Creating Log in Account as Administrator in LabView DSC

download Creating Log in Account as Administrator in LabView DSC

of 24

Transcript of Creating Log in Account as Administrator in LabView DSC

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    1/24

    Creating log in account as administrator in LabView DSC

    1. Project Explorer >> Tool >> Security >> Domain Account Manager

    2. File >> New >> Local domain

    3. Under Domain Properties window, set Domain name as administrator and click OK.Then set the desired password.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    2/24

    4. After setting of Domain name and password is done, the following screen will beappeared.

    5. Then go back to NI Distributed System Manager (DSM) and click Action >> Log In.Then you will see Logged in as: administrator at the bottom of the DSM window.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    3/24

    Creating new Project in Labview DSC using ModBus I/O

    1. Please make sure that Anti-Virus and Firewall are disabled before running LV DSC andModBus OPC Server.

    2. Open Labview and click empty project.3. In Project Explorer, right click on My Computer >> New >> Library

    4. Right click to Untitled Library >> Save >> Save. Then choose the desired location and filename.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    4/24

    5. Right click on Library >> New >> I/O Server.

    6. Choose Modbus and click Continue.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    5/24

    7. Set the Modbus I/O Server setting according to the PC setting and click OK.

    i) To check the PC setting, go to Control Panel >> Hardware and Sound >> DeviceManager.

    ii) Find Ports (COM & LPT)iii)Right click on ATEN USB to Serial Bridge >> Port Settings

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    6/24

    8. Check the Energy Meter setting and it must be the same setting as the Modbus I/O ServerSetting.

    9. Right click on Library >> New >> Variable.

    10. Set the variable name and click on Enable Aliasing check box and click Browse. Thefollowing figure will be appeared.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    7/24

    11.Choose the range of F400001-F465534 for voltage and power in this example. Click OK.12.Set F400010 for Voltage variable and F400008 for Power Variable in this example. Click

    OK.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    8/24

    13.In Project Explorer, right click on My Computer >> New >> VI

    14.Drag and drop the variables from Project Explorer to the blank VI.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    9/24

    15.In Project Explorer, right click on Library and Click Deploy All

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    10/24

    16.In VI , click the run button

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    11/24

    17. In Project Explorer, click Tool >> Distributed System Manager (DSM)

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    12/24

    18.After Log in as an administrator to DSM, the following figures will be displayed.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    13/24

    Data Logging

    1. In Project Explorer, right click on the Library and click properties.

    2. Click on DSC Settings: Database and click the check box as shown in the figure. ClickOK.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    14/24

    3. In NI DSM, right clicks on individual variables and choose edit variable. Choose Loggingand click the check box as shown in the figure.

    4. In Project Explorer, click Tools >> Measurement & Automation Explorer

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    15/24

    5.

    Refer to the diagram

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    16/24

    6. Right click on New Trace View and click Add/ Remove then select the variable that youwant to log in as shown in the figure.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    17/24

    7. Then select all and click on Export Setting as shown in the following figure.

    8. And choose the location that you want to save the file.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    18/24

    9. Click on Archive and follow the procedures shown in the following figures.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    19/24

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    20/24

    10.Click Export to the Text and follow the procedures shown in the following figures.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    21/24

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    22/24

    11.Click on the folder icon to save the output file location.

    12.Click start.

    13.Go to the folder that the output file is saved.

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    23/24

    14.Open the file in MS Excel

  • 8/2/2019 Creating Log in Account as Administrator in LabView DSC

    24/24

    Daisy Chain Connection for Multiple Energy Meters

    A- B+

    Meter #1

    A- B+

    Meter #2

    R-/D- R+/D+

    RS 485 Communication