CURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards: acc. to BS 3938, EN 60044-1 Technical data: Class of accuracy: 0.2S…0,5S (see table). Rated burden: max. 3,75 VA (see table). Rated voltage: 720 V. Rated frequency: 50-60 Hz. Rated sec. current: 5 A Security factor: FS 5 FS10 Working temperature range: -20 … +45°C. Insulation class: E (max. 120°C) High voltage test: 4 kV eff , 50 Hz, 1 min. Protection: IP 00. Case: non-flammable plastic, UL 94 V-0. Rated Type: MAK 62 / 20 primary Acc. Busbar hole: 20,5x12.5 mm current class Rated burden (VA) I n 1,5 2.5 3.75 5 100 A 0,2S 0,5S 125 A 0,2S 0,5S 150 A 0,2S 0,5S 200 A 0,2S 0,5S 250 A 0,2S 0,5S 300 A 0,2S 0,5S 400 A 0,2S 0,5S Ni-Fe Si-Fe Order specification: -Ring-type current transformer. -Class of accuracy: 0,5S -Rated primary current: 250 A. -Rated secondary current 5 A -Rated burden: 2.5 VA -Busbar dimension: 20X12,5mm. MAK 62/20 250/5A Cl. 0,5S 2,5VA 47 33 6.6 35 57 71 44 62 Dimensions in mm. 12.5 15.5 20.5 20.5 12.5 15.5 78 Weight: 350-420gr. 17/1 Note: -On request orders for types different from table are accepted. -On request order for clip for DIN EN 50 022 rail are accepted. Cat. No. 12-3044-94.

Transcript of Current transformers Class: 0,5S - C+D Automatika |...

Page 1: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards: acc. to BS 3938, EN 60044-1 Technical data: Class of accuracy: 0.2S…0,5S (see table). Rated burden: max. 3,75 VA (see table). Rated voltage: 720 V. Rated frequency: 50-60 Hz. Rated sec. current: 5 A

Security factor: FS 5 FS10

Working temperature range: -20 … +45°C. Insulation class: E (max. 120°C)

High voltage test: 4 kVeff, 50 Hz, 1 min.

Protection: IP 00. Case: non-flammable plastic, UL 94 V-0.

Rated Type: MAK 62 / 20

primary Acc. Busbar hole: 20,5x12.5 mm

current class Rated burden (VA)

In 1,5 2.5 3.75 5

100 A 0,2S

0,5S

125 A 0,2S

0,5S

150 A 0,2S

0,5S

200 A 0,2S

0,5S

250 A 0,2S

0,5S

300 A 0,2S

0,5S

400 A 0,2S

0,5S

Ni-Fe Si-Fe

Order specification: -Ring-type current transformer.

-Class of accuracy: 0,5S -Rated primary current: 250 A. -Rated secondary current 5 A -Rated burden: 2.5 VA -Busbar dimension: 20X12,5mm.

MAK 62/20 250/5A Cl. 0,5S 2,5VA

47

336.6

355771

4462

Dimensions in mm.

12.5 15.520.520.5

12.5

15.5

78

Weight: 350-420gr.

17/1

Note: -On request orders for types different from table are accepted. -On request order for clip for DIN EN 50 022 rail are accepted. Cat. No. 12-3044-94.

Page 2: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

MAK 62/30 For currents from 100A to 800A. Type: ring/busbar Standards: acc. to BS 3938, EN 60044-1.

Technical data:

Class of accuracy: 0.2S…0,5S (see table). Rated burden: max. 10 VA (see table). Rated voltage: 720 V. Rated frequency: 50-60 Hz. Rated sec. current: 5 A

Security factor: FS 5 FS10

Working temperature range: -20 … +45°C.

High voltage test: 4 kVeff, 50 Hz, 1 min.

Insulation class: E (max. 120°C) Protection: IP 00. Case: non-flammable plastic, UL 94 V-0.

Rated Type: MAK 62 / 30 Rated Type: MAK 62 / 30

primary Acc. Busbar hole 31x11 mm (see fig.) primary Acc. Busbar hole 31x11 mm (see fig.)

current cl. Rated burden (VA) current cl. Rated burden (VA)

In 1 1.5 2.5 3.75 5 7.5 In 1,5 2,5 3,75 5 7,5 10 15

100 A 0,2S 300 A 0,2S

0,5S 0,5S

125 A 0,2S 400 A 0,2S

0,5S 0,5S

150 A 0,2S 500 A 0,2S

0,5S 0,5S

200 A 0,2S 600 A 0,2S

0,5S 0,5S

250 A 0,2S 750 A 0,2S

0,5S 0,5S

800 A 0,2S

Ni-Fe Si-Fe

0,5S

Dimension in mm

Order specification: -Ring-type current transformer. -Class of accuracy: 0.5S -Rated primary current: 300 A. -Rated secondary current 5 A -Rated burden 2,5 VA -Busbar dimension: 30x10 mm.

MAK 62/30 300/5A Cl. 0,5S 2,5VA

Note:

-On request orders for types different from table are accepted. -On request order for clip for DIN EN 50 022 rail are accepted. Cat. No. 12-3044-94.

Weight:200…380gr

17/2

Page 3: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

MAK 62/40 For currents from 200A to 750A. Type: ring / busbar Standards: acc. to BS 3938, EN 60044-1.

Technical data: Class of accuracy: 0.2S …0,5S (see table). Rated burden: max. 5 VA (see table). Rated voltage: 720 V. Rated frequency: 50-60 Hz. Rated sec. current: 5 A

Security factor: FS 5

Working temperature range: -20 … +45°C. High voltage test: 4 kVeff, 50 Hz, 1 min.

Insulation class: E (max. 120°C) Protection: IP 00. Case: non-flammable plastic, UL 94 V-0.

Rated Type: MAK 62 / 40 Rated Type: MAK 62 / 40

primary

Acc. Busbar hole 40,5x11 mm (see fig.) primary Acc. Busbar hole 40,5x11 mm

current cl. Rated burden (VA) current cl. Rated burden (VA)

In 1 1,5 2,5 3,75 5 In 1,5 2,5 3,75 5 7,5 10

200 A 0,2S 500 A 0,2S

0,5S 0,5S

250 A 0,2S 600 A 0,2S

0,5S 0,5S

300 A 0,2S 750 A 0,2S

0,5S 0,5S

400 A 0,2S

0,5S

Dimension in mm

Ni-Fe Si-Fe

Order specification:

-Ring-type current transformer. -Class of accuracy: 0.2S -Rated primary current: 600 A. -Rated secondary current 5 A -Rated burden: 3,75 VA -Busbar dimension: 40x10 mm.

MAK 62/40 600/5A Cl. 0,2S 3,75VA

Note:

-On request orders for types different from table are accepted. -On request order for clip for DIN EN 50 022 rail are accepted.

Cat. No. 12-3044-94.

Weight:180…250gr

17/3

Page 4: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

MAK74/20 For currents from 100A to 400A Type: ring / busbar Standards: acc. to BS 3938, EN 60044-1.

Technical data: Class of accuracy: 0.2S…0,5S (see table). Rated burden: max. 5 VA (see table). Rated voltage: 720 V. Rated frequency: 50-60 Hz. Rated sec. current: 5 A

Security factor: FS 5 FS10

Working temperature range: -20 … +45°C. High voltage test: 4 kVeff, 50 Hz, 1 min.

Insulation class: E (max. 120°C) Protection: IP 00. Case: non-flammable plastic, UL 94 V-0.

Rated Type: MAK 74/20

primary Acc. Busbar hole 21x11 mm (see fig)

In 1 1,5 2,5 3,75 5

100 A 0,2S

0,5S

125 A 0,2S

0,5S

150 A 0,2S

0,5S

200 A 0,2S

0,5S

250 A 0,2S

0,5S

300 A 0,2S

0,5S

400 A 0,2S

0,5S

Ni-Fe Si-Fe

Order specification:

-Ring-type current transformer -Class of accuracy: 0,2S -Rated primary current: 300 A. -Rated secondary current: 5 A. -Rated burden: 2,5 VA -Busbar dimension: 20x10 mm

MAK 74/20 300/5 A Cl .0,2S 2,5VA

No Note:

-On request orders for types different from table are accepted. -On request order for clip for DIN EN 50 022 rail are accepted.

Cat. No. 12-3044-94.

Dimension in mm

Weight:580…680gr

17/4

Page 5: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

MAK74/30 For currents from 100 A to 800 A. Type: ring / busbar Standards: acc. to BS 3938, EN 60044-1

Technical data: Class of accuracy: 0.2S …0,5S (see table). Rated burden: max. 15 VA (see table). Rated voltage: 720 V. Rated frequency: 50-60 Hz. Rated sec. current: 5 A. Working temperature range: -20 … +45°C.

High voltage test: 4 kVeff, 50 Hz, 1 min.

Insulation class: E (max. 120°C) Protection: IP 00. Case: non-flammable plastic, UL 94 V-0.

Rated Type: MAK 74/30

Rated Type: MAK 74/30

primary Acc. Busbar hole 31x15 mm (see fig.) primary Ac. Busbar hole 31x15 mm (see fig.)

current cl. Rated burden (VA) current cl. Rated burden (VA)

In 1 1.5 2,5 3,75 5 7,5 In 1 1,5 2,5 3,75 5 7,5 10 15

100 A 0,2S 300 A 0,2S

0,5S 0,5S

125 A 0,2S 400 A 0,2S

0,5S 0,5S

150 A 0,2S 500 A 0,2S

0,5S 0,5S

200 A 0,2S 600 A 0,2S

0,5S 0,5S

250 A 0,2S 750 A 0,2S

0,5S 0,5S

800 A 0,2S

0,5S

Ni-Fe Si-Fe

Dimension in mm

Order specification: -Ring-type current transformer -Class of accuracy: 0,5S -Rated primary current: 300 A. -Rated secondary current: 5 A. -Rated burden: 2,5 VA -Busbar dimension 30x15 mm

MAK 74/30 300/5 A Cl.0,5S 2,5VA

Note: -On request orders for types different from table are accepted. -On request order for clip for DIN EN 50 022 rail are accepted. Cat. No. 12-3044-94.

17/5

Security factor: FS 5 FS10

Page 6: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

MAK74/40 For currents from 200A to 1000A Type: ring / busbar Standards: acc. to BS 3938, EN 60044-1

Technical data: Class of accuracy: 0.2S 0,5S (see table). Rated burden: max. 15 VA (see table). Rated voltage: 720 V. Rated frequency: 50-60 Hz. Rated sec. current: 5 A.

Security factor: FS 5 FS10

Working temperature range: -20 … +45°C. High voltage test: 4 kVeff, 50 Hz, 1 min.

Insulation class: E (max. 120°C) Protection: IP 00. Case: non-flammable plastic, UL 94 V-0.

Rated

Type: MAK 74/40

primary Acc. Busbar hole 41x12,5 mm

current cl. Rated burden (VA)

In 1 1,5 2,5 3,75 5

200 A 0,2S

0,5S

250 A 0,2S

0,5S

300 A 0,2S

0,5S

400 A 0,2S

0,5S

Rated

Type: MAK 74/40

primary Acc. Busbar hole 41x12,5 mm (see fig.)

current cl. Rated burden (VA)

In 1,5 2,5 3,75 5 7,5 10 12,5 15

500 A 0,2S

0,5S

600 A 0,2S

0,5S

750 A 0,2S

0,5S

800 A 0,2S

0,5S

1000 A 0,2S

0,5S

Ni-Fe Si-Fe

Order specification:

-Ring-type current transformer -Class of accuracy: 0,5S -Rated primary current: 500 A. -Rated secondary current: 5 A. -Rated burden: 3,75 VA -Busbar dimension: 40x12,5 mm

Note: -On request orders for types different from table

are accepted. -On request order for clip for DIN EN 50 022 rail are accepted. Cat. No. 12-3044-94.

Weight:400…500gr

17/6

MAK 74/40 500/5 A Cl. 0,5S 3,75VA

Page 7: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

MAK74/50 For currents from 250 A to 1000 A. Type: ring / busbar Standards: acc. to BS 3938, EN 60044-1

Technical data: Class of accuracy: 0.2S …0.5S (see table). Rated burden: max. 15 VA (see table). Rated voltage: 720 V. Rated frequency: 50-60 Hz. Rated sec. current: 5 A.

Security factor: FS 5 FS10

Working temperature range: -20 … +45°C.

High voltage test: 4 kVeff, 50 Hz, 1 min.

Insulation class: E (max. 120°C) Protection: IP 00. Case: non-flammable plastic, UL 94 V-0

Rated Type: MAK 74/50

primary Acc. Max. busbar hole 51x12,5 mm (see fig)

current class Rated Burden [VA]

In 1 1.5 2.5 3.75 5 7.5 10 12.5 15

0,2S

250 A 0,5S

0,2S

300 A 0,5S

0,2S

400 A 0,5S

0,2S

500 A 0,5S

0,2S

600 A 0,5S

0,2S

750 A 0,5S

0,2S

800 A 0,5S

0,2S

1000 A 0,5S

Ni-Fe Si-Fe

Order specification:

-Ring-type current transformer -Class of accuracy: 0,5S -Rated primary current: 400 A. -Rated secondary current: 5 A. -Rated burden: 2,5 VA

-Busbar dimension 50x12,5 mm or 41

Note: -On request orders for types different from table are accepted. -On request order for clip for DIN EN 50 022 rail are accepted. Cat. No. 12-3044-94.

MAK 74/50 400/5 A Cl. 0,5S 2, 5VA

Dimension in mm

17/7 Weight: 350…450gr

Page 8: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

MAK 86/60

For currents from 300 A to 1600 A. Type: ring / busbar Standards: acc. to BS 3938, EN 60044-1

Technical data:

Class of accuracy: 0.2S…0,5S (see table). Rated burden: max. 15 VA (see table). Rated voltage: 720 V. Rated frequency: 50-60 Hz. Rated sec. current: 5 A.

Security factor: FS5 FS10

Working temperature range: -20 … +45°C. High voltage test: 4 kVeff, 50 Hz, 1 min.

Insulation class: E (max. 120°C) Protection: IP 00. Case: made of non-flammable plastic, UL 94 V-0.

Outline drawing of MAK 86/60

Weight 460...560gr

Different types of MAK 86/60 current transformers see table on next page

17/8

Dimension in mm

Page 9: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

Table with different types of MAK 86/60 current transformers.

Rated Type: MAK 86/60

Primary Acc. Busbar hole dimensions: 61x12,5 mm (see outline drawing)

Current class Rated Burden (VA)

In 1 1,5 2.5 3.75 5 7.5 10 12.5 15 20

300 A 0,2S

0,5S

400 A 0,2S

0,5S

500 A 0,2S

0,5S

600 A 0,2S

0,5S

750 A 0,2S

0,5S

800 A 0,2S

0,5S

1000 A 0,2S

0,5S

1200 A 0,2S

0,5S

1250 A 0,2S

0,5S

1500 A 0,2S

0,5S

1600 A 0,2S

0,5S

Ni-Fe

Si-Fe

Order specification: -Ring-type current transformer. -Class of accuracy: 0.2S -Rated primary current: 1000 A. -Rated secondary current 5 A -Rated burden: 10 VA

-Busbar dimension: 60x12,5 mm or 50 mm

Note: on request orders for types different from table are accepted.

On request order for clip for DIN EN 50 022 rail are accepted. On request order for clip for DIN EN 50 022 rail are accepted. Cat. No. 12-3044-94.

MAK 86/60 1000/5 A Cl. 0,2S 10VA

17/9

Page 10: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

MAK 104/80 For currents from 600 A to 2000A Type: ring / busbar Standards: acc. to BS 3938, EN 60044-1

Technical data:

Class of accuracy: 0.2S … 0,5S (see table). Rated burden: max. 20 VA (see table). Rated voltage: 720 V. Rated frequency: 50-60 Hz. Rated sec. current: 5 A .

Security factor: FS 5 FS10

Working temperature range: -20 … +45°C. High voltage test: 4 kVeff, 50 Hz, 1 min.

Insulation class: E (max. 120°C) Protection: IP 00. Case: non-flammable plastic, UL 94 V-0.

6.6

56

Dimensions in mm

Outline drawing of MAK104/80

126

40

62

76

57

104

86816151

31

12,5 31 51 6165

Weight: 580...650gr

Different types of MAK104/80 current transformers see table on next page

17/10

Page 11: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

Table with different types of MAK 104/80 current transformers.

Rated Type: MAK 104/80

primary

current

Acc.

class Max. busbar hole dimension: 81x12.5 mm or 65 mm

(see outline drawing)

Rated burden (VA)

In 1.5 2.5 3.75 5 7.5 10 12.5 15 20

400 A 0,2S

0,5S

500 A 0,2S

0,5S

600 A 0,2S

0,5S

750 A 0,2S

0,5S

800 A 0,2S

0,5S

1000 A 0,2S

0,5S

1200 A 0,2S

0,5S

1250 A 0,2S

0,5S

1500 A 0,2S

0,5S

1600 A 0,2S

0,5S

2000 A 0,2S

0,5S

Ni-Fe

Si-Fe

Order specification

-Ring-type current transformer -Class of accuracy: 0.5S -Rated primary current: 2000 A. -Rated secondary current: 5 A. -Rated burden: 15 VA

-Busbar dimension: 80x12,5 mm or 65mm

MAK 104/80 2000/5 A Cl. 0,5S 15VA

Note:

On request orders for types different from table are accepted. On request order for clip for DIN EN 50 022 rail are accepted. Cat. No. 12-3044-94

17/11

Page 12: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

MAK 140/100h For currents from 500 A to 3000 A Tpye: ring / busbar Standards: acc. to BS 3938, EN 60044-1

Technical data:

Class of accuracy: 0,2S … 0,5S (see table). Rated burden: max. 20 VA (see table). Rated voltage: 720 V. Rated frequency: 50-60 Hz. Rated sec. current: 5 A.

Security factor: FS 5 FS10

Working temperature range: -20 … +45°C.

High voltage test: 4 kVeff, 50 Hz, 1 min.

Insulation class: E (max. 120°C) Protection: IP 00. Case: non-flammable plastic, UL 94 V-0.

375973

6.6

155

53

104

86 31 51 61 71 81

74

51

617181

101

121

140

Dimensions in mm.

Outline drawing of MAK140/100h

Weight: 900...1100gr

Different types of MAK140/100h current transformers see table on next page

17/12

Page 13: Current transformers Class: 0,5S - C+D Automatika | …meter.hu/Regula/mak_02S_05S_omh_hiteles.pdfCURRENT TRANSFORMERS MAK 62/20 For currents from 100A to 400A. Type: ring/busbar Standards:

CURRENT TRANSFORMERS

Table with different types of MAK140/100h current transformers.

Rated Type: MAK 140/100h

primary

current

Acc.

class

Max. busbar hole dimension: 101x31 mm or 86 mm

(see outline drawing)

Rated burden (VA)

In 1.5 2.5 3.75 5 7.5 10 12.5 15 20

400 A 0,2S

0,5S

500 A 0,2S

0,5S

600 A 0,2S

0,5S

750 A 0,2S

0,5S

800 A 0,2S

0,5S

1000 A 0,2S

0,5S

1200 A 0,2S

0,5S

1250 A 0,2S

0,5S

1500 A 0,2S

0,5S

1600 A 0,2S

0,5S

2000 A 0,2S

0,5S

2500 A 0,2S

0,5S

3000 A 0,2S

0,5S

Si-Fe

Order specification:

-Ring-type current transformer. -Class of accuracy: 0.5S -Rated primary current: 2500 A. -Rated secondary current: 5 A. -Rated burden: 20 VA

-Busbar dimension: 2x100x10 mm or 86 mm

MAK 140/100h 2500/5 A Cl. 0,5S 20VA

Note: On request orders for types different from table are accepted.

17/13