Date: 21.04.23File: PRO1_18E.1
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
Appendix: Technical Specifications andSpecial Features of the S7-400
Date: 21.04.23File: PRO1_18E.2
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
Technical Specifications of the S7-300 CPUs (1)CPU
Execution time per Binary instruction Load/Transfer (Word) 16 bit integer (+/-) IEEE flaoting pnt (+/-)
User memory Work memory Load memory integr. Load memory extern
Addresses Bit memories Clock memories Timers Counters
Block Types/Number FBs FCs DB's
Size of process image (inputs/outputs)
max. I/O address area
Integral interfaces
314 IFM
300 ns800 ns1500 ns<50 µs
32 KB48 KB-
2048812864
128128127
124 Byte each
752 Byte each
MPI
315-2 DP
300 ns900 ns1500 ns<35 µs
64 KB96 KB4 MB
2048812864
192192254
128 Byte each
1024 Byte each
MPI, DP
315
300 ns900 ns1500 ns<35 µs
48 KB80 KB4 MB
2048812864
192192254
128 Byte each
768 Byte each
MPI
312 IFM
700 ns2400 ns2400 ns<60 µs
6 KB20 KB-
102486432
3232127
32 Byte each
32 Byte each
MPI
314
300 ns800 nsc1500 ns<50 µs
24 KB40 KB4 MB
2048812864
128128127
128 Byte each
768 Byte each
MPI
313
700 ns2400 ns2400 ns<60 µs
12 KB20 KB4 MB
2048812864
128128127
128 Byte each
32 Byte each
MPI
316-2 DP
300 ns900 ns1500 ns<35 µs
128 KB192 KB4 MB
2048812864
256512511
128 Byte each
1024 Byte each
MPI, DP
318-2 DP
100 ns100 ns100 ns0,6 µs
512 KB64 KB4 MB
81928512512
102410242047
256 Byte each
8192 Byte each
MPI/DP, DP
Date: 21.04.23File: PRO1_18E.3
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
313
OB-No.110203540-10080-82, 85, 87121,122
1536 Byte
8 KB8
4
4
1
1
22 bytes
CPU
Organization blocksFree cycleTime-of-day interruptsTime-delay interruptsCyclic interruptsHardware interruptsBackground executionStartupErrors, asynchronous
Errors, synchronous
Local data
max. Block lengthBlock nesting depth per execution level
Program-controlled communication: max. Number of connections
Global Data communication via MPI:GD circles per CPU
Send GD packets perGD circle
Receive GD packets perGD circle
max. user data size of a packet
Technical Specifications of the S7-300 CPUs (2)314 IFM
OB-No.110203540-10080-82, 85, 87121,122
1536 Byte
8 KB8
4
4
1
1
22 bytes
315-2 DP
OB-No.110203540-10080-87
121,122
1536 Byte
16 KB8
4
4
1
1
22 bytes
315
OB-No.110203540-10080-82, 85,87121,122
1536 Byte
16 KB8
4
4
1
1
22 bytes
312 IFM
OB-No.1---40-100-
-
512 Byte
8 KB8
4
4
1
1
22 bytes
316-2 DP
OB-No.110203540-10080-87
121,122
1536 Byte
16 KB8
4
4
1
1
22 bytes
318-2 DP
OB-No.110,1120,2132,3540,4190100,10280-87
121,122
4096 Byte
64 KB16
32
8
1
2
54 bytes
314
OB-No.110203540-10080-82, 85, 87121,122
1536 Byte
8 KB8
4
4
1
1
22 bytes
Date: 21.04.23File: PRO1_18E.4
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
Technical Specifications of the S7-400 CPUs (1)
*) 1 byte = 8 digital inputs/outputs 2 bytes = 1 analog input/output
CPU
Execution time per Binary instruction Load/Transfer (word) 16-bit integer (+/-) IEEE floating pnt (+/-)
User memory Work memory Load memory integr. Load memory extern
Addresses Bit memories Clock memories Timers Counters
Block Types /Number FBs FCs DB's
Size of Process Image (inputs/outputs)
Max. I/O address area
Integral interfaces
414-1
100 ns100 ns100 ns0.6 µs
128 KB8 KB15 MB
81928256256
51210241023
256 byteseach
2 Kbyte each*)
MPI
416-1
80 ns80 ns80 ns0.48 µs
512 KB16 KB15 MB
163848512512
204820484095
512 byteseach
4 KByte each *)
MPI
414-2 DP
100 ns100 ns100 ns0.6 µs
128/384 KB8 KB15 MB
81928256256
51210241023
256 byteseach
4 Kbyte each*)
MPI, DP
412-1
200 ns200 ns200 ns1.2 µs
48 KB8 KB15 MB
40968256256
256256511
128 bytes each
0.5 Kbyte each*)
MPI
413-2 DP
200 ns200 nsc200 ns1.2 µs
72 KB8 KB15 MB
40968256256
256256511
128 byteseach
1 Kbyte each*)
MPI, DP
413-1
200 ns200 ns200 ns1.2 µs
72 KB8 KB15 MB
40968256256
256256511
128 bytes each
1 Kbyte each*)
MPI
416-2 DP
80 ns80 ns80 ns0.48 µs
0.8/1.6 MB16 KB15 MB
163848512512
204820484095
512 byteseach
8 KByte each *)
MPI, DP
417-4
100 ns100 ns100 ns0.48 µs
4...20 MB256 KB64 MB
163848512512
614461448191
1024 bytes each
16 KByte each*)
MPI,4 x DP
Date: 21.04.23File: PRO1_18E.5
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
CPU
Organization blocks Free cycle Time-of-day interrupts Time-delay interrupts Cyclic interrupts Hardware interrupts Multicomp. interrupt
Background execution Startup Errors, asynchronous Errors, synchronous
Local data
Max. block lengthBlock nesting depth per execution level
Program-controlled communication: max. number of connections
Global data communication via MPI:GD circles per CPU
Send GD packets per GD circle
Receive GD packets perGD circle
Max. user data size of a packet
Technical Specifications of the S7-400 CPUs (2)414-1
OB No.110-1320-2332-3540-436090100-10280-87121,122
8 KB
64 KB16
32
8
1
2
54 bytes
416-1
OB No.110-1720-2330-3840-476090100-10280-87121,122
16 KB
64 KB16
64
16
1
2
54 bytes
414-2 DP
OB No.110-1320-2332-3540-436090100-10180-87121,122
8 KB
64 KB16
32
8
1
2
54 bytes
412-1
OB No.110,1120,2132,3540,416090100-10280-87121,122
4 KB
64 KB16
8
8
1
2
54 bytes
413-2 DP
OB No.110,1120,2132,3540,416090100-10280-87121,122
4 KB
64 KB16
16
8
1
2
54 bytes
413-1
OB No.110,1120,2132,3540,416090100-10180-87121,122
4 KB
64 KB16
16
8
1
2
54 bytes
416-2 DP
OB No.110-1720-2330-3840-476090100-10280-87121,122
16 KB
64 KB16
64
16
1
2
54 bytes
417-4
OB No.110-1720-2330-3840-476090100-10280-87121,122
24 KB
64 KB24
64
16
1
2
54 bytes
Date: 21.04.23File: PRO1_18E.6
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
Main Differences to the S7-300
Larger memory and more I/Q/M/T/C
Addresses of input/output modules selectable
Can connect EUs from S5 and use S5 CP/IP modules
More system functions, e.g. programmed block communication
Block size up to 64KB and twice as many DBs
Complete restart and restart
Preset/actual comparison of configuration on startup
Modules can be removed without disconnecting the power supply
Several part process images
Priorities of OBs are parameter-assignable
Several OBs for cyclic, hardware and time-of-day interrupts
Block nesting up to 16 levels
Size of L Stack selectable for each execution level
4 accumulators
Multicomputimg
Date: 21.04.23File: PRO1_18E.7
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
Components of the S7- 400
CPUsCPUs
CPU 412-1CPU 413-1, 413-2 CPU 414-1, 414-2,CPU 416-1, 416-2CPU 417-4
RacksRacks
- Universal rack (UR 1/2) for use as CR and ER- Extension rack (ER 1/2)- Segmented central rack (CR2)
Signal modules (SM)Signal modules (SM)
- DI/DO 32,16,8 channels
- DO wit h relay output- AI/AO 16,8 channels- diagnostics-capable
modules
Communicationprocessors (CP)
Communicationprocessors (CP)
- Point-to-Point CP441-1, 1- channel CP441-2, 2- channel- Networks
Profibus Ethernet
Power supplies (PS)Power supplies (PS)
- AC 120V/230V, 4A/10A/20A- DC 24V, 4A/10A/20A
Function modules (FM)
Function modules (FM)
- Counting- Positioning- Closed-loop control
Date: 21.04.23File: PRO1_18E.8
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
Racks of the S7 - 400
UR1 / UR2(Universal Rack)
Type of Rack Centralrack
Extensionrack
Usable in
Yes Yes
P bus
ER1 / ER2(Extension Rack)
No Yes
P bus
K bus
CR2(Central Rack)
NoYes
P bus, Segment 1
K bus
P bus, Segment 2
Date: 21.04.23File: PRO1_18E.9
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
Module Parameters: Logical Addresses
Date: 21.04.23File: PRO1_18E.10
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
CPU Parameters: Startup
Date: 21.04.23File: PRO1_18E.11
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
CPU Parameters: Interrupts
Date: 21.04.23File: PRO1_18E.12
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
CPU Parameters: Local Data
Date: 21.04.23File: PRO1_18E.13
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
Configuring Multicomputing Operation
Date: 21.04.23File: PRO1_18E.14
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
SFC 35 for Synchronization in Multicomputing Operation
Parameter Declaration Data type Memory Description
JOB INPUT BYTE I, Q, M, D, L, Const. Task identifier (possible values: 1 to 15)
RET_VAL OUTPUT INT I, Q, M, D, L Return value (error code).
Date: 21.04.23File: PRO1_18E.15
SIMATIC S7Siemens AG 1999. All rights reserved.
Information and Training CenterKnowledge for Automation
Remove and Insert Interrupt
Module exists
Module available
Remove/Insert interrupt
Parameter assignment of module through the operating system
Removing amodule
Inserting amodule
max.
1s
max.
1s