4
Specifications Change Without Notice MPC Gensets 2007 Standard Genset Features Single Source Responsibility Design, manufacture and testing of complete generating set are all produced by a company as assembler International Integrity Assurance and strength of a worldwide major corporation baking the product. Global Service 24 hour spares and service availability in 100 countries. Single source warranty Total product guaranteed by assembler . Packaged Self-Contained Units Integrated unit with built-in anti-vibration system, control panel, starting system and provision for base fuel tank and other accessories. Cummins Engine Heavy duty 4 cycle water cooled engine. Electronic or Mechanical governor control. Cooling System 40°C cooling package (50°C option). Alternator Brushless machine. Eagle Group made alternator. Close voltage regulation. Rotor and exciter impregnated with oil and acid resisting resin. Exceptional short circuit capability. Low waveform distortion with non linear loads. Permanent magnet exciter. Ratings Ambient temperature : Not over 40°C. Relative humidity : Not over 95%. Altitude : Below 1500m above sealevel. Skid Base Built-in anti-vibration system bonded rubber units as standard eliminates need for rubber mats or spring mountings. Standard Control Panel System Microprocessor control. Integrated governor and voltage regulation systems. Superior alternator and genset protection system. Accurate battery monitoring system. Totally reliable and proven system. Smart starting control system. Generator Set Performance CEI 2-3. VDE 0530. BS 4999-5000. NFC 51-100-111 and 112. NEMA MG1-22, IEC 34. ISO 3046 and ISO 8528. General Complete set of operating and instruction manuals. Fabricated and welded steel chassis. Built-in anti-vibration mountings. Inteqral lifting points. Optionai sub-base fuel tank with eight hour capacity, Dual flexible fuel lines, dial type fuel gauge and drain bung. Finish Etch undercoated and finished in high gloss durable musell jade green. Optional Control Panel System Easy and multi functional with full automatic failure indicators, manual or automatic (optional) panels can be chosen. Control panels are mounted on the genset with rubber anti-vibration mountings. Standard production control panels have 3 ammeters, volt meter, hour meter, frequency meter, temperature, oil and charge lamp. Automatic units provide protection against over temperature, low oil pressure, start fault, overspeed and overload. Deep Sea Control Panel Cummins Powered Generating Sets Standby Power (50Hz): 28 KVA to 3325 KVA Prime Power (50Hz): 25 KVA to 3000 KVA Model: DSE 7310 Model: DSE 7320

Transcript of Cummins Powered Generating Sets -...

Page 1: Cummins Powered Generating Sets - …cuulongmachinery.com/Uploaded/Members/5065/files/2013/10/CUMMI… · Cummins Powered Generating Sets Standby Power (50Hz): ... Audible DC alarm

Specifications Change Without Notice MPC Gensets 2007

Standard Genset Features Single Source Responsibility Design, manufacture and testing of complete generating set are all produced by a company as assembler International Integrity Assurance and strength of a worldwide major corporation baking the product. Global Service 24 hour spares and service availability in 100 countries. Single source warranty Total product guaranteed by assembler. Packaged Self-Contained Units Integrated unit with built-in anti-vibration system, control panel, starting system and provision for base fuel tank and other accessories. Cummins Engine ● Heavy duty 4 cycle water cooled engine. ● Electronic or Mechanical governor

control. Cooling System 40°C cooling package (50°C option).

Alternator ● Brushless machine. ● Eagle Group made alternator. ● Close voltage regulation. ● Rotor and exciter impregnated with oil

and acid resisting resin. ● Exceptional short circuit capability. ● Low waveform distortion with non linear

loads. ● Permanent magnet exciter. Ratings Ambient temperature : Not over 40°C. Relative humidity : Not over 95%. Altitude : Below 1500m above sealevel. Skid Base Built-in anti-vibration system bonded rubber units as standard eliminates need for rubber mats or spring mountings. Standard Control Panel System ● Microprocessor control. ● Integrated governor and voltage

regulation systems. ● Superior alternator and genset

protection system. ● Accurate battery monitoring system. ● Totally reliable and proven system. ● Smart starting control system.

Generator Set Performance

CEI 2-3. VDE 0530. BS 4999-5000. NFC 51-100-111 and 112. NEMA MG1-22, IEC 34. ISO 3046 and ISO 8528. General Complete set of operating and instruction manuals.

Fabricated and welded steel chassis. Built-in anti-vibration mountings. Inteqral lifting points. Optionai sub-base fuel tank with eight hour capacity, Dual flexible fuel lines, dial type fuel gauge and drain bung. Finish Etch undercoated and finished in high gloss durable musell jade green.

Optional Control Panel System Easy and multi functional with full automatic failure indicators, manual or automatic (optional) panels can be chosen. Control panels are mounted on the genset with rubber anti-vibration mountings. Standard production control panels have 3 ammeters, volt meter, hour meter, frequency meter, temperature, oil and charge lamp. Automatic units provide protection against over temperature, low oil pressure, start fault, overspeed and overload.

Deep Sea Control Panel

Cummins Powered Generating Sets

Standby Power (50Hz): 28 KVA to 3325 KVA Prime Power (50Hz): 25 KVA to 3000 KVA

Model: DSE 7310

Model: DSE 7320

Page 2: Cummins Powered Generating Sets - …cuulongmachinery.com/Uploaded/Members/5065/files/2013/10/CUMMI… · Cummins Powered Generating Sets Standby Power (50Hz): ... Audible DC alarm

Specifications Change Without Notice MPC Gensets 2007

Specifications

Generator Set Performance Generator Set Options

Voltage Regulation Maintains voltage output to within ±1%. At any power factor between 0.8 lagging and unity. At any variations from No load to full load. At any variations from cold to hot. At speed droop variations up to 5%. Frequency Regulation Isochronous under varying loads from no load to 100% full load. Random Frequency Variation Will not exceed ±0.25-0.5% of its mean value for constant loads – no load to full load.

Waveform Total harmonic distortion open circuit voltage waveform in the order of 1.5%. three-phase balanced load in the order of 5%. Telephone Influence Factor TIF better than 50. THF to BS4999 part 40 better than 5%. Alternator Insulation Class H insulation. Radio Interference In compliance with BS800 and VDE levels G and N.

Engine

Cummins series 4-16 cylinder in-line or vee formation, direct injection, four-cycle diesel engines. Type Water cooled, Natural or turbocharged and aftercooled. Construction Four valves per cylinder, forged steel crankshaft and connecting rods, cast iron block, With replaceable wet liners. Starting 12 or 24 volt negative earth, Battery charging alternator.

Fuel System 12 or 24 volt fail safe solenoid, dual spin-on paper element fuel filters, PT fule injection systems with integral electronic governor. Dual flexible fuel lines with connectors. Filters Dry element air filters with restriction indicator and spin-on paper element full flow and by pass lube oil filters. Spin on corrosion resistor filter. Cooling High ambient 40°C radiator as standard with 50°C ambient as option. Oil cooler.

Alternator

Type Brushless, single bearing, revolving field, 4 pole, drip proof, screen protected. 3 phase, 4 wire of 12 wire. Class H insulation. Enclosed to IP21 and IP23 (NEMA) standard. IC 01 cooling system. Fully interconnected damper winding. AC exciter and rotating rectifier unit. Epoxy coated stator winding. Rotor and exciter impregnated with tropical. Grade insulating oil and acid resisting. Polyester resin. Dynamically balanced rotor to BS5625 grade 12.5. Sealed for life bearings. Layer wound mechanically wedged rotor.

Exciter Permanent magnet exciter Triple dipped in moisture, oil and acid resisting polyester varnish and coated with anti-tracking varnish. Sealed solid state automatic voltage regulator – self-exciting, self-regulating.. Output windings with 2/3 pitch for improved harmonics and paralleling ability.Close coupled engine/alternator for perfect alignment. Voltages Standard alternators are equipped with a main winding with 12 or 4 terminals, star with neutral connection. Special voltages available on request.

Engine

Electronic governor control. Mechanical governor control. Heavy duty air cleaner with safety

element. 120 or 240 volt coolant heater

(thermostatically controlled). Low coolant level – warning or

shutdown. Water separator. Sump evacuation pump. Exhaust gas temperature monitoring. Tool kit.

Alternator

Anti-condensation heater. 105°C rise alternator.

Exhaust System

Industrial-grade exhaust silencer. Residential-grade exhaust silencer. Length of flexible exhaust pipe. Bellows.

Fuel System

8hr sub-base fuel tank and gauge. Free-standing 50-3200 gal fuel tanks. High/low/shutdowns and warrings. Electric fuel transfer. Manual transfer pump.

Generator Set

Main line circuit breaker. Auxiliary contacts. Shunt trip. Disconnect switch. Cable entrance box. Battery charger, 5-20 amp. Batteries lead acid or ni-cad. Audible DC alarm (loose). Export box packaging.

Other

Page 3: Cummins Powered Generating Sets - …cuulongmachinery.com/Uploaded/Members/5065/files/2013/10/CUMMI… · Cummins Powered Generating Sets Standby Power (50Hz): ... Audible DC alarm

TECHNICAL DATA SHEET Generating Sets - Cummins Engine Range

● Voltage: 208/120V, 380/220V, 416/240V, 440/254V.

• In accordance with ISO 8528. • Prime: Continuous running at variable load for unlimited periods with 10% overload available for 1 hour in any 12 hour period. • Standby: Continuous running at variable load for duration of an emergency. • All ratings are based on the following reference conditions: - Ambient temperature: 50°C - Altitude above sea level: 1000 metres - Relative humidity: 98%

A Single Source For All Power System Solutions

Specifications Change Without Notice MPC Gensets 2007

RATING 50Hz, 1500rpm, 400V/230V

Fuel Cons (Prime)

(l/h)

APPROXIMATE DIMENSIONS

(mm)

STANBY PRIME

GENSET MODEL

CUMMINS

DIESEL

ENGINE

No.

of Cyls

KVA KW KVA KW 75% load

Full (L) (W) (H) load

NET WEIGHT

(kg)

MPC28 4B3.9G1 4L 28 22 25 20 4.7 6.3 1620 720 1280 780MPC33 4B3.9G2 4L 33 26.4 30 24 5.7 7.6 1700 720 1280 800MPC38 4B3.3G1 4L 38 30 33 26 6.3 8.4 1720 729 1280 820MPC42 4BT3.3G1 4L 42 33 37 30 6.4 8.5 1740 729 1280 830MPC50 4BT3.3G 4L 50 40 45 36 6.5 8.6 1760 729 1280 940MPC55 4BT3.9G2 4L 55 44 50 40 8.6 11.5 1808 729 1280 860MPC70 4BT3.9G4 4L 70 56 63 50 11 15 1828 630 1320 1022MPC80 4BTA3.9G1 4L 80 64 72 58 12 16 1828 630 1368 1077MPC100 6BT5.9G1 6L 100 80 90 72 14 19 2100 830 1490 1250MPC110 6BT5.9G2 6L 110 88 100 80 15 20 2130 900 1500 1300MPC125 6BTA5.9G2 6L 125 100 113 90 16.5 22 2150 1000 1500 1316MPC150 6BTA5.9G2 6L 150 120 136 109 23 31 2176 1000 1500 1440MPC180 6-ISBeG1 6L 180 144 164 131 27 36 2400 1108 1500 1453MPC208 6CTA8.3G2 6L 208 165 188 150 30 40 2427 1000 1685 1870MPC225 6CTAA8.3G2 6L 226 181 205 164 33.7 45 2623 1020 1685 2018MPC250 6CTAA8.3G2 6L 250 200 227 182 38 51 2623 1020 1685 2018MPC275 LTAA8.9L 6L 275 220 250 200 39 52 3000 1100 1750 2200MPC275S NT855GA 6L 275 220 250 200 39.4 52.6 3020 1100 1830 2400MPC300 QSL9 6L 300 240 275 220 40.5 54 3060 1100 1850 2500MPC313 NTA855G1A 6L 313 250 285 228 43 57.5 3100 1100 1850 2800MPC330 QSL9 6L 330 264 300 240 45 60 3120 1100 1850 2860MPC358 NTA855G1B 6L 358 286 325 260 49 65.6 3150 1100 1900 2950MPC388 NTA855G2A 6L 388 310 350 280 53 70.7 3150 1100 1900 2950MPC400 NTA855G4 6L 390 312 350 280 54 72 3156 1100 1914 3032MPC413 NTA855G7 6L 413 330 375 300 55.5 74 3190 1100 1930 3100MPC440 NTA855G7 6L 440 352 400 320 56 75 3228 1100 1941 3140MPC450 NTAA855G7 6L 450 360 413 330 60 80 3300 1100 1950 3200MPC500 KTA19G3 6L 500 400 450 360 72.7 97 3419 1246 1950 4055MPC550 QSX15G8 6L 550 440 500 400 77 103 3494 1500 1807 4100MPC575 KTA19G4 6L 576 461 511 409 80 107 3419 1246 1906 4205MPC625 KTAA19G5 6L 625 500 562 450 86 115 3450 1300 1990 4300MPC650 KTAA19G6 6L 650 520 600 480 88.5 118 3500 1300 2000 4400MPC688 KTAA19G6A 6L 688 550 625 500 97.5 130 3600 1300 2000 4500MPC688S KTAA19G7 6L 688 550 625 500 102 136 3650 1638 2050 4600MPC706 VTA28G5 12V 706 565 640 512 105 140 3819 1483 2037 5604MPC825 VTA28G6 12V 825 660 750 600 110 147 4080 1756 2181 6278MPC825S KTA38G2 12V 825 660 750 600 111.7 149 4500 1780 2430 6450MPC840 QSK23G3 12V 840 672 760 608 113 151 4593 1502 2086 6550MPC900 QSK23G3 12V 900 720 820 656 120.7 161 4693 1502 2086 6700MPC1000 KTA38G2A 12V 1000 800 910 728 136.5 182 4600 1600 2100 6750MPC1041 QST30G3 12V 1041 833 939 751 138 184 4230 1756 2248 6890MPC1100 QST30G4 12V 1110 888 1000 800 151.5 202 4469 1755 2248 7488MPC1133 KTA38G5 12V 1133 907 1030 824 156.7 209 4479 1854 2194 8466MPC1250 KTA38G9 12V 1250 1000 1125 900 187.5 250 4387 2083 2228 8615MPC1375 KTAA38G9 12V 1375 1100 1250 1000 189 252 4387 2083 2230 8650MPC1400 KTA50G3 16V 1400 1120 1256 1005 190.5 254 5283 2066 2233 9960MPC1675 KTA50G8 16V 1675 1341 1500 1200 216.7 289 5637 2250 2250 11300MPC2063 QSK60G3 16V 2063 1650 1875 1500 267 356 5828 2270 2550 15245MPC2250 QSK60G4 16V 2250 1800 2000 1600 295.5 394 5891 2270 2550 15345MPC2500 QSK60G8 16V 2500 2000 2250 1800 337.5 450 5842 2270 2800 17000MPC3325 QSK78G6 16V 3325 2660 3000 2400 NA NA 6628 2251 3200 25800

Page 4: Cummins Powered Generating Sets - …cuulongmachinery.com/Uploaded/Members/5065/files/2013/10/CUMMI… · Cummins Powered Generating Sets Standby Power (50Hz): ... Audible DC alarm

Specifications Change Without Notice MPC Gensets 2007

DEEP SEA - DSE 7320 CONTROL PANEL(Options)

DSE 7320 Control Panel With Amp Sentry Protection

DSE 7320 Control Panel Standard configuration with optional contactor buttons shown

● Integrated automatic voltage regulator

and engine speed governor. ● Amp Sentry Protection guards the

electrical integrity of the alternator and power system from the effects of overcurrent, over/under voltage, under frequency and overload conditions.

● Control components designed to withstand the vibration levels typical in generator sets.

Standard Control Description

● Digital of current mater (amps). ● Digital AC frequency meter. ● Digital AC voltage meter. ● Digital display panel. ● Cycle cranking control. ● Emergency stop switch. ● Idle mode control. ● Menu switch. ● Panel backlighting. ● Remote starting. ● Reset switch. ● Run-Off-Auto switch. ● Sealed front panel, gasketed door. ● Self diagnostics ● Separate customer interconnection box. ● Voltmeter/Ammeter phase selector

switch. Standard Performance Data

AC Alternator Data ● Current by Phase. ● Kilowatts. ● Kilowatt Hours. ● Power Factor. ● Voltage Line to Line. ● Voltage Line to Neutral. Engine Data ● Battery Voltage. ● Coolant Temperature. ● Engine Running Hours. ● Engine Starts counter. ● Oil Pressure. ● RPM. EMC Compliance

The Control system meets EMC Shield Regulations.

Standard Protection Functions

Warnings ● High Coolant Temperature. ● High DC Voltage. ● Low Coolant Temperature. ● Low DC Voltage. ● Low Fuel – Day Tank. ● Low Oil Pressure ● Over Current. ● Overload Load Shed Contacts. ● Up to Four Customer Fault Inputs. ● Weak Battery. Shutdowns ● Emergency Stop. ● Fail to Crank. ● Low Coolant Level.

(Option for alarm only) ● Low Oil Pressure. ● Overcrank. ● Overcurrent. ● Overspeed. ● Short Circuit. ● Underfrequency. ● High/Low AC Voltage. Disconnector Switch

The addition of a circuit breaker is considered unnecessary when control system with Amp Sentry protection is fitted. For isolation purposes a switch disconnector can be supplied and mounted in the normal circuit breaker position on either side of the control panel.

Voltage Regulation

±0.5% with Deep Sea 7320 Control Panel System fitted. Options

Deep Sea Control Panel (Options) Model DSE 7320 ● Audible alarm and shutdown. ● Key switch-operating mode ● Shutdown alarm-relay ● Running relays 4 pole D.T. ● Warning low fuel/high fuel. ● Shut down – low fuel level. ● Earth fault. Shutdown. ● High alternator temperature

alarm/shutdown Other

6 WIRES TYPE TELEPHONE MAX 200m

INTERFACE FOR REMOTE SIGNALS, INTERNET , INTRANET AND VARIOUS

INTERFACE FOR REMOTE SIGNALS, INTERNET , INTRANET AND VARIOUS

THREE MODULES WITH PROGRAMMABLE REMOTE SIGNALS THREE MODULES WITH PROGRAMMABLE REMOTE SIGNALS