Damping of Inrush Current in Low Voltage PFC Equipment
Transcript of Damping of Inrush Current in Low Voltage PFC Equipment
8/22/2019 Damping of Inrush Current in Low Voltage PFC Equipment
http://slidepdf.com/reader/full/damping-of-inrush-current-in-low-voltage-pfc-equipment 1/12
http://www.epcos.com
Damping of Inrush Current in Low-Voltage PFC Equipment Low-Voltage PFC
Application Note 2001
8/22/2019 Damping of Inrush Current in Low Voltage PFC Equipment
http://slidepdf.com/reader/full/damping-of-inrush-current-in-low-voltage-pfc-equipment 2/122 EPCOS AG
Power Quality
Contents
General 3
The risks of high inrush current 4
Single capacitor connection, inrush current calculation 6
Parallel capacitor connection, inrush current calculation 7
Various solutions for limiting inrush current serial aircoils 7
Detuning reactors, connection cable selection 8
Capacitor contactors with damping resistorsFunctionality / comparison 9
Comparison 10
Capacitor bank switching under various conditions 11
8/22/2019 Damping of Inrush Current in Low Voltage PFC Equipment
http://slidepdf.com/reader/full/damping-of-inrush-current-in-low-voltage-pfc-equipment 3/123EPCOS AG
Damping of Inrush Current in Low-Voltage PFC Equipment General
The market trend to reduce lossesin modern low-voltage power- factor-correction capacitors (LV-PFCs)and the requirement for highoutput density result in reducedohmic resistance in PFC capacitors.Especially the switching of capa- citors in parallel to others of thebank, already energized, causesextremely high inrush current,up to 200 times the rated current,and limited only by the ohmicresistance of the capacitor itself. According to the formula ( Eq1),such a capacitor’s AC resistance isvery low and thus contributes tohigh inrush current.
LV-PFC capacitor bank
Inrush current (pulse) is a factor of:
a Remaining capacitor voltagedue to fast switching in auto- matic capacitor banks
a Shortcircuit power of supply transformer
a Output of capacitor switchedin parallel to others already energized
aFault level of supply network
a Output of capacitors already energized
a Ohmic resistance of capacitor itself and distribution switchgear, connection cables or con- ductors
KLK1709-W
2 5 k V A r
2 5 k V A r
2 5 k V A r
2 5 k V A r
2 5 k V A r
2 5 k V A r
1 2 . 5
k V A r
2 5 k V A r
M3~
187,5 kVAr
Automatic capacitor bank with 6 capacitors in parallel
High inrush current for grid,high balancing currents for capacitors
xc =1
2*π*f*c
Eq1:
Switching operation: f ∞ © xc0 © î 200 * Ir
8/22/2019 Damping of Inrush Current in Low Voltage PFC Equipment
http://slidepdf.com/reader/full/damping-of-inrush-current-in-low-voltage-pfc-equipment 4/124 EPCOS AG
Inrush Current by ConnectingCapacitor in Parallel (Energization)
The risks of high inrush current
Connecting LV-PFC capacitors with- out damping to an AC grid stressesthe capacitor like a shortcircuit.To avoid negative effects and toimprove a capacitor’s life time, ade- quate damping of inrush current ishighly recommended.
Influence of high inrush currentand resulting distortion:
a High stress on the capacitor © reduced lifetime
a Welding or fast wearing out of the main contacts of contactors
a Negative effects on power quality (eg.voltage transients)
a Overvoltage:– insulation problems
– defects of electronic equipment
– production stop
a Undervoltage/voltage zerocrossing– measurement failure– problems with numerical
control equipment
– production stop due tocomputer failure
a High cost of maintenance andproduction standstill
73.2 73.8 74.5 75.1 75.7 76.3 77.0 77.6 t (ms)
4000
3000
2000
1000
0
-1000
-2000
-3000
C u r r e n t ( A )
Capacitor inrush current
ONOFF 5th capacitor connected
Peak current occurrence
i = 157* IN = 157*21 = 3300 A i
i
Capacitor connection:IN
=rated current= 21A
8/22/2019 Damping of Inrush Current in Low Voltage PFC Equipment
http://slidepdf.com/reader/full/damping-of-inrush-current-in-low-voltage-pfc-equipment 5/12
0 10 20 30 40 50 60 70 80 90 100t (ms)
1500
1000
500
0
-500
-1000
-1500
V o l t a g e ( V )
1st step on 2nd step on 3rd step on 4th step on 5th step on 6th step on
1
1
High peak voltage (transients) occurrenceû
û
û
û
1 12
2
Û > UINS risk of shortcircuit Û ≤ 0 V results in wrong measurementscausing control failures
1
2
5EPCOS AG
Inrush Measurement of Capacitor Steps
Switching of power factor correc- tion (PFC) capacitors is not only related to high currents but alsoto high voltage transients (ref.capacitor switching-on steps 1–6),causing degradation of power quality, if the negative influenceis not prevented by damping.
Capacitor sample,contact surface damagedby high inrush currents
High inrush current occurrencesdue to insufficient dampingcaused high electromechanicalforces within the capacitor. Espe- cially the contact area betweenelectrodes (windings) and themetal-spray layer was extremely stressed by high current forces.
The example shows that a fractionof metal-spray layer separatedfrom the windings. Even the MKK capacitor with excellent pulsecurrent capability and enhancedcontactability due to wavy cut andheavy edge design of the filmshows that extensive power cancause failures.
Voltage at 0.69 kV - busbar
PFC capacitor cascade connection:High voltage transients occurrence due to no damping
Example
Metal-spray layer separated from thecapacitor windings
8/22/2019 Damping of Inrush Current in Low Voltage PFC Equipment
http://slidepdf.com/reader/full/damping-of-inrush-current-in-low-voltage-pfc-equipment 6/126 EPCOS AG
Inrush Current Calculation
KLK1706-7
G r i d
L 3
L
L 2
1 U N
Connecting a single capacitor
Circuit and formula
Terms
Result
Peak inrush current i A Transformer shortcircuit power Sk kVA Rated capacitor output Q kVAr Rated capacitor current IN A Rated voltage UN V
Ohmic resistance = X C Ω
3 *UN2
* (1/Q1+ 1/Q2)
Grid impedance = XI Ω
o*L (Ω) including– contactor – fuse– busbars
Calculation example
Given parameters:
Grid connection of a single 50 kVAr capacitor, no other capacitor connected:a Grid 400 V/50 Hza Transformer shortcircuit voltage: 5%a Transformer output: 1600 kVA a Capacitor Q = 50 kVAr; IN = 72 A
i = = 2575 A
The inrush current is approximately 35 times the rated current.
Typical inrush currents are
10–40 times the rated current for single capacitors during connection.
1600 kVA
2* 0.05 *72 A 50 kVAr
i=2*Sk
*INQ
^
Eq 2
^
^
8/22/2019 Damping of Inrush Current in Low Voltage PFC Equipment
http://slidepdf.com/reader/full/damping-of-inrush-current-in-low-voltage-pfc-equipment 7/12
Connection of a 50 kVAr capacitor, other 300 kVAr capacitors are already connected:a Grid 400 V/50 Hza Transformer shortcircuit voltage: 6%a Transformer output: 630 kVAr a Q1 = 50 kVAr a Q2 = 300 kVAr a IN = 72 A ; V N = 400 V ; f = 50 Hz
a X C = 3 * U2N * ( + ) = 11.2 Ω
a L /phase = 0.4 µH (empirical)a X L = o * L = 2 * π * f * L = 0.125 mΩ
i = = 15118.6 A
The inrush current is approximately 210 times the rated current.
2*400 V
11.2 Ω*0.125*10–3 Ω
1Q2
1Q1
7EPCOS AG
Various Solutionsfor Limiting Inrush Current
KLK1707-F
3C
1C
2C
C 1
1Q Q 2
C 2 3
C
Capacitor
Contactor
G r i d
L 3
L
L 2
1 U N
KLK1708-N
nL
K n K
L 2
2
1L
K 1
2L
L 1
L 3 G r i d
Q n Q 2 Q 1
U N
Parallel connecting of capacitor: Serial air coils
This example shows that cable turns in seriesbetween contactor and capacitor reduce theinrush current. Contactor suppliers recommendinductivity of 6– 8 µH for damping inrush current.To achieve this inductivity, the following table pro- vides tips for selecting the required turns, diame- ters and cross sections.
Given parameters: Given parameters:
Parallel connection of a 50 kVAr capacitor with cable turns (serial aircoils) for damping,other 300 kVAr capacitors are already connect- ed, 400 V/50 Hz, shortcircuit power 10.5 MVA,rated capacitor current 72 A: damping withapprox. 6 µH with turns.a X c = 11.2Ωa X L1 = 2 *π * f * L = 2 * π * 50 * 6 µH = 1.88 mΩ
a X L2 = 2 * π *f *L =0.125 mΩ
a X L total = 0.125 + 1.88 = 2 mΩ
a L /phase = 0.4 µH (empirical value)1)
i = = 3780 A
The inrush current is approximately 50 times the rated current. This means only about a quarter compared to a capacitor without damping (turns).
2*400 V
11.2 Ω*2 *10–3Ω
Typical inrush currents are
100–250 times rated current for single capacitors in parallel connectionto other capacitors in operation.
This example shows that some cable
turns in series with the capacitor contribute to reducing inrush current(to 50 times rated current).This improves capacitor life cycle.
i=2*UN
X c*X L
i=2*UN
X c*(X L1+ X L2)
^ ^
Eq 3 Eq 4
^^
1) For switch gear and connected cables
8/22/2019 Damping of Inrush Current in Low Voltage PFC Equipment
http://slidepdf.com/reader/full/damping-of-inrush-current-in-low-voltage-pfc-equipment 8/128 EPCOS AG
Damping as described is a possiblesimple solution, but this methoddeals with two contradicting effects:
a Longer (or additional) cablescause electrical losses – higher losses cause higher inherent temperature within the capacitor.
a On the other hand, cable turnsreduce the inrush current andincrease the life cycle of capaci- tors and contactors.
Plus, you must make sure that thecapacitor works below its maximumoperating temperature.
Detuning reactors(series anti-harmonic reactors)
In detuned capacitor banks theinductivity of filter circuit reactorsprovides an excellent dampingeffect for limiting inrush current.The following diagrams show the connection of a detuned andnon-detuned (reactor and capac- itor) system.
The peak current of a conventionalcapacitor is higher than 4000 A.The peak current of detuned capac- itors is only approx. 500 A. Thepurpose of filter circuit reactors isof course not the damping of inrush current, but this exampleshows that in the case of detunedcapacitors no additional damp- ing measures are required.
Examples for detunedcapacitor banks (ref. page 2)
Selection table for connection cables
Detuned capacitor with series reactors
Various Solutions for Limiting Inrush Current
Capacitor Turns Approx. Cablerating diameter cross-section
5 kVAr 10 100 mm 2.5 mm2
10 kVAr 10 100 mm 4 mm2
12.5 kVAr 10 100 mm 4 mm2
16.7 kVAr 7 100 mm 6 mm2
25 kVAr 7 100 mm 10 mm2
33 kVAr 7 100 mm 25 mm2
50 kVAr 7 100 mm 35 mm2
Fig. 1: 25 kVAr (21A /690 V)vertical: 2000 A /div horizontal: 0.625ms /div
Fig. 2: 25 kVAr (21A / 690 V)vertical: 200 A / div horizontal: 10 ms / div
Because of the high inductance inthe circuit, the breaking quality of the contactor is important toavoid restriking during switch-off.Especially large contactors (over- sized motor contactors) may betoo slow and are therefore critical.
î > 4000 A
î = 190 * IN
i = 500 A
î = 24 * IN
This table should help to find the appropriate cable and required turns.
Our PFC-CDROM (available upon request) contains calculation softwarewhich enhances precise calculation of the application (capacitors andswitch gear).
Conventional capacitor without damping
8/22/2019 Damping of Inrush Current in Low Voltage PFC Equipment
http://slidepdf.com/reader/full/damping-of-inrush-current-in-low-voltage-pfc-equipment 9/129EPCOS AG
Capacitor contactors with damping resistors
How does it work?
The series damping resistors areswitched by socalled precontactsor auxiliary contacts. The precon- tact closes before main contactsand preloads the capacitor.
a Reduced voltage differences.
a The peak current is limited.
a The resistor is temporarily in thecircuit and has no thermal losses.
a The total resistance of the resistor wires is mainly ohmic in nature,its inductance can be neglected.The coiling up of the dampingresistors is only a matter of con- struction.
a During operation (main contactsare closed) the resistor wires aredisconnected or shorted out, anddo not cause any permanent losses at all. Due to the very short operation time (a few milliseconds
only) during switch-on of thecontactor, a long life cycle of thedamping resistors is ensured.
Auxiliary switchedcontact with serialresistor (precontacts)
Capacitor contactor (main contacts)
Capacitor
Main contacts
Precontacts2...10 ms
on
Grid/ Mains
onoff
onoff
Functional diagram
i=C*dV
dt
^
Note:Due to pre-loading via aux.contacts the capacitor’svoltage difference will bereduced. Consequently also the capacitor current according to the formula:
Damping
resistor
Pre-switching
aux. contacts
Eq 5
8/22/2019 Damping of Inrush Current in Low Voltage PFC Equipment
http://slidepdf.com/reader/full/damping-of-inrush-current-in-low-voltage-pfc-equipment 10/1210 EPCOS AG
With
damping resistors
Without
damping resistors
The following two diagrams show the difference between a capa- citor’s inrush current without andwith damping series resistorswhen a capacitor is switched inparallel to an already energizedcapacitor bank/unit:
Comparison
Facts and conclusion
a Rated current of a 12.5 kVar/400 V capacitor is 18 A
a Peak inrush current without series resistors is 1200 A
a Peak inrush current with series resistors is only 260 A
a 1200 A is equal to 66 times the rated current
a Inrush current with series resistors is only one fifthof that of the standard contactor
a Substantial difference also in terms of power (integrated area)
a Superior switching behavior of contactor with seriesresistors compared with a standard contactor, results inextended life cycle of contactors as well as of capacitors
a Improved power quality ensures trouble-free and safeoperation of the PFC system and application
Fig.3 : 12.5 kVAr (18 A/400 V)
vertical: 250 A/div horizontal: 0.5 ms/div
Fig.4 : 12.5 kVAr (18 A/400 V)
vertical: 250 A/div horizontal: 0.5 ms/div
i = 1200 A
i = 260 A
8/22/2019 Damping of Inrush Current in Low Voltage PFC Equipment
http://slidepdf.com/reader/full/damping-of-inrush-current-in-low-voltage-pfc-equipment 11/1211EPCOS AG
Without precontacts
(detuned capacitor)
With precontacts
(detuned capacitor)
Without precontacts
(non-detuned capacitor)
ComparisonCapacitor bank switching under various conditions
Facts and conclusion
The peak current during switching without using precontacts(Fig.5) exceeds 4000 A
If capacitors are detuned (Fig. 6) the peak is only 500 A
The latter case shows the influence of inductivity andprecontacts of a “capacitor contactor”, the peak current
(Fig.7) is reduced to approx. 200 A
Fig. 5: 25 kVAr (21A /690 V)
vertical: 2000 A/div horizontal: 0.625 ms/div
Fig. 6: 25 kVAr (21 A/690 V)
vertical: 200 A/div horizontal: 10 ms/div
Fig. 7: 25 kVAr (21 A/690 V)
vertical: 200 A/div horizontal: 10 ms/div
i > 4000 A i = 500 A
i < 200 A
8/22/2019 Damping of Inrush Current in Low Voltage PFC Equipment
http://slidepdf.com/reader/full/damping-of-inrush-current-in-low-voltage-pfc-equipment 12/12
Herausgegeben von EPCOS AG, Marketing Kommunikation
Postfach 801709, 81617 München, DEUTSCHLAND
¤ (089) 636-09, FAX (089) 636-2 2689
© EPCOS AG 2000. Alle Rechte vorbehalten. Vervielfältigung, Veröffentlichung, Verbreitung und Verwertung dieser
Broschüre und ihres Inhalts ohne ausdrückliche Genehmigung der EPCOS AG nicht gestattet.
Mit den Angaben in dieser Broschüre werden die Bauelemente spezifiziert, keine Eigen-schaften zugesichert. Bestellungen
unterliegen den vom ZVEI empfohlenen Allgemeinen Lieferbedingungen für Erzeugnisse und Leistungen der
Elektroindustrie, soweit nichts anderes vereinbart wird. Diese Broschüre ersetzt die vorige Ausgabe. Fragen über Technik,
Preise und Liefermöglichkeiten richten Sie bitte an den Ihnen nächstgelegenen Vertrieb der EPCOS AG oder an unsere
Vertriebsgesellschaften im Ausland. Bauelemente können aufgrund technischer Erfordernisse Gefahrstoffe enthalten.
Auskünfte darüber bitten wir unter Angabe des betreffenden Typs ebenfalls über die zuständige Vertriebsgesellschaft
einzuholen.
Published by EPCOS AG, Marketing Communications
P.O.B. 801709, 81617 Munich, GERMANY
¤ ++49 89 636-09, FAX (089) 636-2 2689
© EPCOS AG 2000. All Rights Reserved. Reproduction, publication and dissemination of this brochure and the information
contained therein without EPCOS’ prior express consent is prohibited.
The information contained in this brochure describes the type of component and shall not be considered as guaranteed
characteristics. Purchase orders are subject to the General Conditions for the Supply of Products and Services of the
Electrical and Electronics Industry recommended by the ZVEI (German Electrical and Electronic Manufacturers’
Association), unless otherwise agreed. This brochure replaces the previous edition. For questions on technology, prices and
delivery please contact the Sales Offices of EPCOS AG or the international Representatives. Due to technical requirementscomponents may contain dangerous substances. For information on the type in question please also contact one of our
Sales Offices.
EPCOS AG