    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page1

    Box 746509, Arvada, Colorado 80006 USA

    (303) 953-3250 phone (303) 953-3251 fax

    www.canamsteelbuildings.com

    SpecificationGuideNotice:Duetoongoingproductimprovement,allinformationhereinissubjecttochangewithoutnotice.

    CONTENTS

    Section1:

    Section2:

    Section3:

    Section4:

    Section5:

    Section6:

    Section7:

    Section8:

    Section9

    Section10:

    Section11:

    General

    StructuralDesign

    AnchorageandFoundations

    Submittals

    StructuralFraming

    RoofCovering PBRpanel

    RoofCovering SSRpanel,Trapezoidal

    WallCovering

    Accessories

    StandardServiceabilityCriteria

    Execution

    Section1. General

    1.1. Scope

    1.1.1. Thesespecificationsareanoutlineofperformancetoensure thatthearchitect,engineer,builder,buyerand/orbuyersagentunderstandsthebasisfordesign,manufacture,andapplicationofallCanamSteelBuildingCorporationmetalbuildingsystems.

    1.1.2. Duetoongoingproductimprovement,allinformationhereinissubjecttochangewithoutnotice.

    1.1.3

    The

    building

    shall

    consist

    of

    all

    primary

    and

    secondary

    structural

    members,

    connection

    bolts, canopies, roof extensions, sheeting, trim, flashing, doors, fasteners, gutters,downspouts,andothermiscellaneousitemsandaccessoriesasspecified,shown,orcalledforinCanamSteelBuildingCorporations'orderdocumentsordrawings. Refertothe2006Edition of the Metal Building Systems Manual section entitled Common IndustryPracticesforthestandards inwhichthisguidewillbeused. CSBCwillnotprovide itemsnotspecificallycalledforintheCSBCorderdocuments.

    1.2. DimensionalTerminology

    1.2.1. Width The building width shall be the distance from outside face of sidewall girt tooutsidefaceofsidewallgirt(steellinetosteelline).

    1.2.2.

    Length

    The

    building

    length

    shall

    be

    the

    distance

    from

    outside

    face

    of

    endwall

    girt

    to

    outsidefaceofendwallgirt(steellinetosteelline).

    1.2.3. EaveHeightThebuildingeaveheightshallbethedistancefromfinishedfloortotopofeave strut or eave purlin at the steel line. For buildings which are to be placed atopconcrete curbs or stem walls, or where column base plates are to be recessed belowfinishedfloor,eaveheightshallstillbemeasuredfromthefinishedfloorelevation.

    1.2.4. BaySpacingThebayspacingshallbethedistancefromcenterlineofprimaryframetocenterlineofprimaryframeforinteriorbays. Endbayspacingshallbethedistancefromoutsidefaceofendwallgirt(steelline)tocenterlineoffirstinteriorprimaryframe.

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    2/14

    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page2

    1.2.5. ModuleSpacingThemodulespacingonmultispanbuildingsshallbethedistancefromoutsidefaceofsidewallgirt(steelline)tocenterlineoffirstinteriorcolumn. Itisalsothedistance from centerline of interior column to centerline of interior column for interiorspans.

    1.2.6. RoofSlopeTheroofslopeshallbebasedonanorderspecifiedverticalriseforeach12"horizontalrununlessotherwisestated.

    1.3. BuildingTypes

    1.3.1.

    Solid

    web

    framing

    consists

    of

    members

    fabricated

    from

    shopwelded,

    hot

    rolled

    steel

    sheetsorplatesandhotrolledflatbars.

    1.3.1.1. Rigid Frame (RF) buildings are clearspan buildings with tapered sidewall columns. Theyarecommonlyusedforclearspansfrom30feettoover300feet(9.14mto91.4m)wide.

    1.3.1.2. Tapered Beam (TB) buildings are clearspan buildings with straight sidewall columns andhorizontalbottomflangerafters. TBbuildingsaresuitableforsmallerclearspanbuildingsfrom20feetto60feet(6.1mto18.29m)wide.

    1.3.1.3. RigidFramewithinteriorcolumns(RFMS)buildingsaremultispanbuildingswithinteriorcolumns. RFMSbuildingsprovideaneconomicaladvantageonbuildingsfrom80feettoover500feet(24.38mto152.4m)wide.

    1.3.1.4.

    Singleslope

    clearspan

    (SS)

    or

    multi

    span

    (SS

    MS)

    buildings

    are

    available

    in

    width

    ranges

    similartoRFandRFMSaspreviouslylisted. Roofslopeisinasingledirectiontothelowsidewall.

    1.3.1.5. Leanto (LT) or Leanto with interior columns (LTMS) buildings are similar to the SSbuildingbutwiththehighsidecolumnbeingeliminated. TheLTrafterissupportedbytheparentbuildingframe,sidewall,orendwallcolumn.

    Section2. StructuralDesign

    2.1. DesignCriteria

    2.1.1. All structural steel sections and welded plate members shall be designed in accordance

    with

    the

    Manual

    of

    Steel

    Construction,

    13th

    Edition,

    American

    Institute

    of

    Steel

    Construction, Chicago, IL; and the latest edition of the Structural Welding Code Steel,ANSI/AWSD1.1,AmericanWeldingSociety

    2.1.2. All lightgagecoldformedstructuralmembersandexteriorcoveringshallbedesigned inaccordancewiththeColdFormedSteelDesignManual,2002Edition,American IronandSteelInstitute. Allstandardsfortheweldingofcoldformedmembersarebaseduponthelatest edition of the Structural Welding Code Sheet Steel, ANSI/AWS D1.3, AmericanWeldingSociety.

    2.1.3. Theprimaryandsecondaryframingandcoveringshallbedesignedforallapplicableloadsandcombinationsofloadsassetforthin:

    2.1.3.1. Thespecifiedgoverningbuildingcodefortheorderunderconsideration. Thismaybeany

    ofthe

    standard

    model

    building

    codes

    currently

    published,

    such

    as:

    the

    International

    Code

    Councils International Building Code (IBC) or the National Research Council CanadasNational Building Code (NBC). Additionally, many orders may be within states,municipalitiesorprovincesthathavetheirownamendmentstothegoverningmodelcodeorthathavetheirownindependentcode. Inthiscase,loads,deflectioncriteria,andloadcombinations will be determined in accordance with this governing local code.Specificationof loadsandcodesanddesignresponsibilityshallbeasstated inArticle IV,Common Industry Practices,of the 2006Edition of the MetalBuildingSystems ManualfromMBMA. Thesecommon industrypracticeswillapplyregardlessofthestate, local,provinceormodelcodechosen.

    2.1.3.2. Inlieuofappropriatestate,local,province ormodelcodes,ArticleI.,LoadApplication of

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    3/14

    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page3

    the 2006 Edition of the Metal Building Systems Manual from MBMA shall be used todetermineloadsandloadcombinations.

    2.1.3.3. Design loadsshallnotbe lessthanthosespecified inArticle IXentitled Wind,SnowandRainDataByCounty,oftheMetalBuildingSystemsManual,MBMA,2006Edition,ifthereisnotacontrollingstateorlocalcode. IfthecontrollingstateorlocalcodespecifiesvaluesthatarelessthanthosefoundinArticleIX,thestateorlocalcodetakesprecedence.

    2.1.3.4. Theappropriategoverningcodeshallbespecifiedatthetimeofthebuildingquotation.

    2.2.

    EngineeringCertifications

    2.2.1. Allbuildingsshallbedesignedbyorunderthedirectsupervisionofregisteredprofessionalengineers in accordance with the information specified to Canam Steel BuildingCorporation intheorderdocumentation incompliancewithArticleIV,Common IndustryPractices,ofthe2006EditionoftheMBMAMetalBuildingSystemsManual. ThesealingengineerisnottheEngineerofRecordfortheprojectandcannotbeconstruedassuch.

    2.2.2. Designcalculations,certifiedbyaprofessionalengineer,maybepurchasedwiththeorder,ifrequested.

    2.2.3. A letter of certification, certified by a professional engineer, may be supplied with thebuildingquoteproposal, ifrequested. A letterofcertificationshallbeprovidedwiththeorderatthetimetheanchorrodplansarecomplete.

    2.2.4. Allpermitdrawingsshallbearthesealed ofaregisteredprofessionalengineerlicensedtopractice inthestateorprovincewherethebuilding istobe located. Approvaldrawingswillnotbesealed. Erectiondrawingswillbesealedonly ifspecificallyrequestedby thecustomer.

    2.3. AuxiliaryDesignLoads

    2.3.1. Crane and impact loads shall be applied in accordance with the Manual of SteelConstruction,13thEdition,AmericanInstituteofSteelConstruction,Chicago,IL,ArticleII,of the 2006 Edition of the MBMA Metal Building Systems Manual; and the appropriatecodespecifiedintheCSBCorderdocuments.

    2.3.2.

    Seismic

    loads,

    for

    buildings

    in

    areas

    subject

    to

    earthquakes,

    shall

    be

    derived

    using

    the

    proceduresetforthbyappropriatebuildingcodesspecifiedintheCSBCorderdocuments.

    2.4. LoadCombinations

    2.4.1. Load combinations shall be per the appropriate building code. In lieu of any specifiedcode,loadsshallbecombinedperArticleI,Section1.3.7ofthe2006EditionoftheMBMAMetalBuildingSystemsManual.

    Section3. AnchorageandFoundations

    3.1. AnchorRods

    3.1.1. Anchorrodsandbaseplatesshallbedesigned toresistallcolumnreactions. Sizesused

    shall

    be

    as

    those

    shown

    on

    Manufacturers

    drawings.

    The

    length

    and

    embedmentanchorageofallanchorrodsshallbetheresponsibilityofthefoundationengineer.

    3.1.2. Anchor rodsshall not be suppliedby Canam Steel BuildingCorporation andshallbe theresponsibilityofthecontractororerectortofurnish,unlessspecificallynotedotherwiseintheCSBCorderdocuments.

    3.1.3. Leveling plates shall not be supplied by Canam Steel Building Corporation unlessspecificallycalledforintheCSBCorderdocuments.

    3.2. Foundations

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    4/14

    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page4

    3.2.1. Foundations shall be designed by a qualified registered professional engineer toaccommodate the local soil conditions and meet building reaction requirements inadditiontootherloadsimposedbybuildinguseoroccupancy. Itshallbetheresponsibilityof the Engineer of Record to verify that the loading criteria defined on the OrderDocumentsisadequateforthelocationoftheprojectinquestion.

    3.2.2. NeitherthefoundationdesignnorthereinforcingsteelshallbesuppliedbyCanamSteelBuildingCorporation. Itshallbetheresponsibilityofthecustomer,contractor,orerectortoobtaintheseitems.

    Section4.

    Submittals

    4.1. General

    4.1.1. Canam Steel Building Corporation shall supply on all orders three sets of anchor roddrawings and reactions. Additional sets of anchor rod drawing and reactions may bepurchasedatadditionalcost.

    4.1.2. Canam Steel Building Corporation shall supply on all orders three sets of final erectiondrawings. Additionalsetsoffinalerectionsdrawingsmaybepurchasedatadditionalcost.

    4.1.3. When called for in the order documents, Canam Steel Building Corporation shall supplythreesetsofpermitdrawingsshowingengineeringdesigndetails,criticalclearances,keyconnection details, material specifications, and lateral load resisting elements such asbracing,

    diaphragm,

    and

    shearwall

    layouts.

    4.1.4. When called for in the order documents, Canam Steel Building Corporation shall supplythree sets of approval drawings. Approval drawings shall show building layout, criticalclearances,criticaldetails,andmayincludepermitdrawinginformationifrequested. Finalfabrication will not begin until approval drawings have been returned with appropriatereleasesignaturesorappropriateinstructionhasbeengiventoCSBCtoreleasetheprojectusingaChangeOrder.

    4.1.5. CanamSteelBuildingCorporation doesnotsupplyshopfabricationdrawingsforrevieworapproval. AsbuiltdrawingsarenotprovidedbyCSBC.

    4.1.6. UnlessspecificallycalledforintheCanamSteelBuildingCorporationorderdocuments,all

    drawings

    shall

    be

    issued

    either

    electronically

    or

    on

    11

    x

    17

    paper

    stock.

    Larger

    size

    drawingsmaybeavailableatanadditionalcost.

    Section5. StructuralFraming

    5.1. General

    5.1.1. Theterms primarystructural or primaryframing shallrefertoanybuiltup,hotrolled,or coldform columns or framing systems which transfer their loads directly to thestructuresfoundation.

    5.1.2. Thetermssecondarystructural orsecondaryframing shallrefertoanycoldform,hotrolled,orbuiltuppurlins,girts,struts,bracing,orbeamswhichtransfertheir loads fromthecladdingtotheprimarystructuralmemberorframingtowhichtheyattach.

    5.1.3. Unlessotherwisespecified intheCanamSteelBuildingCorporationorderdocuments,theminimumstandarddesignthicknessofstructuralframingmembersshallbeasfollows:

    Websofweldedbuiltupmembers 0.125(3.175mm)Flangesofweldedbuiltupmembers 0.175(4.445mm)Coldformedsecondaryframingmembers 0.060(1.524mm)Cablebracing 0.250(6.35mm)/Rodbracing 0.625(15.875mm)Anglebracing 0.1875(4.762mm)

    5.1.4. All hotrolled sheet, plate, and strip steelused in webs from 0.125 to 0.175 (3.175 to4.445mm)thickshallconformtotheprovisionsofASTMA1011SSGrade55(55,000psiminimumyieldstrength). Allthicknessesgreaterthan0.175(3.175mm)shallconformto

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    5/14

    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page5

    ASTMA572Grade55(55,000ksiminimumyield).5.1.5. All hotrolled flat bars used in flanges shall conform to the provisions of ASTM A572

    Grade55,withminimumyieldof55,000psi.

    5.1.6. All wideflange, channel, and S shapes shall conform to the provisions of ASTM A36,ASTMA572orASTMA992(Wshapeonly). AlltubeandpipeshapesshallconformtoASTMA500,GradeB.

    5.1.7. Allhotrolledorcoldrolledsheetandstripsteel lessthan0.150"(3.81mm) thickusedinfabricationofcoldformedstructuralmembersshallbeofASTMA1011,Grade55(55,000

    psiminimum

    yield

    stress)

    or

    Grade

    55

    Mod

    57

    (57,000

    psi

    minimum

    yield

    stress).

    5.1.8. Cable used for diagonal bracing shall conform to ASTM A475; coating Class A, GradeExtraHighStrength7wire. ThreadedrodshallmeetASTMA529,Grade50requirements.AnglesectionsshallmeetminimumA36requirements.

    5.1.9. Structuralsteelmembersshallbesheared,formed,punched,welded,andpaintedbythemanufacturer. Allshopconnectionsshallbeweldedinconformancewithstandardsbasedupon the current edition of ANSI/AWS D1.1 referenced previously in this guide inParagraph 2.1.1. Welders and welding operators are qualified as provided in this samecode.

    5.1.10. All field connections of primary structural members shall be bolted with high strengthbolts and nuts (ASTM A325) and shall be fully tensioned unless otherwise specified.Secondary

    structural

    members

    shall

    be

    field

    bolted

    with

    ASTM

    A307

    or

    A325

    bolt

    assembliesascalledforindesign.

    5.1.11. Light gage coldformed sections shall be manufactured by roll or brakeforming. AlldimensionsshallbefabricatedtoMBMAtolerances.

    5.1.12. Allstructuralframingmembersthatarenotgalvanizedshallbegivenoneshopcoatofaredprimer. Grayprimermaybeavailableatanadditionalcostand,ifavailable,mustbecalled for in the Canam Steel Building Corporation order documents. All surfaces arecleanedof looserust, loosemillscale,andotherforeignmatterbyusing,asaminimum,thehandtoolcleaningmethodSSPCSP21priortopainting. Allpaintedsurfacesaretobereasonablyfreeofexcessivedrips,runs,sags,andcracking. ReferenceMBMA2andAISC3forintendedprimerprotection,propercare,erection,andfunctionofshopprimecoat.

    5.1.13. Allframingmembersshallhaveidentifyingmarkstoaidthe erectorintheerectionofthebuilding.

    5.2. PrimaryFramingMembers

    5.2.1. Rigid frame, sidewall columns, rafter beams, and canopy beams shall be shopwelded,builtup Ishapes. Membersshallbeofconstantdepthor tapered,havingbaseplates,necessaryclips,andspliceplatesforcompletelyfieldboltedassemblyandattachmentofsecondarymembers.

    5.2.2. RafterbeamsandendwallcolumnsshallbeeitherbuiltupIshapes,WFshapes,orrollformedCsectionsasrequiredtosatisfyloadandspanrequirements.

    5.2.3.

    Interiorcolumns

    shall

    be

    round

    pipe

    sections,

    Built

    up

    I shapes,

    hot

    rolled

    WF or

    tube

    sectionsasrequiredtosatisfyloadandorderrequirements.

    5.3. SecondaryFramingMembers

    5.3.1 PurlinsandgirtsshallberollformedZEEorCEEsectionsofadequatesizeandthicknessasdetermined by the design criteria. Purlins and girts shall be either simplespan orcontinuousmembers.

    5.3.2. Purlins for longbay building layouts shall typically consist of barjoists designed underSteelJoist Institutespecificationsfortheprescribed loads. Fieldweldingofjoistbridgingandseatsisthestandardmethodforconnectionofjoiststosupportingprimarystructural

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    6/14

    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page6

    members.5.3.3. EavestrutsshallberollformedorbrakeformedCEEsections.

    5.3.4. Windbracingshallconsistofdiagonalcable, rod,oranglebracing. Adjustment tocablebraces shall be made by an eyebolt assembly. Adjustment to rod bracing may be bythreadedassembly. Anglebracingisnotadjustableandmayrequirefinalfieldwelding.

    5.3.5. Flangebracingshallconsistofanglebracingconnectedtothewebofthepurlinorgirtandto the compression flange of the primary structural member. Flange braces shall beattachedtobarjoistsviafieldwelding.

    5.3.6. Base support for wall panels shall consist of a continuous base angle, base angle flash,basechannelorbasegirtwhichshallbesecurelyattachedtoconcretebythecontractorusingpowderactuateddrivepins,expansionanchors,orothersimilaranchorage.

    Section6. RoofCovering PBRpanel

    6.1. General

    6.1.1. MinimumrecommendedroofslopeforPBRpanelis1/2"in12".

    6.1.2. Maximumrecommendedbuildingwidthis240feet (73.15m)(gable)or120feet(36.58m)(singleslope)forzeepurlinroofs. PBRpanelshallbeusedinconjunctionwithzeeorceepurlins as supports. Joists or roof beams are not acceptable support members unless

    specificallyagreed

    to

    by

    the

    Engineering

    Manager.

    6.1.3. PBRpanelin26gaugematerialqualifiesforaUL580Class90upliftrating(Construction#161)whenfixedtoroofpurlinswhicharespacedat5'0"(1.52m)oncenterorless.

    6.1.4. PBRpanel in 26 gauge material qualifies for a FM1120 uplift rating when fixed to roofpurlinswhicharespacedat5'0"(1.52m)oncenterorless.

    6.2. PanelMaterial

    6.2.1. PBRPanelprofileshallbeprecision rollformed from26gaugesteelsheeting. 24gaugemaybeavailableatadditionalcost.

    6.2.2. Galvanized steel sheeting shall be processed in accordance with ASTM A653. Consultyour

    specific

    plant

    for

    minimum

    yield

    strength

    and

    grade

    of

    material.

    The

    galvanized

    coatingshallbe .90ozpersquarefoot(ClassG90) inaccordancewithASTMA653. ThespangleforgalvanizedpanelisbrightflatspangleinaccordancewithASTMA653.

    6.2.3. Galvalumesteelsheetingshallbealuminumzincalloycoatedsteelsheet inaccordancewith ASTM A792. Consult your specific plant for minimum yield strength and grade ofmaterial. Ithasacoatingthicknessof.55ozpersquarefoot.

    6.2.4. RoofpanelsprovidedbyCanamSteelBuildingCorporation forexterioruseareprecisionrollformed fromprepaintedG90galvanizedorGalvalumecoils. Coilsto receive finishpaintsaresubjectedtoastrenuouscleaningprocesspriortocoating. Next,thecoilsareprimercoatedandovencured. Thefinishcoat isthenappliedandmonitoredforproperovencure temperatureandcoloruniformity. Finishedmaterial issubjected tostringent

    quality

    control

    tests

    including:

    physical

    bend

    and

    impact

    resistance,

    film

    thickness,hardness, gloss, and color. This process is time tested and uses the industry proven

    modifiedSiliconizedModifiedPolyesterpaintsystem. A70%Kynar500finishisavailableatanadditionalcostuponrequest.

    6.3. PanelConfiguration

    6.3.1. PBRPanelpanelprovidesa36(915mm)netcoverageandconsistsofmajorribs1 "(32mm)deepspacedat12"(305mm)oncenterwithanextendedpurlinbearingsidelaptoallowforadditionalsidelapsupport. Minorribsreinforcetheflatareabetweenmajorribstominimizeoilcanning.

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    7/14

    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page7

    6.4. Fasteners

    6.4.1. Roofpaneltosecondary framing fastenershallbea#1214 x11/4 (32mm)selfdrillingcarbonsteelscrew,hexwasherheadwithsealingwasher. Fastenershallhavea20yearcorrosion resistant coating. Fastener shall have a painted head to match panel and/ortrimcolorwhenusedwithpaintedmaterial.

    6.4.2. Paneltopanel,flashingtoflashing,(stitch)fastenerforroofshallbea#12x3/4" (19mm)sharppointcarbonsteelscrew,hexwasherheadwithsealingwasher. Fastenershallhavea20yearcorrosionresistantcoating. Fastenershallhaveapaintedheadtomatchpanel

    and/ortrim

    color

    when

    used

    with

    painted

    materials.

    6.5. TrimandFlashing

    6.5.1. Colorcoated trimand flashingshallbe26gauge. Trimshallbeprovidedateave, ridge,rake,andwherevernecessarytoensureaproperlyconstructedbuilding,asdefinedontheCanamSteelBuildingCorporationorderdocuments.

    6.5.2. Neither counterflashing for parapet conditions nor tiein flashing to existing buildingsshallbeprovidedbyCanamSteelBuildingCorporation.

    6.5.3. All exposed trim and flashing material shall be manufactured from galvanized orGalvalumesteelstrip.

    6.5.4.

    Exterior

    gutters

    and

    gable

    flash

    shall

    be

    manufactured

    in

    20

    (6.1

    m)

    lengths

    wherever

    possible.

    6.6. Sealants

    6.6.1 Mastic for sidelaps, endlaps, and flashing shall be an isobutylene tripolymer rubberpressuresensitivetapemastic.

    6.6.2. Tapemasticforsidelapsshallbe3/32" (2.38 mm) thickX1/2"(12.7mm)wideandmasticforendlapsshallbe1/8"(3.18mm)thickX3/4"(19.05mm)wide.

    6.6.3. Tubesealantsshallbeofthenonhardeningelastomerictype. Thissealantistobeusedatalltrimandflashingendlaps.

    6.7.

    Closures

    6.7.1. Closuresshallbeclosedcellpolyethylenefoamtomatchthepanelconfiguration.

    6.7.2. Closuresshallbeprovidedattheeave endfor roof panels.

    6.8. InstallationofPanels

    6.8.1. Storage and installation of the roofing system shall be in accordance with Canam SteelBuildingCorporationsprintedinstructions.

    6.8.2. All endlaps and sidelaps on roof panels shall be sealed with a continuous row of tapemastictopreventairandwaterfrominfiltratingthebuilding.

    6.8.3. Standard maximum panel length shall be 30 (9.14 m). If required, lengthsofup to 45(13.72m)maybeprovided.

    6.8.4. Useofcuttingtoolsthatdamagethe panelfinishshallnotbeallowed.

    6.8.5. Panelsshallnotbemarkedwithanygraphiteorleadmarkers.

    6.9. Cleanup

    6.9.1. Roof surface should be cleaned daily during construction of all filings, cuttings, screws,pencilmarkings,anddebristo preventdamageduetooxidationofforeignmaterials.

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    8/14

    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page8

    6.9.2. Contractorshallthoroughlycleanallpanels,trim,andguttersofallforeignmaterialuponcompletionofconstruction.

    6.10. FieldCuttingofPanels

    6.10.1. WhenfieldcuttingormiteringPBRPanels,nonabrasivecuttingtoolssuchasnibblersorsnipsshallbeused. Abrasivecutting toolssuchasmechanicalgrinders,saws,shears,orscissors can damage the Galvalume or painted finish and create excess metal shavingsthat can corrode the panels. The use of nonapproved cutting devices may void yourmanufacturerswarranty.

    Section7. RoofCovering StandingSeamRoofSystem, Trapezoidal

    7.1. General

    7.1.1. Specifically includedarepanels,panelclips,flashing,panelsplices,ridgematerial,andallnecessaryfasteners.

    7.1.2. Minimumroofslopeis1/4"in12".

    7.1.3. Panels are rated for UL90 uplift rating UL580 when installed to roof support membersspacedaslistedinULConstructionListing#552,supportedbyeitherpurlinsorjoistswhicharespacedat5'0"(1.52m)oncenterorless.

    7.1.4.

    Panelshave

    an

    FM1

    120

    uplift

    rating

    when

    supported

    by

    either

    purlins

    or

    joists

    which

    are

    spacedat5'0"(1.52m)oncenterorless.

    7.2. PanelMaterial

    7.2.1. TrapezoidalSSRprofileshallbeprecisionrollformedfrom24gagesteel. Galvalumesteelsheeting is aluminumzinc coated steel alloy coated steel sheet with a minimum yieldstrengthof50ksiinaccordancewithASTMA792,Grade50. Ithasacoatingthicknessof.55oz.persquarefoot.

    7.2.2. RoofpanelsprovidedbyCanamSteelBuildingCorporation forexterioruseareprecisionrollformedfromprepaintedGalvalumecoils. Coilstoreceivefinishpaintsaresubjectedto a strenuous cleaning process prior to coating. Next, the coils are prime coated andoven cured. The finish coat is then applied and monitored for proper ovencuretemperature

    and

    color

    uniformity.

    Finished

    material

    is

    subjected

    to

    stringent

    quality

    control tests including: physical bend and impact resistance, film thickness, hardness,gloss, and color. This process is time tested and uses the industry proven modifiedSiliconized Modified Polyester paint system. A 70% Kynar 500 finish is available atadditional cost upon request. Trapezoidal SSR roof accessories (end dams, cinch straps,gutterbrackets)areprovidedasunpainted.

    7.2.3. Panelshallbefactorypunchedandnotchedatridge,highside,andlaplocations.

    7.2.4. PanelsidelapsshallhavefactoryappliednonskinningButylmastic.

    7.3. PanelConfiguration

    7.3.1.

    Panelsshall

    have

    3

    (76.2

    mm)

    trapezoidal

    ribs

    spaced

    24

    (609.6

    mm)

    on

    center.

    Minor

    ribsreinforcetheflatareabetweenmajorribstominimizeoilcanning.

    7.4. PanelClip&Fasteners

    7.4.1. Fixedpanelclipsshallonlybeusedwithpanelrunsof lessthan120(36.58m). Floatingpanelclipsshallbeusedup toa250 (76.2m)panelrunandshallbeselfcenteringandallow forupto11/2 (38.1mm)expansionand/orcontractionoftotalmovement fromthe centered position. The clip design shall insure that movement does not occurbetweenthepanelandclip.

    7.4.2. Thepanelclipsshallhavefactoryappliedmastictoinsureaweathertightinstallation.

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    9/14

    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page9

    7.4.3. Eachclipshallbeattachedtothejoistorpurlinwithtwofasteners. Sizeandtypewillberecommended by Canam Steel Building Corporation for the specific application. ClipfastenersforretrofitapplicationsarenotbyCSBCandmustbespecifiedbytheBuyerorBuyersAgent.

    7.4.4. Panelendlapfastenersshallbea#17 x11/4"(32mm) selftappingcarbonsteelscrew,hexwasherhead. Fastenershallhavea20yearcorrosionresistantcoating.

    7.5. TrimandFlashing

    7.5.1.

    Colorcoated

    trim

    and

    flashing

    shall

    be

    26 gauge.

    Trim

    shall

    be

    provided

    at

    eave,

    ridge,

    rake,andwherenecessarytoensureaproperlyconstructedbuilding.

    7.5.2. Higheaveflashingandflashingparalleltotheroofpanelsshallaccommodatethethermalexpansion and contraction of the roof without damage to the roof panels or flashing.CounterflashingforparapetconditionsandflashtoexistingbuildingsarenotprovidedbyCanamSteelBuildingCorporation.

    7.5.3. All exposed trim and flashing material shall be manufactured from galvanized orGalvalumesteelstrip.

    7.5.4. Exterior gutters and gable flash shall typically be manufactured in 20' (6.07 m) lengthswherepossible.

    7.6.

    Installation

    7.6.1. Storage and installation of the roofing system shall be in accordance with Canam SteelBuildingCorporationsprintedinstructions.

    7.6.2. TheTrapezoidalSSRhandcrimper isspeciallydesigned forusewith theTrapezoidalSSRroof. Undernocircumstancesshallthehandcrimperbeusedonanyothermanufacturersroofsystem. Additionally,undernocircumstances isanothermanufacturerscrimpertobe used on theTrapezoidalSSR roofeven ifpanelsappear to be the same. Permanentdamagetotheseamand/orthepanelfinishmayoccuriftheTrapezoidalSSRcrimpingtoolisnotusedandshallvoidallwarranties.

    7.6.3. Thepanelspliceshallhavea0.060galvanizedsteelbackupplateanda0.090aluminum

    cinch

    strap.

    7.6.4. Thebackupplateandcinchstrapshallbefactorypunchedtoensureproperfit.

    7.6.5. Panelspliceshallbesealedwith tapemastic.

    7.6.6. Standardmaximumpanellengthshallbe550 (16.76m).

    7.6.7. Theuseofcuttingtoolsthatdamagethepanelfinishshallnotbeallowed.

    7.6.8. Panelsshallnotbemarkedwithanygraphiteorlead markers.

    7.7. Cleanup

    7.7.1.

    Roof

    surface

    should

    be

    cleaned

    daily

    during

    construction

    of

    all

    filings,

    cuttings,

    screws,

    pencilmarkings,anddebristopreventdamageduetooxidationofforeignmaterials.

    7.7.2. Contractorshallthoroughlyclean allpanels,trim,andguttersofallforeignmaterialuponcompletionofconstruction.

    7.8. Maintenance

    7.8.1. Theownershallkeeptherooffreeandcleanofdebrisandcorrosivematerialsatalltimes.

    7.8.2. Guttersanddownspoutsshallbecleanedperiodicallyandkeptfreeflowingatalltimes.

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    10/14

    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page10

    7.8.3. Flashingandsheetinginterfacesshallbeinspectedyearlytoensureproperconnectionandwatertightness.

    7.8.4. Endlaps,eaves, ridges,curbs, translucentpanels,andother interfacesshallbe inspectedandmaintainedyearly. Normaladjustmentsortighteningoffastenersmayberequired.

    7.8.5. Theuseoftarandothertopicalappliedproductsshallnotbepermittedunlessspecifiedbythemanufacturer.

    7.8.6. Copper,leadflashing,exposediron,ordebrisshallnotbepermittedontheroof.

    7.8.7. Pipes to and supports for roofsupported units shall be of a noncorrosive or rustfreematerial. Field painting of pipes and supports may be required to resist corrosion.Condensationfromrooftopunitsshallbepipedtointeriororexteriorlocations. Damageduetocondensatewaterisnotcoveredundermanufacturerswarranty.

    7.9. ErectionSequence

    7.9.1. TheTrapezoidalSSRroofsystemisdesignedtobeerectedstartingfromeitherendofthebuilding. Insomecases,duetothebuilding layout, itmayberequiredtostarterectionfromaspecifiedend. Insuchcases,itwillbenotedassuchontheerectiondrawings.

    7.9.2. Sequencingofsteelshallbeclearlymarked ontheorderdocumentsatthetimeoforderentry.

    7.10. CoordinationwithOtherTrades

    7.10.1 SupportsfortheTrapezoidalSSRroofsystem shallbeprovidedandarerequiredasshowninthedrawingsandasnoted inthesespecifications. Allnecessaryclearancedimensionsforproperelevationsrelativetotheroofpanelshavebeenshown. Thecustomershallberesponsibleforcoordinatingthesedimensionalrequirementswithothertradesassociatedwiththebuildingroofsystem.

    7.11. ErectionCare

    7.11.1. Theerectormustbeskilledintheerectionofmetalbuildingsystemsandisresponsibleforcomplyingwithallapplicable local,federal,andstateconstructionandsafetyregulationsincluding OSHA regulations as well as any applicable requirements of local, national, orinternational

    union

    rules

    or

    practices.

    The

    Erector

    remains

    solely

    responsible

    for

    the

    safety and appropriateness of all techniques and methods utilized by its crews in theerectionofthemetalbuildingsystemand/ortheTrapezoidalSSRroofsystem. TheErectorisalsoresponsibleforsupplyinganysafetydevicessuchasscaffolds,runways,nets,etc.,whichmayberequiredbythegoverningcodestosafelyerectthemetalbuildingsystemand/orTrapezoidalSSRroofsystem.

    7.11.2. Anchorage for safety devices may be added at an additional cost provided specificconnections are designed and clearly noted in Canam Steel Building Corporation orderdocuments. All anchorage points must be noted with exact location, magnitude, anddirectionofforceforafullybracedstructure.

    7.11.3. TheerectoroftheTrapezoidalSSRroofsystem shallexercisegreatcareandattentionto

    the

    details

    as

    shown

    on

    the

    erection

    drawings

    and

    in

    the

    erection

    manual

    to

    insure

    asecureandproper fitofallcomponents. CanamSteelBuilding Corporationshallnotbe

    responsible forsupervisingand/orcoordinating theerectionof theTrapezoidalSSR roofsystem with other trades. Erection drawings shall govern when a situation differs fromthatshownintheerectionmanual.

    7.11.4. Dueconsiderationmustbegivenbytheerectortotheeffectsofthermalexpansionandcontraction when erecting a roof tiein to an existing structure to insure a safe, secure,weathertightcondition. Flashing fortieinstoexistingbuildings istypicallynot includedas part of the material provided by Canam Steel Building Corporation. Refer to thesectionsanddetailsforspecificmaterialsprovidedbyCSBC.

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    11/14

    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page11

    7.11.5. Theerectoracknowledgesthatalldetailsforallconditionscanbenotedontheplansandthat due care and judgment are required to make a safe and watertight condition.Sealantsandcaulksmayberequiredbaseduponactualconditionsencountered.

    7.12. FieldCuttingofPanels

    7.12.1. When fieldcutting or mitering Trapezoidal SSR roof panels, nonabrasive cutting toolssuch as nibblers or tinsnips shall be used. Abrasive cutting tools such as mechanicalgrinders,saws,shears,orscissorscandamagetheGalvalumeorpaintedfinishandcreateexcess metal shavings that can corrode the panels. The use of nonapproved cutting

    devicesmay

    void

    your

    manufacturers

    warranty.

    Section8. WallCovering

    8.1. General

    8.1.1. Wall covering shall be PBRpanel, Reverse Roll PBRPanel, or PBAPanel, precision rollformedfrom26gaugesteel.

    8.1.2. ASTME283isanAirinfiltrationspecification.

    8.1.3. ASTME331isaWaterpenetrationspecification.

    8.1.4. All Canam Steel Building Corporation wall panels can meet ASTM E283 & E331

    specificationswith

    the

    requirements

    listed

    below.

    Wallpanelmaterialmustbe80KSIAddx3/32tapemastictoALLsidelapseams.Sidelapfastenerspacingis24O.C.MaximumMinimumpanelgauge:26 (24gaugemaybeavailableatadditionalcost)

    8.2. PanelMaterial

    8.2.1. Galvanized steel sheeting shall be processed in accordance with ASTM A653. Consultyour specific plant for minimum yield strength and grade of material. The galvanizedcoatingshallbe .90ozpersquarefoot(ClassG90) inaccordancewithASTMA653. ThespangleforgalvanizedpanelisbrightflatspangleinaccordancewithASTMA653.

    8.2.2. Galvalumesteelsheetingshallbealuminumzincalloycoatedsteelsheet inaccordance

    with

    ASTM

    A

    792.

    Consult

    your

    specific

    plant

    for

    minimum

    yield

    strength

    and

    grade

    of

    material. Ithasacoatingthicknessof.55ozpersquarefoot.

    8.2.3. WallpanelsprovidedbyCanamSteelBuildingCorporation forexterioruseareprecisionrollformed fromprepaintedG90galvanizedorGalvalumecoils. Coils to receive finishpaintsaresubjectedtoastrenuouscleaningprocesspriortocoating. Next,thecoilsareprimecoatedandovencured. The finishcoat isthenappliedandmonitored forproperovencure temperatureandcoloruniformity. Finishedmaterial issubjected tostringentquality control tests including: physical bend and impact resistance, film thickness,hardness, gloss, and color. This process is time tested and uses the industry provenSiliconized Modified Polyester paint system. A 70% Kynar 500 finish is available at anadditionalcostuponrequest.

    8.3. PanelConfiguration

    8.3.1.

    CanamSteel

    Building

    Corporation

    PBR

    panel

    provides

    a36"

    (915

    mm)

    net

    coverage

    and

    consists of major ribs 1 1/4" (32 mm) high spaced at 12" (305 mm) on center with anextended purlin bearing sidelap to allow for additional sidelap support. Minor ribsreinforcetheflatareabetweenmajorribstominimizeoilcanning.

    8.3.2. Canam Steel Building Corporation reverse roll PBRpanel in a recessed fastener panelwhichprovidesa36" (915mm) netcoverageand consistsofmajor ribs11/4" (32mm)deepspacedat12"(305mm)oncenterwithanextendedpurlinbearingsidelaptoallowfor additional sidelap support. Minor ribs reinforce the flat area between major ribs tominimizeoilcanning..

    8.3.3. Canam Steel Building Corporation PBApanel is an architectural recessed fastener panel

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    12/14

    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page12

    whichprovidesa36"netcoverageandconsistsof11/4"(32mm)deepmajorribsspacedat12"(305mm)oncenterwithanextendedpurlinbearingsidelaptoallowforadditionalsidelapsupport. Ashallowvvalleyoccursbetweenthemajorribs.

    8.4. TrimandFlashing

    8.4.1. Colorcoated trim and flashing shall be supplied in 26 gauge. Trim shall be provided ateave, base, corners, framed openings, and where necessary to insure a properlyconstructedbuilding.

    8.4.2.

    All

    exposed

    trim

    and

    flashing

    material

    shall

    be

    manufactured

    from

    Galvalume,galvanized,orpaintedsteelstrip.

    8.5. Fasteners

    8.5.1. Paneltosecondary framing fasteners forallwallpanelsshallbea#12x11/4" (32mm)long selfdrilling carbon steel screw, hex head. Fastener shall have a painted head tomatchpaneland/ortrimcolor.

    8.5.2. Paneltopanel,stitchfastenerforallwallpanelsshallbea#12x3/4"(19mm)longsharppointcarbonsteelscrew,hexhead. Fastenershallhaveapaintedhead to matchpaneland/ortrimcolor.

    8.5.3. Fasteners required forsecuring trim tomasonryorconcretearenotsupplied byCanam

    SteelBuilding

    Corporation.

    8.6. Sealants

    8.6.1. Tubesealantsshallbeusedatalltrimendlaps,andshallbeapolyurethanesealant.

    8.6.2. Sealants not provided by Canam Steel Building Corporation shall not be used withoutspecificapprovalfromCSBC.

    8.7. Closures

    8.7.1. Closures shall be manufactured of closedcell polyethylene foam to match the panelconfiguration.

    8.7.2.

    Closuresshall

    be

    supplied

    as

    required

    to

    provide

    aclosed

    wall

    panel

    profile

    at

    the

    rake

    condition.

    8.8. InstallationofPanels

    8.8.1. Allsidelapsshallbelappedaminimumofonefullrib. Panelendlapsshallbeaminimumof4"(101.6mm)longonwallpanels.

    8.8.2. All wall panels shall be fabricated in one piece providing the length does not exceedpracticallimitsforshipmentorconstruction.

    8.8.3. Storage and installation of the wall system shall be in accordance with Nucors printedinstructions.

    8.8.4.

    Standardmaximum

    panel

    length

    shall

    be

    30 (9.14

    m).

    If

    required,

    lengths

    of

    up

    to

    45

    (13.72)maybeprovided.

    8.9. Cleanup

    8.9.1. Alldirt,oil,grease,fingerprints,orothercontaminantsshallberemovedafterinstallationtoinsureproperservicelifeofthepaintsurface.

    Section9. Accessories

    9.1. WalkDoors

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    13/14

    C a n a m

    S t e e l

    B u i l d i n g

    C o r p o r a t i o n

    S p e c i f i c a t i o n

    G u i d e Page13

    9.1.1. WalkDoorsprovidedbyCanamSteelBuildingCorporationarecommercialgrade,weldedconstruction. Door leafs are 1 3/4" (44.45 mm) thickness, 20 gauge galvanized facesheets, flush top and bottom channels with polystyrene insulated core. Hinge and lock

    jambsarereinforcedwith10gaugeand14gaugematerialrespectively. Doorsarefactoryfinished baked enamel finish. 16 gauge galvanized subjambs are included for ease ofinstallation. WalkdoorsareprovidedKD(knockdown)forfieldassembly. Preassembledwalkdoorsareavailableatadditionalcost.

    9.2. Windows

    9.1.2.

    Windows

    provided

    by

    Canam

    Steel

    Building

    Corporation

    are

    factoryassembled

    and

    are

    selfflashing forapplicationwithallCSBCstandardwallpanelprofiles. Unlessotherwisespecified in the CSBC order documents, windows are insulated, clearglass. Galvanized

    jambstiffenersaresuppliedforrigidityofinstallation.

    9.3. FramedOpenings

    9.3.1. Framing members for overhead doors shall typically be the same depth as the girts towhichtheyattach. Wallpaneledgeshallbetrimmedandflashedatallopenings.

    9.3.2. Framing for overhead doors shall be primecoated or galvanized, as required per theCanamSteelBuildingCorporationorderdocuments.

    9.4. LightTransmittingPanels

    9.4.1. Translucent light panels shall be glass fiber reinforced composite panel of ACRYLIT,containing100%Acrylicresinmonomers.

    9.4.2. Panelsshallbeproducedtomatchtheroof/wallpanelconfiguration.

    9.4.3. Panelsshallweigheightouncespersquarefoot.

    9.4.4. Nominallengthofpanelsshallbe50,10'0",or110.

    9.4.5. Panelsshallhave5560%LightTransmission perASTMD1494.

    9.4.6. PanelsshallhaveaBurnRate oflessthan21/2perminuteperASTMD635.

    9.4.7.

    Metalpanels

    above

    and

    below

    the

    translucent

    section

    along

    the

    same

    run

    shall

    not

    be

    shorter than the length of three purlin spaces. Roof translucent panels shall not belocatedattheeaveorridge. LightTransmittingpanelsshallbeplacedsuchthattherearefourmetalpanelsminimumbetweeneachLTP.

    9.4.8. The buyer shall advise all parties and the owner that Light Transmitting Panels notdesignednorintendedforfoottraffic.

    9.4.9. PBRpanel Light Transmitting Panels have a UL and Florida approval rating at 50maximumpurlinspace.

    9.5. RakeandEaveExtensions/Canopies

    9.5.1.

    Rake

    and

    eave

    extensions

    shall

    be

    comprised

    of

    cantilevered

    extension

    beams

    or

    roofpurlins,10(0.3m)to60(1.83m)beyondsteelline,completewithallnecessarytrim,

    closures,andflashingtoprovideaweathertightroofcontinuationoftheroofline. Otherdimensionsmaybeavailable.

    9.5.2. Canopiesshallconsistofroofpanelssupportedbycantileveredcanopybeamsandpurlinsfor20(0.61m)to150(4.57m)projection,completewithallnecessarytrim,closures,andflashingtoprovideaweathertightextension.

    9.6. LinerPanel

    9.6.1. Liner panel for a walls or roof is produced from 29 or 28 gauge material with a white

  • 8/10/2019 CSBC_Specification Guide_2010.10.pdf

    14/14

    straight polyester finish or unpainted galvalume plus as called for in the Canam SteelBuildingCorporationorderdocuments. Linerpanel isnot intendedtobeexposedtotheeffectsofweather,sunlight,moisture,orcorrosiveenvironments.

    Section10. StandardServiceabilityCriteria

    Themostcommonlyaddressedcriteria inpreengineered steelbuildingsystemsaredeflectionsandthermalexpansion/contraction. Mostbuildingcodesaresilentonserviceabilityrequirements,leavingthem up to the project Engineer of Record or project architect. However, in most cases with preengineered buildings, deflection limits are based upon rules of thumb or past experience by the

    building

    manufacturer.

    Canam

    Steel

    Building

    Corporation

    standards

    are

    based

    upon

    the

    AmericanInstitute of Steel Construction design guide, Serviceability Design Considerations for LowRise

    Buildings. Anybuildingorderwillmeetorexceed the followingcriteriaunlessspecificallyspecifiedotherwiseintheorderdocuments.

    STRUCTURALELEMENTS LIMIT LOADING

    WALLGIRTSSUPPORTING:MetalWallPanelsMasonryorConcreteWallsDryvit,Wood,Sheetrock,Etc.

    Bay/90HorizontalBay/240HorizontalAsspecifiedbyBuyer

    10YearWind10YearWind10YearWind

    PURLINS:RoofSlopesgreaterthan1/4:12 Bay/150Vertical Collateral+Live/SnowLoad

    WALLPANELS:Metal,byCSBCMaterialbyOthers

    NospecialconsiderationNotbyCSBC

    ROOFPANELS:RoofSlopesgreaterthan1/4:12 PurlinSpacing/180Vertical

    PurlinSpacing/180VerticalCollateral+Live/SnowLoad200lb.LoadonOnePanel

    FRAMESSUPPORTING:RoofSlopesgreaterthan 1/4:12MetalWallPanelsTiltup,PrecastorMasonryWalls

    RafterSpan/150VerticalEaveHeight/60HorizontalWallHeight/100Horizontal

    Collateral+Live/SnowLoad10YearWind10YearWind

    Section11. Execution

    11.1. Erection RECTION of the building system shall be in accordance with the appropriateerectiondrawings,erectionguidesand/orotherdocumentsfurnishedwiththematerials. Itshall be the responsibility of the erector to comply with all appropriate legal and safetyrequirements. The erector shall determining and provide any and all temporary bracing,shoring,blocking,bridging,and/orsecuringofcomponents,Etc.,asrequiredduringerectionofthebuilding.