Tape Shield (page 2) Wire Shield (page 6) UniShield R (page 10) for Single Conductor Tape Shield, Wire Shield and UniShield R Cables ISSUE DATE: 8/5/96 ISSUE: SCALE: Not to scale Silicone Rubber Outdoor Skirted Termination Kits 3M QT–III 78–8117–0566–0 18 NUMBER OF PAGES: 7692–S–4 7694–S–4 7693–S–4 7695–S–4 7696–S–4 B Cold Shrink Silicone Rubber Termination (With High-K Stress Relief) Instruction Sheet QT–III IEEE Std. No. 48–1990 Class 1 Termination 25 kV Class 150 kV BIL Kit Contents: 3 Hi–K, Tracking Resistant, Silicone Rubber Terminations 3 Preformed Ground Braids 3 Constant Force Springs 6 Strips Sealing Mastic (black with white release liners, bagged) 1 Scotch CC–2 Cable Preparation Kit 1 Instruction Sheet Kit Selection Chart NOTE: Final Determination Factor is cable insulation diameter. Kit Primary Insulation Jacket Conductor Size Range (AWG & kcmil) Number O.D. Range O.D. Range 5 kV 8.7 kV 15 kV 25/28 kV 7692–S–4 0.64I – 1.08I (16,3 – 27,4 mm) 0.97I – 1.48I (24,6 – 37,6 mm) 4/0 – 400 3/0 – 300 2 – 4/0 (35 – 120 mm 2 ) 2 – 1/0 (35 – 50 mm 2 ) 7693–S–4 0.72I – 1.29I (18,3 – 32,8 mm) 1.04I – 1.60I (26,4 – 40,6 mm) 300 – 500 250 – 500 2/0 – 300 (70 – 150 mm 2 ) 2 – 4/0 (35 – 120 mm 2 ) 7694–S–4 0.83I – 1.53I (21,1 – 38,9 mm) 1.12I – 1.87I (28,4 – 47,5 mm) 500 – 750 350 – 700 4/0 – 500 (120 – 240 mm 2 ) 2/0 – 250 (70 – 150 mm 2 ) 7695–S–4 1.05I – 1.80I (26,7 – 45,7 mm) 1.39I – 2.40I (35,3 – 61,0 mm) 700 – 1500 600 – 1250 500 – 1000 (240 – 500 mm 2 ) 250 – 800 (150 – 400 mm 2 ) 7696–S–4 1.53I – 2.32I (38,9 – 58,9 mm) 1.84I – 2.80I (46,8 – 71,1 mm) 1750 – 2000 1500 – 2000 1250 – 2000 (500 – 1000 mm 2 ) 900 – 1500 (500 – 800 mm 2 ) Table 1

Transcript of Copa 3m Qtiii (2 40)

Page 1: Copa 3m Qtiii (2 40)

ÉÉÉÉ

ÇÇÇÇÇÇÇÇ

Tape Shield (page 2)

Wire Shield (page 6)

UniShield � (page 10)

for Single Conductor Tape Shield,Wire Shield and UniShield � Cables

ISSUE DATE: 8/5/96 ISSUE:

SCALE: Not to scale

Silicone Rubber OutdoorSkirted Termination Kits

3M QT–III

78–8117–0566–018NUMBER OF PAGES:

7692–S–4 7694–S–47693–S–4 7695–S–4

7696–S–4

B

Cold Shrink Silicone Rubber Termination(With High-K Stress Relief)Instruction Sheet

QT–III

IEEE Std. No. 48–1990Class 1 Termination25 kV Class150 kV BIL

Kit Contents:3 Hi–K, Tracking Resistant, Silicone Rubber Terminations3 Preformed Ground Braids3 Constant Force Springs6 Strips Sealing Mastic

(black with white release liners, bagged)1 Scotch CC–2 Cable Preparation Kit1 Instruction Sheet

Kit Selection ChartNOTE: Final Determination Factor is cable insulation diameter.

Kit Primary Insulation Jacket Conductor Size Range (AWG & kcmil)

Numbery

O.D. Range O.D. Range 5 kV 8.7 kV 15 kV 25/28 kV

7692–S–40.64� – 1.08�

(16,3 – 27,4 mm)0.97� – 1.48�

(24,6 – 37,6 mm)4/0 – 400

—3/0 – 300

—2 – 4/0

(35 – 120 mm2)2 – 1/0

(35 – 50 mm2)

7693–S–40.72� – 1.29�

(18,3 – 32,8 mm)1.04� – 1.60�

(26,4 – 40,6 mm)300 – 500

—250 – 500

—2/0 – 300

(70 – 150 mm2)2 – 4/0

(35 – 120 mm2)

7694–S–40.83� – 1.53�

(21,1 – 38,9 mm)1.12� – 1.87�

(28,4 – 47,5 mm)500 – 750

—350 – 700

—4/0 – 500

(120 – 240 mm2)2/0 – 250

(70 – 150 mm2)

7695–S–41.05� – 1.80�

(26,7 – 45,7 mm)1.39� – 2.40�

(35,3 – 61,0 mm)700 – 1500

—600 – 1250

—500 – 1000

(240 – 500 mm2)250 – 800

(150 – 400 mm2)

7696–S–41.53� – 2.32�

(38,9 – 58,9 mm)1.84� – 2.80�

(46,8 – 71,1 mm)1750 – 2000

—1500 – 2000

—1250 – 2000

(500 – 1000 mm2)900 – 1500

(500 – 800 mm2)

Table 1

ÅÅÎÎÎÎÎÎÎÅÅÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

Page 2: Copa 3m Qtiii (2 40)

���������� ��� — 2 —

ÏÏÏÏ

ÅÅÅÅÅÅÅÅÅÅÅÅ

ÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏ

ÏÏÏÏ

ÏÏÏÏÏÏÏÏÏÏ

ÅÅÅÅÅÅÅÅÅÅÅÅ

Semi-Con Insulation Shield

Ridge at End of CableInsulation Shield (Semi-Con)

Ridge at Endof High-K Tube

Correct Installation of Termination on Tape Shielded Cable

CableInsulation

Conductor

Vinyl TapeMarker

Silicone TopSealStress Controlling Compound

High-K StressRelief Tube

Instructions for Tape Shielded Cable

A. Prepare Cable1. Check to be sure cable size fits within kit range as shown in Table 1 (cover page).

2. Prepare cable using dimensions shown in (Figure 1). Be sure to allow for depth of terminal lug. If necessary toprevent tape shield from unrolling, TEMPORARILY hold down edge with a single wrap of vinyl electrical tape.

NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUMlugs or connectors as follows:

Aluminum LugGrowth Allowance

2 – 3501/4� (6 mm)

400 – 6501/2� (13 mm)

750 – 10003/4� (19 mm)

1250 – 2000Field Determined

Figure 1Jacket Removal Length

9� (229 mm)

3� (76 mm)

Semi-ConTape Shield

Depth Of Terminal Lug + Growth Allowance

1 1/2� (38 mm)

Cable Jacket

Page 3: Copa 3m Qtiii (2 40)

— 3 —���������� ���

B. Install Ground Braid

1. Select one of six mastic strips from kit and remove white release liners. Using light tension apply a single wrap of masticaround the cable jacket 1/4� (6 mm) from cut edge (Figure 2). Cut off excess.

ÅÅÅÅÅÅ

Figure 2

Semi-ConTape Shield

1ST Mastic SealCable Jacket

1/4� (6 mm)

2. Position pre-formed ground braid with short tail over tape shield directly adjacent to cable jacket cut edge. Position longtail of ground braid, extending over cable jacket with solder block over mastic strip (Figure 3). Secure ground braid tocable jacket 4 1/2� (114 mm) from cable semi-con edge using vinyl tape (Figure 3).

NOTE: Position vinyl tape with care, it also serves as a marker for positioning the termination.

ÅÅÅÅÅÅ

ÏÏÏÏÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏ

ÏÏÏÏ

Figure 3

Tape ShieldGround Braid

Cable Jacket Edge

Vinyl Tape Marker

Semi-Con Edge

Solder Block1ST Mastic Strip

4 1/2� (114 mm)

Page 4: Copa 3m Qtiii (2 40)

— 4 —���������� ���

B. Install Ground Braid (continued)

3. Wrap ground braid around cable tape shield one complete wrap, trim excess to prevent overlap and secure in place withconstant force spring. Wrap spring in same direction as ground braid (Figure 4). Cinch (tighten) the spring afterwrapping the final winding.

4. Select second mastic strip from kit and remove white release liners. Apply a second mastic band over solder block onground braid and previously applied mastic (Figure 4). Cut off excess.

Figure 4

ÅÅÅÅÅÅ

ÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏÏÏÏÏ

ÅÅÅÅÅÅ

Tape ShieldConstant Force Spring

Ground Braid1ST Mastic Strip

Solder Block2ND Mastic Strip

Ground Braid Leg

ÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏ

Trim

CableTape

Shield

5. Wrap two half-lapped layers of vinyl tape around mastic seal, constant force spring and exposed tape shield (Figure 5).

NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1� (25 mm) must be exposed.

SPECIAL NOTE FOR CLOTH OR PAPER SEMI-CON INSULATION SHIELDIn cables with cloth or paper semi-conductive shields it is recommended the shield be over wrappedwith one half-lapped layer of highly stretched semi-conductive rubber tape such as Scotch No. 13.

ÅÅÅÅÅÅ

ÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏ

ÅÅÅÅÅÅ

Figure 5

Semi-Con

Constant Force SpringTwo Half-Lapped Layers Vinyl Tape

Tape Shield

Mastic SealVinyl Tape Marker

Page 5: Copa 3m Qtiii (2 40)

— 5 —����������� ���

C. Install Lug or Connector

1. Check to insure QT–III termination assembly fits over the selected lug. If lug (Figure 6) will not fit through thetermination core, clean the insulation (per Step D) and slide termination on cable before installing lug. Do not removecore at this time.

ÅÅÅÅÅÅ

ÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏ

ÏÏÏÏ

ÅÅÅÅÅÅ

Figure 6

Clearance

Connector/Lug

NOTE: Refer to pages 15 – 17 for 3M connector/lug crimping information.

2. Position connector/lug and crimp according to manufacturers directions. Remove excess oxide inhibitor and sharp crimpflashings following crimping.

D. Clean Cable Insulation and Lug Barrel Using Standard Practice

1. Wipe the cable insulation with one of the solvent saturated pads from the CC–2 Cable Preparation Kit. Do not allowsolvent to touch semi-con insulation shield!

2. If abrasive must be used:

a. Use on insulation only. Do not use abrasive on semi-con insulation shield!

b. Use only aluminum oxide abrasive; grit 120 or finer, included in CC–2 Cable Preparation Kit.

c. Be careful not to reduce the cable insulation diameter below that allowed by the kit.

E. Install Termination

1. Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with theloose end (Figure 7). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape markerpreviously applied (Figure 7).

NOTE: Once the termination insulator has made contact over the mastic seal area, there is no need to continuesupporting the assembly. Do not push or pull on the termination assembly while unwinding the core.

Figure 7

Vinyl Tape Marker

Counter-Clockwise

The material being removed at this step is polypropyleneNOTE:

and can be recycled with other waste.

ÅÅÅ

ÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏ

ÅÅÅ

2. When using a short barrel lug or connector on smaller size cable it may be necessary to trim any excess terminationinsulator from the lug or connector.

3. Connect ground braid to system ground according to standard practice.

Page 6: Copa 3m Qtiii (2 40)

���������� ��� — 6 —

ÎÎÎÎ

ÅÅÅÅÅÅÅÅÅÅÅÅ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎ

ÅÅÅÅÅÅÅÅÅÅÅÅ

Semi-Con Insulation Shield

Ridge at End of CableInsulation Shield (Semi-Con)

Ridge at Endof High-K Tube

Correct Installation of Termination on Wire Shielded Cable

CableInsulation

Conductor

Vinyl TapeMarker

Silicone TopSealStress Controlling Compound

High-K StressRelief Tube

Instructions for Wire Shielded Cable

A. Prepare Cable1. Check to be sure cable size fits within kit range as shown in Table 1 (cover page).

2. Prepare cable using dimensions shown in (Figure 8 and Figure 9). Be sure to allow for depth of terminal lug.

NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUMlugs or connectors as follows:

Aluminum LugGrowth Allowance

2 – 3501/4� (6 mm)

400 – 6501/2� (13 mm)

750 – 10003/4� (19 mm)

1250 – 2000Field Determined

9� (229 mm)

Depth Of Terminal Lug + Growth Allowance

3� (76 mm)

Figure 8

Jacket Removal Length

Semi-ConShield Wires

Cable Jacket

Page 7: Copa 3m Qtiii (2 40)

— 7 —���������� ���

A. Prepare Cable (continued)

3. Bend leading 1 1/2� (38 mm) of exposed shield wires back upon themselves to jacket edge (Figure 9).

3� (76 mm)Figure 9

1 1/2� (38 mm)

Semi-ConShield Wires

Cable Jacket

B. Install Ground Braid1. Select one of six mastic strips from kit and remove white release liners. Using light tension apply a single wrap of mastic

around the cable jacket 1/4� (6 mm) from cut edge (Figure 10). Cut off excess.

ÅÅÅÅÅÅ

Figure 10

Semi-Con1ST Mastic Seal

Cable Jacket

1/4� (6 mm)

2. Position pre-formed ground braid with short tail over wire shield directly adjacent to cable jacket cut edge. Position longtail of ground braid, extending over cable jacket with solder block over mastic strip (Figure 11). Secure ground braid tocable jacket 4 1/2� (114 mm) from cable semi-con edge using vinyl tape (Figure 11).

NOTE: Position vinyl tape with care, it also serves as a marker for positioning the termination.

ÅÅÅÅÅÅ

ÏÏÏÏÏÏÏÏÏÏÏÏÏÏ

ÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏ

ÏÏÏÏ

Figure 11

Shield WireGround Braid

Cable Jacket Edge

Vinyl Tape Marker

Semi-Con Edge

Solder Block1ST Mastic Strip

4 1/2� (114 mm)

Page 8: Copa 3m Qtiii (2 40)

���������� ��� — 8 —

B. Install Ground Braid (continued)

3. Wrap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place withconstant force spring. Wrap spring in same direction as ground braid (Figure 12). Cinch (tighten) the spring afterwrapping the final winding.

4. Select second mastic strip from kit and remove white release liners. Apply a second mastic band over solder block onground braid and previously applied mastic (Figure 12). Cut off excess.

ÅÅÅÅÅÅ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎÎ

ÅÅÅÅÅÅ

Figure 12

Shield WiresConstant Force Spring

Ground Braid1ST Mastic StripSolder Block2ND Mastic Strip

Ground Braid Leg

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

Trim

CableWire

Shield

5. Wrap two half-lapped layers of vinyl tape around mastic seal, constant force spring and exposed shield wires(Figure 13).

NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1� (25 mm) must be exposed.

ÅÅÅÅÅÅ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎ

ÅÅÅÅÅÅ

ÅÅÅÅÅÅ

Figure 13

Semi-Con

Constant Force SpringTwo Half-Lapped Layers Vinyl Tape

Shield Wires

Mastic SealVinyl Tape Marker

1 1/2� (38 mm)

C. Install Lug or Connector

1. Check to insure QT–III termination assembly fits over the selected lug. If lug (Figure 14) will not fit through thetermination core, clean the insulation (per Step D) and slide termination on cable before installing lug. Do not removecore at this time.

ÅÅÅÅÅÅ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎ

ÅÅÅÅÅÅ

ÅÅÅÅÅÅ

Figure 14 Clearance

Connector/Lug

NOTE: Refer to pages 15 – 17 for 3M connector/lug crimping information.

2. Position connector/lug and crimp according to manufacturers directions. Remove excess oxide inhibitor and sharp crimpflashings following crimping.

Page 9: Copa 3m Qtiii (2 40)

— 9 —���������� ���

D. Clean Cable Insulation and Lug Barrel Using Standard Practice

1. Wipe the cable insulation with one of the solvent saturated pads from the CC–2 Cable Preparation Kit. Do not allowsolvent to touch semi-con insulation shield!

2. If abrasive must be used:

a. Use on insulation only. Do not use abrasive on semi-con insulation shield!

b. Use only aluminum oxide abrasive; grit 120 or finer, included in CC–2 Cable Preparation Kit.

c. Be careful not to reduce the cable insulation diameter below that allowed by the kit.

E. Install Termination

1. Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with theloose end (Figure 15). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape markerpreviously applied (Figure 15).

NOTE: Once the termination insulator has made contact over the mastic seal area, there is no need to continuesupporting the assembly. Do not push or pull on the termination assembly while unwinding the core.

Figure 15

Vinyl Tape Marker

Counter-Clockwise

The material being removed at this step is polypropyleneNOTE:

and can be recycled with other waste.

ÅÅÅ

ÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏ

ÅÅÅ

2. When using a short barrel lug or connector on smaller size cable it may be necessary to trim any excess terminationinsulator from the lug or connector.

3. Connect ground braid to system ground according to standard practice.

Page 10: Copa 3m Qtiii (2 40)

���������� ��� — 10 —

ÎÎÎÎÎÎ

ÅÅÅÅÅÅ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÅÅÅÅÅÅ

Semi-Con

Ridge at End of CableInsulation Shield (Semi-Con)

Ridge at Endof High-K Tube

Correct Installation of Termination on UniShield � Shielded Cable

Cable Insulation

Conductor

Vinyl TapeMarker

Silicone TopSealStress Controlling Compound

High-K StressRelief Tube

Instructions for UniShield� Shielded Cable

A. Prepare Cable1. Check to be sure cable size fits within kit range as shown in Table 1 (cover page).

2. Prepare cable using dimensions shown in (Figure 16). Be sure to allow for depth of terminal lug.NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUM

lugs or connectors as follows:

Aluminum LugGrowth Allowance

2 – 3501/4� (6 mm)

400 – 6501/2� (13 mm)

750 – 10003/4� (19 mm)

1250 – 2000Field Determined

3. Pull shield wires through semi-conductive jacket to leading edge of constant force spring (Figure 16).

Figure 16

7 1/2� (191 mm)

Semi-Conductive JacketConstant Force Spring

Shield Wires

Depth Of Terminal Lug + Growth Allowance

Page 11: Copa 3m Qtiii (2 40)

— 11 —���������� ���

A. Prepare Cable (continued)

4. Remove constant force spring. Bend shield wires back upon cable jacket 1 1/2� (38 mm). Cut excess shield wire anddiscard (Figure 17).

9� (229 mm)

Figure 17

1 1/2� (38 mm)

Semi-Conductive JacketFold Back Shield Wires

Depth Of Terminal Lug + Growth Allowance

5. Remove semi-conductive jacket to dimension shown in Figure 18.

NOTE: To ease jacket removal, install constant force spring as shown in Figure 18 and ring cut 80% throughjacket. Remove jacket sections by pulling against constant force spring. DO NOT BELL SEMI-CONJACKET. Remove constant force spring.

Some UniShield� cables feature dual-layer semi-conductive jackets. Both layers must be removed during cablepreparation.

Figure 18Depth Of Terminal Lug + Growth Allowance

6� (152 mm)

1 1/2� (38 mm)

Semi-Conductive JacketCut LineConstant Force Spring

Fold Back Shield Wires

1 1/2� (38 mm)

B. Install Ground Braid1. Select one of six mastic strips from kit and remove white release liners. Using light tension apply a single wrap of mastic

around the cable semi-conductive jacket 1/4� (6 mm) from shield wires (Figure 10). Cut off excess.

ÅÅÅÅÅÅ

Figure 19

Semi-ConShield Wires

1ST Mastic Seal

1/4� (6 mm)

Page 12: Copa 3m Qtiii (2 40)

���������� ��� — 12 —

B. Install Ground Braid (continued)

1. Position pre-formed ground braid with short tail directly over cut edge of folded back shield wires. Position long tail ofground braid, extending over cable semi-conductive jacket with solder block over mastic strip (Figure 20). Secureground braid to cable semi-conductive jacket 4 1/2� (114 mm) from cable semi-con edge using vinyl tape (Figure 20).

NOTE: Position vinyl tape with care, it also serves as a marker for positioning the termination.

ÅÅÅÅÅÅÅÅÅ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎ

Figure 20

Shield WireGround Braid

Solder Block

Semi-Con Edge

1ST Mastic StripVinyl Tape Marker

4 1/2� (114 mm)

2. Wrap ground braid around cable shield wires one complete wrap, trim excess to prevent overlap and secure in place withconstant force spring. Wrap spring in same direction as ground braid (Figure 21). Cinch (tighten) the spring afterwrapping the final winding.

3. Select second mastic strip from kit and remove white release liners. Apply a second mastic band over solder block onground braid and previously applied mastic (Figure 21). Cut off excess.

ÅÅÅÅÅÅÅÅÅ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎ

ÅÅÅÅÅÅ

Figure 21

Shield WiresConstant Force Spring

Ground Braid1ST Mastic StripSolder Block2ND Mastic Strip

Ground Braid Leg

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

Trim

CableWire

Shield

Page 13: Copa 3m Qtiii (2 40)

— 13 —���������� ���

B. Install Ground Braid (continued)

4. Wrap two half-lapped layers of vinyl tape around mastic seal, constant force spring and exposed shield wires(Figure 22).

NOTE: Take care not to cover exposed semi-con insulation shield. A minimum of 1� (25 mm) must be exposed.

ÅÅÅÅÅÅ

ÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏ

ÏÏÏÏ

ÏÏÏÏÏÏÏÏÏÏ

ÅÅÅÅÅÅ

Figure 22

Semi-Con

Constant Force SpringTwo Half-Lapped Layers Vinyl Tape

Shield Wires

Mastic SealVinyl Tape Marker

1 1/2� (38 mm)

C. Install Lug or Connector

1. Check to insure QT–III termination assembly fits over the selected lug. If lug (Figure 23) will not fit through thetermination core, clean the insulation (per Step D) and slide termination on cable before installing lug. Do not removecore at this time.

ÅÅÅÅÅÅ

ÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏÏ

ÏÏÏÏ

ÏÏÏÏÏÏÏÏÏÏ

ÅÅÅÅÅÅ

Figure 23

Clearance

Connector/Lug

NOTE: Refer to pages 15 – 17 for 3M connector/lug crimping information.

2. Position connector/lug and crimp according to manufacturers directions. Remove excess oxide inhibitor and sharp crimpflashings following crimping.

D. Clean Cable Insulation and Lug Barrel Using Standard Practice

1. Wipe the cable insulation with one of the solvent saturated pads from the CC–2 Cable Preparation Kit. Do not allowsolvent to touch semi-con insulation shield!

2. If abrasive must be used:

a. Use on insulation only. Do not use abrasive on semi-con insulation shield!

b. Use only aluminum oxide abrasive; grit 120 or finer, included in CC–2 Cable Preparation Kit.

c. Be careful not to reduce the cable insulation diameter below that allowed by the kit.

Page 14: Copa 3m Qtiii (2 40)

���������� ��� — 14 —

E. Install Termination

1. Slide the termination body onto the cable and remove core. Pull while unwinding, counter-clockwise, starting with theloose end (Figure 24). Make sure the termination body (not the core) is butted up to the edge of the vinyl tape markerpreviously applied (Figure 24).

NOTE: Once the termination insulator has made contact over the mastic seal area, there is no need to continuesupporting the assembly. Do not push or pull on the termination assembly while unwinding the core.

ÅÅ

ÎÎÎÎÎÎÎÎÎÎÎÎÎÎ

ÎÎÎÎÎÎÎÎÎÎÅÅ

Figure 24

Vinyl Tape Marker

Counter-Clockwise

The material being removed at this step is polypropyleneNOTE:

and can be recycled with other waste.

2. When using a short barrel lug or connector on smaller size cable it may be necessary to trim any excess terminationinsulator from the lug or connector.

3. Connect ground braid to system ground according to standard practice.

Page 15: Copa 3m Qtiii (2 40)

— 15 —���������� ���

Tooling Index

Lug and Crimping Information for Scotchlok Copper Lugs

30014 thru 30045One hole

31036 thru 31068One hole — long barrel

31145 thru 31178Two hole

CableCRIMPING TOOL-DIE SETS (NUMBER OF CRIMPS)

CableSize

AWG/kcmil

StudSize(in.)

Scotchlok Copper Lug

NumberBurndy Corporation Thomas & Betts Corporation Square D Co. An-

derson Div.kcmil

MD6 MY29 Y34A Y35, Y39, Y45*, Y46* TBM 5 TBM 8 TBM 15 VC6–3, VC6–FT**

6101/45/16

300143001530016

— 6AWG(1) — U5CRT(1) Blue(1) Blue(1) — Universal(1)

4101/43/8

300183001930021

W161(1) 4AWG(1) A4CR(1) U4CRT(1) Grey(1) Grey(1) — Universal(1)

21/45/163/8

300223002330024

W162(2) 2AWG(1) A2CR(1) U2CRT(2) Brown(1) Brown(1) 33(1) Universal(2)

1 5/163/8

3002730028 — 1AWG(1) A1CR(1) U1CRT(2) Green(1) Green(1) 37(1) Universal(2)

1/0 5/163/8

3003130032 W163(2) 1/0(1) A25R(1) U25RT(1) Pink(2) Pink(2) 42H(2) Universal(1)

2/0 3/83/8

3003631036

W241(2)W241(3)

2/0(1)2/0(2)

A26R(1)A26R(2)

U26RT(2)U26RT(3)

Black(2)Black(3)

Black(2)Black(3)

45(1)45(2)

Universal(1)Universal(2)

3/0 1/21/2

3004131041

W243(2)W243(3)

3/0(1)3/0(2)

A27R(1)A27R(2)

U27RT(2)U27RT(3)

Orange(2)Orange(3)

Orange(2)Orange(3)

50(1)50(2)

Universal(2)Universal(3)

4/01/21/21/2

300453104531145

BG(3)BG(4)BG(4)

4/0(1)4/0(2)4/0(2)

A28R(2)U28RT(2)U28RT(3)U28RT(3)

Purple(2)Purple(3)Purple(3)

Purple(2)Purple(3)Purple(3)

54H(2)54H(3)54H(3)

Universal(2)Universal(3)Universal(3)

250 1/21/2

3104931149 W166(4) 250(2) A29R(2) U29RT(3) Yellow(2) Yellow(2) 62(2) Universal(2)

300 1/21/2

3105331153 — — A30R(2) U30RT(3) — White(3) 66(3) Universal(3)

350 1/21/2

3105631156 — — A31R(2) U31RT(3) — Red(4) 71H(4) —

400 1/21/2

3106031160 — — A32R(2) U32RT(3) — Blue(4) 76H(4) —

5001/25/81/2

310663106731166

— — A34R(2) U34RT(3) — Brown(4) 87H(4) —

600 1/21/2

3106831168 — — — U36RT(3) — Green(4) 94H(4) —

750 1/2 31172 — — — Y39, Y45, Y46U39RT(5) — — 106H(4) —

1000 1/2 31178 — — — Y45: S44RT(6)Y46: P44RT(6) — — 125H(4) —

* Y45 and Y46 accept all Y35 dies (“U” series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter.** Anderson VC6–3, VC6–FT, VC8C and Burndy Y1000 require no die se ��

Page 16: Copa 3m Qtiii (2 40)

���������� ��� — 16 —

Tooling Index

Lug and Crimping Information for Scotchlok Copper/Aluminum Lugs

40016 thru 40079One hole

40132 thru 40178Two hole

CRIMPING TOOL-DIE SETS (NUMBER OF CRIMPS)

CableSize

AWG/kcmil

StudSize(in.)

Scotch-lok Lug

Number

Burndy Corporation Thomas & Betts Corporation Square D Co. Ander-son Div.

ITTBlack-

burn Co.

KearnyNat’lDiv.

kcmil Number

MD6 MY29 Y34A Y35, Y39,Y45*, Y46* Y1000* TBM 5 TBM 8 TBM 12 TBM 15 VC6–3**

VC6–FT** VC8C** OD58 TYPE O

6 5/16 40016 W161(1) 6AWG(1) A6CAB(1) U6CABT(1) (1) Grey(1) Grey(1) — 29(1) (1) — BY19(3) J(3)

4 5/16 40020 W162(3) 4AWG(1) A4CAB(1) U4CABT(1) (1) Green(2) Green(2) — 37(1) (1) — BY53(3) P(3)

2 3/81/2

4002440025

W163(3)W163(3)

2AWG(1)2AWG(1)

A2CAB(1)A2CAB(1)

U2CABT(1)U2CABT(1)

(1)(1)

Pink(2)Pink(2)

Pink(2)Pink(2) — 42H(2)

42H(2)(1)(1) — BY23(3)

BY23(3)1/2(3)1/2(3)

1 3/81/2

4002840029

W163(3)W163(3)

1AWG(1)1AWG(1)

A1CAR(1)A1CAR(1)

U1CART(1)U1CART(1)

(1)(1)

Gold(2)Gold(2)

Gold(2)Gold(2) — 45(1)

45(1)(1)(1) — BY23(3)

BY23(3)1/2(3)1/2(3)

1/03/81/23/8

400324003340132

W241(3)W241(3)W241(3)

1/0(1)1/0(1)1/0(1)

A25AR(1)A25AR(1)A25AR(1)

U25ART(1)U25ART(1)U25ART(1)

(1)(1)(1)

Tan(2)Tan(2)Tan(2)

Tan(2)Tan(2)Tan(2)

—50(1)50(1)50(1)

(1)(1)(1)

—BY25(3)BY25(3)BY25(3)

5/8–1(3)5/8–1(3)5/8–1(3)

2/0 1/21/2

4003740137

BG(4)BG(4)

2/0(1)2/0(1)

A26AR(2)A26AR(2)

U26ART(2)U26ART(2)

(1)(1)

Olive(2)Olive(2)

Olive(2)Olive(2) — 54H(2)

54H(2)(2)(2) — BY31C(3)

BY31C(3)5/8–1(3)5/8–1(3)

3/0 1/21/2

4004140141

W166(4)W166(4)

3/0(1)3/0(1)

A27AR(2)A27AR(2)

U27ART(2)U27ART(2)

(1)(1)

Ruby(2)Ruby(2)

Ruby(2)Ruby(2) — 60(2)

60(2)(2)(2) — — 737(3)

737(3)

4/01/25/81/2

400454004640145

W660(4)W660(4)W660(4)

4/0 (2)4/0 (2)4/0 (2)

A28AR(2)A28AR(2)A28AR(2)

U28ART(2)U28ART(2)U28ART(2)

(1)(1)(1)

—White(4)White(4)White(4)

—66(4)66(4)66(4)

(2)(2)(2)

—BY35C(4)BY35C(4)BY35C(4)

840(4)840(4)840(4)

2501/25/81/2

400494005040149

W249(3)W249(3)W249(3)

—A29AR(2)A29AR(2)A29AR(2)

U29ART(2)U29ART(2)U29ART(2)

(1)(1)(1)

— —71H(4)71H(4)71H(4)

71H(2)71H(2)71H(2)

(3)(3)(3)

— — —

300 1/21/2

4005340153 — — A30AR(2)

A30AR(2)U30ART(2)U30ART(2)

(1)(1) — — 76H(4)

76H(4)76H(2)76H(2)

(3)(3) — — —

3501/25/81/2

400564005740156

— — —U31ART(2)U31ART(2)U31ART(2)

(1)(1)(1)

— —87H(4)87H(4)87H(4)

87H(3)87H(3)87H(3)

(3)(3)(3)

— — —

400 1/2 40160 — — — U32ART(4) (1) — — 94H(4) 94H(4) — (2) — —

500 5/81/2

4006740166 — — — U34ART(4)

U34ART(4)(1)(1) — — 106H(4)

106H(4)106H(3)106H(3) — (2)

(2) — —

600 1/2 40170 — — — U36ART(4) (1) — — — 115H(3) — (3) — —

750 5/81/2

4007340172 — — — U39ART(4)

U39ART(4)(1)(1) — — — 125H(5)

125H(5) — (3)(3) — —

1000 5/81/2

4007940178 — — — S44ART(4)

S44ART(4)(1)(1) — — — 140H(4)

140H(4) — (3)(3) — —

* Y45 and Y46 accept all Y35 dies (“U” series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter.** Anderson VC6–3, VC6–FT, VC8C and Burndy Y1000 require no die se t.

Page 17: Copa 3m Qtiii (2 40)

— 17 —���������� ���

Tooling Index

Crimping Information for3M Stem ConnectorsCopper/Aluminum

CRIMPING TABLE FOR 3M STEM TYPE CONNECTOR

Cond ctor Size 3M Connector Num-Recommended Crimping Tools

Cond uctor Size berManufacturer Mech. Tool Die (No. Crimps) Hydraulic Die (No. Crimps)

Burndy MD6 BG(4), W243(4) Y35, Y39, Y45** U25ART(2), U243(2)

2 Solid1 2

SC0020SC0001

Kearny 0–51, 0–52 5/8–1 (4) 12, 20, 40, Ton 5/8–1(4)1, 21/0

SC0001SC0010 T & B TBM 8 Olive(2) TBM 15 50(2)*

Anderson — — VC6 Universal(2)

Burndy MD6 W669(0) 840(5)* Y35, Y39, Y45** U28ART(2)

2/03/0

SC0020SC0030

Kearny 0–51, 0–52 840(5)* WH–1, WH–2 840(2)3/04/0

SC0030SC0040 T & B TBM 8 White(4) TBM 15 66(3)

Anderson - — VC6 Universal(2)

* Y45 and Y46 accept all Y35 dies (“U” series). For Y45 use PT6515 adapter. For Y46 use PUADP adapter.** Anderson VC6–3, VC6–FT, VC8C and Burndy Y1000 require no die se t.

Page 18: Copa 3m Qtiii (2 40)

%��� %�30) !-5.2/� &2) %!(37(-03/� &5* 75&)*1&5/6 3+ ��#2.!-.*0) .6 & 5*,.67*5*) 75&)*1&5/ 3+ ���� �&'0*6�

6801 River Place Blvd.Austin, TX 78726-9000

Electrical Products Division

Important Notice to Purchaser:

�00 67&7*1*276� 7*(-2.(&0 .2+351&7.32 &2) 5*(311*2)&7.326 5*0&7*) 73 7-* !*00*5�6 453)8(76 &5* '&6*) 32 .2+351&7.32 '*0.*9*) 73 '* 5*0.&'0*� '87

7-* &((85&(< 35 (3140*7*2*66 7-*5*3+ .6 237 ,8&5&27**)� �*+35* 87.0.=.2, 7-* 453)8(7� 7-* 86*5 6-380) )*7*51.2* 7-* 68.7&'.0.7< 3+ 7-* 453)8(7 +35

.76 .27*2)*) 86*� "-* 86*5 &6681*6 &00 5.6/6 &2) 0.&'.0.7< :-&763*9*5 .2 (322*(7.32 :.7- 68(- 86*�

�2< 67&7*1*276 35 5*(311*2)&7.326 3+ 7-* !*00*5 :-.(- &5* 237 (327&.2*) .2 7-* !*00*5�6 (855*27 48'0.(&7.326 6-&00 -&9* 23 +35(* 35 *++*(7 820*66

(327&.2*) .2 &2 &,5**1*27 6.,2*)'< &2 &87-35.=*) 3++.(*5 3+ 7-* !*00*5� "-* 67&7*1*276 (327&.2*) -*5*.2 &5*1&)* .2 0.*8 3+ &00 :&55&27.*6 *;45*66*)

35 .140.*)� .2(08).2, '87 237 0.1.7*) 73 7-* .140.*) :&55&27.*6 3+ 1*5(-&27&'.0.7< &2) +.72*66 +35 & 4&57.(80&5 485436* :-.(- :&55&27.*6 &5* -*5*'<

*;45*660< ).6(0&.1*)�

!���� !���� ��" �� ������ "� "�� #!� � ��$ �"�� �� !�� #��� ��$ ����� "��� $� ����#���� �#" ��" ����"�� "�

����������� !" ��" �������"$� �� ��$ ���# $� �� ��$�� ��"� ���!��#��"��� ������! !#!"������ ���# ���$

��!�� �� "�� #!� �� ��$ �� "�� !���� �! � ��#�"!�

�.7-3 .2 #!�

��� �

��� ������� ���