LIST OF DRAWINGS F-001 NO. DRAWING TITLE ABV AD AFF ALT. ARCH. BSC CAP. ABOVE ABOVE FINISHED FLOOR ALTERNATE ARCHITECTURAL BUILDING CAPACITY CLG CO. COL. COMB. CONC. CONN. CONST. CONT. CEILING CLEANOUT COLUMN COMBINATION CONCRETE CONNECTION CONSTRUCTION CONTINUOUS DET. DIA. DIM. DN. DWG. DWH E.C. ELEV. EM. GEN. ENCL. EQUIP. EWC ELECTRICAL CONTRACTOR EMERGENCY GENERATOR ENCLOSURE EQUIPMENT ELECTRIC WATER COOLER DETAIL DIAMETER DIMENSION DOWN DRAWING DOMESTIC WATER HEATER EXIST. EXP. F FAI FD FHR FIN. FIXT. FLR FAHRENHEIT FRESH AIR INLET FLOOR DRAIN FIRE HOSE RACK FINISH FIXTURE FLEXIBLE FLOOR ID INSUL. INV. JC LAV. LF INSIDE DIAMETER INSULATION INVERT JANITOR CLOSET LAVATORY LINEAL FOOT LTG. MB MECH. MFR. MTD. MTL. N/A NIC NOT APPLICABLE NOT IN CONTRACT METAL MOUNTED MANUFACTURER MECHANICAL MOP BASIN LIGHTING NOM. NTS OC OD OH OVERHEAD OUTSIDE DIAMETER ON CENTER NOT TO SCALE NOMINAL P.C. PRESS. PSI REV. RM. SCHED. SECT. SF SIM. SPEC. S/STL STAINLESS STEEL SPECIFICATION SIMILAR SQUARE FOOT SECTION SCHEDULE ROOM REVISION PRESSURE STL. STOR. STP STRUCT. SUSP. TEMP. U VERT. VERTICAL TEMPERATURE URINAL SUSPENDED STRUCTURAL STANDPIPE STORAGE STEEL VOL. VTR WC WH WEIGHT WATER HEATER WATER CLOSET VENT THROUGH ROOF VOLUME EXISTING EXPANSION FIRE HOSE CONNECTION S SINK AREA DRAIN SH SHOWER FP FPM FPS GA. GAL G.C. GPH GPM HEO HP FIRE PROTECTION FEET PER MINUTE FEET PER SECOND FOOT (FEET) GAUGE GALLONS GENERAL CONTRACTOR GALLONS PER HOUR GALLONS PER MINUTE HORSEPOWER FD FLOOR DRAIN HB HOSE BIBB CONTRACTOR PLUMBING SQUARE INCH POUNDS PER GO LAB FUEL GAS OUTLET HAO COMPRESSED AIR OUTLET LABORATORY HIGH PRESSURE WT FT FLEX BLDG HGT HEIGHT LABORATORY HELIUM GAS OUTLET LAO COMPRESSED AIR OUTLET LABORATORY LOW PRESSURE LVO LABORATORY VACUUM OUTLET NO NITROGEN GAS OUTLET SQ FT SQUARE FEET BTM BOTTOM BIO SAFETY CABINET PD PLANTER DRAIN BWV BACKWATER VALVE AM. ARGON MANIFOLD ETM ETHANE MANIFOLD FM FLOURINE MANIFOLD HM HELIUM MANIFOLD NM. NITROGEN MANIFOLD PM. PROPANE MANIFOLD LEGEND OF SYMBOLS ABBREVIATIONS NOTE: SOME ABBREVIATIONS HAVE NOT BEEN USED ON THIS PROJECT SCW SOFTENED WATER ELEVATION DATE DD SUBMISSION CD SUBMISSION TP M FLOW METER P201 B2 REVISION INDICATOR 2 HB WALL HYDRANT C.0. RISER WITH WALL CLEAN OUT FLOOR CLEAN OUT C.0. ON THE SAME PAGE) (REFERS TO NOTES KEYNOTE INDICATOR PRESSURE/TEMPERATURE TEST PLUG TEMPERATURE & PRESSURE RELIEF VALVE (section B2 on dwg. P201) PIPE RISER INDICATOR (Riser LCW-1, Drawing P301) 2 DETAIL INDICATOR XXXX XXXX 1A PIPE TURNED UP PIPE TURNED DOWN CAP STRAINER PRESSURE GAUGE THERMOMETER UNION BALL VALVE PUMP LCW-1 P301 PIPE SIZE TAGGING (ie. First Floor Pipe Group A) EX CW RX CW (i.e. EX CW = Existing Cold Water) EXISTING PIPING TO REMAIN (i.e. RX CW - Remove Existing Cold Water) REMOVE EXISTING PIPING DESIGNATES POINT OF CONNECTION DESIGNATES POINT OF DEMOLITION CLEAN OUT C.0. WATER HAMMER ARRESTOR TEE TURNED DOWN TEE TURNED UP GAS COCK CALIBRATED BALANCING VALVE SWING CHECK VALVE WC 1 (type WC, number 1) BACKFLOW PREVENTER BACKWATER VALVE OS & Y GATE VALVE FIXTURE / EQUIPMENT TAG ROOF DRAIN / EMERGENCY ROOF DRAIN FLOOR DRAIN AREA DRAIN / DECK DRAIN NOTE: SOME SYMBOLS HAVE NOT BEEN USED ON THIS PROJECT PRESSURE REDUCING VALVE AND GAUGE BUTTERFLY VALVE S SOLENOID VALVE REVIEW DATE AREA NOT IN SCOPE PAF PRE-ACTION FIRE PIPE CD SUBMISSION DATE DATE CD SUBMISSION F-001 FIRE PROTECTION COVER SHEET FIRE PROTECTION COVER SHEET F-201 1. 2. 3. 4. 5. 6. 7. 8. 13. 12. 11. 10. 9. SEALERS) DAMAGED DURING THE CONSTRUCTION SHALL BE REPLACED AT THE COST OF THE CONTRACTOR AT FAULT. OR MATERIALS STORED ON FLOORS, AND IN AREA WHERE CONSTRUCTION MAY DAMAGE THE FLOOR SURFACES. BUILDING SURFACES (INCLUDING PROTECT BUILDING SURFACES FROM DAMAGE DURING THE CONSTRUCTION PERIOD. PROVIDE PLYWOOD OR SIMILAR MATERIAL UNDER EQUIPMENT EXPERTISE NECESSARY TO INCLUDE NECESSARY ACCESSORIES. THESE FIRE PROTECTION DOCUMENTS MAY NOT EXPLICITLY DISCLOSE FINAL DETAILS; HOWEVER, FIRE PROTECTION CONTRACTOR SHALL HAVE THE PROTECTION WORK REQUIRED. THEREFORE, IT SHOULD BE OBVIOUS TO ANY PRUDENT FIRE PROTECTION CONTRACTOR WITH EXPERIENCE THAT FIRE PROTECTION CONTRACTOR SHALL HAVE SUFFICIENT EXPERTISE IN THIS TYPE OF CONSTRUCTION TO REALIZE THE EXTENT OF THE FIRE PROVIDE ITEMS THAT MAY BE REQUIRED TO MEET THE CONDITIONS AT THE BUILDING. MANNER THAT INTERFERENCES BETWEEN PIPES, CONDUIT, DUCTS, EQUIPMENT, ARCHITECTURAL AND STRUCTURAL FEATURES ARE AVOIDED. REQUIRED TO MAKE A COMPLETE OPERATING SYSTEM. CAREFULLY INVESTIGATE CONDITIONS AFFECTING WORK AND INSTALL WORK IN SUCH A BECAUSE OF THE SCALE OF THE DRAWINGS; IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, FITTINGS, VALVES, OR SIMILAR ITEMS WHICH MAY BE PROTECTION WORK. DIAGRAMMATIC AND INDICATE ONLY THE GENERAL ARRANGEMENT OF THE ITEMS COMPRISING THE SEVERAL SYSTEMS INCLUDED IN THE FIRE THE PRIMARY CONTRACT REQUIREMENTS OF PROVIDING COMPLETE FIRE PROTECTION SYSTEMS. THE FIRE PROTECTION DRAWINGS ARE THE DRAWINGS AND SPECIFICATIONS ARE PRESENTED TO DEFINE SPECIFIC FIRE PROTECTION SYSTEM REQUIREMENTS AND SERVE TO EXPAND ON SHALL CONFORM WITH ACCEPTED TRADE PRACTICES, LOCAL CODES, AND GOVERNING AUTHORITIES. DRAWINGS. ITEMS OR WORK NOT SHOWN OR SPECIFIED, BUT REQUIRED FOR A COMPLETE FIRE PROTECTION SYSTEM, SHALL BE PROVIDED AND PROJECT. THE FIRE PROTECTION SYSTEM SHALL CONFORM TO THE DETAILS STATED IN THE SPECIFICATIONS AND SHOWN ON THE FIRE PROTECTION INTENT OF THE FIRE PROTECTION DRAWINGS AND SPECIFICATIONS ARE TO PROVIDE A COMPLETE FIRE PROTECTION SYSTEM FOR THE PROPOSED REQUIREMENTS. FIRE PROTECTION PIPING, COMPONENTS, AND APPURTENANCES LOCATED IN STAIRWELLS SHALL BE PROVIDED TO MAINTAIN EGRESS WIDTH FIRE PROTECTION CONTRACTOR SHALL PROVIDE ALTERNATE SOLUTION. APPROVAL PRIOR TO ANY CUTTING OR CORING. IF THE STRUCTURAL ENGINEER DOES NOT APPROVE SIZE OR LOCATION OF BEAM PENETRATION, LOCATION SHALL BE DETERMINED BY THE FIRE PROTECTION CONTRACTOR AND SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW AND COORDINATE FIRE PROTECTION PIPE INSTALLATION WITH BUILDING STRUCTURE. WHEN BEAM PENETRATIONS ARE REQUIRED, THE EXACT SIZE AND AND SIZING SHALL BE DETERMINED BY THE FIRE PROTECTION CONTRACTOR. FIRE PROTECTION PIPING INDICATED ON DRAWINGS IS SHOWN IN APPROXIMATE LOCATIONS AND SIZED FOR REFERENCE ONLY. EXACT LOCATION CONFIGURATION. FIRE PROTECTION PIPING SHALL BE COORDINATED WITH THE ARCHITECT AND HYDRAULIC CALCULATIONS BASED ON APPROVED SPRINKLER PIPING THIS MAY RESULT IN THE QUANTITY OF SPRINKLERS BEING GREATER THAN WHAT IS REQUIRED BY NFPA. FIRE PROTECTION CONTRACTOR SHALL PROVIDE SPRINKLERS AND APPURTENANCES BASED ON ARCHITECTURAL FEATURES AND COMPONENTS. PROVIDE SPRINKLER PROTECTION ABOVE AND BELOW ALL OBSTRUCTIONS CREATED BY OTHER DISCIPLINES. SPACE. PIPING SHALL NOT BE LOCATED IN ANY ELECTRICAL ROOMS, CLOSETS, OR TELE / COMMUNICATION ROOMS UNLESS THOSE PIPES SERVE ONLY THAT COORDINATE WORK WITH WORK SHOWN ON OTHER TRADES DRAWINGS. 21. 20. 19. 18. 17. 16. 15. 14. FIRE PROTECTION GENERAL NOTES FIRE PROTECTION WATER PIPE WET SPRINKLER PIPE SPR F UPRIGHT SPRINKLER CONCEALED PENDENT SPRINKLER DRY UPRIGHT SPRINKLER D HT HIGH TEMPERATURE UPRIGHT SPRINKLER PENDANT SPRINKLER SIDEWALL SPRINKLER EARTH UNDISTURBED PLAN 2 . 5 ' x 2 . 5 ' MI N B E A R I NG F A C E EXCAVATED TRENCH WIDTH BACKFILL FINAL 78 " MI N I MU M PIPING FIRE 12" MIN 12" MAX 6" MIN - BEDDING BACKFILL INITIAL GRADE FINAL 2 . 5 ' x 2 . 5 ' MI N B E A R I NG F A C E GRADE ELEVATION FOOTER BUILDING WALL THRUST BLOCK THRUST BLOCK CEILING SPRINKLER ARM-OVER PIPING OR CROSS MAIN SPRINKLER BRANCH 1" X 1/2" REDUCER OF CEILING TILE. SPRINKLER IN CENTER CONCEALED SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 CEILING OBSTRUCTION 48" OR LARGER SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN SPRINKLER ARM-OVER PIPING UPRIGHT SPRINKLER, PIPING, AND APPURTENACES PROVIDED IN ACCORDANCE WITH NFPA 13 SPRINKLER BRANCH OR CROSS MAIN MAIN WATER P L U MB I NG C ON T R A C T O R P O I N TO FC ONN E C T I ON B Y B YWA TE R AU T HO R I T Y CLEARANCE 30" MAX. 12" MIN. TO GRADE S I D E W A L K STREET SOIL UNDISTURBED THRUST BLOCK THRUST BLOCK 12" 12" HORIZONTAL CLEARANCE LINE HORIZONTAL CLEARANCE LINE (TYPICAL) TEST COCK TO FIRE HYDRANT TO BAS TAMPER SWITCH AUTHORITY) (BY WATER FIRE WATER VAULT DEPARTMENT CONNECTION TO FREE STANDING FIRE CHECK VALVE PRESSURE GAUGE PRESSURE GAUGE WITH METERED BYPASS BACKFLOW PREVENTER GATE VALVE NTS 1 THRUST BLOCK DETAIL FP-001 NTS 2 FP-001 UNDERGROUND INSTALLATION OF FIRE PIPE SYSTEM NO. W-L-5096 SECTION A-A F RATINGS - 1 AND 2 HR (SEE ITEM 1 AND 3) T RATINGS - 0,1/2 AND 1 HR (SEE ITEMS 1, 3 AND 4) 3 ONE METALLIC PIPE OR TUBING SHALL BE PROVIDED CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE OR TUBE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. 4 VOID OR CAVITY - SEALANT SHALL BE PROVIDED WITH A MINIMUM 5/8 INCH OR THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF SLEEVE. FOR AT POINT CONTACT AN ADDITIONAL 1/2 INCH BEAD OF SEALANT SHALL BE PROVIDED TO THE INSULATED PIPE/ WALL INTERFACE. 1 WALL ASSEMBLY - REFER TO ARCHITECTURAL DRAWINGS FOR RATED WALL ASSEMBLY LOCATIONS AND CONSTRUCTIONS. 2 PIPE SLEEVE - PROVIDE PIPE SLEEVE THROUGH CIRCULAR CORE DRILLED OPENING IN WALL. LENGTH OF SLEEVE BE EQUAL TO THICKNESS OF WALL. 2 3 4 1 4 NTS 3 FP-001 THROUGH RATED WALL UN-INSULATED PIPE PENETRATION NTS 5 FP-001 NTS 6 FP-001 SPRINKLER ARM-OVER DETAIL SPRINKLER UNDER MECHANICAL OBSTRUCTIONS DETAIL NTS 7 FP-001 FIRE WATER SERVICE ENTRANCE DETAIL IN BOTH DIRECTIONS SPRINKLER TO BE ALIGNED TILE 24" SQUARE C L C L NTS 5 FP-001 SPRINKLER LOCATION IN CEILING TILES TAMPER SWITCH FLOW SWITCH 12" MIN. 12" MIN. PROVIDE TEMPORARY FIRE PROTECTION FOR USE DURING CONSTRUCTION IN ACCORDANCE WITH NFPA. JURISDICTION REQUIREMENTS. PROVIDE SWAY BRACING AND SEISMIC BRACING FOR ALL FIRE PROTECTION PIPING IN COMPLIANCE WITH NFPA - 13 AND AUTHORITY HAVING BE COORDINATED IN THE FIELD BASED ON REFLECTED CEILING PLANS AND FM GLOBAL SPACING REQUIREMENTS. SHOP DRAWINGS SHALL BE PREPARED AND SUBMITTED IN ACCORDANCE WITH FM GLOBAL SPACING REQUIREMENTS. SPRINKLER LOCATIONS SHALL SPRINKLER LOCATIONS SHOWN ARE THE MINIMUM REQUIRED FOR THE PROJECT TO MEET ARCHITECTURAL REQUIREMENTS. SPRINKLER SYSTEM INSTALLATION. COORDINATE THE EXACT LOCATION OF SPRINKLERS, COMPONENTS, AND DEVICES WITH OTHER TRADES DRAWINGS PRIOR TO ROUGH - IN AND RESPONSIBLE FOR ANY REQUIRED CROSS REFERENCE BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND OTHER DISCIPLINES. PIPING AND VALVE IDENTIFICATION SHALL BE IN ACCORDANCE WITH OWNER'S IDENTIFICATION SYSTEM AND RELEVANT CODES. CONTRACTORS ARE PROVIDE PIPING SO THAT VALVES ARE ACCESSIBLE AND STEMS ARE EXTENDED VERTICALLY UP. EACH FLOOR MAIN TAKE OFF FROM RISER. PROVIDE SHUT-OFF VALVES WITH TAMPER SWITCHES AT EACH FLOOR SUPPLY. PROVIDE FLOOR CONTROL TEST AND DRAIN VALVE ASSEMBLIES ON PROVIDE AUXILIARY DRAINS FOR TRAPPED SECTIONS OF PIPING. PROVIDE FIRE PROTECTION PIPING WITH POSITIVE GRADE TO DRAIN. PIPING SHALL BE GRADED TO DRAIN BACK TO THE SUPPLY PIPING BY GRAVITY. FLOW SWITCH FIRST FLOOR AND ROOF FIRE PROTECITON PLANS OS & Y VALVE ALARM CKECK VALVE DISCHARGE TO GRADE OS & Y VALVE CAH CLG 8/4/17 8/4/17 Revisions No. Date Description A B C D E F G H 1 2 3 4 5 6 The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing - any errors or omissions shall be reported to Stantec without delay. The Copyrights to all designs and drawings are the property of Stantec. Reproduction or use for any purpose other than that authorized by Stantec is forbidden. Copyright Reserved Drawing No. Scale 7 I 8 CONFIDENTIAL INFORMATION: The information set forth hereon constitutes confidential proprietary technology of PPG INDUSTRIES, Inc. In consideration of the opportunity to supply goods or services to or on behalf of PPG requiring the use of said information, the recipient of this document agrees: (1) not to copy or reproduce said document in whole or in part without prior written authorization by PPG; (2) to return said document upon demand by PPG; (3) to make no use of said information other than for supplying goods or services in connection with the installation shown in the title without prior written authorization by PPG; (4) not to disclose said document or the information it includes to any third party. DISCIPLINE ITEM NO. DO NOT SCALE THIS PRINT DRAWN BY CHECKED APPROVED FRAME NO. DATE DATE 1 2 3 4 5 6 0 THIS PRINT SUPERSEDES ALL PRINTS PRIOR TO REVISION WORKS NO. OPERABLE UNIT LINE NO. Seal: 1 2 3 4 5 6 7 8 J DATE Title: SUBJECT INDEX BURBANK, CA 91504 2890 WEST EMPIRE AVENUE PPG AEROSPACE (724) 285-4761 (724) 285-6815 400 Morgan Center 101 East Diamond Street Butler, PA 16001-5923 www.stantec.com Tel: Fax: Stantec Architecture Inc. 2017.08.04 1 PACKAGE 2 FOX PROPERTY - PHASE 2

Transcript of C:TempF-001 Fox 218011155 - Chalmers Construction...

LIST OF DRAWINGS

F-001

NO. DRAWING TITLE

ABV

AD

AFF

ALT.

ARCH.

BSC

CAP.

ABOVE

ABOVE FINISHED FLOOR

ALTERNATE

ARCHITECTURAL

BUILDING

CAPACITY

CLG

CO.

COL.

COMB.

CONC.

CONN.

CONST.

CONT.

CEILING

CLEANOUT

COLUMN

COMBINATION

CONCRETE

CONNECTION

CONSTRUCTION

CONTINUOUS

DET.

DIA.

DIM.

DN.

DWG.

DWH

E.C.

ELEV.

EM. GEN.

ENCL.

EQUIP.

EWC

ELECTRICAL CONTRACTOR

EMERGENCY GENERATOR

ENCLOSURE

EQUIPMENT

ELECTRIC WATER COOLER

DETAIL

DIAMETER

DIMENSION

DOWN

DRAWING

DOMESTIC WATER HEATER

EXIST.

EXP.

F

FAI

FD

FHR

FIN.

FIXT.

FLR

FAHRENHEIT

FRESH AIR INLET

FLOOR DRAIN

FIRE HOSE RACK

FINISH

FIXTURE

FLEXIBLE

FLOOR

ID

INSUL.

INV.

JC

LAV.

LF

INSIDE DIAMETER

INSULATION

INVERT

JANITOR CLOSET

LAVATORY

LINEAL FOOT

LTG.

MB

MECH.

MFR.

MTD.

MTL.

N/A

NIC

NOT APPLICABLE

NOT IN CONTRACT

METAL

MOUNTED

MANUFACTURER

MECHANICAL

MOP BASIN

LIGHTING

NOM.

NTS

OC

OD

OH OVERHEAD

OUTSIDE DIAMETER

ON CENTER

NOT TO SCALE

NOMINAL

P.C.

PRESS.

PSI

REV.

RM.

SCHED.

SECT.

SF

SIM.

SPEC.

S/STL STAINLESS STEEL

SPECIFICATION

SIMILAR

SQUARE FOOT

SECTION

SCHEDULE

ROOM

REVISION

PRESSURE

STL.

STOR.

STP

STRUCT.

SUSP.

TEMP.

U

VERT. VERTICAL

TEMPERATURE

URINAL

SUSPENDED

STRUCTURAL

STANDPIPE

STORAGE

STEEL

VOL.

VTR

WC

WH

WEIGHT

WATER HEATER

WATER CLOSET

VENT THROUGH ROOF

VOLUME

EXISTING

EXPANSION

FIRE HOSE CONNECTION

S SINK

AREA DRAIN

SH SHOWER

FP

FPM

FPS

GA.

GAL

G.C.

GPH

GPM

HEO

HP

FIRE PROTECTION

FEET PER MINUTE

FEET PER SECOND

FOOT (FEET)

GAUGE

GALLONS

GENERAL CONTRACTOR

GALLONS PER HOUR

GALLONS PER MINUTE

HORSEPOWER

FD FLOOR DRAIN

HB HOSE BIBB

CONTRACTOR

PLUMBING

SQUARE INCH

POUNDS PER

GO LAB FUEL GAS OUTLET

HAOCOMPRESSED AIR OUTLET

LABORATORY HIGH PRESSURE

WT

FT

FLEXBLDG

HGT HEIGHT

LABORATORY HELIUM GAS OUTLET

LAO

COMPRESSED AIR OUTLET

LABORATORY LOW PRESSURE

LVO LABORATORY VACUUM OUTLET

NO NITROGEN GAS OUTLET

SQ FT SQUARE FEET

BTM BOTTOM

BIO SAFETY CABINET

PD PLANTER DRAIN

BWV BACKWATER VALVE

AM. ARGON MANIFOLD

ETM ETHANE MANIFOLD

FM FLOURINE MANIFOLD

HM HELIUM MANIFOLD

NM. NITROGEN MANIFOLD

PM. PROPANE MANIFOLD

LEGEND OF SYMBOLS ABBREVIATIONS

NOTE: SOME ABBREVIATIONS HAVE NOT BEEN USED ON THIS PROJECT

SCW SOFTENED WATER

ELEVATION

DATEDD SUBMISSION CD SUBMISSION

TP

M FLOW METER

P201

B2

REVISION INDICATOR2

HB WALL HYDRANT

C.0. RISER WITH WALL CLEAN OUT

FLOOR CLEAN OUTC.0.

ON THE SAME PAGE)

(REFERS TO NOTES

KEYNOTE INDICATOR

PRESSURE/TEMPERATURE

TEST PLUG

TEMPERATURE & PRESSURE

RELIEF VALVE

(section B2 on dwg. P201)

PIPE RISER INDICATOR

(Riser LCW-1, Drawing P301)

2

DETAIL INDICATORXXXX

XXXX

1A

PIPE TURNED UP

PIPE TURNED DOWN

CAP

STRAINER

PRESSURE GAUGE

THERMOMETER

UNION

BALL VALVE

PUMP

LCW-1

P301

PIPE SIZE TAGGING

(ie. First Floor Pipe Group A)

EX CW

RX CW

(i.e. EX CW = Existing Cold Water)

EXISTING PIPING TO REMAIN

(i.e. RX CW - Remove Existing Cold Water)

REMOVE EXISTING PIPING

DESIGNATES POINT OF CONNECTION

DESIGNATES POINT OF DEMOLITION

CLEAN OUTC.0.

WATER HAMMER ARRESTOR

TEE TURNED DOWN

TEE TURNED UP

GAS COCK

CALIBRATED BALANCING VALVE

SWING CHECK VALVE

WC

1 (type WC, number 1)

BACKFLOW PREVENTER

BACKWATER VALVE

OS & Y GATE VALVE

FIXTURE / EQUIPMENT TAG

ROOF DRAIN / EMERGENCY ROOF DRAIN

FLOOR DRAIN

AREA DRAIN / DECK DRAIN

NOTE: SOME SYMBOLS HAVE NOT BEEN USED ON THIS PROJECT

PRESSURE REDUCING VALVE AND GAUGE

BUTTERFLY VALVE

SSOLENOID VALVE

REVIEW DATE

AREA NOT IN SCOPE

PAF PRE-ACTION FIRE PIPE

CD SUBMISSIONDATE DATE

CD SUBMISSION

F-001

FIRE PROTECTION COVER SHEET

FIRE PROTECTION COVER SHEET

F-201

1.

2.

3.

4.

5.

6.

7.

8.

13.

12.

11.

10.

9.

SEALERS) DAMAGED DURING THE CONSTRUCTION SHALL BE REPLACED AT THE COST OF THE CONTRACTOR AT FAULT.

OR MATERIALS STORED ON FLOORS, AND IN AREA WHERE CONSTRUCTION MAY DAMAGE THE FLOOR SURFACES. BUILDING SURFACES (INCLUDING

PROTECT BUILDING SURFACES FROM DAMAGE DURING THE CONSTRUCTION PERIOD. PROVIDE PLYWOOD OR SIMILAR MATERIAL UNDER EQUIPMENT

EXPERTISE NECESSARY TO INCLUDE NECESSARY ACCESSORIES.

THESE FIRE PROTECTION DOCUMENTS MAY NOT EXPLICITLY DISCLOSE FINAL DETAILS; HOWEVER, FIRE PROTECTION CONTRACTOR SHALL HAVE THE

PROTECTION WORK REQUIRED. THEREFORE, IT SHOULD BE OBVIOUS TO ANY PRUDENT FIRE PROTECTION CONTRACTOR WITH EXPERIENCE THAT

FIRE PROTECTION CONTRACTOR SHALL HAVE SUFFICIENT EXPERTISE IN THIS TYPE OF CONSTRUCTION TO REALIZE THE EXTENT OF THE FIRE

PROVIDE ITEMS THAT MAY BE REQUIRED TO MEET THE CONDITIONS AT THE BUILDING.

MANNER THAT INTERFERENCES BETWEEN PIPES, CONDUIT, DUCTS, EQUIPMENT, ARCHITECTURAL AND STRUCTURAL FEATURES ARE AVOIDED.

REQUIRED TO MAKE A COMPLETE OPERATING SYSTEM. CAREFULLY INVESTIGATE CONDITIONS AFFECTING WORK AND INSTALL WORK IN SUCH A

BECAUSE OF THE SCALE OF THE DRAWINGS; IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, FITTINGS, VALVES, OR SIMILAR ITEMS WHICH MAY BE

PROTECTION WORK.

DIAGRAMMATIC AND INDICATE ONLY THE GENERAL ARRANGEMENT OF THE ITEMS COMPRISING THE SEVERAL SYSTEMS INCLUDED IN THE FIRE

THE PRIMARY CONTRACT REQUIREMENTS OF PROVIDING COMPLETE FIRE PROTECTION SYSTEMS. THE FIRE PROTECTION DRAWINGS ARE

THE DRAWINGS AND SPECIFICATIONS ARE PRESENTED TO DEFINE SPECIFIC FIRE PROTECTION SYSTEM REQUIREMENTS AND SERVE TO EXPAND ON

SHALL CONFORM WITH ACCEPTED TRADE PRACTICES, LOCAL CODES, AND GOVERNING AUTHORITIES.

DRAWINGS. ITEMS OR WORK NOT SHOWN OR SPECIFIED, BUT REQUIRED FOR A COMPLETE FIRE PROTECTION SYSTEM, SHALL BE PROVIDED AND

PROJECT. THE FIRE PROTECTION SYSTEM SHALL CONFORM TO THE DETAILS STATED IN THE SPECIFICATIONS AND SHOWN ON THE FIRE PROTECTION

INTENT OF THE FIRE PROTECTION DRAWINGS AND SPECIFICATIONS ARE TO PROVIDE A COMPLETE FIRE PROTECTION SYSTEM FOR THE PROPOSED

REQUIREMENTS.

FIRE PROTECTION PIPING, COMPONENTS, AND APPURTENANCES LOCATED IN STAIRWELLS SHALL BE PROVIDED TO MAINTAIN EGRESS WIDTH

FIRE PROTECTION CONTRACTOR SHALL PROVIDE ALTERNATE SOLUTION.

APPROVAL PRIOR TO ANY CUTTING OR CORING. IF THE STRUCTURAL ENGINEER DOES NOT APPROVE SIZE OR LOCATION OF BEAM PENETRATION,

LOCATION SHALL BE DETERMINED BY THE FIRE PROTECTION CONTRACTOR AND SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW AND

COORDINATE FIRE PROTECTION PIPE INSTALLATION WITH BUILDING STRUCTURE. WHEN BEAM PENETRATIONS ARE REQUIRED, THE EXACT SIZE AND

AND SIZING SHALL BE DETERMINED BY THE FIRE PROTECTION CONTRACTOR.

FIRE PROTECTION PIPING INDICATED ON DRAWINGS IS SHOWN IN APPROXIMATE LOCATIONS AND SIZED FOR REFERENCE ONLY. EXACT LOCATION

CONFIGURATION.

FIRE PROTECTION PIPING SHALL BE COORDINATED WITH THE ARCHITECT AND HYDRAULIC CALCULATIONS BASED ON APPROVED SPRINKLER PIPING

THIS MAY RESULT IN THE QUANTITY OF SPRINKLERS BEING GREATER THAN WHAT IS REQUIRED BY NFPA.

FIRE PROTECTION CONTRACTOR SHALL PROVIDE SPRINKLERS AND APPURTENANCES BASED ON ARCHITECTURAL FEATURES AND COMPONENTS.

PROVIDE SPRINKLER PROTECTION ABOVE AND BELOW ALL OBSTRUCTIONS CREATED BY OTHER DISCIPLINES.

SPACE.

PIPING SHALL NOT BE LOCATED IN ANY ELECTRICAL ROOMS, CLOSETS, OR TELE / COMMUNICATION ROOMS UNLESS THOSE PIPES SERVE ONLY THAT

COORDINATE WORK WITH WORK SHOWN ON OTHER TRADES DRAWINGS.

21.

20.

19.

18.

17.

16.

15.

14.

FIRE PROTECTION GENERAL NOTES

FIRE PROTECTION WATER PIPE

WET SPRINKLER PIPESPR

F

UPRIGHT SPRINKLER

CONCEALED PENDENT SPRINKLER

DRY UPRIGHT SPRINKLERD

HT HIGH TEMPERATURE UPRIGHT SPRINKLER

PENDANT SPRINKLER

SIDEWALL SPRINKLER

EARTH

UNDISTURBED

PLAN

2.5'x 2.5' MIN

BEARIN

G FAC

E

EXCAVATED TRENCH WIDTH

BACKFILL

FINAL

78"

MINIM

UM

PIPING

FIRE

12" MIN

12" MAX

6" MIN -

BEDDING

BACKFILL

INITIAL

GRADE

FINAL

2.5'x 2.5' MIN

BEARIN

G F

ACE

GRADE

ELEVATION

FOOTER

BUILDING WALL

THRUST BLOCK

THRUST BLOCK

CEILING

SPRINKLER ARM-OVER PIPINGOR CROSS MAINSPRINKLER BRANCH

1" X 1/2" REDUCER

OF CEILING TILE.SPRINKLER IN CENTERCONCEALED

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

CEILING OBSTRUCTION48" OR LARGER

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

SPRINKLER ARM-OVER PIPING

UPRIGHT SPRINKLER, PIPING, ANDAPPURTENACES PROVIDED INACCORDANCE WITH NFPA 13

SPRINKLER BRANCHOR CROSS MAIN

MAIN

WATER

PLU

MBIN

G C

ON

TR

AC

TO

R

POIN

T O

F C

ON

NE

CTIO

N B

Y

BY W

ATE

R

AU

TH

ORIT

Y

CLEARANCE

30" MAX.

12" MIN. TO

GRADESIDEWALK

STREET

SOIL

UNDISTURBED

THRUST BLOCK THRUST BLOCK

12"

12"

HORIZONTAL CLEARANCE LINE

HORIZONTAL CLEARANCE LINE

(TYPICAL)

TEST COCK

TO FIRE HYDRANT

TO BAS

TAMPER SWITCH

AUTHORITY)

(BY WATER

FIRE WATER VAULT

DEPARTMENT CONNECTION

TO FREE STANDING FIRE

CHECK VALVE

PRESSURE GAUGE

PRESSURE GAUGE

WITH METERED BYPASS

BACKFLOW PREVENTER

GATE VALVE

NTS

1 THRUST BLOCK DETAILFP-001 NTS

2

FP-001

UNDERGROUND INSTALLATION OF FIRE PIPE

SYSTEM NO. W-L-5096

SECTION A-A

F RATINGS - 1 AND 2 HR (SEE ITEM 1 AND 3)

T RATINGS - 0,1/2 AND 1 HR (SEE ITEMS 1, 3 AND 4)

3 ONE METALLIC PIPE OR TUBING SHALL BE PROVIDED CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP

SYSTEM. PIPE OR TUBE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.

4 VOID OR CAVITY - SEALANT SHALL BE PROVIDED WITH A MINIMUM 5/8 INCH OR THICKNESS OF FILL MATERIAL APPLIED WITHIN

THE ANNULUS, FLUSH WITH BOTH SURFACES OF SLEEVE. FOR AT POINT CONTACT AN ADDITIONAL 1/2 INCH BEAD OF SEALANT

SHALL BE PROVIDED TO THE INSULATED PIPE/ WALL INTERFACE.

1 WALL ASSEMBLY - REFER TO ARCHITECTURAL DRAWINGS FOR RATED WALL ASSEMBLY LOCATIONS AND CONSTRUCTIONS.

2 PIPE SLEEVE - PROVIDE PIPE SLEEVE THROUGH CIRCULAR CORE DRILLED OPENING IN WALL. LENGTH OF SLEEVE BE EQUAL

TO THICKNESS OF WALL.

2

3

4 1

4

NTS

3

FP-001

THROUGH RATED WALL

UN-INSULATED PIPE PENETRATION

NTS

5

FP-001 NTS

6

FP-001

SPRINKLER ARM-OVER DETAIL SPRINKLER UNDER MECHANICAL OBSTRUCTIONS DETAIL

NTS

7

FP-001

FIRE WATER SERVICE ENTRANCE DETAIL

IN BOTH DIRECTIONS

SPRINKLER TO BE ALIGNED

TILE

24" SQUARE

CL

CL

NTS

5

FP-001

SPRINKLER LOCATION IN CEILING TILES

TAMPER SWITCH

FLOW SWITCH

12" MIN.

12" MIN.

PROVIDE TEMPORARY FIRE PROTECTION FOR USE DURING CONSTRUCTION IN ACCORDANCE WITH NFPA.

JURISDICTION REQUIREMENTS.

PROVIDE SWAY BRACING AND SEISMIC BRACING FOR ALL FIRE PROTECTION PIPING IN COMPLIANCE WITH NFPA - 13 AND AUTHORITY HAVING

BE COORDINATED IN THE FIELD BASED ON REFLECTED CEILING PLANS AND FM GLOBAL SPACING REQUIREMENTS.

SHOP DRAWINGS SHALL BE PREPARED AND SUBMITTED IN ACCORDANCE WITH FM GLOBAL SPACING REQUIREMENTS. SPRINKLER LOCATIONS SHALL

SPRINKLER LOCATIONS SHOWN ARE THE MINIMUM REQUIRED FOR THE PROJECT TO MEET ARCHITECTURAL REQUIREMENTS. SPRINKLER SYSTEM

INSTALLATION.

COORDINATE THE EXACT LOCATION OF SPRINKLERS, COMPONENTS, AND DEVICES WITH OTHER TRADES DRAWINGS PRIOR TO ROUGH - IN AND

RESPONSIBLE FOR ANY REQUIRED CROSS REFERENCE BETWEEN THESE DRAWINGS AND SPECIFICATIONS AND OTHER DISCIPLINES.

PIPING AND VALVE IDENTIFICATION SHALL BE IN ACCORDANCE WITH OWNER'S IDENTIFICATION SYSTEM AND RELEVANT CODES. CONTRACTORS ARE

PROVIDE PIPING SO THAT VALVES ARE ACCESSIBLE AND STEMS ARE EXTENDED VERTICALLY UP.

EACH FLOOR MAIN TAKE OFF FROM RISER.

PROVIDE SHUT-OFF VALVES WITH TAMPER SWITCHES AT EACH FLOOR SUPPLY. PROVIDE FLOOR CONTROL TEST AND DRAIN VALVE ASSEMBLIES ON

PROVIDE AUXILIARY DRAINS FOR TRAPPED SECTIONS OF PIPING.

PROVIDE FIRE PROTECTION PIPING WITH POSITIVE GRADE TO DRAIN. PIPING SHALL BE GRADED TO DRAIN BACK TO THE SUPPLY PIPING BY GRAVITY.

FLOW SWITCH

FIRST FLOOR AND ROOF FIRE PROTECITON PLANS

OS & Y VALVE ALARM CKECK VALVE

DISCHARGE TO GRADE

OS & Y VALVE

CAH

CLG

8/4/17

8/4/17

Revisions

No. Date Description

A B C D E F G H

1

2

3

4

5

6

The Contractor shall verify and be responsible for all dimensions. DO NOT scale the drawing - any errors

or omissions shall be reported to Stantec without delay.

The Copyrights to all designs and drawings are the property of Stantec. Reproduction or use for any

purpose other than that authorized by Stantec is forbidden.

Copyright Reserved

Drawing

No.

Scale

7

I

8

CONFIDENTIAL INFORMATION: The information set forth hereon constitutes confidential proprietary technology of PPG INDUSTRIES, Inc. In

consideration of the opportunity to supply goods or services to or on behalf of PPG requiring the use of said information, the recipient of this document agrees: (1)

not to copy or reproduce said document in whole or in part without prior written authorization by PPG; (2) to return said document upon demand by PPG; (3) to

make no use of said information other than for supplying goods or services in connection with the installation shown in the title without prior written authorization by

PPG; (4) not to disclose said document or the information it includes to any third party.

DISCIPLINE ITEM NO.

DO NOT SCALE THIS PRINT

DRAWN BY

CHECKED

APPROVED

FRAME NO.

DATE

DATE

1 2 3 4 5 60

THIS PRINT SUPERSEDES ALL PRINTS

PRIOR TO REVISION

WORKS NO. OPERABLE UNITLINE NO.

Seal:

1

2

3

4

5

6

7

8

J

DATE

Title:

SUBJECT

INDEX

BURBANK, CA 91504

2890 WEST EMPIRE AVENUE

PPG AEROSPACE

(724) 285-4761

(724) 285-6815

400 Morgan Center

101 East Diamond Street

Butler, PA 16001-5923

www.stantec.com

Tel:

Fax:

Stantec Architecture Inc.

2017.08.041 PACKAGE 2

FOX PROPERTY - PHASE 2