Danfoss Sprezarki R-134 Katalog

212
Compressors for R134a 220-240V 50Hz & 60Hz COMPRESSORS Collection of Datasheets REFRIGERATION AND AIR CONDITIONING

Transcript of Danfoss Sprezarki R-134 Katalog

COMPRESSORS

Collection of Datasheets

Compressors for R134a 220-240V 50Hz & 60Hz

R E F R I G E R AT I O N A N D A I R C O N D I T I O N I N G

Standard CompressorsP-Series PL20F (50Hz) PL35F (50Hz) PL50F (50Hz) PL50F (HST/50Hz) T-Series TL2.5F (50Hz) TL3F (50Hz) TL4F (50Hz) TL5F (50Hz) TLS4F (50Hz) TLS5F (50Hz) TLS6F (50Hz) TLS7F (50Hz) N-Series NL6F (50Hz) NL7F (50Hz) NL8F (50Hz) NL9F (50Hz) NL11F (50Hz) NF7FX (50/60Hz) NF9FX (50Hz) NF10FX (50/60Hz) NF11FX (50Hz) NL10MF (50/60Hz) F-Series FR7.5F (50Hz) FR8.5F (50Hz) FR10F (50Hz) S-Series SC15F (50Hz) SC18F (50Hz) SC21F (50Hz) SC12G (60Hz) SC15G (60Hz) SC18G (60Hz) Page Page Page Page 12 14 16 18

Energy-optimized CompressorsN-Series NLE6F (50Hz) NLE7F (50Hz) NLE8FK (50Hz) NLE9F (50Hz) Page Page Page Page 88 90 92 94

Energy-optimized Tropical CompressorsN-Series NLE9FT (50Hz)

Page 146

Page Page Page Page Page Page Page Page

20 22 24 26 28 30 32 34

Universal CompressorsP-Series PL35G (50/60Hz) Page 148 T-Series TL2.5G TL3G TL4G TL5G F-Series FR6G FR7.5G FR8.5G FR10G FR11G

High Energy-optimized CompressorsT-Series TLY4F TLY5FK TLX6FK N-Series NLY5.5FK NLY6F NLY7F NLY9FK (50Hz) (50Hz) (50Hz) Page 96 Page 98 Page 100

(50/60Hz) (50/60Hz) (50/60Hz) (50/60Hz)

Page Page Page Page

150 152 154 156

Page Page Page Page Page Page Page Page Page Page

36 38 40 42 44 46 48 50 52 54

(50Hz) (50Hz) (50Hz) (50Hz)

Page Page Page Page

102 104 106 108

(50/60Hz) (50/60Hz) (50/60Hz) (50/60Hz) (50Hz)

Page Page Page Page Page

158 160 162 164 166

Variable Speed Drive CompressorsT-Series TLV5F (50-60Hz) TLV6F (50-60Hz) TLV7F (50-60Hz)

Page 56 Page 58 Page 60

Page 110 Page 112 Page 114

Page Page Page Page Page Page

62 64 66 68 70 72

Tropical CompressorsT-Series TLS3FT (50Hz) TLS4FT (50Hz) TLS5FT (50Hz) TFS4FT (50Hz) TFS4.5FT (50Hz) N-Series NL6FT NL6.1FT NL7FT NL9FT NL10FT Page Page Page Page Page 116 118 120 122 124

S-Series SC10G (50/60Hz) SC12G (50/60Hz) SC15G (50/60Hz) SC18G (50/60Hz) SC21G (50/60Hz) S-Series (Twins) SC12/12G (50Hz) SC15/15G (50Hz) SC18/18G (50Hz) SC21/21G (50Hz)

Page Page Page Page Page Page Page Page Page

168 170 172 174 176 178 180 182 184

Heat Pump CompressorsT-Series TL4GH (50/60Hz) Page 186

Energy-optimized CompressorsP-Series PLE35F (50Hz) PLE50F (50Hz) T-Series TLES3F (50Hz) TLES4F (50Hz) TLES5F (50Hz) TLES6F (50Hz) TLES7F (50Hz) Page 74 Page 76

F-Series FR7GH (50/60Hz) Page 188 (50/60Hz) (50Hz) (50Hz) (50Hz) (50Hz) Page Page Page Page Page 126 128 130 132 134 S-Series SC10GH SC12GH SC15GH SC18GH SC10GHH SC15GHH SC10GH SC12GH SC15GH SC18GH

Page Page Page Page Page

78 80 82 84 86

S-Series SC12FT (50/60Hz) SC15FT (50/60Hz) SC18FTX (50/60Hz) SC21FTX (50Hz) SC21FTX (60Hz)

Page Page Page Page Page

136 138 140 142 144

(50Hz) (50Hz) (50Hz) (50Hz) (50Hz) (50Hz) (50/60Hz) (50/60Hz) (50/60Hz) (50/60Hz)

Page Page Page Page Page Page Page Page Page Page

190 192 194 196 198 200 202 204 206 208

2

CK.40.B7.02

August 2003

1. General

This collection of datasheets contains information on Danfoss hermetic refrigeration compressors for 220-240V especially designed for refrigeration systems using refrigerant R134a (CF3-CH2F). The programme consists of the basic types PL, TL, TLV, TF, NL, NF, FR, SC and SC Twin.

8238-2

8238-3

8238-16

8238-4

PL

TL (TF similar)

TLV

NL (NF similar)

8238-5

8238-6 8238-7

FR 1.1 Compressor designations

SC

SC Twin

The compressor designations are built up according to the following system:Compressor design Optimization level Compressor size Application range F R134a LBP(MBP) FT R134a LBP tropical FK R134a LBP/(MBP) LST FX R134a LBP/(MBP) HST G R134a LBP/MBP/HBP GH R134a Heat pumps GHH R134a Heat pumps (optimized) MF R134a MBP Start characteristics

PL

TL, TF

Blank Standard energy level S Semi-direct intake E Energy-optimized (optimized motor) Y, X High Energyoptimized (high optimization level)

Nominal displacement in cm3

Blank universal (principal rule) K = LST characteristics (capillary tube) X = HST characteristics (expansion valve)

NL, NF

FR

Exception: For PL compressors the capacity at rating point is stated

SC Example TL NL SC

ES E

5 7 21

F F FT X

1.2 Design

Compressors with the denominations PL, PLE, TLS, TFS, TLES, TLY, NL, NF and NLE are designs with semi-direct intake. Compressors with the denomination NLY are designs with direct intake. Please note that the suction and process connectors on all TLS, TLES, and TLY compressors have been interchanged as compared with the basic TL compressors. Using the wrong connector as suction connector on PL, PLE, TLS, TFS, TLES, TLY, NL, NF and NLE compressors will lead to reduced capacity and efficiency. Using the wrong connector as suction connector on the NLYs is not allowed since the compressor will not function.

August 2003

CK.40.B7.02

3

1.3 Type label

NL6FApplication220-240V~50Hz LBP LST/HST

105GR134a

Barcode on white background Yellow background

DANFOSS COMPRESSORS

1.4 Data stamping

Danfoss compressors have a manufacturing date code stamping on the housing. The form mainly used recently is stamping into the top cover of the housing. On some compressor production lines the stamping has been changed to needle printing into the side of the housing. This is going to be introduced on all products. For a certain period 2 different codes, in needle printing and cover stamping, will be used in parallel. The coding is designed not to be mixed up with the previous version.

Example (recent date code):L--4F-4400 F-203E1157 The first line states the model designation and the code no. L= last letter (or last two letters) of the compressor type -4F- = nominal displacement and application 4400 = 4 last digits in the code no. (= position mark) The second line states the date of manufacture and internal Danfoss codes. F = manufacturing place (F = Germany, AL = Slovenia, AM = Mexico) 20 = week 20 3 = 2003 E = Friday (A = Monday etc.) 115 = nominal voltage 7 = internal Danfoss code The country of origin (manufacturing place) is also stamped on the compressor cover.

Example (new date code):H49477 (6 characters) 113A01B (7 characters) Composition of line 1 H4947: Compressor type information (102H4947 = H4947) 7: internal Danfoss code Composition of line 2 11: Production week 3: Production year A: Production day A = Monday, B = Tuesday, C = Wednesday, etc. 01: Production hour 00 to 23 or shift code -1, -2, -3 B: Danfoss Compressors internal production location code A to G Germany K to N Slovenia R, S Mexico

1.5 Compressor dimensions

The build-in conditions (total height, weight, tube dimensions etc.) are specified in the individual datasheets including dimensioned sketches for the compressors.

4

CK.40.B7.02

8273-3

Blue stripe Approvals

6606

All compressors have a yellow label with the type designation. This label has a blue stripe and the text R134a. The country of origin indicated on the compressor paper label and on the compressor cover varies depending on the manufacturing place. Information can be found on our technical information sheet Country of Origin.

August 2003

2. Application range

F

Compressors with denominations ending with F are primarily designed for low evaporating temperatures (LBP Low Back Pressure) for use in refrigerators, freezers and similar applications in regions with stable supply voltage. Compressors with denominations ending with FT are designed for low evaporation temperatures (LBP Low Back Pressure) for use in refrigerators, freezers and similar applications operating in regions with unstable supply voltage. Compressors with denominations ending with FK are F-types designed for low evaporation temperatures with LST starting characteristics (capillary tube). Compressors with denominations ending with FX are F-types designed for low evaporation temperatures with HST starting characteristics (expansion valve). Compressors with denominations ending with G are primarily designed for high evaporation temperatures (HBP High Back Pressure) for use in liquid coolers, dehumidifiers, refrigerated display counters, vending machines and similar applications. The compressors can also be used for Heavy Duty purposes at low evaporating temperatures for use in refrigerators, freezers and similar applications operating in regions with unstable supply voltage. Compressors with denominations ending with GH are designed for high evaporating temperatures for cooling of electronic cabinets and for use in heat pump systems. Compressors with denominations ending with GHH are optimized versions of GH compressors. Compressors with denominations ending with MF are primarily designed for medium evaporation temperatures (MBP Medium Back Pressure) for use in commercial refrigerators, bottle coolers, ice machines and similar applications. The table on page 6 shows the normally recommended applications as regards voltage/ frequency, ambient temperature, evaporating temperature and necessary compressor cooling. The recommendations must be regarded as a guideline only as they presuppose a proper dimensioning of the refrigeration system.

FT

FK

FX

G

GH

GHH

MF

2.1 Design limits

Condensing temperature Winding temperature

In order to secure a satisfying lifetime of the compressor, and to protect the compressor against overload, some design criteria for the appliances must be fulfilled. Both the condensing temperature and the compressor temperature should be kept as low as possible. This can be done by using well-dimensioned condenser surfaces and by ensuring good ventilation around the compressor under all operating conditions. In order to protect the compressor against overload, the compressor has to start and work properly through pressure peaks obtained in the highest ambient temperature and lowest obliging voltage. At peak load the condensing temperature must not exceed 70C. The winding temperature must not exceed 135C. At stable operation conditions the condensing temperature must not exceed 60C. The winding temperature must not exceed 125C. These limitations secure a protection of valves, gaskets, oil, and motor insulation.

August 2003

CK.40.B7.02

5

Compressor PL20 - 35 - 50F PLE35 - 50F TL2.5 - 3F TL4 - 5F TLS4 - 5 - 6F TLS7F TLES3F TLES4F TLES5F TLES6F TLES7F TLY4F TLY5FK TLX6FK TLV5 - 6 - 7F NF7FX NF9FX NF10FX NF11FX NL6 - 7 - 8 - 9F NL11F NLE6 - 7 - 9F - NLE8FK NLY6 - 7F - NLY5.5 - 9FK FR7.5 - 8.5 -10F SC15 - 18 - 21F TFS4 - 4.5FT TLS3 - 4 - 5FT NL6FT NL6.1FT NL7FT NL9 - 10FT NLE9FT SC12 - 15FT SC18FTX SC21FTX SC21FTX PL35G

Mains [V/Hz] 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50-60 198 - 242 /50 198 - 242 /60 198 - 242 /50 198 - 242 /50 198 - 242 /60 198 - 242 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /50 176 - 242 /50 187 - 254 /50 187 - 254 /50 198 - 254 /60 187 - 254 /50 187 - 254 /50 187 - 254 /50 187 - 254 /50 187 - 254 /50 198 - 254 /60 187 - 254 /50 198 - 254 /60 187 - 254 /50 187 - 254 /60 198 - 254 /50 198 - 254 /60 187 - 254 /50 198 - 254 /50 198 - 254 /60 207 - 254 /60 187 - 254 /50 198 - 254 /50 198 - 254 /60 187 - 254 /50 198 - 254 /50 198 - 254 /60 187 - 254 /50 198 - 254 /50 198 - 254 /60 187 - 254 /50 198 - 254 /50 198 - 254 /60 198 - 254 /50 187 - 254 /50 198 - 254 /50 198 - 254 /60 187 - 254 /50 198 - 254 /50 198 - 254 /60 198 - 254 /60 187 - 254 /50 198 - 254 /50 198 - 254 /60 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /60 198 - 254 /50 198 - 254 /60 198 - 254 /50 198 - 254 /50 198 - 254 /50 198 - 254 /60 198 - 254 /50 187 - 254 /50 198 - 254 /60 LBP S S* S S S S S S S S S S S S* S S F1 O/F1 F1 F2 F2 S O/F1 S S* S O/F1 S S S S S S S S O/F1 O/F1 F2 F2 F2 F2

S

S S S*1) S* S S* S

S

F FK FX

S F1 O/F1 F1 F2 F2

S*

Run capacitor compulsory Run capacitor recommended Not applicable below -25C evaporating temperature in 43C ambient temp. above 240V O/F1 possible at 220V nominal (187-242V)

32C MPB S S* S

HBP

FT FTX

S S S S S O/F1 O/F1 S F2*** F2*** F2 F2 F2 F2

F2 F2 S S

F2

TL2.5G

S

S

S

S

S S S F2 S S

S F2 S S

F2 F2

TL3 - 4 - 5G

FR6G

S

S

F2

S

S

F2

S

S

F2

FR7.5G

S

F2

F2

S

F2

F2

O/F1

F2

F2

G

FR8.5 - 10G FR11G SC10G

S F2 F1

F2 F2 F1

F2 F2 F2

O/F1 F2 F1

F2 F2 F1

F2 F2 F2

O/F1 F2 F1

F2 F2 F1

F2 F2 F2

SC12 - 15 - 18G SC12 - 15 - 18G SC21G SC12/12G SC15/15G Twin SC18/18G SC21/21G Twin TL4GH FR7GH GH SC10 - 12 - 15 GH SC18GH SC10 - 12 - 15 - 18GH GHH MF SC10 - 15GHH NL10MF

O/F1

F2 F2

F2

O/F1

F2 F2

F2

O/F1

F2 F2

F2

F2

F2

F2

F2

F2

F2

F2**

F2

F2

F2 F2

F2 F2 F2 O/F1

F2 F2 F2 O/F1 F1 F2

F2 F2

F2 F2 F2 O/F1

F2 F2 F2 O/F1 F1 F2

F2 F2**

F2 F2 F2 O/F1

F2 F2 F2 O/F1 F1 F2

F2 O/F1 O/F1

F2 O

F2 O/F1 O/F1

F2 O

F2 O/F1 O/F1

F2 O

6

CK.40.B7.02

S O F1 F2

= = = = =

Static cooling normally sufficient Oil cooling Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temp.) Fan cooling 3.0 m/s necessary Outside application range, not recommended

S

S

F2

August 2003

The application limits regarding evaporating temperatures and motor systems are specified in the individual compressor datasheets.

Ambient temperature 38C LBP MBP HBP S S S* S* S S S S S* S S S S S* S* S S S* S F1 F1 F1 F1 O/F1 O/F1 F2 F2 F2 F2 F2 F2 S O/F1 S S* S O/F1 S S S S S S O/F1 S O/F1 O/F1 F2 F2 F2 F2 F2 F2 F2

LBP

43C MBP

HBP

* *1) ** ***

= = = =

3. Electrical equipment

The compressors are equipped with a single-phase AC motor. With the exception of the smallest TL and the biggest SC compressors the TL, TLS, NL, FR, and SC compressors are designed with universal motors which means that they can obtain a high (HST) or low starting torque (LST) depending on the external electrical equipment used. The electrical equipments are classified as normal tight (IP20) The motor protector is built into the motor (winding protector). Earth connections are located on the bracket around the current lead-in of the compressor. No attempt must be made to start the compressor without a complete starting device. The compressors can be supplied with the following motor systems:

3.1 LST (RSIR)standard

8074

8073

alternative

PL, TL, NL, FR

TFS

Compressors with the motor type Resistant Start Induction Run (RSIR) have a starting device for Low Starting Torque (LST). The design of the electrical equipment depends on the actual compressor design. The following designs of starting devices exist: a) PTC + cord relief + cover, the motor protector is built into the motor (winding protector), used for compressors with the denominations PL, TL, NL, FR, and SC. b) Relay housing including motor protector + cord relief + cover (alternative: terminal board with cord relief), used for compressors with the denomination TFS. The PTC starting device requires a pressureSC equalization before each start. This starting device is normally used in well-designed refrigerating systems with capillary tube as throttling device. The PTC needs a compressor standstill period of 5 minutes to cool down before each start. 3.2 LST (RSCR)8190

Compressors with the motor type Resistant Start Capacitor Run (RSCR) have a starting device for Low Starting Torque (LST). This starting device consists of a PTC and a run capacitor and is mandatory for compressors with the denominations PLE, TLY and NLY. The PTC starting device requires a pressure-equalization before each start. This starting device is normally used in well-designed refrigerating systems with capillary tube as throttling device.8075

PLE, TLES, TLY, NLE, NLYAugust 2003 CK.40.B7.02 7

8074-2

3.3 HST (CSIR)

PL, TL, NL, FR

8076

NF

Compressors with the motor type Capacitor Start Induction Run (CSIR) have a starting device for High Starting Torque (HST). This starting device consists of a starting relay and a starting capacitor and is used for compressors with the denominations TL, NL, NF, FR and SC. The following designs of starting devices exist: a) Relay + starting capacitor + cord relief + cover, used for compressors with the denominations TL, NL, FR and SC. b) Relay housing including motor protector + starting capacitor + cord relief (2x) + cover, used for compressors with the denomination NF. The starting device requires no pressure-equalization before each start and is normally used in refrigerating systems with expansion valve as throttling device or in capillary tube systems where pressure equalizing is not obtained during the standstill periods. The starting device is mandatory for NF-FX compressors and for some of the biggest SC compressors. The starting capacitor is designed for short time cut-in. 1.7% ED, which is stamped on the starting capacitor, means for instance max. 10 cutins per hour each with a duration of 6 seconds.

SC

8088

3.4 HST (CSR)

Compressors with the motor type Capacitor Start Run (CSR) have a starting device for High Starting Torque (HST). This starting device consists of a starting relay, a starting capacitor, a run capacitor, a terminal board, a cord relief, and a cover. The starting device is mandatory for some of the biggest SC compressors. The starting capacitor is designed for short time cutin. 1.7% ED, which is stamped on the starting capacitor, means for instance max. 10 cut-ins per hour each with a duration of 6 seconds.8191

SC8 CK.40.B7.02 August 2003

8077-2

3.5 Electronic unit (variable speed)

8434

TLV

The variable speed compressor motors are electronically controlled. No attemp must be made to start the compressor without a complete electronic unit, as specified in the data sheet for the compressor type in question. The electronic unit has a built-in overload protection as well as thermal protection. In case of activation of this protection the electronic unit will protect the compressor motor as well as itself. When the protection has been activated, the electronic unit automatically will restart the compressor after a certain time. The electronic unit provides the compressor with High Starting Torque (HST) which means that a pressure-equalizeation of the system before start is not necessary.

The compressors are equipped with permanent magnet rotors (PM motor) and 3 identical stator windings. The electronic unit is mounted directly on the compressor and controls the PM motor. Connecting the motor to AC mains, by fault, will damage the magnets and lead to drastically reduced efficiency, or even non functioning. For further information on which starting device to use on individual compressors, please refer to the actual datasheets (some compressors have limitations for either LST or HST).

3.6 Connections

The electrical equipments are equipped with connectors depending on the ordered code number, Starting relays: 6.3 mm spade connectors only PTCs: 6.3 or 4.8 mm spade connectors and screws Variable speed electronic unit: 6.3 mm spade connectors only The power supply must be connected as shown in the wiring diagrams for the chosen electrical equipment given in the actual datasheets.

3.7 Approvals

The compressors have been approved in respect of safety by testing authorities in the majority of Western European countries. Actual standards to which the compressors have been approved are specified in the individual datasheets. Approval markings appear on the compressor labels. To fulfil the requirements of EN 60355-2-34 the protection screen 103N0476 must be applied to the PTC starting device. Most compressors which are capable of running at 60Hz have been approved in respect of safety by testing authorities UL and CSA. Actual standards to which the compressors have been approved are specified in the individual datasheets. Approval markings appear on a separate approval mark label.

R

TL3G 230V-60Hz 1PHTHERMALLY PROTECTED

7363

Approval mark

Protection screen

August 2003

CK.40.B7.02

8284-4

9

4. Moisture and impurities

The compressors are dried to a maximum moisture content of 60 to 75 mg depending on the compressor size. The maximum impurity content is 40 to 50 mg depending on the compressor size.

5. Max. refrigerant charge

The refrigerant charge must never be too large to be contained on the condenser side of the refrigeration system. Only the refrigerant amount which is necessary for the system to function must be charged. The refrigerant amount may be critical as regards oil foaming and liquid hammer after long standstill periods. Because of this, limitations of refrigerant charges have been introduced. The maximum refrigerant charge is specified in the individual datasheets. If these limitations cannot be complied with, the risk may be reduced if a crankcase heater is properly used or if a pump down system is established.

6. Oil charge

The compressors are supplied charged with dried and degassed oil, which is normally sufficient for the lifetime of the compressor. The refrigeration systems and the system components must be dimensioned in such a way that the oil can be lead back continuously to the compressor housing without accumulating in the system, e.g. without oil pockets and with sufficient gas velocity. The compressors use polyolester oils and are approved only for these oils and R134a. The oil charge is specified in the individual datasheets.

7. Mounting

Soldering problems caused by oil in the connectors can be avoided by placing the compressor on its baseplate some time before soldering it into the system. The compressor must never be placed upside down when mounting the rubber grommets in the baseplate. Instead place the compressor on its side with the connectors upwards.

7.1 Mounting accessories

Washer Compressor base

Nut M6 Grommet sleeve

Washer Compressor base

Clip Steel pin

9

3327-2

Cabinet base Cabinet base Screw M6 x 25 Rubber grommet

Rubber grommet

Bolt joint

Snap-on joint

The mounting accessories for the compressors are available in two versions, with bolt joint or snap-on joint. The code numbers for the mounting accessories are specified in the individual compressor datasheets. These rubber grommets are designed for the 5/8 in. (16 mm) holes of the baseplate: Bolt joint for one compressor in a bag 118 - 1917 (with screw M6 x 25 mm) 118 - 1946 (with screws 1/4 inch) Bolt joint in quantities 118 - 1918 (with screws M6 x 25 mm) Snap-on in quantities 118 - 1919 Snap-on for one compressor in a bag 118 - 1947 These rubber grommets are designed for the 3/4 in. (19 mm) holes of the baseplate: Bolt joint in quantities 118 - 1949 (with screws 1/4 inch)

10

CK.40.B7.02

August 2003

97382-2

8. Condition at delivery

The compressors are delivered without mounted starting devices on pallets with the dimensions 1144 x 800 mm. Quantities per pallets are specified in the individual datasheets. Electrical equipment is packed in separate boxes. The most important performance controls carried out during manufacturing are, A high potential insulation test with 1650V for 1 second Pumping capacity Tightness of discharge side and discharge valve Tightness of compressor housing Check of the right oil charge Noise test The compressors are supplied with sealed connectors and the sealing should not be removed before the system assembly takes place (max. 15 minutes with open connectors).

9. Twin-compressors

The Twin version consists of two SC compressors mounted on a common baseplate. The two compressors are joined by an oil-equalizing tube and also have an intake manifold with screw connector for a service valve or a solder connector (these parts are supplied as accessories). Each Twin compressor is supplied with two sets of electrical equipment and mounting accessories. To ensure optimum starting characteristics and the smallest possible mains load we recommend that the compressors be equipped with a time-delay relay for start of the second compressor.Twin compressors can operate with capacity regulation depending on the controls used.

10. Conversion from R12 to R134a

Normally, the capillary tube shall be adjusted at low evaporating temperatures. Compared to an optimized R12 system with the same evaporator capacity, the R134a system must have an increased resistance defined as approx. 10% less N2 flow at 10 bar inlet pressure. The same size of capillary tube as used for R12 can be used at high evaporating temperatures. A drier with 3 desiccant of Molecular Sieves must always be used. Rules for dryness and cleanliness of system components (DIN 8964) are transferred to R134a systems. The system components must not contain mineral oil or greasy substances. The compressors must be soldered into the system no later than 15 minutes after the connector seals have been removed. The same evacuation procedure as for R12 systems must be used. Max. 1% non-condensable gases. The system must not contain any chlorine. The charging equipment must only be used for R134a. If the same vacuum pump is to be used for R12 and R134a systems, a special Ester oil must be used in agreement with the pump supplier.

11. Warnings

No high potential test nor start tests must be carried out while the compressor is under vacuum. No attempt must be made to start the compressor without a complete starting device. Allow the compressor to assume a temperature above 10C before starting the first time in order to avoid starting problems. Anti-freeze agents must not be used in the compressors as such agents are damaging to several of the materials used. In particular, the ethyl or methyl alcohol contents of such anti-freeze agents have a destructive effect on the synthetic motor insulation.

August 2003

CK.40.B7.02

11

PL20F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CD.41.B8.02) GeneralCompressor Code number PL20F 101G0100Application

PL20FR134a

101G

Blue stripe

Application Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz

MBP -25 to 0 198 - 254 /50 RSIR 38 S S

Barcode on white background Yellow background

DANFOSS COMPRESSORS

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 1.41 150 300 800 3.8

MotorMotor size LRA (rated after 4 sec. UL984) LST Cut-in current LST Resistance, main and start winding (25C) Approvals watt A A 29 1.2 5.7 84.0/19.0 EN 60335-2-34 with Annex AA100 35 70

204 170

DimensionsHeight mm A B B1 B2 Suction connector Process connector Discharge connector Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm pcs. C D E 129 127 120 73 6.2 0.09 6.2 0.09 5.0 +0.12/+0.20 1502068241

16

D

C

9

E

B1 B A B2

50 60.5

127

February 2003

CD.41.B9.02

46 59 130

8270-2

Application

Approvals

0100

1

12

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C PL20F -25 16.0 -23.3 19.0 -20 25.4 -15 36.5 -10 49.6 -5 64.9

watt0 82.6g

Capacity (ASHRAE)Comp.\C PL20F -25 19.7 -23.3 23.4 -20 31.3 -15 45.0 -10 61.3 -5 80.3

watt0 102b8224

Power consumptionComp.\C PL20F -25 42.0 -23.3 43.4 -20 46.4 -15 51.5 -10 57.2 -5 63.3

watt0 69.7d

a1

Current consumptionComp.\C PL20F -25 0.35 -23.3 0.35 -20 0.36 -15 0.37 -10 0.39 -5 0.41

A0 0.43

Main winding a1 Start windingN

COP (EN 12900/CECOMAF)Comp.\C PL20F -25 0.38 -23.3 0.44 -20 0.55 -15 0.71 -10 0.87 -5 1.03

W/W0 1.19N C L

COP (ASHRAE)Comp.\C PL20F -25 0.47 -23.3 0.54 -20 0.67 -15 0.87 -10 1.07 -5 1.27

W/W0 1.47Winding protector

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

AccessoriesDevices PTC starting device Cover Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 b d g PL20F 103N0011 103N0018 103N0491 103N1010 103N0476 118-1917 118-1918 118-1919

2

CD.41.B9.02

February 2003

August 2003

CK.40.B7.02

13

PL35F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CD.41.E3.02) GeneralCompressor Code number PL35F 101G0202Application

PL35FR134a

101G

Blue stripe

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz MBP -25 to 0 198 - 254 /50 RSIR 38 S S

Approvals Barcode on white background Yellow background

0202DANFOSS COMPRESSORS

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 2.00 150 300 830 4.1

MotorMotor size LRA (rated after 4 sec. UL984) LST Cut-in current LST Resistance, main and start winding (25C) Approvals watt A A 43 1.7 5.6 52.0/19.0 EN 60335-2-34 with Annex AA1009 204 170

DimensionsHeight mm A B B1 B2 Suction connector Process connector Discharge connector Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm pcs. C D E 134 132 125 73 6.2 0.09 6.2 0.09 5.0 +0.12/+0.20 1502068241

16

D

35 70

C

E

B1 B A B2

50 60.5

127

February 2003

CD.41.E4.02

46 59 130

8270

1

14

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C PL35F -25 32 -23.3 36 -20 45 -15 60 -10 79 -5 101

watt0 125g

Capacity (ASHRAE)Comp.\C PL35F -25 39 -23.3 44 -20 55 -15 74 -10 97 -5 124

watt0 155b8224

Power consumptionComp.\C PL35F -25 50 -23.3 52 -20 57 -15 64 -10 72 -5 80

watt0 88d

a1

Current consumptionComp.\C PL35F -25 0.50 -23.3 0.50 -20 0.51 -15 0.53 -10 0.55 -5 0.58

A0 0.62

Main winding a1 Start windingN

COP (EN 12900/CECOMAF)Comp.\C PL35F -25 0.64 -23.3 0.69 -20 0.79 -15 0.94 -10 1.10 -5 1.26

W/W0 1.42N C L

COP (ASHRAE)Comp.\C PL35F -25 0.78 -23.3 0.85 -20 0.97 -15 1.16 -10 1.36 -5 1.55

W/W0 1.76Winding protector

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

AccessoriesDevices PTC starting device Cover Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 b d g PL35F 103N0011 103N0018 103N0491 103N1010 103N0476 118-1917 118-1918 118-1919

2

CD.41.E4.02

February 2003

August 2003

CK.40.B7.02

15

PL50F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CD.41.F3.02) GeneralCompressor Code number PL50F 101G0220Application

PL50FR134a

101G

Blue stripe

Application Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz

LBP -35 to -10 198 - 254 /50 RSIR 38 S S

Barcode on white background Yellow background

DANFOSS COMPRESSORS

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 2.50 150 300 850 4.3

MotorMotor size LRA (rated after 4 sec. UL984) LST Cut-in current LST Resistance, main and start winding (25C) Approvals watt A A 54 2.2 6.0 38.0/20.0 EN 60335-2-34 with Annex AA1009 204 170

DimensionsHeight mm A B B1 B2 Suction connector Process connector Discharge connector Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm pcs. C D E 137 135 128 73 6.2 0.09 6.2 0.09 5.0 +0.12/+0.20 1502068241

16

D

35 70

C

E

B1 B A B2

50 60.5

127

February 2003

CD.41.F4.02

46 59 130

8270-3

Application

Approvals

0220

1

16

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C PL50F -35 14.2 -30 26.2 -25 40.0 -23.3 45.1 -20 55.8 -15 74.1

watt-10 95.2g

Capacity (ASHRAE)Comp.\C PL50F -35 17.4 -30 32.3 -25 49.3 -23.3 55.6 -20 68.9 -15 91.5

watt-10 118b8224

Power consumptionComp.\C PL50F -35 43.6 -30 51.9 -25 60.0 -23.3 62.7 -20 68.1 -15 76.5

watt-10 85.6d

a1

Current consumptionComp.\C PL50F -35 0.47 -30 0.48 -25 0.50 -23.3 0.51 -20 0.53 -15 0.55

A-10 0.58

Main winding a1 Start windingN

COP (EN 12900/CECOMAF)Comp.\C PL50F -35 0.32 -30 0.50 -25 0.67 -23.3 0.72 -20 0.82 -15 0.97

W/W-10 1.11N C L

COP (ASHRAE)Comp.\C PL50F -35 0.40 -30 0.62 -25 0.82 -23.3 0.89 -20 1.01 -15 1.20

W/W-10 1.38Winding protector

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

AccessoriesDevices PTC starting device Cover Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 b d g PL50F 103N0011 103N0018 103N0491 103N1010 103N0476 118-1917 118-1918 118-1919

2

CD.41.F4.02

February 2003

August 2003

CK.40.B7.02

17

PL50F Standard Compressor HST Starting Characteristics R134a 220-240V 50HzData Sheet (Replaces CD.41.G3.02) GeneralCompressor Code number PL50F 101G0222Application

PL50FR134a

101G

Blue stripe

Application Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz

MBP -25 to 0 198 - 254 /50 CSIR 38 F2 F2

Barcode on white background Yellow background

DANFOSS COMPRESSORS

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 2.50 150 300 850 4.3

MotorMotor size LRA (rated after 4 sec. UL984) HST Cut-in current HST Resistance, main and start winding (25C) Approvals watt A A 54 4.2 4.2 38.0/14.0 EN 60335-2-34 with Annex AA100 35 70

204 170

DimensionsHeight mm A B B1 B2 Suction connector Process connector Discharge connector Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm pcs. C D E 137 135 128 73 6.2 0.09 6.2 0.09 5.0 +0.12/+0.20 1502068241

16

D

C

9

E

B1 B A B2

50 60.5

127

February 2003

CD.41.G4.02

46 59 130

8283-2

Application

Approvals

0222

1

18

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C PL50F -25 40.0 -23.3 45.1 -20 55.8 -15 74.1 -10 95.2 -5 120

watt0 148c

Capacity (ASHRAE)Comp.\C PL50F -25 49.3 -23.3 55.6 -20 68.9 -15 91.5 -10 118 -5 148

watt0 183b

Power consumptionComp.\C PL50F -25 58.0 -23.3 60.7 -20 66.1 -15 74.5 -10 83.6 -5 93.7

watt0 105d a2

8225

Current consumptionComp.\C PL50F -25 0.50 -23.3 0.51 -20 0.53 -15 0.55 -10 0.58 -5 0.62

A0 0.6610 11

c

COP (EN 12900/CECOMAF)Comp.\C PL50F -25 0.69 -23.3 0.74 -20 0.84 -15 0.99 -10 1.14 -5 1.28

W/W0 1.4112 14 13

COP (ASHRAE)Comp.\C PL50F -25 0.85 -23.3 0.92 -20 1.04 -15 1.23 -10 1.41 -5 1.58

W/W0 1.74Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Fan cooling, 220V 50Hz

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

AccessoriesDevices Starting relay Cover Starting capacitor 60 F Cord relief Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities Fig. a2 b c d PL50F 117U6021 103N0491 117U5014 103N1010 118-1917 118-1918 118-1919

2

CD.41.G4.02

February 2003

August 2003

CK.40.B7.02

19

TL2.5F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CD.42.S3.02) GeneralCompressor Code number (small baseplate) Code number (large baseplate) TL2.5F 102G4200 102G4201Blue stripe Approvals Application

TL2.5FR134a

102G

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz MBP -25 to 0 198 - 254 /50 RSIR 38 S S

Yellow background

DANFOSS COMPRESSORS

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 2.61 180 400 1600 6.73.6 16

MotorMotor size LRA (rated after 4 sec. UL984) LST Cut-in current LST Resistance, main and start winding (25C) Approvals watt A A 60 2.3 7.0 40.0/15.0EN 60335-2-34 with Annex AA, CCIB9 19 170 178 186 204 222 176

DimensionsHeight mm

102G4200A B 163 159

102G4201

C or D

or

D C E

Suction connector Process connector Discharge connector Compressors on a pallet

location/I.D. mm location/I.D. mm location/I.D. mm pcs.

C 6.2 0.09 D 6.2 0.09 E 5.0 +0.12/+0.20 125

6.5 0.09 6.5 0.09 5.0 +0.12/+0.20

105

157 60.5 66

51 20

29

105 107

A B

30

8428

102

96 117

June 2001

CD.42.S4.02

71

20

CK.40.B7.02

August 2003

101.6 136 31.5 28

35 70 100

8271-2

Barcode on white background

4200

45

1

Capacity (EN 12900/CECOMAF)Comp.\C TL2.5F -25 32 -23.3 37 -20 47 -15 65 -10 86 -5 110

watt0 137g

Capacity (ASHRAE)Comp.\C TL2.5F -25 39 -23.3 45 -20 58 -15 80 -10 106 -5 136

watt0 169b8217

Power consumptionComp.\C TL2.5F -25 54 -23.3 57 -20 63 -15 71 -10 80 -5 89

watt0 98d

a1

Current consumptionComp.\C TL2.5F -25 0.44 -23.3 0.45 -20 0.46 -15 0.49 -10 0.52 -5 0.55

A0 0.58

Main winding a1 Start windingN

COP (EN 12900/CECOMAF)Comp.\C TL2.5F -25 0.59 -23.3 0.64 -20 0.75 -15 0.91 -10 1.07 -5 1.24

W/W0 1.40N C L

COP (ASHRAE)Comp.\C TL2.5F -25 0.73 -23.3 0.79 -20 0.92 -15 1.12 -10 1.33 -5 1.53

W/W0 1.73Winding protector

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

AccessoriesDevices PTC starting device Cover Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 b d g TL2.5F 103N0011 103N0018 103N2010 103N1010 103N0476 118-1917 118-1918 118-1919

2

CD.42.S4.02

June 2001

August 2003

CK.40.B7.02

21

TL3F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CD.42.I5.02) GeneralCompressor Code number TL3F 102G4300Application

TL3FR134aBlue stripe Approvals

102G

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz MBP -25 to 0 198 - 254 /50 RSIR/CSIR 38 S S

Yellow background

DANFOSS COMPRESSORS

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 3.13 180 400 1600 6.716

MotorMotor size LRA (rated after 4 sec. UL984) LST/HST Cut-in current LST/HST Resistance, main and start winding (25C) Approvals watt A A 75 2.8/4.5 7.5/4.5 31.5/15.0EN 60335-2-34 with Annex AA, CCIB9 170 178 186 204 222 17635 70 100

DimensionsHeight mm A B Suction connector Process connector Discharge connector Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm pcs. C D E 163 159

C or D

or

D C E

6.2 0.09105

5.0 +0.12/+0.20 125

157 60.5 66

51 20

29 71

102

96 117

June 2001

CD.42.I6.02

105 1078263

A B

30

6.2 0.09

8271-3

Barcode on white background

4300

31.5 28

45

1

22

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C TL3F -25 42 -23.3 48 -20 60 -15 82 -10 108 -5 138

watt0 173HSTc

Capacity (ASHRAE)Comp.\C TL3F -25 52 -23.3 59 -20 74 -15 101 -10 133 -5 171

watt0 214b

Power consumptionComp.\C TL3F -25 66 -23.3 69 -20 76 -15 87 -10 99 -5 111

watt0 124d a2

8219

Current consumptionComp.\C TL3F -25 0.50 -23.3 0.51 -20 0.52 -15 0.54 -10 0.57 -5 0.61

A0 0.6710 11

c

COP (EN 12900/CECOMAF)Comp.\C TL3F -25 0.64 -23.3 0.69 -20 0.79 -15 0.94 -10 1.09 -5 1.24

W/W0 1.3912 14 13

COP (ASHRAE)Comp.\C TL3F -25 0.78 -23.3 0.85 -20 0.97 -15 1.16 -10 1.35 -5 1.53

W/W0 1.72Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

LSTg

b8217

a1

AccessoriesDevices PTC starting device Starting relay Cover Starting capacitor 60 F Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 a2 b c d g TL3F 103N0011 103N0018 117U6007 103N2010 117U5014 103N1010 103N0476 118-1917 118-1918 118-1919N C L

d Main winding a1 Start windingN

Winding protector

2

CD.42.I6.02

June 2001

August 2003

CK.40.B7.02

23

TL4F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CD.42.Z1.02) GeneralCompressor Code number Code number TL4F 102G4400 102G4426Blue stripe Approvals Application

TL4FR134a

102G

Application Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz

LBP -35 to -10 198 - 254 /50 RSIR/CSIR 38 S S

Yellow background

DANFOSS COMPRESSORS

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 3.86 180 400 1600 6.716

MotorMotor size alternative motor LRA (rated after 4 sec. UL984) LST/HST alternative motor Cut-in current LST/HST alternative motor Resistance, main and start winding (25C) alternative motor Approvals A A watt 85 80 3.2/4.8 3.2/4.6 7.5/4.8 7.8/4.6 25.7/16.3 26.8/13.530

9 170 178 186 204 222 176

35 70 100

C or D

or

D C E

EN 60335-2-34 with Annex AA, CCIBA B

DimensionsHeight mm

102G4400A B 163 159

102G4426

Suction connector Process connector Discharge connector Compressors on a pallet

location/I.D. mm location/I.D. mm location/I.D. mm pcs.

C 6.2 0.09 D 6.2 0.09 E 5.0 +0.12/+0.20 125

6.5 0.09 6.5 0.09157 60.5 668263

105

29 71

5.0 +0.12/+0.20

102

June 2001

CD.42.Z2.02

51 20

96 117

105 107

8271-4

Application

Barcode on white background

4400

31.5 28

45

1

24

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C TL4F -35 31 -30 44 -25 61 -23.3 67 -20 81 -15 107

watt-10 137HSTc

Capacity (ASHRAE)Comp.\C TL4F -35 38 -30 54 -25 75 -23.3 83 -20 100 -15 131

watt-10 170b

Power consumptionComp.\C TL4F -35 60 -30 70 -25 81 -23.3 85 -20 93 -15 107

watt-10 122d a2

8219

Current consumptionComp.\C TL4F -35 0.51 -30 0.53 -25 0.55 -23.3 0.56 -20 0.58 -15 0.63

A-10 0.6910 11

c

COP (EN 12900/CECOMAF)Comp.\C TL4F -35 0.52 -30 0.63 -25 0.75 -23.3 0.79 -20 0.88 -15 1.00

W/W-10 1.1212 14 13

COP (ASHRAE)Comp.\C TL4F -35 0.64 -30 0.77 -25 0.92 -23.3 0.98 -20 1.08 -15 1.24

W/W-10 1.38Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

LSTg

b8217

AccessoriesDevices PTC starting device Starting relay Cover Starting capacitor 60 F Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 a2 b c d g TL4F 103N0011 103N0018 117U6009 103N2010 117U5014 103N1010 103N0476 118-1917 118-1918 118-1919N

a1 d Main winding a1 Start windingN

C

L

Winding protector

2

CD.42.Z2.02

June 2001

August 2003

CK.40.B7.02

25

TL5F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CG.42.B1.02) GeneralCompressor Code number TL5F 102G4501Application

TL5FR134aBlue stripe Approvals

102G

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz LBP -35 to -10 198 - 254 /50 RSIR/CSIR 38 S S

Yellow background

DANFOSS COMPRESSORS

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 5.08 180 400 1790 7.516

MotorMotor size alternative motor LRA (rated after 4 sec. UL984) LST/HST alternative motor Cut-in current LST/HST alternative motor Resistance, main and start winding (25C) alternative motor Approvals A A watt 110 125 4.3/5.1 4.7/5.8 8.6/5.1 8.7/5.8 18.2/15.1 16.0/17.0EN 60335-2-34 with Annex AA, CCIB30

9 170 178 186 204 222 176

35 70 100

C or D

or

D C E

DimensionsHeight mm A B Suction connector Process connector Discharge connector Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm pcs. C D E 173 169 6.2 0.09 6.2 0.09 5.0 +0.12/+0.20

105

157 60.5 66

29 71

125

102

June 2001

CG.42.B2.02

51 20

96 117

105 1078263

A B

8271

Barcode on white background

4501

31.5 28

45

1

26

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C TL5F -35 43 -30 60 -25 82 -23.3 91 -20 110 -15 144

watt-10 183HSTc

Capacity (ASHRAE)Comp.\C TL5F -35 53 -30 74 -25 101 -23.3 112 -20 136 -15 177

watt-10 226b

Power consumptionComp.\C TL5F -35 70 -30 85 -25 101 -23.3 107 -20 118 -15 136

watt-10 154d a2

8219

Current consumptionComp.\C TL5F -35 0.75 -30 0.78 -25 0.81 -23.3 0.83 -20 0.86 -15 0.91

A-10 0.9710 11

c

COP (EN 12900/CECOMAF)Comp.\C TL5F -35 0.61 -30 0.70 -25 0.81 -23.3 0.85 -20 0.93 -15 1.06

W/W-10 1.1912 14 13

COP (ASHRAE)Comp.\C TL5F -35 0.75 -30 0.86 -25 1.00 -23.3 1.05 -20 1.15 -15 1.30

W/W-10 1.47Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

LSTg

b8217

a1

AccessoriesDevices PTC starting device Starting relay Cover Starting capacitor 60 F Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 a2 b c d g TL5F 103N0011 103N0018 117U6004 103N2010 117U5014 103N1010 103N0476 118-1917 118-1918 118-1919N C L

d Main winding a1 Start windingN

Winding protector

2

CG.42.B2.02

June 2001

August 2003

CK.40.B7.02

27

TLS4F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CG.42.J3.02) GeneralCompressor Code number TLS4F 102G4425Blue stripe Application

TLS4FR134a SUCTION CONNECTOR

102G

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz LBP -35 to -10 198 - 254 /50 RSIR/CSIR 38 S SS O F1 F2Approvals Barcode on white background Yellow background

DANFOSS COMPRESSORS

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

3.86 180 400 1600 6.7

cm3 g cm3 kg

MotorMotor size alternative motor LRA (rated after 4 sec. UL984) LST/HST alternative motor Cut-in current LST/HST alternative motor Resistance, main and start winding (25C) alternative motor Approvals A A watt 85 8035 70 100

16

3.2/4.8 3.2/4.6 7.5/4.8 7.8/4.6 25.7/16.3 26.8/13.5 EN 60335-2-34 with Annex AA9 170 178 186 204

C

222 176

D E

Dimensions 31.5 28

Height

mm

A B

163105

Suction connector Process connector Discharge connector Compressors on a pallet

location/I.D. mm location/I.D. mm location/I.D. mm pcs.

C D E

6.2 0.09 6.2 0.09 5.0 +0.12/+0.20 125

157 60.5 66

51 20

29 71

102

96 117

May 2001

CG.42.J4.02

105 1078244

159

A B

30

8272-4

4425

45

1

28

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C TLS4F -35 34.6 -30 51.5 -25 72.0 -23.3 79.9 -20 96.8 -15 126

watt-10 162HSTc

Capacity (ASHRAE)Comp.\C TLS4F -35 42.6 -30 63.5 -25 88.9 -23.3 98.6 -20 119 -15 156

watt-10 200b

Power consumptionComp.\C TLS4F -35 67.5 -30 77.8 -25 89.0 -23.3 93.0 -20 101 -15 115

watt-10 130d a2

8219

Current consumptionComp.\C TLS4F -35 0.59 -30 0.62 -25 0.66 -23.3 0.68 -20 0.71 -15 0.76

A-10 0.8110 11

c

COP (EN 12900/CECOMAF)Comp.\C TLS4F -35 0.51 -30 0.66 -25 0.81 -23.3 0.86 -20 0.96 -15 1.10

W/W-10 1.2512 14 13

COP (ASHRAE)Comp.\C TLS4F -35 0.63 -30 0.82 -25 1.00 -23.3 1.06 -20 1.18 -15 1.36

W/W-10 1.54Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

LSTg

b8217

a1

AccessoriesDevices PTC starting device Starting relay Cover Starting capacitor 60 F Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 a2 b c d g TLS4F 103N0011 103N0018 117U6009 103N2010 117U5014 103N1010 103N0476 118-1917 118-1918 118-1919N C L

d Main winding a1 Start windingN

Winding protector

2

CG.42.J4.02

May 2001

August 2003

CK.40.B7.02

29

TLS5F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CD.42.K5.02) GeneralCompressor Code number Code number TLS5F 102G4520 102G4526Blue stripe Application

TLS5FR134a SUCTION CONNECTOR

102G

Approvals

Application Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz

LBP -35 to -10 198 - 254 /50 RSIR/CSIR 38 S S

DANFOSS COMPRESSORS

Yellow background

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 5.08 180 400 1790 7.316

MotorMotor size alternative motor LRA (rated after 4 sec. UL984) LST/HST alternative motor Cut-in current LST/HST alternative motor Resistance, main and start winding (25C) alternative motor Approvals A A watt 125 110 4.7/5.8 4.3/5.1 8.7/5.8 8.6/5.1 16.0/17.0 18.2/15.13035 70 100

9 170 178 186 204

C

222 176

D E 31.5 28

EN 60335-2-34 with Annex AAA B

DimensionsHeight mm

102G4520A B 173 169

102G4526

Suction connector Process connector Discharge connector Compressors on a pallet

location/I.D. mm location/I.D. mm location/I.D. mm pcs.

C 6.2 0.09 D 6.2 0.09 E 5.0 +0.12/+0.20 125

6.5 0.09 6.5 0.09157 60.5 668244

105

29 71

5.0 +0.12/+0.20

102

May 2001

CD.42.K6.02

51 20

96 117

105 107

8272

Application

Barcode on white background

4520

45

1

30

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C TLS5F -35 47.8 -30 70.7 -25 98.0 -23.3 109 -20 131 -15 170

watt-10 216

HSTc

Capacity (ASHRAE)Comp.\C TLS5F -35 58.9 -30 87.2 -25 121 -23.3 134 -20 161 -15 209

watt-10 267b

Power consumptionComp.\C TLS5F -35 82.7 -30 97.1 -25 112 -23.3 117 -20 128 -15 144

watt-10 162d a2

8219

Current consumptionComp.\C TLS5F -35 0.96 -30 0.98 -25 1.01 -23.3 1.02 -20 1.05 -15 1.10

A-10 1.1510 11

c

COP (EN 12900/CECOMAF)Comp.\C TLS5F -35 0.58 -30 0.73 -25 0.88 -23.3 0.93 -20 1.02 -15 1.18

W/W-10 1.3312 14 13

COP (ASHRAE)Comp.\C TLS5F -35 0.71 -30 0.90 -25 1.08 -23.3 1.14 -20 1.26 -15 1.45

W/W-10 1.65Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

LSTg

b8217

a1

AccessoriesDevices PTC starting device Starting relay Cover Starting capacitor 60 F Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 a2 b c d g TLS5F 103N0011 103N0018 117U6004 103N2010 117U5014 103N1010 103N0476 118-1917 118-1918 118-1919N

d Main winding a1 Start windingN

C

L

Winding protector

2

CD.42.K6.02

May 2001

August 2003

CK.40.B7.02

31

TLS6F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CG.42.G1.02) GeneralCompressor Code number TLS6F 102G4620Blue stripe Application

TLS6FR134a SUCTION CONNECTOR

102G

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz LBP -35 to -10 198 - 254 /50 RSIR/CSIR 38 S S

Barcode on white background Yellow background

DANFOSS COMPRESSORS

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 5.70 180 400 1790 7.316

MotorMotor size alternative motor LRA (rated after 4 sec. UL984) LST/HST alternative motor Cut-in current LST/HST alternative motor Resistance, main and start winding (25C) alternative motor Approvals A A watt 125 110 4.7/5.8 4.3/5.1 8.7/5.8 8.6/5.1 16.0/17.0 18.2/15.1 EN 60335-2-34 with Annex AA3035 70 100

9 170 178 186 204

C

222 176

D E 31.5 28

DimensionsHeight mm A B Suction connector Process connector Discharge connector Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm pcs. C D E 173 169 6.2 0.09 6.2 0.09 5.0 +0.12/+0.20

105

157 60.5 66

29 71

125

102

June 2001

CG.42.G2.02

51 20

96 117

105 1078244

A B

8272-2

Approvals

4620

45

1

32

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C TLS6F -35 58 -30 77 -25 104 -23.3 115 -20 139 -15 183

watt-10 235HSTc

Capacity (ASHRAE)Comp.\C TLS6F -35 71 -30 95 -25 128 -23.3 142 -20 172 -15 226

watt-10 290b

Power consumptionComp.\C TLS6F -35 84 -30 101 -25 119 -23.3 125 -20 138 -15 159

watt-10 181d a2

8219

Current consumptionComp.\C TLS6F -35 0.78 -30 0.82 -25 0.86 -23.3 0.88 -20 0.92 -15 0.99

A-10 1.0810 11

c

COP (EN 12900/CECOMAF)Comp.\C TLS6F -35 0.69 -30 0.76 -25 0.87 -23.3 0.92 -20 1.01 -15 1.15

W/W-10 1.3012 14 13

COP (ASHRAE)Comp.\C TLS6F -35 0.85 -30 0.94 -25 1.08 -23.3 1.13 -20 1.24 -15 1.42

W/W-10 1.60Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

LSTg

b8217

a1

AccessoriesDevices PTC starting device Starting relay Cover Starting capacitor 60 F Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 a2 b c d g TLS6F 103N0011 103N0018 117U6004 103N2010 117U5014 103N1010 103N0476 118-1917 118-1918 118-1919N C L

d Main winding a1 Start windingN

Winding protector

2

CG.42.G2.02

June 2001

August 2003

CK.40.B7.02

33

TLS7F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CG.42.H1.02) GeneralCompressor Code number TLS7F 102G4720Blue stripe Application

TLS7FR134a SUCTION CONNECTOR

102G

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz LBP -35 to -10 198 - 254 /50 RSIR/CSIR 38* S S

Barcode on white background Yellow background

DANFOSS COMPRESSORS

S O F1 F2

* run capacitor 4 F compulsory in 38C ambient temperature

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 6.49 180 400 1790 7.516

MotorMotor size LRA (rated after 4 sec. UL984) LST/HST Cut-in current LST/HST Resistance, main and start winding (25C) Approvals watt A A 140 5.4/5.7 9.7/5.7 14.5/14.8 EN 60335-2-34 with Annex AA9 170 178 186 20435 70 100

DimensionsHeight mm A B Suction connector Process connector Discharge connector Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm pcs. C D E 173 169

C

222 176

D E 31.5 28

6.2 0.09105

5.0 +0.12/+0.20 125

157 60.5 66

51 20

29 71

102

96 117

June 2001

CG.42.H2.02

105 1078244

A B

30

6.2 0.09

8272-3

Approvals

4720

45

1

34

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C TLS7F -35 66 -30 89 -25 120 -23.3 133 -20 160 -15 208

watt-10 264HSTc

Capacity (ASHRAE)Comp.\C TLS7F -35 81 -30 109 -25 148 -23.3 163 -20 197 -15 256

watt-10 326b

Power consumptionComp.\C TLS7F -35 97 -30 116 -25 136 -23.3 143 -20 158 -15 182

watt-10 207d a2

8219

Current consumptionComp.\C TLS7F -35 0.87 -30 0.91 -25 0.96 -23.3 0.98 -20 1.03 -15 1.11

A-10 1.2010 11

c

COP (EN 12900/CECOMAF)Comp.\C TLS7F -35 0.68 -30 0.77 -25 0.88 -23.3 0.92 -20 1.01 -15 1.14

W/W-10 1.2812 14 13

COP (ASHRAE)Comp.\C TLS7F -35 0.84 -30 0.94 -25 1.09 -23.3 1.14 -20 1.24 -15 1.41

W/W-10 1.57Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

LSTg

AccessoriesDevices PTC starting device 6.3 mm spades 4.8 mm spades Fig. a1 TLS7F 103N0011 103N0018 103N0016* 103N0021* 117U6000 103N2010 117U5014 103N1010 103N0476 117-7117* 117-7119* 118-1917 118-1918 118-1919

b8217

a1 d Main winding a1 Start windingN

PTC starting device Starting relay Cover Starting capacitor 60 F Cord relief Protection screen for PTC Run capacitor 4 F

6.3 mm spades a1** 4.8 mm spades a2 b c d g 6.3 mm spades 4.8 mm spades

N

C

L

Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities

Winding protector

* run capacitor 4 F compulsory in 38C ambient temperature ** with connector for RC

2

CG.42.H2.02

June 2001

August 2003

CK.40.B7.02

35

NL6F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CD.43.P5.02) GeneralCompressor Code number NL6F 105G6606Application

NL6FR134aBlue stripe Approvals

105G

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz LBP -35 to -10 198 - 254 /50 RSIR/CSIR 38 S S

Yellow background

DANFOSS COMPRESSORS

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 6.13 320 400 2130 9.3204 170

MotorMotor size LRA (rated after 4 sec. UL984) LST/HST Cut-in current LST/HST Resistance, main and start winding (25C) Approvals watt A A 125100 70

5.0/5.0 9.6/5.0 16.0/13.6 EN 60335-2-34 with Annex AA

16 178

DDimensionsHeight mm A B Suction connector Process connector Discharge connector Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm pcs. C D E 18825

205

181 6.2 0.09 6.2 0.09 5.0 +0.12/+0.20 80A B93.5

102.5

2548248

60.5

166

72

47

113

119 127

January 2003

CD.43.P6.02

54 78

51

27

75.5

8273-2

Barcode on white background

6606

E C3515

1

36

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C NL6F -35 52 -30 77 -25 110 -23.3 123 -20 151 -15 200

watt-10 258HSTc

Capacity (ASHRAE)Comp.\C NL6F -35 64 -30 95 -25 135 -23.3 151 -20 186 -15 247

watt-10 318b

Power consumptionComp.\C NL6F -35 80 -30 98 -25 118 -23.3 125 -20 139 -15 161

watt-10 185d a2

8219

Current consumptionComp.\C NL6F -35 0.78 -30 0.81 -25 0.86 -23.3 0.88 -20 0.92 -15 0.99

A-10 1.0810 11

c

COP (EN 12900/CECOMAF)Comp.\C NL6F -35 0.65 -30 0.78 -25 0.93 -23.3 0.99 -20 1.09 -15 1.24

W/W-10 1.3912 14 13

COP (ASHRAE)Comp.\C NL6F -35 0.80 -30 0.96 -25 1.15 -23.3 1.21 -20 1.34 -15 1.53

W/W-10 1.72Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

LSTg

b8217

a1

AccessoriesDevices PTC starting device Starting relay Cover Starting capacitor 80 F Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 a2 b c d g NL6F 103N0011 103N0018 117U6004 103N2010 117U5015 103N1010 103N0476 118-1917 118-1918 118-1919N

d Main winding a1 Start windingN

C

L

Winding protector

2

CD.43.P6.02

January 2003

August 2003

CK.40.B7.02

37

NL7F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CG.43.K1.02) GeneralCompressor Code number Code number compressor with oil cooler NL7F 105G6706 105G6716Blue stripe Approvals Application

NL7FR134a

105G

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz LBP -35 to -10 198 - 254 /50 RSIR/CSIR 38 S S

Yellow background

DANFOSS COMPRESSORS

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 7.27 320 400 2180 9.6204 170

MotorLRA (rated after 4 sec. UL984) LST/HST Cut-in current LST/HST Resistance, main and start winding (25C) Approvals A A 5.9/5.9 10.4/5.9 13.3/14.1EN 60335-2-34 with Annex AA, CCIB178 205 16100 70

Motor size

watt

150

D

Dimensions25

Height

mm

A B

190 183 6.2 0.09 6.2 0.09 5.0 +0.12/+0.20 5.0 +0.12/+0.20A B93.5

Suction connector Process connector Discharge connector Oil cooler Compressors on a pallet

location/I.D. mm location/I.D. mm location/I.D. mm location/I.D. mm pcs.

C D E F

2548249

40 102.5 75.5

F

8060.5

166

51

27

72

47

113

119 127

August 2001

CG.43.K2.02

40 54 78

8273-4

Barcode on white background

6706

E C3515

1

38

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C NL7F -35 71 -30 99 -25 136 -23.3 151 -20 182 -15 238

watt-10 303HSTc

Capacity (ASHRAE)Comp.\C NL7F -35 87 -30 122 -25 167 -23.3 186 -20 225 -15 293

watt-10 374b

Power consumptionComp.\C NL7F -35 97 -30 121 -25 146 -23.3 155 -20 173 -15 201

watt-10 232d a2

8219

Current consumptionComp.\C NL7F -35 0.92 -30 0.96 -25 1.02 -23.3 1.04 -20 1.10 -15 1.20

A-10 1.3310 11

c

COP (EN 12900/CECOMAF)Comp.\C NL7F -35 0.73 -30 0.82 -25 0.93 -23.3 0.97 -20 1.06 -15 1.18

W/W-10 1.3112 14 13

COP (ASHRAE)Comp.\C NL7F -35 0.90 -30 1.01 -25 1.15 -23.3 1.20 -20 1.30 -15 1.46

W/W-10 1.61Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

LSTg

b8217

a1

AccessoriesDevices PTC starting device Starting relay Cover Starting capacitor 80 F Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 a2 b c d g NL7F 103N0011 103N0018 117U6000 103N2010 117U5015 103N1010 103N0476 118-1917 118-1918 118-1919N

d Main winding a1 Start windingN

C

L

Winding protector

2

CG.43.K2.02

August 2001

August 2003

CK.40.B7.02

39

NL8F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CD.43.J5.02) GeneralCompressor Code number NL8F 105G6822Application

NL8FR134aBlue stripe Approvals Barcode on white background Yellow background

105G

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz LBP -35 to -10 198 - 254 /50 RSIR/CSIR 38 S S

DANFOSS COMPRESSORS

S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 7.95 320 400 2230 9.8204 170

MotorMotor size LRA (rated after 4 sec. UL984) LST/HST Cut-in current LST/HST Resistance, main and start winding (25C) Approvals watt A A 175100 70

6.6/7.9 10.9/7.9 10.7/13.0 EN 60335-2-34 with Annex AA

16 178

DDimensionsHeight mm A B Suction connector Process connector Discharge connector Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm pcs. C D E 19725

205

191 6.2 0.09 6.2 0.09 5.0 +0.12/+0.20 80A B93.5

102.5

2548248

60.5

166

72

47

113

119 127

June 2001

CD.43.J6.02

54 78

51

27

75.5

8273-5

6822

E C3515

1

40

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C NL8F -35 82 -30 112 -25 149 -23.3 163 -20 194 -15 249

watt-10 317HSTc

Capacity (ASHRAE)Comp.\C NL8F -35 101 -30 139 -25 184 -23.3 201 -20 240 -15 308

watt-10 392b

Power consumptionComp.\C NL8F -35 116 -30 134 -25 154 -23.3 162 -20 177 -15 203

watt-10 232d a2

8219

Current consumptionComp.\C NL8F -35 0.92 -30 0.98 -25 1.04 -23.3 1.07 -20 1.13 -15 1.22

A-10 1.3410 11

c

COP (EN 12900/CECOMAF)Comp.\C NL8F -35 0.70 -30 0.84 -25 0.97 -23.3 1.01 -20 1.09 -15 1.23

W/W-10 1.3712 14 13

COP (ASHRAE)Comp.\C NL8F -35 0.87 -30 1.04 -25 1.19 -23.3 1.25 -20 1.35 -15 1.52

W/W-10 1.69Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

LSTg

b8217

a1

AccessoriesDevices PTC starting device Starting relay Cover Starting capacitor 80 F Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 a2 b c d g NL8F 103N0011 103N0018 117U6001 103N2010 117U5015 103N1010 103N0476 118-1917 118-1918 118-1919N

d Main winding a1 Start windingN

C

L

Winding protector

2

CD.43.J6.02

June 2001

August 2003

CK.40.B7.02

41

NL9F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CG.43.M1.02) GeneralCompressor Code number Code number Code number compressor with oil cooler)

NL9F 105G6802 105G6804*) 105G6812* Performance data established on 8.2 mm suction line. Restrictions due to 6.2 mm suction line can affect system performance.Blue stripe Approvals Application

NL9FR134a

105G

Yellow background

DANFOSS COMPRESSORS

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz LBP -35 to -10 198 - 254 /50 RSIR/CSIR 38 S S204 170F2 S O F1 = Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 8.35 320 400 2280 10.0100 70

16

MotorMotor size LRA (rated after 4 sec. UL984) LST/HST Cut-in current LST/HST Resistance, main and start winding (25C) Approvals watt A A 175 6.6/7.9

D

178 205

8273

Barcode on white background

6802

E C

25

10.9/7.9 10.7/13.0

35

A B93.5

15

EN 60335-2-34 with Annex AA

DimensionsHeight mm A B Suction connector Process connector Discharge connector Oil cooler Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm location/I.D. mm pcs.

105G6812

105G6802 105G6804 197 19160.5

2548249

40 102.5 75.5

F

166

C 8.2 0.09 D 6.2 0.09 E 6.2 0.09 F 6.2 0.09

8.2 0.09 6.2 0.09 6.2 0.09

6.2 0.09 6.2 0.09 5.0 +0.12/+0.20

51

27

72

47

80

113

119 127

August 2001

CG.43.M2.02

40 54 78

1

42

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C NL9F -35 80 -30 112 -25 155 -23.3 172 -20 208 -15 272

watt-10 346HSTc

Capacity (ASHRAE)Comp.\C NL9F -35 98 -30 138 -25 191 -23.3 212 -20 256 -15 335

watt-10 427b

Power consumptionComp.\C NL9F -35 117 -30 141 -25 167 -23.3 176 -20 195 -15 225

watt-10 257d a2

8219

Current consumptionComp.\C NL9F -35 0.92 -30 0.99 -25 1.08 -23.3 1.11 -20 1.18 -15 1.29

A-10 1.4110 11

c

COP (EN 12900/CECOMAF)Comp.\C NL9F -35 0.68 -30 0.80 -25 0.93 -23.3 0.98 -20 1.07 -15 1.21

W/W-10 1.3512 14 13

COP (ASHRAE)Comp.\C NL9F -35 0.84 -30 0.98 -25 1.14 -23.3 1.20 -20 1.32 -15 1.49

W/W-10 1.66Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

LSTg

b8217

a1

AccessoriesDevices PTC starting device Starting relay Cover Starting capacitor 80 F Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 a2 b c d g NL9F 103N0011 103N0018 117U6001 103N2010 117U5015 103N1010 103N0476 118-1917 118-1918 118-1919N

d Main winding a1 Start windingN

C

L

Winding protector

2

CG.43.M2.02

August 2001

August 2003

CK.40.B7.02

43

NL11F Standard Compressor R134a 220-240V 50HzData Sheet (Replaces CG.43.J1.02) GeneralCompressor Code number Code number Code number compressor with oil cooler)

NL11F 105G6900 105G6901*) 105G6910* Performance data established on 8.2 mm suction line. Restrictions due to 6.2 mm suction line can affect system performance.Blue stripe Approvals Application

NL11FR134a

105G

Yellow background

DANFOSS COMPRESSORS

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. C 32C 38C C V/Hz LBP -35 to -10 198 - 254 /50 RSIR/CSIR 38 O/F1 O/F1204 170F2 S O F1 = Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge Free gas vol. in compressor Weight without electrical equipment cm3 cm3 g cm3 kg 11.15 320 400 2360 10.7100 70

16

MotorMotor size LRA (rated after 4 sec. UL984) LST/HST Cut-in current LST/HST Resistance, main and start winding (25C) Approvals watt A A 235 9.2/10.4

D

178 205

8273-6

Barcode on white background

6900

E C

25

13.6/10.4 8.2/14.7

35

A B93.5

15

EN 60335-2-34 with Annex AA

DimensionsHeight mm A B Suction connector Process connector Discharge connector Oil cooler Compressors on a pallet location/I.D. mm location/I.D. mm location/I.D. mm location/I.D. mm pcs.

105G6910

105G6900 105G6901 203 19760.5

2548249

40 102.5 75.5

F

166

C 8.2 0.09 D 6.2 0.09 E 6.2 0.09 F 6.2 0.09

8.2 0.09 6.2 0.09 6.2 0.09

6.2 0.09 6.2 0.09 5.0 +0.12/+0.20

51

27

72

47

80

113

119 127

August 2001

CG.43.J2.02

40 54 78

1

44

CK.40.B7.02

August 2003

Capacity (EN 12900/CECOMAF)Comp.\C NL11F -35 102 -30 144 -25 200 -23.3 223 -20 271 -15 356

watt-10 455HSTc

Capacity (ASHRAE)Comp.\C NL11F -35 125 -30 177 -25 246 -23.3 274 -20 334 -15 438

watt-10 561b

Power consumptionComp.\C NL11F -35 146 -30 178 -25 212 -23.3 224 -20 248 -15 286

watt-10 325d a2

8219

Current consumptionComp.\C NL11F -35 1.40 -30 1.46 -25 1.54 -23.3 1.57 -20 1.64 -15 1.75

A-10 1.8910 11

c

COP (EN 12900/CECOMAF)Comp.\C NL11F -35 0.70 -30 0.81 -25 0.94 -23.3 0.99 -20 1.09 -15 1.25

W/W-10 1.4012 14 13

COP (ASHRAE)Comp.\C NL11F -35 0.86 -30 0.99 -25 1.16 -23.3 1.22 -20 1.34 -15 1.53

W/W-10 1.73Main winding Winding protector Start winding

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Static cooling, 220V 50Hz, PTC consumption incl.

EN 12900/CECOMAF 55C 32C 55C

ASHRAE 55C 32C 32C

LSTg

b8217

a1

AccessoriesDevices PTC starting device Starting relay Cover Starting capacitor 80 F Cord relief Protection screen for PTC Mounting accessories Bolt joint for one compressor Bolt joint in quantities Snap-on in quantities 6.3 mm spades 4.8 mm spades Fig. a1 a2 b c d g NL11F 103N0011 103N0018 117U6002 103N2010 117U5015 103N1010 103N0476 118-1917 118-1918 118-1919N

d Main winding a1 Start windingN

C

L

Winding protector

2

CG.43.J2.02

August 2001

August 2003

CK.40.B7.02

45

NF7FX Standard Compressor R134a 220V 50/60HzData Sheet (Replaces CD.43.W4.22) GeneralCompressor Connector-material Copper-plated steel Copper-plated steel Copper Sealing Aluminium caps Rubber plugs Rubber plugs 105G6743 105G6753Barcode on white background Yellow background

NF7FX Code number

Application Blue stripe

NF7FXR134a SUCTION CONNECTOR

105G

DANFOSS COMPRESSORS

ApplicationApplication Evaporating temperature range Voltage range F (C) V/Hz LBP/MBP -30 to 45 (-34.4 to 7.2) 198 - 242 /50 198 - 242 /60 Motor type Max. ambient temperature Comp. cooling at ambient temp. 90F (32C) 100F (38C) 50Hz: S 50Hz: F1 60Hz: F1 60Hz: F1 F (C) CSIR 100 (38)S O F1 F2

= Static cooling normally sufficient = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary

DesignDisplacement Oil quantity Maximum refrigerant charge cu.in. (cm3) fl.oz. (cm ) oz. (g)3

0.44 (7.27)6.54"(166) 2.83"(72) 2.34" (59.5)

10.8 (320) 14.0 (400) 79.7 (2360) 23.0 (10.5)

Free gas vol. in compressor housing fl.oz. (cm3) Weight without electrical equipment lbs. (kg)

47

MotorMotor size LRA (rated after 4 sec.UL984) HST Cut-in current HST watt A A 340 15.8 15.825

4.45"(113)

4.69"(119) 5.00"(127)

D

8.10"(205)

(54)

51

3.01"(78)

27

2.13"

E C35

Resistance, main and start winding (77F) Approvals (105G6743) Approvals (105G6753)

5.8/12.63.68"(93.5)

EN 60335-2-34 with Annex AA

A B

DimensionsHeight in. (mm) A B Suction connector Process connector Discharge connector Compressors on a pallet 8.00 (203) 7.76 (197)5.20"(132) 4.00"(101.6) 2.76"(70)

9.92"(252) 8.03"(204) 6.70"(170)

8367

location/I.D. in. (mm) C 0.320-0.327 (8.20.09)1.38"(35)

location/I.D. in. (mm) D 0.252-0.259 (6.50.09) location/I.D. in. (mm) E pcs. 0.252-0.259 (6.50.09) 80

6.50"(165) 7.32"(186)

August 2003

CD.43.W5.22

4.04"(102.5)

0.75"(19) 0.63"(16) 0.38"(9.7)

2.97"(75.5)

8340

6743

15

1

46

CK.40.B7.02

August 2003

Capacity at LBP conditions (ASHRAE)Comp.\F -30 Comp.\C -34.4 NF7FX 341 Comp.\F -30 Comp.\C -34.4 NF7FX 304 Comp.\F -30 Comp.\C -34.4 NF7FX 82 Comp.\F -30 Comp.\C -34.4 NF7FX 134 Comp.\F -30 Comp.\C -34.4 NF7FX 1.70 Comp.\F -30 Comp.\C -34.4 NF7FX 2.55 Comp.\F -30 Comp.\C -34.4 NF7FX 2.27 Comp.\F -30 Comp.\C -34.4 NF7FX 0.61 -20 -28.9 496 -20 -28.9 442 -20 -28.9 119 -20 -28.9 158 -20 -28.9 1.73 -20 -28.9 3.13 -20 -28.9 2.80 -20 -28.9 0.75 -13 -25 630 -13 -25 562 -13 -25 151 -13 -25 176 -13 -25 1.76 -13 -25 3.58 -13 -25 3.19 -13 -25 0.86 -10 -23.3 696 -10 -23.3 620 -10 -23.3 167 -10 -23.3 184 -10 -23.3 1.78 -10 -23.3 3.79 -10 -23.3 3.37 -10 -23.3 0.91 0 -17.8 943 0 -17.8 840 0 -17.8 226 0 -17.8 209 0 -17.8 1.83 0 -17.8 4.52 0 -17.8 4.02 0 -17.8 1.08 10 -12.2 1255 10 -12.2 1117 10 -12.2 301 10 -12.2 235 10 -12.2 1.89 10 -12.2 5.36 10 -12.2 4.76 10 -12.2 1.28 20 -6.7 1630 20 -6.7 1450 20 -6.7 390 20 -6.7 261 20 -6.7 1.95 20 -6.7 6.27 20 -6.7 5.56 20 -6.7 1.49 30 -1.1 2086 30 -1.1 1854 30 -1.1 498 30 -1.1 287 30 -1.1 2.02 30 -1.1 7.29 30 -1.1 6.46 30 -1.1 1.73 40 4.4 2604 40 4.4 2312 40 4.4 622 40 4.4 314 40 4.4 2.10 40 4.4 8.35 40 4.4 7.36 40 4.4 1.98

Btu/h45 7.2 2899

Capacity at MBP conditions (ASHRAE)

Btu/h45 7.2 2573c a28226

Capacity (EN 12900/CECOMAF)

watt45 7.2 691

d

Power consumption

watt45 7.2 327b

dc

a2

Current consumption

A45 7.2 2.1410 12 11 13

c Start winding Thermostat14

EER at LBP conditions (ASHRAE)

Btu/Wh45 7.2 8.90

Main winding

M

EER at MBP conditions (ASHRAE)

Btu/Wh45 7.2 7.87

Motor protector

COP (EN 12900/CECOMAF)

W/W45 7.2 2.11

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Fan cooling F1, 220V 50Hz

ASHRAE (LBP) 130F (54.4C) 90F (32C) 90F (32C)

ASHRAE (MBP) 130F (54.4C) 95F (35C) 115F (46C)

EN12900/CECOMAF 55C (131F) 32C (90F) 55C (131F)

AccessoriesDevices Star ting relay (Klixon incl.) Protector 3/4" Star ting capacitor 125 F Cover Cord relief Cord relief capacitor Mounting accessories Bolt joint for one compressor Bolt joint for one compressor Snap-on for one compressor Texas Instruments Fig. a2 c b d dc in. (mm) 5 /8 (16) 3 /4 (19) 5 /8 (16) NF7FX 117U4140 MRP59EN-6 117U5018 117U1023 117U0349 117U0349 118-1946 118-1949 118-1947

2

CD.43.W5.22

August 2003

August 2003

CK.40.B7.02

47

NF9FX Standard Compressor R134a 220V 50HzData Sheet (Replaces CD.43.Z2.22) GeneralCompressor Connector-material Copper-plated steel Copper-plated steel Sealing Aluminium caps Rubber plugs 105G6842 (UL-recognized) 105G6952* (UL-recognized) Copper-plated steel Rubber plugs 105G6843 105G6953* Copper Rubber plugs * Oil cooler versionBarcode on white background Yellow backgroundR

NF9FX Code number

Application Blue stripe

NF9FXR134a SUCTION CONNECTOR

105G

DANFOSS COMPRESSORS

ApplicationApplication Evaporating temperature range Voltage range Motor type Max. ambient temperature Comp. cooling at ambient temp. 90F (32C) 100F (38C) O/F1 O/F16.54"(166) 2.83"(72) 2.34" (59.5)

LBP/MBP F (C) V/Hz -30 to 45 (-34.4 to 7.2) 198 - 242 /50 CSIR F (C) 100 (38)S O F1 F2

NF9FX 220V-50Hz 1PHTHERMALLY PROTECTED = Static cooling normally sufficient Approval mark = Oil cooling = Fan cooling 1.5 m/s (compressor compartment temperature equal to ambient temperature) = Fan cooling 3.0 m/s necessary8340-6

DesignDisplacement Oil quantity Maximum refrigerant charge cu.in. (cm3) fl.oz. (cm ) oz. (g)3

10.8 (320) 14.0 (400) 79.7 (2360) 23.0 (10.5)

47

Free gas vol. in compressor housing fl.oz. (cm3) Weight without electrical equipment lbs. (kg)

4.45"(113)

4.69"(119) 5.00"(127)

DMotorMotor size LRA (rated after 4 sec.UL984) HST Cut-in current HST watt A A 340A B3.68"(93.5)25

8.10"(205)

(54)

51

E C35

15.8 15.8 5.8/12.6 UL984/CSA-C22.2 -

4.04"(102.5)

Approvals (105G6843, 105G6853)

DimensionsHeight in. (mm) A B Suction connector Process connector Discharge connector Oil cooler 8.00 (203)5.20"(132) 4.00"(101.6) 2.76"(70)1.38"(35)

9.92"(252) 8.03"(204) 6.70"(170)

1.57" (40)

Approvals (105G6842, 105G6852)

8336

7.76 (197)

location/I.D. in. (mm) C 0.320-0.327 (8.20.09) location/I.D. in. (mm) D 0.252-0.259 (6.50.09) location/I.D. in. (mm) E location/I.D. in. (mm) F pcs. 0.252-0.259 (6.50.09) 0.252-0.259 (6.50.09) 80 CD.43.Z3.22

0.75"(19) 0.63"(16) 0.38"(9.7) 6.50"(165) 7.32"(186)

Compressors on a pallet August 2003

2.97"(75.5)

Resistance, main and start winding (77F)

F

3.01"(78)15

27

2.13"

0.51 (8.35)

1.57" (40)

8340-2

6843

1

48

CK.40.B7.02

August 2003

Capacity at LBP conditions (ASHRAE)Comp.\F -30 Comp.\C -34.4 NF 9FX 389 Comp.\F -30 Comp.\C -34.4 NF9FX 347 Comp.\F -30 Comp.\C -34.4 NF9FX 94 Comp.\F -30 Comp.\C -34.4 NF9FX 151 Comp.\F -30 Comp.\C -34.4 NF9FX 1.72 Comp.\F -30 Comp.\C -34.4 NF9FX 2.57 Comp.\F -30 Comp.\C -34.4 NF9FX 2.30 Comp.\F -30 Comp.\C -34.4 NF9FX 0.62 -20 -28.9 562 -20 -28.9 501 -20 -28.9 135 -20 -28.9 180 -20 -28.9 1.77 -20 -28.9 3.13 -20 -28.9 2.78 -20 -28.9 0.75 -13 -25 712 -13 -25 635 -13 -25 171 -13 -25 200 -13 -25 1.81 -13 -25 3.57 -13 -25 3.17 -13 -25 0.86 -10 -23.3 786 -10 -23.3 701 -10 -23.3 189 -10 -23.3 209 -10 -23.3 1.83 -10 -23.3 3.76 -10 -23.3 3.35 -10 -23.3 0.90 0 -17.8 1061 0 -17.8 945 0 -17.8 254 0 -17.8 238 0 -17.8 1.89 0 -17.8 4.46 0 -17.8 3.97 0 -17.8 1.07 10 -12.2 1409 10 -12.2 1255 10 -12.2 337 10 -12.2 269 10 -12.2 1.97 10 -12.2 5.25 10 -12.2 4.66 10 -12.2 1.25 20 -6.7 1825 20 -6.7 1624 20 -6.7 436 20 -6.7 299 20 -6.7 2.05 20 -6.7 6.12 20 -6.7 5.43 20 -6.7 1.46 30 -1.1 2331 30 -1.1 2072 30 -1.1 557 30 -1.1 330 30 -1.1 2.14 30 -1.1 7.08 30 -1.1 6.28 30 -1.1 1.68 40 4.4 2912 40 4.4 2586 40 4.4 694 40 4.4 361 40 4.4 2.24 40 4.4 8.05 40 4.4 7.16 40 4.4 1.92

Btu/h45 7.2 3237

Capacity at MBP conditions (ASHRAE)

Btu/h45 7.2 2873c a28226

Capacity (EN 12900/CECOMAF)

watt45 7.2 771

d

Power consumption

watt45 7.2 377b

dc

a2

Current consumption

A45 7.2 2.2910 12 11 13

c Start winding Thermostat14

EER at LBP conditions (ASHRAE)

Btu/Wh45 7.2 8.62

Main winding

M

EER at MBP conditions (ASHRAE)

Btu/Wh45 7.2 7.62

Motor protector

COP (EN 12900/CECOMAF)

W/W45 7.2 2.04

Test conditions Condensing temperature Ambient and suction gas temp. Liquid temperature Fan cooling F1, 220V 50Hz

ASHRAE (LBP) 130F (54.4C) 90F (32C) 90F (32C)

ASHRAE (MBP) 130F (54.4C) 95F (35C) 115F (46C)

EN12900/CECOMAF 55C (131F) 32C (90F) 55C (131F)

AccessoriesDevices Star ting relay (Klixon incl.) Protector 3/4" Texas Instruments Star ting capacitor 125 F Cover (105G6842, 105G6852) Cover (105G6843, 105G6853) Cord relief Cord relief capacitor Mounting accessories Bolt joint for one compressor Bolt joint for one compressor Snap-on for one compressor Fig. a2 c b b d dc in. (mm) 5 /8 (16) 3 /4 (19) 5 /8 (16) NF9FX 117U4140 MRP59EN-6 117U5018 117U1021 117U1023 117U0349 117U0349 118-1946 118-1949 118-1947