Cryogenik waste heat utilization for DESY and European XFEL2nd Workshop on Energy for Sustainable Science at Research Infrastructurs
Jens-Peter Jensen, Eva LeisterEnergy for Sustainable ScienceGenf, 24.10.2013
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 3
DESY premises heat distribution
XFEL cryogenics plant
district heating transfer station
XFEL injector
Heat distribution pipes 110 °C (red)
Heat pipes 80 °C (blue)
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 4
Energy foot print of DESY and XFEL
DESY premises in 2015 ff
>Electrical energy: 160 GWh, 25 MW
>Heating energy: 20 GWh, 10 MW
>Dominated by the accelerators and experimental halls
XFEL operation at 10 Hz in 2016 ff
>Electrical energy: 120 GWh, 20 MW
>Heating energy: 10 GWh, 5 MW Schenefeld premises
>Cryogenics electrical energy at 10 Hz: 24 GWh/a
Heating demand is predominant on the Schenefeld and Osdorf premises
XFEL cryogenic plant is on the DESY premises, ex HERA cryogenics plant
>XFEL cryogenics waste heat utilization possible for DESY premises
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 6
Coldbox
Dewar
Subcooler
oilseperatorcompressors
air cooler He preheater
The helium-heater is only used when the subcooler is cooling down or heating up.
Helium
Oil Breox B35
Oil-Helium mixture
6 K
300 K
40°C
75°C
XFELmodulestunnelinjector
Cryogenic Plant Functionality
50°C
heat exchanger
to the heat distribution return pipe
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 7
Oilsystem of the XFEL Cryogenic Plant
heat exchanger for cryogenics waste heat utilization air/oil cooler
low pressure compressors
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 8
Temperature Plot of the Breox Oil in 2012
average: 70,2 °C
oil temperature of the high pressure compressor in 2012
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 9
Heat emission of 1 street of the cryogenic plant in 2012
average value: 823 kW
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 10
District heating transfer station
UST 48
UST 8
UST 47
UST 28c
UST 49
UST 72
UST 24UST 30
UST 25b3
UST 25
UST 25c
UST 1d
UST 54
UST 2 UST 1a
UST 7
UST 5
UST 10
UST 16
UST 17
UST 3b
UST 3
UST 80b
UST 62
UST 64
UST 69
UST 67
UST 67-2
UST 67-1
1
8
7
54
3
6
210
11
13
14
15
16
17
18
19 20
21
23242526
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41 42
912
44
UST CFEL
46
UST ZOQ
45
4a
UST CSSB
3a
UST 11a
UST Nanolab
20a
UST FLASHII
UST PXN22
Vattenfall district heat supply
Heat Distribution Sceme of DESY Premises
XFEL cryogenic
UST = heat substation
cuts for calculations
exist access to heat distribution
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 11
Simulation Models for MATLAB/Simulink
district heat transfer station heat substation
heat pipes heat exchanger of the cryogenic plant
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 12
Classified Heat Load Curve of 2012
1 street of the cryogenic plant
2 streets of the cryogenic plant
DESY heat consumption 2012 20,9 GWh/a
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 13
Results of Cryogenic Heat Utilization
1 street 2 streets
heat extraction 4,6 GWh/a 7,0 GWh/a
cost savings1) 228.450 €/a 350.600 €/a
payback period 2) 2,6 a 1,7 a
cash value after 10 years 3) 807.740 € 1.558.298 €
CO2-Emission 4) 1.087 t-CO2/a 1.669 t-CO2/a
1) price for district heat: 0,05 €/kWh2) investment costs: 592 k€3) refunding rate: 10 %4) district heat: 238 g CO2/kWh
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 14
Waste Heat Utilization from the XFEL Water Cooling
Pump HouseDESY campus
Pump HouseSchenefeld
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 15
cooling towers
klystrons: 7500 kWmagnets: 500 kW
compression chiller
air conditioning: 800 kW electronic racks: 200 kW(water cooled)
heat exchanger heat exchanger
30°C 8°C 20°C 20°C
summer Tair >16°C
winter Tair<16°C
heat exchanger
Water Cooling of XFEL Injector and Main Linac XTL
45°C 14°C 30°C 30°C
18°C28°C
25°C40°C
Electronic rack cooling in winter
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 16
District heating transfer station
UST 48
UST 8
UST 47
UST 28c
UST 49
UST 72
UST 24UST 30
UST 25b3
UST 25
UST 25c
UST 1d
UST 54
UST 2 UST 1a
UST 7
UST 5
UST 10
UST 16
UST 17
UST 3b
UST 3
UST 80b
UST 62
UST 64
UST 69
UST 67
UST 67-2
UST 67-1
1
8
7
54
3
6
210
11
13
14
15
16
17
18
19 20
21
23242526
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41 42
912
44
UST CFEL
46
UST ZOQ
45
4a
UST CSSB
3a
UST 11a
UST Nanolab
20a
UST FLASHII
UST PXN22
Vattenfall district heat supply
Heat Distribution Sceme of DESY Premises
XHMP waste heat pump
UST = heat substation
cuts for calculations
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 17
Waste Heat Pump Calculation
> Heat pump: 630 kW, Tcond = 85 °C, Tvap = 40 °C
> Heat is transferred into the heat distribution return pipe
> Investment costs are 725 k€
> Without heat utilization from the cryogenics
1 heat pump
heat economy 4,6 GWh/a
cost savings1) 74.300 €/a
payback period 2) 9,8 a
Cash value after 10 years 3) - 270.222 €
CO2-Emission 4) 745 t-CO2/a
1) price for district heating: 0,05 €/kWh electricity: 0,15 €/kWh2) investment costs: 725.000 €3) adequate target rate: 10 %4) district heating: 238 g-CO2/kWh elecricity: 336 g-CO2/kWh
Jens-Peter Jensen, Eva Leister | Energy for Sustainable Science | 24.10.2013 | page 18
Conclusion
Cooling water waste heat utilization with heat pump
>The most waste heat goes into the cooling water
>The cooling water temperatures are to low for direct transfer into the heat distribution pipes
>One needs a heat pump to boost the temperature
>The savings does not pay back the invest and service costs
and
>The XFEL pump house XHMP is near the cryogenics hall
>The heat pump is in competition with the cryogenics
>This makes it even more uneconomic