ELECTRIC CIRCUIT BREAKERS

By

GAURAV GANGWAR

(1247420017)

Submitted to the Department of Electrical Engineering

In partial fulfillment of the requirements

For the degree of

Bachelor of Technology

In

ELECTRICAL ENGINEERING

Signature

(Seminar Guide)

SHRI SIDDHI VINAYAK INSTITUTE OF TECHNOLOGYUttar Pradesh Technical University, Lucknow

2

Page 3: cricuit breaker report

DECLARATION

I hereby declare that this submission is my own work and that, to the best of my

knowledge and belief, it contains no material previously published or written by

another person nor material which to a substantial extent has been accepted for

the award of any other degree or diploma of the university or other institute of

higher learning, except where due acknowledgment has been made in the text.

Signature

Name- GAURAV GANGWAR

Roll No. 1247420017

Date-27/03/2015

3

Page 4: cricuit breaker report

CERTIFICATE

This is to certify that seminar Report entitled “CIRCUIT BREAKERS” which is submitted by GAURAV GANGWAR in partial fulfillment of the requirement for the award of degree B. Tech. in Department of ELECTRICAL ENGINEERING of U. P Technical University Lucknow, is a record of the candidate own work carried out by him under my/our supervision. The matter embodied in this thesis is original and has not been submitted for the award of any other degree.

Date: Seminar Guide

26/03/2015 Mr Devendra Maurya

4

Page 5: cricuit breaker report

ACKNOWLEDGEMENT

It gives us a great sense of pleasure to present the report of the B. Tech Seminar undertaken during B. Tech. Third Year. We owe special debt of gratitude to DEVENDRA MOURYA, Department of ELECTRCAL ENGINEERING SSVIT, Bareilly for his constant support and guidance throughout the course of our work. His sincerity, thoroughness and perseverance have been a constant source of inspiration for us. It is only his cognizant efforts that our endeavors have seen light of the day.

We also take the opportunity to acknowledge the contribution of RAHUL CHANDRA DHAM for his full support and assistance during the development of the seminar.

We also do not like to miss the opportunity to acknowledge the contribution of all faculty members of the department for their kind assistance and cooperation during the development of our project. Last but not the least, we acknowledge our friends for their contribution in the completion of the project.

Signature:

Name :GAURAV GANGWAR

Roll No.: 1247420017.

5

Page 6: cricuit breaker report

ABSTRACT

A circuit breaker was examined to determine how it works. Basically, it is designed to disconnect the current if the current passing through the breaker is higher than the allowable current. Its main parts consist of a switch, connecting pads, and the disconnect device. Since the breaker consists of many individual parts, the only improvement found was to combine some of the parts into a single part. Introduction Our group dissected a thirty-amp household Circuit-breaker. Its purpose is to protect electrical appliances from being damaged though excessive currents. A circuit breaker limits the amount of current that may safely enter a household electrical system via a predetermined amperage rating. It is placed in series between your house and the provided electricity. Any current in excess of the rated current amount will trip the circuit breaker in to a non-conducting or open path condition. The closed path is maintained until either magnetism or thermal expansion causes the circuit to trip. Device Description The circuit breaker has several features that are worth noting in the design discussion. First is its ability to detect various types of loading situations. The breaker can not only open a circuit in response to a current spike, but can also react to a sustained moderate current draw, just above its rated current. The circuit breaker also has an easily resetable 3-position switch, and various internal safety features such as spark arrestors and cavity vents. Operation of the circuit breaker is simple, but utilizes complex mechanisms. Essentially there are to main internal mechanisms; the trigger and the switch.

6

Page 7: cricuit breaker report

TABLE OF CONTENT

1. Introduction………………………………………...…………9

2. Circuit Breakers As Switches

• Over-Currents ……….………………………………….10

• Circuit Breakers As High Temperature Limit Switch..11

3. NEC Requirements For Circuit Break

• Circuit Breaker Functions……………………………...11

• Circuit Breaker Types ………………………………….11

• Circuit Breaker Voltage Ratings……………………….11

• Circuit Breaker Ampere Ratings………………………16

• Ampere Interrupting Capacity (AIC)………………….16

4. Testing-Listing OF Circuit Breakers……………………….17

5. The Electrical Arc……………………………………………18

6. The Effects of Current Flow………………………………...19

7. Thermal Energy……………………………………………..19

8. Thermal Trip Element………………………………………19

9. Magnetic Trip Element……………………………………..20

10. Hydraulic-Magnetic Trip…………………………………...20

11. Elements Methods Of Mounting Circuit Breakers

• Fixed Mounted Circuit Breakers……………………...21

• Removable Mounted Circuit Breakers…………….….21

12. Methods Of Securing Circuit Breakers……………….….21

7

Page 8: cricuit breaker report

• Insulated Case Circuit Breakers (ICCB)

• Molded Case Circuit Breaker Maintenance (MCCB)

13. Type Of Circuit Breakers

• Oil Circuit Breaker…………………………………………...28• SF6 Circuit Breaker…………………………………………..35• Vaccum Circuit Breaker………………………….…………..39• Air Blast Circuit Breaker………………………….………….41

14. Reference………………………………………….…………45

8

Page 9: cricuit breaker report

1. INTRODUCTION

The American National Standards Institute (ANSI) defines a circuit breaker as: “A mechanical switching device, capable of making, carrying and breaking currents under normal circuit conditions. Also capable of making and carrying for a specified time and breaking currents under specified abnormal circuit conditions, such as those of a short circuit.” The NEC defines a circuit breaker as “a device designed to open and close a circuit by non-automatic means, and to open the circuit automatically on a predetermined over current without damage to itself when properly applied within it’s rating.” While the ANSI and the NEC definitions describe the same family of devices, they do have some differences. The same is true with the actual circuit breakers themselves. They are much the same in general terms; however, there are a number of significant differences between the many types of electrical circuit breakers installed in various types of facilities today.

9

Page 10: cricuit breaker report

2. Circuit Breakers As Switches

Both the ANSI and the NEC definitions acknowledge the potential for the legitimate use of circuit breakers as switches. Switches (pass, but do not consume electrical energy) are considered as being control devices, thus one may also say that a breaker is a control

10

Page 11: cricuit breaker report

device, or a controller. A circuit breaker can control and protect an electrical circuit and people operating the utilization equipment. An electrical relay is an example of an operating control; it opens and closes the circuit. Circuit breakers are not designed as replacements for operating controls such as relays, contactors, or motor starters. There is as you may intuitively have anticipated an exception. Some circuit breakers are manufactured for use in a specific type of application. When a circuit breaker is designed to also be routinely used as an on-off switch to control 120 or 277volt florescent luminaires they are marked SWD, for switch duty. This does not mean that a switch duty breaker can be used to manually control a traffic signal light where it will be cycled on and off 1,000 or more times per day. The point is; the listing for switch duty (SWD) does not mean a circuit breaker can be used as a high frequency cycling operating control, such as a relay that has a life span rated in tens, if not hundreds of thousands of duty cycles. While circuit breakers can be legitimately and safely used as switches, the frequency and duration of such use is limited. Routinely circuit breakers are manually operated for service-maintenance, and repair type activities. With the preceding enhancing our understanding, we can say that circuit breakers can legitimately be used as switches, though generally they are not intended for prolonged repetitive manual breaking and making type control of electrical energy utilization equipment.Current Levels to Be Broken For general consideration, and our immediate purposes; the amounts of current circuit breakers are required to open, can be divided into the following three broad current amplitude groups.The first and lowest being rated load or less. For example: a 60 amp low voltage molded case thermal-magnetic breaker must be able to open or close 48 amps (80% of its rating) or less.Next up in current quantity, this same breaker must be able to open Overload level currents. Overloads, for our purposes, can be understood by reference to the NEC requirements for overload protection for motors. Thermal overloads are commonly sized for some 115% of the motor’s nameplate full load amps. A motor with a service factor of one, having a rated load of 10 amps would be overloaded when pulling 11.5 amps or more. Overload currents can for our immediate purposes be considered to be percentages increases above rated normal load current.The third and highest current level grouping is Short Circuit Currents. Short circuit (fault) currents can be considered as being fifteen (15) or more times normal rated load currents.In summation, circuit breakers may be called upon to open or close a circuit within a range of from no current flow, to as much as fifteen (15) times or more its rated current. For a 100 amp breaker that could 1,500 amps or more.As will be covered later, this high value of short circuit current is routinely exceeded by circuit breakers today. This should not be considered as implying that circuit breakers can open unlimited amounts of current, as will be covered later on, they can not.

Over-CurrentsThe National Electrical Code (NEC) defines over current as “any current in excess of the rated current of the equipment or the ampacity of a conductor.“ Over current (or excessive current) conditions are caused by defective conductor insulation, equipment, or an excessive workload burden placed upon the utilization equipment and its electrical circuit. Fuses and circuit breakers provide a level of safety against

11

Page 12: cricuit breaker report

over current conditions in electrical circuits. We therefore routinely say that fuses and circuit breakers are over current protective devices (OCPD). That is they protect the circuit’s components from too much current.Gazing into the fog that is the future, perhaps we will begin to see these types of electrical devices taking on additional roles, thus becoming a more general intelligent circuit protective device. To minimize the length of this paper, only automatic circuit breaker type over current protective devices will be covered. Restated, this paper does not cover fuses, and motor starter type overload relays.A circuit breaker’s primary functions are to provide over current protection, isolation from energized circuit components and un-energized circuit components.Breakers must perform these functions when properly applied without fail in all circumstances completely and safely, while protecting the electrical circuit against over current induced damage between normal rated current and the breaking capacity of the breaker called its Ampere Interrupting Capacity (AIC). Now that is a big job and an important job.Modern breakers routinely do their job day in and day out with very little maintenance. Like all things that are made by man, they do have limits and they do fail. Hopefully this paper will help you better understand and appreciate the task performed by those little black boxes. Hopefully this paper Hope full Current and Temperature The movement of electrons (electricity) in a conductor produces a rise in the temperature of the conductor’s material and it’s electrical insulation. Excessive temperature rise (caused by an excessive amount of electron collisions with base material atoms) can result in the melting of the wires material (assumed to be copper by the NEC), if it is allowed to rise as high as 1,980 degrees F. For a point of reference, the NEC limits the operating temperature of XHHW type conductor insulation to no more than 194 degrees F. Thus it can be understood that long before the copper wire will begin to melt, the wires insulation material will have melted, and perhaps to have even burned up.Our first priority therefore is the temperature of the conductor’s electrical insulating materials. Different types of insulating materials have different maximum design operating temperatures.

Circuit Breakers As High Temperature Limit SwitchesElectrical energy is transported throughout an electrical circuit by the conductive path provided by electrically insulated wires. The material that performs the insulation function in the circuit has a high temperature limit far below that of the copper wire. Circuit breakers are routinely sized to limit thermal energy related damage to the electrical insulation material and not the copper wire. This being the case we can say that a circuit breaker limits the temperature of the connected protected wire’s insulation materials.Amp cities Of Electrical Conductors Just how hot an electrically insulated wire can get before its insulation melts, suffers damage or a decrease in electrical dielectric strength (the ability to perform as an electrical insulator) are well-known facts. The various types of materials used as electrical insulation have been tested and the results listed in what are called ampacity tables in the NEC in article 310.16.How long an installed conductor’s electrical insulation material will last without overload, is yet another question. Research is underway to determine the life of an installed insulated conductor. No doubt when completed, it will point to many factors that have a negative impact upon the in service life of an insulated conductor. For

12

Page 13: cricuit breaker report

now we can book a safe bet that voltage spikes, vibration, environmental factors such as temperature, dust (both electrically and thermally conductive and nonconductive types), UV light, aggressive vapors and fluids, and relative humidity will all be proven to shorten, to some degree, the life of modern plastic type electrical insulation materials.I suspect that many of these same factors also have a negative impact upon circuit breakers. I do not know of any research, in the past or currently, that defines them service life of circuit breakers. Considering the importance of the safety provided to people and property that circuit breakers provide, it is a bit puzzling as to why such research has not already been undertaken.For many years various types of materials have been used as electrical insulators.Today conductors are made using material for outer jacketing, and for filling in the gaps (indices) between bundled round conductors. These materials may or may not be considered to be electrical insulators. Some medium and high voltage cables are made using materials that are considered to be conductive, or semi-conductive.

Short CircuitsA short circuit is an unintended path through which current can flow. Any time current flows in a path that is not the normal path, we say that the circuit is shorted.

Arcing FaultsWhen a loose connection (a gap is present) is made in the faulted circuit, so loose that the current flow is non-continuous, it is called an arcing or arc fault. This type of circuit defect is much like a welder using a welding electrode to produce an electric arc. Arcing type faults are the most difficult to locate (due to conductor concealment in conduit or inside of walls and their non-continuous nature) and can be the cause of fires. This type of defect is the opposite of a bolted fault, the circuit impedance is higher and the connection is very irregular (high frequency). The current flows for only a fraction of a second and then cools down and may not flow current, or heat up again and produce an arc across the gap between the two conducting surfaces.During the A-C cycle there are two times that the supply circuit voltage goes to zero volts; there are two times when the circuit’s electromotive pressure is zero and an arc cannot be produced. This zero volts time helps to increase the faulted circuit’s impedance. This higher impedance makes it more difficult for the arc to re-establish it’s self again. These types of faults produce heat in a very small area thus they can start a fire and not trip a common thermal-magnetic circuit breaker and their energy level is so low and they last for such a short time, that they typically are not responded to by a common circuit breaker.In response to this unique type of circuit defect, a new family of circuit protectors called arc fault circuit interrupter (AFCI) type circuit breakers has been under development over for the last ten years. Because of the unique components (microcomputers) of these devices they will not be covered in this short paper. The common circuit breaker will not respond to the development of an arcing type fault due to the low total amount of thermal energy developed by the arc and the very high frequency of the arc. Perhaps one can think of an arcing fault as an embryonic electrical circuit defect, unlike the defect that has fully developed and matured into an adult electrical fault such as a bolted fault. Experience shows that on occasion a short circuit will clear its self before, or after the operation of the OCPD. That is it will develop into an open circuit.

13

Page 14: cricuit breaker report

Bolted FaultsOccasionally a shorted circuit will evolve that has such a firm connection (to either a grounded conductive object or another hot wire), that it is said to be a bolted fault.We are saying that it was not a loose connection, it was not wiggling around. A bolted fault offers less impedance to the flow of current than does an arcing type fault.A loose connection type of fault may produce enough heat to melt or plasticize the conductor’s conductive material and having cooled enough to then produce a joint so firm and secure as to be comparable to a welded joint. Then we would call it a bolted fault. Circuit breakers are typically calibrated to be capable of responding to a bolted type fault. This is because a bolted type fault produces sufficient current flow to cause either the thermal (after some intentional delay) or the magnetic (non-delay, but only if sufficient current flow is produced) trip elements to open the circuit.Safety First, Always First The exact nature of electricity, that is it can not be detected with the eyes, ears, or the nose, yet if it is touched, it can kill, must be remembered at all times. Circuit breakers are very reliable components of an electrical system, however they are man made; and are subject to becoming defective. Proper lock-out-tag-out procedures must be followed when working on electrical circuits above 50 volts. Proper personnel protective equipment must be in serviceable condition and properly worn. Safety is a requirement, not an option of every electrical task, large or small, be it routine or emergency in nature. Always use the three-step method when checking for voltage.Take good care of your electrical test meters, having them checked at least every three years for insulation strength and for calibration as listed in the instruction booklet, or once a year. While a switch may visually indicate that the contacts have opened, a meter must be used to confirm that no voltage remains in the equipment to be worked on. Many times more than one source of power is provided to a machine. Some electrical circuits contain motor starting/running or power factor correction capacitors that may still be charged even after power has been removed from the circuit.When working with others do not assume that they know how to operate your meter, and do not assume that you know how to operate their meter. Take the time necessary to learn how to properly operate the test instruments that you will be required to use. I know that it is temporarily embarrassing to admit that we do not know something, but being found dead on the job, I believe to be permanently embarrassing. If you would like to learn more about the use of multi-meters and such, I suggest that you see if you can get your hands on a copy of the book titled “Test Equipment” published by Delmar. ISBN: 0-8273-4923-8.

NEC Requirements For Circuit BreakersThe National Electrical code has several requirements for circuit breakers (overcurrent protective devices). The following is a listing of some of them. Others can be found in the various specific articles, such as 430 covering motors.• Main, feeder and branch circuit breakers must be installed in a readily accessible location.• A working space as wide as the equipment, or at least 30 inches wide and three feet deep, or deep enough to allow any doors to be opened at a 90 degree angle be provided in front of the equipment housing a breaker.

14

Page 15: cricuit breaker report

• That when the operating handle is in the up position that it’s center line be not more than 6 ft. 7 inches above the floor or working platform.• That it be installed so that it is secure on its mounting surface.• That when installed that the up position be on and that when the operatingm handle is moved down that this be the off position.• That the breaker be clearly marked as to its off and on positions.• That the breaker be clearly marked, such that after installation that the amperage rating is clearly visible. (There are some exceptions, see 240.83)• That the operating handle be of a trip free design, that is it cannot be blocked or kept from tripping due to some type of obstruction keeping the operating handle from moving to the tripped position.• When wires are connected to a breaker that they be properly torqued to them breaker’s termination points.• The NEC has specific requirements for both AFC and GFCI type circuit protectors that are mostly applicable based upon specific locations.There are specific product type requirements for circuit breakers to be listed by a nationally recognized testing lab (NRTL) such as UL, that we will not be covering in this short paper. That means detailed information relating to engineering type testing and things that the circuit breaker manufacture must know about are not covered. I am saying this to call your attention to the fact that this is not an everything your ever wanted to know about circuit breakers, type of encyclopedic article.In this portion of the article; the following topics are covered:• Functions• Types• Components• Voltage Ratings• Ampere Ratings• Ampere Interrupting Capacity (AIC)• Testing--Listing Of Circuit Breakers• Not All “Breakers” Are Rated the Same• The Electrical Arc• Effects Of Current Flow• Thermal Energy• Thermal Trip Element• Magnetic Trip Element• Hydraulic-Magnetic Trip Elements

Circuit Breaker FunctionsLater in this article we will cover several more specific features of some specialized types of circuit breakers; but for now let us begin by saying that a circuit breaker’s main functions are:• Sense the current flowing in the circuit• Measure the current flowing in the circuit• Compare the measured current level to its pre-set trip point• Act within a predetermined time period by opening the circuit as quickly as possible to limit the amount of energy that is allowed to flow after the trip point has been reached.

15

Page 16: cricuit breaker report

Circuit Breaker TypesMediums and low voltage circuit breakers are commonly separated into the following groups based upon the type of material used to make the frames or cases out of:• Molded case, (MCCB) the most common low voltage type• Insulated case, (ICCB) the intermediate voltage and amperage sizes• Metal clad, the higher in voltage (medium) and amperage ratingCircuit Breaker ComponentsThe five basic components of a circuit breaker are:• Frame or case made of metal, or some type of electrical insulation• Electrical contacts• Arc extinguishing assembly• Operating mechanism• Trip unit, containing either a thermal element, or a magnetic element or both

Circuit Breaker Voltage RatingsLow voltage (under 600 volts) circuit breakers are commonly rated for; 120 volts, 240 volt, 277 or 480 volts A-C. Some breakers are rated for used in DC circuits, while others are rated for use in either AC or DC circuits.Single pole circuit breakers are rated for a voltage potential between the one hot wire and a grounded surface. Breakers that are intended to be part of a two or three phase circuit are rated for a voltage potential from opposite potential, to opposite potential, or phase-to-phase. You must not use two single pole a 240 volt breakers to control a 480 volt circuit, but two single pole breakers rated 277 volts could be used to control a 240 volt circuit.When improperly applied out side of it’s rating, a breaker may not be able to extinguish the arc when attempting to clear a fault. Some breakers have what is called a slash (/) rating such as 120/240 or 277/480. Breakers that are slash rated should not be used on un-grounded systems, as they have not been tested for safe operation on these types of systems. For a more detailed coverage of this topic review Mr. Holt’s article “Understanding Circuit Breaker Markings” in the November 2001 issue of EC&M magazine. Cooper-Busman also has an article covering slash rated circuit breakers, if you would like to read still more.

Circuit Breaker Ampere RatingsCircuit breakers have an ampere rating (typically marked on the end of the operating handle). This is the maximum continuous current that the breaker can carry without exceeding its rating. As a general rule the circuit breaker’s ampere rating should be the same as the conductor’s ampacity. In other words we would not want to put a 60 amp breaker on a 10 amp wire. Breakers are tested in open air, with a temperature of some 40 or 50 degrees C.When a breaker is placed within an enclosure, cooling airflow is restricted; this reduces the ability of the breaker to carry a current to 80% of its ampere rating.When they are installed in an electrical enclosure, breakers will trip when a current in the amount of their rating is placed upon them continuously. Breakers are designed to be able to safely carry a current in excess of their rating for very very short periods of time to allow some types of electrical equipment (called inductive loads) such as motors to start up.While not as common, some breakers are rated for 100% continuous loads. These are typically called supplemental protectors (SP) and not circuit breakers.

16

Page 17: cricuit breaker report

Ampere Interrupting Capacity (AIC)Circuit breakers are tested and then rated as to their ability to open the protected circuit with a specific amount of current flowing in the circuit. Circuit breakers typically have AIC ratings of between 5,000 and 200,000 AIC. The amount of fault current available must not exceed the breaker’s ability to safely open the circuit. Not only must the breaker be rated for the applied voltage, and continuous amperage load; it must also have an AIC rating equal to or greater than the available current at the location in the circuit where it will be installed. Breakers that have been installed so that the available fault current exceeds its AIC rating may blow up, just like a bomb would explode, were it to attempt to clear a fault current above its rating. When opening a faulted circuit, it is possible for smoke and fire to be exhausted from a breaker. If you would like to see a breaker belch fire and smoke, see if you can locate and view the Cooper-Busman fuse company videotape titled “Specification Grade Protection”. This tape well enhances your appreciation of the importance of an electrical device’s AIC rating.In your safety classes, you likely have received training in the step to the side routine before manually switching electrical circuits and this videotape will reinforce the value of this easy safety step. This is also a good reason why sheet metal covers called dead front trim should be re-installed on load centers, panel boards, and the like before operating switching devices.Electrical engineers tell us that the two major factors that govern the amount of fault current that can be delivered in a system are the KVA rating of the transformer and the impedance of the transformer. The presence of connected electric motors in the circuit also adds to the amount of potential fault current. Considering 480 volt systems, combined transformer and motor fault currents can range from 14,400 amps for a 500-KVA transformer with an impedance of 5.0% to some 90,000 ampsn for a 3500 KVA transformer with 5.75% impedance. Selecting all circuit breakers for higher AIC ratings may be the safety first and cost last method.An engineering level study of a facility’s electrical system every five years (or before plant remodeling is undertaken) is a good idea. The study should include (among other things, like is every thing properly grounded) a review of the AIC of the plant’s breakers and the fault current that the plant’s electrical circuits can deliver to the line terminals of all major circuit breakers.Testing-Listing OF Circuit BreakersMolded case low voltage circuit breakers are typically tested to UL standard 489. UL uses the following test goals to determine if a breaker is considered to be safe, (incompliance with their safety standard):� The breaker must interrupt the maximum short circuit current two times.� The breaker must protect its self and the connected conductor and the equipment it is installed in.� After having been tested the breaker must be fully functional and pass a thermal calibration trip test at 250% of its rated ampacity; and pass a dielectric withstand test at two times its rated voltage, (or a minimum of 900 volts).� The tested breaker must also operate properly and have continuity in all of its poles.UL-489 listed circuit breakers are tested with a four-foot length of wire. This is so they perform during the test as they would when installed in the real world, thus the wire is connected to make the test a bit more realistic. During the test the

17

Page 18: cricuit breaker report

conductor’s insulation must not be damaged. The connected wires must not be pulled loose from the breaker-conductor termination lug. The breaker case must not be damaged as a result of cable whip forces (caused by the poetically huge amount of magnetic force developed under short circuit conditions). The connected wire acts to some degree as a heat sink for the breaker. That is it helps to dissipate heat produced within the breaker. This is because the breakers’ case acts as not only an electrical, but a thermal insulation as well, in that it tends to retard heat transfer. This is one reason why breakers have wire size ranges marked on them. Too small a wire attached to the breaker cannot adequately aid in cooling the breaker.The temperature at the circuit breaker’s terminals must not rise more than 50m degrees C. above the ambient air surrounding the breaker. The UL-489 test standard has been used to test many many circuit breakers over the years and has proven to be a pretty good standard by which the safety of circuit breakers can be determined.Not All “Breakers” Are Rated The SameA circuit breaker listed to UL-489 standard is not the same animal as a breaker looking thing listed to a UL standard as a supplemental circuit protector (SP). Acircuit breaker listed to UL standard 489 will open the circuit under fault current conditions and is tested to a higher degree to do so than is a supplemental protector (commonly also tested to UL safety standards).Supplemental protectors cannot be used as service equipment; that is without some device such as a UL-498 listed breaker or fuse in the circuit up-stream of them, they may or may not open the circuit under short circuit conditions. It may be difficult to determine the difference between a circuit breaker and a supplemental protector by simply looking at an installed device. The good folks with UL have pointed out that we need to pay close attention to what we are working with, as the testing procedures and listing requirements differ among all of these look-a-like black boxes.I wish that I could pass on some sure fire just looking at it (without using a book orremoving the device) method of determing if it was a circuit breaker, or a supplemental circuit protector, but at this moment regrettably I am unable to do so.The same is somewhat true of magnetic trip (short circuit protection) only motor circuit protectors (MCP). With MCP’s it helps that an amperage rating is not imprinted on the end of the operator handle. However that aid is of limited value, as the NEC allows the marking to be hidden by some type of covering trim, when a circuit breaker is rated over 100 amps.Supplemental protectors are not required to have an AIC marked on them, but neither are circuit breakers that have an AIC of 5,000 amps. If you are a bit confused, so am I; and try as best they can, UL has not been able to communicate tome a hard and fast rule of how I can physically tell the difference in the field without removing the device, or finding part numbers and looking them up in a parts book (that plant maintenance folks do not typically have readily accessible). You can obtain additional information about the listing of Supplemental protectors by obtaining a copy of UL’s listing guide number: QVNU2 and circuit breakers number: DIVQ.The Electrical ArcAs soon as two energized electrical contacts separate, one contact (called the cathode) transmits electrons and the other (called the anode) receives them, an electrical arc is created. If you were to ask a layman to tell you what electricity looks like, he would likely describe an electrical arc, which it is not. We frequently see a wide range of arcs; the Godzilla of electrical arcs, the lightening strike, and the

18

Page 19: cricuit breaker report

micron sized static electrical discharge occasionally experienced after walking across a carpeted floor.The electrical arc is a naturally occurring event; a part of doing business with electricity so to speak. The visible arc (ionized air) is not electricity but an effect of electricity, just as heating of conductors when current flows in a circuit. An Electrical arc produces an intense amount of heat that can reach temperatures of 4,000 C and higher. If not extinguished quickly, an arc can pit (a transfer of metal from one surface to another), or even destroy the electrical contacts and insulating material such as the breaker’s casing.Circuit breakers are designed to minimize, if not eliminate damage caused by electrical arcs in the following ways:� Submerge the contacts in oil� Place the contacts in a vacuum tight enclosure� Immerse the contacts with an inert gas such as SF-6� Divert the arc away from the main contacts to secondary contacts or arc horns� Divert the arc away from the contacts with a magnetic field (blowout coils)� Deflect the arc off of the contacts by use of a differential pressure� Extinguish the arc in arc chutes� Making and separating contacts at high speedLow and medium voltage circuit breaker manufactures have used combinations of the above methods. Methods such as oil, vacuum, and gases are less common on modern low and medium voltage breakers.While it is correct to say that when the A-C sine wave reaches the zero voltage points, the arc will go out due to the lack of voltage. This is not the entire picture, for arcs are much more complicated. Quickly stated the arc has a voltage of its own, and if the air between the contacts is not cooled sufficiently, or the air gap is not wide enough, the arc may re-establish its self when the supply circuit voltage again increases.A common method used in the above 200 amp or so size breaker is the use of arc extinguishing chutes. This method diverts and separates individual sections of the arc away from the contacts into thermally and electrically conductive chutes where the arc is stretched and cooled sufficiently to extinguish it. The use of contact surface coating material such as silver is used to harden contact surfaces and reduce pitting damage. Spring powered switching contacts are designed to increase contact movement speed, to reduce the life of an arc.Copper only contacts are not used because heating causes a type of corrosion that increases the contact’s impedance, which in turn increases the amount of heat generated.An arc can travel across some types of insulated surfaces that have been heated so hot as to produce a carbon tract that provides a lower resistance path for future current flow. This means that external breaker insulation materials should be inspected from time to time for indications of overheating, dust, and for the possible formation of a fine carbon like material trail that can result in a short circuit.The Effects of Current FlowWhen current flows in a circuit two effects are produce, magnetic and. Thermal energy is comparatively a much slower phenomenon to build up than a magnetic force. For example, under short circuit current conditions, the magnetic forces build up very quickly. Just as a magnetic can be used to move a metal object, so can magnetic forces torque or stress circuit components.

19

Page 20: cricuit breaker report

Under severe short circuit current conditions bus bars have been instantly ripped from their mountings, large cables have been whipped so violently as to have been pulled loose from their terminations. At the same time the slower thermal energy was melting sand in fuses into glass, while steel and copper metals were being heated so hot as to be turned into a superheated gas (the solid metal became a liquid and then a vapor).We tend occasionally to focus our attention on the electrical insulation aspects, while potentially forgetting magnetic and thermal effects under short circuit current conditions. The practice of securing big cables in place, so that they stay in place under short circuit current conditions with thin plastic like twine should be reconsidered. So to should the practice of tightening buss bar fasteners without the use of a torque wrench.Thermal EnergyExcessive current flowing in a circuit can result in heat related damage to electrical equipment. That is because a rise in current results in an increase in thermal energy.Mathematically speaking, a current increase results in a squared value increase in the amount of heat, that is, I squared T means that the higher the current the much greater the amount of heat that will be developed. Many years ago it was established that, an increase of only twenty degrees C. above the maximum rated temperature of an electrical insulator (motor windings) can reduce its life by as much as 50%.Electrical insulation can withstand only a limited amount of repeated overheating (much the same as structural stress cycles are cumulative) before it fails.Thermal Trip ElementWhen the circuit is required to be provided with a protective device for overload type conditions, a thermal time delay element is typically provided. The thermal element provides a time delay function called Inverse. That is to say, as the current flow in the circuit increases, heat begins to builds up in a BI-metal element, (that is made from two thin strips of different metal) and it begins to bow and cause the contacts of the breaker to open. These two metals are selected for their different rates of thermal expansion (heating) and contraction (cooling). Having been fused together by the manufacture, changes in their temperature results in them expanding and contracting in an arc, and not in a straight line. This movement allows them to be used as the source of the force needed to open the breaker’s contacts.Thermal elements require some of the heat to be dissipated before they can be reset after having tripped. This means that when a breaker trips on thermal element (due to a running overload) it may need a few minutes to cool off before it can be reset.Magnetic Trip ElementThe trip unit is the brain of the breaker. It consists of the components necessary to automatically open the circuit when an overcurrent is sensed. Generally a magnetic sensing element, or both a magnetic and a thermal sensing element will be included in the trip unit.When a breaker has only a magnetic sensing element, it is a non-delay instantaneous trip type. With this type of circuit breaker, no delay has been intentionally designed into its operation. These devices have a magnetic coil that surrounds a moveable plunger, which is held in place by a spring. The circuit current flows through the magnetic coil and when it produces a pull on the plunger greater than the retaining spring, it will move the plunger, which results in the device’s contacts opening.

20

Page 21: cricuit breaker report

When an OCPD has only a magnetic sensing element it will provide protection only from short circuit level currents and not from overload level currents. These types of devices are called motor circuit protectors (MCP). They are used when running overload protection is provided by a device such as a three phase motor starter with thermal overload relay-heater elements. When a circuit breaker has tripped on the magnetic element, they can be immediately reset. One should not reset a breaker more than twice without correcting the cause of the fault. To do so may result in serious personal injury.Hydraulic-Magnetic Trip ElementsSome brands of circuit breakers use a hydraulic fluid (silicone) type of current sensing element. With this type of sensor, a wire is coiled around an oil filled cylinder containing a piston, which is connected on one end to the breaker’s trip unit. This forms a magnetic coil through which load current flows. The piston is held in a position by a spring. When current flows in the coil, a magnetic field is created that pulls the piston deeper and deeper into the coil. As the current in the circuit increases, so does the coil’s magnetic field strength, the spring is compressed, drawing the piston deeper into the coil, increasing the coil’s magnetic field, as plunger movement progresses, the fluid tends to oppose rapid movement of the piston in the cylinder.By varying the fluid’s viscosity the manufacture can, alter the amount of opposing retarding force; this in turn allows the amount of time delay to be varied. By changing the size of the coil wire and number of wraps of the wire in the coil; the amount of force (MMF) created by the magnetic field can be changed (changing either or both the quantity of amps, or the number of turns of the wire changes the amount of pull produced by a electro-magnetic coil).Manufactures using this type of element design can offer the protection of a quick responding magnetic element and the time delay of a thermal element in their breakers with out using a bi-metal element.In this portion of the article; the following topics are covered:� Methods Of Mounting Circuit Breakers� Fixed Mounted Circuit Breakers� Removable Mounted Circuit Breakers� Drawout Mounted Circuit Breakers� Methods Of Securing Circuit Breakers� Stab Lock Type Circuit Breakers� Bolted Type Circuit Breakers� Din Rail Mounted Circuit Breakers

Methods Of Mounting Circuit BreakersFor our study purposes we will divide the methods used to mount circuit breakers into three general groups, those being: Fixed, Removable, and Drawout. A review of these mounting methods follows.Fixed Mounted Circuit BreakersA circuit breaker that is bolted in its enclosure and wired to the load frame, we can call a fixed mounted circuit breaker. These units are typically rated 600 volts or less and are front mountable. Power is provided to the breaker typically by wires or sectional type bus bars. Power feeding the circuit breaker must be turned off in order to physically remove the fixed mounted breaker.Removable Mounted Circuit Breakers

21

Page 22: cricuit breaker report

A removable circuit breaker has two parts, a base, which is bolted to and wired to the frame, and the actual breaker, which has insulated parts that electrically mate with the base. This means of mounting allows the unit to be replaced with out re-wiring the unit on the line side of the breaker. This type of mounting is typically used for breakers rated 600 volts or less.Drawout Mounted Circuit BreakersA drawout circuit breaker also has two parts, the base, which is bolted and wired to the frame and the actual breaker, which slides into and electrically mates with the base. This allows the unit to be replaced without having to turn off the power feeding the breaker. The load must be turned off in order to test, remove or replace the unit.As a safety feature these units are interlocked to automatically turn the power off just before removal of the breaker begins. By design, only the circuit breaker’s load must be turned off to remove the breaker. This method of mounting allows for a single breaker to be disconnected from the power supply. That is to say that it does not require that all of the power be disconnected from all of the breakers installed in the larger enclosure such as a motor control center.There are various designs used to facilitate the “racking-in”(installation) and “racking out”(withdrawal) of the draw out type circuit breaker. Commonly some form of jacking screw is used to initially move and thus electrically disengage the breaker, then a traveling trolley type of hoist (somewhat like a small boat winch) supports the breaker during removal and re-installation. A transient supporting device is necessary as these sizes of breakers are too heavy and too bulky to be safely moved into and out of position by one person.Methods Of Securing Circuit BreakersCircuit breakers are typically secured in place by one of the following methods:� Through bolts� Stab locked to the bus or some type of receptacle connection� Bolted to the bus� Din rail mounted

Stab Lock Type BreakersThis type of breaker employs a male-female type of plug & receptacle connection to a metal bus bar on one end. The opposite end of the breaker is mated to the enclosure housing and does not make electrical contact with the bus bar. These types of breakers are found in homes and light commercial applications installed in load centers. With this method of mounting some movement of the breaker is normal.This small amount of breaker case movement is typically 1/8 of an inch or less on the bus bar end. The circuit conductor termination lug may also exhibit some minor movement of the termination lug; again normally this movement is less than about 1/8 of an inch.Bolted Type BreakersWhen a longer service life breaker is wanted, a bolted type is typically used. These types have a metal tab (one for each phase) sticking out from one end that is bolted to the bus bar with a machine screw (bolt type fine threads and not sheet metal screw type steep pitch threads). When replacing these types of breakers, the retaining bolts or machine screws will have power on them unless power to the entire panel board has been removed.It is not un-common for some individuals to initially determine that it is necessary to replace these types of breakers with power still applied to the bus bars. I am not a

22

Page 23: cricuit breaker report

big fan of working any thing above 12 volts hot, for I have witnessed too many good folks get hurt doing what was initially anticipated as being a quick and simple task. When this type of breaker must be replaced with power still applied to the bus bars, it should be done only under strict safety procedures; using proper personnel protective equipment and double insulated tools (every day plastic handle screwdrivers must not be used). A detailed job safety analysis should be conducted before any hot work is undertaken. On more than one occasion I have witnessed some truly professionals conducting rehearsals of this type of activity several times until each safety step was done correctly. Take the time you need to be safe.Din Rail Mounted BreakersWith this method, a mounting rail is secured to the enclosure and the breaker is snapped onto the mounting rail. This allows for replacement to be made quickly as the device can be un-clipped and a new one clipped on to the DIN rail. Conductors for the supply and load are typically secured to the breaker using pressure connectors that are tightened by some type of threaded fastener. While not as easy to replace as say a stab-lock type breaker, it does allow for some saving of time, both during panel building and individual breaker replacement later on.The letters DIN stand for German Industry Standards. Din rails are available in more than one physical size. The DIN rail mounting method is increasingly replacing thru bolt, foot, and plate mounting methods once more commonly used.In this portion of the article, the following topics are covered:� Time Current Curves� Available Fault Current� Series Rated Devices� Selective Coordination� Line and Load Terminal Connections� Ambient Compensated Circuit Breakers

Time Current CurvesThe proper design of an electrical system involves many-detailed task, such as selection of the circuit breakers that will protect the conductors, equipment and people who operate the equipment. Proper selection, and coordination of breakers for a specific installed system is facilitated by the use of time current curves. Readingm these curves is quite technical and will not be covered in adequate detail to allow someone to properly select OCPD’s; my intention is to provide only a brief overview in this short paper.Time current curves are plots of the amount of current (vertical scale) flowing in the circuit to the time (horizontal scale) required for the breaker to clear the fault current.Curves are listed by some manufactures as being instantaneous, ultra-short, short, medium and long.Current limiting fuses have no moving parts, so no inertial forces need to be overcome for the fuse to open the circuit. Breakers on the other hand have parts that must be moved from one position to the other to open the circuit. Generally speaking fuses can open a circuit faster than can circuit breakers. Some solid-state components can be damaged beyond repair in less time than a breaker may be able to open the circuit. For this and other reasons, some types of electrical components are best protected by fuses and not breakers. Restated, you cannot always replace a fuse with a circuit breaker of the same voltage, and amperage values.

23

Page 24: cricuit breaker report

The time a circuit protective device operates can be divided into the following time segments: sensing time; magnetic elements are quicker than thermal elements (which intentionally add delay). opening time, fuses are quicker than breakers as they have no parts to move, and arcing time, the time during which an arc is present.Both fuses and breakers have to extinguish the resultant arc, and arc extinguishing time, the time the protective device takes to extinguish the faults arc, varies with the type of device, amperage rating, AIC rating, voltage, and the amount of short circuit or overload current developed.Available Fault CurrentWhen selecting circuit breakers it is important to know both the maximum continuous amperage and the available fault current. The NEC in article 110.9 provides the following guidance, “ Equipment intended to interrupt current at fault levels, shall have an interrupting rating sufficient for the nominal circuit voltage and the current that is available at the line terminals of the equipment. “ There are two methods commonly used to comply with this NE code requirement.The most conservative method is to select all OCPD’s based upon the fault current available at the electrical service (or source of supply). For example if 50,000 amps of fault current could be supplied to a building at the service, even the most distant (from the service) branch circuit breaker would be selected to have the ability to safely open the circuit with 50,000 amps of fault current, even though that amount of current would not be available to the line terminals of the most distant circuit protective device. Depending upon the specific nature (such as arcing, or a bolted low impedance type fault) of the fault, the total amount of fault current available may or may not be developed during operation of the nearest upstream protective device.Series Rated DevicesThe second method of breaker selection, which is more realistic and more economical, is to select the device based upon the level of fault current that engineering level calculations determine can be potentially available at the device's line terminals.One may question why spend the extra money purchasing breakers that have higher AIC than the system can deliver? When it is reasonable to anticipate that the power supply’s capacity will be increased, the initially more costly selection may be justified based upon anticipated system capacity growth.Available Fault CurrentWhen selecting circuit breakers it is important to know both the maximum continuousamperage and the available fault current. The NEC in article 110.9 provides the following guidance, “ Equipment intended to interrupt current at fault levels, shall have an interrupting rating sufficient for the nominal circuit voltage and the current that is available at the line terminals of the equipment. “ There are two methods commonly used to comply with this NE code requirement.The most conservative method is to select all OCPD’s based upon the fault current available at the electrical service (or source of supply). For example if 50,000 amps of fault current could be supplied to a building at the service, even the most distant(from the service) branch circuit breaker would be selected to have the ability to safely open the circuit with 50,000 amps of fault current, even though that amount of current would not be available to the line terminals of the most distant circuit protective device. Depending upon the specific nature (such as arcing, or a bolted low impedance type fault) of the fault, the total amount of fault current available may or may not be developed during operation of the nearest upstream protective device.

24

Page 25: cricuit breaker report

Series Rated DevicesThe second method of breaker selection, which is more realistic and moreeconomical, is to select the device based upon the level of fault current that engineering level calculations determine can be potentially available at the device's line terminals.One may question why spend the extra money purchasing breakers that have a higher AIC than the system can deliver? When it is reasonable to anticipate that the power supply’s capacity will be increased, the initially more costly selection may be justified based upon anticipated system capacity growth.Selective CoordinationSelective coordination is the selection and application of circuit protective devices in series such that under overload or fault current conditions, only the device just up stream from the overload, or fault will open to clear the fault. The remainder of the circuit’s protective devices will remain closed passing power to their individual loads.Selectivity can be based upon time or current levels. This method of selection allows two devices to be connected in series with each other, and seeing the same current level to respond in differing times, the one closest to the fault, with the shortest operating time would open the circuit. The device up stream from it while having the same current level trip point, would have a longer trip delay time, allowing the closer device to react first to open the protected circuit.If not properly coordinated, the device closest to the fault could have the longer time of response (both having the same current level trip values), and the next protective device up stream could open the circuit, resulting in a potentially more wide spread circuit outage to be experienced by the facility. When the breaker nearest the circuit’s faulted point does not trip, yet the one above it does, a review of the degree of coordination should be undertaken.Line and Load Terminal ConnectionsThe terminals (when installed in a vertical position) at the top of a breaker are for connection to the source of supply and are refereed to as the line connections (NEMA markings L-1, L-2, L-3, or IEC markings 11, 21,31). The terminals at the bottom of the breaker are for connection to the load (NEMA markings T-1, T-2, T-3, or IEC markings12, 22, 32). Most breakers must be installed with the source of supply connecting to the top terminals.Some breakers are listed such that they may be connected to the source of supply either at the top (line) or the bottom (load). These breakers can then be used in a back-fed type of application; that is power can be connected to the bottom (load) of the breaker and the breaker can be used to supply power via it’s line (top) connections to a bus bar. When a breaker is marked line or load, it must be installed in that manner only. That is line to the source of power and load terminations connected to the utilization equipment. The NEC requires that back-fed type breakers be so installed that it takes more than a pull on the breaker to remove it. See article 408.16 (F) of the 2002 edition.Ambient Compensated Circuit BreakersThere are some common installations where the electrical load to be protected will be located in an area that is subject to a different range of environmental conditions, particularly ambient temperature. An extreme example of this type would be where a fan motor is located in say a minus 40 degree ice cream freezer and its protective circuit breaker is located in a poorly ventilated motor control center room where the air temperature routinely exceeds 100 degrees F. during hot summer months. This

25

Page 26: cricuit breaker report

could result in the breaker’s thermal element trip point being reduced due to its hotter ambient.Were a motor to be placed in a hot environment (say a boiler room) and its circuit breaker be placed in an air conditioned space, the breaker may experience nuisance type tripping. To avoid temperature related offsets breakers are available with an ambient compensation feature. This allows the breaker to open the circuit, withoutdeviation caused by changes in the ambient air temperature within a listed ambient temperature range.In this portion of the article, the following topics are covered:� Insulated Case Circuit Breakers� Accessories� Shunt Trip� Auxiliary-Remote Alarm Switch� Ground Fault Sensor� Under Voltage Trip� Lock-Out-Tag-Out Provisions� Remote Operator Handle� Stored Energy Breaker Operator

Insulated Case Circuit Breakers (ICCB)This type of circuit breaker is assembled on a metal frame contained within an insulated case and is provided with air break contacts. Its intended use is as a component of larger installations such as switchboards and MCC type switchgear. Its components are larger and heavier for severe duty applications.The insulated case circuit breaker typically has a high short time withstand and high interrupting ratings. They are available today with both a local and a remote means of communication for setting of the various values, and facilitate such task as remote monitoring of electrical energy consumption and troubleshooting. The insulated case circuit breaker can be purchased today with any of a growing list of accessories, several of which are briefly reviewed in the following paragraphs.

Molded Case Circuit Breaker Maintenance (MCCB)MCCB have many years of life built into them, allowing for very little maintenance type attention be paid to them. This should not be taken as an indication that periodic maintenance is not required. NETA (InterNational Electrical TestingAssociation Inc.) has developed and published a book titled “Maintenance Testing Specifications (NETA-MTS-01) that provides some guidance as to how various types of electrical equipment, including MCCB, and ICCBs should be tested. Again you may have anticipated my next statement. I recommend that you obtain a copy for your reference. I know that books cost money, but not knowing how, or what to do cost a lot more money, so try and talk the boss into purchasing it for you. In the interim, the following is a quick overview of some MCCB maintenance task. It is recommended that at least once a year a qualified electrician, properly trained and equipped perform the following maintenance task:� Visually inspect the case to determine if any portion indicates overheating, replace the breaker if overheating indications are found.� Check connections for indications of overheating.� Cycle the breaker five times manually.� Check and record the voltage drop across the breaker using a calibrated digital voltmeter (capable of reading three places to the right of the decimal point).

26

Page 27: cricuit breaker report

� The load should be operated at full load for three hours, or until the breaker reaches normal load temperature, scan the breaker with an IR type non contact thermometer, record the readings.� Record voltages, and note any voltage imbalance from phase to phase.� Current readings should be taken with a true RMS type meter due to the increasing harmonic content in many electrical systems in commercial/industrial facilities today.� Current readings on equipment grounding conductors (where required) for specific machines should be noted. Clamp on type ground-rod circuit resistance reading meters should be used for this task as they can detect both the impedance and the level of current on the conductor (if any is present, as other clamp on type amp-meters will not indicate Ma levels).While breaker test sets are commercially available, they are for use on the larger frame size breakers. Generally molded case breakers 250 amps and under cannot be tested to confirm operation on their original time-current curves. Testing of the larger frame power type breakers is a very specialized area, requiring special training and test equipment and should be conducted only by competent personnel.In this portion of the article, the following topics are covered:� Microcomputer Circuit Breakers� Field Selectable Rating Circuit Breakers� Operation Overview� Current Sensing� Continuous Amps� Long Time Delay� Short Time Pick-up� Short Time Delay� Instantaneous Current Pick-up Trip� Ground Fault Current� Ground Fault Pick-up� Ground Fault Delay� Visual Annunciation-indication Lamps� Power Consumption Monitoring

TYPE OF CIRCUIT BREAKERS

1. OIL CIRCUIT BREAKER2. SF6 CIRCUIT BREAKER3. VACCUME CIRCUIT BREAKER

OIL CIRCUIT BREAKER

Operation of Oil Circuit Breaker

27

Page 28: cricuit breaker report

The operation of oil circuit breaker is quite simple let’s have a discussion. When the current carrying contacts in the oil are separated an arc is established in between the separated contacts.

Actually, when separation of contacts has just started, distance between the current contacts is small as a result the voltage gradient between contacts becomes high. This high voltage gradient between the contacts ionized the oil and consequently initiates arcing between the contacts. This arc will produce a large amount of heat in surrounding oil and vaporizes the oil and decomposes the oil in mostly hydrogen and a small amount of methane, ethylene and acetylene. The hydrogen gas can not remain in molecular form and it is broken into its atomic form releasing lot of heat. The arc temperature may reach up to 5000° K. Due to this high temperature the gas is liberated surround the arc very rapidly and forms an excessively fast growing gas bubble around the arc. It is found that the mixture of gases occupies a volume about one thousand times that of the oil decomposed. From this figure we can assume how fast the gas bubble around the arc will grow in size. If this growing gas bubble around the arc is compressed by any means then rate of de – ionization process of ionized gaseous media in between the contacts will accelerate which rapidly increase the dielectric strength between the contacts and consequently the arc will be quenched at zero crossing of the current cycle. This is the basic operation of oil circuit breaker. In addition to that cooling effect of hydrogen gas surround the arc path also helps, the quick arc quenching in oil circuit breaker.

Types of Oil Circuit Breakers

There are mainly two types of oil circuit breakers available-

Bulk Oil Circuit Breaker or BOCB

Bulk oil circuit breaker or BOCB is such types of circuit breakers where oil is used as arc quenching media as well as insulating media between current carrying contacts and earthed parts of the breaker. The oil used here is same as transformer insulating oil.

Minimum Oil Circuit Breaker or MOCB

These types of circuit breakers utilize oil as the interrupting media. However, unlike bulk oil circuit breaker, a minimum oil circuit breaker places the interrupting unit in insulating chamber at live potential. The insulating oil is available only in interrupting chamber. The features of designing MOCB is to reduce requirement of oil, and hence these breaker are called minimum oil circuit breaker.

Bulk Oil Circuit Breaker

28

Page 29: cricuit breaker report

Construction of Bulk Oil Circuit Breaker

The basic construction of bulk oil circuit breaker is quite simple. Here all moving contacts and fixed contacts are immerged in oil inside closed iron vessel or iron tank. Whenever the current carrying contacts are being open within the oil the arc is produced in between the separated contacts. The large energy will be dissipated from the arc in oil which vaporizes the oil as well as decomposes it. Because of that a large gaseous pressure is developed inside the oil which tries to displace the liquid oil from surrounding of the contacts. The inner wall of the oil tank has to withstand this large pressure of the displaced oil. Thus the oil tank of bulk oil circuit breaker has to be sufficiently strong in construction. An air cushion is necessary between the oil surface and tank roof to accommodate the displaced oil when gas forms around the arc. That is why the oil tank is not totally filled up with oil it is filled up to certain level above which the air is tight in the tank. The breaker tank top cover should be securely bolted on the tank body and total breaker must be properly locked with foundation otherwise it may jump out during interruption of high fault current. In these type of equipment where expansible oil is enclosed in an air tight vessel (oil tank) there must be a gas vent fitted on the tank cover. Naturally some form of gas vent always is provided on the cover of bulk oil circuit breaker tank. This is very basic features for construction of bulk oil circuit breaker.

Arc Quenching in Bulk Oil Circuit Breaker

A pot or cross jet pot. The principle of operation of cross jet pot is quite simple let’s have a discussion. The pressure developed by the vaporization and dissociation of the oil is retained in the side vented explosive pot by withdrawing the moving contact through a stack of insulating plates having a minimum radial clearance around the contact. Thus there is practically no release of pressure until the moving contact uncovers one of the side vents. The compressed hydrogen gas can then escape across the arc path, thus exerting a powerful cooling action on the ionized column.

29

Page 30: cricuit breaker report

When the current zero is reached, the post arc resistance increased rapidly due this cooling action. At higher breaking currents larger will be the pressure generated and a bulk oil circuit breaker gives its best performance at the highest current within its rating. These single break bulk oil circuit breaker may have problem during clearing low currents such as load current of the breaker.

Various improvement in the design of pressure chamber or side vented explosive chamber have been suggested to overcome the problem of low current interruption. One solution of this is providing a supplementary oil chamber below the side vents. This supplementary oil chamber is known as compensating chamber which provides fresh source of oil to be vaporized in order to feed more clean gas back across the arc path during clearing low current.

Double Break Bulk Oil Circuit Breaker

Various improvements in the design of bulk oil circuit breaker have been suggested to satisfactory and safe arc interruption especially at currents below the rated maximum. One solution to this problem is to use an intermediate contact between tow current carrying contacts. The arc is here split into two parts in series. The aim here is to extinguish the second arc quickly by using the gas pressure and oil momentum due to the first arc. In double break bulk oil circuit breaker, there are two fixed contact and are bridged by one moving contact. The moving contact is fitted with driving mechanism of the oil circuit breaker by means of an insulated rod. As the moving contact bridge moves downwards the contact gaps are created with fixed contacts at both end of the intermediate moving contact bridge. Hence arcs are produced at both contacts gap.

Minimum Oil Circuit Breaker

30

Page 31: cricuit breaker report

As the volume of the oil in bulk oil circuit breaker is huge, the chances of fire hazard in bulk oil system are more. For avoiding unwanted fire hazard in the system, one important development in the design of oil circuit breaker has been introduced where use of oil in the circuit breaker is much less than that of bulk oil circuit breaker. It has been decided that the oil in the circuit breaker should be used only as arc quenching media not as an insulating media. Then the concept of minimum oil circuit breaker comes. In this type of circuit breaker the arc interrupting device is enclosed in a tank of insulating material which as a whole is at live potential of system. This chamber is called arcing chamber or interrupting pot. The gas pressure developed in the arcing chamber depends upon the current to be interrupted. Higher the current to be interrupted causes larger the gas pressure developed in side the chamber, hence better the arc quenching. But this put a limit on the design of the arc chamber for mechanical stresses. With use of better insulating materials for the arcing chambers such as glass fiber, reinforced synthetic resin etc, the minimum oil circuit breaker are able to meet easily the increased fault levels of the system.

Working Principle or Arc Quenching in Minimum Oil Circuit Breaker

Working Principle of minimum oil circuit breaker or arc quenching in minimum oil circuit breaker is described below. In a minimum oil circuit breaker, the arc drawn across the current carrying contacts is contained inside the arcing chamber.

Hence the hydrogen bubble formed by the vaporized oil is trapped inside the chamber. As the contacts continue to move, after its certain travel an exit vent becomes available for exhausting the trapped hydrogen gas. There are two different types of arcing chamber is available in terms of venting are provided in the arcing chambers. One is axial venting and other is radial venting. In axial venting, gases (mostly Hydrogen), produced due to vaporization of oil and decomposition of oil during arc, will sweep the arc in axial or longitudinal direction.

Let’s have a look on working principle Minimum Oil Circuit Breaker with axial venting arc chamber.

31

Page 32: cricuit breaker report

The moving contact has just been separated and arc is initiated in MOCB.

The ionized gas around the arc sweep away through upper vent and cold oil enters into the arcing chamber through the lower vent in axial direction as soon as the moving contact tip crosses the lower vent opening and final arc quenching in

32

Page 33: cricuit breaker report

minimum oil circuit breaker occurs.

The cold oil occupies the gap between fixed contact and moving contact and the minimum oil circuit breaker finally comes into open position.

Whereas in case of radial venting or cross blast, the gases (mostly Hydrogen) sweep the arc in radial or transverse direction.

The axial venting generates high gas pressure and hence has high dielectric strength, so it is mainly used for interrupting low current at high voltage.

On the other hand radial venting produces relatively low gas pressure and hence low dielectric strength so it can be used for low voltage and high current interruption. Many times the combination of both is used in minimum oil circuit breaker so that the chamber is equally efficient to interrupt low current as well as high current. These types of circuit breaker are available up to 8000 MVA at 245 KV.

33

Page 34: cricuit breaker report

SF6 CIRCUIT BREAKERS

A circuit breaker in which the current carrying contacts operate in sulphur hexafluoride or SF6 gas is known as an SF6 circuit breaker. SF6 has excellent insulating property. SF6 has high electro-negativity. That means it has high affinity of absorbing free electron. Whenever a free electron collides with the SF6 gas molecule, it is absorbed by that gas molecule and forms a negative ion.

The attachment of electron with SF6 gas molecules may occur in two different ways,

These negative ions obviously much heavier than a free electron and therefore over all mobility of the charged particle in the SF6 gas is much less as compared other common gases. We know that mobility of charged particle is majorly responsible for conducting current through a gas.

34

Page 35: cricuit breaker report

Hence, for heavier and less mobile charged particles in SF6 gas, it acquires very high dielectric strength. Not only the gas has a good dielectric strength but also it has the unique property of fast recombination after the source energizing the spark is removed. The gas has also very good heat transfer property. Due to its low gaseous viscosity (because of less molecular mobility) SF6 gas can efficiently transfer heat by convection. So due to its high dielectric strength and high cooling effect SF6 gas is approximately 100 times more effective arc quenching media than air. Due to these unique properties of this gas SF6 circuit breaker is used in complete range of medium voltage and high voltage electrical power system. These circuit breakers are available for the voltage ranges from 33KV to 800KV and even more.

Disadvantages of SF6 CB

The SF6 gas is identified as a greenhouse gas, safety regulation are being introduced in many countries in order to prevent its release into atmosphere.

35

Page 36: cricuit breaker report

Puffer type design of SF6 CB needs a high mechanical energy which is almost five times greater than that of oil circuit breaker.

Types of SF6 Circuit Breaker

There are mainly three types of SF6 CB depending upon the voltage level of application-

1. Single interrupter SF6 CB applied for up to 245 KV(220 KV) system.2. Two interrupter SF6 CB applied for up to 420 KV(400 KV) system.

3. Four interrupter SF6 CB applied for up to 800 KV(715 KV) system.

Working of SF6 Circuit Breaker

The working of SF6 CB of first generation was quite simple it is some extent similar to air blast circuit breaker. Here SF6 gas was compressed and stored in a high pressure reservoir. During operation of SF6 circuit breaker this highly compressed gas is released through the arc in breaker and collected to relatively low pressure reservoir and then it pumped back to the high pressure reservoir for re utilize.

36

Page 37: cricuit breaker report

The working of SF6 circuit breaker is little bit different in modern time. Innovation of puffer type design makes operation of SF6 CB much easier. In buffer type design, the arc energy is utilized to develop pressure in the arcing chamber for arc quenching.

Here the breaker is filled with SF6 gas at rated pressure. There are two fixed contact fitted with a specific contact gap. A sliding cylinder bridges these to fixed contacts. The cylinder can axially slide upward and downward along the contacts. There is one stationary piston inside the cylinder which is fixed with other stationary parts of the SF6 circuit breaker, in such a way that it can not change its position during the movement of the cylinder. As the piston is fixed and cylinder is movable or sliding, the internal volume of the cylinder changes when the cylinder slides.

37

Page 38: cricuit breaker report

During opening of the breaker the cylinder moves downwards against position of the fixed piston hence the volume inside the cylinder is reduced which produces compressed SF6 gas inside the cylinder. The cylinder has numbers of side vents which were blocked by upper fixed contact body during closed position. As the cylinder move further downwards, these vent openings cross the upper fixed contact, and become unblocked and then compressed SF6 gas inside the cylinder will come out through this vents in high speed towards the arc and passes through the axial hole of the both fixed contacts. The arc is quenched during this flow of SF6 gas.

During closing of the circuit breaker, the sliding cylinder moves upwards and as the position of piston remains at fixed height, the volume of the cylinder increases which introduces low pressure inside the cylinder compared to the surrounding. Due to this pressure difference SF6 gas from surrounding will try to enter in the cylinder. The higher pressure gas will come through the axial hole of both fixed contact and enters into cylinder via vent and during this flow; the gas will quench the arc.

VACCUM CIRCUIT BREAKER

A vacuum circuit breaker is such kind of circuit breaker where the arc quenching takes place in vacuum. The technology is suitable for mainly medium voltage application. For higher voltage vacuum technology has been developed but not commercially viable. The operation of opening and closing of current carrying contacts and associated arc interruption take place in a vacuum chamber in the breaker which is called vacuum interrupter. The vacuum interrupter consists of a

38

Page 39: cricuit breaker report

steel arc chamber in the centre symmetrically arranged ceramic insulators. The vacuum pressure inside a vacuum interrupter is normally maintained at 10 – 6 bar.

The material used for current carrying contacts plays an important role in the performance of the vacuum circuit breaker. CuCr is the most ideal material to make VCB contacts. Vacuum interrupter technology was first introduced in the year of 1960. But still it is a developing technology. As time goes on, the size of the vacuum interrupter is being reducing from its early 1960’s size due to different technical developments in this field of engineering. The contact geometry is also improving with time, from butt contact of early days it gradually changes to spiral shape, cup shape and axial magnetic field contact. The vacuum circuit breaker is today recognized as most reliable current interruption technology for medium voltage switchgear. It requires minimum maintenance compared to other circuit breaker technologies.

Advantages of Vacuum Circuit Breaker or VCB

Service life of vacuum circuit breaker is much longer than other types of circuit breakers. There is no chance of fire hazard as oil circuit breaker. It is much environment friendly than SF6 Circuit breaker. Beside of that contraction of VCB is much user friendly. Replacement of vacuum interrupter (VI) is much convenient.

Operation of Vacuum Circuit Breaker

The main aim of any circuit breaker is to quench arc during current zero crossing, by establishing high dielectric strength in between the contacts so that reestablishment of arc after current zero becomes impossible. The dielectric strength of vacuum is eight times greater than that of air and four times greater than that of SF6 gas. This high dielectric strength makes it possible to quench a vacuum arc within very small contact gap. For short contact gap, low contact mass and no compression of medium the drive energy required in vacuum circuit breaker is minimum. When two face to face contact areas are just being separated to each other, they do not be separated instantly, contact area on the contact face is being reduced and ultimately comes to a point and then they are finally de-touched. Although this happens in a fraction of micro second but it is the fact. At this instant of de-touching of contacts in a vacuum, the current through the contacts concentrated on that last contact point on the contact surface and makes a hot spot. As it is vacuum, the metal on the contact surface is easily vaporized due to that hot spot and create a conducting media for arc path. Then the arc will be initiated and continued until the next current zero.

39

Page 40: cricuit breaker report

At current zero this vacuum arc is extinguished and the conducting metal vapor is re-condensed on the contact surface. At this point, the contacts are already separated hence there is no question of re-vaporization of contact surface, for next cycle of current. That means, the arc cannot be reestablished again. In this way vacuum circuit breaker prevents the reestablishment of arc by producing high dielectric strength in the contact gap after current zero.

There are two types of arc shapes. For interrupting current up to 10 kA, the arc remains diffused and the form of vapor discharge and cover the entire contact surface. Above 10 kA the diffused arc is constricted considerably by its own magnetic field and it contracts. The phenomenon gives rise over heating of contact at its center. In order to prevent this, the design of the contacts should be such that the arc does not remain stationary but keeps travelling by its own magnetic field. Specially designed contact shape of vacuum circuit breaker make the constricted stationary arc travel along the surface of the contacts, thereby causing minimum and uniform contact erosion.

40

Page 41: cricuit breaker report

Air Blast Circuit Breaker

This type of circuit breakers, is those kind of circuit breaker which operates in air at atmospheric pressure. After development of oil circuit breaker, the medium voltage air circuit breaker (ACB) is replaced completely by oil circuit breaker in different countries. But in countries like France and Italy, ACBs are still preferable choice up to voltage 15 KV. It is also good choice to avoid the risk of oil fire, in case of oil circuit breaker. In America ACBs were exclusively used for the system up to 15 KV until the development of new vacuum and SF6 circuit breakers.

Working Principle of Air Circuit Breaker

The working principle of this breaker is rather different from those in any other types of circuit breakers. The main aim of all kind of circuit breaker is to prevent the reestablishment of arcing after current zero by creating a situation where in the contact gap will withstand the system recovery voltage. The air circuit breaker does the same but in different manner. For interrupting arc it creates an arc voltage in excess of the supply voltage. Arc voltage is defined as the minimum voltage required maintaining the arc. This circuit breaker increases the arc voltage by mainly three different ways,

1. It may increase the arc voltage by cooling the arc plasma. As the temperature of arc plasma is decreased, the mobility of the particle in arc plasma is reduced, hence more voltage gradient is required to maintain the arc.

2. It may increase the arc voltage by lengthening the arc path. As the length of arc path is increased, the resistance of the path is increased, and hence to maintain the same arc current more voltage is required to be applied across the arc path. That means arc voltage is increased.

3. Splitting up the arc into a number of series arcs also increases the arc voltage.

Types of ACB

There are mainly two types of ACB are available.

1. Plain air circuit breaker. 2. Air blast Circuit Breaker.

Operation of ACB The first objective is usually achieved by forcing the arc into contact with as large an area as possible of insulating material. Every air circuit breaker is fitted with a chamber surrounding the contact. This chamber is called ‘arc chute’. The arc is driven into it. If inside of the arc chute is suitably shaped, and if the arc can be made conform to the shape, the arc chute wall will help to achieve cooling. This type of arc chute should be made from some kind of refractory material. High temperature plastics reinforced with glass fiber and ceramics are preferable materials for making arc chute.

41

Page 42: cricuit breaker report

The second objective that is lengthening the arc path, is achieved concurrently with fist objective. If the inner walls of the arc chute is shaped in such a way that the arc is not only forced into close proximity with it but also driven into a serpentine channel projected on the arc chute wall. The lengthening of the arc path increases the arc resistance.

The third technique is achieved by using metal arc slitter inside the arc chute. The main arc chute is divided into numbers of small compartments by using metallic separation plates. These metallic separation plates are actually the arc splitters and each of the small compartments behaves as individual mini arc chute. In this system the initial arc is split into a number of series arcs, each of which will have its won mini arc chute. So each of the split arcs has its won cooling and lengthening effect due to its won mini arc chute and hence individual split arc voltage becomes high. These collectively, make the over all arc voltage, much higher than the system voltage.

This was working principle of air circuit breaker now we will discuss in details the operation of ACB in practice.

The air circuit breaker, operated within the voltage level 1 KV, does not require any arc control device. Mainly for heavy fault current on low voltages (low voltage level above 1 KV) ABCs with appropriate arc control device, are good choice. These breakers normally have two pairs of contacts. The main pair of contacts carries the current at normal load and these contacts are made of copper. The additional pair is the arcing contact and is made of carbon. When circuit breaker is being opened, the main contacts open first and during opening of main contacts the arcing contacts are still in touch with each other. As the current gets, a parallel low resistive path through the arcing contact during opening of main contacts, there will not be any arcing in the main contact. The arcing is only initiated when finally the arcing contacts are separated. The each of the arc contacts is fitted with an arc runner which helps, the arc discharge to move upward due to both thermal and electromagnetic effects as shown in the figure. As the arc is driven upward it enters in the arc chute, consisting of splitters. The arc in chute will become colder, lengthen and split hence arc voltage becomes much larger than system voltage at the time of operation of air circuit

breaker, and therefore the arc is quenched finally during the current zero.Although this type of circuit breakers have become obsolete for medium voltage application, but they are still preferable choice for high current rating in low voltage application.

Air Blast Circuit Breaker

42

Page 43: cricuit breaker report

These types of air circuit breaker were used for the system voltage of 245 KV, 420 KV and even more, especially where faster breaker operation was required. Air blast circuit breaker has some specific advantages over oil circuit breaker which are listed as follows,

1. There is no chance of fire hazard caused by oil.2. The breaking speed of circuit breaker is much higher during operation of air

blast circuit breaker.

3. Arc quenching is much faster during operation of air blast circuit breaker.

4. The duration of arc is same for all values of small as well as high currents interruptions.

5. As the duration of arc is smaller, so lesser amount of heat realized from arc to current carrying contacts hence the service life of the contacts becomes longer.

6. The stability of the system can be well maintained as it depends on the speed of operation of circuit breaker.

7. Requires much less maintenance compared to oil circuit breaker.

There are also some disadvantages of air blast circuit breakers-

1. In order to have frequent operations, it is necessary to have sufficiently high capacity air compressor.

2. Frequent maintenance of compressor, associated air pipes and automatic control equipments is also required.

3. Due to high speed current interruption there is always a chance of high rate of rise of re-striking voltage and current chopping.

4. There also a chance of air pressure leakage from air pipes junctions.

As we said earlier that there are mainly two types of ACB, plain air circuit breaker and air blast circuit breaker. But the later can be sub divided further into three different categories.

1. Axial Blast ACB.2. Axial Blast ACB with side moving contact.

3. Cross Blast ACB.

43

Page 44: cricuit breaker report

Axial Blast Air Circuit Breaker

In axial blast ACB the moving contact is in contact with fixed contact with the help of a spring pressure as shown in the figure. There is a nozzle orifice in the fixed contact which is blocked by tip of the moving contact at normal closed condition of the breaker. When fault occurs, the high pressure air is introduced into the arcing chamber. The air pressure will counter the spring pressure and deforms the spring hence the moving contact is withdrawn from the fixed contact and nozzle hole becomes open. At the same time the high pressure air starts flowing along the arc through the fixed contact nozzle orifice. This axial flow of air along the arc through the nozzle orifice will make the arc lengthen and colder hence arc voltage become much higher than system voltage that means system voltage is insufficient to sustain the arc consequently the arc is quenched.

44

Page 45: cricuit breaker report

REFERENCE:

1. www.electrical4u.com/circuitbreaker 2. www.fadduengineers.com/operationofcircuitbreakers 3. www.bookstore.in/electricals 4. www.google.co.in/oilcircuitbreaker