Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller Databank - Technical Bulletin Title: Ethernet comms between Qn and FX3U Page 1 of 13 Keywords: Qn, QJ71E71 Ethernet FX3U, FX3U-ENET This document illustrates how to connect a D700 Drive to the following: FX3U PLC GOT 1020/1030 Modbus master E1000 as a Modbus master The information in this document to based around software versions GX Developer V8 GX IEC Developer V7 GT Designer 2 V2.77 E-Designer V7.4 For full communication details see the relevant manuals FX3U PLC to inverter communication FX3U User’s Manual (Data Communication) 168594 GOT 1020/1030 GOT1000 Series Connection Manual SH/NA -08053 Modbus FR-E700-EC (European version applied manual) ib0600336engb Chapter 4.20.6

Transcript of D700 Communication

Page 1: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 1 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

This document illustrates how to connect a D700 Drive to the following: FX3U PLC GOT 1020/1030 Modbus master E1000 as a Modbus master The information in this document to based around software versions GX Developer V8 GX IEC Developer V7 GT Designer 2 V2.77 E-Designer V7.4 For full communication details see the relevant manuals FX3U PLC to inverter communication FX3U User’s Manual (Data Communication) 168594 GOT 1020/1030 GOT1000 Series Connection Manual SH/NA -08053 Modbus FR-E700-EC (European version applied manual) ib0600336engb

Chapter 4.20.6

Page 2: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 2 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

FX3U to D700 FX3U configuration In GX Developer or GX IEC Developer enter the following in to the PLC Parameters:

Page 3: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 3 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

D700 Configuration Enter the following parameters into the D700 drive

Parameter Number

Name Set Value

160 Enable Parameters 0 - 79 Operation mode

selection 0 PU/EXT switch over mode

117 Station number 1 Set to Salve Station number 118 Communication speed 192 19200 119 Stop bit length 10 7 bits 1 stop 120 Parity check

presence/absence 2 With even parity check

121 Number of communication retries

9999 Disabled, but can be used to stop drive if comms failed

122 Communication check time interval

9999 Disabled, but can be used to stop drive if comms failed

123 Waiting time setting 9999 Disabled, but can be used to stop drive if comms failed

124 CR, LF presence/absence

selection

1

340 Link start mode selection

1 Net mode

549 Mitsubishi or Modbus Protocol

0 Mitsubishi

551* PU mode operation command source

selection

9999 Parameter unit automatic recognition Normally, operation panel is the command

source. When the parameter unit is connected to the PU connector, PU is the

command source. For PU operation the same as the E500 set Pr.551 = 2.

Page 4: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 4 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

Wiring

Page 5: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 5 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

GOT configuration. GOT Configuration In GT Designer 2 enter the following in to the system environment

D700 Configuration Enter the following parameters into the D700 drive

Parameter Number

Name Set Value

160 Enable Parameters 0 - 79 Operation mode

selection 0 PU/EXT switch over mode

117 Station number 1 Set to Salve Station number 118 Communication speed 192 19200 119 Stop bit length 10 7 bits one stop 120 Parity check

presence/absence 1 CL

121 Number of communication retries

9999 Disabled, but can be used to stop drive if comms failed

122 Communication check time interval

9999 Disabled, but can be used to stop drive if comms failed

123 Waiting time setting 90 Disabled, but can be used to stop drive if comms failed

124 CR, LF presence/absence selection

1

340 Link start mode selection 1 Net mode 549 Mitsubishi or Modbus

Protocol 0 Mitsubishi

Page 6: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 6 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

Wiring

Photo of wiring a standard Ethernet cable from the RJ-45 PU port on the inverter to the terminal strip on the GOT 1030

Page 7: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 7 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

Addressing

Page 8: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 8 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

Page 9: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 9 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

Modbus E1000 Settings In E-Designer enter the following in to the HMI peripherals

D700 Configuration Enter the following parameters into the D700 drive

Parameter Number

Name Set Value

160 Enable Parameters 0 - 79 Operation mode selection 0 PU/EXT switch over mode

117 Station number 1 Set to Salve Station number 118 Communication speed 192 19200 119 Stop bit length 10 7 bits one stop

This setting has no effect using modbus 120 Parity check

presence/absence 2 CL

This setting has no effect using modbus 121 Number of

communication retries 9999 Disabled, but can be used to stop drive if

comms failed 122 Communication check

time interval 9999 Disabled, but can be used to stop drive if

comms failed 123 Waiting time setting 9999 Disabled, but can be used to stop drive if

comms failed 124 CR, LF presence/absence

selection 1 This setting has no effect using modbus

340 Link start mode selection 1 Net mode 549 Mitsubishi or Modbus

Protocol 1 Modbus

Page 10: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 10 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

Modbus protocol details

Drive parameter details

In this product, the inverter data are classified in the holding register area, register addresses 40001 to 49999.

Page 11: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 11 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

Modbus registers System environment variable

Real time monitor

Page 12: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 12 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

Parameters

Errors

Page 13: D700 Communication

Issued by: Mitsubishi Electric Europe B.V. - UK Branch Document issue: Ver August 2008 Produced by : - CTC Travellers Lane, Hatfield, Herts, AL10 8XB, UK Author: Barry Weller

Databank - Technical Bulletin

Title: Ethernet comms between Qn and FX3U Page 13 of 13 Keywords: Qn, QJ71E71

Ethernet FX3U, FX3U-ENET

Wiring Point-to-Point The RS422 port on the operator terminal is connected to the PU port on the FR-A/F/E/D frequency inverter system or to the RJ45 port on the FR-S500 inverter system with the standard cable CAB9.

The RS232 port on the operator terminal is connected to the PU port on the FR-A/F/E/D frequency inverter system or to the RJ45 port on the FR-S500 inverter system with the standard cable SC-FR-PC.