Creating Performance Curves for VRF System

download Creating Performance Curves for VRF System

of 8

Transcript of Creating Performance Curves for VRF System

  • 8/22/2019 Creating Performance Curves for VRF System

    1/8

    39 | P a g e

    4.2.3 Creating Performance Curves for VRF System

    In order to simulate the performance of AC System Energy plus need the performance

    curves of the system. The performance of a VRF AC system is based on multiple

    performance characteristics.

    The cooling model inputs for a VRF AC system are:

    Rated Total Cooling Capacity 5.2 kW

    Rated Cooling COP 3.25

    Minimum Outdoor Temperature inCooling Mode

    -5 OC

    Maximum Outdoor Temperature inCooling Mode

    46 OC

    Cooling Capacity Ratio ModifierFunction of Low Temperature Curve

    NameDaikinCAPFTLow

    Cooling Capacity Ratio BoundaryCurve Name

    VRFBoundary

    Cooling Capacity Ratio ModifierFunction of High Temperature Curve

    NameDaikinCAPFTHi

    Cooling Energy Input Ratio ModifierFunction of Low TemperatureCurveName

    DaikinEIRFTLow

    Cooling Energy Input Ratio BoundaryCurve Name

    VRFBoundary

    Cooling Energy Input Ratio ModifierFunction of High TemperatureCurveName

    DakinEIRFTHi

    Cooling Energy Input Ratio ModifierFunction of Low Part-Load RatioCurveName

    CoolingPLR

    Cooling Part-Load FractionCorrelation Curve Name

    PLRFraction

  • 8/22/2019 Creating Performance Curves for VRF System

    2/8

    40 | P a g e

    Full-load performance data defines the variations of capacity and power when outdoor

    or indoor conditions changes. Part-load performance identifies how the capacity and

    power change when variable compressor changes speed.

    Table 9Capacity Table of Inverter based VRF AC

    AFR 16.8

    BF 0.29

    INDOOREWB C 14 16 18 19 22 24

    EDB C 20 22 25 27 30 32

    OUTDOORTEMPERATURE

    (CDB)

    20

    TC 5.33 5.57 5.81 5.93 6.29 6.53

    SHC 3.84 3.77 3.93 4.13 3.97 3.86

    PI 1.23 1.23 1.24 1.25 1.26 1.26

    25

    TC 5.09 5.32 5.56 5.68 6.04 6.28

    SHC 3.71 3.65 3.82 4.02 3.88 3.78

    PI 1.35 1.35 1.36 1.36 1.37 1.38

    30

    TC 4.84 5.08 5.32 5.44 5.8 6.04

    SHC 3.59 3.54 3.71 3.92 3.79 3.69

    PI 1.46 1.47 1.48 1.48 1.49 1.5

    32

    TC 4.75 4.99 5.23 5.35 5.7 5.94

    SHC 3.54 3.49 3.67 3.87 3.75 3.66

    PI 1.51 1.52 1.53 1.53 1.54 1.55

    35

    TC 4.6 4.84 5.08 5.2 5.56 5.8

    SHC 3.47 3.42 3.6 3.81 3.7 3.61

    PI 1.58 1.59 1.6 1.6 1.61 1.62

    40

    TC 4.36 4.6 4.84 4.96 5.32 5.56SHC 3.35 3.31 3.5 3.71 3.61 3.53

    PI 1.7 1.71 1.71 1.72 1.73 1.74

  • 8/22/2019 Creating Performance Curves for VRF System

    3/8

    41 | P a g e

    Table 9 shows typical information provided by manufacturer of the system which is

    used in this study, using tabular representations. From this information, full-load

    capacity and power performance curves can be developed.

    The data here is presented as an absolute value Tabular data with rated condition

    highlighted, as shown in Table 9 (i.e., 5.2 kW rated total capacity, 3.81 rated Sensible

    Heat capacity and 1.6 kW rated power).

    4.2.3.1 Cooling Performance Curves

    The operating capacity of the VRF system is calculated based on the rated cooling

    capacity and the actual operating conditions. The operating conditions describing

    cooling performance are outdoor dry-bulb (DB) temperature entering the condenser

    and average indoor wet-bulb (IWB) temperature entering the active zone terminal

    units. The first step in defining cooling performance is plotting the manufacturers

    data from Table 9 to represent the relation of cooling capacity with Indoor WBT and

    outdoor DBT.

    Figure 21 Cooling Capacity Ratio as a Function of Outdoor Drybulb and Indoor WetbulbTemperature

    It is evident from the plotted manufacturers data in Figure 21 that the system

    performance behavior changes at 30 0C.

    0.80

    0.85

    0.90

    0.95

    1.00

    1.05

    1.10

    1.15

    1.20

    1.25

    1.30

    20 25 30 32 35 40

    CoolingCapacityRat

    io

    Outdoor Drybulb Temperature

    14

    16

    18

    19

    22

    24

    Indoor

    Wetbulb

  • 8/22/2019 Creating Performance Curves for VRF System

    4/8

    42 | P a g e

    We can therefore conclude that the boundary curve equation for our system can be

    defined as =30 and the corresponding energy Plus class object definition is

    shown in theFigure 22.

    Figure 22Input values of Boundary curve object

    . A typical cooling capacity curve equation is given below

    = +, +,+() +() ++,()

    Where:

    CAPFT= heat pump Cooling Capacity Ratio Modifier

    TWB,i= wet-bulb temperature of the air entering the cooling coil.

    a f = equation coefficients for Cooling Capacity Ratio Modifier

    TC= Temperature of the air entering the condenser

    The equation for the simulation model is generated by following algorithm defined

    below.

    1) Sorting the manufacturers' data in the tabular form of CAPFT, Indoor Wet

    Bulb, and Outdoor Dry Bulb.

    2) Prepare the data and compute the values for (WB2), (DB2) and (WB*DB)

    3) The equation is generated using a regression analysis tool called Eureqa

    Formulize developed by Nutonian which is a scientific data mining software

    package that searches for mathematical patterns hidden in a data set.

  • 8/22/2019 Creating Performance Curves for VRF System

    5/8

    43 | P a g e

    Since the cooling capacity of the system cannot be defined by single curve, two

    different equations have been generated for high and low outdoor dry bulb

    temperature

    (i)Cooling Capacity Ratio Modifier Function of LowTemperatures

    Select the data from Table 9 that represent the cooling capacity ratio at low outdoor

    temperatures (i.e., data to the left of and including the boundary curve inFigure 21)

    and organize the indoor and outdoor temperatures according to the fundamental form

    of the CAPFT equation. The tabular data given by the manufacturer is in the form

    capacity(kW), in order to obtain the capacity curves the data must be converted to a

    cooling capacity ratio term (i.e., the data must be normalized).

    Table 10Regression Analysis for Creating Cooling Performance curve

    CAPFT IWB IWB^2 DB DB^2 IWB*DB Predicted

    CAPFT

    1.025 14 196 20 400 280 1.02517

    0.978846 14 196 25 625 350 0.977386

    0.930769 14 196 30 900 420 0.930878

    1.071154 16 256 20 400 320 1.07123

    1.023077 16 256 25 625 400 1.02345

    0.976923 16 256 30 900 480 0.976942

    1.117308 18 324 20 400 360 1.1173

    1.069231 18 324 25 625 450 1.06951

    1.023077 18 324 30 900 540 1.02301

    1.140385 19 361 20 400 380 1.14033

    1.092308 19 361 25 625 475 1.09255

    1.046154 19 361 30 900 570 1.04604

    1.209615 22 484 20 400 440 1.20942

    1.161538 22 484 25 625 550 1.161641.115385 22 484 30 900 660 1.11513

    1.255769 24 576 20 400 480 1.25549

    1.207692 24 576 25 625 600 1.2077

    1.161538 24 576 30 900 720 1.1612

  • 8/22/2019 Creating Performance Curves for VRF System

    6/8

    44 | P a g e

    To do so we use the rated conditions as the reference point and Divide all capacity

    data by the Rated Total Cooling Capacity to yield cooling capacity ratio. Table below

    shows a typical spreadsheet layout of this data.

    = 0.906616945+0.02303191162 +2.552047779

    ( 2) 0.01070512808

    Table 11 Statistical data of Generated Cooling Performance Equation

    R^2 Goodness of Fit 0.999

    Correlation Coefficient 0.999

    Maximum Error 0.001

    Mean Squared Error 1.64E-07

    Mean Absolute Error 2.44 E-04

    (ii)Cooling Capacity Ratio Modifier Function of HighTemperatures

    Similar analysis is done to create Cooling Capacity Ratio Modifier Function of High

    Temperatures and following equation is obtained

    =0.885+ 0.0231 IWB 0.009425 DB

    R^2 Goodness of Fit 0.999

    Correlation Coefficient 0.999

    Maximum Error 0.001

    Mean Squared Error 2.38E-07

    Mean Absolute Error 0.000272

    4.2.3.2 Cooling Energy Input Ratio Modifier

    The method used to create performance curve coefficients for cooling energy input

    ratio modifier function of temperatures is identical to the method used for cooling

    capacity ratio. Table 12 below shows the power input ratio data extracted from

    capacity tables provide by manufacturer. This data is normalized to the rated power

    input in order to create the performance curves.

  • 8/22/2019 Creating Performance Curves for VRF System

    7/8

    45 | P a g e

    Table 12 Input Power Ratio Normalized to Rated Power

    IWB 14 16 18 19 22 24

    ODB Power ratio

    20 0.768750 0.76875 0.775 0.78125 0.7875 0.7875

    25 0.843750 0.84375 0.85 0.85 0.85625 0.8625

    30 0.912500 0.91875 0.925 0.925 0.93125 0.9375

    32 0.943750 0.95 0.95625 0.95625 0.9625 0.96875

    35 0.987500 0.99375 1 1 1.00625 1.0125

    40 1.062500 1.06875 1.06875 1.075 1.08125 1.0875

    Figure 23 Manufacturer's Data of Cooling Energy Input Ratio

    0.76

    0.86

    0.96

    1.06

    20 25 30 32 35 40

    PowerInputRatio

    Outdoor Dry Bulb Temperature

    14

    16

    18

    19

    22

    24

    IWB

  • 8/22/2019 Creating Performance Curves for VRF System

    8/8

    46 | P a g e

    It is evident from the cooling energy input data plotFigure 23 that performance of the

    system changes at the outdoor temperature of 30 OC Therefore same boundary curve

    from cooling capacity curve is used The following equations are obtained from the

    analysis of manufacturers performance data.

    =0.4802+0.01317 +5.854 +3.169

    R^2 Goodness of Fit 0.999035

    Correlation Coefficient 0.99957

    Maximum Error 0.003891

    Mean Squared Error 3.49E-06

    Mean Absolute Error 0.001406

    = = 0.4355+ 0.01484 + 0.002364

    R^2 Goodness of Fit 0.999525

    Correlation Coefficient 0.999767

    Maximum Error 0.003136

    Mean Squared Error 1.62E-06