An Apples for Apples Comparison of the Data Centre Cooling Landscape To provide integrated thermal management solutions, differentiated through innovation and service www.airedale.c om Mark Viner Commercial Director

description

Under the title “An apples for apples comparison of the data centre cooling landscape”, Airedale’s Commercial Director, Mark Viner, provides an overview of legacy and latest generation data centre cooling systems, taking into account the key criteria of energy efficiency, reliability and footprint in addition to capital and operational costs.

Transcript of Data Centre World 2014 Airedale International Air Conditioning Presentation

Page 1: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

An Apples for Apples Comparison of the Data Centre Cooling Landscape

To provide integrated thermal management solutions, differentiated through innovation and service

Mark VinerCommercial Director

Page 2: Data Centre World 2014 Airedale International Air Conditioning Presentation

Who Are We

40 years experience

Design to delivery3kW to 2.0MW

www.airedale.com

Global provider of

efficient cooling

solutions

A Pioneer in free-cooling

technology

An industry leader in rack level cooling

Largest UK manufacturer of IT cooling

solutions

Page 3: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Global Presence

50,000+ applications since 1974

1,400+ last year2013

Page 4: Data Centre World 2014 Airedale International Air Conditioning Presentation

Products

Commercial Products:

• Commercial Heating• Commercial Air Conditioning• Commercial Ventilation• Data Centre Cooling• Air Handling Units• Geothermal

Commercial Products Group

£110 M

£60 M £50 M

Page 5: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Our Clients

Page 6: Data Centre World 2014 Airedale International Air Conditioning Presentation

Business Issues

Efficiency

Capital Costs

Operational Costs

Footprintand Density Uptime

Solution

Page 7: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Key Driver - “Increasing Digitalisation”

The data centre market is growing on a global scale The need for data is growing…

Power demand is rising

and thus cooling needsare increasing

Psy’s Gangnam Style

Research Courtesy of ‘Jon Summers’ of University of Leeds

Page 8: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

An Apples for Apples Comparison of the Data Centre Cooling Landscape

To provide integrated thermal management solutions, differentiated through innovation and service

Mark VinerCommercial Director

Page 9: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Apples For Apples

500kW heat load

10kW per rack

50 racks

UK ambient dry and wet bulb profile

Fixed return air temperatures

Page 10: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Definitions

Adiabatic

Free Cooling

Mechanical Cooling

Direct Indirect

Page 11: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape

-10 -5 0 5 10 15 20 25 30 35 40

20

40

60

80

100

120

Ambient Dry Bulb Temperature (°C)

DX CRACs

Chillers

Free Cooling AHUs

Power Consumption(kWhour)

Page 12: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape

-10 -5 0 5 10 15 20 25 30 35 40

20

40

60

80

100

120

Ambient Dry Bulb Temperature (°C)

DX CRACs

Chillers

Free Cooling AHUs

Power Consumption(kWhour)

Page 13: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – CRAC and AHUs

System TypePrimary Cooling Medium

IndoorProduct

OutdoorProduct

DirectOr

Indirect

FreeCooling

ConcurrentMechanical

CoolingAdiabatic

Chiller System+ Adiabatic Chiller

DX CRAC System Condenser

Chiller System

Standard Chiller

Chiller System+ Free Cool Chiller

FREE

COOL

Chiller System+ Adiabatic & Free Cool Chiller

FREE

COOL

System TypePrimaryCoolingMedium

OutdoorProduct

DirectOr

Indirect

FreeCooling

Concurrent

Mechanical Cooling

Adiabatic

Direct AHU+ Concurrent AHU

FREE

COOL

Direct AHU + Adiabatic AHU

FREE

COOL

Indirect AHU+ Concurrent AHU

FREE

COOL

Indirect AHU+ Adiabatic AHU

FREE

COOL

Page 14: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – CRAC Unit Options

System Type IndoorProduct

OutdoorProduct

FreeCooling

AdiabaticPrimary Cooling Medium

Direct Or

Indirect

DX CRAC SystemCondenser

Page 15: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Primary Cooling Medium

Direct / Indirect

FREE

COOL

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Landscape – CRAC Unit Options

Refrigerant CRAC System and Condenser

Page 16: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – CRAC Unit Options

Chiller SystemStandard Chiller

System Type IndoorProduct

OutdoorProduct

FreeCooling

AdiabaticPrimary Cooling Medium

Direct Or

Indirect

DX CRAC SystemCondenser

Page 17: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Landscape – CRAC Unit Options

Chilled Water CRAC System + Chiller

Page 18: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – CRAC Unit Options

Chiller SystemStandard Chiller

System Type IndoorProduct

OutdoorProduct

FreeCooling

AdiabaticPrimary Cooling Medium

Direct Or

Indirect

DX CRAC SystemCondenser

Chiller System+ Adiabatic Chiller

Page 19: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Landscape – CRAC Unit Options

Chilled Water CRAC System + Adiabatic Chiller

Page 20: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – CRAC Unit Options

Chiller SystemStandard Chiller

Chiller System + Free Cool Chiller

FREE

COOL

System Type IndoorProduct

OutdoorProduct

FreeCooling

AdiabaticPrimary Cooling Medium

Direct Or

Indirect

DX CRAC SystemCondenser

Chiller System+ Adiabatic Chiller

Page 21: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – CRAC Unit Options

Chilled Water CRAC System + Free Cooling Chiller

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Page 22: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – CRAC Unit Options

Chiller System + Adiabatic & Free

Cool Chiller

FREE

COOL

Chiller SystemStandard Chiller

Chiller System + Free Cool Chiller

FREE

COOL

System Type IndoorProduct

OutdoorProduct

FreeCooling

AdiabaticPrimary Cooling Medium

Direct Or

Indirect

DX CRAC SystemCondenser

Chiller System+ Adiabatic Chiller

Page 23: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – CRAC Unit Options

Chilled Water CRAC System + Adiabatic Free Cooling Chiller

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Page 24: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – Air Handling Unit Options

System TypePrimary Cooling Medium

Outdoor Product

Director

Indirect

FreeCooling

Concurrent Adiabatic

Direct AHU + Concurrent AHU

FREE

COOL

Page 25: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Landscape – Air Handling Unit Options

Direct Air Free Cooling Air Handling Unit

Page 26: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – Air Handling Unit Options

System TypePrimary Cooling Medium

Outdoor Product

Director

Indirect

FreeCooling

Concurrent Adiabatic

Direct AHU + Adiabatic AHU

FREE

COOL

Direct AHU + Concurrent AHU

FREE

COOL

Page 27: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Cooling Landscape – Air Handling Unit Options

Direct Air Free Cooling Air Handling Unit + Adiabatic

Page 28: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – Air Handling Unit Options

System TypePrimary Cooling Medium

Outdoor Product

Director

Indirect

FreeCooling

Concurrent Adiabatic

Direct AHU + Adiabatic AHU

FREE

COOL

Direct AHU + Concurrent AHU

FREE

COOL

Indirect AHU + Concurrent AHU

FREE

COOL

Page 29: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – Air Handling Unit Options

Indirect Air Free Cooling Air Handling Unit

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Page 30: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – Air Handling Unit Options

System TypePrimary Cooling Medium

Outdoor Product

Director

Indirect

FreeCooling

Concurrent Adiabatic

Direct AHU + Adiabatic AHU

FREE

COOL

Indirect AHU + Adiabatic AHU

FREE

COOL

Direct AHU + Concurrent AHU

FREE

COOL

Indirect AHU + Concurrent AHU

FREE

COOL

Page 31: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – Air Handling Unit Options

Indirect Air Free Cooling Air Handling Unit + Adiabatic

FREE

COOL

Primary Cooling Medium

Direct / Indirect

Free Cooling

Concurrent (Free and

Mech)

Mechanical Cooling

Adiabatic Cooling

Page 32: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape – CRAC and AHUs

System TypePrimary Cooling Medium

IndoorProduct

OutdoorProduct

DirectOr

Indirect

FreeCooling

ConcurrentMechanical

CoolingAdiabatic

Chiller System+ Adiabatic Chiller

DX CRAC System Condenser

Chiller System

Standard Chiller

Chiller System+ Free Cool Chiller

FREE

COOL

Chiller System+ Adiabatic & Free Cool Chiller

FREE

COOL

System TypePrimaryCoolingMedium

OutdoorProduct

DirectOr

Indirect

FreeCooling

Concurrent

Mechanical Cooling

Adiabatic

Direct AHU+ Concurrent AHU

FREE

COOL

Direct AHU + Adiabatic AHU

FREE

COOL

Indirect AHU+ Concurrent AHU

FREE

COOL

Indirect AHU+ Adiabatic AHU

FREE

COOL

Page 33: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Free Cooling Potential

Wet Bulb atPeak Dry Bulb

Peak Dry Bulb

35

15

0

10

5

20

25

30

Jan May Jun Jul Aug Sep Oct Nov DecFeb Mar Apr

°C

ASHRAE Data for London Gatwick. IWEC (International Weather for Energy Calculation)

FREE

COOL

Free CoolingThreshold

Page 34: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Total Cost of Ownership (5yrs) – 500kW System

DX CRAC

Chiller

Adiabatic Chiller

FC Chiller

Adiabatic FC Chiller

Direct + Concurrent

Direct + Adiabatic

Indirect + Concurrent

Indirect + Adiabatic

0 400 800£k

Operational Costs

Capital Costs

Page 35: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Annualised PUE – 500kW System

1.10 1.25 1.45

DX CRAC

Chiller

Adiabatic Chiller

FC Chiller

Adiabatic FC Chiller

Direct + Concurrent

Direct + Adiabatic

Indirect + Concurrent

Indirect + Adiabatic

Page 36: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Total Cost of Ownership – 500kW System

700

200

Year 1

Year 2

Year 3

Year 4

Year 5

400

0

£k Chiller - Standard£676,000

Chiller + Adiabatic£686,000

Chiller + Free Cooling£384,000

Chiller + Adiabatic & Free Cooling

£359,000

Direct AHU + Concurrent£272,000

Direct AHU + Adiabatic£271,000

Indirect + Concurrent£358,000

Indirect + Adiabatic£354,000

DX CRAC£628,000

£357,573£270,079

100

300

500

600

Page 37: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Equipment Footprint

0 25 50m2

Indoor Footprint

Total System Footprint

DX CRAC

Chiller

Adiabatic Chiller

FC Chiller

Adiabatic FC Chiller

Direct + Concurrent

Direct + Adiabatic

Indirect + Concurrent

Indirect + Adiabatic

Indoor Footprint

Page 38: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape

-10 -5 0 5 10 15 20 25 30 35 40

20

40

60

80

100

120

Ambient Dry Bulb Temperature (°C)

Power Consumption(kW/hour)

DX CRACs

Chillers

Free Cooling AHUs

Page 39: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Cooling Landscape

-10 -5 0 5 10 15 20 25 30 35 40

20

40

60

80

100

120

Ambient Dry Bulb Temperature (°C)

DX CRACs

Chillers

Free Cooling AHUs

Power Consumption(kW/hour)

Page 40: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Data Centre Solutions

AireFlowTM

AHUs100-300kW

SmartCoolTM

16-233kWInRakTM

10-63kWCondensers/Dry Coolers12-174kW

Free-coolingChillers20kW-1.8MW

OnRakTM

3-35kW

Page 41: Data Centre World 2014 Airedale International Air Conditioning Presentation

www.airedale.com

Data Centre Solutions

ACISTM Integrated Controls Solutions

AireFlowTM AHUs

100-300kW

SmartCoolTM

16-233kWInRakTM

10-63kWCondensers/Dry Coolers12-174kW

Free-coolingChillers20kW-1.8MW

OnRakTM

3-35kW

Page 42: Data Centre World 2014 Airedale International Air Conditioning Presentation

Data Centre Cooling Solutions

Efficiency

Capital Costs

Operational Costs

Footprintand Density Uptime

Data CentreSolution