Data Mate

44
5/26/2018 DataMate-slidepdf.com http://slidepdf.com/reader/full/data-mate-56206a985cc54 1/44 Liebert ®  DataMate ™  –1.5 to 3 Tons (5 to 10.5kW) Capacity Technical Data Manual– Air, Water/Glycol and Chilled Water Units, 50 & 60Hz

Transcript of Data Mate

  • Liebert DataMate1.5 to 3 Tons (5 to 10.5kW) CapacityTechnical Data Manual Air, Water/Glycol and Chilled Water Units, 50 & 60Hz

  • iTABLE OF CONTENTS1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11.1 Designed to Match Computer and Electronic Equipment NeedsFrom Installation

    to Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

    2.0 STANDARD FEATURES1.5- TO 3-TON SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22.1 Evaporator SectionSplit-Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    2.2 Condensing Unit SectionRemote Split-Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    2.2.1 Indoor Centrifugal Fan Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.2.2 Outdoor Prop Fan Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.2.3 Indoor Remote Water/Glycol Condensing Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    2.3 Condensing Unit SectionClose-Coupled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    2.4 Chilled Water Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

    2.5 System Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    2.5.1 Other Standard Control Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    3.0 OPTIONAL FACTORY-INSTALLED FEATURESEVAPORATOR/CHILLED WATER ANDCONDENSING UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

    3.1 Electric Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    3.2 Humidifier/Electric Reheat Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    3.3 Optional ConfigurationsProp Fan Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    3.4 Optional ConfigurationsIndoor Remote Water/Glycol Condensing Units . . . . . . . . . . . . . . 4

    4.0 SHIP-LOOSE ACCESSORIESFIELD-INSTALLED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54.1 Remote Monitoring, Autochangeover and Leak Detection Equipment. . . . . . . . . . . . . . . . . . 6

    5.0 FLEXIBLE CONFIGURATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76.0 AIR-COOLED SYSTEMSCAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . .87.0 WATER/GLYCOL SYSTEMSCAPACITIES AND DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . .148.0 CHILLED WATER SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .219.0 ELECTRICAL DATAALL UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2410.0 REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2711.0 GLYCOL LOOP PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2912.0 MODEL NUMBER NOMENCLATUREALL SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30GUIDE SPECIFICATIONSFOR LIEBERT DATAMATE 1.5- TO 3-TON (5 TO 10.5KW). . . . . . . . . . . .321.0 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 322.0 PRODUCT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323.0 EXECUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

  • ii

    FIGURESFigure 1 Wall-box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Figure 2 Flexible configurationsAll systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Figure 3 General arrangement, air-cooled split systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Figure 4 Dimensions, evaporator unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Figure 5 Cabinet and floor planning dimensionsOutdoor air-cooled condensing units . . . . . . . . . . . . . . 12Figure 6 Dimensions, indoor air-cooled condensing units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Figure 7 General arrangement, water/glycol, split systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Figure 8 General arrangement, water/glycol systems, close-coupled condensing unit . . . . . . . . . . . . . . . . 16Figure 9 Dimensions, evaporator unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17Figure 10 Dimensions and piping, close-coupled water/glycol condensing unit. . . . . . . . . . . . . . . . . . . . . . . 18Figure 11 Cabinet dimensions and piping data, water/glycol indoor remote condensing modules. . . . . . . . 20Figure 12 General arrangementChilled water systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Figure 13 DimensionsChilled water unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Figure 14 Step-down transformer for 277V input power applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26Figure 15 Refrigerant piping diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28Figure 16 Heat rejection loop, multiple drycoolers and multiple indoor units. . . . . . . . . . . . . . . . . . . . . . . . 29Figure 17 Model number nomenclatureEvaporator units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Figure 18 Model number nomenclatureOutdoor air-cooled condensing units . . . . . . . . . . . . . . . . . . . . . . 30Figure 19 Model number nomenclatureIndoor air-cooled condensing units. . . . . . . . . . . . . . . . . . . . . . . . 30Figure 20 Model number nomenclature, close-coupled water/glycol condensing units60Hz only . . . . . . . 31Figure 21 Model number nomenclatureIndoor remote water/glycol-cooled condensing units. . . . . . . . . . 31Figure 22 Model number nomenclatureChilled water units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

  • iii

    TABLESTable 1 60Hz capacities & typical specifications, air-cooled applications. . . . . . . . . . . . . . . . . . . . . . . . . . . 8Table 2 50Hz capacities & typical specifications, air-cooled applications. . . . . . . . . . . . . . . . . . . . . . . . . . . 9Table 3 Evaporator section dimensionsair-cooled applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Table 4 Evaporator unit refrigerant connectionspipe size/coupling number . . . . . . . . . . . . . . . . . . . . . 11Table 5 Propeller fan, air-cooled condensing unit dimensions, inches (mm) . . . . . . . . . . . . . . . . . . . . . . . 12Table 6 Remote centrifugal fan, air-cooled condensing, weight and dimensions . . . . . . . . . . . . . . . . . . . . 13Table 7 60Hz capacities & typical specifications, water-cooled and glycol-cooled applications. . . . . . . . . 14Table 8 50Hz capacities & typical specifications, water-cooled and glycol-cooled applications. . . . . . . . . 15Table 9 Evaporator section dimensionswater/ glycol-cooled applications . . . . . . . . . . . . . . . . . . . . . . . . 17Table 10 Evaporator unit refrigerant connectionspipe size/coupling number . . . . . . . . . . . . . . . . . . . . . 17Table 11 Unit refrigerant connection sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Table 12 Net weight, water/glycol condensing units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Table 13 Net weight, indoor water/glycol-cooled condensing unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Table 14 Chilled water data, 50/60Hz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Table 15 Chilled water capacity correction factors based on 10F (5.6C) water rise . . . . . . . . . . . . . . . . . 22Table 16 Net weights and dimensions, chilled water units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Table 17 Electrical data, split system evaporator or chilled water unit, 60/50Hz . . . . . . . . . . . . . . . . . . . . 24Table 18 60Hz electrical data, evaporator with close-coupled water/glycol condensing unit with

    common power feed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Table 19 60Hz electrical data, outdoor air-cooled condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Table 20 50Hz electrical data, outdoor air-cooled condensing unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Table 21 Electrical data, indoor air & water/glycol remote condensing units, 50 & 60Hz . . . . . . . . . . . . . 26Table 22 Refrigerant charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Table 23 Recommended refrigerant line sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Table 24 Pipe length and condenser elevation relative to evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Table 25 Refrigerant charge in Liebert pre-charged R-407C line sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Table 26 Line charges - refrigerant per 100 ft. (30m) of Type L copper tube . . . . . . . . . . . . . . . . . . . . . . . . 28Table 27 Equivalent lengths for various pipe fittings, ft (m). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

  • iv

  • Introduction

    1 Liebert DataMate

    1.0 INTRODUCTION

    1.1 Designed to Match Computer and Electronic Equipment NeedsFrom Installation to OperationInstalled on the floor or on the wall, Liebert DataMate Precision Cooling systems control the cooling, humidity and air distribution required by sensitive electronic equipment. A range of sizes and configurations is available to meet varying sites needs.

    The Liebert DataMate is also easy to use. Advanced microprocessor technology allows easy, precise control and menu-driven monitoring keeps you informed of system operation through the LCD readout.

    These features, combined with Emerson quality construction and reliable components, guarantee satisfaction from installation through operation.

    Liebert Precision CoolingLiebert Precision Cooling systems are designed to control the environment required for computers and other sensitive electronic equipment. The Liebert DataMate provides complete control on an around-the-clock basis and the high sensible heat ratio required by sensitive electronic equipment.

    Easy InstallationThe Liebert DataMate is a split-system evaporator combined with a remote air-, water- or glycol-cooled condensing unit or a close-coupled water/glycol-cooled condensing unit or is a self-contained, chilled water unit.

    Each split system has thermostat-type wiring to controls and condensing unit. System components are pre-charged with refrigerant using quick-connect fittings and can be easily connected together. Optional pre-charged line sets or sweat adapters for field refrigerant piping are available for remote condensing units.

    Easy to ServiceThe Liebert DataMate is designed for front service access. Routine maintenance and service can be performed quickly and easily. Spare parts are always in Emerson inventory and available on short notice.

    Advanced Control TechnologyA menu-driven microprocessor control system provides precise temperature and humidity control and accurate alarm setpoints. Using touch-sensitive buttons, the wall-mounted monitor/control panel allows you to select and display temperature and other monitored parameters.

    High EfficiencyHigh sensible heat ratio, scroll compressor and precise microprocessor control allow the system to operate efficiently.

    Space Saving DesignModels available to fit any room without disrupting workstation layout. Requires 5 ft2 (0.5m2) or less of floor space or can be mounted on a wall.

    ReliableThe Liebert DataMate installed base is a testimony to the system reliability.

    Agency ListedStandard 60Hz units are CSA certified to the harmonized U.S. and Canadian product safety standard, CSA C22.2 No 236/UL 1995 for Heating and Cooling Equipment and are marked with the CSA c-us logo.

    C US

  • Standard Features1.5- to 3-Ton Systems

    Liebert DataMate 2

    2.0 STANDARD FEATURES1.5- TO 3-TON SYSTEMS

    2.1 Evaporator SectionSplit-SystemsThe Liebert DataMate is available as a split system air, water/glycol-cooled unit or self-contained chilled water unit.

    Split-System Evaporator Section includes the evaporator coil, 2-speed centrifugal blower assembly, filter-drier, galvanized steel drain pan, R-407C refrigerant charge, cleanable filters and microprocessor control with wall-mounted display panel. The unit construction is galvanized steel with powder-coated, removable exterior panels. A reversible discharge grille provides the ability to redirect airflow. The evaporator can be floor- or wall-mounted.

    2.2 Condensing Unit SectionRemote Split-Systems2.2.1 Indoor Centrifugal Fan Condensing Units

    Indoor Air-Cooled Centrifugal Fan Condensing Units include scroll compressor, factory-mounted disconnect switch, condenser coil, R-407C unit charge, belt-driven centrifugal blower assembly, high-pressure switch, Liebert Lee-Temp head pressure control system, hot gas bypass and liquid-line solenoid valve. Unit must be mounted indoors. Condensing unit is designed to use outdoor air with temperatures ranging from -30F to 95F (-34C to 35C). Available in 2- & 3-Ton models.

    2.2.2 Outdoor Prop Fan Condensing UnitsOutdoor Prop Fan Condensing Units include scroll compressor, condenser coil, R-407C unit charge, prop fan, liquid-line solenoid valve, high pressure switch, Liebert Lee-Temp head pressure control and hot gas bypass. Condensing unit is designed for outdoor locations with operating ambients ranging from -30F to 95F (-34C to 35C).

    2.2.3 Indoor Remote Water/Glycol Condensing UnitsIndoor Remote Water/Glycol Condensing Units include scroll compressor, R-407C unit charge, factory-mounted disconnect, coaxial condenser, hot gas bypass, high head pressure switch and two-way water regulating valve designed for 150psi (1034.3kPa). Condensing units can be used on either a water or glycol cooling loop. Available in 2- and 3-ton models.

    2.3 Condensing Unit SectionClose-CoupledThe Close-Coupled Water/Glycol Condensing Unit is designed to attach to the split-system evaporator to become a single wall- or floor-mounted unit.

    Indoor close-coupled water/glycol condensing units include scroll compressor, brazed plate condenser, R-407C refrigerant charge and 2-way water regulating valve. Unit is available in 60Hz models only. Design pressure is 150psi (1034kPa).

    2.4 Chilled Water UnitsSelf-Contained Chilled Water Models include a chilled water coil, a two-way, solenoid open, slow-close (On/Off) spring-return valve, two-speed centrifugal blower assembly, cleanable filters and microprocessor control with wall-mounted display panel. Design pressure is 125psi (862kPa).

  • Standard Features1.5- to 3-Ton Systems

    3 Liebert DataMate

    2.5 System ControlsSystem controls include a microprocessor control board mounted in the evaporator/chilled water unit and a wall-mounted interface with a two-line, 16-character liquid crystal display. An eight-key, membrane keypad for setpoint/program control, unit On/Off, fan speed and alarm silence is below the LCD screen. It provides temperature setpoint and sensitivity adjustment, humidity setpoint and sensitivity adjustment, digital display of temperature, humidity, setpoints, sensitivities, fan speed and alarm conditions.

    The wall-box is field-wired to the microprocessor control using standard four-conductor thermostat wire (field-supplied). The temperature and humidity sensors are in the wall box, which can be installed up to 300 feet (91.4m) from the evaporator unit. The unit-mounted control board also includes common alarm terminals and shutdown terminals. The unit automatically restarts after a power outage.

    Figure 1 Wall-box

    2.5.1 Other Standard Control Features

    Adjustable auto restart Calibrate sensors

    5 day/2 day setback Predictive humidity control

    Password protection Common alarm output

    Alarm enable/disable Remote shutdown terminals

    Self-diagnostics

  • Optional Factory-Installed FeaturesEvaporator/Chilled Water and Condensing Units

    Liebert DataMate 4

    3.0 OPTIONAL FACTORY-INSTALLED FEATURESEVAPORATOR/CHILLED WATER AND CONDENSING UNITS

    3.1 Electric ReheatElectric low watt tubular reheat element with non-corrosive metal sheath provides one stage of non-ionizing reheat to maintain room dry bulb temperature.

    3.2 Humidifier/Electric Reheat PackageThe humidifier and electric reheat are available as a package for complete humidity control. The canister humidifier includes a steam-generating type humidifier with automatic flushing circuit, inlet strainer, drain, 1" (25.4mm) air gap on fill line and solenoid valves. Humidifier problem alarm annunciates at the wall-mounted display panel. Maximum humidifier water supply pressure is 150psi (1034kPa).

    3.3 Optional ConfigurationsProp Fan Condensing UnitsOutdoor Prop Fan Condensing Units are also available in the following optional configurations:

    High ambient models for providing catalog capacities at ambient temperatures up to 105F (40C): 2- and 3-ton models only.

    Liebert Quiet-Line models for low noise level conditions (below 58 dBA) and for providing catalog capacities at ambient temperatures up to 95F (35C).

    Condenser coils can be phenolic-coated for extended coil life in coastal areas.

    3.4 Optional ConfigurationsIndoor Remote Water/Glycol Condensing UnitsIndoor Remote Water/Glycol Condensing Units are also available with the following piping options:

    Two-way water regulating valve with 350psi (2413kPa) design pressure Three-way water regulating valve with 150psi (1034kPa) design pressure Three-way water regulating valve with 350psi (2413kPa) design pressure

  • Ship-Loose AccessoriesField-Installed

    5 Liebert DataMate

    4.0 SHIP-LOOSE ACCESSORIESFIELD-INSTALLED

    The Condensate Pump is field-mounted internal to the unit and wired to the unit power block or is field-mounted external to the unit with power from unit or external power supply. Pump is complete with integral float switch, discharge check valve, pump, motor assembly and reservoir. A secondary float can be field-wired to shut down the unit upon high condensate level.

    The Canister Humidifier Kit can be field-installed to customize cooling only or reheat only units. The kit includes full installation instructions and are designed to be added to the evaporator unit before it is mounted on its wall or floor location.

    The 277V Step-Down Transformer is available for units needing 277-1-60 input power; one each for evaporator section and remote condensing section (37.5A max. each). Use one 37.5A transformer for 1-1/2 or 2-ton self-contained water/glycol systems; use 50A transformer for 3-ton self-contained water/glycol systems. Epoxy-encapsulated, transformer is suitable for either indoor or outdoor service.

    Pre-Charged Refrigerant Line Set (R-407C) contains an insulated copper suction line and a copper liquid line for interconnection of the indoor and outdoor sections. Available in 15-foot (4.5m) and 30-foot (9m) sections for interconnection of evaporator to remote condensing unit without brazing. Maximum recommended combined line set length is 45 ft.(13.7m).

    The Refrigerant-Line Sweat Adapter Kit contains two suction and two liquid line fittings that allow field-supplied refrigerant piping between the evaporator and condensing unit.

    A Remote Temperature and Humidity Sensor package includes sensors in an attractive case with 30 ft. (9 m) of cable. Can be wall or duct mounted. Remote sensors should be used when the wall box is not located in the space to be conditioned.

    NOTEInstalling the remote sensors disables the sensors included in the wall box.

  • Ship-Loose AccessoriesField-Installed

    Liebert DataMate 6

    4.1 Remote Monitoring, Autochangeover and Leak Detection EquipmentThe Liebert RCM4 is a four-point, normally open, dry contact monitoring panel. One Form-C, dry contact common alarm relay output (rated at 24 VAC, 3 Amp) is provided. Four red LEDs illuminate on the respective alarm and the alarm buzzer is silenced by a front panel switch. The RCM4 requires a 24VAC or 24VDC power source. Power supply is not included.

    The Liebert AC4 Autochangeover Controller provides autochangeover and autosequence control for up to four Liebert DataMate units within a room. The Liebert AC4 will enable redundant units in an alarm condition, balance usage and test standby units at programmed intervals. Two common alarm relay outputs are available. A built-in LCD and RS-232 port for direct PC/terminal connection provides two options for configuration and monitoring of the product. The Liebert AC4 requires 24VAC input power.

    The Liebert AC8 is ideal for coordinated control of systems with redundant units. The Liebert AC8 enables redundant devices during an alarm condition, balances usage of devices and tests standby devices at programmable intervals. Supports four zones and can use the 4-20mA temperature sensor (TW420) for temperature staging in each zone. Two programmable output control relays are available for auxiliary control such as humidity lockout. Emergency power operation input provided for device control during an emergency. Two common alarm relay outputs are available. A built-in LCD and RS-232 port for direct PC/terminal connection provides two options for configuration and monitoring of the product.

    The Liebert ENV-DO interface card provides 16 discrete outputs, corresponding to status and major alarm conditions of Environmental units. The Liebert ENV-DO-ENCL1 packages one Environmental DO interface card in its own steel enclosure and the ENV-DO-ENCL2 packages two Environmental DO interface cards in one enclosure for installation external to the Liebert DataMate. The self-contained kit includes an external 120VAC-to-24VAC power transformer. Wiring harnesses are not provided. Power and communication wiring is field-provided.

    The Liebert Liqui-tect 410 Point Leak Detection Sensor detects the presence of conductive liquid using a pair of corrosion-resistant, gold-plated probes mounted in a painted, height-adjustable enclosure. Dual Form-C, dry contact common alarm relays (rated at 24VAC, 3A) signal a leak detected as well as loss of power and cable fault. The Liebert Liqui-tect 410 requires an external 24VAC or 24VDC power source.

    Liebert LT460 Zone Leak Detection Kits include one LT460 sensor, a specified length of LT500-xxY cable (maximum length is 100 ft [30.5m]) and a corresponding number of hold-down clips. The Liebert LT460 requires an external 24VAC, 0.12A power source, such as EXT-XFMR or XFMR24.

    Liebert SiteScan is a monitoring solution that gives you decision-making power to effectively manage the equipment critical to your business.

    Liebert SiteScan enables communication from Liebert environmental and power units, as well as many other pieces of analog or digital equipment, to a front-end software package that provides real-time status and alarms so you can react quickly to changing situations.

    Liebert SiteScan is designed with flexibility for both small systems and large, complex systems such as those in computer rooms, telecommunications facilities or industrial process control rooms. Contact your local Emerson representative for assistance with a Liebert SiteScan system.

    The NIC-ENCL1 and NIC-ENCL2 packages have one or two Liebert IntelliSlot Web/485 Cards with Adapters, respectively, in one steel enclosure. These are for installation external to the Liebert DataMate. The Liebert IntelliSlot Web/485 Card with Adapter provides communication with Liebert DataMate via SNMP, HTTP, RTU Modbus 485 and BACnet IP. The self-contained NIC-ENCL1 and NIC-ENCL2 kits include an external 120VAC-to-24VAC transformer as a power source. Wiring harnesses are not provided. Power and communication wiring is field-provided.

  • Flexible Configurations

    7 Liebert DataMate

    5.0 FLEXIBLE CONFIGURATIONS

    Figure 2 Flexible configurationsAll systems

    L ie be rt

    OUTDOOR, AIR-COOLED CONDENSING UNITSuitable for installation on a roof or at ground level.

    Liebert

    INDOOR AIR-COOLED CONDENSING UNITFor applications where roof or ground level locations are impractical.

    L ie be rt

    WATER/GLYCOL-COOLED REMOTECondensing unit is installed under raised floor or above dropped ceiling.

    Liebert

    WATER/GLYCOL-COOLED CLOSE-COUPLEDA single power and water supply

    connection puts the unit in operation.

    Liebert

    CHILLED WATERConnects to a chilled water loop for quick and easy installation.

    Air-Cooled Systems

    Water/Glycol-Cooled Systems

    Chilled Water Systems

  • Air-Cooled SystemsCapacities and Dimensions

    Liebert DataMate 8

    6.0 AIR-COOLED SYSTEMSCAPACITIES AND DIMENSIONSTable 1 60Hz capacities & typical specifications, air-cooled applications Evaporator Model DME020E DME027E DME037E Condensing Unit Type PFH - Outdoor PFH - Outdoor MCD - Indoor PFH - Outdoor MCD - Indoor DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM

    80F DB, 62.8F WB(26.7C DB, 17.1C

    WB) 38 %RH

    Total 5.50 (18,800) 7.20 (24,500) 6.90 (23,600) 10.25 (35,000) 9.70 (33,100)

    Sensible 5.50 (18,800) 7.20 (24,500) 6.90 (23,600) 9.95 (33,900) 9.60 (32,800)

    75F DB, 61F WB(23.9C DB, 16.1C

    WB) 45 %RH

    Total 5.10 (17,400) 6.70 (22,800) 6.45 (22,000) 9.80 (33,500) 9.25 (31,600)

    Sensible 5.05 (17,200) 6.65 (22,700) 6.40 (21,900) 8.90 (30,300) 8.60 (29,400)

    72F DB, 60F WB(22.2C DB, 15.5C

    WB) 50 %RH

    Total 4.90 (16,700) 6.40 (21,900) 6.20 (21,100) 9.60 (32,700) 9.05 (30,900)

    Sensible 4.70 (16,000) 6.20 (21,100) 6.05 (20,600) 8.20 (28,000) 7.95 (27,100)

    Fan Data - Evaporator CFM (CMH) - High Speed 870 (1478) 1230 (2090) 1320 (2243) CFM (CMH) - Low Speed 750 (1274) 1050 (1784) 1175(1996)

    Fan Motor hp (W) 0.16 (120) 0.20 (150)* 0.27 (200)** Evaporator Coil - Copper Tube/Aluminum Fin

    Face Area ft2 (m2) 2.44 (0.23) 3.92 (0.36) 3.92 (0.36) Coil Rows 4 3 4

    Max Face Velocity-fpm (m/s) 356 (1.8) 313 (1.6) 336 (1.7) Unit Refrigerant Charge, oz. (kg) 4 (0.11) 5 (0.14) 6.5 (0.18)

    Unit Operating Weight, lb. (kg) 230 (104) 330 (150) 365 (165)Electric Reheat Capacities (Includes Fan Motor)-kW (Btuh)

    Input Voltage 230-1-60 2.7 (9215) 5.3 (18080) 5.5 (18765)Humidifier Data - Steam Generator Type

    Steam capacity - lb/hr (kg/hr) 3 (1.4) 3 (1.4) 3 (1.4)Electrical Input Power - kW 1 1 1

    Evaporator Connection SizesLiquid line Diameter - Aeroquip

    Coupling Size, - #6 Female 3/8" 3/8" 3/8"

    Suction Line Diameter - AeroquipCoupling Size, #11 Female 1/2" 7/8" 7/8"

    Humidifier Supply,OD Cu Compression Fitting 1/4" 1/4" 1/4"

    Humidifier Drain, Barb Fitting 1/2" 1/2" 1/2"Evaporator Drain, Barb Fitting 3/4" 3/4" 3/4"

    Filter Washable Polypropylene/AluminumCondensing Unit Model Number PFH020A-_L7 PFH027A-_L7 MCD24AL_H7 PFH037A-_L7 MCD36AL_H7

    Condensing Unit Rating Conditions 95F (35C) AmbientCoil Face Area ft2 (m2) 4.1 (0.38) 4.1 (0.38) 4.6 (0.43) 7.7 (0.72) 4.6 (0.43)

    Rows of Coil 2 2 4 2 4 CFM (CMH) 2200 (3738) 2200 (3738) 1000 (1699) 3000 (5097) 1430 (2490)

    Motor, hp (W) 0.20 (149) 0.20 (149) 0.33 (246) 0.20 (149) 0.5 (373) External Static Pressure, in wg.

    (mm) N/A N/A 0.50 (13) N/A 0.50 (13)

    Condensing Unit RefrigerantCharge, oz. (kg) 134 (3.8) 134 (3.8) 134 (3.8) 213 (6.0) 213 (6.0)

    Unit Operating Weight, lb. (kg) 200 (91) 351 (159) 449 (204) 351 (159) 449 (204)The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75F (23.9 C), 45%RH, is the standardrating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be 5%.

    * DME027 has two motors - 0.08 & 0.12 HP** DME037 has two motors - 0.11 & 0.16 HP

  • Air-Cooled SystemsCapacities and Dimensions

    9 Liebert DataMate

    Table 2 50Hz capacities & typical specifications, air-cooled applications Evaporator Model DME037E Condensing Unit Type PFH - Outdoor MCD - Indoor DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM

    80F DB, 62.8F WB (26.7C DB, 17.1C WB) 38 %RH Total 10.60 (36,200) 9.55 (32,600)

    Sensible 9.40 (32,100) 8.90 (30,400)

    75F DB, 61F WB (23.9C DB, 16.1C WB) 45 %RH Total 10.25 (34,900) 9.10 (31,400)

    Sensible 8.45 (28,800) 7.95 (27,100)

    72F DB, 60F WB (22.2C DB, 15.5C WB) 50 %RH Total 10.00 (34,100) 9.00 (30,700)

    Sensible 7.85 (26,700) 7.35 (25,100)

    Fan Data - Evaporator CFM (CMH) - High Speed 1100 (1869)

    CFM (CMH) - Low Speed 980 (1665) Fan Motor HP (W) 0.27 (200)**

    Evaporator Coil - Copper Tube/Aluminum Fin Face Area ft2 (m2) 3.92 (0.36)

    Coil Rows 4

    Max Face Velocity-fpm (m/s) 336 (1.7)

    Unit Refrigerant Charge, oz. (kg) 6.5 (0.18)

    Unit Operating Weight, lb. (kg) 365 (165)

    Electric Reheat Capacities (Includes Fan Motor)-kW (Btuh)Input Voltage 230-1-50 5.5 (18765)

    Humidifier Data - Steam Generator TypeSteam capacity - lb/hr (kg/hr) 3 (1.4)

    Electrical Input Power - kW 1

    Evaporator Connection SizesLiquid line Diameter - Aeroquip Coupling Size, #6 Female 3/8"

    Suction Line Diameter - Aeroquip Coupling Size, - #11 Female 7/8"

    Humidifier Supply,OD Cu Compression Fitting 1/4"

    Humidifier Drain, Barb Fitting 1/2"

    Evaporator Drain, Barb Fitting 3/4"

    Filter Washable Polypropylene/Aluminum

    Condensing Unit Model Number PFH036A-_L7 MCD35AL_H7 Condensing Unit Rating Conditions

    Coil Face Area ft2 (m2) 7.7 (0.72) 4.6 (0.43) Rows of Coil 2 4

    CFM (CMH) 2500 (4248) 1430 (2430)

    Motor, hp (W) 0.20 (149) 0.5 (373) External Static Pressure, in wg. (mm) N/A 0.50 (13)

    Condensing Unit Refrigerant Charge, oz. (kg) 213 (6.0) 213 (6.0)

    Unit Operating Weight, lb. (kg) 351 (159) 449 (204)The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75F (23.9 C), 45%RH, is the

    standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be 5%.** DME037 has two motors - 0.11 & 0.16 HP

  • Air-Cooled SystemsCapacities and Dimensions

    Liebert DataMate 10

    Figure 3 General arrangement, air-cooled split systems

    *

    *

    Liquid InjectionValve

    DPN000261REV 2

    CondenserCoil

    High PressureSwitchScroll

    Compressor

    Hot GasBypassSolenoidValve

    Hot Gas By

    pass

    Control Valve

    3 - WayHeadPressureRelief Valve

    CheckValve

    3/8" SAE 45 Male FlarePressure Relief Valve

    Sight Glass

    Liebert Lee-TempReceiverLiquid Line

    Solenoid Valve

    FilterDrier

    FIELD PIPINGFACTORY PIPING

    * Use Liebert sweat adapter kit with field hard piping or use Liebert pre-charged line set.Evaporator Coil

    External EqualizerSensing Bulb

    Suction Line Female QuickConnect Coupling

    Liquid InjectionValve Bulb

    Suction Line Male QuickConnect Coupling

    Liquid Line Male QuickConnect Coupling

    Liquid Line Female QuickConnect Coupling

    Expansion Valve

    Service AccessPorts

  • Air-Cooled SystemsCapacities and Dimensions

    11 Liebert DataMate

    Figure 4 Dimensions, evaporator unit

    Table 3 Evaporator section dimensionsair-cooled applications

    Model Weightlb (kg)

    Width - Ain. (mm)

    Depthin. (mm)

    Heightin. (mm)

    DME020E 230 (104) 46-1/2 (1181) 11-7/8 (302) 32 (813)

    DME027E 330 (150) 64-1/8 (1628) 11-7/8 (302) 32 (813)

    DME037E 365 (165) 64-1/8 (1628) 11-7/8 (302) 32 (813)Source: DPN000262, Rev. 0

    Table 4 Evaporator unit refrigerant connectionspipe size/coupling numberModel Liquid Line A Suction Line B

    DME020E 3/8" / #6 1/2" / #11

    DME027E 3/8" / #6 7/8" / #11

    DME037E 3/8" / #6 7/8" / #11

    Grilles are reversibleto allow air direction changesas shown by the arrows

    CabinetOutline

    5/8"(16mm)

    3-1/2"(89mm)

    1"(25mm)

    10-7/8"(276mm)

    Shaded area indicates arecommended clearanceof 34" (864mm) in frontof the unit.

    Standard Refrigeration and ChilledWater Piping Opening

    Removable AccessPanel

    A

    32"(813mm)

    AirInlet

    Air Outlet

    A

    DPN000262Rev. 0

    FLOOR CUTOUTDIMENSIONS

    for Raised-Floor Piping

    See Table 3 for Dimension A

  • Air-Cooled SystemsCapacities and Dimensions

    Liebert DataMate 12

    Figure 5 Cabinet and floor planning dimensionsOutdoor air-cooled condensing units

    Table 5 Propeller fan, air-cooled condensing unit dimensions, inches (mm)Model Numbers Dimensional Data, inches (mm)

    Module NetWeight, lb (kg)60Hz 50Hz A B C

    PFH020A-L 40 (1016) 23-1/2 (597) 18 (457) 200 (91)

    PFH027A-L

    PFH027A-H

    48 (1219) 31 (787) 18 (457) 241 (109)PFHZ27A-L

    PFH037A-L PFH036A-L

    PFH037A-H PFH036A-H53 (1343) 36 1/4 (918) 18 (457) 351 (159)

    PFHZ37A-L PFHZ36A-L

    Source: DPN000130, Rev. 1

    A

    B

    CC

    Fan RotationCCW(left side)

    Shaded areaindicates a minimumclearance of 18" (457mm)for proper air flow.

    Shaded areaindicates a minimumclearance of 18" (457mm)for proper air flow

    Shaded areaindicates a recommendedclearance of 24" (610mm)for component access andremoval.

    DPN000130Rev. 1

    Removable panel for accessto high-voltage and low-voltageconnections and refrigerationcomponents

    Right Air Discharge

    Removable (right) panelfor access torefrigeration component

    Left Air Intake

  • Air-Cooled SystemsCapacities and Dimensions

    13 Liebert DataMate

    Figure 6 Dimensions, indoor air-cooled condensing units

    Table 6 Remote centrifugal fan, air-cooled condensing, weight and dimensions

    ModelWeightlb (kg)

    Dimensions, in (mm)A B C D

    MC*24A 230 (104)1-7/16 (37) 11-7/16 (290) 1/2 (13) 20-7/16 (519)MC*35A

    240 (109)MC*36A

    Source: DPN000206, Rev. 1

    50-1/4" (1276mm)

    Overall Dimension

    46-1/2" (1181mm)

    Cabinet Dimension

    48-1/4" (1225mm)

    Threaded Rod Centers

    19-1/2" (495mm)Threaded RodCenters

    21-1/2" (546mm)Cabinet Dimension

    22-3/4" (578mm)Overall Dimension

    Customer-SuppliedThreaded Rods forModule Supportfrom Ceiling (typ. 4)

    Air OutletDuct Connection

    Air OutletDuct Connection

    Blower Motor Service AccessPanel on Bottom of UnitMinimum Clearance 33" (838mm)for Component Access and Removal

    DIMENSIONAL DATANote:Unit is evenly spaced inreference to threaded rod centers.

    DuctFlange

    30-1/8"(765mm)Coil InletDuct Connection

    2-1/4"(57mm)

    1"(25.4mm)

    Minimum Clearance 33" (838mm)This End for ComponentAccessand Removal

    Integral HangingBracket

    Holes for ModuleRigging (typ. 2 each end)

    22-1/2"(572mm)

    CabinetDimension

    20-3/4"(527mm)

    20-7/16"(519mm)Coil Inlet

    DuctConn.

    7/8" (22.2mm) Dia.Electrical Entrancefor Line VoltageConnection.

    7/8" (22.2mm) Dia.Electrical Entrancefor Low-VoltageConnection

    Liquid LineMale QuickConnect

    PIPINGCONNECTIONS

    DPN000206Rev. 1

    D

    C

    Suction LineMale QuickConnect

  • Water/Glycol SystemsCapacities and Dimensions

    Liebert DataMate 14

    7.0 WATER/GLYCOL SYSTEMSCAPACITIES AND DIMENSIONSTable 7 60Hz capacities & typical specifications, water-cooled and glycol-cooled applications Evaporator Model DME020E DME027E DME037E

    Condensing Unit TypeWater-Cooled

    Glycol-Cooled

    Water-Cooled

    Glycol-Cooled

    Water-Cooled

    Glycol-Cooled

    DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM80F DB, 62.8F WB (26.7C DB,

    17.1C WB) 38 %RH Total 5.90 (20,100) 5.15 (17,600) 7.95 (27,200) 6.75 (23,000) 11.4 (38,900) 9.65 (32,900)

    Sensible 5.80 (19,800) 5.15 (17,600) 7.90 (27,000) 6.75 (23,000) 10.3 (35,300) 9.40 (32,100)75F DB, 61F WB (23.9C DB,

    16.1C WB) 45 %RH Total 5.50 (18,800) 4.80 (16,300) 7.55 (25,800) 6.25 (21,300) 11.0 (37,400) 9.20 (31,400)

    Sensible 5.15 (17,600) 4.75 (16,200) 7.10 (24,200) 6.25 (21,300) 9.20 (31,400) 8.35 (28,500)72F DB, 60F WB (22.2C DB,

    15.5C WB) 50 %RH Total 5.35 (18,100) 4.60 (15,700) 7.35 (25,000) 6.00 (20,500) 10.7 (36,600) 8.95 (30,600)

    Sensible 4.75 (16,200) 4.35 (14,900) 6.55 (22,300) 5.85 (19,900) 8.55 (29,100) 7.70 (26,300) Fan Data - Evaporator

    CFM (CMH) - High Speed 870 (1478) 1230 (2090) 1320 (2243) CFM (CMH) - Low Speed 750 (1274) 1050 (1784) 1175(1996)

    Fan Motor hp (W) 0.16 (120) 0.20 (150)* 0.27 (200)** Evaporator Coil - Copper Tube/Aluminum Fin

    Face Area ft2 (m2) 2.44 (0.23) 2.44 (0.23) 3.92 (0.36) 3.92 (0.36) Coil Rows 4 3 4

    Max Face Velocity-fpm (m/s) 356 (1.8) 313 (1.6) 336 (1.7)Unit Refrigerant Charge, oz. (kg) 4 (0.11) 5 (0.14) 6.5 (0.18)

    Unit Operating Weight, lb. (kg) 230 (104) 330 (150) 365 (165)Electric Reheat Capacities (Includes Fan Motor)-kW (Btuh)

    Input Voltage 230-1-60 2.7 (9215) 5.3 (18080) 5.5 (18765)Humidifier Data - Steam Generator Type

    Steam capacity - lb/hr (kg/hr) 3 (1.4) 3 (1.4) 3 (1.4)Electrical Input Power - kW 1 1 1

    Evaporator Connection SizesLiquid Line Diameter - Aeroquip Coupling Size 3/8"- #6 Female 3/8" - #6 Female 3/8" - #6 Female

    Suction Line Diameter - Aeroquip Coupling Size 1/2" - #11 Female 7/8" - #11 Female 7/8" - #11 FemaleHumidifier Supply 1/4" OD Copper Compression Fitting

    Humidifier Drain, Barb Fitting 1/2" 1/2" 1/2"Evaporator Drain, Barb Fitting 3/4" 3/4" 3/4"

    Filter Washable Polypropylene/AluminumClose-Coupled DMC Condensing Unit Model DMC022WG DMC029WG DMC040WG

    Condenser Fluid Requirements, F (C) 85 (29.4) EWT110 (43.3) EGT - 40%

    PG85 (29.4)

    EWT110 (43.3) EGT - 40%

    PG85 (29.4)

    EWT110 (43.3) EGT - 40%

    PGTHR - kW (Btuh) @ 75F/45%RH 7.30 (24,900) 7.10 (24,200) 9.60 (32,700) 9.10 (31,000) 13.9 (47,400) 13.2 (45,100)

    Flow Rate - GPM (l/m) 4.0 (15.2) 5.9 (22.4) 4.6 (17.4) 6.9 (26.2) 7.8 (29.6) 9.1 (34.5)Pressure Drop - ft. of H20 (kPa) 7.0 (20.9) 17.0 (50.8) 4.4 (13.2) 10.4 (31.1) 8.4 (25.1) 13.6 (40.7)

    Water-Cooled Condensing Temperature, F (C) 105 (40.6) N/A 105 (40.6) N/A 105 (40.6) N/AWater/Glycol Connection Sizes, in. (mm) OD 5/8 (15.9) 7/8 (22.2)

    Liquid Line Diameter - Aeroquip Coupling 3/8" - #6 Male 3/8" - #6 Male 3/8" - #6 MaleSuction Line Diameter - Aeroquip Coupling 5/8" - #11 Male 5/8" - #11 Male 3/4" - #11 Male

    Unit Volume - Gal (l) 0.25 (0.95) 0.40 (1.5) 0.50 (1.9)Unit Refrigerant Charge, oz. (kg) 47 (1.33) 59 (1.67) 61 (1.72)

    Unit Operating Weight, lb. (kg) 169 (77) 169 (77) 172 (78)Remote MCD Condensing Unit Model # MCD26W MCD38W

    Condenser Fluid Requirements, F (C) N/A 85 (29.4) EWT110 (43.3) EGT - 40%

    PG85 (29.4)

    EWT110 (43.3)EGT - 40%

    PGTHR - kW (Btuh) @ 75F/45%RH 9.60 (32,700) 9.10 (31,000) 13.9 (47,400) 13.2 (45,100)

    Flow Rate - GPM (l/m) 7.7 (24.2) 8.9 (33.7) 6.5 (24.6) 12.1 (45.9)Pressure Drop - ft. of H20 (kPa) 16.6 (49.6) 26.0 (77.7) 11.6 (34.7) 44.7 (133.7)

    Water-Cooled Condensing Temperature 105F (40.6C) N/A105F

    (40.6C) N/A

    Water/Glycol Connection Sizes, in. (mm) OD 7/8 (22.2) 7/8 (22.2)Unit Volume - Gal (l) 1.2 (4.5) 1.2 (4.5)

    Unit Refrigerant Charge, oz. (kg) 41 (1.16) 54 (1.54)Unit Operating Weight, lb. (kg) 175 (79) 220 (100)

    The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75F (23.9 C), 45%RH, is thestandard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be 5%.

    * DME027 has two motors - 0.08 & 0.12 HP; ** DME037 has two motors - 0.11 & 0.16 HP

  • Water/Glycol SystemsCapacities and Dimensions

    15 Liebert DataMate

    Table 8 50Hz capacities & typical specifications, water-cooled and glycol-cooled applications Evaporator Model DME037E Condensing Unit Type Water-Cooled Glycol-Cooled DX Evaporator- Net Capacity Data - kW (Btuh) @ High Speed CFM

    80F DB, 62.8F WB (26.7C DB, 17.1C WB) 38 %RHTotal 11.3 (38,700) 9.30 (31,800)

    Sensible 9.55 (32,600) 8.60 (29,300)

    75F DB, 61F WB (23.9C DB, 16.1C WB) 45 %RHTotal 11.0 (37,400) 8.95 (30,500)

    Sensible 8.55 (29,200) 7.60 (26,000)

    72F DB, 60F WB (22.2C DB, 15.5C WB) 50 %RHTotal 10.7 (36,600) 8.75 (29,900)

    Sensible 7.95 (27,200) 7.05 (24,000)

    Fan Data - Evaporator CFM (CMH) - High Speed 1100 (1869) CFM (CMH) - Low Speed 980 (1665)

    Fan Motor HP (W) 0.27 (200)**

    Evaporator Coil - Copper Tube/Aluminum Fin Face Area ft2 (m2) 3.92 (0.36)

    Coil Rows 4 Max Face Velocity-fpm (m/s) 336 (1.7)

    Unit Refrigerant Charge, oz. (kg) 6.5 (0.18)Unit Operating Weight, lb. (kg) 365 (165)

    Electric Reheat Capacities (Includes Fan Motor)-kW (Btu/H)Input Voltage 230-1-50 5.5 (18765)

    Humidifier Data - Steam Generator Type Steam capacity - lb/hr (kg/hr) 3 (1.4)

    Electrical Input Power - kW 1

    Evaporator Connection SizesLiquid Line Diameter - Aeroquip Coupling Size 3/8" - #6 Female

    Suction Line Diameter - Aeroquip Coupling Size 7/8" - #11 FemaleHumidifier Supply 1/4" OD Cu Compression Fitting

    Humidifier Drain, Barb Fitting 1/2"Evaporator Drain, Barb Fitting 3/4"

    Filter Washable Polypropylene/Aluminum

    Remote MCD Condensing Unit Model # MCD37W

    Condenser Fluid Requirements 85F (29.4C)EWT110F (43.3C)EGT - 40% PG

    THR - kW (Btuh) @ 75F/45%RH 13.7 (46,700) 12.9 (44,000)Flow Rate - GPM (l/m) 6.4 (24.3) 13.5 (51.2)

    Pressure Drop - ft. of H20 (kPa) 11.7 (35.0) 55.8 (166.8)Water-Cooled Condensing Temperature 105 F (40.6 C) N/A

    Water/Glycol Connection Sizes, in. (mm) OD 7/8 (22.2)Unit Volume - Gal (l) 1.2 (4.5)

    Unit Refrigerant Charge, oz. (kg) 54 (1.54)Unit Operating Weight, lb. (kg) 220 (100)

    The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75F (23.9 C), 45%RH, is thestandard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be 5%.

    ** DME037 has two motors - 0.11 & 0.16 hp

  • Water/Glycol SystemsCapacities and Dimensions

    Liebert DataMate 16

    Figure 7 General arrangement, water/glycol, split systems

    Figure 8 General arrangement, water/glycol systems, close-coupled condensing unit

    *

    *

    Tube-in-TubeCondenser

    Tube-in-TubeCondenser

    DPN000260Rev. 2

    Scroll Compressor

    Hot GasBypassSolenoidValve

    Hot Gas BypassControlValve

    LiquidInjectionValve

    Suction Line Male QuickConnect Coupling

    Liquid InjectionValve Bulb

    Liquid LineMale QuickConnectCoupling

    Water/GlycolReturn Line

    Fluid ReturnFrom Unit

    Water/GlycolSupply Line

    FluidSupplyTo Unit

    Shutoff **Valves

    Hose Bibs **

    2 - Way WaterRegulating Valve

    Fluid ReturnFrom Unit

    FluidSupplyTo Unit

    3 - Way WaterRegulating Valve(Optional)

    Suction Line Female QuickConnect Coupling

    Liquid LineFemale QuickConnectCoupling

    SensingBulb

    Service AccessPorts

    FilterDrier

    EvaporatorCoil

    ExpansionValve

    ExternalEqualizer

    FIELD PIPING

    FACTORY PIPING

    High-PressureSwitch

    * Use Liebert sweat adapter kit with field hard piping or use Liebert pre-charged line set.

    ** Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance.

    SensingBulb

    ScrollCompressor

    Factory-Connected

    High-PressureSwitch

    Suction LineMale QuickConnectCouplingSuction Line

    Female QuickConnect Coupling

    EvaporatorCoil

    Brazed PlateCondenser

    Fluid Supplyto Unit

    Fluid ReturnFrom Unit

    * Shutoff Valves

    FIELD PIPING

    DPN000259Rev. 2

    WaterSupplyLine

    WaterReturnLine

    * Components are not supplied by Emerson but are recommended for proper circuit operation and maintenance

    Service AccessPorts

    FACTORY PIPING

    Liquid LineFemale QuickConnect Coupling

    Filter Drier

    ExpansionValve

    Liquid Line MaleQuick ConnectCoupling

    ExternalEqualizer

    * Hose Bibs

    2-Way WaterRegulatingValve

  • Water/Glycol SystemsCapacities and Dimensions

    17 Liebert DataMate

    Figure 9 Dimensions, evaporator unit

    Table 9 Evaporator section dimensionswater/ glycol-cooled applications

    Model Weightlb (kg)

    Width - Ain. (mm)

    Depthin. (mm)

    Heightin. (mm)

    DME020E 230 (104) 46-1/2 (1181) 11-7/8 (302) 32 (813)

    DME027E 330 (150) 64-1/8 (1628) 11-7/8 (302) 32 (813)

    DME037E 365 (165) 64-1/8 (1628) 11-7/8 (302) 32 (813)

    Table 10 Evaporator unit refrigerant connectionspipe size/coupling numberModel Liquid Line A Suction Line B

    DME020E 3/8" / #6 1/2" / #11

    DME027E 3/8" / #6 7/8" / #11

    DME037E 3/8" / #6 7/8" / #11

    Grilles are reversibleto allow air direction changesas shown by the arrows

    CabinetOutline

    5/8"(16mm)

    3-1/2"(89mm)

    1"(25mm)

    10-7/8"(276mm)

    Shaded area indicates arecommended clearanceof 34" (864mm) in frontof the unit.

    Standard Refrigeration and ChilledWater Piping Opening

    Removable AccessPanel

    A

    32"(813mm)

    AirInlet

    Air Outlet

    A

    DPN000262Rev. 0

    FLOOR CUTOUTDIMENSIONS

    for Raised-Floor Piping

    See Table 9 for Dimension A

  • Water/Glycol SystemsCapacities and Dimensions

    Liebert DataMate 18

    Figure 10 Dimensions and piping, close-coupled water/glycol condensing unit

    Note: Do Not remove evaporatorend panel from panel assembly wheninstalling internal water/glycolcondensing unit

    Piping AccessPlate inEvaporatorEnd Panel

    A - Liquid Refrigerant LineQuick Connect MaleCoupling

    B - Suction Refrigerant LineQuick Connect MaleCoupling

    D - ReturnLeavingCondenserWater/Glycol

    C - SupplyEnteringCondenserWater/glycol

    RemovablePanels

    Outline ofEvaporatorModule

    Piping and ElectricalKnockoutsLocated on Bottomand on Back of Unit

    Piping and Electrical KnockoutsLocated on Bottom and onBack of Unit

    DPN000270Rev. 3

    DPN000269Rev. 0

    14"(356mm)

    Access Panel(Removable)

    Unit Dimensions

    Access Panel(Removable)

    Access

    Panel

    (Remo

    vable)

    12" (305mm)

    CondensingUnit

    Shaded area indicates a recommendedclearance of 34" (864mm) in front of the unit and 12" (305mm) onthe left side for component access andremoval. Minimum clearance is 1" (25mm)on left side and 18" (457mm) in front.

    Floor

    LiebertDataMateEvaporator

    32"(813mm)

    14"(356mm)

  • Water/Glycol SystemsCapacities and Dimensions

    19 Liebert DataMate

    Table 11 Net weight, water/glycol condensing unitsModel Tons Weight

    DMC022WG 1-1/2 170lb (77kg)

    DMC029WG 2 170lb (77kg)

    DMC040WG 3 170lb (77kg)Source: DPN000269, Rev. 0

    Table 12 Unit refrigerant connection sizes

    Model

    Unit Refrigerant Connections -Internal Pipe Size/ Coupling No.

    Water/Glycol Piping ConnectionSizes O.D. Cu

    Liquid LineA

    Suction LineB

    SupplyC

    ReturnD

    DMC022WG 3/8 / #6 5/8 / #11 5/8 5/8

    DMC029WG 3/8 / #6 5/8 / #11 7/8 7/8

    DMC040WG 3/8 / #6 3/4 / #11 7/8 7/8Source: DPN000270, Rev. 3

  • Water/Glycol SystemsCapacities and Dimensions

    Liebert DataMate 20

    Figure 11 Cabinet dimensions and piping data, water/glycol indoor remote condensing modules

    Table 13 Net weight, indoor water/glycol-cooled condensing unitModel Numbers Weight

    lb (kg)60Hz 50Hz

    MC*26W 175 (79)

    MC*38W MC*37W 220 (100)

    MC*44W MC*43W Source: DPN000208, Rev. 4

    Holes for ModuleRigging (typ. 2 each end)

    7/8" (22mm) Dia.Electrical Entrancefor High VoltageConnection

    DPN000208Rev. 4

    PIPING CONNECTIONS7/8" (22mm) Dia. ElectricalEntrance for Low-VoltageConnection

    7/8" (22.2mm) OD CUWater/Glycol Outlet ConnectionExtends 3-1/2" (88.9mm)beyond panel exterior

    7/8" (22.2mm) OD CUWater/Glycol Inlet ConnectionExtends 3-1/2" (88.9mm)beyond panel exterior

    Suction LineMale QuickConnect

    Liquid LineMale QuickConnect

    14" (356mm)Overall CabinetDimension

    8-7/8" (225mm)50-1/4" (1276mm)Overall Dimension

    48-1/4" (1225mm)Threaded Rod Centers

    46-1/2" (1181mm)

    20-3/4"(527mm)

    Minimum Clearance33" (838mm) This Sidefor Component Accessand Removal

    Customer SuppliedThreaded Rods for ModuleSupport from Ceiling (typ. 4) Outlet

    Inlet

    Note: Unit is Spaced Evenly inReference to Threaded Rod Centers

    DIMENSIONAL DATAIntegral Hanging Bracket

    12" (305mm)Threaded RodCenters

    22-1/2" (572mm)Cabinet Dimension

    3-7/8" (98mm)

    8-7/16" (214mm) Cabinet Dimension

  • Chilled Water Systems

    21 Liebert DataMate

    8.0 CHILLED WATER SYSTEMSTable 14 Chilled water data, 50/60Hz

    CW Model, 60 Hz DME044C

    208/230-1-60 200/220-1-50Net Capacity Data - kW (Btuh) based on 45F (7.2C) EWT & 10F (5.6C) temperature rise

    80F DB, 62.8F WB (26.7C DB, 17.1C WB) 38 %RHTotal 10.5 (35,900) 9.1 (31,000)

    Sensible 9.65 (32,900) 8.25 (28,100)Flow Rate, GPM (l/m) 7.3 (27.7) 6.3 (23.9)

    Pressure Drop, ft. water (kPa) 12.0 (35.9) 9.3 (27.8)

    75F DB, 61F WB (23.9C DB, 16.1C WB) 45 %RHTotal 8.75 (29,800) 7.55 (25,800)

    Sensible 7.90 (27,000) 6.8 (23,200)Flow Rate, GPM (l/m) 6.1 (23.1) 5.3 (20.1)

    Pressure Drop, ft. water (kPa) 8.7 (26.0) 6.7 (20.0)

    72F DB, 60F WB (22.2C DB, 15.5C WB) 50 %RHTotal 7.65 (26,100) 6.6 (22,600)

    Sensible 6.90 (23,500) 5.9 (20,100)Flow Rate, GPM (l/m) 5.3 (20.1) 4.6 (17.4)

    Pressure Drop, ft. water (kPa) 6.9 (20.6) 5.3 (15.8) Fan Data - Evaporator

    CFM (CMH) - High Speed 1320 (2243) 1100 (1869) CFM (CMH) - Low Speed 1175 (1996) 980 (1665)

    Fan Motor, hp (W) 0.27 (200)** 0.27 (200)CW Coil - Copper Tube/Aluminum Fin

    Face Area, ft2 (m2) 3.92 (0.36) Coil Rows 4

    Max Face Velocity-fpm (m/s) 336 (1.7) 281 (1.4)

    Electric Reheat Capacity (Includes Fan Motor), kW (Btuh)Input Voltage 230-1-60/50 5.5 (18,765)

    Humidifier Data - Steam Generator TypeSteam capacity, lb/hr (kg/hr) 3 (1.4)

    Electrical Input Power, kW 1Unit Connection Sizes

    CW supply and return connections, in (mm) OD 7/8 (22.2)Humidifier Supply 1/4" OD Copper Compression Fitting

    Humidifier Drain, Barb Fitting 1/2"Evaporator/Condensate Drain, Barb Fitting 3/4"

    Unit Internal Fluid Volume, gal (l) 1.0 (3.8)Filter Washable Polypropylene/Aluminum

    Unit Operating Weight, lb. (kg.) 365 (165)Unit Valve Types On/Off Slow Close, 2-Way

    Valve Size 3/4"Valve Cv 8

    Max. Water Static Operating Pressure, psi (kPa) 125 (862)Close-Off Pressure, psi (kPa) 8 (55)

    The net capacity data has fan motor heat factored in for all ratings and the entering air conditions of 75F (23.9 C), 45%RH, is the standard rating condition for ASHRAE 127-2007. All capacities are nominal values; actual performance will be 5%.** DME044C has two motors - 0.11 & 0.16 HP

  • Chilled Water Systems

    Liebert DataMate 22

    Figure 12 General arrangementChilled water systems

    Table 15 Chilled water capacity correction factors based on 10F (5.6C) water rise

    EWT

    72F (22.2C) 50% 75F (23.9C) 45%RH

    TCC SCC TCC SCC

    42F (5.6C) 1.27 1.14 1.23 1.11

    43F (6.1C) 1.17 1.09 1.15 1.07

    44F (6.7C) 1.08 1.04 1.07 1.04

    45F (7.2C) 1.00 1.00 1.00 1.00

    46F (7.8C) 0.93 0.96 0.94 0.96

    47F (8.3C) 0.86 0.92 0.88 0.93

    48F (8.9C) 0.79 0.88 0.82 0.89

    49F (9.4C) 0.74 0.83 0.77 0.85

    Bleed Valve

    Chilled WaterCoil

    Chilled WaterControlValve

    Chilled WaterReturn

    Chilled WaterSupply

    * Shutoff Valves FIELD PIPING

    DPN000259Rev. 2

    FACTORY PIPING* Hose Bibs

    * Components are not supplied by Liebert but are recommended for proper circuit operation and maintenance

  • Chilled Water Systems

    23 Liebert DataMate

    Figure 13 DimensionsChilled water unit

    Table 16 Net weights and dimensions, chilled water units

    ModelDimensions

    W x D x H, in (mm)Weightlb (kg) Water Connection Sizes

    DME044C 64-1/8 x 11-7/8 x 32(1628 x 302 x 813) 364 (165) 7/8" (22.2mm) OD Cu

    Source: DPN000262, Rev. 0

    Grilles are reversibleto allow air direction changesas shown by the arrows

    CabinetOutline

    5/8"(16mm)

    3-1/2"(89mm)

    1"(25mm)

    10-7/8"(276mm)

    Shaded area indicates arecommended clearanceof 34" (864mm) in frontof the unit.

    Standard Refrigeration and ChilledWater Piping Opening

    Removable AccessPanel

    A

    32"(813mm)

    AirInlet

    Air Outlet

    A

    DPN000262Rev. 0

    FLOOR CUTOUTDIMENSIONS

    for Raised-Floor Piping

  • Electrical DataAll Units

    Liebert DataMate 24

    9.0 ELECTRICAL DATAALL UNITSTable 17 Electrical data, split system evaporator or chilled water unit, 60/50Hz

    Base Evaporator/Chilled Water

    208/230V-1ph-60Hz 200/220V-1-50

    DME020E DME027EDME037EDME044C DME020E DME027E

    DME037EDME044C

    Cooling OnlyFLA 1.4 1.5 2.2 1.4 1.5 2.2

    WSA 1.8 1.9 2.8

    OPD 15 15 15

    With ReheatFLA 11.8 22.3 23.0 11.8 22.3 23.0

    WSA 14.8 27.9 28.8

    OPD 15 30 30

    With Reheat & HumidifierFLA 18.8 29.3 30.0 18.8 29.3 30.0

    WSA 23.5 36.6 37.5

    OPD 25 40 40

    Table 18 60Hz electrical data, evaporator with close-coupled water/glycol condensing unit with common power feed

    Nominal Capacity, Tons 1.5 2 3

    Evaporator Model DME020E DME027E DME037E

    Condensing Model DMC022WG DMC029WG DMC040WGVolt-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60

    Cooling OnlyFLA 12.1 13.5 19.3

    WSA 14.8 16.5 23.6OPD 25 25 40

    With Reheat or With Reheat & HumidifierFLA 22.5 34.3 40.1

    WSA 27.8 42.5 49.6OPD 35 45 60

  • Electrical DataAll Units

    25 Liebert DataMate

    Table 19 60Hz electrical data, outdoor air-cooled condensing unitNom. Capacity, Tons 1.5 2 3 3 3 3

    Standard 95F (35C) Propeller Fan Condensing UnitModel PFH020A-PL7 PFH027A-PL7 PFH037A-PL7 PFH037A-YL7 PFH037A-AL7 PFH037A-BL7

    Volt-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60

    FLA 12.1 13.4 18.5 13.4 7.1 5.8

    WSA 14.8 16.4 22.8 16.4 8.7 7.0

    OPD 25 25 35 25 15 15

    High Ambient Propeller Fan Condensing UnitModel N/A PFH027A-PH7 PFH037A-PH7 PFH037A-YH7 PFH037A-AH7 PFH037A-BH7

    Volt-Ph-Hz N/A 208/230-1-60 208/230-1-60 208/230-3-60 460-3-60 575-3-60

    FLA N/A 15.4 20.5 15.4 8.1 5.8

    WSA N/A 18.4 24.8 18.4 9.7 7.0

    OPD N/A 30 40 30 15 15

    Quiet-Line Propeller Fan Condensing UnitModel N/A PFHZ27A-PL7 PFHZ37A-PL7 PFHZ37A-YL7 PFHZ37A-AL7

    Volt-Ph-Hz N/A 208/230-1-60 208/230-1-60 208/230-3-60 460-3-60

    FLA N/A 12.9 18.0 12.9 7.1

    WSA N/A 15.9 22.3 15.9 8.7

    OPD N/A 25 40 30 15

    Table 20 50Hz electrical data, outdoor air-cooled condensing unitNominal Capacity, Tons 3 3

    Standard 95F (35C) Propeller Fan Condensing UnitModel PFH036A-SL7 PFH036A-ML7

    Volt-Ph-Hz 220-1-50 380/415-3-50

    FLA 18.4 7.0

    High Ambient Propeller Fan Condensing UnitModel PFH036A-SH7 PFH036A-MH7

    Volt-Ph-Hz 220-1-50 380/415-3-50

    FLA 20.5 8.1

    Quiet-Line Propeller Fan Condensing UnitModel PFHZ36A-SL7 PFHZ36A-ML7

    Volt-Ph-Hz 220-1-50 380/415-3-50

    FLA 18.0 6.9

  • Electrical DataAll Units

    Liebert DataMate 26

    Figure 14 Step-down transformer for 277V input power applications

    Table 21 Electrical data, indoor air & water/glycol remote condensing units, 50 & 60Hz

    Model60 Hz 50 Hz

    208/230-1ph-60Hz 277-1ph-60Hz 208/230-3ph-60Hz 460-3ph-60Hz 220-1ph-50Hz 380/415-3ph-50HzMC*24A MC*24A MC*24A MC*24A

    FLA 14.3 12.7 WSA 17.3 15.3 OPD 25 25

    MC*36A MC*36A MC*36A MC*36A MC*35A MC*35AFLA 20.8 16.6 15.7 7.8 20.1 7.8WSA 25.1 20.2 18.7 9.4 OPD 40 30 30 15

    MC*26W MC*26W MC*26W MC*26W FLA 12.0 10.4 WSA 15.0 13.0 OPD 25 20

    MC*38W MC*38W MC*38W MC*38W MC*37W MC*37WFLA 17.1 14.3 12.0 6.4 17.1 6.4WSA 21.4 17.9 15.0 8.0 OPD 35 30 25 15

    * Specify disconnect or no disconnect

    DPN000647Rev0

    .281" (7mm) Dia.For wall-mounting purposes

    .31" (8mm) Dia.For rigid mountingand shipping purposes

    1/4-20 (2 screws &lock washers) use forrigid mounting andshipping purposes

    Remove screws& attach bracket

    4.92"(125mm) Access to electrical

    connections frombottom

    5.5"(140mm)

    1D18214P110.3" (262mm)

    1D18214P211.68" (297mm)

    WALL MOUNTING RIGID MOUNTINGNotes:1. 1D18214P1 = Acme catalog no. T-1-37921 for all small systems except 3-ton Liebert DataMate with integral condenser.2. 1D18214P2 = Acme catalog no. T-1-37922 for 3-ton DataMate with integral condenser.3. Epoxy encapsulated. Suitable for indoor/outdoor service. Horizontal or vertical mount.

    Totally enclosed, non-ventilated.4. Both brackets are shipped loose with transformer.

  • Refrigerant Piping

    27 Liebert DataMate

    10.0 REFRIGERANT PIPINGTable 22 Refrigerant charge

    60 Hz 50 Hz Charge R-407C, oz (kg)DME020E 4 (0.11)

    DME027E 5 (0.14)

    DME037E DME037E 6.5 (0.18)

    MC*24AL_H7 134 (3.80)

    MC*36AL_H7 MC*35AL_H7 213 (6.04)

    MC*26W__H7 41 (1.16)

    MC*38W__H7 MC*37W__H7 54 (1.54)

    DMC022WG 47 (1.33

    DMC029WG 59 (1.67

    DMC040WG 61 (1.72)

    PFH020A-_L7 134 (3.80)

    PFH027A-_L7 134 (3.80)

    PFH027A-_H7 213 (6.04)

    PFHZ27A-_L7 213 (6.04)

    PFH037A-_L7 PFH036A-_L7 213 (6.04)

    PFH037A-_H7 PFH036A-_H7 426 (12.08)

    PFHZ37A-_L7 PFHZ36A-_L7 426 (12.08)

    Table 23 Recommended refrigerant line sizes

    EquivalentLength, ft (m)

    1.5-Ton 2-Ton 3-Ton

    Suction Liquid Suction Liquid Suction Liquid

    50 (15.2 5/8" 3/8" 7/8" 3/8" 7/8" 3/8"

    100 (30.5) 7/8" 3/8" 7/8" 1/2" 1-1/8" 2 1/2"

    150 (45.7) 7/8" 1/2" 7/8" 1/2" 1-1/8" 2 1/2"1. Suction line and liquid line sizing based on < 3 psi pressure drop in each and horizontal suction line refrigerant velocities

    >700FPM (3.6m/s).2. Suction sizes should be reduced one pipe size for vertical riser sections to maintain suction line velocity > 1000FPM (5.1m/s)

    for proper oil return.

    Table 24 Pipe length and condenser elevation relative to evaporatorNominal

    System SizeTons

    Max. Equiv.Pipe Length

    ft. (m)

    Maximum PFHLevel Above

    Evaporator, ft. (m)

    Maximum PFHLevel Below

    Evaporator, ft. (m)

    1.5 & 2 150 (45) 40 (12) 15 (4.6)

    3 150 (45) 50 (15) 15 (4.6)Maximum recommended total equivalent pipe length is 150 ft (46m). Suction and liquid lines may require additional specialty items when vertical lines exceed 20 ft. (6m) and/or condensing unit installation is more than 15 ft. (4.6m) below the evaporator. Contact Emerson Application Engineering for assistance.

    Table 25 Refrigerant charge in Liebert pre-charged R-407C line setsLine Size, in. Length, ft. (m) Charge R-407C, oz (kg)

    3/8 liquid15 (4.5) 5 (0.14)30 (9) 10 (0.28)

    5/8 or 7/8 suction15 (4.5) 5 (0.14)30 (9) 10 (0.28)

  • Refrigerant Piping

    Liebert DataMate 28

    Figure 15 Refrigerant piping diagram

    Table 26 Line charges - refrigerant per 100 ft. (30m) of Type L copper tube

    Line Size,O.D., in.

    R-407C, lb/100 ft. (kg/30m) Liquid Line Suction Line

    3/8 3.7 (1.7) 1/2 6.9 (3.1) 5/8 11.0 (5.0 0.4 (0.2) 3/4 15.7 (7.1) 0.6 (0.3) 7/8 23.0 (10.4) 1.0 (0.4)

    1-1/8 1.7 (0.7) 1-3/8 2.7 (1.1)

    Table 27 Equivalent lengths for various pipe fittings, ft (m)Copper Pipe

    OD, in.90 Degree

    Elbow Copper90 Degree

    Elbow Cast45 Degree

    Elbow TeeGateValve

    GlobeValve

    AngleValve

    1/2 0.8 (0.24) 1.3 (0.39) 0.4 (0.12) 2.5 (0.76) 0.26 (0.07) 7.0 (2.13) 4.0 (1.21)5/8 0.9 (0.27) 1.4 (0.42) 0.5 (0.15) 2.5 (0.76) 0.28 (0.08) 9.5 (2.89) 5.0 (1.52)3/4 1.0 (0.3) 1.5 (0.45) 0.6 (0.18) 2.5 (0.76) 0.3 (0.09) 12.0 (3.65) 6.5 (1.98)7/8 1.45 (0.44) 1.8 (0.54) 0.8 (0.24) 3.6 (1.09) 0.36 (0.1) 17.2 (5.24) 9.5 (2.89)

    1-1/8 1.85 (0.56) 2.2 (0.67) 1.0 (0.3) 4.6 (1.4) 0.48 (0.14) 22.5 (6.85) 12.0 (3.65)1-3/8 2.4 (0.73) 2.9 (0.88) 1.3 (0.39) 6.4 (1.95) 0.65 (0.19) 32.0 (9.75) 16.0 (4.87)1-5/8 2.9 (0.88) 3.5 (1.06) 1.6 (0.48) 7.2 (2.19) 0.72 (0.21) 36.0 (10.97) 19.5 (5.94)

    Refrigerant trap = Four times equivalent length of pipe per this table

    Evaporator

    Evaporator

    Condensing Unit

    NOTEWhen installing remote condensing units below the evaporator, the suction gas line should be trapped with an inverted trap to the height of the evaporator . This prevents refrigerant migration to the compressors during off cycles . Maximum recommended vertical level drop to condensing unit is 15 ft. (4.6m) .

    Pitch down 1/2" (13mm) per 10 ft. (3m)

    Suction Line PipingCondensing Unit Above EvaporatorTraps recommended at the base of riser exceeding 5 ft (1.5m) and every 20 feet (6m) of vertical rise.

    Suction Line Piping Condensing Unit Below Evaporator

    Condensing Unit

    Pitch down 1/2" (13mm) per 10 ft. (3m)

    See Table 24 for recommended maximum vertical rise above evaporator/maximum vertical fall below evaporator.

  • Glycol Loop Piping

    29 Liebert DataMate

    11.0 GLYCOL LOOP PIPING

    Contact Emerson Application Engineering for assistance in choosing correct drycooler models. Refer to Figure 16.

    Figure 16 Heat rejection loop, multiple drycoolers and multiple indoor units

    LEGEND

    P:FS

    FS

    HP____(kW) ____ Per Pump @ ____(kPa)

    GPM (l/s) ft.

    PUMP PACKAGE

    DPN000991Rev. 0

    Drycooler No. 1 Model ______GPM (l/s) ____ P: ___ ft (kPa)

    Expansion Tank______ Gal. (L)

    Drycooler No. 2 Model ______GPM (l/s) ____ P: ___ ft (kPa)

    Gate Valve

    Check Valve

    Relief Valve

    Union

    Butterfly Valve

    Ball or Flow Control Valve

    Flow Switch

    Pressure Drop

    Strainer/Filter

    Notes:1. Pressure and temperature gauges (or ports for same) are recommended to monitor component pressure drops and performance.2. Flow measuring devices, drain and balancing valves to be supplied by others and located as required.3. See product literature for installation guidelines and clearance dimensions.4. Drawing shows dual pump package. Alternate pump packages with more pumps may be considered; consult supplier

    See Note 3

    Cooling Unit #ModelGPM (l/s)P ft (kPa):

    Cooling Unit #ModelGPM (l/s)P ft (kPa):

    Cooling Unit #ModelGPM (l/s)P ft (kPa):

    Cooling Unit #ModelGPM (l/s)P ft (kPa):

    Cooling Unit #ModelGPM (l/s)P ft (kPa):

    Cooling Unit #ModelGPM (l/s)P ft (kPa):

    Cooling Unit #ModelGPM (l/s)P ft (kPa):

    Cooling Unit #ModelGPM (l/s)P ft (kPa):

    Cooling Unit #ModelGPM (l/s)P ft (kPa):

    Cooling Unit #ModelGPM (l/s)P ft (kPa):

    Cooling Unit #ModelGPM (l/s)P ft (kPa):

    Cooling Unit #ModelGPM (l/s)P ft (kPa):

    TotalGPM(L/s): _____PipeDiam.: _____ In. (mm) P: _____ Ft. (kPa)

  • Model Number NomenclatureAll Systems

    Liebert DataMate 30

    12.0 MODEL NUMBER NOMENCLATUREALL SYSTEMS

    Figure 17 Model number nomenclatureEvaporator units

    Figure 18 Model number nomenclatureOutdoor air-cooled condensing units

    Figure 19 Model number nomenclatureIndoor air-cooled condensing units

    H = With Humidifier & Reheat0 = Reheat OnlyC = Cooling Only

    DME 037 E P H 7

    DME = Liebert DataMate Evaporator Unit

    Nominal capacity (kBtuh)

    E = EvaporatorC = Chilled Water

    P = 208/230 1ph, 60HzW = 200/220, 1ph, 50Hz

    7 = R-407C Refrigerant

    PFH A 70

    PFH = Prop FanCondensing Unit with Hot Gas Bypass

    0= Std. Sound LevelZ= Quiet-Line

    A = Air-Cooled

    - = Std. CoilC = Coated Coil

    R-407C Refrigerant

    * Not all combinations are possible.

    37

    Nominal Capacity(kBtuh)

    P L

    P=208/230/1/60Y=208/2303/60A=460/3/60B=575/3/60S=220-1-50M=380/415/3/50

    L = 95 F Ambient.H = 105 F Ambient

    MC

    D = Disconnect Switch0 = No Disconnect Switch

    MC = Liebert Mini-Mate2 Style Indoor Condensing Units

    Refrigerant7 = R-407C

    H = Hot Gas Bypass

    D 36 L A H 7Head Pressure ControlsL = Liebert Lee-Temp Receiver

    Supply PowerP = 208/230V - 1 ph - 60 HzX = 277V - 1 ph - 60 HzS = 220V - 1 ph - 50 HzA = 460V - 3 ph - 60 Hz (3-ton only)Y = 208/230V - 3 ph - 60 Hz (3-ton only)M = 380/415V - 3ph - 50Hz

    A

    Cooling MethodA = Air-Cooled

    Nominal Capacity24 = 2-ton, 60Hz35 = 3-ton, 50Hz36 = 3-ton, 60Hz

  • Model Number NomenclatureAll Systems

    31 Liebert DataMate

    Figure 20 Model number nomenclature, close-coupled water/glycol condensing units60Hz only

    Figure 21 Model number nomenclatureIndoor remote water/glycol-cooled condensing units

    Figure 22 Model number nomenclatureChilled water units

    DMC 040 WG P 07

    Liebert DataMate Evaporator Section

    Nominal Capacity (kBtuh)

    WG = Water/Glycol

    P = 208/230/1/60

    07 = R-407CRefrigerant

    MC

    D = Disconnect Switch0 = No Disconnect Switch

    MC = Liebert Mini-Mate2 Style Indoor Condensing Units

    Refrigerant7 = R-407C

    H = Hot Gas Bypass

    D 38 2 A H 7Head Pressure Controls2 = 2-Way Standard Pressure Water Reg Valve3 = 3-Way Standard Pressure Water Reg ValveD = 2-Way High-Pressure Water Reg ValveT = 3-Way High-Pressure Water Reg Valve

    Supply PowerP = 208/230V - 1 ph - 60 HzX = 277V - 1ph - 60 HzS = 220V - 1ph - 50 HzA = 460V - 3ph - 60 Hz (3-ton only)Y = 208/230V - 3ph - 60 Hz (3-ton only)M = 380/415V 3ph-50Hz

    W

    Cooling MethodW = Water/Glycol

    Nominal Capacity26 = 2-ton, 60Hz37 = 3-ton, 50Hz38 = 3-ton, 60Hz

    DME 044 C P H 7

    Liebert DataMate Cooling Unit

    Nominal Capacity (kBtuh)

    C = Chilled Water

    P = 208/230/1/60W = 200/220/1/50

    H = With Humidifierand Reheat

    0 = Reheat onlyC = Cooling only

    (no RH or HUM)7 = Unit Revision

    Level

  • Guide SpecificationsFor Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)

    Liebert DataMate 32

    GUIDE SPECIFICATIONSFOR LIEBERT DATAMATE 1.5- TO 3-TON (5 TO 10.5KW)

    1.0 GENERAL1.1 Summary

    These specifications describe requirements for an environmental control system. The system shall be designed to maintain temperature and relative humidity conditions within the room.

    The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation requirements of the site.

    System shall be supplied with CSA Certification to the harmonized U.S. and Canadian product safety standard CSA C22.2 No 236/UL 1995 for Heating and Cooling Equipment and marked with the CSA c-us logo (60 Hz only).

    1.2 Design RequirementsThe environmental control system shall be a Liebert DataMate factory assembled unit. The refrigeration system shall be split, with the compressor located in a remote or close-coupled condensing unit. The evaporator section shall be specifically designed for floor or wall-mounted installation and serviceable from the front of the system. Condensing units shall be designed for outdoor or indoor mounting, below the raised floor, above-dropped-ceiling, or in room installation. Refer to Section 2.3 on page 35 and 36 for condensing unit guide specifications.

    Each system shall be capable of delivering ______ CFM. The circulating-air fan shall be two-speed for precise dehumidification control. The fan motor(s) shall total ______hp (kW). The system shall be designed for blow-through air arrangement.

    The system shall have a total cooling capacity of ______ Btu/hr (kW), and a sensible cooling capacity of _____ Btu/hr (kW), based on the entering air condition of ____ F (C) dry bulb, and ____ F (C) wet bulb. These units are to be supplied with ____ Volt, ____ PH, ____ Hz power supply.

    1.3 SubmittalsSubmittals shall be provided with the proposal and shall include: Single-Line Diagrams; Dimensional, Electrical, and Capacity data: Piping and Electrical Connection Drawings.

    1.4 Quality AssuranceThe specified system shall be factory-tested before shipment. Testing shall include, but shall not be limited to: Quality Control Checks, HiPot Test (two times rated voltage plus 1000 volts, per NRTL agency requirements), and Metering Calibration Tests. The system shall be designed and manufactured according to world class quality standards. The manufacturer shall be ISO 9001 certified.

    2.0 PRODUCT2.1 Standard Features/All Systems2.1.1 Evaporator Cabinet and Frame Construction

    The cabinet and chassis shall be constructed of heavy gauge, painted furniture steel. The cabinet shall be designed for easy installation and service access from the front only.

    2.1.2 Air DistributionThe air distribution system shall be constructed with a quiet, direct-drive fan assembly equipped with multiple double-inlet blowers, self-aligning sleeve bearings and lifetime lubrication. Fan motor(s) shall be permanent-split capacitor, high efficiency type, equipped with two speeds for air flow modulation. Dehumidification shall utilize the lower fan speed.

    Air filter shall be a cleanable polypropylene monofilament type over expanded aluminum with aluminum frame. It shall be easily removable from the front of the system by means of quarter-turn fasteners and shall not require system shutdown for service.

  • Guide SpecificationsFor Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)

    33 Liebert DataMate

    2.1.3 Microprocessor Control SystemThe control system shall be microprocessor-based, factory-wired into the system and tested prior to shipment. The wall-mounted control enclosure shall include a 2-line by 16-character LCD providing continuous display of operating status and alarm condition. An 8-key membrane keypad for setpoint/ program control, fan speed selection and unit On/Off shall be located below the display. The control display shall be field-wired to the control board using 4-conductor field-supplied thermostat wire.

    Temperature and humidity sensors shall be located in the wall box, which shall be capable of being located up to 300 ft (91.4m) from the evaporator unit.

    2.1.3.1 MonitoringThe LCD shall provide On/Off indication, operating mode indication (cooling, heating, humidifying, dehumidifying), fan speed indication and current day, time, temperature and humidity (if applicable) indication. The monitoring system shall be capable of relaying unit operating parameters and alarms to the Liebert SiteScan monitoring system.

    2.1.3.2 Control Setpoint Parameters Temperature Setpoint: 65-85F (18 to 29C) Temperature Sensitivity: 1 to 9.9F (1 to 5C) Humidity Setpoint: 20-80% RH Humidity Sensitivity: 1 to 30% RH

    The microprocessor can be set within these ranges; however, the unit may not be able to control to extreme combinations of temperature and humidity.

    2.1.3.3 Unit Controls

    2.1.3.3.1 Compressor Short-Cycle ControlThe control system shall prevent compressor short-cycling by a 3-minute timer from compressor stop to the next start.

    2.1.3.3.2 Common Alarm and Remote On/OffA common alarm relay shall provide a contact closure to a remote alarm device. Two (2) terminals shall also be provided for remote On/Off control. Individual alarms shall be enabled or disabled from reporting to the common alarm.

    2.1.3.3.3 Setback ControlThe control shall be user-configurable to use a manual setpoint control or a programmable, time-based setback control. The setback control will be based on a 5 day/2 day programmed weekly schedule with capability of accepting 2 events per program day.

    2.1.3.3.4 Temperature CalibrationThe control shall include the capabilities to calibrate the temperature and humidity sensors and adjust the sensor response delay time from 10 to 90 seconds. The control shall be capable of displaying temperature values in F or C.

    2.1.3.3.5 System Auto RestartFor startup after power failure, the system shall provide automatic restart with a programmable (up to 9.9 minutes in 6-second increments) time delay. Programming can be performed either at the wall-mounted controller or from the central, site-monitoring system.

  • Guide SpecificationsFor Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)

    Liebert DataMate 34

    2.1.4 Alarms

    2.1.4.1 Unit AlarmsThe control system shall monitor unit operation and activate an audible and visual alarm in the event of the following factory preset alarm conditions.

    High Temperature (max 90F, 32.2C) Low Temperature (min 35F, 1.7C) High Humidity (max 85% RH) Low Humidity (min 15% RH) High Water Alarm - Lockout Unit Operation High Head Pressure Loss of Power Compressor Short Cycle

    2.1.4.2 Custom Alarms (2x) Humidifier Problem Filter Clog Water Detected Smoke Detected Custom Alarm (1) Custom Alarm (2)

    User-customized text can be entered for the two (2) custom alarms

    2.1.4.3 Alarm ControlsEach alarm (unit and custom) shall be individually enabled or disabled (except for high head pressure and high water in condensate pan) and can be programmed for a time delay of 0 to 255 seconds of continuous alarm condition to be recognized as an alarm. Each alarm shall also be enabled or disabled to activate the common alarm (except high head pressure and high water in condensate pan).

    2.1.4.4 Audible AlarmThe audible alarm shall annunciate at the LCD wall box any alarm that is enabled by the operator.

    2.1.4.5 Common AlarmA programmable common alarm shall be provided to interface user selected alarms with a remote alarm device.

    2.1.4.6 Remote MonitoringAll alarms shall be communicated to the Liebert site monitoring system with the following information: date and time of occurrence, unit number and present temperature and humidity.

    2.2 Chilled Water System Components2.2.1 Chilled Water Control Valve

    The water circuit shall include a 2-way, slow-close On/Off solenoid valve. Design pressure shall be 125psi (862kPa). Valve shall be spring return.

    2.2.2 Chilled Water CoilThe cooling coil shall have a minimum of 2.6 ft.2 (.24m2) face area, three rows deep. It shall be constructed of copper tubes and aluminum fins and be mounted in a galvanized condensate drain pan. The coil shall be designed for a maximum face velocity of _____FPM (m/s) at ___ CFM (CMH). The water circuit shall be designed to distribute water into the entire coil face area. The coil shall be supplied with ___ F (C) entering water temperature, with a ___F (C) temperature rise. The coil shall be supplied with ___ GPM (l/s) of chilled water and the pressure drop shall not exceed ______ psi (kPa).

  • Guide SpecificationsFor Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)

    35 Liebert DataMate

    2.2 Direct Expansion System Components2.2.1 Direct Expansion Coil

    The evaporator section shall include an evaporator coil, thermostatic expansion valve and filter-drier.

    The evaporator coil shall have ___ ft2 (m2) face area, ___ rows deep. It shall be constructed of copper tubes and aluminum fins and have a maximum face velocity of ___ FPM (m/s) at _____ CFM (CMH). An externally equalized thermostatic expansion valve shall control refrigerant flow. The evaporator coil shall be factory-charged with R-407C refrigerant and sealed. The coil shall be provided with a galvanized steel drain pan. The evaporator unit can be coupled directly with a water/glycol condensing unit or mounted remote to the indoor or outdoor condensing unit.

    2.3 Indoor Air-Cooled Centrifugal Fan Condensing UnitCondensing unit components shall include condenser coil, scroll compressor, high-pressure switch, Liebert Lee-Temp refrigerant receiver, head pressure control valve, hot gas bypass system and liquid line solenoid valve. The hot gas bypass circuit shall be provided to reduce compressor cycling and improve operation under low-load conditions. Units available for [(2-ton)(3-ton)] systems.

    All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal piping, brazing, dehydration or charging shall be required. Condensing unit shall be designed for 95F (35C) ambient and be capable of operation to -30F (-34C). The condensing unit can be mounted directly to the evaporator or can be mounted remote to the evaporator.

    The condensing coil shall be constructed of copper tubes and aluminum fins. The condenser fan shall be centrifugal type, double inlet, direct drive and shall operate at 1050 rpm (890 rpm @ 50 Hz). The fan and motor shall be mounted on vibration isolators. The condenser fan shall be designed for ____CFM (CMH) at ____" (mm) w.g. external static pressure.

    2.3 Outdoor Air-Cooled Prop Fan Condensing UnitCondensing unit components shall include a condenser coil, a direct-drive propeller-type fan, a scroll compressor, high-pressure switch, Liebert Lee-Temp receiver and head pressure control valve, hot gas bypass system and liquid line solenoid valve. A hot gas bypass system shall be provided to reduce compressor cycling and improve operation under low-load conditions.

    All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal piping, brazing, dehydration or charging shall be required. Condensing unit shall be designed for 95F (35C) ambient and be capable of operation to -30F (-34.4C).

    The condenser coil shall be constructed of copper tubes and aluminum fins.

    (Option) The 2- or 3-ton condensing unit shall be designed to operate at a sound level less than 58dBA.

    (Option) The 2- or 3-ton condensing unit shall be designed for design ambient operation of 105F (40.6C).

    (Option) The condenser coil shall be phenolic-coated for extended coil life in coastal areas.

    2.3 Indoor Close-Coupled Water/Glycol Condensing UnitThe water/glycol-cooled condensing unit shall include a scroll compressor and a water/glycol cooled condenser, and shall be capable of being close-coupled to the evaporator module. The water/glycol cooled condenser shall be designed to balance the heat rejection at ______ F (C) entering water/glycol temperature with a flow rate of ___ GPM (l/s) and have a total system pressure drop of _____ ft of water (kPa). An adjustable two-way water regulating valve shall be included. The condenser water/glycol circuit shall be designed for a static operating pressure of 150psi (1034kPa).

    All components shall be factory assembled, charged with R-407C refrigerant, sealed and be capable of being connected to the evaporator section using quick connect refrigerant couplings and integral wiring harness for single-point power connection for close-coupled system. No refrigeration piping, brazing, dehydration or charging shall be required.

  • Guide SpecificationsFor Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)

    Liebert DataMate 36

    2.3 Indoor Remote Water/Glycol-Cooled Condensing UnitThe water/glycol condensing unit shall include a scroll compressor, high-pressure switch, coaxial condenser, water-regulating valve, hot gas bypass system and liquid line solenoid valve. A hot gas bypass circuit shall be provided to reduce compressor cycling and improve operation under low-load conditions. All components shall be factory-assembled, charged with R-407C refrigerant and sealed. No internal piping, brazing dehydration or charging shall be required. Units available for [(2-ton)(3-ton)] systems.

    The water/glycol condensing unit shall be equipped with a coaxial condenser having a total system pressure drop of ______ ft. of water (kPa) and a flow rate of ______ GPM (l/s) with ______ F (C) entering water/glycol temperature.

    The condenser circuit shall be pre-piped with a [(2-way) (3-way)] regulating valve that is head-pressure actuated.

    The condenser water/glycol circuit shall be designed for a static operating pressure of [(150psi (1034kPa)) (350 PSI (2413 kPa))].

    2.4 Factory-Installed Options2.4.1 Electric Reheat

    The electric reheat shall be low-watt density, tubular element and shall include agency approved safety switch to protect the system from overheating. The capacity of the reheat coil shall be ______ BTU/HR, ____ kW, controlled in 1 stage.

    2.4.2 Steam Generating HumidifierThe environmental control system shall be equipped with a steam generating humidifier that is controlled by the microprocessor control system. It shall be complete with disposable canister, all supply and drain valves, 1" (25.4mm) air gap on fill line, inlet strainer, steam distributor and electronic controls. The need to change the canister shall be annunciated on the microprocessor wall box control panel. The humidifier shall have a capacity of 3 lb./hr. (1.4kg/h). An LED light on the humidifier assembly shall indicate cylinder full, overcurrent detection, fill system fault and end of cylinder life conditions.

    2.5 Ship-Loose Accessories2.5.1 Remote Sensors

    The unit shall be supplied with remote temperature and humidity sensors. The sensors shall be connected to the unit by a 30 ft. (9m) shielded cable.

    2.5.2 Condensate PumpThe condensate pump shall have the capacity of _____ GPH (___ l/h) at ___ ft. head (___ kPa). It shall be complete with integral float switch, discharge check valve, pump, motor assembly and reservoir. A secondary float switch shall be provided to permit field wiring to the unit control to shut down the evaporator upon a high water level condition.

    2.5.3 Refrigerant Line SetsPre-charged refrigerant line sets shall be provided by Emerson in proper lengths for application. Line set length shall be (15 ft. [4.5m]) (30 ft. [9m]) not to exceed 45ft. (13.5m) in total length.

    2.5.4 Refrigerant Line Sweat Adapter KitProvide a sweat adapter kit to permit field brazing of refrigerant line connections for application to split systems.

  • Guide SpecificationsFor Liebert DataMate 1.5- to 3-Ton (5 to 10.5kW)

    37 Liebert DataMate

    2.5.5 Step-Down TransformerA step-down transformer shall be provided for [(Indoor Evaporator) (Close-Coupled Water/Glycol Condensing Unit) (Outdoor Air-Cooled Condensing Unit)] needing 277V input power voltage. The transformer shall be coated with epoxy and contained in an enclosed, non-ventilated electrical box with adaptable mounting brackets, suitable for [(indoor) (outdoor)] mounting.

    2.5.6 Liebert Local Monitoring Systems, Autochangeover and Leak DetectionProvide indicated quantities of the following:

    ______ Leak Detection System(s) Model __________________________________ ______ Remote Monitor(s) Model ________________________________________ ______ Autochangeover Control(s) Model ________________________________

    2.5.7 Liebert SiteScan Site Monitoring SystemA Liebert SiteScan Site Monitoring System Model __________________ shall be provided for remote monitoring of the Liebert DataMate unit and monitoring of other Liebert support equipment. The Liebert SiteScan shall have the capability to monitor and change (at the user direction) the temperature and humidity setpoints and sensitivities of each unit. The printer shall provide the user with chronological alarm information. It shall also be capable of being programmed to print out environmental conditions or operating modes at each unit.

    2.5.8 DrycoolerThe Liebert drycooler shall be a low-profile, direct-drive propeller fan-type air-cooled unit. The drycooler shall be constructed with an aluminum cabinet and a copper-tube aluminum fin coil, and one or more direct drive fans. All electrical connections and controls shall be enclosed in an integral, NEMA 3R rated electrical panel section of the drycooler. The drycooler shall be quiet and corrosion resistant.

    The drycooler shall be designed for _____F (C) ambient.

    2.5.9 Glycol Pump PackageThe system shall include a centrifugal pump mounted in a weatherproof and vented enclosure. The pump shall be rated for ____ gpm (l/s) at ____ ft. (kPa) of head, and operate on _____ volt, ____ phase, ______ Hz.

    3.0 EXECUTION3.1 Installation of Air Conditioning Units3.1.1 General

    Install air conditioning units in accordance with manufacturers installation instructions. Install unit plumb and level, firmly anchored in locations indicated and maintain manufacturer's recommended clearances.

    3.1.2 Electrical WiringInstall and connect electrical devices furnished by manufacturer but not specified to be factory-mounted. Furnish copy of manufacturer's electrical connection diagram submittal to electrical contractor.

    3.1.3 Piping ConnectionsInstall and connect devices furnished by manufacturer but not specified to be factory-mounted. Furnish copy of manufacturer's piping connection diagram submittal to piping contractor.

    3.1.4 Supply and Drain Water PipingConnect water supply and drains to air conditioning unit. Provide pitch and trap as manufacturer's instructions and local codes require.

    3.2 Field Quality ControlStartup air conditioning units in accordance with manufacturer's start up instructions. Test controls and demonstrate compliance with requirements.

  • While every precaution has been taken to ensure the accuracyand completeness of this literature, Liebert Corporation assumes noresponsibility and disclaims all liability for damages resulting from use ofthis information or for any errors or omissions. 2013 Liebert CorporationAll rights reserved throughout the world. Specifications subject to changewithout notice. Liebert is a registered trademark of Liebert Corporation.All names referred to are trademarksor registered trademarks of their respective owners.

    Technical Support / ServiceWeb Site

    www.liebert.comMonitoring

    [email protected]

    Outside North America: +00800 1155 4499Single-Phase UPS & Server Cabinets

    [email protected]

    Outside North America: +00800 1155 4499Three-Phase UPS & Power Systems

    800-543-2378Outside North America: 614-841-6598

    Environmental Systems800-543-2778

    Outside the United States: 614-888-0246

    LocationsUnited States

    1050 Dearborn DriveP.O. Box 29186

    Columbus, OH 43229Europe

    Via Leonardo Da Vinci 8Zona Industriale Tognana

    35028 Piove Di Sacco (PD) Italy+39 049 9719 111

    Fax: +39 049 5841 257Asia

    29/F, The Orient Square BuildingF. Ortigas Jr. Road, Ortigas Center

    Pasig City 1605Philippines

    +63 2 687 6615Fax: +63 2 730 9572

    Emerson Network PowerDivision: LiebertWeb: www.emerson.com

    www.EmersonNetworkPower.com

    SL-11035_REV7_10-13

    1.0 Introduction1.1 Designed to Match Computer and Electronic Equipment NeedsFrom Installation to Operation

    2.0 Standard Features1.5- to 3-Ton Systems2.1 Evaporator SectionSplit-Systems2.2 Condensing Unit S