COVER SHEET FIRE RISK ASSESSMENT
Employer or other Responsible Person: University of Kent; Vice Chancellor; Director of Kent Hospitality
Address of Property: Rutherford College
(excludes Extension)
Person(s) Consulted: Reception, Housekeeping & Estates staff; various residents; Master & Assistant;
Rob Sherwood (Fire Safety Officer, Kent Fire & Rescue Authority)
Assessor: Andrew Briggs, TechIFSM, MIIRSM
Date of Fire Risk Assessment: 16th November 2007 - 29th February 2008
Date of Previous Fire Risk Assessment: 20th February 2006 - SHOULD BE READ IN CONJUNCTION WITH THIS REVIEW.
Suggested Date for Review: February 2010, or as per UoK SHEU official schedule, or in event of significant change
Document dated 29th February 2008
8th October 2008 - 16.6 amended/updated
13th February 2009 - 10.2 amended/updated
Fire Risk Assessment in accordance with Publicly Available Standard PAS 79 (British
Standards Institute): Fire Risk Assessment - Guidance and a recommended methodology
GENERAL BUILDING DESCRIPTION FIRE RISK ASSESSMENT
1.0 The Building
1.1 Number of floors Five
1.2 Approximate floor area: Not reviewed
1.3 Construction Details: Predominantly concrete/block - robust fire performance
1.4 Occupancy: Not reviewed
2.0 The Occupants
2.1 Approximate maximum number: Not reviewed
2.2 Maximum number of staff at any one time: Not reviewed
2.3 Maximum number of members of public: Not reviewed
(Add more detail by area or room as appropriate)
3.0 Occupants at Special Risk
3.1 Sleeping occupants: 305 student study bedrooms
3.2 Occupants with disabilities: Disabled access to levels 2, 3 & 4.
3.3 Occupants in remote areas: Some 11 corridors are dead-end conditions containing excessive travel distances.
3.4 Others: Nil significant
4.0 Fire Loss Experience
4.1 Fires in past 12 years: 11, all relatively minor and rapidly extinguished. See summary on file (SHEU).
GENERAL BUILDING DESCRIPTION FIRE RISK ASSESSMENT
5 of above fires originated in residential kitchenettes.
4.2 Cost of fire losses: Not reviewed
5.0 Other Relevant Information
5.1 Detail: N/A
6.0 Relevant Fire Safety Legislation
6.1 Statutory provisions: Regulatory Reform (Fire Safety) Order 2005 & referred Official Guidance
FIRE HAZARDS FIRE RISK ASSESSMENT
INDEX DETAIL YES NO N/A CONTROL MEASURES
7.0 Electrical Sources of Ignition
7.1 Reasonable measures taken to prevent fires of
electrical origin?
X Continue to maintain safe separation distance of ½ metre between appliances
and combustible materials throughout building . Switch equipment off at the end
of the working day.
7.2 Fixed installation periodically inspected and
tested? Portable appliance testing carried out?
Suitable policy regarding use of personal
electrical appliances? Suitable limitation of
trailing leads and adaptors?
X One item found missed from Portable Appliance Testing (iron in W2.3 laundry) -
PAT generally fully implemented but all staff should be trained to remain vigilant
as to status and condition of appliances.
7.2 suppl. Recommendation to consider Portable Appliance Testing of student-owned
appliances.
8.0 Smoking
8.1 Reasonable measures taken to prevent fires as a
result of smoking? Prohibited where appropriate?
Arrangements for smokers? Evidence of
breaches?
X Ensure University smoking policy continues to be implemented and enforced
insofar as possible.
9.0 Arson
9.1 Does basic security against arson by outsiders
appear reasonable? Fire load available for
ignition by outsiders?
X
10.0 Cooking & Heating
10.1 Are reasonable measures taken to prevent fires
as a result of cooking & heating? Is all essential
maintenance up to date and recorded?
X Ensure ban on additional cooking and other appliances in residences continues
to be enforced insofar as possible. Portable electrical heaters with open
elements, such as fan or convector heaters, must not be used.
10.2 Are filters changed and ductwork cleaned
regularly?
X Ductwork apparently not cleaned since 1994. Clean urgently and implement
regular maintenance programme, to include fire dampers.
10.3 Are suitable extinguishing appliances available? X
11.0 Lightning
FIRE HAZARDS FIRE RISK ASSESSMENT
11.1 Does the building have a lightning protection
system?
X
12.0 Other Significant Ignition Sources
12.1 Are there other significant ignition sources
present?
X Ensure ban on candles, joss sticks etc continues to be enforced insofar as
possible.
13.0 Housekeeping Note: some office & academic areas contain relatively high fire loadings which
should be reduced.
13.1 Is the standard of housekeeping adequate? X Standard of housekeeping in S3-1 and 'rag store' is unacceptable (see 13.3
below) and must be corrected.
13.2 Are combustible materials separated from ignition
sources?
X Continue to maintain safe separation distance of ½ metre between appliances
and combustible materials throughout building .
13.3 Is there an avoidance of unnecessary
accumulation of combustible materials or waste?
X S3-1, S3-3 and the 'rag store' off the E1S stairwell contain very high fire loading.
Combustibles content must be reduced significantly and kept in an orderly
manner so as to minimise flame spread in the event of a fire.
13.4 Is there appropriate storage of combustible
materials?
X
13.5 Is there avoidance of inappropriate storage of
combustibles materials?
X
14.0 Outside Contractor and Building Works
Hazards14.1 Is there satisfactory control over works carried out
in the building by outside contractors?
X
14.2 Are adequate fire safety conditions imposed on
outside contractors?
X
15.0 Dangerous Substances
15.1 Have the hazardous properties of dangerous
substances been considered?
X
15.2 Is there adequate information on safety provided
by the supplier on any relevant safety data sheet?
X
15.3 Has account been taken regarding:
FIRE HAZARDS FIRE RISK ASSESSMENT
● the special, technical and organisational
measures and the substances used and their
possible interactions.
X
● the amount of the substance involved X
● where the work will involve more than one
dangerous substance, the risk presented by such
substances in combination
X
● the arrangements for the safe handling, storage
and transport of dangerous substances and of
waste containing dangerous substances
X
● any other measures introduced as a result of the
RRO X
15.4 Are there safe systems of work for maintenance,
where there is the potential for a high level of
risk? X
15.5 Are sufficient control measures in place to counter
the likelihood that an explosive atmosphere will
occur and its persistence including adjacent
areas? X
15.6 Are sufficient control measures in place to counter
the likelihood that ignition sources, including
electrostatic discharges, will be present and
become active and effective X
15.7 Has account been taken regarding the scale of
the anticipated effects? X
15.8 Is sufficient additional safety information available
to enable the assessment to be completed?
X
FIRE PROTECTION FIRE RISK ASSESSMENT
INDEX DETAIL YES NO N/A CONTROL MEASURES
16.0 Means of Escape
16.1 Is it considered that the building is provided with
reasonable means of escape in case of fire?
X
16.2 Is there adequate provision of exits? (Calculate
for room and premises occupancy numbers &
types, where relevant.)
X Exits/widths/occupancies not recalculated at this time (except for Rutherford Bar)
but, based on previous Fire Risk Assessment and approximate visual
confirmation, appear satisfactory. Verification should be planned for next fire risk
assessment review.
16.3 Are exits easily and immediately openable where
necessary? (Alarm-linked features such as
electronic door release mechanisms to be verified
as compliant, functional and suitably failsafe)
X Satisfactory on sampled basis, not practicable to verify exhaustively.
16.4 Do escape exits open in the direction of escape
where necessary?
X Double fire doors near W4W/W4N should be reversed or made double swing.
16.5 Are there satisfactory means for securing exits? X Break-glass hammer for S4E alternative exit missing, to be replaced.
16.6 Are there reasonable travel distances where there
is a single direction of travel?
X Dead end conditions exist in a number of corridors; travel distances grossly
exceed guidance values, representing a high risk to sleeping occupants without
further mitigating features. Top priority must be given to reducing risk to tolerable
levels - recent and continuing improvements are in hand at time of writing (Oct
08) including specific planning meetings.
16.7 Are there reasonable travel distances where there
is an alternative means of escape?
X
FIRE PROTECTION FIRE RISK ASSESSMENT
16.8 Is there suitable protection of escape routes? X (1) Many fire doors are in poor condition having grossly excessive gaps and
ineffective seals, and some are binding on floor/failing to self-close, etc - to be
checked throughout, adjusted/repaired/corrected and appropriate intumescent
and/or smoke seals fitted. (2) Self-closers found missing from W2S & W4W
corridor fire doors - to replace. (3) New double fire doors from common room
adjacent Rutherford Bar - self closer defective, to repair. (4) Alarm-linked
automatic holdback devices must be fitted to fire doors between servery and
kitchen (1 single, 1 double) and washing-up area (1 single) and the self-closing
action of these doors corrected. Similar devices are very strongly recommended
for the rear kitchen double doors. (5) Designated fire doors must not be propped
or wedged open. Every effort must be made to stop the practice of wedging fire
doors, e.g. of residential kitchenettes.
16.9 Are all escape routes unobstructed? X (1) The alternative exit from the Upper Senior Common Room is habitually
obstructed, and the alternative exit from W3.2 Lecture Room 2 is particularly
prone to obstruction; signage must be corrected/enhanced and its impact
maximised, to control these situations. (2) Vending machines considerably
obstruct the escape route corridor adjacent Rutherford Bar (and furthermore
should not be present as a potential source of ignition) and should be removed to
a suitable location. (3) One leaf of 'old' double door exit from common room
adjacent Rutherford Bar was found bolted - both leaves of all such exit route
doors must be maintained immediately available at all times. (a) All such
bolts/locks should be removed, and (b) in the meantime clear and reliable
management responsibilities and procedures should apply.
16.10 Is the building provided with reasonable
arrangements for means of escape for occupants
with disabilities?
X Powered door openers to several W2 residential corridors were inoperative at
time of inspections, and at least one corridor (W2S) is equipped at the entrance
but not at the alternative exit - openers must be fully provided/repaired if any
persons with disabilities are in residence.
16.10 supplementary: Basic existing arrangements for assisting the evacuation
of all disabled persons from the building in the case of fire should be developed
further and a system of PEEPs introduced. (Greater provision of technical,
physical, organisational and human resources is necessary to provide
comprehensive systems for disabled evacuation, in connection with campus-wide
developments.)
17.0 Fire Spread and Development Limitation
FIRE PROTECTION FIRE RISK ASSESSMENT
17.1 Is it considered that there is compartmentation of
a reasonable standard? (Including e.g. dampers
in ductwork; fire-stopping of service penetrations)
X (1) Repair displaced/poor fire stopping above door frame of quiet study room
adjacent S3-1. (2) Question as to adequate fire resistance of panels above
residential corridor fire doors - to be identified, established and replaced as
necessary. (3) Service penetrations though panels above corridor & other fire
doors (especially Level 1 and e.g. N3W and store adjacent W2-3) - fire stopping
to be applied throughout. (4) Level 1 plant room and two rooms adjacent, Rag
store & Trunk store - numerous service penetrations in walls, ceilings & above
doors to be fire-stopped to half hour resistance; all vents to stairwell must be
sealed to same standard or intumescent seals fitted. (5) Laundry W2.3 - vent to
corridor must be sealed with half hour fire resisting material or intumescent seals
fitted. (6) Georgian wire glass vision panel in S2E corridor door has dropped
leaving a gap - to correct. (7) Similar conditions are highly likely to exist
elsewhere - audit must be conducted and remedial fire stopping etc undertaken
throughout.
17.2 Is it considered that there is reasonable limitation
of linings that may promote fire spread?
X Postering of walls in corridor N3W is nearing excessive extent, in terms of area
potential for fire spread.
18.0 Escape Lighting
18.1 Is a reasonable standard of escape lighting
provided?
X
19.0 Fire Safety Signs and Notices NOTE: Fire Action Notices must continue to be posted in all residential rooms,
especially for the information of short-duration visitors.
FIRE PROTECTION FIRE RISK ASSESSMENT
19.1 Does the building have a reasonable standard of
fire safety signs and notices?
X (See also 16.9 item 1 and 20.1 item 2). (1) Escape route signage is inadequate
in many areas (variously missing, interfered with, inadequate, incorrect [e.g. (3)
below] or noncompliant - needs overall review & correction (to include
emergency illumination and disabled signage), noting recent Fire Service
instructions. (2) Many fire exit doors are not marked 'keep clear', e.g. most
alternative exits from residential corridors - these must be fitted throughout (most
critical cases corrected via Estates Helpdesk but many not yet addressed). (3)
Disabled muster point signs are incorrectly used in place of directional signs at a
number of locations. (4) Entry from roof into Plant Room 4 (alternative escape
route from Upper Senior Common Room): "Break Glass" sign to be fitted. (5)
Cloister seminar rooms & garden: the need to evacuate via building escape
routes is particularly unclear, leaving potential for persons to remain in the garden
area; special attention to signage is required here. (6) Redundant signage (e.g. to
former call point outside N4-9) must be removed throughout.
20.0 Fire Warning Arrangements Note - flip-up call point covers are to be fitted, contrary to BS5839 but with clear
"lift up" indication visible, as a necessary measure to combat malicious
activations.
20.1 Is a reasonable manually operated electrical fire
alarm system provided?
X (1) Call points should be provided at Final Exits from staircases serving
residential corridors etc. (2) In the meantime additional signs are required to
direct persons to call points on landings above.
20.2 Is automatic fire detection provided in building? X Smoke detection should be present in the lobby of the film production suite (level
2 W) - to be verified or corrected.
20.3 Is the fire alarm system audible or perceptible
throughout the building?
X Appears adequate, subject to ongoing verification by Estates that 75dB is
attained at every bedhead.
20.4 Is there a remote transmission of alarm signal? X
21.0 Portable Fire Extinguishing Appliances
21.1 Is the provision of portable fire extinguishers
reasonable?
X Additional 13A water and 2kg CO2 extinguishers to be provided at far end of
each dead end corridor (see 16.6).
21.2 Are hose reels provided? X Fire hose reels should be removed and, in locations with no alternative portable
extinguisher provision in accordance with official guidance, relaced with same.
22.0 Automatic Fixed Systems
FIRE PROTECTION FIRE RISK ASSESSMENT
22.1 Is there a suitable sprinkler or water based
system that is adequate for the risk present?
X
22.2 Is there a suitable gaseous local application or
total flooding provided that is adequate for the
risk?
X
Other Fixed Systems
22.3 Are there suitable smoke control facilities for the
risk present?
X
23.0 Luminous Discharge Tubes
23.1 Has notice been given to the fire and rescue
authority regarding luminous discharge tubes cut-
off switch, its colouring and marking.
X
FIRE PROTECTION FIRE RISK ASSESSMENT
NOTES
Example of
travel distance to
place of relative
safety (applying
2/3 rule within
study bedroom)
is 25m, as
against guidance
maximum of
18m.
MANAGING FIRE SAFETY FIRE RISK ASSESSMENT
INDEX DETAIL YES NO N/A CONTROL MEASURES
24.0 Procedures and Arrangements
24.1 Appropriate fire procedures in place (including
calling the fire service)?
X Provide, resource and implement a written Fire Emergency Plan covering
all appropriate procedures, responsibilities and features of the building.
The Plan should include arrangements to assist disabled persons; for
academic staff etc to take responsibility for the evacuation of students in
their presence; to conduct a full coordinated sweep of the building to
confirm full evacuation or otherwise; and to provide clear instructions for
liaising with the fire brigade on arrival and notifying them of any special
risks or conditions.
25.0 Training and drills See 19.1 item 5 - a means should be devised of providing extra
information & instruction regarding evacuation from the cloister seminar
rooms and garden, probably via special signage.
25.1-2 Are all staff given instruction on induction, and
periodic refresher training at suitable intervals?
> > > Ensure full & appropriate induction information and training is provided to
all employees, with suitable refresher information and training at not less
than three year intervals.
25.1-2
suppl.
Are all students and visitors given suitable
information and instruction?
> > > Ensure adequate fire safety information and briefing is given to all students
and visitors. Fire safety awareness and behaviour should be enhanced by
any available means.
25.3 Do key staff have suitable competence &
training? (Responsible & competent persons, fire
marshals etc, nominated fire extinguisher users,
academic staff, etc)
X (1) Sufficient fire marshals etc are not available and should be appointed
in order to facilitate evacuation (see 24.1) during staffed times, and for
other fire safety requirements such as inspections. (2) Insufficient persons
are nominated and trained in the use of fire extinguishers. Management of
all departments occupying and operating in the building must cooperate
and coordinate in making such provisions.
26.0 Inspection, Testing and Maintenance
26.1 Adequate maintenance and checking of
workplace and fire safety features?
X Ensure that a system of monthly checks of fire extinguishers and other fire
safety features is implemented, and records kept. Checks should take
account of behavioural aspects such as abuse of fire safety provisions.
MANAGING FIRE SAFETY FIRE RISK ASSESSMENT
26.2 Weekly testing and periodic servicing of fire
detection and alarm system?
X
26.3 Monthly, six-monthly and annual testing routines
for emergency lighting?
X
26.4 Annual maintenance of fire extinguishing
appliances?
X
26.6 Weekly testing and periodic inspection of
sprinkler installations?
X
26.7 Other relevant inspections or tests: (including
e.g. ductwork dampers, fire shutters, venting
systems, door holdback devices, electronic door
release systems)
X
27.0 Records
27.1 Are appropriate records kept for fire training? > > > Ensure appropriate fire safety training records are kept.
27.2 Are appropriate records kept for fire alarm tests? X
27.3 Are appropriate records kept for escape lighting
tests?
X
27.4 Are appropriate records kept for the maintenance
and testing of other fire protection systems?
X
28.0 Young Persons
28.1
Have the following matters been taken into
particular account in risk assessment in respect
of young persons:
28.2
the inexperience, lack of awareness of risks and
immaturity of young persons> > >
Consider providing enhanced comprehensive induction training package to
raise awareness levels of young persons (e.g. summer school students).
28.3 the fitting-out and layout of the premises X
MANAGING FIRE SAFETY FIRE RISK ASSESSMENT
28.4the nature, degree and duration of exposure to
physical and chemical agents X
28.5the form, range, and use of work equipment and
the way in which it is handled; X
28.6 the organisation of processes and activities Consider re-evaluating the activities and supervision of young persons.
28.7the extent of the safety training provided or to be
provided to young persons
As 28.2
28.8
risks from agents, processes and work listed in
the Annex to Council Directive 94/33/EC on the
protection of young people at work X
MANAGING FIRE SAFETY FIRE RISK ASSESSMENT
NOTES
(Extra note)
Cannot generalise response - mostly 'yes'
but inevitably variable by department
Cannot generalise response - inevitably
variable by department
Cannot generalise response - inevitably
variable by department
MANAGING FIRE SAFETY FIRE RISK ASSESSMENT
Response field left blank - mostly 'yes'
but inevitably variable by department
Cannot generalise response -
QUESTIONABLE
FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT
This simple risk level estimator is based on a more general health and safety risk level estimator in BS 8800:
Potential consequences of fire ► Slight harm Moderate harm Extreme harm
Fire hazard ▼
Low Trivial risk Tolerable risk Moderate risk
Medium Tolerable risk Moderate risk Substantial risk
High Moderate risk Substantial risk Intolerable risk
Taking into account the fire prevention measures observed at the time of this risk assessment, it is considered that the
hazard from fire (probability of ignition) at this building is:
Low / highly unlikely X - following completion of recommendations of this fire risk assessment
Medium / unlikely X - prior to completion of recommendations of this fire risk assessment
High / likely
Taking into account the nature of the building and the occupants, as well as the fire protection and procedural arrangements
observed at the time of this risk assessment, it is considered that the consequences for life safety in the event of fire would be:
Slight harm X - following completion of recommendations of this fire risk assessment
Moderate harm X - prior to completion of recommendations of this fire risk assessment
Extreme harm X - certain occupants only, at present - see 16.6
In this context, a definition of the above terms is as follows:
Slight harm: Outbreak of fire unlikely to result in serious injury or death of any occupant (other than an occupant
sleeping in a bedroom in which a fire occurs).
Moderate harm: Outbreak of fire could result in injury of one or more occupants, but it is unlikely to involve multiplefatalities.
Extreme harm: Significant potential for serious injury or death of one or more occupants.
FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT
Accordingly, it is considered that the risk to life from fire at this building is:
Trivial
Tolerable X - following completion of ALL recommendations of this fire risk assessment
(INCLUDING consigning all rooms with excessive travel distances to unoccupied uses)
Moderate X - prior to completion of ALL recommendations of this fire risk assessment
Substantial X - certain occupants only, at present - see 16.6
Intolerable
A suitable risk-based control plan should involve effort and urgency that is proportional to risk. The following risk-based
control plan is based on one advocated by BS 8800 for general health and safety risks:
Risk Level Action and Timescale
Trivial No action is required and no additional detailed records need be kept.
Tolerable No major additional controls required. However, there may be a need for consideration
of improvements that involve minor or limited cost, and various corrective actions may
be required.
Moderate It is essential that efforts are made to reduce the risk. Risk reduction measures should
be implemented within a defined time period.
Where moderate risk is associated with consequences that constitute extreme harm, further
assessment may be required to establish more precisely the likelihood of harm as a basis
for determining the priority for improved control measures.
Substantial Considerable resources may have to be allocated to reduce the risk. If the building is
unoccupied, it should not be occupied until the risk has been reduced. If the building is
occupied, urgent action should be taken.
Intolerable Building (or relevant area) should not be occupied until the risk is reduced.
FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT
Any significant change, occurrence, finding or development should be reported immediately to the University’s Safety, Health & Environment Unit so that mitigating action
can be taken and this Fire Risk Assessment reviewed and updated.
FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT
(INCLUDING consigning all rooms with excessive travel distances to unoccupied uses)
ACTION PLAN FIRE RISK ASSESSMENT
ORGANISATION: University of Kent
BUILDING: RUTHERFORD COLLEGE
ASSESSOR: Andrew Briggs, TechIFSM, MIIRSM
DATE: 16th November 2007 - 29th February 2008 & 13th February 2009
ACTION PLAN It is considered that the following recommendations should be implemented
in order to reduce fire risk to the following level: TOLERABLE
REFERENCE ACTION REQUIRED TO ELIMINATE OR CONTROL SIGNIFICANT HAZARDS PRIORITY * RESPONSIBILITY TARGET DATE
7.0 Electrical Sources of Ignition
7.2 suppl. Recommendation to consider Portable Appliance Testing of student-owned
appliances.
3A/B Kent
Hospitality/Estates
10.0 Cooking & Heating
10.2 Ductwork apparently not cleaned since 1994. Clean urgently and implement
regular maintenance programme, to include fire dampers.
1A/B,
URGENT
Kent Hospitality/
Estates
(TBA)
13.0 Housekeeping
13.3 S3-1, S3-3 and the 'rag store' off the E1S stairwell contain very high fire loading.
Combustibles content must be reduced significantly and kept in an orderly manner
so as to minimise flame spread in the event of a fire.
1A/B Kent Union
16.0 Means of Escape
16.4 Double fire doors near W4W/W4N should be reversed or made double swing. 2A Estates
16.5 Break-glass hammer for S4E alternative exit missing, to be replaced. 1A HDWR175142
ACTION PLAN FIRE RISK ASSESSMENT
16.6 Dead end conditions exist in a number of corridors; travel distances grossly exceed
guidance values, representing a high risk to sleeping occupants without further
mitigating features. Top priority must be given to reducing risk to tolerable levels -
recent and continuing improvements are in hand at time of writing (Oct 08)
including specific planning meetings.
1A Kent
Hospitality/Estates
16.8 (1) Many fire doors are in poor condition having grossly excessive gaps and
ineffective seals, and some are binding on floor/failing to self-close, etc - to be
checked throughout, adjusted/repaired/corrected and appropriate intumescent
and/or smoke seals fitted. (2) Self-closers found missing from W2S & W4W
corridor fire doors - to replace. (3) New double fire doors from common room
adjacent Rutherford Bar - self closer defective, to repair. (4) Alarm-linked
automatic holdback devices must be fitted to fire doors between servery and
kitchen (1 single, 1 double) and washing-up area (1 single) and the self-closing
action of these doors corrected. Similar devices are very strongly recommended
for the rear kitchen double doors. (5) Designated fire doors must not be propped or
wedged open. Every effort must be made to stop the practice of wedging fire
doors, e.g. of residential kitchenettes.
2A (1) Estates
(2) HDWR175061
(3) Kent Union
(4) Estates/Kent
Hospitality
(5) Kent Hospitality
& all departments
NB other specific
HDWRs apply to (1)
16.9 (1) The alternative exit from the Upper Senior Common Room is habitually
obstructed, and the alternative exit from W3.2 Lecture Room 2 is particularly prone
to obstruction; signage must be corrected/enhanced and its impact maximised, to
control these situations. (2) Vending machines considerably obstruct the escape
route corridor adjacent Rutherford Bar (and furthermore should not be present as a
potential source of ignition) and should be removed to a suitable location. (3) One
leaf of 'old' double door exit from common room adjacent Rutherford Bar was found
bolted - both leaves of all such exit route doors must be maintained immediately
available at all times. (a) All such bolts/locks should be removed, and (b) in the
meantime clear and reliable management responsibilities and procedures should
apply.
2A (1) Estates (2) Kent
Hospitality (3a)
Estates (3b) Kent
Hospitality & all
departments
16.10 Powered door openers to several W2 residential corridors were inoperative at time
of inspections, and at least one corridor (W2S) is equipped at the entrance but not
at the alternative exit - openers must be fully provided/repaired if any persons with
disabilities are in residence.
1A/2A Estates/Kent
Hospitality
(HDWR175145 also
applies)
17.0 Fire Spread and Development Limitation
ACTION PLAN FIRE RISK ASSESSMENT
17.1 (1) Repair displaced/poor fire stopping above door frame of quiet study room
adjacent S3-1. (2) Question as to adequate fire resistance of panels above
residential corridor fire doors - to be identified, established and replaced as
necessary. (3) Service penetrations though panels above corridor & other fire
doors (especially Level 1 and e.g. N3W and store adjacent W2-3) - fire stopping to
be applied throughout. (4) Level 1 plant room and two rooms adjacent, Rag store &
Trunk store - numerous service penetrations in walls, ceilings & above doors to be
fire-stopped to half hour resistance; all vents to stairwell must be sealed to same
standard or intumescent seals fitted. (5) Laundry W2.3 - vent to corridor must be
sealed with half hour fire resisting material or intumescent seals fitted. (6)
Georgian wire glass vision panel in S2E corridor door has dropped leaving a gap -
to correct. (7) Similar conditions are highly likely to exist elsewhere - audit must be
conducted and remedial fire stopping etc undertaken throughout.
2A Estates
(1) HDWR175059,
others not on
HDWRs
19.0 Fire Safety Signs and Notices
19.1 (See also 16.9 item 1 and 20.1 item 2). (1) Escape route signage is inadequate in
many areas (variously missing, interfered with, inadequate, incorrect [e.g. (3) below]
or noncompliant - needs overall review & correction (to include emergency
illumination and disabled signage), noting recent Fire Service instructions. (2)
Many fire exit doors are not marked 'keep clear', e.g. most alternative exits from
residential corridors - these must be fitted throughout (most critical cases corrected
via Estates Helpdesk but many not yet addressed). (3) Disabled muster point signs
are incorrectly used in place of directional signs at a number of locations. (4) Entry
from roof into Plant Room 4 (alternative escape route from Upper Senior Common
Room): "Break Glass" sign to be fitted. (5) Cloister seminar rooms & garden: the
need to evacuate via building escape routes is particularly unclear, leaving potential
for persons to remain in the garden area; special attention to signage is required
here. (6) Redundant signage (e.g. to former call point outside N4-9) must be
removed throughout.
2A Estates
(some specific
aspects covered by
HDWRs)
20.0 Fire Warning Arrangements
20.1 (1) Call points should be provided at Final Exits from staircases serving residential
corridors etc. (2) In the meantime additional signs are required to direct persons to
call points on landings above.
2A Estates
ACTION PLAN FIRE RISK ASSESSMENT
20.2 Smoke detection should be present in the lobby of the film production suite (level 2
W) - to be verified or corrected.
2A Estates
21.0 Portable Fire Extinguishing Appliances
21.1 Additional 13A water and 2kg CO2 extinguishers to be provided at far end of each
dead end corridor (see 16.6).
2A Estates
21.2 Fire hose reels should be removed and, in locations with no alternative portable
extinguisher provision in accordance with official guidance, relaced with same.
3A Estates
24.0 Procedures and Arrangements
24.1 Provide, resource and implement a written Fire Emergency Plan covering all
appropriate procedures, responsibilities and features of the building. The Plan
should include arrangements to assist disabled persons; for academic staff etc to
take responsibility for the evacuation of students in their presence; to conduct a full
coordinated sweep of the building to confirm full evacuation or otherwise; and to
provide clear instructions for liaising with the fire brigade on arrival and notifying
them of any special risks or conditions.
1A Safety Unit & Kent
Hospitality
25.0 Training and drills
25.1-2 suppl. Ensure adequate fire safety information and briefing is given to all students and
visitors. Fire safety awareness and behaviour should be enhanced by any available
means.
2A Kent Hospitality &
Safety Unit
25.3 (1) Sufficient fire marshals etc are not available and should be appointed in order to
facilitate evacuation (see 24.1) during staffed times, and for other fire safety
requirements such as inspections. (2) Insufficient persons are nominated and
trained in the use of fire extinguishers. Management of all departments occupying
and operating in the building must cooperate and coordinate in making such
provisions.
2A All departments
25 suppl. See 19.1 item 5 - a means should be devised of providing extra information &
instruction regarding evacuation from the cloister seminar rooms and garden,
probably via special signage.
2A Estates/Kent
Hospitality/SHEU
28.0 Young Persons
28.2 Consider providing enhanced comprehensive induction training package to raise
awareness levels of young persons (e.g. summer school students). 2A Kent Hospitality
ACTION PLAN FIRE RISK ASSESSMENT
28.6 Consider re-evaluating the activities and supervision of young persons. 2A Kent Hospitality
HDWR = Helpdesk Work Request
* PRIORITY (N.B. to Fire Service College Fire Safety Engineering Division scale, not PAS 79)
Category A. Fire Risk to Persons:
1A - A serious life safety risk and/or a major or serious contravention of current fire safety legislation.
This matter requires immediate attention and must be given high priority.
2A - An important life safety issue and/or a contravention of current fire safety legislation and/or official guidance, that may lead to enforcement action if not addressed.
This matter requires attention with the minimum of delay.
3A - A significant life safety issue which, in combination with other significant findings, may result in an increased risk to persons.
Advised to implement programme of work or action in accordance with good fire safety practice.
4A - A life safety issue recommended for consideration in accordance with good fire safety practice.
Advised to implement action or programme of work as appropriate.
Category B. Fire Risk to Property, Business Continuity, Environment, Amenity, Heritage etc.
1B - A serious risk of damage by fire (with possible legal implications, depending on the enforcing authority involved).
This matter requires immediate attention and must be given high priority.
2B - An important potential fire damage issue (with possible legal implications, depending on the enforcing authority involved).
This matter requires attention with the minimum of delay.
3B - A significant potential fire damage issue which, in combination with other significant findings,may result in an increased risk to the property.
Advised to implement programme of work or action in accordance with good fire protection/prevention practice.
4B - A property protection issue recommended for consideration as a medium of longer term objective in accordance with good fire prevention/protection practice.
Advised to implement action or programme of work as appropriate.
ACTION PLAN FIRE RISK ASSESSMENT
2A - An important life safety issue and/or a contravention of current fire safety legislation and/or official guidance, that may lead to enforcement action if not addressed.
3B - A significant potential fire damage issue which, in combination with other significant findings,may result in an increased risk to the property.
4B - A property protection issue recommended for consideration as a medium of longer term objective in accordance with good fire prevention/protection practice.