC, I/O 0.4 T4 Battery 1.2 T5 Load 0.5 Note: General tolerance: ±10% Tools PZ2 PH1 Flat 3.5mm Flat 6mm Minipack 1U System, Integrated DC Distribution 2 Rectifiers, Compack Controller, LVBD Contactor & 2 Battery MCBs, 6 Load Fuses 249.0mm 44.5mm (1U) 482.5mm (19”) A1: 263043 Parts Overview A2: (option) 241117.120, (48VDC, 400W) 241117.130, (48VDC, 800W WIR) (1-2) (1-2) A4: (option) 239128 Blind Cover A3: 242100.400

Transcript of DC Power Supply System Integrated Applicationscomsv.ru › data › Catalog › storage › position...

Page 1: DC Power Supply System Integrated Applicationscomsv.ru › data › Catalog › storage › position › attach... · DC Power Supply System Integrated Applications Minipack 1U System,

356824.103

Quick Installation Guide

DC Power Supply System Integrated Applications

Minipack 1U System, Integrated DC Distribution

Torque RecommendationsType& Size

Torque(Nm)

T1 Screws M6 2.5T2 Screws M3 0.3

T3 AC, I/O 0.4T4 Battery 1.2T5 Load 0.5

Note: General tolerance: ±10%

ToolsPZ2

PH1

Flat 3.5mmFlat 6mm

Minipack 1U System, Integrated DC Distribution2 Rectifiers, Compack Controller, LVBD Contactor & 2 Battery MCBs, 6 Load Fuses

249.0mm

44.5mm(1U)

482.5mm (19”)

A1: 263043

Parts Overview

A2: (option)241117.120, (48VDC, 400W) 241117.130, (48VDC, 800W WIR)

(1-2) (1-2)

A4: (option)239128

Blind Cover

A3:242100.400

Page 2: DC Power Supply System Integrated Applicationscomsv.ru › data › Catalog › storage › position › attach... · DC Power Supply System Integrated Applications Minipack 1U System,

Quick Installation Guide Minipack 1U System, Integrated DC Distribution 356824.103, Issue 1 2009-11 2

Remove Top Lock Cover 1-2

Fasten to Cabinet 1-4

A(M3)

A1

A1

2

Top Lock Cover A(M3)

1.5cm0.5cm

1 PH1(2x)

ccw

Compack controller (A3)not inserted

A1

Cabinet

B(~M6)

B(~M6)

Cabinet

A1

Sliding Drawer Shelf inMaintenance Position

2

PZ2 (2x)(T1)

cw

3

PZ2 (2x)

(1/2 turn) ccw

1

4

CAUTION: Slide/rail mounted equipment is not to be usedas a shelf or a work space. To comply with UL requirements and supportthe sliding drawer shelf, always fasten theMinipack 1U system to the cabinet, rightbelow a rigid, supporting surface (plate orcabinet mounted equipment).

Page 3: DC Power Supply System Integrated Applicationscomsv.ru › data › Catalog › storage › position › attach... · DC Power Supply System Integrated Applications Minipack 1U System,

Quick Installation Guide Minipack 1U System, Integrated DC Distribution 356824.103, Issue 1 2009-11 3

Electrical Connections 1-8

Mains Protection Cover

–,–,+,+

BatteryTerminalsFlat 6mm (T4)

Fasten All Cables

8

A1Sliding Drawer Shelf in Maintenance Position

AC Earth (PE) Screw M6 (Chassis) PZ2

LN

TBY(Mains Input 1, Internal use)

AC Mains Input 1Flat 3.5mm (T3)

L N

TBX (AC Mains

Input 2)

N L

DC Earth (TE) Flat 6mm (Mounted M4 screw connects AC Earth (PE) to Positive DC Output (TE))

Internal 3 wiresMains Loom, ML

(blue, black, yellow& green)

F1, Load Fuse

DC Load Terminals (E)Flat 3.5mm (T5) (Plug-in Terminals)

External AC FusesRecommended Rating

16A-C Type Hy/Mag (Europe)20A-C Type Hy/Mag (USA)

1

AC Mains (OFF)

Max 2.5mm2(12AWG)

2(+,–)1(+,–)

6(+,–)

A3

FB1, Battery FuseLVBD

CAN1

7

2 FB1&FB2

OFF(0)

CAUTION: When using “Dual Mains Input”(two feeds 1phase 100-250VAC),turn AC mains OFF, remove theinternal 3 wires Mains Loom MLbetween TBY and TBX and connectthe second Mains feed to TBX.

4

Batteries

Correct Polarity

3 Max 10mm2(6AWG)

For installations in USA and Canada only!

– An AC Overvoltage Protec-tion Device (OVP) must be installed in the system’s AC input. The device must comply with overvoltage category II according to IEC60950-1, Class II by IEC61643-1 or Class C by DIN VDE0675 – For supply connectors, use wire suitable for at least 75ºC, type: FEPW, RH, RHW, THHW, YHW, THWN, ZHHW, USE, ZX or similar. Use copper conductors only

5

Max 4mm2(10AWG)DC Load

Electric Shock

WARNING: Do NOT unscrew theload fuses while poweris ON and the loadcables connected! To disconnect the loadwhile power is ON,always unplug the loadterminals (E). The loadfuse can then beunscrewed.

CAUTION:This equipment has aconnection between theearthed conductor of theDC supply circuit and theearthing conductor.

I/O TerminalsFlat 3.5mm (T3)

(Plug-in Terminals)

6 I/O Alarms

Max 1.5mm2 (14AWG)

FlatHandle in

lockedposition

A3A3

Handle raised in open position

Locked Compack Controller

A3

Ethernet

Pin 1

Pin 16=Dig 3– 5=Dig 3+ 4=Dig 2– 3=Dig 2+ 2=Dig 1– 1=Dig 1+

9=AL3-nc 8=AL3-no 7=AL3-c 6=AL2-nc 5=AL2-no 4=AL2-c 3=AL1-nc 2=AL1-no 1=AL1-c

Out

puts

In

puts

Contacts shown with de-energized coil (Alarm)

Page 4: DC Power Supply System Integrated Applicationscomsv.ru › data › Catalog › storage › position › attach... · DC Power Supply System Integrated Applications Minipack 1U System,

www.eltekvalere.com

Headquarters:Eltek Valere

Gråterudv. 8, Pb 2340 Strømsø, 3003 Drammen, NorwayPhone: +47 32 20 32 00 Fax: +47 32 20 32 10

This product is CE marked and complies with all currentrequirements for relevant standards and directives.

Copyright © Eltek Valere, 2009 This document may be changed without notice Art. No. 356824.103, Issue 1.0, 2009 Nov (draft5) Published 2009-12-dd

Start Up 1-4

Drawer Shelf in Operation Position 1-5

3

AC MainsON

A2

A1

PH1cw

CAUTION: Double Pole / Neutral Fusing. There is a Mains fuse in each line.

A2

A1

4

FB1&FB2ON(1)

1 A1

A2 2 CabinetA2

Electric Shock

WARNING: Mount blind covers in unused rectifier slots! Blind

Cover

A4

Technical Specifications AC Input 100-250V, 14.8A max Frequency 45-66Hz DC Output 43.5-57.6V, 33.3A max Suitable for connection to IT systems

Top Lock Cover

A1

1 A(M3) A(M3)

2 PH1(2x) (T2)

cw

Cabinet

4

PZ2 (2x)(T1) cw

5

PZ2 (2x)

(1/2 turn)cw

3

A1

C(~M6)

C(~M6)