CPU-95 OI 4-08

download CPU-95 OI 4-08

of 34

Transcript of CPU-95 OI 4-08

  • 8/13/2019 CPU-95 OI 4-08

    1/34

    OPERATING INSTRUCTIONS

    CPU-95DIGITAL IGNITION SYSTEMMODELS 791950-8/16/18, 791952-18, 791958-16

    DEVIATION FROM THESE INSTRUCTIONS MAY LEAD TO IMPROPER OP-

    ERATION OF THE MACHINE WHICH COULD CAUSE PERSONAL INJURYTO OPERATORS OR OTHER NEARBY PERSONNEL.WARNING:

    www.altronicinc.com

    FORM CPU-95 OI 4-08

    www.altronicinc.com 1

    DEVIATION FROM THESE INSTRUCTIONS MAY LEAD TO IMPROPER

    ENGINE OPERATION WHICH COULD CAUSE PERSONAL INJURY TOOPERATORS OR OTHER NEARBY PERSONNEL.WARNING:

    1.0 OVERVIEW

    1.1 The Altronic CPU-95Digital Ignition system has been designed forapplication on natural gas fueled engines. This system is eld-programmable and offers a variety of advanced control, emissionsreduction, primary and spark diagnostics, self diagnostics, se-rial communications and engine protection features. The systemconsists of two main parts: an engine mounted Ignition Module(791950-8/16/18, 791952-18 OR 791958-16) and an optional user inter-face Display Module (791902-1 OR 791908-1).

    1.2 This document provides instructions and descriptions to be usedin the operation of the ignition system, and does not cover physicalinstallation. Reference the installation instructions, form CPU-95 II,for instructions regarding installation and mounting.

    NOTE: These instructions

    pertain to CPU-95 systems

    equipped with rmware

    release 4.0, dated 01/01/99

    and later. The rmware dates

    can be displayed from the

    home screen by pressing

    DIAG and then ENTER.

    The date of the installed

    rmware is viewed:

    Top line (LOGIC) applies

    to the output module

    rmware date.

    Lower line (DISPLAY)

    applies to the display

    module rmware date.

    THE IGN ITIO N SYST EM MUST B E CONF IGURE D PRIOR T OUSE ON AN ENGINE. REFER TO SECTION 9.7 TO VIEW THECURRENT CONFIGURATION. REFERENCE FORM CPU-95 PIFOR INSTRUCTIONS DESCRIBING HOW TO CONFIGURE THEIGNITION SYSTEM. VERIFY EEPROM PROGRAMMING PRIORTO STA RTIN G ENGI NE.

    WARNING:

  • 8/13/2019 CPU-95 OI 4-08

    2/34

    FORM CPU-95 OI 4-082

    CPU-95 DIGITAL IGNITION SYSTEM

    NOTE: If possible, keep the

    original shipping container.

    If future transportation or

    storage is necessary, this

    container will provide the

    optimum protection.

    2.0 IGNITION MODULE OUTPUT SWITCHES, LED INDICATORS AND CONTROL INPUT2.1 Three output switches in the Ignition Module provide a means of

    communicating the current ignition status to other systems. Theseswitches have isolated outputs and share one common return path

    which is not referenced to engine or power ground. They will be inthe open condition when the unit is unpowered. A typical applica-tion would be as a relay or solenoid coil driver.

    FIRE-CONFIRM OUTsitch: closed hen the inition is rin or trin to re. Coulde used as a sinal to the control sstem to turn fuel on.

    FAULT OUTsitch: closed to sinal that the inition has no dianostic faults hichould result in a self-shutdon. Upon detectin a fault that ould result in a self-shutdon of the inition, this sitch ill open. Could e used as a sinal to the con -trol sstem to turn fuel off.

    ALARM OUTsitch: closed to sinal that no unacnoleded faults or arnins arepresent. Upon detection of a dianostic fault or arnin, this sitch ill open. This

    output is desined to control an alarm indicator or soundin device.

    2.2 Four red LED indicators are provided inside the ignition unit fortroubleshooting purposes:

    POWER LED:on to indicate that the unit has poer and the microprocessor isrunnin. The Poer LED ashes to indicate that the unit has poer ut is notoperatin correctl. The Poer LED is off to indicate that the unit has no poer.

    TX LED: ashes to indicate that the inition unit is transmittin on the RS-485 serial lin.

    RX LED:ashes to indicate that the inition unit is receivin on the RS-485serial lin.

    ALARM LED:turns on to indicate that a arnin or fault is present. TheALARM LED ashes hen an acnoleded arnin is present.

    2.3 One RS-485 serial communications port is provided within the Ig-nition Module. This port is normally used for communication tothe optional Display Module. A PC (personal computer) or a PLC(programmable logic controller) can be connected to the RS-485portto perform remote monitoring or control functions. The IgnitionModule can be operated in a stand-alone mode, but diagnostic andcontrol features would not be accessible. This port is also used tocongure the ignition system for its application using a PC and theCPU-95PC terminal software.

    2.4 One digital input is provided inside the ignition system (MISC. INPUT).This logic level input is active when shorted to ground, and is used

    to control any combination of the following features: one-step re-tard, spark energy level or multi-strike option. These features areenabled based on the special features conguration settings as de-scribed in the programming instructions, FORM CPU-95 PI.

  • 8/13/2019 CPU-95 OI 4-08

    3/34

    www.altronicinc.com 3

    OPERATING INSTRUCTIONS

    3.0 DISPLAY MODULE USER INTERFACE AND INPUTS

    3.1 DISPLAY MODULE:serves as the user interface for the CPU-95ignitionsystem. An RS-485two wire serial communications format is usedto connect the Display Module to the Ignition Module. This linkcommunicates between the modules using a proprietary protocol.

    3.2 LCD DISPLAY: An alphanumeric 16-character x 2-line back-lit LCDdisplay is used to provide output to the user. A sealed membranekeypad is used to accept user input. The LCD display and the key-pad function together to provide an interactive user interface whichprompts the user as different functions are selected. SEE FIGURE 1for a description of the keypad.

    3.3 All actions and adjustments are immediate and are performed onan incremental basis using up and down arrow keys. All keypadadjustments, except individual offset timing adjustments are per-formed directly in non-volatile EEPROM memory. This EEPROMmemory retains previous settings even after an engine shutdown,

    or an ignition power down.

    3.4 Capital letters are used on the LCD display screen to designate anactive selection while lower case letters are used to indicate otherpossible options.

    3.5 The Display Module includes an isolated current loop input whichcan be congured to control spark timing. Reference the program-ming instructions, FORM CPU-95 PI.

    3.6 One logic level digital input (MISC. INPUT)is available at the DisplayModule which can be used in the same fashion as the input of theIgnition Module. If either input is shorted to ground, then the MISC.

    INPUTfunctions are active.

  • 8/13/2019 CPU-95 OI 4-08

    4/34

    FORM CPU-95 OI 4-084

    CPU-95 DIGITAL IGNITION SYSTEM

    4.0 UNDERSTANDING THE HOME SCREEN

    4.1 A series of HOMEscreens are used to describe the current status ofthe ignition system. The LCD display always reverts back to one ofthe home screens after a keypad operation is completed or timesout. The HOMEscreen is designed to display the most critical operat-

    ing parameters on one screen.

    4.2 All of the HOMEscreens provide a status word in the upper left cor-ner, the engine speed (xxxx rpm)in the upper right corner, the currentloop (xx.x mA)in the lower left corner and the global ignition timing(xx.xBtdc or xx.xAtdc)in the lower right corner.

    4.3 The READYmessage is displayed when the ignition is ready for theengine to crank for starting.

    READY 0rpm

    15.0mA 10.0Btdc

    4.4 Once the engine begins turning, the SYNCINGmessage is displayedwhile the ignition system veries signals from the engine pickups.

    SYNCING 155rpm

    15.0mA 10.0Btdc

    4.5 The FIRING message is displayed when the ignition begins ring.Additional data is provided on this screen to describe the selectedmode of operation for the ignition. The energy mode (E1,E2,E3) andthe single-strike/multi-strike type (S or M)are described in the mid-

    dle of the upper line in small characters.

    FIRING E1S1000rpm

    15.0mA 10.0Btdc

    4.6 The STALLEDmessage is displayed when a loss of rotation is detectedafter the ignition is ring and neither a SHUTDOWNor FAULThas oc-curred. This signies that the engine has stopped without any de-tected cause from the ignition system.

    STALLED 0rpm

    15.0mA 10.0Btdc

  • 8/13/2019 CPU-95 OI 4-08

    5/34

    www.altronicinc.com 5

    OPERATING INSTRUCTIONS

    4.7 The WARNINGmessage will supersede all of the above home screensif a diagnostic warning condition is present. When a diagnostic

    warning exists, aVIEW DIAGNOSTICSmessage will ash on the bottomline of the display. The Ignition Module will continue to operateunder a warning condition while alerting the operator of a poten-tial problem in several ways: by turning on the Alarm LED in the

    Ignition Module and by changing the state of the Alarm Out switch(switch opens). The Display Module will display the Warning mes-sage. The various types of diagnostic warnings are described inSECTION 10.0.

    WARNING 1000rpm

    15.0mA 10.0Btdc

    WARNING 1000rpm

    VIEW DIAGNOSTICS

    4.8 The FAULTmessage will supersede all of the above home screens ifa diagnostic fault condition is present. When a diagnostic fault ex-ists, aVIEW DIAGNOSTICSmessage will ash on the bottom line of thedisplay. The ignition system will stop operating under a fault condi-tion and will alert the operator to the problem in several ways: bychanging the state of the Fire Conrm Out switch (switch opens),

    by turning on the alarm LED inside the Ignition Module, by chang-ing the state of the Alarm Out switch (switch opens), by changingthe state of the Fault Out switch (switch opens), and by displayingthe Fault message. The various types of diagnostic faults are de-scribed inSECTION 10.0.

    FAULT 0rpm

    15.0mA 10.0Btdc

    FAULT 0rpm

    VIEW DIAGNOSTICS

  • 8/13/2019 CPU-95 OI 4-08

    6/34

    FORM CPU-95 OI 4-086

    CPU-95 DIGITAL IGNITION SYSTEM

    4.9 The SHUTDOWN screen will supersede all other home displays if thelogic level shutdown input of the Ignition Module or the G-Lead ofthe output primary connector is grounded or was previously ground-ed and the engine has not stopped rotating. This screen indicates thatthe ignition is not ring because a shutdown input was triggered toshutdown the engine. If a diagnostic fault or warning exists while the

    ignition is in shutdown, aVIEW DIAGNOSTICSmessage will ash on thebottom line of the display. The Fire Conrm Out switch will changestate (switch opens) and the other outputs will function as describedabove based on the existence of faults or warnings.

    SHUTDOWN 0rpm

    15.0mA 10.0Btdc

    SHUTDOWN 0rpm

    VIEW DIAGNOSTICS

  • 8/13/2019 CPU-95 OI 4-08

    7/34

    www.altronicinc.com 7

    OPERATING INSTRUCTIONS

    5.0 ADJUSTING GLOBAL RETARD

    5.1 Global retard is an adjustment affecting the timing of all cylin-ders equally. This adjustment can be equated to the manual timingswitch of the Altronic CPU-90 system. Adjustments made as de-scribed below will be in effect until another adjustment is made.

    5.2 To adjust global retard:

    FROM PRESS

    FIRING E1S1000rpm

    15.0mA 10.0Btdc

    TIMING

    THEN AT PRESS

    =GLOBAL(ENGINE)

    =CYLINDER(INDV)

    THEN AT PRESS

    = ADJUST RETARD

    = SELECT MODE

    THEN AT NOTE: Resultant timing shown on bottom line.

    MANUAL RET 10.5

    Esc 10.0Btdc

    PRESS TO PRESS TO PRESS TO PRESS TOINCREASE DECREASE EXITRETARD RETARD

    ESC

    5.3 The increment of timing change is dependent on the number ofholes or teeth being sensed. The minimum timing change is denedas follows.

    If N < 270, then Increment = 45/N derees

    If N 270, then timin increment is 90/N derees, here N = no. of holes or teeth.

    5.4 Global spark timing is determined based on the sum of severalspark retard components which include manual retard, currentloop retard, rpm retard, and one step retard. The range of total re -tard is limited to 255 X TIMING INCREMENT. When the sum of all retardcomponents reaches 255 X TIMING INCREMENT, the actual timing will

    be at the retard limit.

  • 8/13/2019 CPU-95 OI 4-08

    8/34

    FORM CPU-95 OI 4-088

    CPU-95 DIGITAL IGNITION SYSTEM

    6.0 SELECTION OF GLOBAL TIMING MODES

    6.1 Several options exist with regard to global timing modes. Once theglobal timing mode menu is entered as described below, the statusof each option can be viewed and changed.

    FROM PRESS

    FIRING E1S1000rpm15.0mA 10.0Btdc

    TIMING

    THEN AT PRESS

    =GLOBAL(ENGINE)

    =CYLINDER(INDV)

    THEN AT PRESS

    = ADJUST RETARD

    = SELECT MODE

    6.2 The rst mode selection can enable or disable the pre-conguredretard curve controlled by the 4-20 mAcurrent loop input. The choic-es are ONor OFF, with the active selection displayed in capital letters.

    A PC is required to congure the 4-20 mAcurve; reference the pro-gramming instructions, form CPU-95 PI. When the current loop is on,the current loop value is displayed (xx.x mA)with the A capitalized.

    When the current loop is off, the value is displayed (xx.x ma)with thelower case a.

    AT NOTE: Displa shos Current loop ON.

    CURRENT LOOP RET

    ON/offNext Esc

    TO TO FOR TOTURN TURN NEXT EXITON OFF OPTION

    NEXT

    ESC

    6.3 The Next mode selection can enable or disable the pre-conguredretard curve controlled internally by engine RPM. To congure theRPM retard curve, reference form CPU-95 PI.

    AT THE NOTE: DisplaNEXT shows RPMOPTION Map OFF.SCREEN

    RPM RETARD MAP

    ON/offNext Esc

    TO TO FOR TOTURN TURN NEXT EXITON OFF OPTION

    NEXT

    ESC

  • 8/13/2019 CPU-95 OI 4-08

    9/34

    www.altronicinc.com 9

    OPERATING INSTRUCTIONS

    6.4 The NEXTmode selection can increase or decrease the one-step retardvalue. The rst screen below is displayed when one-step retard isboth congured and is active. The second screen below is displayedwhen the one-step retard is congured but not active. The defaultconguration selects one-step retard to be controlled by the Misc.Input terminal. The additional retard would be implemented when

    the input is grounded. The third screen below is displayed when theone-step retard feature is not congured. The actual engine timingis displayed on this screen so the effect of 1 step retard can be seenduring adjustments (if the Misc Input terminal is grounded).

    AT THE NOTE: Upper caseNEXT 1 STEP RET = on.OPTIONSCREEN

    1 STEP RET 10.0

    Esc 0.0Btdc

    OR NOTE: Lower case 1 step retard = off.

    1 step ret 10.0

    Esc 0.0Btdc

    OR NOTE: 1 Step Retard not conured.

    ONE-STEP FEATURE

    NOT PRESENT Next

    TO TO TO GO TOINCREASE DECREASE BACK TO EXIT FIRST

    NEXT

    ESC

  • 8/13/2019 CPU-95 OI 4-08

    10/34

    FORM CPU-95 OI 4-0810

    CPU-95 DIGITAL IGNITION SYSTEM

    7.0 ADJUSTING INDIVIDUAL OFFSETS7.1 The timing of individual cylinders can be offset by up to 3degrees of

    advance or retard from the global timing of the engine. Adjustmentsmade as described below should be considered temporary. The ig-nition will revert back to the values saved in EEPROM memory on

    every reset, start or power-up. To save temporary adjustments toEEPROM memorySEE SECTION 8.0.

    7.2 Enter the individual timing adjustment menu as described below.

    FROM PRESS

    FIRING E1S1000rpm

    15.0mA 10.0Btdc

    TIMING

    THEN AT PRESS

    =GLOBAL(ENGINE)

    =CYLINDER(INDV)

    THEN AT PRESS

    = ADJUST RETARD

    = SELECT MODE

    7.3 The individual timing adjustment screen identies the primary out-put to be adjusted, and the degrees of offset in use for the output.

    THEN AT NOTE: 2.5 degrees advance for output A.

    output A.

    CYL A 2.5ADV

    Esc Next

    TO TO TO TOADVANCE RETARD SELEC T EXIT NEXT

    CYL.

    NEXT

    ESC

    7.4 The output identication characters will be provided as follows:

    IGNITION MODULE 791950-8/16 OR 791958-16: A B C D E F K L M N P R S T U V

    IGNITION MODULE 791950-18 OR 791952-18: A B C D E F G H K G R P 1 L M N P R S T U V G R P 2

    This identication is the CPU-95 output harness identication;match-up to the engine ring order to determine the engine cylin-der number.

    NOTE: In applications with

    narrow ring angles, theadjustment range may be

    limited.

  • 8/13/2019 CPU-95 OI 4-08

    11/34

    www.altronicinc.com 11

    OPERATING INSTRUCTIONS

    8.0 INDIVIDUAL CYLINDER OFFSET MODES

    8.1 Two additional functions with regard to individual cylinder timingoffsets are provided. These functions can be accessed from the indi -

    vidual timing mode menu which can be entered as described below.

    FROM PRESS

    FIRING E1S1000rpm15.0mA 10.0Btdc

    TIMING

    THEN AT PRESS

    =GLOBAL(ENGINE)

    =CYLINDER(INDV)

    THEN AT PRESS

    = ADJUST RETARD

    = SELECT MODE

    8.2 The rst function is used to save the current (temporary) individualoffsets to EEPROM memory. When this is done, the ignition will loadthese offset settings every time the engine starts or reset is pressed.REFERENCE SECTION 7.0to adjust individual (temporary) offsets.

    AT THEFIRSTOPTIONSCREEN

    SAVE CYL OFFSETS

    NEXT or ENTER

    PRESS TO PRESS TO PRESS PRESS TOSAVE FOR NEXT EXITOFFSETS OPTION

    ENTER

    NEXT

    ESC

    8.3 The NEXTmode function can be used to reset all cylinder offset val-ues back to zero (both temporary memory and EEPROM memory).

    AT THENEXTOPTIONSCREEN

    RESET OFFSETS =0

    ENTER OR NEXT

    PRESS TO PRESS TO PRESS PRESS TORESET FOR NEXT EXITOFFSETS OPTION

    ENTER

    NEXT

    ESC

  • 8/13/2019 CPU-95 OI 4-08

    12/34

    FORM CPU-95 OI 4-0812

    CPU-95 DIGITAL IGNITION SYSTEM

    9.0 SETUP CONTROL OPTIONS

    9.1 Additional control settings and display features can be accessed un-der the setup menu. Changes made under the Setup menu are storedin EEPROM and remain xed until changed again. The Setup menucan be entered as described below.

    FROM PRESS

    FIRING E1S1000rpm

    15.0mA 10.0Btdc

    SETUP

    9.2 The rst setup screen permits the operator to enable or disable theMulti-Strike feature.

    Note 1: A special feature can e selected durin conuration to force Multi-Strieto e active elo 250 rpm, or hen the Misc. Input is rounded.

    This feature is not active in a standard conuration.

    Note 2: The Multi-Strie feature is automaticall turned off aove 1050 rpm.

    Note 3: The use of Multi-Strie rins ma tend to accelerate spar plu electrode

    erosion.Note 4: The Multi-Strie feature res the spar plu 2 times per event (~1100usec apart).

    Note 5: ON 791958-16 UNIT ONLY: The Multi-Strie feature is replaced the VariSpar lon duration (~2000 usec) spar.

    AT MULTI STRIKE

    on/OFFNext Esc

    TO TO FOR TOTURN TURN NEXT EXIT

    ON OFF OPTIONMULTI

    MULTI

    NEXT

    ESC

    9.3 The next setup screen permits the operator to select one of three igni-tion energy levels (E1,E2,E3). The energy levels are 75 millijoules (E1), 100millijoules (E2), 125 millijoules (E3).

    Note 1: A special feature can e selected durin conuration to use the maximumener level elo 250 rpm, or hen the Misc Input is rounded.

    This feature is not active in a standard conuration.

    Note 2: The ener is automaticall limited to E2 hen Multi-Strie is active.

    Note 3: The use of hiher spar ener ma tend to accelerate spar plu electrodeerosion.

    AT NOTE: Ener levelE1 is displaed.

    output A.

    OUTPUT ENERGYEsc E1/e2/e3

    TO TO FOR TOINCREASE DECREASE NEXT EXIT OPTION

    NEXT

    ESC

  • 8/13/2019 CPU-95 OI 4-08

    13/34

    www.altronicinc.com 13

    OPERATING INSTRUCTIONS

    9.4 The next setup screen is used to adjust the engine overspeed set-point. The setpoint can be adjusted in increments of 10 rpmto a max-imum of 2550 rpm.

    AT

    output A.

    ADJUST OVERSPEED

    Esc 2000 RPM

    TO TO FOR TOINCREASE DECREASE NEXT EXIT OPTION

    NEXT

    ESC

    9.5 The next setup screen is used to specify the exact position of the re-set pin. Both the reset position and the engine timing are displayed.

    Adjustments are made here to make the displayed timing match theactual spark timing as veried with a timing light. This adjustmenteffects the displayed timing but does NOTchange the actual timing

    of the rings.

    AT

    output A.

    RESET PIN> 30.5

    Esc 10.5Btdc

    TO TO FOR TOINCREASE DECREASE NEXT EXIT OPTION

    NEXT

    ESC

    9.6 The next setup screen is used to enable or disable VALUE PROTECTIONof all user values in the EEPROM memory. When protection is on,

    none of the EEPROM settings under the Setup or Timing menuscan be changed. This feature can be used to provide limited protec-tion from random changes by inexperienced operators.

    AT

    output A.

    VALUE PROTECTION

    on/OFFNext Esc

    TO TURN TO TURN FOR TOON PRO- OFF PRO- NEXT EXITTECTION TECTION OPTION

    NEXT

    ESC

    NOTE: Adjustment of this

    parameter should be done

    while individual cylinder off-

    sets are all at zero.

  • 8/13/2019 CPU-95 OI 4-08

    14/34

    FORM CPU-95 OI 4-0814

    CPU-95 DIGITAL IGNITION SYSTEM

    FOR DISPLAY MODULE P/N 791908-1 ONLY:The VALUE PROTECTIONcan bePASSWORDprotected. The password PROTECTION LOCKis enabled whenprogramming options from the 791908-1PC terminal program. Seethe Programming Instructions, FORM CPU-95 PI for details. Whenpassword protection is enabled the following menu appears insteadof the VALUE PROTECTIONmenu.

    PROTECTION LOCK

    ***** Next Esc

    To enter the password press, use the function keys F1, F2, F3, F4whereF1=1, F2=2, F3=3, F4=4where the number entered is equal to the userassigned ve digit password. After the last digit of the proper pass-

    word is entered, theVALUE PROTECTIONmenu shown above will appear.If the password is not known, press the ESCkey to exit or the NEXTkey to go on to the VIEW IGNITION SETUPmenu.

    9.7 The next setup screen can be used to view the conguration com-ments which describe the conguration of the ignition system.There are a total of 8 screens which can be rotated to the displayusing the NEXTkey.

    ATVIEW IGN. CONFIG

    Next Esc Enter

    PRESS TO PRESS TO PRESS TO PRESS TOVIEW GO TO EXITCONFIG NEXTENTER

    NEXT

    ESC

    The conguration screens are shown starting on the next page.

    NOTE: Because EEPROMS

    can be recongured (using

    a PC and Altronics con-

    guration software), these

    comments should be viewed

    to identify and verify the

    conguration settings of the

    ignition prior to operation.

    Refer to the programming

    instructions, form CPU-95

    PI, for further information on

    conguration.

  • 8/13/2019 CPU-95 OI 4-08

    15/34

    www.altronicinc.com 15

    OPERATING INSTRUCTIONS

    The folloin tpes of screens can e vieed pressin ENTER to start and NEXT to advance.

    FIRING PATTERN CODE: (H4A360.FS100)

    SPECIAL FEATURE CODE: (#001) (1STEP DEFAULT)

    IGNITION MODULE TYPE: (PART NUMBER)

    DATE CONFIGURED: (01-22-07)

    TIME CONFIGURED: (12:00)

    CONFIGURED BY: (USER NAME)

    TERMINAL VERSION #: (V1.00)

    CURRENT LOOP CURVE DESCRIPTION

    AT 4 MA 0 RETARD

    AT 20 MA 24 RETARD

    USER SPECIFIED DESCRIPTION

    RPM RETARD CURVE DESCRIPTIONRETARD 10 BELOW 100 RPM

    RAMP TO 0 AT 200 RPM

    USER SPECIFIED DESCRIPTION

    LOCATION: USER SPECIFIED DESCRIPTION

    ENGINE NUMBER OR DESCRIPTIONUSER SPECIFIED DESCRIPTION

    SPECIAL USER COMMENTS AREA #1 USER SPECIFIED COMMENTS

    SPECIAL USER COMMENTS AREA #2 USER SPECIFIED COMMENTS

    ROTATION CONTINUES AGAIN THROUGH THE 8CONFIGURATION COMMENT SCREENS.

    ESC. TO EXIT TO HOME SCREEN.

    H4A360.FS100#001

    UNIT 791950-16 NEXT

    01-22-07 12:00

    By:Joe v1.00 NEXT

    LOOP RETARD: 24

    4/20ma 0/24ret NEXT

    RPM RETARD: YES

    Ramp10/0 100/200 NEXT

    LOCATION: ALT.

    GIRARD OHIO USA NEXT

    ENGINE#: 8G825

    Number 4 USA-GAS NEXT

    USER

    COMMENTS #1 NEXT

    USER

    COMMENTS #2 NEXT

    H4A360.FS100#001

    UNIT 791950-160 NEXT

  • 8/13/2019 CPU-95 OI 4-08

    16/34

    FORM CPU-95 OI 4-0816

    CPU-95 DIGITAL IGNITION SYSTEM

    BREAKDOWN OF FIRING PATTERN CODE:

    H REPRESENTS THE NUMbER OF OUTPUTS USED, IN THIS CASE 8 (F =6, L = 12, ETC.)

    4 REPRESENTS THE CYCLE TYPE OF THE ENGINE

    2 = TwO-CyCLE

    4 = FOUR-CyCLE

    A REPRESENTS THE ALTRONIC PATTERN CODE (SEE FORM CPU-95 AL)

    360 REPRESENTS THE NUMBER OF GEAR TEETH OR HOLES TO BE SENSED

    F REPRESENTS A DESIGNATOR FOR CPU-95 VERSION 1

    S REPRESENTS THE CURRENT LOOP RETARD CURVE TYPE

    A = 0 AT 4MA / 48 AT 20MA

    b = 0 AT 4MA / 36 AT 20MA

    C = 0 AT 4MA / 24 AT 20MA

    D = 0 AT 4MA / 16 AT 20MA

    E = 0 AT 4MA / 8 AT 20MA

    N = SPECIAL NON-STANDARD TIMING CURVE VS. CURRENT OR RPM, NON-FACTORY PROGRAMMED

    S = SPECIAL NON-STANDARD TIMINg CURVE VS. CURRENT OR RPM, FACTORy PROGRAMMED

    X = NO CURRENT LOOP CURVE

    100 REPRESENTS THE SPECIAL VERSION NUMBER (ONLY EXISTS FOR TYPES N AND S)

    #001 REPRESENTS THE SPECIAL FEATURE CODE

    (TOTAL SUM OF ALL SELECTED OPTIONS; 001=DEFAULT) 064 = FORCE MULTI-STRIkE wHEN RPM IS LESS THAN 250

    032 = FORCE MAX ENERgy wHEN RPM IS LESS THAN 250

    016 = USE 1 STEP RETARD wHEN RPM IS LESS THAN 250

    004 = FORCE MULTI-STRIkE wHEN MISC INPUT IS gROUNDED

    002 = FORCE MAX ENERgy wHEN MISC INPUT IS gROUNDED

    001 = USE 1 STEP RETARD WHEN MISC INPUT IS GROUNDED

    NOTE: This number must be

    selected and properly docu-

    mented by the originator.

  • 8/13/2019 CPU-95 OI 4-08

    17/34

    www.altronicinc.com 17

    OPERATING INSTRUCTIONS

    9.8 The last setup screen permits the operator to enter an ignition testmode. This test mode can re all outputs in rotation, or individualoutputs at a slow rate. This feature can be used to troubleshoot pri-mary wiring and Output Module operation. Test mode will termi-nate if rotation of the engine is sensed. Diagnostic features do notfunction while in test mode.

    ATRUN TEST MODE

    Next Esc Enter

    PRESS FOR PRESS TO PRESS PRESS TOTEST MODE FOR NEXT EXIT

    OPTIONENTER

    NEXT

    ESC

    THE OPERATOR MUST FULLY PURGE THE ENGINE OF COM-BUSTIBLE MIXTURES PRIOR TO SELECTING THE TEST MODEOPERATION. PRESSING THE ENTER KEY AGAIN IS A CONFIRMA-

    TION OF THIS ACTION.

    WARNING:

    THENBEFORESTARTINGTEST MODE

    IS ENGINE PURGED

    Esc Enter

    PRESS TO PRESS TO PRESS TOVERIFY EXITPURGED

    ENTER

    NEXT

    Then the test mode screen indicates that the ignition is ring and

    permits the operator to select the output to be red.

    ATTest-Mode ALL

    Esc

    PRESS TO PRESS TO PRESS TO PRESS TOSELECT SELECT EXITPREVIOUS NEXTOUTPUT

    OUTPUT

    ESC

    Test-Mode selection rotates as described below.

    MODEL # ROTATION SEQUENCE

    791950-8: ALL, A, B, C, D, E, F, K, L

    791950-16, 791958-16: ALL, A, B, C, D, E, F, K, L, M, N, P, R, S, T, U, V, ALL

    791950-18: ALL, A, B, C, D, E, F, G, H, K, L, M, N, P, R, S, T, U, V, ALL

    791952-18: ALL (Individual output test mode not availale.)

    NOTE: 791908-1 Display

    Module only: The Test-Mode

    is enabled by the user dur-

    ing initial setup of display

    module from PC terminal

    program. See form CPU-95 PI

    for details.

  • 8/13/2019 CPU-95 OI 4-08

    18/34

    FORM CPU-95 OI 4-0818

    CPU-95 DIGITAL IGNITION SYSTEM

    10.0CPU-95 DIAGNOSTICS

    10.1 A diagnostic fault represents the most severe classication of prob-lems. The presence of a diagnostic fault will inhibit the ignitionfrom ring. When a fault is detected several things will occur:

    Inition ill stop rin.

    Fire Conrm Out sitch ill open.

    Fault Out sitch ill open.

    Alarm Out sitch ill open.

    Alarm LED in the inition unit ill turn on.

    Home status ill read FAULT, and the ottom line ill ash VIEwDIAGNOSTICS.

    FAULT 0rpm

    VIEW DIAGNOSTICS

    10.2 A diagnostic warning represents the least severe classication of prob-lems. The ignition will continue to re in the presence of a diagnostic

    warning. When a warning is detected, several things will occur:

    Alarm Out sitch ill open.

    Alarm LED in the inition unit ill turn on.

    Home status ill read wARNINg, and the ottom line ill ash VIEwDIAGNOSTICS.

    WARNING 300rpm

    VIEW DIAGNOSTICS

    10.3 If the Alarm Out switch is being used to turn on an audible alarm orasher, the user can acknowledge the alarm as described below.

    PRESS

    ALARM

    ACK

    Acknowledgment of the alarm results in the following until a resetis commanded or until another fault or warning may occur.

    Alarm Out sitch ill return to its closed position.

    Alarm LED ill ash to indicate that an alarm is present ut acnoleded.

    NOTE: Diagnostic FAULTS

    will supersede diagnostic

    WARNINGS.

  • 8/13/2019 CPU-95 OI 4-08

    19/34

    www.altronicinc.com 19

    OPERATING INSTRUCTIONS

    10.4When a fault or warning is present, the operator can display theactual cause of the diagnostic as depicted below.

    FROM THE PRESSHOMESCREEN

    FAULT 0rpm

    VIEW DIAGNOSTICS

    DIAG

    Then from the diagnostic description screens use the following keys.

    PRESS TO OR PRESS PRESS TOVIEW NEXT TO VIEW EXIT

    NEXTDIAG

    NEXT

    ESC

    10.5 Diagnostic Fault screens, in order of display priority:

    when zero ear-tooth pulses areseen eteen to reset pulses.

    when too man ear-tooth pulsesare seen ithout a reset pulse.

    when there are no Hall-effectpicup pulses or hen the pic-ups are not snchronized.

    when too man or too fe ear-tooth pulses are seen eteenreset pulses.

    The received numer of pulses isdisplaed.

    when the enine speed exceedsthe overspeed setpoint.

    Maximum oserved speed is alsodisplaed.

    when the chec-sum of micro-processor rmare cannot everied.

    Unit requires service.

    GT PICK-UP FAULT

    MISSING PULSES

    RS PICK-UP FAULT

    MISSING PULSES

    HE PICK-UP FAULT

    MISSING//NO-SYNC

    RING-GEAR FAULT

    352 TEETH READ

    ENGINE OVERSPEED

    1023 RPM

    BOTTOM BOARD uP

    CHECKSUM FAILED

  • 8/13/2019 CPU-95 OI 4-08

    20/34

    FORM CPU-95 OI 4-0820

    CPU-95 DIGITAL IGNITION SYSTEM

    10.6 Diagnostic Warning screens, in order of display priority:

    This screen indicates that the current-loop has deviated out-side the limits of2 mA and 22 mA. The current loop follos the conured curve hich is speci -ed from 0-25 mA. This dianostic is active onl if the current loop retard is on.

    This screen indicates that at some point no loop data as received from theDispla Module. In this condition, the timin for 0 mA is used. This test is ac -tive onl if the current loop retard is on.

    This screen indicates that the rin pattern conuration data saved inEEPROM memor is incorrect or incomplete. The EEPROM memor must ereprorammed or replaced.

    This screen indicates that dianostics have identied an open circuit on theprimar output pin A. Normall indicates fault irin or a failed coil.

    This screen indicates that dianostics have identied a short circuit condition

    on the primar output pin b. This ould normall indicate a coil is misired,or the primar ire is shorted.

    This screen indicates that the dianostics have identied a lo spar demandcondition on the plu at the C coil. This is often caused a shorted spar

    plu or shorted secondar ire.

    This screen indicates that the dianostics have identied a hih spar de-mand condition on the spar plu at the D coil. This is often caused ornspar plus.

    This screen indicates that the dianostics have identied a no spar conditionon the plu at the E coil. No spar occurred since the demand as reaterthan the output capailit of the coil.

    This screen indicates that the dianostics have detected a condition here

    the averae value of output F is sinicantl loer than the averae of all theactive outputs on the enine.

    This screen indicates that the dianostics have detected a condition herethe averae value of output k is sinicantl hiher than the averae of allthe active outputs on the enine.

    CURRENT LOOP

    OUT OF RANGE

    DISPLAY BOARD

    DATA INTERRUPTED

    EEPROM MEMORY

    CHECKSUM FAILED

    PRIMARY OPEN

    A

    PRIMARY SHORT

    B

    LO SPARK VOLT.

    C

    HI SPARK VOLT.

    D

    NO SEC. SPARK

    E

    LO FROM ENGINE F

    HI FROM ENGINE

    K

  • 8/13/2019 CPU-95 OI 4-08

    21/34

    www.altronicinc.com 21

    OPERATING INSTRUCTIONS

    10.7 After all of the diagnostics have been read, the user can reset thewarnings and faults by pressing the reset key as pictured below.

    PRESS PRESSTO EXIT

    ESC

    Reset

    Pressing the reset key performs all of the following actions:

    Clears all dianostic arnins from memor.

    Clears all dianostic faults from memor.

    Clears a latched shutdon condition hen the input is no lonerrounded.

    Causes temporar clinder timin offsets to e overritten fromEEPROM memor

  • 8/13/2019 CPU-95 OI 4-08

    22/34

    FORM CPU-95 OI 4-0822

    CPU-95 DIGITAL IGNITION SYSTEM

    11.0 UNDERSTANDING AND USING THE SECONDARY SPARKDIAGNOSTICS

    11.1. The spark reference number is a unitless number which correlateswith voltage demand at the spark plug and is calculated for every r-ing of each cylinder. As the voltage increases, the reference number

    also increases. The number is non-linear and will increase faster athigher voltages (aove 20V). The usefulness of the number lies not inits absolute value, but rather in how the number changes over timeas the spark plugs erode. With a little experience, the engine opera-tor will be able to tell when spark plugs require changing. Abnormalconditions in the ignition system, such as open or short circuits inthe primary and secondary wiring, can also be detected.

    11.2 The reference cylinder spark data number can be viewed separate-ly for each ignition output (cylinder) in two ways, and compared tothe average of the entire engine:

    INSTANTANEOUSvalue: shon in ( )

    CYLINDER AVERAGEvalue: CAVgFROM THE PRESSHOME SCREEN TO VIEW DISPLAY

    FIRING E1S1000rpm

    15.0mA 10.0Btdc SCREENF1

    CYLINDER CYLINDERDESIGNATOR AVERAGE VALUEINSTANTANEOUS AVERAGE VALUE

    CYL A 115 CAVG

    (112) 116 EAVG

    PRESS PRESS PRESS PRESSTO VIEW TO VIEW TO VIEW TO

    NEXT OFFSET NEXT EXITCYLINDER

    F1 ADJ. F4 CYLINDERNEXT

    ESC

    ON THE 791908-1 DISPLAY MODULE ONLY:Press F2for Bar Graph displayof Spark number.

    CYLINDER CYLINDERDESIGNATOR AVERAGE VALUEINSTANTANEOUS AVERAGE VALUE

    CYL A 115 CAVG

    L|||||||| H

    PRESS PRESS PRESS PRESS

    TO VIEW TO VIEW TO VIEW TONEXT OFFSET NEXT EXITCYLINDER

    F1 ADJ.

    F4 CYLINDER

    NEXT

    ESC

  • 8/13/2019 CPU-95 OI 4-08

    23/34

    www.altronicinc.com 23

    OPERATING INSTRUCTIONS

    11.3 The offset adjustment screen (F4) permits the operator to adjust anoffset to the spark reference number ( 15 counts)to compensate forminor variations in reference numbers between individual coils ofthe same type and voltage demand. To initialize all offset values tozero from this screen, press RESET.

    FROM THE PRESSHOME TO VIEWSCREEN DISPLAY

    FIRING E1S1000rpm

    15.0mA 10.0Btdc SCREENF1

    CYLINDER CYLINDERDESIGNATOR AVERAGE VALUEINSTANTANEOUS AVERAGE VALUE

    CYL A1 115 CAVG

    + 0 116 EAVG

    PRESS PRESS PRESS TO VIEW TO VIEW TO NEXT NEXT EXIT

    CYLINDER

    F4 CYLINDER

    NEXT

    ESC

    PRESS PRESSTO VIEW TO ZEROBASE ALLDISPLAY

    F1 OFFSETS

    Reset

    11.4 The spark reference number is used in conjunction with compara-tive thresholds to set diagnostic codes for several different ignitionsystem and spark plug conditions. When a threshold is violatedtwice in a row, the corresponding diagnostic ag is set for the ap-propriate cylinder. The diagnostic ags are latching and will existuntil the unit is restarted or until a reset or power-down occurs.

    Open Primar CAVg < 1

    Shorted Primar CAVg < 50

    Lo Spar Voltae CAVg < user prorammale threshold (tp. 100)

    Hih Spar Voltae CAVg > user prorammale threshold (tp. 180), also Forces E2

    No Secondar Spar CAVg > user prorammale threshold (tp. 250), also Forces E3

    Lo From Enine (EAVg - CAVg) > user prorammale threshold (tp. 20)

    Hih From Enine (CAVg - EAVg) > user prorammale threshold (tp. 20)

    NOTE: Improper use of this

    feature may limit the effec-

    tiveness of the diagnostic

    system and result in spark

    reference numbers that

    mask real or create false

    problems.

  • 8/13/2019 CPU-95 OI 4-08

    24/34

    FORM CPU-95 OI 4-0824

    CPU-95 DIGITAL IGNITION SYSTEM

    11.5The spark reference number is also used to automatically changespark energy for different ignition system conditions. The minimumenergy setting is selected under the Setup Menu(SEE SECTION 9.3).En-ergy will automatically be adjusted in response to the engine aver-age spark reference number (EAVG)based on four individual thresh-olds listed below. Additionally, spark energy will automatically be

    increased when a High Spark Voltage or No Secondary Spark warn-ing exists for any cylinder.

    Auto Enale E2 EAVg > user prorammale threshold (tpical 200)

    Auto Disale E2 EAVg < user prorammale threshold (tpical 190)

    Auto Enale E3 EAVg > user prorammale threshold (tpical 205)

    Auto Disale E3 EAVg < user prorammale threshold (tpical 195)

    11.6 The above user programmable thresholds need to be adjusted basedon the type of coil being used and on the operating characteristics(specically, voltage demand) of the engine. There are known dif-ferences between various types of Altronic coils, and slight varia-

    tions are normal between coils of the same type. In order to maxi-mize the usefulness of the cylinder spark reference number, it isrecommended that all coils be of the same type and vintage(production date). This will aid greatly in detecting variations inone cylinder vs. the general trend in the engine. The typical rangesto be expected in normal operation with new spark plugs are:

    Older 501061 (lue) coils: 70 to 90

    Current 501061 (lue) coils: 90 to 120

    Current 591010 (red) coils: 120 to 140

    Current 501061-S (shielded lue) coils: 110 to 130

    Current 591007 / 591011A / 591011b coils: 70 to 90

    11.7 The indicated thresholds were designed to be adjustable so that theuser can customize these diagnostics to t the specic needs of eachengine. It will take some testing and adjustment to obtain thresholdsthat optimize the use of these features. For maximum benet, thespark reference number for each cylinder should be recorded at nor-mal operating load with new spark plugs installed and then moni-tored over a period of time for changes. The HI SPARK VOLTAGEalarmlevel should be set (typically) at 180 initially and can be adjusted asexperience dictates. A gradual increase in the spark reference num-

    ber is expected over time as the spark plug electrodes erode.

  • 8/13/2019 CPU-95 OI 4-08

    25/34

    www.altronicinc.com 25

    OPERATING INSTRUCTIONS

    11.8 In addition to energy control and the diagnostic ags, the referencenumbers can also be used for predictive purposes:

    A. As the numbers increase toward the preset HI SPARK VOLTAGEthreshold(SEE SECTION 12.3), the operator knows that a changeof spark plugs should be scheduled. With this information, thisfunction can be determined on an actual need basis rather than

    a predetermined schedule. Also, unexpected engine misring orshutdowns can be avoided by tracking the reference numbers ona routine basis.

    B. The reference numbers can provide an early warning of a dif-ference in operation in a given cylinder(s). A reading higher (orlower) than the other cylinders, when such a difference is notnormally present, tells the operator of a potential problem; thisallows further troubleshooting and evaluation to take place be-fore an unexpected operational problem develops. (SEE SECTION12.5, 12.6.)

    11.9 Other Information regarding the spark reference number:

    A. The spark energy setting has only a small effect on the referencenumber if the spark plug res correctly. Therefore, the high andlow voltage thresholds should hold across the energy settingsif the spark plugs continue to re correctly. On the other hand,a worn plug may not re consistently on energy setting E1but

    will on energy setting E2; in this case there will be a signicantdifference in the reference number when the energy setting ischanged. Operators may be able to increase spark plug life byoperating initially with new spark plugs on E1energy setting anduse the HI SPARK VOLTAGE alarm as an indicator to manually in-crease the energy progressively to E3.

    B. The spark reference number is designed to work with one coilper output. Where two coils are connected to the same primarylead, the number will tend to be an average of the conditions atthe two spark plugs. While some of the benets of the spark ref-erence number can still be realized, the usefulness of the num-

    ber in detecting deviations between cylinders (alarm levels) willbe reduced.

    NOTE:See Section 11.5for

    automatic system adjust-

    ment of ignition energy.

  • 8/13/2019 CPU-95 OI 4-08

    26/34

    FORM CPU-95 OI 4-0826

    CPU-95 DIGITAL IGNITION SYSTEM

    12.0 THRESHOLD ADJUSTMENT SCREENS

    12.1 Nine threshold adjustment screens enable the operator to calibratethresholds used to diagnose potential ignition problems and control ig-nition energy based on the spark reference numbers. All of the thresh-old screens have the same button functions as described with the rst

    threshold screen. All thresholds are accessed under the F2key.

    FROM PRESS TO VIEW 1ST THRESHOLD

    FIRING E1S1000rpm

    15.0mA 10.0Btdc SCREEN

    F2

    12.2 If the CAVGreference number of a cylinder is below the LOW SPARK

    VOLTAGEthreshold, a diagnostic warning for that cylinder will occur.This test will identify a low voltage demand condition which mayresult from a shorted coil, secondary lead or spark plug. To disablediagnostic, set value to zero.

    LO SPARK VOLTAGE

    THRESHOLD< 100

    PRESS TO PRESS TO PRESS TO VIEW NEXT VIEW NEXT EXIT THRESHOLD THRESHOLDF2

    NEXT

    ESC

    PRESS TO PRESS TOINCREASE DECREASETHRESHOLD THRESHOLD

    12.3 If the CAVGreference number of a cylinder is above the HIGH SPARK

    VOLTAGEthreshold, a diagnostic warning for that cylinder will occur.When a high spark warning is present, the ignition energy will au-tomatically be increased to at least E2. This test will identify a high

    voltage demand condition which may result, for example, from wornspark plugs or poor air-fuel ratio control. To disable, set to 255.

    HI SPARK VOLTAGE

    THRESHOLD >150

  • 8/13/2019 CPU-95 OI 4-08

    27/34

    www.altronicinc.com 27

    OPERATING INSTRUCTIONS

    12.4 If the CAVGreference number of a cylinder is above the NO SECONDARYSPARKthreshold, a diagnostic warning for that cylinder will occur.

    When a no secondary spark warning is present, the ignition energywill automatically be increased to E3as long as the system is not inmulti-strike mode. This test will identify cylinder rings that do notresult in a spark an open circuit condition at the secondary of the

    coil resulting from a worn spark plug, or a disconnected or failedsecondary wire. To disable, set to 255.

    NO SEC. SPARK

    THRESHOLD >250

    12.5 If the difference between EAVGand CAVGreference numbers is great-er than the LOW FROM ENGINEthreshold, a diagnostic warning for thatcylinder will occur. This test will identify a cylinder whose voltagedemand is too far below the average engine voltage demand.

    Default = 60

    LO FROM ENGINE

    THRESHOLD > 60

    12.6 If the difference between CAVGand EAVGreference numbers is greaterthan the HIGH FROM ENGINEthreshold, a diagnostic warning for thatcylinder will occur. This test will identify a cylinder whose voltagedemand is too far above the average engine voltage demand.

    Default = 60

    HI FROM ENGINE

    THRESHOLD > 60

    12.7 If the EAVG reference number is greater than the EAVG E2 ENABLEthreshold, the energy will be increased to at least E2. This featurecan be used to automatically increase the spark energy as the volt-age demand of the engine increases.

    Default = 200

    EAVG E2 ENABLE

    THRESHOLD >200

  • 8/13/2019 CPU-95 OI 4-08

    28/34

    FORM CPU-95 OI 4-0828

    CPU-95 DIGITAL IGNITION SYSTEM

    12.8 If the energy is at level E2and if the base energy setting under theSETUPkey is E1, then the EAVG E2 DISABLEthreshold setting is used toautomatically decrease the energy from E2.

    Default = 190

    EAVG E2 DISABLE

    THRESHOLD 205

    12.10If the energy is at E3and if the base energy setting under the SETUPkey is not E3, then the EAVG E3 DISABLEthreshold setting is used to au-tomatically decrease the energy from E3. NOTE:This threshold must

    be at least 2counts below the enable threshold (SECTION 12.9).

    Default = 195

    EAVG E3 DISABLE

    THRESHOLD >195

    NOTE: This threshold must

    be at least 2 counts below

    the enable threshold.

    See section 12.7.

  • 8/13/2019 CPU-95 OI 4-08

    29/34

    www.altronicinc.com 29

    OPERATING INSTRUCTIONS

    13.0 SPECIAL INSTRUCTIONS FOR 791908-1 DISPLAY MODULE ONLY

    13.1 The 791908-1 Display Module incorporates data logging and a half du-plex RS-485port which is Modbus RTU slave compliant. The protocolused follows the Modicon Modbus RTU standard. A complete listing

    of the Modbus register addresses is included on the CPU-95terminalprogram CD, along with a PC based Modbus compatible monitoringprogram which can be used to access the ignition data remotely.

    13.2 The auxiliary communications port conguration must be set tomatch the values expected by the Modbus master. This is done inthe 791908-1Display Module via the AUX PORT SETUPmenu which ap-pears immediately after the RUN TEST MODEmenu under the SETUPmenu. (SEE SECTION 9.8).

    AUX PORT SETUP

    Next Esc Enter

    PRESS TO PRESS TOSETUP PORT EXIT

    ENTER

    ESC

    AUX PORT NODE ID

    1

    PRESS PRESS TOARROWS TO CONTINUE

    SET NODE

    NEXT

    AUX PORT MODE

    ModbusRTU96008n1

    PRESS TO PRESS TOARROWS TO EXITSET MODE

    ESC

    Supported aud rates are 300, 600, 1200, 2400, 4800, 9600, 19200, 38400.

    Supported parit selections are n (none), o(odd), e(even).

    Supported data it format is 8 ith 1 stop it.

    In order to simplify troubleshooting of the Modbus connection, anAUX PORTdiagnostic menu is provided. To access this menu, pressthe DIAGkey when viewing any of theAUX PORTsetup screens above.

  • 8/13/2019 CPU-95 OI 4-08

    30/34

    FORM CPU-95 OI 4-0830

    CPU-95 DIGITAL IGNITION SYSTEM

    PRESS TOVIEW DIAGS.

    DIAG

    MODBUS ERROR

    NONE

    PRESS TORETURN TOPREVIOUSMENU

    NEXT

    ERROR LIST: CRC Checsum on incomin data invalid

    INVALID ADDRESS Received data contained invalid address

    INVALID DATA LEN Received data as the ron lenth

    REC bUF OVF Incomin data reater than 256 tes

    UkN FN Unnon function called

    NONE No errors since last reset

    PRESS TO PRESS TOCLEAR EXITERROR

    Reset

    ESC

    13.3 The 791908-1 Display Module supports data logging of the infor-mation normally available from the display of the CPU-95. The unitretains 100 datalogs which are stored in a FIFO (rst in, rst out)manner. When 100logs are stored, the oldest log is purged and thenewest added. The oldest data is stored as LOG NO. 100and the new-

    est as NO. 1; there is also a copy of the current values available asDATALOG 0. The datalogs can be accessed by the special PC terminalprogram supplied with the unit or by a special Modbus commandsent by the User supplied PLC or computer system. More detailedinformation is provided on the terminal CD.

    The DATALOG SETUPmenu appears after the AUX PORT SETUPmenu. Ifdatalogs are not being used, press the NEXTkey to proceed to theBARGRAPH SETUPmenu.

    DATALOG SETUP

    Next Esc Enter

    PRESS TO PRESS TOSET SEECURRENT BARGRAPHMONTH

    ENTER

    SETUP

    NEXT

  • 8/13/2019 CPU-95 OI 4-08

    31/34

    www.altronicinc.com 31

    OPERATING INSTRUCTIONS

    CURRENT DATE

    0122/2007

    ARROWS TO PRESS TO

    SET MONTH SET DAY

    ENTER

    CURRENT DATE

    0122/2007

    ARROWS TO PRESS TOSET DAY SET YEAR

    ENTER

    CURRENT DATE

    01/222007

    ARROWS TO PRESS TOSET YEAR SET

    CURRENT TIME

    NEXT

    CURRENT TIME

    0801:00

    ARROWS TO PRESS TOSET HOUR SET

    MINUTE

    ENTER

    CURRENT TIME

    0801:00

    ARROWS TO PRESS TOSET MINUTE SET

    DATALOG INTERVAL

    NEXT

  • 8/13/2019 CPU-95 OI 4-08

    32/34

    FORM CPU-95 OI 4-0832

    CPU-95 DIGITAL IGNITION SYSTEM

    DATALOG INTERVAL

    5min.

    ARROWS TO PRESS TOSET SET

    INTERVAL DATALOG RETENTION

    NEXT

    DATALOG POWERUP

    RETAIN/erase

    ARROWS TO PRESS TOSET SETRETENTION DATALOG

    STOP

    NEXT

    LOG AFTER STOP?

    yes/NO

    ARROWS TO PRESS TOSET STOP SET

    TIMING TRACKER

    ESC

    It is possible to setup the system so that any change to the ignitiontiming will trigger a datalog event (an exception report). Exceptionreports are automatically generated for alarms or shutdowns.

    TRACK TIMING?

    yes/NO

    ARROWS TO PRESS TOSET OPTION RETURN TO

    DATE MENU

    NEXT

  • 8/13/2019 CPU-95 OI 4-08

    33/34

    www.altronicinc.com 33

    OPERATING INSTRUCTIONS

    13.4 The Bargraph displaySEE SECTION 11.2of the spark reference num-ber on Display Module 791908-1can be scaled by changing the LOWand HIGHendpoints of the bargraph. A smaller range between end-points increases the resolution of the Bargraph.

    BARGRAPH SETUP

    Next Esc Enter

    PRESS TO PRESS TOSET RETURN TOBARGRAPH OTHERENDPOINTS

    ENTER

    MENUS

    NEXT

    BARGRAPH LIMIT

    LOW 100

    PRESS PRESS TOARROWS CONTINUESET LOW

    NEXT

    BARGRAPH LIMIT

    HIGH 150

    PRESS PRESS TOARROWS RETURNSET NODE HOME

    ESC

    The Bargraph LOW LIMITis adjustable from 0 to the value set for theLOW SPARK threshold alarm SEE SECTION 12.2 for details. The Bar-graph HIGH LIMITis adjustable from the value set for the HIGH SPARKthreshold to 255SEE SECTION 12.3for details.

  • 8/13/2019 CPU-95 OI 4-08

    34/34

    CPU-95 DIGITAL IGNITION SYSTEM

    SPECIFICATIONS