Flow Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October 2005

Transcript of D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation...

Page 1: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

Flow Computer Division

MI-2667 Annubar Flow Calculation Program (For the FloBoss 103)

User Manual

(QER 05Q038)

D301833X012

Form A6194

October 2005

Page 2: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 ii

Revision Tracking Sheet

October 2005

This manual may be revised periodically to incorporate new or updated information. The revision date of each page appears at the bottom of the page opposite the page number. A change in revision date to any page also changes the date of the manual that appears on the front cover. Listed below is the revision date of each page (if applicable):

Page Revision All pages Oct-05

FloBoss and ROCLINK are marks of one of the Emerson Process Management companies. The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their respective owners.

Fisher Controls International, LLC. 2005. All rights reserved. Printed in the U.S.A. www.EmersonProcess.com/flow While this information is presented in good faith and believed to be accurate, Fisher Controls does not guarantee satisfactory results from reliance upon such information. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding the performance, merchantability, fitness or any other matter with respect to the products, nor as a recommendation to use any product or process in conflict with any patent. Fisher Controls reserves the right, without notice, to alter or improve the designs or specifications of the products described herein.

Page 3: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 iii

Table of Contents

Page

1 INTRODUCTION ................................................................................................................................. 1 1.1 Scope and Organization ........................................................................................................... 1 1.2 Product Overview .................................................................................................................... 1

1.2.1 Annubar Flow Calculations ...................................................................................... 2 1.3 Program Requirements ............................................................................................................. 3

2 INSTALLATION .................................................................................................................................. 4 2.1 Downloading the Program ....................................................................................................... 4

3 CONFIGURATION ............................................................................................................................... 8 3.1 Device Information Screen ...................................................................................................... 8 3.2 Meter Setup Screen – General Tab .......................................................................................... 9 3.3 Meter Setup Screen – Inputs Tab ........................................................................................... 10 3.4 Meter Setup Screen – Gas Quality Tab .................................................................................. 11 3.5 Meter Setup Screen – Advanced Tab ..................................................................................... 12 3.6 Annubar Calculation Screen .................................................................................................. 13 3.7 Saving the Configuration ....................................................................................................... 17 3.8 Monitoring the Annubar Flow Calculation Program ............................................................. 19

3.8.1 Meter Values Screen ............................................................................................... 19

4 REFERENCE: ANNUBAR FLOW CALCULATION POINT TYPE PARAMETERS .................... 20

Page 4: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 1

1 INTRODUCTION 1.1 Scope and Organization This document serves as the user manual for the MI-2667 Annubar Flow Calculation User Program (QER 05Q038), which is intended for use in a FloBoss™ 103. This manual describes how to download and configure this program (referred to as the “Annubar Calculation program” or “the program” throughout the rest of this manual). You access and configure this program using ROCLINK 800 Configuration Software (version 1.50 or greater) loaded on an IBM-compatible personal computer running Windows 98, ME, NT 4.0 (with Service Pack 6), 2000 (with Service Pack 2), or XP. The sections in this manual provide information in a sequence appropriate for first-time users. Once you become familiar with the procedures and the software running in a FloBoss 103, the manual becomes a reference tool. This manual has the following major sections:

Section 1 – Introduction Section 2 – Installation Section 3 – Configuration Section 4 – Reference

This manual assumes that you are familiar with the FloBoss unit and its configuration. For more information, refer to the FloBoss 103 Flow Manager Instruction Manual (Form A6114) or the ROCLINK 800 Configuration Software User Manual (Form A6121). 1.2 Product Overview The MI-2667 Annubar Flow Calculation user program enables a FloBoss 103 to calculate flow rates, integrate volumes, and store historical values determined using the Russian MI-2667 standard. The program provides flow calculations for gas, steam/water, and fluid applications in Metric units. It supports installations implementing either an Annubar Diamond II or an Annubar 485 T-shaped element type. This program provides a program-specific Annubar Calculation screen (see Figure 14) for entering additional program-specific parameters. The FloBoss 103 reads flow inputs (differential pressure, temperature, and static pressure) once every second. The program performs Annubar instantaneous flow rate calculation once every second. You configure the program using the standard Meter Setup screen and the Annubar Calculation screen. The program itself does not perform gas or fluid property calculations. It obtains gas properties from FloBoss firmware, using AGA8 1992 standards, or from a separate user program installed in the FloBoss. The gas calculation requires you to provide compressibility, gas correction factors, and heating values. For steam, water, or fluid applications, you must install a separate user program to calculate and provide the necessary fluid properties, including density and heating value. The Annubar Calculation program accumulates volume (or mass) and energy and provides the accumulations to the FloBoss 103 to be archived into the periodic and daily databases. Values saved to the historical database will be in the units shown below.

Page 5: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 2

Volume/Mass Units Energy Units Gas volume calculation km3 GJoules Mass rate calculation 1000 kg GJoules

1.2.1 Annubar Flow Calculations The MI-2667 Annubar Flow Calculation program provides an instantaneous flow rate for Annubar installations. In gas applications, the program calculates an instantaneous volume flow rate, corrected to base conditions and provided in m3/hour. In steam, water and fluid applications, the program calculates an instantaneous mass flow rate in or kg/hour. Equations used for the gas (volume) and mass calculations are shown below. Gas Volume Equation The program uses the following equation for determining gas volume:

KTP

TPPDq

CC

CC

2

42 x 3600

Where:

D Internal pipe diameter at working condition Meters Annubar flow coefficient - Expansion factor - K Compressibility coefficient - P Absolute pressure Pa Pc Absolute pressure at standard condition Pa

P Differential pressure Pa qc Volume flowrate at standard condition m3/hour Tc Temperature at standard condition Kelvin T Thermodynamic temperature Kelvin с Density at standard condition kg/m3 Mass Rate Equation The program uses the following equation for determine mass rate:

PDqm 2

42 x 3600

Where:

D Internal pipe diameter at working condition Meters Annubar flow coefficient - Expansion factor -

P Differential pressure Pa qm Mass flow rate at standard condition kg/hour Density at flowing condition kg/m3

Page 6: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 3

1.3 Program Requirements You download the Annubar Calculation program to—and then run it from—the Flash and RAM memory on the FloBoss 103. The Annubar Calculation program is compatible only with firmware version 2.12 (or greater) of the FloBoss 103. Download and configure the program using the ROCLINK 800 Configuration software (version 1.50 or greater). The downloadable program is: File Name Unit Task Code Space Data Space UDP

MI2667_Annubar.BIN FloBoss 103 User 1 790000–79FFFF 46C000–46CFFF 22

Note: You must connect a PC to the FloBoss unit’s LOI port before starting the download. For information on viewing the memory allocation of user programs, refer to the ROCLINK 800 Configuration Software User Manual (Form A6121).

Page 7: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 4

2 INSTALLATION This section provides instructions for installing the Annubar Calculation program into FloBoss memory. Read Section 1.3 of this manual for program requirements. 2.1 Downloading the Program

This section provides instructions for installing the user program into FloBoss memory. To download the user program using ROCLINK 800 software:

1. Connect the FloBoss to your computer using the LOI port.

2. Start and logon to ROCLINK 800.

3. Select ROC > Direct Connect to connect to the FloBoss unit.

4. Select Utilities > User Program Administrator from the ROCLINK menu bar. The User Program Administrator screen displays (see Figure 1):

Figure 1. User Program Administrator

5. Click Browse in the Download User Program File frame. The Select User Program File screen displays (see Figure 2).

6. Select the path and user program file to download from the CD-ROM. (Program files are typically located in the Program Files folder on the CD-ROM). As Figure 2 shows, the screen lists all valid user program files with the .BIN extension:

Page 8: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 5

Figure 2. Select User Program File

7. Click Open to select the program file. The User Program Administrator screen displays. As shown in Figure 3, note that the Download User Program File frame identifies the selected program and that the Download & Start button is active:

Figure 3. User Program Administrator

Page 9: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 6

8. Click Download & Start to begin loading the selected programs. The following message displays:

Figure 4. Confirm Download

9. Click Yes to begin the download. During the download, the program performs a Warm Start, creates an event in the Event Log, and—when the download completes—displays the following message:

Figure 5. ROCLINK 800 Download Confirmation

10. Click OK. The User Program Administrator screen displays (see Figure 6). Note that:

The User Programs Installed in Device frame identifies the loaded program. The Status field in that frame shows the device status as “ON” (indicating a successful Warm

Start). The Memory Usage frame indicates the memory the program uses.

Page 10: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 7

Figure 6. User Program Administrator

11. Click Close. The ROCLINK 800 screen displays and the download is complete.

Figure 7. ROCLINK 800

Page 11: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 8

3 CONFIGURATION

After you have loaded the GOST Compressibility program, you configure it using the ROCLINK 800 software. To do this, you use two standard ROCLINK 800 screens (Device Information and Meter Setup) and a program-specific screen (Annubar Calculation):

Use the Device Information screen to select Metric engineering units.

Use the General, Inputs, Gas Quality, and Advanced tabs on the Meter Setup screen to set general parameters.

Use the Annubar Calculation screen to set the program-specific parameters.

3.1 Device Information Screen

Use this screen to check the default units.

1. From the ROCLINK 800 screen, select ROC > Information. The Device Information screen displays.

Figure 8. Device Information

2. Review—and change as necessary—the value in the following field: Field Description

Units Sets the engineering units the program uses. Metric is the required value for this program.

Note: Changing this value may not automatically refresh other displayed values. Verify that what you enter is appropriate for the engineering units you select.

3. Click Apply if you changed the value in this field.

4. Click OK to return to the ROCLINK 800 screen.

Page 12: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 9

3.2 Meter Setup Screen – General Tab

Use the General tab on the Meter Setup screen to define the meter type, calculation standard, and values for the pipe and orifice diameters.

1. From the ROCLINK 800 screen, select Meter > Setup. The Meter Setup screen displays.

2. Select the General tab.

Figure 9. Meter Setup General Tab

3. Assure that the Orifice and 1992 AGA3 radio buttons are clicked and complete the Pipe Diameter field. Review the remainder of the screen to make sure that the values correspond to your organization’s requirements.

Note: The Orifice Diameter field indicates the diameter of the Annubar probe. The program sets this value based on the probe model selected in the Sensor Model field on the Annubar Calculation screen.

4. Click Apply to save any changes. Go to Section 3.3.

Page 13: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 10

3.3 Meter Setup Screen – Inputs Tab

Use the Inputs tab on the Meter Setup screen to identify the I/O definitions and values for differential pressure, static pressure, and temperature.

1. From the Meter Setup screen, select the Inputs tab.

Figure 10. Meter Setup Inputs Tab

2. Complete the Differential Pressure, Static Pressure, and Temperature definitions and values. Review the rest of the screen to make sure that the values correspond to your organization’s requirements.

3. Click Apply to save any changes. Go to Section 3.4.

Page 14: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 11

3.4 Meter Setup Screen – Gas Quality Tab

Use the Gas Quality tab on the Meter Setup screen to define gas composition.

1. From the Meter Setup screen, select the Gas Quality tab.

Figure 11. Meter Setup Gas Quality Tab

2. Review the values on this screen to make sure that they correspond to your organization’s requirements.

3. Click Apply to save any changes. Go to Section 3.5.

Page 15: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 12

3.5 Meter Setup Screen – Advanced Tab

Use the Advanced tab on the Meter Setup screen to set base pressure and base temperature.

1. From the Meter Setup screen, select the Advanced tab.

Figure 12. Meter Setup Advanced Tab

2. Review any values you enter—especially for Base Pressure, Base Temperature, and Elevation—on this screen to make sure that they correspond to your organization’s requirements.

3. Click Apply to save any changes. Go to Section 3.6.

Page 16: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 13

3.6 Annubar Calculation Screen

The Annubar Calculation screen enables you to enter program-specific calculation parameters and displays calculated values.

To access this screen:

1. Click User Data > Annubar Calc MI-2667 from the ROCLINK configuration tree:

Figure 13. ROCLINK 800

2. Double-click #1. The Annubar Calculation screen displays (see Figure 14):

Page 17: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 14

Figure 14. Annubar Calculation

3. Complete the screen fields based on your organization’s requirements. Field Description

Point Number Identifies the iteration (“logical”) of this screen. 1 is the only valid value, since the FloBoss 103 permits only one meter run.

Calc Enable Selects the flow calculation for the meter run. Valid values are 1 (use the Annubar flow calculation) or 0 (use the AGA3 flow calculation).

Softpoint Enable Enables a host to access data from a softpoint if it cannot access the data through other means. Valid values are 0 (disable the access) or 1 through 16 (enable the access and indicate the softpoint to use):

1 Annubar Coefficient (K)

2 Base Density (kg/m3)

3 Flowing Density (kg/m3)

4 Pipe Diameter at Temperature (millimeters)

5 Annubar Probe Diameter at Temperature (millimeters)

6 Current Differential Pressure (Pa)

7 Current Static Pressure (Pa)

8 Current Flowing Temperature (K)

9 Mass Rate (1000 kg/day)

10 Volume Rate (km3/day)

11 Energy Rate (GJoules/day)

Page 18: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 15

Field Description

Softpoint Enable (cont.) 12 Calculation Period (seconds)

13 Expansion Factor (Fa)

14 Base Pressure Factor (Fpb)

15 Base Temperature Factor (Ftb)

16 Flowing Temperature Factor (Ftf)

17 Specific Gravity Factor (Fgr)

18 Compressibility Factor (Fpv)

Sensor Model Identifies the model and size of the Annubar sensor. The program supports both the Annubar Diamond II and Annubar 485 T-shape models. For the Annubar 485 valid values are 1, 2, or 3 (corresponding to sensor size). For the Diamond II valid values are 10, 15, 16, 25, 26, 35, 36, 45, or 46 (corresponding to sensor type).

K (0=Calc,1=Enter) Indicates whether the program automatically calculates the Annubar flow coefficient or uses a value you enter in the Flow Coeff (K) field. Valid values are 0 (program calculates based on sensor type and size and pipe diameter) or 1 (program uses a value you enter). The default is 0.

Enter Density (0=No) Indicates whether the program uses a density you enter or uses density values calculated by a separate fluid properties program. Valid values are 0 (use calculated values) or 1 (use values entered in the Base Density and Flowing Density fields). The default is 0.

Pipe Coeff A Sets the A coefficient required for corrections to pipe diameters in accordance with the GOST 8.563.1 standard.

Pipe Coeff B Sets the B coefficient required for corrections to pipe diameters in accordance with the GOST 8.563.1 standard.

Pipe Coeff C Sets the C coefficient required for corrections to pipe diameters in accordance with the GOST 8.563.1 standard.

Probe Coeff A Sets the A coefficient required for corrections to Annubar probe diameters in accordance with the GOST 8.563.1 standard.

Probe Coeff B Sets the B coefficient required for corrections to Annubar probe diameters in accordance with the GOST 8.563.1 standard.

Probe Coeff C Sets the C coefficient required for corrections to Annubar probe diameters in accordance with GOST 8.563.1 standard.

Gas=0,Steam=1,Liq=2 Indicates the substance under measurement. Valid values are 0 (gas), 1 (steam), and 2 (liquid). Default value is 0.

Calc (Vol=0,Mass=1) Indicates whether the program performs a volumetric or mass calculation. Valid values are 0 (volumetric flow rate calculation) or 1 (mass flow rate calculation). The default is 0.

Flow Coeff (K) Sets the Annubar flow coefficient used in the rate calculation.

Note: In order to enter this value, you must first enter 1 in the K (0=Calc,1=Enter) field.

Base Density Sets, in kg/m3, the density at base (standard) conditions.

Flowing Density Sets, in kg/m3, the density at flowing conditions.

Properties Calc This read-only field shows the gas or fluid properties calculation used to calculate and provide gas correction factors, density, and heating value.

Page 19: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 16

Field Description

For gas volume calculations, this field may show AGA8 1992 Detailed if the FloBoss 103 internal AGA8 properties calculation is active. If a separate gas properties user program (such as GOST properties) is active in the unit, the field displays the name of the standards calculation implemented in that program. For mass calculations, a separate fluid properties user program must be active in the FloBoss 103 providing density and heating value. None displays in the field when no valid fluid properties user program is active in the unit.

Pipe Dia @ Temp This read-only field shows the corrected pipe diameter for temperature at flowing conditions, calculated according to the GOST 8.653.1 standard.

Probe Dia @ Temp This read-only field shows the corrected Annubar probe (orifice) diameter for temperature at flowing conditions, calculated according to the GOST 8.653.1 standard.

Diff Pressure This read-only field shows the live differential pressure reading in Pa.

Static Pressure This read-only field shows the live static pressure reading in Pa.

Flowing Temperature This read-only field shows the live flowing temperature in Degrees K.

Mass Rate This read-only field shows the calculated mass flow rate in 1000 kilograms/day.

Note: This field shows 0 when a volumetric calculation is being performed.

Volume Rate This read-only field shows the calculated volumetric flow rate in km3/day.

Note: This field shows 0 when a mass rate calculation is being performed.

Energy Rate This read-only field shows the calculated energy flow rate in GJoules/day.

Mass Today This read-only field shows the accumulated mass in the current contract day in 1000 kg.

Flow Today This read-only field shows the accumulated volumetric flow in the current contract day in km3.

Energy Today This read-only field shows the accumulated energy in the current contract day in GJoules.

Mass Yesterday This read-only field shows the mass accumulated in the previous contract day in 1000 kg.

Flow Yesterday This read-only field shows volumetric flow accumulated in the previous contract day in km3.

Energy Yesterday This read-only field shows the accumulated energy in the previous contract day in GJoules.

Calc Time (Seconds) This read-only field shows the current rate calculation period, in seconds.

Note: This value should always be 1.0 during normal operation. A value greater than 1.0 may indicate the unit is overloaded.

4. Click Apply to save any changes you have made to this screen.

5. Click OK to close this screen. This completes the process of configuring the Annubar Calculation program. Proceed to Section 3.7 to save your configuration.

Page 20: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 17

3.7 Saving the Configuration

Whenever you modify or change the configuration, save the final configuration to memory. To save the configuration:

1. Select ROC > Flags. The Flags screen displays:

Figure 15. Flags

2. Click Save Configuration. A verification message displays:

Figure 16. Save Verification

Page 21: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 18

3. Click Yes. When the save process completes, a confirmation message displays:

Figure 17. Confirmation

Note: Depending on the size and complexity of the user program, this process may take several minutes. When the process ends, the Status field on the Flags screen displays Completed.

4. Click Update on the Flags screen. This completes the process of saving your new configuration.

Page 22: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 19

3.8 Monitoring the Annubar Flow Calculation Program

You can monitor the operation and status of the Annubar Calculation program through user defined points, softpoint parameters, and the Meter Values screen. Refer to section 3.6 for a discussion of the user defined points and softpoint parameters.

3.8.1 Meter Values Screen

The ROCLINK 800 Meter Values screen displays current input values, instantaneous gas rates, accumulation totals, and correction factors. For gas applications, all values shown are corrected. For mass applications, units shown as M3 are actually kg, while units shown as kM3 are actually 1000 kg.

To access this screen:

1. From the ROCLINK 800 screen, select Meter > Values. The Meter Values screen displays:

Figure 18. Meter Values

Page 23: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 20

4 REFERENCE: ANNUBAR FLOW CALCULATION POINT TYPE PARAMETERS

Table 1 shows the parameter definitions for the Annubar user defined point type, which is a tailored for the Annubar flow calculation application. The program creates this point type on startup.

Table 1. Point Type 22, Annubar Flow Parameters

Param number

Read/ write

Valid range Data type

Length

Default value

Description

0 R/W 0, 1 UC 1 1 Compressibility Calc (0=AGA8 Enabled, 1=NX19/SGERG Enabled)

1 R/W 0, 1->16 UC 1 0 Softpoint Write Enable (0=Disabled, 1->16=Enabled=Softpoint Number)

2 R/W 0, 1, 2 UC 1 0 Fluid Type (0=Gas, 1=Steam, 2=Liquid)

3 R/W 0, 1 UC 1 0 Calc Output (0=Volume, 1=Mass)

4 R/W 1, 2, 3, 10, 15, 16, 25, 26, 35, 36, 45, 46

UC 1 1 Sensor Model: 1 through 3 = 485 T-shape Models, 15 through 46 = Diamond II Models

5 R/W 0, 1 UC 1 0 Annubar Flow Coefficient Calc Option (0=Calculate, 1=Enter)

6 R/W NA FLP 4 0.0 Annubar Flow Coefficient Value

7 R/W 0, 1 UC 1 0 Density Calc Option (0=Calculate, 1=Enter)

8 R/W NA FLP 4 0.0 Density Value at Base Conditions (kg/m3)

9 R/W NA FLP 4 0.0 Coefficient A for Pipe Diameter Temperature Correction

10 R/W NA FLP 4 0.0 Coefficient B for Pipe Diameter Temperature Correction

11 R/W NA FLP 4 0.0 Coefficient C for Pipe Diameter Temperature Correction

12 R/W NA FLP 4 0.0 Coefficient A for Probe Diameter Temperature Correction

13 R/W NA FLP 4 0.0 Coefficient B for Probe Diameter Temperature Correction

14 R/W NA FLP 4 0.0 Coefficient C for Probe Diameter Temperature Correction

15 R/O NA FLP 4 0.0 Pipe Diameter at Flowing Temperature (millimeters)

16 R/O NA FLP 4 0.0 Probe Diameter at Flowing Temperature (millimeters)

17 R/O Printable ASCII characters, 0x20-0x7d

AC20 20 “ “ ASCII text string describing the active properties calculation for density and compressibility

18 R/O NA FLP 4 0.0 Live Differential Pressure Value (Pa)

19 R/O NA FLP 4 0.0 Live Static Pressure Value (Pa)

20 R/O NA FLP 4 0.0 Live Flowing Temperature Value (Deg K)

21 R/O NA FLP 4 0.0 Calculated Mass Rate (1000 kg/day)

22 R/O NA FLP 4 0.0 Calculated Volume Rate (km3/day)

Page 24: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 21

Param number

Read/ write

Valid range Data type

Length

Default value

Description

23 R/O NA FLP 4 0.0 Calculated Energy Rate (GJoules/day)

24 R/O NA FLP 4 0.0 Accumulated Mass Today (1000 kg)

25 R/O NA FLP 4 0.0 Accumulated Volume Today (km3)

26 R/O NA FLP 4 0.0 Accumulated Energy Today (GJoules)

27 R/O NA FLP 4 0.0 Accumulated Mass Yesterday (1000 kg)

28 R/O NA FLP 4 0.0 Accumulated Volume Yesterday (km3)

29 R/O NA FLP 4 0.0 Accumulated Energy Yesterday (GJoules)

30 R/O NA FLP 4 1.0 Flow Calculation Period (Seconds)

31 R/O NA FLP 4 0.0 Density at Flowing Conditions (kg/m3)

Page 25: D301833X012 MI-2667 Annubar Flow Calculation … Computer Division MI-2667 Annubar Flow Calculation Program (For the FloBoss 103) User Manual (QER 05Q038) D301833X012 Form A6194 October

MI-2667 Annubar Flow Calculation Program User Manual

Issued Oct-05 22

If you have comments or questions regarding this manual, please direct them to your local sales representative or contact: Emerson Process Management Flow Computer Division Marshalltown, Iowa 50158 USA Houston, TX 77065 USA Pickering, North Yorkshire UK Y018 7JA Website: www.EmersonProcess.com/flow