CPU224 XP/CPU 224 XPsi - GRAMgram.com.ph/wordpress2/wp-content/uploads/2013/05/CPU224XP.pdf ·...
Transcript of CPU224 XP/CPU 224 XPsi - GRAMgram.com.ph/wordpress2/wp-content/uploads/2013/05/CPU224XP.pdf ·...
Page 148 Mar 2008 Siemens ITS
CPU224 XP/CPU 224 XPsi
Overview
The power CPU With 24 digital and 3 analog inputs/outputs onboard Expandable with up to 7 expansion modules
Design
The CPU 224 XP and CPU 224 XPsi are equipped with: Integral 24 V encoder/load current supply:
For direct connection of sensors and encoders. With 280 mA, output current can also be used as loadpower supply.
CPU 224 XP:2 device variants with different supply and control voltages.CPU 224 Xpsi:1 device variant (24V DC) with current sinking.
Integral digital inputs/outputs:14 inputs and 10 outputs.
Integral analog inputs/outputs:2 inputs and 1 output.
2 communication interfaces:Optional
Page 149 Mar 2008 Siemens ITS
As PPI interface with PPI protocol for programming functions, HMI functions (TD 200, OP), S7-200internal CPU/CPU communication (9.6/19.2/187.5 Kbit/s) or as MPI slave for data exchange withMPI masters (S7-300/-400, OPs, TDs, pushbutton panels).
Freely-programmable interface (freeport) with interrupt facility for serial data exchange with third-party devices, e.g. with ASCII protocol baud rates 1.2/2.4/4.8/9.6/19.2/38.4/57.6/115.2 Kbit/s; PC/PPIcable can be used as RS 232/RS 485 converter.
Expansion bus:Connection of expansion modules (only EMs of the 22x series can be used).
Interrupt inputs:For extremely fast response to rising or falling edges of process signals.
Fast counters: 6 fast counters (2x200 kHz, 4x400 kHz), with parameterizable enable and reset input, can be used
simultaneously as up and down counters with 2 separate inputs or for connecting incremental encoders with2 pulse trains (2x100 kHz, 2x20 kHz) offset by 90o.
Problem-free expansion with digital and analog expansion modules (EM, optional). Simulator (optional):
For simulating the integral inputs and for testing the user program. EEPROM submodule (optional):
For saving the complete STEP 7-Micro/WIN user program as well as other documents.For supporting the data logging function and recipe management.Permits fast changing of program (even without programming device) and additional program archiving.
Battery module for long-term backup: To increase the storage period up to typically 200 days. Without abattery module, user data (e.g. bit memory states, data blocks, times, counts) are saved by an internal high-performance capacitor for approx. 5 days. The program is always saved permanently (maintenance-free).The battery module is inserted into the slot for the memory submodule.
Page 150 Mar 2008 Siemens ITS
Device variants CPU 224 XPVariant Supply voltage Input voltage Output voltage Output current•DC outputs 24 V DC 24 V DC 24 V DC 0.75 A, transistor•Relay outputs 85 to 264 V AC 24 V DC 24 V DC, 24 to
230 V AC2 A, relay
Device variants CPU 224 XPsiVariant Supply voltage Input voltage Output voltage Output current•DC outputs,current sinking
24 V DC 24 V DC 24 V DC, currentsinking
0.75 A, transistor
Page 151 Mar 2008 Siemens ITS
Function
Extensive instruction set:A large number of Basic operations such as binary logic operations, result allocation, save, count, create times, load,
transfer, compare, shift, rotate, create complement, call subprogram (with local variables) Integrated communication instructions (e.g., S7-200 communication (Network read NETR,
Network write NETW) or Freeport (Transmit XMT, Receive RCV)) User-friendly functions such as pulse-duration modulation, pulse sequence function, arithmetic
functions, floating-point arithmetic, PID closed-loop control, jump functions, loop functions andcode conversions simplify programming
Counting:User-friendly counting functions in conjunction with the integrated counters and special commands forhigh-speed counters open up new application areas for the user
Interrupt handling: Edge-triggered interrupts (activated by rising or falling edges of process signals on interrupt
inputs) support a rapid response to process events Time-controlled interrupts can be set at 1 ms increments from 1 ms to 255 ms Counter interrupts can be triggered when a setpoint is reached or when the direction of counting
changes Communication interrupts make exchanging information with peripheral devices such as printers
or bar code readers quick and easy Direct interrogation and control of inputs/outputs:
Inputs and outputs can also be scanned and set directly independent of the cycle. The controller is thenable to respond quickly to process events (e.g., direct resetting of outputs on the occurrence of aninterrupt).
Page 152 Mar 2008 Siemens ITS
Password protection:The 3-level password protection concept effectively safeguards your know-how. The protection concepthas the following options for access to the user program: Full access: the program can be altered as desired.Read-only: the program is protected against unauthorized changes. Testing, setting system parametersand copying the program are possible. Complete protection: the program is protected against modification and unauthorized readout and
copying. Parameter settings are supported
Test and diagnostic functions:User-friendly functions support testing and diagnostics: The entire program is executed and analyzed usinga definable number of cycles. Internal parameters such as bit memories, timers or counters, are logged in amax. of 124 cycles."Forcing” of inputs and outputs during test and diagnostic operation:Inputs and outputs can be set independently of cycle and thus permanently, for example, to test the userprogram.Runtime edit:In RUN mode, programs can be edited and modified programs can be loaded into the CPU at the click of amouse, without having to interrupt the current program.Additional mathematical modules such as SIN, COS, TAN, LN, EXPData logging:Time-controlled or event-controlled saving of data records on the EEPROM memory submodule, e.g.performance data, statistical data, fault/error messages, optionally with a time tag. The log file can betransferred at any time using the S7 Explorer in STEP 7-Micro/WIN.
Page 153 Mar 2008 Siemens ITS
Recipe management:Recipes are defined and downloaded within the STEP 7-Micro/WIN project. For better memory utilization,the recipes are stored in the EEPROM memory submodule. The recipes can be modified and updatedonline.
Programming
The STEP 7-Micro/WIN32 V4 programming package permits complete programming of all S7-200CPUs.
Note:
The CPU 224 cannot be programmed using STEP 7-Micro/DOS. If programming is to take place viathe serial interface of the PG/PC, the PC/PPI cable is required additionally. If the STEP 7 Micro/WinV4 programming software is used, programming can take place via the SIMATIC CP 5511 or CP5611 (see SIMATIC NET) as well as via the MPI interface of the programming device. This increasesthe maximum permissible transmission rate to 187.5 kbps
Technical specifications
Page 154 Mar 2008 Siemens ITS
6ES7 214-2AD23-0XB0
6ES7 214-2BD23-0XB0
6ES7 214-2AS23-0XB0
Supply voltage
Technical specifications
24 V DC Yes Yespermissible range,lower limit (DC)
20.4 V 20.4 V
permissible range,upper limit (DC)
28.8 V 28.8 V
Page 155 Mar 2008 Siemens ITS
120 V AC Yes230 V AC YesLine frequency•Frequency of thesupply voltage
63 Hz
Load voltage L+•Rated value (DC) 24 V 24 V 24 V•permissible range,lower limit (DC)
20.4 V 5 V 20.4 V
•permissible range,upper limit (DC)
28.8 V 30 V 28.8 V
Load voltage L1
•Rated value (AC) 100 V; 100 to 230 VAC
•permissible range,lower limit (AC)
5 V
•permissible range,upper limit (AC)
250 V
•permissible frequencyrange, lower limit
47 Hz
•permissible frequencyrange, upper limit
63 Hz
Page 156 Mar 2008 Siemens ITS
Input currentInrush current, max. 12 A; at 28.8 V 20 A; at 264 V 12 A; at 28.8 V
from supply voltage L+,max.
900 mA; 120 to900 mA, outputcurrent forexpansionmodules (DC 5V) 660 mA
900 mA; 120 to 900 mA,output current forexpansion modules (DC 5V) 660 mA
from supply voltage L1,max.
220 mA; 35 to100 mA (240V); 70 to 220mA (120 V);output currentfor expansionmodules (5 VDC) 600 mA
Encoder supply24 V encoder supply
•24 V Yes; permissiblerange: 15.4 to28.8 V
Yes; Permissiblerange: 20.4 to28.8 V
Yes; permissible range:15.4 to 28.8 V
•Short-circuit protection Yes; electronic at280 mA
Yes; electronicat 280 mA
Yes; electronic at 280 mA
Page 157 Mar 2008 Siemens ITS
•Output current, max. 280 mA 280 mA 280 mA
Backup batteryBattery operation•Backup time, max. 100 h; (min. 70
h at 40 °C); 200days (typ.) withoptional batterymodule
100 h; (min. 70h at 40 °C);200 days (typ.)with optionalbattery module
100 h; (min. 70 h at 40 °C);200 days (typ.) with optionalbattery module
MemoryNumber of memorymodules (optional)
1; pluggablememory module,content identicalwith integralEEPROM; canadditionally storerecipes, data logsand other files
1; pluggablememory module,content identicalwith integralEEPROM; canadditionally storerecipes, datalogs and otherfiles
1; pluggable memorymodule, content identicalwith integral EEPROM; canadditionally store recipes,data logs and other files
Data and programmemory•Data memory, max. 10 Kibyte 10 Kibyte 10 Kibyte
•Program memory, max. 16 Kibyte; 12KB with activerun-time edit
16 Kibyte; 12KB with activerun-time edit
16 Kibyte; 12 KB withactive run-time edit
Page 158 Mar 2008 Siemens ITS
Backup•present Yes; Program:
Entire programmaintenance-freeon integralEEPROM,programmable viaCPU; data: EntireDB 1 loaded fromPG/PCmaintenance-freeon integralEEPROM, currentvalues of DB 1 inRAM, retentivememory bits,timers, counters,etc. maintenance-free via high-performancecapacitor; optionalbattery for long-term buffering
Yes; Program:Entire programmaintenance-free onintegral EEPROM,programmable viaCPU; data: EntireDB 1 loaded fromPG/PCmaintenance-free onintegral EEPROM,current values ofDB 1 in RAM,retentive memorybits, timers,counters, etc.maintenance-freevia high-performancecapacitor; optionalbattery for long-term buffering
Yes; Program: Entireprogram maintenance-freeon integral EEPROM,programmable via CPU;data: Entire DB 1 loadedfrom PG/PC maintenance-free on integral EEPROM,current values of DB 1 inRAM, retentive memorybits, timers, counters, etc.maintenance-free via high-performance capacitor;optional battery for long-term buffering
Page 159 Mar 2008 Siemens ITS
CPU processingtimesfor bit operations,max.
0.22 µs 0.22 µs 0.22 µs
Counters, timersand their retentivityS7 counter•Number 256 256 256•of which retentivewith battery
• adjustableYes; via high-performancecapacitor orbattery
Yes; via high-performancecapacitor or battery
Yes; via high-performancecapacitor or battery
• lower limit1 1 1
• upper limit256 256 256
•Counting range
• lower limit0 0 0
• upper limit32 767 32 767 32 767
Page 160 Mar 2008 Siemens ITS
S7 times•Number 256 256 256•of which retentivewith battery
• adjustableYes; via high-performance capacitoror battery
Yes; via high-performance capacitoror battery
Yes; via high-performance capacitoror battery
• upper limit64 64 64
•Time range
• lower limit1 ms 1 ms 1 ms
• upper limit54 min; 4 timers: 1ms to 30 s; 16timers: 10 ms to 5min; 236 timers: 100ms to 54 min
54 min; 4 timers: 1ms to 30 s; 16timers: 10 ms to 5min; 236 timers: 100ms to 54 min
54 min; 4 timers: 1ms to 30 s; 16timers: 10 ms to 5min; 236 timers: 100ms to 54 min
Data areas andtheir retentivityFlag•Number, max. 32 byte 32 byte 32 byte•Retentivity available Yes; M 0.0 to M
31.7Yes; M 0.0 to M31.7
Yes; M 0.0 to M31.7
Page 161 Mar 2008 Siemens ITS
•of which retentivewith battery
0 to 255, via high-performancecapacitor or battery,adjustable
0 to 255, via high-performance capacitoror battery, adjustable
0 to 255, via high-performance capacitoror battery, adjustable
•of which retentivewithout battery
0 to 112 inEEPROM, adjustable
0 to 112 inEEPROM, adjustable
0 to 112 inEEPROM, adjustable
HardwareconfigurationExpansion devices,max.
7; Only expansionmodules of the S7-22x series can beused. Due to thelimited outputcurrent, the use ofexpansion modulesmay be limited.
7; Only expansionmodules of the S7-22x series can beused. Due to thelimited outputcurrent, the use ofexpansion modulesmay be limited.
7; Only expansionmodules of the S7-22x series can beused. Due to thelimited output current,the use of expansionmodules may belimited.
Connectableprogrammingdevices/PCs
SIMATIC PG/PC,standard PC
SIMATIC PG/PC,standard PC
SIMATIC PG/PC,standard PC
Expansion modules
Page 162 Mar 2008 Siemens ITS
•Analoginputs/outputs, max.
38; 2 onboardinputs and 1output, also max.28 inputs and 7outputs (EM) ormax. 0 inputsand 14 outputs(EM)
38; 2 onboard inputsand 1 output, alsomax. 28 inputs and 7outputs (EM) or max.0 inputs and 14outputs (EM)
38; 2 onboard inputsand 1 output, also max.28 inputs and 7 outputs(EM) or max. 0 inputsand 14 outputs (EM)
•Digitalinputs/outputs, max.
168; max. 94inputs and 74outputs (CPU +EM)
168; max. 94 inputsand 74 outputs (CPU +EM)
168; max. 94 inputsand 74 outputs (CPU +EM)
•AS-Interfaceinputs/outputs max.
62; AS-InterfaceA/B slaves (CP243-2)
62; AS-Interface A/Bslaves (CP 243-2)
62; AS-Interface A/Bslaves (CP 243-2)
Digital inputsNumber/binary inputs 14 14 14m/p-reading Yes; optionally,
per groupYes; optionally, pergroup
Yes; optionally, pergroup
Input voltage•Rated value, DC 24 V 24 V 24 V•for signal "0" 0 to 5 V; 0 to 1
V (I 0.3 to I0.5)
0 to 5 V; 0 to 1 V (I0.3 to I 0.5)
0 to 5 V; 0 to 1 V (I0.3 to I 0.5)
Page 163 Mar 2008 Siemens ITS
•for signal "1" min. 15 V; min.4 V (I 0.3 to I0.5)
min. 15 V; min. 4 V(I 0.3 to I 0.5)
min. 15 V; min. 4 V(I 0.3 to I 0.5)
Input current•for signal "1", typ. 2.5 mA; 8 mA
for I0.3 to I0.52.5 mA; 8 mA for I0.3to I0.5
2.5 mA; 8 mA for I0.3to I0.5
Input delay (for ratedvalue of input voltage)•for standard inputs
• ParameterizableYes; all Yes; all Yes; all
• at "0" to "1",min.
0.2 ms 0.2 ms 0.2 ms
• at "0" to "1",max.
12.8 ms 12.8 ms 12.8 ms
•for interrupt inputs
• ParameterizableYes; I 0.0 to I0.3
Yes; I 0.0 to I 0.3 Yes; I 0.0 to I 0.3
•forcounter/technologicalfunctions
Page 164 Mar 2008 Siemens ITS
• ParameterizableYes; (E0.0 to E1.5)up to 200 kHz
Yes; (E0.0 to E1.5)up to 200 kHz
Yes; (E0.0 to E1.5)up to 200 kHz
Cable length•Cable length, shielded,max.
500 m; Standardinput: 500 m, high-speed counters: 50m
500 m; Standardinput: 500 m, high-speed counters: 50 m
500 m; Standardinput: 500 m, high-speed counters: 50 m
•Cable lengthunshielded, max.
300 m; not for high-speed signals
300 m; not for high-speed signals
300 m; not for high-speed signals
Digital outputsNumber/binary outputs 10; Transistor 10; Relay 10; Transistor current
sinkingFunctionality/short-circuit strength
No; to be providedexternally
No; to be providedexternally
No; to be providedexternally
Limitation of inductiveshutdown voltage to
1 W 1 W
Switching capacity ofthe outputs•with resistive load,max.
0.75 A 2 A 0.75 A
•on lamp load, max. 5 W 200 W; 30 W DC;200 W AC
5 W
Output voltage
Page 165 Mar 2008 Siemens ITS
•for signal "1", min. L+ (-0.4 V (5 V /20.4 V for A 0.0 toA 0.4; 20.4 V A0.5 to A1.1))
L+/L1 1M -0.4 V
Output current•for signal "1" ratedvalue
750 mA 2 A 750 mA
•for signal "0"residual current, max.
10 µA 0 mA 10 µA
Output delay withresistive load•0 to "1", max. 15 µs; of the
standard outputs,max. (Q0.2 to Q1.1)15 µs; of the pulseoutputs, max. (Q0.0to Q0.1) 0.5 µs
10 ms; all outputs 15 µs; of the standardoutputs, max. (Q0.2 toQ1.1) 15 µs; of thepulse outputs, max.(Q0.0 to Q0.1) 0.5 µs
•1 to "0", max. 130 µs; of thestandard outputs,max. (Q0.2 to Q1.1)130 µs; of the pulseoutputs, max. (Q0.0to Q0.1) 1.5 µs
10 ms; all outputs 130 µs; of thestandard outputs, max.(Q0.2 to Q1.1) 130µs; of the pulseoutputs, max. (Q0.0 toQ0.1) 1.5 µs
Page 166 Mar 2008 Siemens ITS
Parallel switching of 2outputs•for increased power Yes No YesSwitching frequency•of the pulse outputs,with resistive load,max.
100 kHz; Q0.0 toQ0.1
1 Hz 100 kHz; Q0.0 toQ0.1
Aggregate current ofoutputs (per group)
• up to 40 °C,max.
3.75 A 10 A 3.75 A
•horizontal installation
• up to 55 °C,max.
3.75 A 10 A 3.75 A
Cable length•Cable length, shielded,max.
500 m 500 m 500 m
•Cable lengthunshielded, max.
150 m 150 m 150 m
Relay outputs
Page 167 Mar 2008 Siemens ITS
Number of operatingcycles
10 000 000;mechanically 10million, at rated loadvoltage 100,000
Analog inputsNumber of analogpotentiometers
2; Analogpotentiometer;resolution 8 bit
2; Analogpotentiometer;resolution 8 bit
2; Analogpotentiometer;resolution 8 bit
EncoderConnectableencoders•2-wire BEROS Yes Yes Yes
• permissiblequiescentcurrent (2-wire BEROS),max.
1 mA 1 mA 1 mA
1st interfaceType of interface Integrated RS 485
interfaceIntegrated RS 485interface
Integrated RS 485interface
Physics RS 485 RS 485 RS 485
Page 168 Mar 2008 Siemens ITS
Functionality•MPI Yes; As MPI slave
for data exchangewith MPI masters(S7-300/S7-400 CPUs,OPs, TDs, PushButton Panels); S7-200-internalCPU/CPUcommunication ispossible in the MPInetwork withrestrictions;transmission rates:19.2/187.5 kbit/s
Yes; As MPI slavefor data exchangewith MPI masters(S7-300/S7-400 CPUs,OPs, TDs, PushButton Panels); S7-200-internalCPU/CPUcommunication ispossible in the MPInetwork withrestrictions;transmission rates:19.2/187.5 kbit/s
Yes; As MPI slavefor data exchangewith MPI masters(S7-300/S7-400 CPUs,OPs, TDs, PushButton Panels); S7-200-internalCPU/CPUcommunication ispossible in the MPInetwork withrestrictions;transmission rates:19.2/187.5 kbit/s
•PPI Yes; with PPIprotocol for programfunctions, HMIfunctions (TD 200,OP), S7-200-internalCPU/CPUcommunication ;transmission rates9.6/19.2/187.5 kbit/s
Yes; with PPIprotocol for programfunctions, HMIfunctions (TD 200,OP), S7-200-internalCPU/CPUcommunication ;transmission rates9.6/19.2/187.5 kbit/s
Yes; with PPIprotocol for programfunctions, HMIfunctions (TD 200,OP), S7-200-internalCPU/CPUcommunication ;transmission rates9.6/19.2/187.5 kbit/s
Page 169 Mar 2008 Siemens ITS
•Serial data exchange Yes; As freelyprogrammableinterface withinterrupt facility forserial data exchangewith third-partydevices with ASCIIprotocol transferrates: 1.2 / 2.4 / 4.8/ 9.6 / 19.2 / 38.4 /57.6 / 115.2 kbit/s;the PC/PPI cable canalso be used asRS232/RS485converter
Yes; As freelyprogrammableinterface withinterrupt facility forserial data exchangewith third-partydevices with ASCIIprotocol transferrates: 1.2 / 2.4 / 4.8/ 9.6 / 19.2 / 38.4 /57.6 / 115.2 kbit/s;the PC/PPI cable canalso be used asRS232/RS485converter
Yes; As freelyprogrammableinterface withinterrupt facility forserial data exchangewith third-partydevices with ASCIIprotocol transferrates: 1.2 / 2.4 / 4.8/ 9.6 / 19.2 / 38.4 /57.6 / 115.2 kbit/s;the PC/PPI cable canalso be used asRS232/RS485converter
MPI•Transmission rate,max.
187.5 kbit/s 187.5 kbit/s 187.5 kbit/s
•Transmission rate,min.
19.2 kbit/s 19.2 kbit/s 19.2 kbit/s
2nd interfaceType of interface Integrated RS 485
interfaceIntegrated RS 485interface
Integrated RS 485interface
Physics RS 485 RS 485 RS 485
Page 170 Mar 2008 Siemens ITS
Functionality•MPI Yes; As MPI slave
for data exchangewith MPI masters(S7-300/S7-400CPUs, OPs, TDs,Push Button Panels);S7-200-internalCPU/CPUcommunication ispossible in the MPInetwork withrestrictions;transmission rates:19.2/187.5 kbit/s
Yes; As MPI slavefor data exchangewith MPI masters(S7-300/S7-400 CPUs,OPs, TDs, PushButton Panels); S7-200-internal CPU/CPUcommunication ispossible in the MPInetwork withrestrictions;transmission rates:19.2/187.5 kbit/s
Yes; As MPI slavefor data exchangewith MPI masters(S7-300/S7-400 CPUs,OPs, TDs, PushButton Panels); S7-200-internal CPU/CPUcommunication ispossible in the MPInetwork withrestrictions;transmission rates:19.2/187.5 kbit/s
•PPI Yes; with PPIprotocol for programfunctions, HMIfunctions (TD 200,OP), S7-200-internalCPU/CPUcommunication ;transmission rates9.6/19.2/187.5 kbit/s
Yes; with PPIprotocol for programfunctions, HMIfunctions (TD 200,OP), S7-200-internalCPU/CPUcommunication ;transmission rates9.6/19.2/187.5 kbit/s
Yes; with PPIprotocol for programfunctions, HMIfunctions (TD 200,OP), S7-200-internalCPU/CPUcommunication ;transmission rates9.6/19.2/187.5 kbit/s
Page 171 Mar 2008 Siemens ITS
•serial data exchange Yes; As freelyprogrammableinterface withinterrupt facility forserial data exchangewith third-partydevices with ASCIIprotocol transferrates: 1.2 / 2.4 / 4.8/ 9.6 / 19.2 / 38.4 /57.6 / 115.2 kbit/s;the PC/PPI cablecan also be used asRS232/RS485converter
Yes; As freelyprogrammableinterface with interruptfacility for serial dataexchange with third-party devices withASCII protocoltransfer rates: 1.2 /2.4 / 4.8 / 9.6 / 19.2/ 38.4 / 57.6 / 115.2kbit/s; the PC/PPIcable can also beused as RS232/RS485converter
Yes; As freelyprogrammableinterface with interruptfacility for serial dataexchange with third-party devices withASCII protocoltransfer rates: 1.2 /2.4 / 4.8 / 9.6 / 19.2/ 38.4 / 57.6 / 115.2kbit/s; the PC/PPIcable can also beused as RS232/RS485converter
MPI•Transmission rate,max.
187.5 kbit/s 187.5 kbit/s 187.5 kbit/s
•Transmission rates,min.
19.2 kbit/s 19.2 kbit/s 19.2 kbit/s
Integrated FunctionsNumber of counters 6; High-speed
counters (2 to 2006; High-speedcounters (2 to 200
6; High-speedcounters (2 to 200
Page 172 Mar 2008 Siemens ITS
(2 to 200 kHz and 4to 30 kHz), 32 bits(incl. sign), can beused as up/downcounters or forconnectingincremental encoderswith 2 pulse trainsoffset by 90° (max.1 to 100 kHz and 3to 20 kHz (A/Bcounters));parameterizableenable and resetinput; interruptfacilities (incl. call ofsubroutine with anycontent) when thesetpoint is reached;reversal in countingdirection, etc.
kHz and 4 to 30kHz), 32 bits (incl.sign), can be used asup/down counters orfor connectingincremental encoderswith 2 pulse trainsoffset by 90° (max. 1to 100 kHz and 3 to20 kHz (A/Bcounters));parameterizable enableand reset input;interrupt facilities(incl. call ofsubroutine with anycontent) when thesetpoint is reached;reversal in countingdirection, etc.
kHz and 4 to 30kHz), 32 bits (incl.sign), can be usedas up/down countersor for connectingincremental encoderswith 2 pulse trainsoffset by 90° (max.1 to 100 kHz and 3to 20 kHz (A/Bcounters));parameterizableenable and resetinput; interruptfacilities (incl. callof subroutine withany content) whenthe setpoint isreached; reversal incounting direction,etc.
Counter frequency(counter) max.
200 kHz 200 kHz 200 kHz
Page 173 Mar 2008 Siemens ITS
Number of alarm inputs4; 4 rising edgesand/or 4 falling edges
4; 4 rising edgesand/or 4 fallingedges
4; 4 rising edgesand/or 4 fallingedges
Number of pulse outputs2; High-speed outputs,20 kHz, with interruptoption; pulse-widthand frequencymodulation option
2; High-speedoutputs, 20 kHz,with interruptoption; pulse-widthand frequencymodulation option
Limit frequency (pulse) 20 kHz 20 kHz
Galvanic isolationGalvanic isolation digitalinputs•between the channels Yes Yes Yes
•between the channels,in groups of
6 and 8 6 and 8 6 and 8
Galvanic isolation digitaloutputs•between the channels Yes; Optocoupler Yes; Relay Yes; Optocoupler
•between the channels,in groups of
5 3 and 4 10
Page 174 Mar 2008 Siemens ITS
Permissible potentialdifference
between different circuits500 V DC between24 V DC and 5 VDC
500 V DC between 24V DC and 5 V DC;1500 V AC between24 V DC and 230 VAC
500 V DC between24 V DC and 5 VDC
Ambient conditionsEnvironmental conditionsFor further
environmentalconditions, see"AutomationSystem S7-200,System Manual"
For furtherenvironmentalconditions, see"Automation SystemS7-200, SystemManual"
For furtherenvironmentalconditions, see"Automation SystemS7-200, SystemManual"
Operating temperature•vertical installation,min.
0 °C 0 °C 0 °C
•vertical installation,max.
45 °C 45 °C 45 °C
•horizontal installation,min.
0 °C 0 °C 0 °C
•horizontal installation,max.
55 °C 55 °C 55 °C
Page 175 Mar 2008 Siemens ITS
Air pressure•permissible range, min. 860 hPa 860 hPa 860 hPa•permissible range, max. 1 080 hPa 1 080 hPa 1 080 hPaRelative humidity•Operation, min. 5 % 5 % 5 %•Operation, max. 95 %; RH class 2
in accordance withIEC 1131-2
95 %; RH class 2 inaccordance with IEC1131-2
95 %; RH class 2in accordance withIEC 1131-2
Degree and class ofprotectionIP20 Yes Yes YesConfigurationprogramming•Programming language
• LADYes Yes Yes
• FBDYes Yes Yes
• STLYes Yes Yes
•Command set Bit logicinstructions,compareinstructions, timer
Bit logic instructions,compare instructions,timer instructions,counter instructions,
Bit logicinstructions,compareinstructions, timer
Page 176 Mar 2008 Siemens ITS
instructions, counterinstructions, clockinstructions,transmissionsinstructions, tableinstructions, logicinstructions, shiftand rotateinstructions,conversioninstructions,program controlinstructions,interrupt andcommunicationsinstructions, logicstack instructions,integer maths,floating-point mathinstructions,numerical functions
clock instructions,transmissionsinstructions, tableinstructions, logicinstructions, shift androtate instructions,conversion instructions,program controlinstructions, interruptand communicationsinstructions, logic stackinstructions, integermaths, floating-pointmath instructions,numerical functions
instructions, counterinstructions, clockinstructions,transmissionsinstructions, tableinstructions, logicinstructions, shift androtate instructions,conversioninstructions, programcontrol instructions,interrupt andcommunicationsinstructions, logicstack instructions,integer maths,floating-point mathinstructions, numericalfunctions
•Program processing free cycle (OB 1),interrupt-controller,time-controlled (1
free cycle (OB 1),interrupt-controller,time-controlled (1 to
free cycle (OB 1),interrupt-controller,time-controlled (1 to
Page 177 Mar 2008 Siemens ITS
to 255 ms) to 255 ms) to 255 ms)•Program organization 1 OB, 1 DB, 1 SDB
subroutineswith/withoutparameter transfer
1 OB, 1 DB, 1 SDBsubroutineswith/withoutparameter transfer
1 OB, 1 DB, 1 SDBsubroutineswith/withoutparameter transfer
•Number ofsubroutines, max.
64 64 64
Know-how protection
•User programprotection/passwordprotection
Yes; 3-stage passwordprotection
Yes; 3-stage passwordprotection
Yes; 3-stage passwordprotection
Connection methodPlug-in I/O terminals Yes Yes Yes
DimensionsWidth 140 mm 140 mm 140 mmHeight 80 mm 80 mm 80 mmDepth 62 mm 62 mm 62 mmWeightWeight, approx. 390 g 440 g 390 g