DATA SHEET Armoured Cables SWA and AWA ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com Page1 CONSTRUCTION OF THE CABLE CONDUCTORS Current carrying component of the cable. Material Plain, stranded, compacted copper as per IEC: 60228 Aluminium, stranded, compacted conductors INSULATION The rated voltage level of the cable depends on the dielectric strength and thickness of the insulation. Material Cross-linked polyethylene (XLPE) Type GP8 as per BS 7655: Section 1.3. FILLERS For providing circular shape to the cable, non-hygroscopic compatible fillers (wherever necessary) are included between laid up cores. BEDDING Extruded bedding serves as a bedding for the armour and as a protection for the laid-up cores. Material Extruded PVC Type 9 Compound as per BS 7655. Reduced propagation flame retardant (RPLHCL)/R PPVC Compound for reduced flame propagation characteristics. ARMOUR Armour provides mechanical protection to the cable. It also serves as an Earth Continuity Conductor (ECC). One layer of round wire is applied helically over the bedding. Material 1. Galvanised round steel wire (GSWA) - FOR MULTICORE CABLE 2. Aluminium round wire armour (AWA) - FOR SINGLE CORE. OVERSHEATH - FINISH General Purpose: Extruded PVC Type 9 Compound as per BS 7655 and also meet fire test requirement of IEC 60332-1. Material 1. Medium Density Polyethylene (MDPE): Offers higher protection from water ingress and mechanical abrasion. 2. Anti-Termite: Termite resistance can be built in both types described above by compounding with proper additives. 3. Reduced Propagation (RP): Retards propagation of flame in fire situatioŶ. ;OdžLJgeŶ IŶdedž ≈ 3ϬͿ 4. Reduced Propagation and Low Acid Fumes (RPLHCL): Retards propagation of flames and gives low emission of hLJdrochloric acid fuŵes. ;OI ≈ 3Ϭ & acid gas eŵissioŶ is less thaŶ ϭ8%Ϳ CHARACTERISTICS Voltage Rating Uo/U= 0.6/1kV Temperature Rating Fixed: -25°C to +90°C Minimum Bending Radius 1.5mm2 to 16mm2 - Fixed: 6 x overall diameter 25mm2 and above - Fixed: 8 x overall diameter STANDARDS BS 5467 for XLPE insulated armoured cables BS 7889 for XLPE insulated single core unarmoured cables IEC 60502-1 for XLPE insulated single/multicore armoured/unarmoured cables IEC 60228/BS6360 for copper conductor BS 7655 for Insulation, bedding and outersheath IEC 60332 for Flame propagation CORE IDENTIFICATION 1 core Red, Black 2 core Red, Black 3 core Red, Yellow, Blue. 4 core Red, Yellow, Blue, Black. 5 core Red, Yellow, Blue, Black, Yellow/ Green APPLICATION Multi-core PVC cable with steel wire armour (SWA). Power and auxiliary fixed wiring cables for use in power networks, underground, outdoor and indoor applications and for use in cable ducting. PVC SHEATHED

Transcript of DATA SHEET ArmourCables SWA ed and AWA - Electric Way · 2021. 6. 4. · BS 7889 for XLPE insulated...

Page 1: DATA SHEET ArmourCables SWA ed and AWA - Electric Way · 2021. 6. 4. · BS 7889 for XLPE insulated single core unarmoured cables IEC 60502-1 for XLPE insulated single/multicore armoured/unarmoured

DATA SHEET

Armoured Cables SWA and AWA

ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com

Pa

ge

1

CONSTRUCTION OF THE CABLE

CONDUCTORS Current carrying component of the cable.

Material Plain, stranded, compacted copper as per IEC: 60228

Aluminium, stranded, compacted conductors

INSULATION The rated voltage level of the cable depends on the dielectric strength and thickness of the insulation.

Material Cross-linked polyethylene (XLPE) Type GP8 as per BS

7655: Section 1.3.

FILLERS For providing circular shape to the cable, non-hygroscopic compatible fillers (wherever necessary) are

included between laid up cores.

BEDDING Extruded bedding serves as a bedding for the armour and as a protection for the laid-up cores.

Material Extruded PVC Type 9 Compound as per BS 7655. Reduced propagation flame retardant (RPLHCL)/R PPVC

Compound for reduced flame propagation characteristics.

ARMOUR Armour provides mechanical protection to the cable. It also serves as an Earth Continuity Conductor (ECC).

One layer of round wire is applied helically over the bedding.

Material 1. Galvanised round steel wire (GSWA) - FOR MULTICORE CABLE

2. Aluminium round wire armour (AWA) - FOR SINGLE CORE.

OVERSHEATH - FINISH General Purpose: Extruded PVC Type 9 Compound as per BS 7655 and also meet fire test requirement of IEC

60332-1.

Material 1. Medium Density Polyethylene (MDPE): Offers higher protection from water ingress and mechanical

abrasion.

2. Anti-Termite: Termite resistance can be built in both types described above by compounding with proper

additives.

3. Reduced Propagation (RP): Retards propagation of flame in fire situatio . O ge I de ≈ 3

4. Reduced Propagation and Low Acid Fumes (RPLHCL): Retards propagation of flames and gives low emission

of h drochloric acid fu es. OI ≈ 3 & acid gas e issio is less tha 8%

CHARACTERISTICS

Voltage Rating Uo/U= 0.6/1kV

Temperature Rating Fixed: -25°C to +90°C

Minimum Bending

Radius

1.5mm2 to 16mm2 - Fixed: 6 x overall diameter

25mm2 and above - Fixed: 8 x overall diameter

STANDARDS

BS 5467 for XLPE insulated armoured cables

BS 7889 for XLPE insulated single core unarmoured cables

IEC 60502-1 for XLPE insulated single/multicore armoured/unarmoured cables

IEC 60228/BS6360 for copper conductor

BS 7655 for Insulation, bedding and outersheath

IEC 60332 for Flame propagation

CORE IDENTIFICATION

1 core Red, Black

2 core Red, Black

3 core Red, Yellow, Blue.

4 core Red, Yellow, Blue, Black.

5 core Red, Yellow, Blue, Black, Yellow/ Green

APPLICATION

Multi-core PVC cable with steel wire armour (SWA). Power and auxiliary fixed wiring cables for use in power networks, underground,

outdoor and indoor applications and for use in cable ducting.

PVC SHEATHED

Page 2: DATA SHEET ArmourCables SWA ed and AWA - Electric Way · 2021. 6. 4. · BS 7889 for XLPE insulated single core unarmoured cables IEC 60502-1 for XLPE insulated single/multicore armoured/unarmoured

DATA SHEET Armoured Cables SWA

ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com

Pa

ge

2

ITEM No. 1 2 3 4

Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 2 x 1.5 2 x 2.5 2 x 4 2 x 10

1 Type of Cable CU/XLPE/PVC/SWA/PVC

2 Standard BS 5467

3 Nominal voltage rating Volts 600/1000

4 Max. continuous current carrying capacity when laid

In air Amps 29 39 52 90

In ground Amps 38 49 65 109

In duct Amps 31 41 53 89

5 Conductors :

Material Plain Annealed Copper

No. of Cores No. 2 2 2 2

Nominal cross section mm² 1.5 2.5 4 10

6 Insulation of conductors :

Material XLPE

Minimum average thickness mm 0.6 0.7 0.7 0.7

7 Bedding :

Material Extruded PVC

Nominal thickness mm 0.8 0.8 0.8 0.8

Approx.diameter over bedding mm 7.8 9 10.1 13

8 Armouring :

Material Galvanised steel wire.

Armour wire dia. mm 0.9 0.9 0.9 0.9

Approx. diameter over armour mm 9.5 10.7 11.8 14.7

9 Sheath :

Material Extruded PVC

Nominal thickness mm 1.3 1.4 1.4 1.5

Approx. outer diameter of cable. mm 11.5 12.9 14 17

10 Maximum DC Resistance of conductor at 20°C Ohm/km 12.1 7.41 4.61 1.83

11 Maximum AC Resistance per core at 90°C(Approx) Ohm/km 15.4 9.45 5.88 2.33

12 AC Impedance per phase at 90°C(Approx) Ohm/km 15.4 9.45 5.88 2.33

13 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.1 0.098 0.092 0.08

14 Maximum Conductor short circuit capacity for one sec : kA 0.215 0.358 0.57 1.43

15 Max.conductor operating temperature. °C 90

16 Max. Conductor permissible temp under SC conditions. °C 250

17 Voltage drop mv/Amp/mt 31 19 12 4.7

18 Max. allowable tensile strength Kgf 18 30 48 120

19 Minimum allowable bending radius mm *6D *6D *6D *6D

20 Approx. weight of completed cable. kg/km 275 340 420 640

21 Conditions of installations :

Soil thermal resistivity °C m/W 1.2

Ground temperature °C 15

Air temperature °C 30

Burial depth meters 0.5

Note : *D = Overall diameter

PVC SHEATHED

Page 3: DATA SHEET ArmourCables SWA ed and AWA - Electric Way · 2021. 6. 4. · BS 7889 for XLPE insulated single core unarmoured cables IEC 60502-1 for XLPE insulated single/multicore armoured/unarmoured

DATA SHEET Armoured Cables SWA

ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com

Pa

ge

3

ITEM No. 5 6 7

Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 2 x 6 2X16 2X25

1 Type of Cable CU/XLPE/PVC/SWA/PVC

2 Standard BS 5467

3 Nominal voltage rating Volts 600/1000

Number of Core(s) Nos 2 2 2

Nominal cross sectional area mm2 6 16 25

Approx. Diameter of Conductor mm 2.92 4.7 6.15

4 Insulation - XLPE

Color (s) Red, Black

Nominal Thickness mm 0.7 0.7 0.9

Approx. Diameter over Insulation mm 4.4 6.2 8.1

5 Core Laid up

Approx. Diameter over Laid Up mm 8.8 12.4 16.1

6 Extruded Bedding - PVC

Nominal Thickness mm 0.8 0.8 0.8

Approx. Diameter over bedding mm 10.9 14.5 18.2

7 Armor - Type: Steel Wire

Nominal Diameter of wire mm 0.9 1.25 1.25

Approx. Diameter over armour mm 12.6 16.9 20.6

8 Extruded Outer Sheath - PVC (Black)

Nominal Thickness mm 1.4 1.5 1.6

Approx. Diameter over outer sheath mm 14.8 19.2 23.1

9 Approx. Weight of complete cable kg / km 476 835 1171

Max. DC Resistance of Conductor at 20°C Ohm/km 3.08 1.15 0.727

Approx. AC Resistance of Conductor at Maximum

Operating Temperature Ohm/km 3.9274 1.4666 0.9273

Approx. Capacitance uF / km 0.42 0.39 0.41

Approx. Inductance mH / km 0.3 0.26 0.25

Approx. Inductive Reactance Ohm/km 0.088 0.081 0.079

Approx. Impedance Ohm/km 3.93 1.47 0.927

Approx. Voltage Drop mV/Amp/mt 7.9 2.9 1.9

10 CURRENT CARRYING CAPACITY based on the conditions

specified

Installation Type (Single Circuit)

Soil Thermal Resistivity oC.m/W 1.2 1.2 1.2

Ground temperature ˚C 15 15 15

Ambient air temperature ˚C 30 30 30

Burial depth mm 500 500 500

Laid in ground Amps 81 140 180

Laid in Duct Amps 67 115 145

In air Amps 66 115 152

Maximum conductor temperature for continuous

operation / Short Circuit Operation ˚C 90/250 90/250

90/25

0

11 Installation Parameters

Maximum pulling force (For Conductor) kgf 72 192 300

Minimum Bending Radius mm 90 120 144

PVC SHEATHED

Page 4: DATA SHEET ArmourCables SWA ed and AWA - Electric Way · 2021. 6. 4. · BS 7889 for XLPE insulated single core unarmoured cables IEC 60502-1 for XLPE insulated single/multicore armoured/unarmoured

DATA SHEET Armoured Cables SWA

ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com

Pa

ge

4

ITEM No. 1 2 3 4 5

Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 3 x 1.5 3 x 2.5 3 x 4 3 x 6 3 x 10

1 Type of Cable CU/XLPE/PVC/SWA/PVC

2 Standard BS 5467

3 Nominal voltage rating Volts 600/1000

4 Max. continuous current carrying capacity when laid

In air Amps 25 33 44 56 78

In ground Amps 32 42 55 69 92

In duct Amps 26 34 45 56 75

5 Conductors :

Material Plain Annealed Copper

No. of Cores No. 3 3 3 3 3

Nominal cross section mm² 1.5 2.5 4 6 10

6 Insulation of conductors :

Material XLPE

Minimum average thickness mm 0.6 0.7 0.7 0.7 0.7

7 Bedding :

Material Extruded PVC

Nominal thickness mm 0.8 0.8 0.8 0.8 0.8

Approx.diameter over bedding mm 8.3 9.6 10.7 11.9 13.9

8 Armouring :

Material Galvanised steel wire.

Armour wire dia. mm 0.9 0.9 0.9 0.9 1.25

Approx. diameter over armour mm 10 11.3 12.4 13.6 16.3

9 Sheath :

Material Extruded PVC

Nominal thickness mm 1.3 1.4 1.4 1.4 1.5

Approx. outer diameter of cable. mm 12 13.5 14.6 15.8 18.6

10 Maximum DC Resistance of conductor at 20°C Ohm/km 12.1 7.41 4.61 3.08 1.83

11 Maximum AC Resistance per core at 90°C(Approx) Ohm/km 15.4 9.45 5.88 3.93 2.33

12 AC Impedance per phase at 90°C(Approx) Ohm/km 15.4 9.45 5.88 3.93 2.33

13 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.1 0.098 0.092 0.088 0.083

14 Maximum Conductor short circuit capacity for one sec : kA 0.22 0.358 0.57 0.858 1.43

15 Max.conductor operating temperature. °C 90

16 Max. Conductor permissible temp under SC conditions. °C 250

17 Voltage drop mv/Amp/mt 27 16 10 6.8 4

18 Max. allowable tensile strength Kgf 27 45 72 108 180

19 Minimum allowable bending radius mm *6D *6D *6D *6D *6D

20 Approx. weight of completed cable. kg/km 300 385 460 570 835

21 Conditions of installations :

Soil thermal resistivity °C m/W 1.2

Ground temperature °C 15

Air temperature °C 30

Burial depth meters 0.5

Note : *D = Overall diameter

PVC SHEATHED

Page 5: DATA SHEET ArmourCables SWA ed and AWA - Electric Way · 2021. 6. 4. · BS 7889 for XLPE insulated single core unarmoured cables IEC 60502-1 for XLPE insulated single/multicore armoured/unarmoured

DATA SHEET Armoured Cables SWA

ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com

Pa

ge

5

ITEM No. 6 7 8 9 10

Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 3 x 16 3 x 25 3 x 35 3x50 3x70

1 Type of Cable CU/XLPE/PVC/SWA/PVC

2 Standard BS 5467

3 Nominal voltage rating Volts 600/1000

4 Max. continuous current carrying capacity when laid

In air Amps 99 131 162 197 251

In ground Amps 115 150 180 215 265

In duct Amps 94 125 150 175 215

5 Conductors :

Material Plain Annealed Copper

No. of Cores No. 3 3 3 3 3

Nominal cross section mm² 16 25 35 50 70

6 Insulation of conductors :

Material XLPE

Minimum average thickness mm 0.7 0.9 0.9 1 1.1

7 Bedding :

Material Extruded PVC

Nominal thickness mm 0.8 1 1 1 1

Approx.diameter over bedding mm 15.8 17.6 19.6 23.1 25.2

8 Armouring :

Material Galvanised steel wire.

Armour wire dia. mm 1.25 1.6 1.6 1.6 2

Approx. diameter over armour mm 18.2 20.7 22.7 25 28.3

9 Sheath :

Material Extruded PVC

Nominal thickness mm 1.6 1.7 1.8 1.8 1.9

Approx. outer diameter of cable. mm 20.7 23.3 25.5 29 31.3

10 Maximum DC Resistance of conductor at 20°C Ohm/km 1.15 0.727 0.524 0.387 0.268

11 Maximum AC Resistance per core at 90°C(Approx) Ohm/km 1.47 0.927 0.668 0.494 0.342

12 AC Impedance per phase at 90°C(Approx) Ohm/km 1.47 0.93 0.67 0.5 0.35

13 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.08 0.079 0.077 0.076 0.075

14 Maximum Conductor short circuit capacity for one sec : kA 2.29 3.58 5.01 7.15 10.1

15 Max.conductor operating temperature. °C 90

16 Max. Conductor permissible temp under SC conditions. °C 250

17 Voltage drop mv/Amp/mt 2.6 1.6 1.2 0.87 0.61

18 Max. allowable tensile strength Kgf 288 450 630 900 1260

19 Minimum allowable bending radius mm *6D *6D *6D *8D *8D

20 Approx. weight of completed cable. kg/km 1065 1550 1850 2380 3060

21 Conditions of installations :

Soil thermal resistivity °C m/W 1.2

Ground temperature °C 15

Air temperature °C 30

Burial depth meters 0.5

Note : *D = Overall diameter

PVC SHEATHED

Page 6: DATA SHEET ArmourCables SWA ed and AWA - Electric Way · 2021. 6. 4. · BS 7889 for XLPE insulated single core unarmoured cables IEC 60502-1 for XLPE insulated single/multicore armoured/unarmoured

DATA SHEET Armoured Cables SWA

ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com

Pa

ge

6

ITEM No. 11 12 13 14 15 16

Sr

# Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 3x95 3x120 3x150 3x185 3x240 3x300

1 Type of Cable CU/XLPE/PVC/SWA/PVC

2 Standard BS 5467

3 Nominal voltage rating Volts 600/1000

4 Max. continuous current carrying capacity

when laid

In air Amps 304 353 406 463 546 628

In ground Amps 315 360 405 460 530 590

In duct Amps 260 300 335 380 440 495

5 Conductors :

Material Plain Annealed Copper

No. of Cores No. 3 3 3 3 3 3

Nominal cross section mm² 95 120 150 185 240 300

6 Insulation of conductors :

Material XLPE

Minimum average thickness mm 1.1 1.2 1.4 1.6 1.7 1.8

7 Bedding :

Material Extruded PVC

Nominal thickness mm 1.2 1.2 1.4 1.4 1.4 1.6

Approx.diameter over bedding mm 28.8 32.1 36 40.5 44.8 50.4

8 Armouring :

Material Galvanised steel wire.

Armour wire dia. mm 2 2.5 2.5 2.5 2.5 2.5

Approx. diameter over armour mm 32.7 36 40.9 45.4 49.7 55.2

9 Sheath :

Material Extruded PVC

Nominal thickness mm 2.1 2.2 2.3 2.4 2.6 2.7

Approx. outer diameter of cable. mm 36.1 39.6 44.7 49.3 54 59.7

10 Maximum DC Resistance of conductor at 20°C Ohm/km 0.19 0.153 0.124 0.099 0.075 0.06

11 Maximum AC Resistance per core at

90°C(Approx) Ohm/km 0.25 0.197 0.16 0.128 0.099 0.08

12 AC Impedance per phase at 90°C(Approx) Ohm/km 0.26 0.21 0.18 0.15 0.12 0.11

13 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.07 0.072 0.073 0.073 0.072 0.072

14 Maximum Conductor short circuit capacity for

one sec : kA 13.6 17.2 21.5 26.5 34.4 42.9

15 Max.conductor operating temperature. °C 90

16 Max. Conductor permissible temp under SC

conditions. °C 250

17 Voltage drop mv/Amp/mt 0.45 0.36 0.3 0.25 0.21 0.19

18 Max. allowable tensile strength Kgf 1710 2000 2000 2000 2000 2000

19 Minimum allowable bending radius mm *8D *8D *8D *8D *8D *8D

20 Approx. weight of completed cable. kg/km 4180 5050 6400 7770 9650 11725

21 Conditions of installations :

Soil thermal resistivity °C m/W 1.2

Ground temperature °C 15

Air temperature °C 30

Burial depth meters 0.5

Note : *D = Overall diameter

PVC SHEATHED

Page 7: DATA SHEET ArmourCables SWA ed and AWA - Electric Way · 2021. 6. 4. · BS 7889 for XLPE insulated single core unarmoured cables IEC 60502-1 for XLPE insulated single/multicore armoured/unarmoured

DATA SHEET Armoured Cables SWA

ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com

Pa

ge

7

ITEM No. 1 2 3 4 5

Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 4 x 1.5 4 x 2.5 4 x 4 4 x 6 4 x 10

Manufacturer DUBAI CABLE COMPANY (PVT) LTD.

2 Country of Origin U.A.E

3 Type of Cable CU/XLPE/PVC/SWA/PVC

4 Standard BS 5467

5 Nominal voltage rating Volts 600/1000

6 Max. continuous current carrying capacity when laid

In air Amps 25 33 44 56 78

In ground Amps 32 42 55 69 92

In duct Amps 26 34 45 56 75

7 Conductors :

Material Plain Annealed Copper

No. of Cores No. 4 4 4 4 4

Nominal cross section mm² 1.5 2.5 4 6 10

8 Insulation of conductors :

Material XLPE

Minimum average thickness mm 0.6 0.7 0.7 0.7 0.7

9 Bedding :

Material Extruded PVC

Nominal thickness mm 0.8 0.8 0.8 0.8 0.8

Approx.diameter over bedding mm 9.0 10.5 11.8 13.1 15.3

10 Armouring :

Material Galvanised steel wire

Armour wire dia. mm 0.90 0.90 0.9 1.25 1.25

Approx. diameter over armour mm 10.7 12.2 13.5 15.5 17.7

11 Sheath :

Material Extruded PVC

Nominal thickness mm 1.3 1.4 1.4 1.5 1.5

Approx. outer diameter of cable. mm 12.7 14.4 15.7 17.8 20.0

12 Maximum DC Resistance of conductor at 20°C Ohm/km 12.1 7.41 4.61 3.08 1.83

13 Maximum AC Resistance per core at 90°C(Approx) Ohm/km 15.4 9.45 5.88 3.93 2.33

14 AC Impedance per phase at 90°C(Approx) Ohm/km 15.4 9.45 5.88 3.93 2.33

15 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.1 0.098 0.092 0.088 0.083

16 Maximum Conductor short circuit capacity for one sec : kA 0.215 0.358 0.570 0.858 1.430

17 Max.conductor operating temperature. °C 90

18 Max. Conductor permissible temp under SC conditions. °C 250

19 Voltage drop mv/Amp/mt 27 15 10 6.2 4

20 Max. allowable tensile strength Kgf 36 60 96 144 240

21 Minimum allowable bending radius mm *6D *6D *6D *6D *6D

22 Approx. weight of completed cable. kg/km 355 445 550 760 985

23 Conditions of installations :

Soil thermal resistivity °C m/W 1.2

Ground temperature °C 15

Air temperature °C 30

Burial depth meters 0.5

Note : *D = Overall diameter

PVC SHEATHED

Page 8: DATA SHEET ArmourCables SWA ed and AWA - Electric Way · 2021. 6. 4. · BS 7889 for XLPE insulated single core unarmoured cables IEC 60502-1 for XLPE insulated single/multicore armoured/unarmoured

DATA SHEET Armoured Cables SWA

ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com

Pa

ge

8

ITEM No. 1 2 3 4 5 6

Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95

1 Manufacturer DUBAI CABLE COMPANY (PVT) LTD.

2 Country of Origin U.A.E

3 Type of Cable CU/XLPE/PVC/SWA/PVC

4 Standard BS 5467

5 Nominal voltage rating Volts 600/1000

6 Max. continuous current carrying capacity when laid

In air Amps 99 131 162 197 251 304

In ground Amps 115 150 180 215 265 315

In duct Amps 94 125 150 175 215 260

7 Conductors :

Material Plain Annealed Copper

No. of Cores No. 4 4 4 4 4 4

Nominal cross section mm² 16 25 35 50 70 95

8 Insulation of conductors :

Material XLPE

Minimum average thickness mm 0.7 0.9 0.9 1.0 1.1 1.1

9 Bedding :

Material Extruded PVC

Nominal thickness mm 0.8 1.0 1.0 1.0 1.2 1.2

Approx.diameter over bedding mm 17.5 19.9 22.7 25.4 29.1 33.1

10 Armouring :

Material Galvanised steel wire.

Armour wire dia. mm 1.25 1.6 1.6 1.6 2.0 2.0

Approx. diameter over armour mm 19.9 23.0 25.8 28.5 33.0 37.0

11 Sheath :

Material Extruded PVC

Nominal thickness mm 1.6 1.7 1.8 1.9 2.1 2.2

Approx. outer diameter of cable. mm 22.4 25.6 28.6 31.5 36.4 40.6

12 Maximum DC Resistance of conductor at 20°C Ohm/km 1.15 0.727 0.524 0.387 0.268 0.193

13 Maximum AC Resistance per core at 90°C(Approx) Ohm/km 1.47 0.927 0.668 0.494 0.342 0.247

14 AC Impedance per phase at 90°C(Approx) Ohm/km 1.47 0.93 0.67 0.5 0.35 0.26

15 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.081 0.079 0.077 0.076 0.075 0.073

16 Maximum Conductor short circuit capacity for one sec : kA 2.29 3.58 5.01 7.15 10.10 13.60

17 Max.conductor operating temperature. °C 90

18 Max. Conductor permissible temp under SC conditions. °C 250

19 Voltage drop mv/Amp/mt 2.6 1.6 1.2 0.87 0.61 0.45

20 Max. allowable tensile strength Kgf 384 600 840 1200 1680 2000

21 Minimum allowable bending radius mm *6D *8D *8D *8D *8D *8D

22 Approx. weight of completed cable. kg/km 1300 1840 2340 2930 4130 5300

23 Conditions of installations :

Soil thermal resistivity °C m/W 1.2

Ground temperature °C 15

Air temperature °C 30

Burial depth meters 0.5

Note : *D = Overall diameter

PVC SHEATHED

Page 9: DATA SHEET ArmourCables SWA ed and AWA - Electric Way · 2021. 6. 4. · BS 7889 for XLPE insulated single core unarmoured cables IEC 60502-1 for XLPE insulated single/multicore armoured/unarmoured

DATA SHEET Armoured Cables SWA

ELECTRICWAY | Data Sheet - Armoured Cables SWA and AWA TEL +971-04-48170777 | FAX +971-04-8825700 | www.electricway.com

Pa

ge

9

ITEM No. 7 8 9 10 11 12

Sr # Cu/XLPE/PVC/SWA/PVC - BS 5467 UNIT 4 x 120 4 x 150 4 x 185 4 x 240 4 x 300 4 x 400

1 Manufacturer DUBAI CABLE COMPANY (PVT) LTD

2 Country of Origin U.A.E

3 Type of Cable CU/XLPE/PVC/SWA/PVC

4 Standard BS 5467

5 Nominal voltage rating Volts 600/1000

6 Max. continuous current carrying capacity when laid

In air Amps 353 406 463 546 628 728

In ground Amps 360 405 460 530 590 667

In duct Amps 300 335 380 440 495 570

7 Conductors :

Material Plain Annealed Copper

No. of Cores No. 4 4 4 4 4 4

Nominal cross section mm² 120 150 185 240 300 400

8 Insulation of conductors :

Material XLPE

Minimum average thickness mm 1.2 1.4 1.6 1.7 1.8 2.0

9 Bedding :

Material Extruded PVC

Nominal thickness mm 1.4 1.4 1.4 1.6 1.6 1.8

Approx.diameter over bedding mm 36.5 40.6 45.6 51.0 56.5 63.9

10 Armouring :

Material Galvanised steel wire.

Armour wire dia. mm 2.5 2.5 2.5 2.5 2.5 3.15

Approx. diameter over armour mm 41.4 45.5 50.5 55.8 61.3 70.0

11 Sheath :

Material Extruded PVC

Nominal thickness mm 2.3 2.4 2.6 2.7 2.9 3.2

Approx. outer diameter of cable. mm 45.2 49.4 54.8 60.3 66.2 75.4

12 Maximum DC Resistance of conductor at 20°C Ohm/km 0.153 0.124 0.0991 0.0754 0.0601 0.0470

13 Maximum AC Resistance per core at 90°C(Approx) Ohm/km 0.197 0.16 0.128 0.0989 0.0802 0.0641

14 AC Impedance per phase at 90°C(Approx) Ohm/km 0.21 0.18 0.15 0.12 0.11 0.1

15 Star reactance per phase at 50 Hz(Approx) Ohm/km 0.072 0.073 0.073 0.072 0.072 0.072

16 Maximum Conductor short circuit capacity for one sec : kA 17.20 21.50 26.50 34.40 42.90 57.20

17 Max.conductor operating temperature. °C 90

18 Max. Conductor permissible temp under SC conditions. °C 250

19 Voltage drop mv/Amp/mt 0.36 0.3 0.25 0.21 0.19 0.18

20 Max. allowable tensile strength Kgf 2000 2000 2000 2000 2000 2000

21 Minimum allowable bending radius mm *8D *8D *8D *8D *8D *8D

22 Approx. weight of completed cable. kg/km 6750 8110 9800 12320 14910 19280

23 Conditions of installations :

Soil thermal resistivity °C m/W 1.2

Ground temperature °C 15

Air temperature °C 30

Burial depth meters 0.5

Note : *D = Overall diameter

Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)Powered by TCPDF (www.tcpdf.org)