Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10...

42
Current Trends in UPS Technology Fly Wheels 1 June 5, 2012

Transcript of Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10...

Page 1: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Current Trends in UPS Technology• Fly Wheels

1June 5, 2012

Page 2: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Current Trends in UPS Technology• Fly Wheels

– PowerThru (Phillips Service Industries, Inc.), formerly known as Pentadyne

– Active Power– Vycon Energy– Caterpillar Electric Power

2

http://www.activepower.comhttp://www.vyconenergy.com

June 5, 2012

Page 3: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Current Trends in UPS Technology• Fly Wheels

– Low Speed – More mass means more energy– Double mass = double energy– “Low-speed” 1800 to 8000RPM

– High Speed– More energy by higher rpm– Double rpm = quadruple energy– “High-speed” 36000 to 55000RPM

3

http://www.activepower.com

http://www.vyconenergy.com

June 5, 2012

Page 4: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Current Trends in UPS Technology

4

0.5 to 1 min0.3%

Under 10 Sec96.3%

2 min to 8 hours2.1%

1 to 2 min0.9%

10 to 30s0.5%

EPRI Distribution Power Quality Study 1993 - 1995

• Fly Wheel Applications– Power Protection – Battery Hardening– Ride through to Generator

Two Year Study, 300 Sites, 24 Utilities• 97.2% under 30 sec.• 96.3% under 10 sec.• 93.0% Under 2 sec

June 5, 2012

Page 5: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Flywheel UPS Parallel Online Architecture

Static Bypass

» Most energy efficient UPS – up to 98% efficient

» Power dense – twice the power in half the space

» Highly reliable source» Environmentally friendly

Harmonic Current

http://www.activepower.com

5June 5, 2012

Page 6: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Current Trends in UPS Technology• Fly Wheels - Run Times

6http://www.vyconenergy.com

June 5, 2012

Page 7: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

UPS and Flywheel ConfigurationsGen

7http://www.vyconenergy.com

Current Trends in UPS Technology

June 5, 2012

Page 8: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

UPS Flywheel and Battery(Battery Hardening)

Gen

8http://www.vyconenergy.com

Current Trends in UPS Technology

June 5, 2012

Page 9: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Gen

Gen

Multi Module / Parallel Configurations

9http://www.vyconenergy.com

Current Trends in UPS Technology

June 5, 2012

Page 10: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Current Trends in UPS Technology• Other Trends

10June 5, 2012

Page 11: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Current Trends in UPS Technology• Other Trends

– Compressed Air • ActivePower has dropped the concept• Utility Scale Storage is still being pursued

11

http://www.activepower.com http://www.smartgrid.gov/sites/default/files/pge-oe0000198-oct-2011.pdf

June 5, 2012

Page 12: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Current Trends in UPS Technology• Other Trends

– Compressed Air Energy Storage (CAES)–

12

http://www.sandia.gov/ess/docs/ARRA_StorDemos_4-22-11.pdf

June 5, 2012

Page 13: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Other Current Trends in Data Centers

13June 5, 2012

Page 14: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• Real Time Power Monitoring enhance maintenance of power quality and system availability– battery monitoring systems– advanced private meters more

accurately measure• real power consumption• building’s power supply• power conditioners • load banks

UPS Evaluation Report Released, Aug 10, 2009, EC&M Magazine

14

Other Current Trends in Data Centers

June 5, 2012

Page 15: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• high-tech SCADA systems– control the power flow to a building based

on events in the public utility grid– automatically change the amount of power

consumption in a building capable of onsite generation of its own

– smart grid solutions communicate with utility so the facility can react to certain outages

– facility sensors ping the utility that they are active and stable, and if there are problems

– can dispatch utility crews for repairsUPS Evaluation Report Released, Aug 10, 2009, EC&M Magazine

15

Other Current Trends in Data Centers

June 5, 2012

Page 16: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Other Current Trends in Data Centers• High Performance Computing (HPC)

16June 5, 2012

Page 17: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• High Performance Computing (HPC)– Loads

• 32kW per rack liquid cooled– 2,000 W per equipment SF

• 8 kW per rack air cooled– 500 W per equipment SF

June 5, 2012

June 5, 2012

17

Other Current Trends in Data Centers

Page 18: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• High Performance Computing (HPC)

June 5, 2012

June 5, 2012

18

Other Current Trends in Data Centers

Page 19: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• High Performance Computing (HPC)

June 5, 2012

June 5, 2012

19

Other Current Trends in Data Centers

Page 20: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• High Performance Computing (HPC)

June 5, 2012

June 5, 2012

20

Other Current Trends in Data Centers

Page 21: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• High Performance Computing (HPC)

June 5, 2012

June 5, 2012

21

Other Current Trends in Data Centers

Page 22: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• High Performance Computing (HPC)

June 5, 2012

June 5, 2012

22

Other Current Trends in Data Centers

Page 23: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• 80 Plus Computer Power Supplies

June 5, 2012

June 5, 2012

23

Other Current Trends in Data Centers

Page 24: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• 80 Plus• The 80 PLUS performance

specification requires power supplies in computers and servers to be 80% or greater energy efficient. This makes an 80 PLUS certified power supply more than 33% more efficient than current power supplies.

June 5, 2012

June 5, 2012

24

Other Current Trends in Data Centers

www.80PLUS.org

Page 25: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• 80 Plus Computer Power Supplies

June 5, 2012

June 5, 2012

25

Other Current Trends in Data Centers

www.80PLUS.org

Page 26: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• 80 Plus Computer Power Supplies

June 5, 2012

June 5, 2012

26

Other Current Trends in Data Centers

www.80PLUS.org

Page 27: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• 80 Plus Computer Power Supplies

June 5, 2012

June 5, 2012

27

Other Current Trends in Data Centers

www.80PLUS.org

Page 28: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• 80 Plus Computer Power Supplies

June 5, 2012

June 5, 2012

28

Other Current Trends in Data Centers

ASHRAE, Datacom Equipment Power Trends and Cooling Applications, Chapter 3, Fig 3.10 New ASHRAE updated and expanded power trend chart, © 2005 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., www.ashrae.org.

+

+

Page 29: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

Other Current Trends in Data Centers• Putting these efficiencies together:

– Using the higher efficiencies of the different conversion steps from facility entry AC to the processor:

• Step Down Transformer (99.5%)• AC UPS (95%) [12-pulse]• Computer Power Supply (90%) [80Plus Gold]• Point of load converter (98%)

– Step Down Transformer (99.5%) x AC UPS (95%) x Computer Power Supply (90%) x Point of Load Converter (98%) = 83%

– Versus 58%, this is a 43% improvement in efficiency

http://hightech.lbl.gov/documents/UPS/Final_UPS_Report.pdf

29June 5, 2012

Page 30: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• 80 Plus Computer Power Supplies

June 5, 2012

June 5, 2012

30

Other Current Trends in Data Centers

Page 31: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

June 5, 2012

June 5, 2012

31

Other Current Trends in Data Centers

Page 32: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• Fuel Cells

June 5, 2012

June 5, 2012

32

Other Current Trends in Data Centers

Page 33: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• Fuel Cells

June 5, 2012

June 5, 2012

33

Other Current Trends in Data Centers

400 kW471 kVA480 V, 60 Hz, 3-wire

Electrical Efficiency: >40% initial >38% 10-year average

Page 34: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• Fuel Cells– The PureCell® system Model 400 is a stationary

phosphoric acid fuel cell (PAFC) powerplantintended for distributed generation (DG) and combined heat and power (CHP) applications

– Power Factor Range (at nominal line voltage)• 0.85 lag/lead to 1.0 (adjustable)• 0.85 leading to ±5% line• 0.9% lag at +5% line.

– Heat Recovery Characteristics• low-grade (LG) heating delivered at up to 190ºF • high-grade (HG) heating delivered at up to

250ºF

June 5, 2012

June 5, 2012

34

Other Current Trends in Data Centers

Page 35: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• Fuel Cells

June 5, 2012

June 5, 2012

35

Other Current Trends in Data Centers

Page 36: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

• Fuel Cells– Unlike a battery which has a finite capacity (before requiring

recharge), a fuel cell can operate as long as it is supplied with fuel…runtime is only limited to the number of hydrogen tanks that can be physically (and economically) stored on site. Since a fuel cell takes some time to start before it can take on the critical load, a power-bridging technology is…required (such as a battery, flywheel, or ultracapacitor) as part of the entire solution.

June 5, 2012

June 5, 2012

36

Other Current Trends in Data Centers

Comparing Data Center Batteries, Flywheels, and Ultracapacitors; http://www.apcmedia.com

Advantages:• Clean – no hazardous

materials• Silent and vibration free• Lightweight and compact• Few moving parts

Disadvantages:• Does not eliminate need for

bridging technology• Complex site preparation to

accommodate• High cost of processing,

transporting,• storing hydrogen (or other) fuel

Page 37: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

June 5, 2012

June 5, 2012

37

Questions

Page 38: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

References:1. Forbs.com, Commentary, Data Centers Aren't All The Same, Kenneth G.

Brill, 02.11.09, http://www.forbes.com/2009/02/10/data-center-computing-technology-cio-network_0211_data_center.html

2. www.eaton.com/pq/whitepapers, Maximizing UPS Availability, Chris Loeffler,WP11-01 www.eaton.com/powerquality January 2011

3. IEEE 493-2007, Recommended Practice for the Design of Reliable Industrial and Commercial Power Systems (Gold Book), ©2007 IEEE

4. http://www.distributedenergy.com/DE/Articles/Quality_and_Reliability_17127.aspx, Quality and Reliability Power failures can ruin reputations and bottom lines, Dan Rafter, Distributed Energy Magazine, Tuesday, May 01, 2012,

5. The Uptime Institute, http://uptimeinstitute.com/6. EPRI Distribution Power Quality Report RP 3098-1, April 19957. The Power of Green: Mitsubishi 9900A Series High Efficiency True On-Line

Double Conversion Uninterruptible Power Supply (UPS), Mitsubishi Electric Power Products Inc., Dean Richards BEng (Hons) CEng MIET, Junichiro Onishi BEc (Hons) Document: DRJO-TP1rev1, December 17, 2008

8. What Will the Data Center of the Future Look Like?, Paul Rubens, © 2011, Internet.com, a division of QuinStreet, Inc.

June 5, 2012

June 5, 2012

38

Page 39: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

References:9. 15 Seconds Flywheel Reserve or 15 Minutes Battery Reserve? The

reliability difference, D. DeCoster, Mission Critical West Inc., www.mcwestinc.com

10. UPS Evaluation Report Released, Aug 10, 2009, EC&M Magazine, 11. Roadmap for Public Interest Research for High-Performance Data Centers

William Tschudi, Tengfang Xu, Dale Sartor, and Jay Stein – E Source Building Technologies Department Environmental Energy Technologies Division Ernest Orlando Lawrence Berkeley National Laboratory University of California 1 Cyclotron Road Berkeley, California 94720-8134 USA, LBNL-53483

12. High Performance Buildings: Data Centers Uninterruptible Power Supplies (UPS), December, 2005 My Ton, Ecos Consulting, Portland, Oregon; Brian Fortenbury, EPRI Solutions Knoxville, TN; December, 2005, Lawrence Berkeley National Laboratory's (LBNL); http://hightech.lbl.gov/documents/UPS/Final_UPS_Report.pdf

13. Blade Server Power Solutions: Cabinet Level Power Distribution Solutions for High Density Cabinets, High Density Cabinet Power Solutions, February 22, 2006, White Paper STI-100-001, ©2006Server Technology Inc., all right reserved, www.servertech.com

14. Steve Fairfax of MTechnology, Inc., 7X24 Conference Nov 2010

June 5, 2012

June 5, 2012

39

Page 40: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

References:15. Flywheels Gain as Alternative to Batteries, Rich Miller, June 26th, 2007

http://www.datacenterknowledge.com/archives/2007/06/26/flywheels-gain-as-alternative-to-batteries

16. Comparing Data Center Batteries, Flywheels, and Ultracapacitors, Stephen McCluer and Jean-Francois Christin, Schneider Electric, 2011 http://www.apcmedia.com/salestools/DBOY-77FNCT_R2_EN.pdf,

17. A Quantitative Comparison of High Efficiency AC vs. DC Power Distribution for Data Centers, Neil Rasmussen and James Spitaels, Schneider Electric, 2012

18. Pacific Gas and Electric Company, Advanced Underground Compressed Air Energy Storage, Kimberly Nuhfer, Kevin F Swartz, October 2011; http://www.smartgrid.gov/sites/default/files/pge-oe0000198-oct-2011.pdf

19. ARRA Energy Storage Demonstrations, Sandia National Laboratories, retrieved April 13, 2012; http://www.sandia.gov/ess/docs/ARRA_StorDemos_4-22-11.pdf

June 5, 2012

June 5, 2012

40

Page 41: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

References:

June 5, 2012

June 5, 2012

41

Page 42: Current Trends in UPS Technology · Current Trends in UPS Technology 4 0.5 to 1 min 0.3% Under 10 Sec 96.3% 2 min to 8 hours 2.1% 1 to 2 min 0.9% 10 to 30s 0.5% EPRI Distribution

References:

June 5, 2012

June 5, 2012

42